BLD2023-1360_Other_10.31.2023_9.04.39_AM_3870597PV Single Line
- - - - - - - - - - - - - - - -
String 1 — +�
z
13 modules PI
o
V
String 2 U
10 modules String 3
8 modules
0 Equipment Schedule
A
Storage Single Line I 0
------
I I I
I I
I I A
A 60A/2p I I
• I I
I I
30A/2p I I
2
L--
30A/2p
Battery
Disconnect,
Located within
10' of net meter
PV breaker in Gateway
to serve as exterior
solar rapid shutdown
initiation device
200A TESLA Gateway2 with
200A Internal Panelboard
Solar OCPD:60A
Battery OCPD:60A
Co -Located with Net Meter
Battery combiner panel I I I
Bus Rating: 125A I o
' I I
I 4/0 XHHW-2
(
I L1 & L2)
----------------------------—-=--———————————————------------------------- 2/ 0 XHHW-2
Ref.
Category
Equipment
QTY
1
Modules
Q.Peak DUO BLK ML-G10+ 405
31
2
Optimizers
S440 SolarEdge Optimizer
31
3
Jbox
Soladeck
5
41
Inverters
I Solar Edge SE10000H
1
Monitoring
I SolarEdge PV Inverter Monitoring
1
0 Conductor Schedule
I nverter Specs
Watts
LW-1
Output
AC
Voltage
# of
Inverters
OCPD
u
Solar Edge SE11400H
11400
47.5
240
1
60
****N/A****
0
0
0
0
0
****N/A****
0
0
0
0
0
Module Specs
Watts w
LrKLp
Vmp
Voc
Isc
Q.Peak DUO BLK VIL-G10+4
405
10.83
37.39
45.34
11.17
Temp. Adjusted
0
0
32.8
1 49.3
0
Summary
Distance
(ft)
Current
@125%
Operating
Voltage
Voltage
Drop
V. Drop
(total)
A
(2)#10 CU, (1)#6 EGC, PV Wire 600V, AIR
50
18.75A
400V
0.41%
0.99%
B
(6)#10 CU, (1)#10 EGC, THWN-2, 0.75"EMT(min)
50
18.75A
400V
0.41%
C
(2)#6 CU, (1)#8 N, (1)#10 EGC, THWN-2, 0.75"EMT(min)
10
52.5A
240V
0.17%
(N)
#6 THWN-2 200A/2p
(EGC)
Protected Loads Panel
(Existing)
Main Service Panel
(lph 240V Service)
Main Breaker: 200A
Bus Rating:200A
0 Equipment Schedule
Ref.
Category
Equipment
QTY
1
Gateway
Tesla Backup Gateway2: Service Rated
1
Breakers
200A Main Breaker (Eaton CSR2200N)
1
Misc.
Tesla 200A Internal Panelboard Kit
1
Breakers
2p60A, 2p60A
2
Battery
Tesla Powerwall 2, 13.5 kWh
2
Misc.
Powerwall Stack Kit
1
3
Loadcenters
MLO, 125A, 240V, 1ph, Nema 1, Flush, 8 space (min.)
1
Breakers
2p60A, 2p30A, 2p30A
Misc.
Breaker Hold down kit
1
4
Disconnect
60A 600V 2 Pole I Heavy Duty, No Fuse, Lockable
1
Misc.
Neurio Meter Kit
1
0 Conductor Schedule
■=A&RScope `,'I'
I
= Existing or A&RSOLAR
Others Scope
3211 Martin Luther King Jr Way S.
Seattle, WA 98144 (206)707-9937
OI Net Meter
4/0 XHHW-2
(L1 & L2)
2/0 XHHW-2
(N)
200A/2p
Unprotected Loads Panel
(Existing)
Main Service Panel
(lph 240V Service)
Main Breaker: 200A
Bus Rating:200A
Inverter Specs
Watts
Output
AC
Voltage
# of
Inverters
OCPD
LW-1
Tesla Powerwall 2
5000
1 24
240
2
30
Summary
Distance
(ft)
Current
@125%
Operating
Voltage
Voltage
Drop
A
(4)#10 CU, (2)#10 N, (1)#10 EGC, THWN-2, & com wire, 1"EMT(min)
10
30A
240V
0.25%
B
(2)#6 CU, (1)#6 N, (1)#10 EGC, THWN-2, & com wire, 1"EMT(min)
10
60A
240V
0.20%
THIS DRAWING CONSTITUTES THE
:ONFFIDENTIAL INFORMATION OF A&R SOLAR
AND ITS RECEPTOR POSSESSION DOES NOT
:ONFER ANY RIGHT IN OR LICENSE TO USE IT
OR THE INFORMATTION DISCLOSED HERE IN
NOR ANY RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART HERE IN WITHOUT
THE WRITTEN CONSENT OF A&R SOLAR.
L
O
07
p�
O
C:
O
N
a-+
O
CO
00)Lnm
■
Q
Q
I
O
00
N
Q
Q
4W
U
O
o
(f)
a-+
O
N
Ln
�10
U
O
��
U
w
a�
Ln
Ln
Ln
N
REVISIONS
Rev. #: Date:
1 1 Oct 23, 2023
General Notes:
Designed by: Thomas N
Utility: Snohomish PUD PM: Will MacArthur
1. EGC Where exposed to physical damage will be #6AWG (206) 307-1741
Bare CU Current Date:Oct 23, 2023
2. If installing conduit on the roof, maintain greater than 7/8"
above the surface
3. NEC 690.12: Rapid Shutdown initiated by AC Disconnect I E1 Single Line
PV Electrical Calculations
Inverter Specs
Watts
(W)
Output
AC
Voltage
# of
Inverters
OCPD
Total AC
Comb.
EGC
AC
out.(A)
OCPD
Solar Edge SE10000H
10000
42.00
240
1
60
42.0
60
#10
Ar
****N/A****
0
0.00
0
0
0
****N/A****
0
0.00
0
0
0
Module Specs
Watts
IMP
Vmp
Voc
Isc
Temp. Coef V(oc)
EGC
DC
at
a.Peak DUO BLK ML-G10+ 40
405
10.83
37.39
45.34
11.17
-0.27
#10
Ma
IV
Temp. Adjusted
32.8
49.3
Optimizer?
S440 SolarEdge Optimizer
Max current output: 15A, Max Voltage: 480V
Equipment
Solar Edge SE10000H
****N/A****
****N/A****
Mppt Input
1
2
1 3
1
2
1 3
1
2
1 3
Module
leak DUO BLK ML-G10+ 4
****SELECT****
****SELECT****
# Modules per String
13
10
8
0
0
0
0
0
0
# Strings
1
1
1
0
0
0
0
0
0
# of Mods per group
13
10
8
0
0
0
0
0
0
# of Mods/inverter
31
0
0
# of Inverters
1
0
0
Total # of Modules
31
Ref.
Conductor Description
Distance
AL CU
A
String to Jbox
50
CU
B
Jbox to Inverter
50
CU
C
Inverter to Gateway
10
CU
D
E
F
G
HI
I
J
Arrav Specs (Adiusted for Temperature
I nverter
Solar Edge SE10000H
****N/A****
**'
Mppt Input
1
2
3
1
2
3
1
iperage (Imp)
13.16
10.13
8.10
0.00
0.00
0.00
0.00
toltage (Vmp)
400.0
400.0
400.0
0.0
0.0
0.0
0.0
c Voltage(DC)
ax Amps (DC)
480.0
480.0
480.0
0.0
0.0
0.0
0.0
15.00
115.00
1 15.00
1 0.00
1 0.00
0.00
0.00
Max Array Power(STC): 12.555 kW DC
Max Continuous AC Power: 10kW AC
Interconnection Calcs
Main Breaker
200
Bus Bar
200
Max PV OCD Allowed
N/A
PV OCPD Device Used
60
Tap or Breaker?
Breaker
Wire
Gauge
(QTY) Phase
Neutral
Neutral
EGC
(AWE)
Wire Type
Conduit Type
Min.
Conduit
I 90°C
I Rating
Temp
Correct.
Fill
Derate
Derated
I 75°C
Ratt
Conductors
AWE
QTY
Ampacity
#10
2
N/A
N/A
#6
PV Wire 600V
AIR
N/A
40
1
100%
40.00
35
#10
6
N/A
N/A
#10
THWN-2
EMT
0.75"
40
1
80%
32.00
35
#6
2
#8
1
#10
THWN-2
EMT
0.75"
75
1 1
1 100%1
75.00
65
&ffl.
A&RSOLAR
3211 Martin Luther King Jr Way S.
Seattle, WA 98144 (206)707-9937
`N/A****
2
3
0.00
0.00
THIS DRAWING CONSTITUTES THE
O 0
0 O
CONFIDENTIAL INFORMATION OF A&R SOLAR
NO ITS RECEPTOR. POSSESSION DOES NOT
)NFER ANY RIGHT IN OR LICENSE TO USE IT
)R THE INFORMATION DISCLOSED HEREIN
NOR ANY RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART HEREIN WITHOUT
0.0
0 0
THE WRITTEN CONSENT OF A&R SOLAR.
0.00
0.00
U
=Q
Q
(A
C.
3
-�e
O
O
0
cn
�-
O
N
m
Op
4 -+
u)
N
o
O
CO
m
Q
Site Conditions
ASHRAE Site:
Seattle
Low Temp (°F)
19
High 2%Temp (°F)
84
T
I
O
Q
High 0.4%Temp (°F)
91
No
Voln�
U
0Ul
(n
00
110
IQ)
■
Q
L
a
Se
Ln
Ln
(!
cV�
O
W
Current
Operating
Voltage
@125%
Voltage
Drop
18.8
400
0.41 %
18.8
400
0.41 %
52.5
1 240
10.17%
REVISIONS
Rev. #: I Date:
Designed by: Thomas N
XVoltage drop 0.82% kCVoltage drop #### Total Voltage Drop: 1 0.99% 1 Project Manager:
Will MacArthur
(206)307-1741
Current Date:Apr 11, 2023
E2 Electrical
Calculations
Typical Placards
Custom Placards
A) NEC 2020 690.13 & 691.15
B) NEC 2020 705.12 (13)(3)(2)
C) Utility Requirement
D) Utility Requirement (Commercial Only)
D) A&R Solar Requirement (Residential
Customer -Owned)
E) A&R Solar Requirement * if combiner used
F) NEC 2020 690.13 (B)
I) NEC 2020 690.31 (D)(2)
K) NEC 2020 690.13 (B)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFFPOSITION TO
SOLARAELS
PV PANELS
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD IN THE
ARRAY
L) NEC 2020 690.56 (C)
*Used with Micro Inverters or DC Optimizers
O) A&R Solar Requirement * if
multiple inverters
IAWARNING DUAL POWER SOURCE]
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
P) NEC 2020 705.12(C) & 690.59
R) AHJ Requirement * if combiner used
S) NEC 2020 230.85(1)
T) NEC 2020 230.85(3)
NEC 690.54
NEC 690.53
NEC 690.54
PLACARD
ti,=CS
L Ti
Letter Height: 1/8" Inverter
Maintain 1/4" border 1
Interconnection Point
Red / White
Letter Height: 1/8"
Maintain 1/4" border 1 Solar Edge SE10000H
Red / White
Letter Height: 1/8" (1) for each
Maintain 1/4" border 1 Disconnect or upstream
Red / White loadcenters.
A&RSOLAR
3211 Martin Luther King Jr Way S.
Seattle, WA 98144 (206)707-9937
THIS DRAWING CONSTITUTES THE
CONFIDENTIAL INFORMATION OF A&R SOLAR
AND ITS RECEPTOR. POSSESSION DOES NOT
CONFER ANY RIGHT IN OR LICENSE TO USE IT
OR THE INFORMATION DISCLOSED HEREIN
NOR ANY RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART HEREIN WITHOUT
THE WRITTEN CONSENT OF A&R SOLAR.
U
cQ
0
_I-z
O
O
O
0
O
�(nO�
ul
ViU
CO
f�
..
V
p
(n
oIn�.oC
N
z vi
��
��;10
E
O
L
Ln
U)J
_0
W
aN
REVISIONS
Rev. #: I Date:
Designed by: Thomas N
Project Manager:
Will MacArthur
(206)307-1741
Current Date:Apr 11, 2023
G4 Placards
J) NEC 2020 690.56 (C)(2)
Standard Storage Placards
Custom Storage Placards
Label Location:
(BLC)
Label Location:
(GP)
Label Location:
(BLC)
Label Location:
(BLC,MSP,NM)
NEC 705.12(C)
For storage only
projects
Label Location:
(TG if outside,
service disconnect
breaker if TG
is inside)
NEC 230.85
BLC - Backup Load Center
GP - Generation Panel
MSP - Main Service Panel
NM - Net Meter
TG - Tesla Gateway
Label Location:
(BLC,MSP,NM)
NEC 705.12(C)
For PV+storage
projects
Label Location:
(BLC)
NEC 705.12(B)(3)(3)
Label Location:
(TG)
Label Location:
(GP)
Label Location:
(Battery breaker or
battery disconnect)
NEC 706.15(C)
CAUTION:
POWER TO THIS SERVICE IS ALSO SUPPLIED FROM SOLAR PV AND ENERGY
STORAGE SYSTEM SOURCES WITH DISCONNECTS LOCATED AS SHOWN:
N
MAPLE STREET
Directory Placard Qty: 1
NET METER
OLAR AND
ATTERY AC
uISCONNECTS
A&RSOLAR
3211 Martin Luther King Jr Way S.
Seattle, WA 98144 (206)707-9937
THIS DRAWING CONSTITUTES THE
CONFFIDENTIAL INFORMATION OF A&R SOLAR
AND ITS RECEPTOR POSSESSION DOES NOT
CONFER ANY RIGHT IN OR LICENSE TO USE IT
OR THE INFORMATTION DISCLOSED HERE IN
NOR ANY RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART HERE IN WITHOUT
THE WRITTEN CONSENT OF A&R SOLAR.
a)
a
ra
L-
O
C
Oo
( n
a N
E a
U
Q
U�
L U
la o
Y
Ln
Ln
Ln
N
T -1
O
N
O O
CN4-;00
0C-1 U-)M
Ln 0 00 W a
E O Q3:
— 00 ru
U0 N 2:
0 Ln �o C
U N N p
�.o
W
REVISIONS
Rev. #: I Date:
Designed by: Thomas N
PM: Will MacArthur
(206)307-1741
Current Date:Apr 11, 2023
PV-G3 Placards