STRUCTURAL CALCULATIONS
(Permit Submittal)
EDMONDS MEDICAL
21616 76T" AVE W
EDMONDS, WA 98026
Quantum Job Number: 23269.01
Prepared for:
VITAL MECHANICAL SERVICE
1420 Maple Ave SW
Renton, WA 98057
Prepared by:
QUANTUM CONSULTING ENGINEERS
1511 Third Avenue, Suite 323
Seattle, WA 98101
TEL 206.957.3900
FAX 206.957.3901
RECEIVED
Jul 14 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
This document shall be onsite for
inspector. RTU anchorage details.
July 12, 2023
QUANTUM I CONSULTING ENG INEERS
1511 Third Avenue, Suite 323
Seattle, WA 98101
TEL 206.957.3900
FAX 206.957.3901
EDMONDS MEDICAL
2616 76" Ave W
Edmonds, WA 98026
Quantum Job Number: 23269.01
INDEX
STRUCTURAL SKETCHES......................................................................... 3
DESIGN CRITERIA................................................................................... 5
STRUCTURAL DESIGN........................................................................... 11
EDMONDS MEDICAL
21616 76t" Ave W
Edmonds, WA 98026
Quantum Job Number: 23269.01
STRUCTURAL SKETCHES
RT
(E)
(E)
(E) TRUSS PER PLAN—/
Edmonds Medical
project
1511 THIRD AVENUE RTU Anchorage
SUITE 323
SEATTLE, WA 98101
TEL 206.957.3900 Vital Mechanical Service
QUANTUM FAX 206.957.3901
C O N S U L T I N G E N G I N E E R S www.quantumce.ccrn Client
(2) 1/4" DIA. x 3" SIDS SCREWS
TO
D
7/12/23 23269.01
date job no.
drawn by:
MKS
design by: sheet no.
EDMONDS MEDICAL
21616 76t" Ave W
Edmonds, WA 98026
Quantum Job Number: 23269.01
DESIGN CRITERIA
Structural Design Criteria
Building
Code:
2018 International Building Code
Building
Department: City of Edmonds
Seismic Criteria
Ss:
1.28
le: 1.00
S,:
0.45
Seismic Soil Site Class: D
Sds:
1.03
Seismic Design Category: D
Sd1:
0.56
Materials Criteria
Wood Framing:
2x, 3x & 4x Framing Members
Wind Criteria
Wind Speed: 97
Risk Category: II
Wind Exposure: B
Kzt: 1.0
HF#2 or DF#2
Quantum Consulting Engineers LLC Project: Edmonds Medical Date: 7/12/23 Job No: 23269.01
1511 Third Avenue, Suite 323 Designer: MKS Sheet: 1
Seattle, WA 98101 Client: Vital Mechanical Service Checked By: JHR
Building Loads
Snow Load Roof 25 psf
Assembly Loads
Roof
Roofing
2.0 psf
Sheathing
2.3 psf
Insulation
1.0 psf
Roof Trusses @ 48" o.c
5.0 psf
Mech./Elec.
1.0 psf
Acoustic Panels
0.5 psf
Sprinklers
2.0 psf
Misc.
1.2 psf
Total:
15.0 psf
Comments
SL=25 PSF
Deflection Criteria
Roof Walls L/120 *flexible finishes Floor
Live Load: L/240 L/240 *brittle finish Live Load: L/360
Total Load: L/180 L/240 *supporting glass Total Load: L/240
9 Quantum Consulting Engineers LLC Project: Edmonds Medical Date: 7/12/23 Job No: 23269.01
1511 Third Avenue, Suite 323 Designer: MKS Sheet: 1
Seattle, WA 98101 Client: Vital Mechanical Service Checked By:
A This is a beta release of the new ATC Hazards by Location website. Please contact us with feedback.
6 The ATC Hazards by Location website will not be updated to support ASCE 7-22. Find out why.
LITC Hazards by Location
Search Information
Address:
Parking lot, 21616 76th Ave W ste 208, Edmonds, WA
98026, USA
Coordinates:
47.8026806,-122.3367596
Elevation:
407 ft
Timestam p:
2023-07-07T22:01:34.885Z
Hazard Type:
Seismic
Reference
ASCE7-16
Document:
Risk Category:
II
Site Class:
D-default
Basic Parameters
Name
Value
Description
SS
1.282
MCER ground motion (period=0.2s)
S,
0.451
MCER ground motion (period=1.Os)
SMS
1.538
Site -modified spectral acceleration value
SMt
* null
Site -modified spectral acceleration value
SDg
1.026
Numeric seismic design value at 0.2s SA
SDt
* null
Numeric seismic design value at 1.0s SA
* See Section 11.4.8
Additional Information
Name
Value
Description
SDC
* null
Seismic design category
Fa
1.2
Site amplification factor at 0.2s
Fv
* null
Site amplification factor at 1.0s
CRs
0.91
Coefficient of risk (0.2s)
CRt
0.895
Coefficient of risk (1.0s)
PGA
0.546
MCER peak ground acceleration
FpGA
1.2
Site amplification factor at PGA
PGAM
0.655
Site modified peak ground acceleration
4
¢5egwm Marysville
Wh rlh
—„a
rett,.
101 fs 407 ft ]
Edm sW
i r k
eaftIe oRedmonr
D
O
Bremerton Renton
�}I{ O
SeaTac4 r...�� �
Mpt AI
Baker- naqualmi
National Foresi
Fo
TL
6
Long -period transition period (s)
SsRT
1.282
Probabilistic risk -targeted ground motion (0.2s)
SsUH
1.409
Factored uniform -hazard spectral acceleration (2% probability of
exceedance in 50 years)
SsD
2.3
Factored deterministic acceleration value (0.2s)
S1 RT
0.451
Probabilistic risk -targeted ground motion (1.0s)
S1 UH
0.504
Factored uniform -hazard spectral acceleration (2% probability of
exceedance in 50 years)
S1 D
0.94
Factored deterministic acceleration value (1.0s)
PGAd
0.807
Factored deterministic acceleration value (PGA)
* See Section
11.4.8
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building code adoption
process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before proceeding with design.
Please note that the ATC Hazards by Location website will not be updated to support ASCE 7-22. Find out why.
Disclaimer
Hazard loads are provided by the U.S. Geological Survey Seismic Design Web Services.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility or liability for
its accuracy. The material presented in the report should not be used or relied upon for any specific application without competent examination and
verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does not intend that the use of this information
replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the standard
of care required of such professionals in interpreting and applying the results of the report provided by this website. Users of the information from this
website assume all liability arising from such use. Use of the output of this website does not imply approval by the governing building code bodies
responsible for building code approval and interpretation for the building site described by latitude/longitude location in the report.
A This is a beta release of the new ATC Hazards by Location website. Please contact us with feedback.
6 The ATC Hazards by Location website will not be updated to support ASCE 7-22. Find out why.
LITC Hazards by Location
Search Information
Address: Parking lot, 21616 76th Ave W ste 208, Edmonds, WA
98026, USA
Coordinates:
Elevation:
Timestamp:
Hazard Type:
ASCE 7-16
MRI 10-Year
MRI 25-Year
MRI 50-Year
MRI 100-Year
Risk Category I
Risk Category II
Risk Category III
Risk Category IV
47.8026806,-122.3367596
407 ft
2023-07-07T21:58:15.924Z
Wind
ASCE 7-10
67 mph MRI 10-Year
73 mph MR125-Year
78 mph MRI 50-Year
83 mph MRI 100-Year
92 mph Risk Category I
97 mph Risk Category II
104 mph Risk Category III -IV
108 mph
4
¢5egwm Marysville
Wh rlh
-„a
rett,.
101 fs 407 ft ]
Edm S
i r k
eaftIe oRedmonr
a
G
Bremerton Renton
pie; a
SeaTacG
ASCE 7-05
72 mph ASCE 7-05 Wind Speed
79 mph
85 mph
91 mph
100 mph
110 mph
115 mph
Baker- naqualmi
National Foresi
85 mph
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building code adoption
process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before proceeding with design.
Please note that the ATC Hazards by Location website will not be updated to support ASCE 7-22. Find out why.
Disclaimer
Hazard loads are interpolated from data provided in ASCE 7 and rounded up to the nearest whole integer. Per ASCE 7, islands and coastal areas outside
the last contour should use the last wind speed contour of the coastal area — in some cases, this website will extrapolate past the last wind speed
contour and therefore, provide a wind speed that is slightly higher. NOTE: For queries near wind-borne debris region boundaries, the resulting
determination is sensitive to rounding which may affect whether or not it is considered to be within a wind-borne debris region.
Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility or liability for
its accuracy. The material presented in the report should not be used or relied upon for any specific application without competent examination and
verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does not intend that the use of this information
replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the standard
of care required of such professionals in interpreting and applying the results of the report provided by this website. Users of the information from this
website assume all liability arising from such use. Use of the output of this website does not imply approval by the governing building code bodies
responsible for building code approval and interpretation for the building site described by latitude/longitude location in the report.
EDMONDS MEDICAL
21616 76t" Ave W
Edmonds, WA 98026
Quantum Job Number: 23269.01
STRUCTURAL DESIGN
Seismic Base Shear for the Equivalent Lateral Force Procedure
Per IBC 2018 & ASCE 7-16
Structure: Edmonds Medical
Address: 21616 76th Ave W, Edmonds, WA
Latitude: 47.8027 Longitude:-122.3368
Structure Classification
Risk Category: II per ASCE Table 1.5-1
Seismic Force -Resisting System: Light -Framed Wood Walls Sheathed with Structural Panels
R: 6 1/2 per ASCE Table 12.2-1
Wo: 3 per ASCE Table 12.2-1
Cd: 4 per ASCE Table 12.2-1
hn (ft): 24.00 height above the base to the highest level of the structure
Site Ground Motion
Reg. Structure/5 Stories Max:
S, (g-sec):
Site Class:
Fv 1.85
SM, (g-sec): 0.83
Spi (g-sec): 0.56
SDC: D
IE: 1.00
Yes Sds (max) = 1.0 Per ASCE 12.8.1.3
0.45 SS (g-sec): 1.28
D Assumed Value per ASCE 11.4.3
ASCE 11.4.8 Exception 2 Used
Fa 1.20
1.2 Min Value where SC D Assumed
Sans (g-sec): 1.54
SDS (g-sec): 1.03
per ASCE 11.6
per ASCE Table 1.5-2
Fundamental Period per ASCE 12.8.2
Period Method: Approximate Fundamental Period
Structure Type: All Other Structural Systems
TL (sec): 6.00 ASCE Figures 22-14 through 22-17
Ts: 0.54
Ta (sec): 0.22 Ct * hnx per ASCE Eq. 12.8-7
Tuse (sec): 0.22 - — TL
Equivalent Lateral Force Procedure Desian Base Shear per ASCE 12.8
Cs: 0.16 = SDS / (R/IE) per ASCE Eq. 12.8-2
Cs -max: 0.39 = Sol / (Ta*R/IE) for T <= TL per ASCE Eq. 12.8-3
CS -Max,• -- = Sp,*TL / (Ta2*R/IE) for T > TL per ASCE Eq. 12.8-4
Cs -min: 0.05 per ASCE Eq. 12.8-5
Cs -min: -- = 0.5S, / (R/IE) for S, _> 0.6g per ASCE Eq. 12.8-6
Cs -use: 0.16
V : 0.158 W = Cs -use * W per ASCE Eq. 12.8-1
per ASCE 11.4.4
per ASCE 11.4.5
GJQuantum Consulting Engineers LLC Project: Edmonds Medical Date: 7/12/23 Job No: 23269.01
1511 Third Avenue, Suite 323 esigner: MKSSheet:
Seattle, WA 98101 Client: Vital Mechanical Checked By:
Non -Structural Component Seismic Anchorage Design
IBC 2018, ASCE 7-16 Chapter 13
Seismic Criteria:
Site Class:
D
SDs:
1.03
SD1:
0.56
IP:
1
Fpmax= 1.65 Wp
Controls Fp= 0.52 Wp
Fpmin= 0.31 Wp
z: 24.0 ft
h: 24.0 ft
aP: 2.5
RP: 6
Table 13.5-1
Fpmax= 1.6 Sos WP IP
Fp= 0.4 apSDsWPx (1+2z/h)/(RP/ IP)
Fpmin= 0.3 Sos WP IP
Mechanical Unit:
Ht to Center of Mass, Y: 20 in
Overturning Distance, X: 45 in
Weight, WP: 0.62 k
Anchors/Side: 2
Shear and Overturning
Loads:
Seismic Force, Fp:
0.32 k
Shear/Anchor:
0.08 k
0.06 k
OT Moment:
6.4 k-in
Tension/Side:
-0.143 k
Net Uplift/Anchor:
0.04 k
0.02 k
r
U LT
ASD
U LT
ULT (0.9-0.2Sds)DL+ 1.OEQ
ASD (0.6-0.14Sds)DL + 0.7EQ
Anchorage Design:
1/4" Diann. x 3" SDS Screw into P/T HF Sleeper
Vallowable: 0.32 k
Tallowable: 0.38 k
Unity EQ: 0.12 <1.0
EQ 13.3-2
EQ 13.3-1
EQ 13.3-3
Quantum Consulting Engineers LLC Project: Edmonds Medical Date: 7/12/23 Job No: 23269.01
1511 Third Avenue, Suite 323 Designer: MKS Sheet:
Seattle, WA 98101 Client: Vital Mechanical Checked:
Non -Structural Component Wind Anchorage Design
IBC 2018, ASCE 7-16 Chapter 29
Wind Criteria:
Kz:
0.85
Kzt:
1.0
Kd:
0.9
Ke
1
V:
97
Building Ht:
24
Building Width, B:
120
Building Length, L:
240
(GCr):
1.9
(GCr):
1.5
qh:
18.4
Ph:
35.0
Pv:
27.6
Mechanical Unit:
ASCE TABLE 26.10-1 FOR EXPOSURE B AND z = 60' MAX.
ASCE SEC 26.8
ASCE TABLE 26.6-1
ASCE TABLE 26.9-1
MPH
ft
ft, Normal to Wind Direction
ft, Parallel to Wind Direction
ASCE SEC 29.4.1 Lateral Force
ASCE SEC 29.4.1 Uplift Force
PSF [ASCE EQUATION 26.10-11
PSF [ASCE EQUATION 29.4-2] Lateral Force
PSF [ASCE EQUATION 29.4-3] Uplift Force
Weight, Wp:
0.62 k
Ht of Unit, h:
41 in
Overturning Distance, L:
45 in
Dist. Normal to Wind, B:
78 in
Anchors/Side:
2
Shear and Overturning Loads:
Wind Force, Fh:
0.78 k
Wind Force, Fv:
0.67 k
Shear/Anchor:
0.19 k
0.12 k
OT Moment:
15.9 k-in
Tension/Side:
-0.7 k
Net Uplift/Anchor:
-0.21 k
-0.11 k
Lateral Force
Uplift Force
U LT
ASD
U LT
ULT 0.9DL+ 1.OW
ASD 0.6DL + 0.6W
Anchorage Design:
1/4" Diam. x 3" SDS Screw into P/T HF Sleeper
Vallowable: 0.32 k
Tallowable: 0.38 k
Unity EQ: 0.66 <1.0
WIND
T
l
• Quantum Consulting Engineers LLC Project: Edmonds Medical Date: 7/12/23 Job No: 23269.01
1511 Third Avenue, Suite 323 Designer: MKS Sheet:
Seattle, WA 98101 Client: Vital Mechanical Checked:
Edmonds Medical RTU Ei71:7tii Existing Roof Truss
Span, L (ft): 48.0000 Min. Shear: 25% Required Uniform Load for:
Joist Spcg (ft): 4.0000 Hold Joist Depth (in): 24.0000 Shear Envelope (plfl: N.A. Actual Moment (plfl: 172
(Leave blank for most economical)
-----------------------------------------------------•
LOADS Provide Load Diagram to Vulcraft for most economical joist solution.
Full Uniform:
------------------------------------------------------------
w_dead (psf): 15.00 w_live (psf): 25.00
Suggested SJI Designation: N.A.
Suggested Load -per -Ft Designation: 24 LH SP
RL
Nomenclature
Point Loads:
Version 2.6
Bridging (H/X/EX) & Max. Chord Width: N.A.
Reactions:
TIIII
RL = 3.98 k RR
RR :Maximum Moments:
+M(max) = 49.32 ft-k @ x = 24.00 ft.
M(max) = 0.00 ft-k @ x = 0.00 ft.
Shear Diagram
5.0
..
W
a
i 0.0
M
W
s
U)
5.0
0 Ln o Ln o )n o Ln o in
N N M M 7
x (ft.)
.. 60.0
a
Y 40.0
w
4J 20.0
C
N
E 0.0
O
1 -20.0
0
0
0
-- -- Shear
Moment Diagram
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
in 0 in 0 Ln 0 Ln 0 in 0
.--i .--i N N M M V V U)
x (ft.)
-- -- Mx_eq
Edmonds Medical RTU
Existing Roof Truss w/ new RTU
Span, L (ft): 48.0000 Min. Shear: 25% Required Uniform Load for:
Joist Spcg (ft): 4.0000 Hold Joist Depth (in): 24.0000 Shear Envelope (plfl: N q Actual Moment (plfl: 173
(Leave blank for most economical)
-----------------------------------------------------•
LOADS Provide Load Diagram to Vulcraft for most economical joist solution.
Full Uniform:
w_dead (psf): 15.00 w_live (psf): 25.00
Suggested SJI Designation: N.A.
Suggested Load -per -Ft Designation: 24 LH SP
RL
Nomenclature
Point Loads:
Bridging (H/X/EX) & Max. Chord Width: N.A.
Reactions:
T1111
RL = 4.00 k RR
RR :Maximum Moments:
+M(max) = 49.80 ft-k @ x = 24.00 ft.
M(max) = 0.00 ft-k @ x = 0.00 ft.
Moment Increase = 49.80/49.32
=101%,OK
Shear Increase = 4.00/3.98
=101%,OK
Shear Diagram
5.0
5.0
0 Ln o Ln o in o Ln o in
N N M M 7
x (ft.)
.. 60.0
a
Y 40.0
i
w
4J 20.0
a�
E 0.0
0
X -20.0
0
0
0
---- Shear
Moment Diagram
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
Ln o in o Ln o Ln o in o
.--i .--i N N M M V V LO
x (ft.)
Version 2.6
- - - Mx_eq