Loading...
BLD2023-1360_Other_10.31.2023_9.04.39_AM_3870597PV Single Line - - - - - - - - - - - - - - - - String 1 — +� z 13 modules PI o V String 2 U 10 modules String 3 8 modules 0 Equipment Schedule A Storage Single Line I 0 ------ I I I I I I I A A 60A/2p I I • I I I I 30A/2p I I 2 L-- 30A/2p Battery Disconnect, Located within 10' of net meter PV breaker in Gateway to serve as exterior solar rapid shutdown initiation device 200A TESLA Gateway2 with 200A Internal Panelboard Solar OCPD:60A Battery OCPD:60A Co -Located with Net Meter Battery combiner panel I I I Bus Rating: 125A I o ' I I I 4/0 XHHW-2 ( I L1 & L2) ----------------------------—-=--———————————————------------------------- 2/ 0 XHHW-2 Ref. Category Equipment QTY 1 Modules Q.Peak DUO BLK ML-G10+ 405 31 2 Optimizers S440 SolarEdge Optimizer 31 3 Jbox Soladeck 5 41 Inverters I Solar Edge SE10000H 1 Monitoring I SolarEdge PV Inverter Monitoring 1 0 Conductor Schedule I nverter Specs Watts LW-1 Output AC Voltage # of Inverters OCPD u Solar Edge SE11400H 11400 47.5 240 1 60 ****N/A**** 0 0 0 0 0 ****N/A**** 0 0 0 0 0 Module Specs Watts w LrKLp Vmp Voc Isc Q.Peak DUO BLK VIL-G10+4 405 10.83 37.39 45.34 11.17 Temp. Adjusted 0 0 32.8 1 49.3 0 Summary Distance (ft) Current @125% Operating Voltage Voltage Drop V. Drop (total) A (2)#10 CU, (1)#6 EGC, PV Wire 600V, AIR 50 18.75A 400V 0.41% 0.99% B (6)#10 CU, (1)#10 EGC, THWN-2, 0.75"EMT(min) 50 18.75A 400V 0.41% C (2)#6 CU, (1)#8 N, (1)#10 EGC, THWN-2, 0.75"EMT(min) 10 52.5A 240V 0.17% (N) #6 THWN-2 200A/2p (EGC) Protected Loads Panel (Existing) Main Service Panel (lph 240V Service) Main Breaker: 200A Bus Rating:200A 0 Equipment Schedule Ref. Category Equipment QTY 1 Gateway Tesla Backup Gateway2: Service Rated 1 Breakers 200A Main Breaker (Eaton CSR2200N) 1 Misc. Tesla 200A Internal Panelboard Kit 1 Breakers 2p60A, 2p60A 2 Battery Tesla Powerwall 2, 13.5 kWh 2 Misc. Powerwall Stack Kit 1 3 Loadcenters MLO, 125A, 240V, 1ph, Nema 1, Flush, 8 space (min.) 1 Breakers 2p60A, 2p30A, 2p30A Misc. Breaker Hold down kit 1 4 Disconnect 60A 600V 2 Pole I Heavy Duty, No Fuse, Lockable 1 Misc. Neurio Meter Kit 1 0 Conductor Schedule ■=A&RScope `,'I' I = Existing or A&RSOLAR Others Scope 3211 Martin Luther King Jr Way S. Seattle, WA 98144 (206)707-9937 OI Net Meter 4/0 XHHW-2 (L1 & L2) 2/0 XHHW-2 (N) 200A/2p Unprotected Loads Panel (Existing) Main Service Panel (lph 240V Service) Main Breaker: 200A Bus Rating:200A Inverter Specs Watts Output AC Voltage # of Inverters OCPD LW-1 Tesla Powerwall 2 5000 1 24 240 2 30 Summary Distance (ft) Current @125% Operating Voltage Voltage Drop A (4)#10 CU, (2)#10 N, (1)#10 EGC, THWN-2, & com wire, 1"EMT(min) 10 30A 240V 0.25% B (2)#6 CU, (1)#6 N, (1)#10 EGC, THWN-2, & com wire, 1"EMT(min) 10 60A 240V 0.20% THIS DRAWING CONSTITUTES THE :ONFFIDENTIAL INFORMATION OF A&R SOLAR AND ITS RECEPTOR POSSESSION DOES NOT :ONFER ANY RIGHT IN OR LICENSE TO USE IT OR THE INFORMATTION DISCLOSED HERE IN NOR ANY RIGHT TO REPRODUCE THIS DRAWING OR ANY PART HERE IN WITHOUT THE WRITTEN CONSENT OF A&R SOLAR. L O 07 p� O C: O N a-+ O CO 00)Lnm ■ Q Q I O 00 N Q Q 4W U O o (f) a-+ O N Ln �10 U O �� U w a� Ln Ln Ln N REVISIONS Rev. #: Date: 1 1 Oct 23, 2023 General Notes: Designed by: Thomas N Utility: Snohomish PUD PM: Will MacArthur 1. EGC Where exposed to physical damage will be #6AWG (206) 307-1741 Bare CU Current Date:Oct 23, 2023 2. If installing conduit on the roof, maintain greater than 7/8" above the surface 3. NEC 690.12: Rapid Shutdown initiated by AC Disconnect I E1 Single Line PV Electrical Calculations Inverter Specs Watts (W) Output AC Voltage # of Inverters OCPD Total AC Comb. EGC AC out.(A) OCPD Solar Edge SE10000H 10000 42.00 240 1 60 42.0 60 #10 Ar ****N/A**** 0 0.00 0 0 0 ****N/A**** 0 0.00 0 0 0 Module Specs Watts IMP Vmp Voc Isc Temp. Coef V(oc) EGC DC at a.Peak DUO BLK ML-G10+ 40 405 10.83 37.39 45.34 11.17 -0.27 #10 Ma IV Temp. Adjusted 32.8 49.3 Optimizer? S440 SolarEdge Optimizer Max current output: 15A, Max Voltage: 480V Equipment Solar Edge SE10000H ****N/A**** ****N/A**** Mppt Input 1 2 1 3 1 2 1 3 1 2 1 3 Module leak DUO BLK ML-G10+ 4 ****SELECT**** ****SELECT**** # Modules per String 13 10 8 0 0 0 0 0 0 # Strings 1 1 1 0 0 0 0 0 0 # of Mods per group 13 10 8 0 0 0 0 0 0 # of Mods/inverter 31 0 0 # of Inverters 1 0 0 Total # of Modules 31 Ref. Conductor Description Distance AL CU A String to Jbox 50 CU B Jbox to Inverter 50 CU C Inverter to Gateway 10 CU D E F G HI I J Arrav Specs (Adiusted for Temperature I nverter Solar Edge SE10000H ****N/A**** **' Mppt Input 1 2 3 1 2 3 1 iperage (Imp) 13.16 10.13 8.10 0.00 0.00 0.00 0.00 toltage (Vmp) 400.0 400.0 400.0 0.0 0.0 0.0 0.0 c Voltage(DC) ax Amps (DC) 480.0 480.0 480.0 0.0 0.0 0.0 0.0 15.00 115.00 1 15.00 1 0.00 1 0.00 0.00 0.00 Max Array Power(STC): 12.555 kW DC Max Continuous AC Power: 10kW AC Interconnection Calcs Main Breaker 200 Bus Bar 200 Max PV OCD Allowed N/A PV OCPD Device Used 60 Tap or Breaker? Breaker Wire Gauge (QTY) Phase Neutral Neutral EGC (AWE) Wire Type Conduit Type Min. Conduit I 90°C I Rating Temp Correct. Fill Derate Derated I 75°C Ratt Conductors AWE QTY Ampacity #10 2 N/A N/A #6 PV Wire 600V AIR N/A 40 1 100% 40.00 35 #10 6 N/A N/A #10 THWN-2 EMT 0.75" 40 1 80% 32.00 35 #6 2 #8 1 #10 THWN-2 EMT 0.75" 75 1 1 1 100%1 75.00 65 &ffl. A&RSOLAR 3211 Martin Luther King Jr Way S. Seattle, WA 98144 (206)707-9937 `N/A**** 2 3 0.00 0.00 THIS DRAWING CONSTITUTES THE O 0 0 O CONFIDENTIAL INFORMATION OF A&R SOLAR NO ITS RECEPTOR. POSSESSION DOES NOT )NFER ANY RIGHT IN OR LICENSE TO USE IT )R THE INFORMATION DISCLOSED HEREIN NOR ANY RIGHT TO REPRODUCE THIS DRAWING OR ANY PART HEREIN WITHOUT 0.0 0 0 THE WRITTEN CONSENT OF A&R SOLAR. 0.00 0.00 U =Q Q (A C. 3 -�e O O 0 cn �- O N m Op 4 -+ u) N o O CO m Q Site Conditions ASHRAE Site: Seattle Low Temp (°F) 19 High 2%Temp (°F) 84 T I O Q High 0.4%Temp (°F) 91 No Voln� U 0Ul (n 00 110 IQ) ■ Q L a Se Ln Ln (! cV� O W Current Operating Voltage @125% Voltage Drop 18.8 400 0.41 % 18.8 400 0.41 % 52.5 1 240 10.17% REVISIONS Rev. #: I Date: Designed by: Thomas N XVoltage drop 0.82% kCVoltage drop #### Total Voltage Drop: 1 0.99% 1 Project Manager: Will MacArthur (206)307-1741 Current Date:Apr 11, 2023 E2 Electrical Calculations Typical Placards Custom Placards A) NEC 2020 690.13 & 691.15 B) NEC 2020 705.12 (13)(3)(2) C) Utility Requirement D) Utility Requirement (Commercial Only) D) A&R Solar Requirement (Residential Customer -Owned) E) A&R Solar Requirement * if combiner used F) NEC 2020 690.13 (B) I) NEC 2020 690.31 (D)(2) K) NEC 2020 690.13 (B) SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFFPOSITION TO SOLARAELS PV PANELS SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY L) NEC 2020 690.56 (C) *Used with Micro Inverters or DC Optimizers O) A&R Solar Requirement * if multiple inverters IAWARNING DUAL POWER SOURCE] SECOND SOURCE IS PHOTOVOLTAIC SYSTEM P) NEC 2020 705.12(C) & 690.59 R) AHJ Requirement * if combiner used S) NEC 2020 230.85(1) T) NEC 2020 230.85(3) NEC 690.54 NEC 690.53 NEC 690.54 PLACARD ti,=CS L Ti Letter Height: 1/8" Inverter Maintain 1/4" border 1 Interconnection Point Red / White Letter Height: 1/8" Maintain 1/4" border 1 Solar Edge SE10000H Red / White Letter Height: 1/8" (1) for each Maintain 1/4" border 1 Disconnect or upstream Red / White loadcenters. A&RSOLAR 3211 Martin Luther King Jr Way S. Seattle, WA 98144 (206)707-9937 THIS DRAWING CONSTITUTES THE CONFIDENTIAL INFORMATION OF A&R SOLAR AND ITS RECEPTOR. POSSESSION DOES NOT CONFER ANY RIGHT IN OR LICENSE TO USE IT OR THE INFORMATION DISCLOSED HEREIN NOR ANY RIGHT TO REPRODUCE THIS DRAWING OR ANY PART HEREIN WITHOUT THE WRITTEN CONSENT OF A&R SOLAR. U cQ 0 _I-z O O O 0 O �(nO� ul ViU CO f� .. V p (n oIn�.oC N z vi �� ��;10 E O L Ln U)J _0 W aN REVISIONS Rev. #: I Date: Designed by: Thomas N Project Manager: Will MacArthur (206)307-1741 Current Date:Apr 11, 2023 G4 Placards J) NEC 2020 690.56 (C)(2) Standard Storage Placards Custom Storage Placards Label Location: (BLC) Label Location: (GP) Label Location: (BLC) Label Location: (BLC,MSP,NM) NEC 705.12(C) For storage only projects Label Location: (TG if outside, service disconnect breaker if TG is inside) NEC 230.85 BLC - Backup Load Center GP - Generation Panel MSP - Main Service Panel NM - Net Meter TG - Tesla Gateway Label Location: (BLC,MSP,NM) NEC 705.12(C) For PV+storage projects Label Location: (BLC) NEC 705.12(B)(3)(3) Label Location: (TG) Label Location: (GP) Label Location: (Battery breaker or battery disconnect) NEC 706.15(C) CAUTION: POWER TO THIS SERVICE IS ALSO SUPPLIED FROM SOLAR PV AND ENERGY STORAGE SYSTEM SOURCES WITH DISCONNECTS LOCATED AS SHOWN: N MAPLE STREET Directory Placard Qty: 1 NET METER OLAR AND ATTERY AC uISCONNECTS A&RSOLAR 3211 Martin Luther King Jr Way S. Seattle, WA 98144 (206)707-9937 THIS DRAWING CONSTITUTES THE CONFFIDENTIAL INFORMATION OF A&R SOLAR AND ITS RECEPTOR POSSESSION DOES NOT CONFER ANY RIGHT IN OR LICENSE TO USE IT OR THE INFORMATTION DISCLOSED HERE IN NOR ANY RIGHT TO REPRODUCE THIS DRAWING OR ANY PART HERE IN WITHOUT THE WRITTEN CONSENT OF A&R SOLAR. a) a ra L- O C Oo ( n a N E a U Q U� L U la o Y Ln Ln Ln N T -1 O N O O CN4-;00 0C-1 U-)M Ln 0 00 W a E O Q3: — 00 ru U0 N 2: 0 Ln �o C U N N p �.o W REVISIONS Rev. #: I Date: Designed by: Thomas N PM: Will MacArthur (206)307-1741 Current Date:Apr 11, 2023 PV-G3 Placards