APPROVED PLN BLD BLD2023-1018+Building_Elevations_Plans+8.11.2023_9.26.59_AM+3720531ABBREVIATIONS
GENERAL -LEGEND
0
DIAMETER
RTU EQUIPMENT TAG TYPE
ABV
ABOVE
2 EQUIPMENT TAG NUMBER
ACH
AIR CHANGES PER HOUR
AD
ACCESS DOOR
1 DETAIL OR DIAGRAM NUMBER
AFF
ABOVE FINISHED FLOOR
M2.1 SHEET NUMBER WHERE DETAIL SHOWN
AFG
AVERAGE FINISHED GRADE
AFUE
ANNUAL FUEL UTILIZATION EFFICIENCY
1 SECTION LETTER
AHU
AIR HANDLING UNIT
M2.1 SHEET NUMBER WHERE SECTION SHOWN
AHRI
AIR CONDITIONING, HEATING REFRIGERATION
INSTITUTE
AP
ACCESS PANEL
Al REVISION CLOUD AND CHRONOLOGICAL NUMBER
ARI
AMERICAN REFRIGERATION INSTITUTE
BHP
BRAKE HORSEPOWER
DETAIL REFERENCE OUTLINE
BDD
BACKDRAFT DAMPER
BOD
BOTTOM OF DUCT
POINT OF CONNECTION TO EXISTING OR TO
BF
BELOW FLOOR
OTHERS' WORK
BOT
BOTTOM
BTU(H)
BRITISH THERMAL UNIT (HOUR)
O1 KEY NOTE CALLOUT
CD
CONDENSATE
CFM
CUBIC FEET PER MINUTE
1Q PHOTO ID CALLOUT
CONN
CONNECTION
COP
COEFFICIENT OF PERFORMANCE
' ' ' ' ' WORK TO BE REMOVED
DB
DRY BULB/DECIBELS
BELS
H VAC - L E G E N D
DIBFF
DIFFERENTIAL
DN
DOWN
DR
DRAIN
�► AIR FLOW DIRECTION
E
EXISTING
EA
EACH OR EXHAUST AIR
SUPPLY OR OSA DUCT SECTION UP, ROUND OR
EAT
ENTERING AIR TEMPERATURE
RECTANGULAR
EC
ELECTRICAL CONTRACTOR
EER
ENERGY EFFICIENCY RATIO
RETURN, RELIEF OR EXHAUST DUCT SECTION UP,
EF
EXHAUST FAN
ROUND OR RECTANGULAR
EFF
EFFICIENCY
EG
ELEV
EXHAUST GRILLE
ELEVATION
SUPPLY OR OSA DUCT SECTION DOWN, ROUND
0
OR RECTANGULAR
EQUIP
EQUIPMENT
ESP
EXH
EXTERNAL STATIC PRESSURE
EXHAUST
RETURN, RELIEF OR EXHAUST DUCT SECTION
0
DOWN, ROUND OR RECTANGULAR
EXIST
EXISTING
F
FURNACE
EXISTING DUCTWORK
°F
FAHRENHEIT
FF
FINISHED FLOOR
SLSM SOUND LINED SHEET METAL
FLA
FULL LOAD AMPERAGE
FPM
FEET PER MINUTE
FC FLEXIBLE EQUIPMENT CONNECTION
FREQ
FREQUENCY
FT
FOOT OR FEET
°
SFD COMBINATION FIRE AND SMOKE DAMPER
G
NATURAL GAS
HP
HORSEPOWER OR HEAT PUMP
FD FIRE DAMPER
HR
HOUR
HSPF
HEATING SEASONAL PERFORMANCE FACTOR
SD SMOKE DAMPER
HT
HEIGHT
HVAC
HEATING, VENTILATING, AIR-CONDITIONING
EVADE VOLUME DAMPER
HZ
HERTZ
IBC
INTERNATIONAL BUILDING CODE
M MD MOTORIZED DAMPER
ID
INSIDE DIAMETER
IEER
INTEGRATED ENERGY EFFICIENCY RATIO
IFC
INTERNATIONAL FIRE CODE
TURNING VANES
IFGC
INTERNATIONAL FUEL GAS CODE
IMC
INTERNATIONAL MECHANICAL CODE
IN
INCHES
ROUND TO ROUND 45° FITTING
IN WG
INCHES WATER GAUGE
KW
KILOWATT
LAT
LEAVING AIR TEMPERATURE/LATITUDE
SQUARE TO SQUARE 45° FITTING
LBS
POUNDS
LIN FT
LINEAR FOOT OR FEET
LRA
LOCKED ROTOR AMPS
SQUARE TO ROUND 45° FITTING
MAX
MAXIMUM
MBH
1,000 BTU PER HOUR
MCA
MINIMUM CURRENT AMPS
VD 45° FITTING FOR DUCTWORK
MFR
MANUFACTURER
MIN
MINIMUM
GAS PIPING
MOCP
MAX OVER CURRENT PROTECTION
NEC
NATIONAL ELECTRICAL CODE
O CARBON MONOXIDE SENSOR
NIC
NOT IN CONTRACT
NOM
NOMINAL
O COORDINATED POWER LOCATION
OD
OUTSIDE DIAMETER/DIMENSION
OPTS
OPTIONS
O REMOTE SENSOR
OSA
OUTSIDE AIR
PH
ELEC POWER PHASE (1 0 OR 30)
O THERMOSTAT
PN
PROJECT NORTH (REFERENCE)
POC
POINT OF CONNECTION
PRESS
PRESSURE
COMMISSIONING
PSI
POUNDS PER SQUARE INCH
RA
RETURN AIR OR RELIEF AIR
MECHANICAL SYSTEMS
RD
ROOF DRAIN
REF
REFERENCE
COPIES OF ALL APPLICABLE SERVICE AND EQUIPMENT DATA, AS WELL AS
RPM
REVOLUTIONS PER MINUTE
PROJECT DOCUMENTATION THAT RELATES, SHALL BE PROVIDED TO THE
RTU
ROOFTOP UNIT
OWNER AND MADE AVAILABLE TO THE AUTHORITY HAVING JURISDICTION (AHJ)
SA
SUPPLY AIR
WITHIN 90 DAYS OF PROJECT COMPLETION AND IN ACCORDANCE WITH 2O15
SEER
SEASONAL ENERGY EFFICIENCY RATIO
WSEC SECTION C408.1, INCLUDING:
SF
SUPPLY FAN OR SQUARE FOOT OR FEET
SMACNA
SHEET METAL NATIONAL ASSOCIATION
1. PRELIMINARY COMMISSIONING REPORT AND OTHER RELATED REPORTS
T
TON (1 TON = 12,000 BTUH)
SUCH AS AIR BALANCING, START-UP AND/OR PRESSURE TESTING DATA.
TN
TRUE NORTH (REFERENCE)
T-STAT
THERMOSTAT
2. RECORD DRAWINGS DEPICTING FINAL INSTALLATION CONFIGURATIONS OF
TYP
TYPICAL
SYSTEMS AND EQUIPMENT.
ULL
ULTRA LOW LEAK DAMPER
UNO
UNLESS NOTED OTHERWISE
3. OPERATION AND MAINTENANCE EQUIPMENT MANUALS INCLUDING:
UPC
UNIFORM PLUMBING CODE
MANUFACTURER'S INFORMATION WITH SPECIFIC MODEL NUMBERS AND
W
WATTS/WIDTH/WINDOW
OPTIONS NOTED, CONTROLS DATA INCLUDING CALIBRATION AND SET
WB
WET BULB
POINT INFORMATION, AND A SIMPLE NARRATIVE DESCRIPTION OF EACH
WSEC
WASHINGTON STATE ENERGY CODE
SYSTEM.
COPYRIGHT 2023
PINEHURST ENGINEERING, PLLC
PROJECT DESCRIPTION
THE PROJECT IS A LIKE -FOR -LIKE, ONE (1) SPLIT SYSTEM HEAT PUMP REPLACEMENT FOR
A RESIDENTIAL SPACE, WITHIN A THREE-STORY ASSISTED LIVING BUILDING. THE BUILDING IS
SITED WITHIN THE CITY OF EDMONDS (JURISDICTION), SNOHOMISH COUNTY, WASHINGTON.
MECHANICAL PERMIT: UNDER APPLICATION
RELATED ELECTRICAL PERMIT: UNDER SEPARATE PERMIT
GENERAL NOTES
1. COORDINATE ALL NEW WORK WITH STRUCTURE AND OTHER TRADES.
2. FIELD VERIFY UNIT LOCATIONS, DROPS AND POSITIONS.
3. ALL LINE VOLTAGE WORK SHALL BE INSTALLED BY AN LICENSED COMMERCIAL ELECTRICIAN.
4. HVAC SYSTEMS HAVE BEEN DESIGNED PER THE REQUIREMENTS OF 2015 WSEC, IBC AND
IMC.
5. ALL RIGGING AND LIFTING TO BE COORDINATED WITH THE BUILDING OWNERSHIP AND ANY
OTHER CITY AND LOCAL JURISDICTIONS.
APPLICABLE CODES
1. 2018 WASHINGTON STATE ENERGY CODE (WAC) CHAPTER 51-11)
2. 2018 INTERNATIONAL BUILDING CODE (WAC CHAPTER 51-50)
3. 2018 INTERNATIONAL MECHANICAL CODE (WAC CHAPTER 51-52)
4. 2018 INTERNATIONAL FUEL GAS CODE (WAC CHAPTER 51-52)
5. 2018 UNIFORM PLUMBING CODE (WAC CHAPTER 51-56)
6. NATIONAL ELECTRICAL CODE (NFPA 70 - WAC CHAPTER 296-46B)
CODE COMPLIANCE NOTES
1. PROGRAMMABLE CONTROLS SHALL BE CAPABLE OF PROVIDING 5 DEGREE DEAD BAND AS
REQUIRED BY 2018 WSEC SECTION C403.2.4.1.2. CONTROLS SHALL ALSO BE CAPABLE OF
PROVIDING SEVEN DAY PROGRAMMABLE TEMPERATURE SETTINGS, AUTOMATIC SETBACK AND
SHUTOFF AND OPTIMUM START AS REQUIRED BY 2018 WSEC SECTION C403.2.4.2
(OFF -HOUR CONTROLS). CONTROLS SHALL BE CONFIGURED TO PREVENT SIMULTANEOUS
HEATING AND COOLING.
2. REPLACEMENT SPLIT SYSTEM AIR CONDITIONERS ARE OF THE SAME TYPE AND OUTPUT
CAPACITY.
3. THIS PROJECT MEETS THE 2018 WSEC MINIMUM EFFICIENCY REQUIREMENTS FOR COOLING
PROVIDED BY ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS PER TABLE
C403.2.3(2)A WITH A SEER OF 12.2, WHICH MATCHES THE MINIMUM REQUIREMENT OF 11.2
SEER FOR EQUIPMENT SIZE CATEGORY <65 MBH (UNITARY AIR CONDITIONERS, SPLIT
SYSTEM).
MECHANICAL SCOPE
THE PROJECT IS FOR THE REPLACEMENT OF ONE (2) EXISTING SPLIT SYSTEM HEAT PUMP HVAC
UNITS. THE EXISTING SYSTEMS HAVE REACHED THE END OF THEIR USEFUL LIFE. THE NEW
SYSTEMS ARE THE SAME TYPE AND SAME NOMINAL OUTPUT CAPACITY:
1. DEMO THE (2) OAC-1 EXISTING ROOFTOP HVAC UNITS & HEAT PUMP SERVING ROOMS 222
& 313.
2. THE REMOVAL AND DISPOSAL OF THE EXISTING UNITS FROM BUILDING SHALL BE IN A
LAWFUL MANNER. RECLAIM EXISTING REFRIGERANT PER EPA STANDARDS; R-22 IS EXISTING
REFRIGERANT PER EQUIPMENT NAME PLATE DATA.
3. PROVIDE AND INSTALL ONE (2) ROOFTOP HP UNITS & (2) FAN COILS IN PLACE OF THE
EXISTING UNITS PER PLAN. NEW EQUIPMENT INCLUDES ELECTRIC DX COOLING, & BASIC
ELECTRO-MECHANICAL CONTROLS.
4. DISCONNECT AND RE -CONNECT REPLACEMENT OAC & IFCU TO EXISTING ELECTRICAL
SERVICES. RE -USE EXISTING ELECTRICAL DISCONNECT WHERE PRACTICABLE. LINE VOLTAGE
WORK SHALL BE BY LICENSED COMMERCIAL ELECTRICIAN (UNDER SEPARATE PERMIT).
5. REUSE EXISTING THERMOSTAT AND CONTROL WIRING.
6. EQUIPMENT AND SYSTEM START-UP, TEST AND BALANCE, PROGRAMMING AND OWNER
TRAINING FOR NEW EQUIPMENT, 0&M MANUALS AND RECORD DRAWINGS.
7. THERE IS AN EXISTING ±48" HIGH PERIMETER PARAPET WALL SURROUNDING ALL OF THE
MECHANICAL EQUIPMENT ON THE ROOF. NO SCREENING IS NECESSARY.
City Of Edmonds
Building Department
Work HEAT PUMP SPLIT SYSTEM IN RM 222 & 313
-----------------
Address 750 EDMONDS WAY
................................. ..........'--'--'--'--'--'--'--'-
Owner SUNRISE OF EDMONDS
Approved Date 08/21 /2023
Building Official Erg
Permit Number BLD2023-1018
- ay Fir. � �7# i••, -- � �'�;
.� • sr Z,• +t i
f 1
;
PROJECT LOCATION - (2) ROOFTOP UNITS TO BE REPLACED --J
BUILDING INFORMATION
PROJECT ADDRESS: SUNRISE OF EDMONDS
750 EDMONDS WAY, EDMONDS, WA. 98020-5126
SITE CONTACT: RICHARD (425) 673-9700
PROPERTY OWNER: HCP SUN1 EDMONDS WA LLC., 2235 FARADAY AVE,
SUITE #0, CARLSBAD, CA. 92009
TAX PARCEL NUMBER: 27032500306200
CONSTRUCTION TYPES: 11 - 1 HR FULLY SPRINKLERED
PRIMARY OCCUPANCIES: CONVALESCENT CENTER APPROVED BY PLANNING
ORIGINAL CONSTRUCT: 2004
�0-
TOTAL BUILDING AREA: 60,052 SF Aug 28 2023
CLIMATE ZONE: 4C-SNOHOMISH
THIS ASSISTED LIVING RESIDENTIAL PROPERTY HAS A SINGLE INSTUTUTIONAL RELATED
OCCUPANCY AND BUILDING IDENTIFICATION ASSOCIATED WITH IT. ADDITIONAL PROPERTY
AND BUILDING DATA CAN BE FOUND FROM THE CITY OF EDMONDS AND SNOHOMISH
COUNTY ASSESSORS MAPS.
DRAWING INDEX
PAGE #
SHEET #
SHEET TITLE
SCALE
1
MO.1
COVER SHEET, LEGEND AND NOTES
N/A
2
M0.2
EQUIPMENT SCHEDULES & DATA
N/A
3
M0.3
EQUIPMENT DATA
N/A
F4
M 1.1
ROOF PLAN - MECHANICAL
1 /8" = 1'-0"
VICINITY MAP (BY GOOGLE MAPS, NOT TO SCALE) /- PROJECT LOCATION - 750 EDMONDS WAY, EDMONDS
I71r
. f f r.
•' F
FC
ir
,s � r •r T
�+AtrT-
ir
APrNo
'
NORTH
SITE MAP (BY GOOGLE MAPS, NOT TO SCALE)
•' s. r 'w
1..� •1` �.. ti s� ��. 1
F77"%,
NORTH
LEGAL DESCRIPTION
SEC 25 TWP 27 RGE 03 TH PTN SW1/4
SE1 /4 SW1 /4 DAF: BEG SW COR SD SUBJH
NO1*00 36E ALG W LN 60.6FT TH N60*11
41 E 358.30 FT TO SWLY MGN OF SR-104
(EDMONDS WAY) AS CONVD PER DEED REC
AF2180193; THS39*05 51 E PLW & 40FT SWLY
C/L SR-104 ALG SWLY MGN AS CONVD TO ST
OF WA BY DEEDS REC AFN'S 2180193,
2181901 & 2185476 DIST OF 201.69FT TAP
OPST HWY ENGR STA 97+85; TH S01 *05 34W
ALG SD MGN DIST OF46.49FT TAP 30FT NWLY
& OPST HES 0-70; TH N88*29 44W DIST OF
382.17FT TO POB; PER CITY OF EDM
LL-2000-134 REC AFN200303175004
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
APPROVED
PLANS MUST B
ON JOB SITE 8' 16'
SCALE: 1/8" = 1'-0"
F
w
�
C
L
m
Cn 00
ZI F
IZI-
00
Q z
O N
O
QZrn
C
0-
�N
� = M
00
0 C
..
°O
w Q
w
4J
C)OW
U) C
Z
=w
�C
LL
0 ~
:z
Q L
Sin
o
r+ 0
13>m _
vN z
OQNER"T���M'9�
•.. � �FWASry/n;
4559 6
Fcls-R ..• ''
AL ENG�O6-2 3
°oa❑❑❑o�° 8-
EXPIRES: 10/25/24
RECEIVED
Aug 11 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SHEET NO.
M001
COVER SHEET
LEGEND AND
NOTES
PROJECT NO. 020-078B
8/6/23
OHP
222
OHP
313
FCU
222
FCU
313
OUTDOOR HEAT PUMP
EQUIP NO.
SERVICE
CONNECTED
INDOOR
UNIT
NOMINAL
CAPACITY,
TONS
TOTAL COOLING
CAPACITY,
BTUH
SEER
I
ELECTRICAL DATA
SOUND
POWER,
DBA
WEIGHT,
LBS
BASIS OF DESIGN
1(1) (2) (3) (4)
VOLTAGE
MOCP
OHP-222
RM 222
FCU-222
1 1.5
18,000
15
230V/1 P
20
71
140
CARRIER 25SCA518AO03
OHP-313
IRM 313
FCU-313
1.5
18,000
15
230V/1 P
20
71
140
CARRIER 25SCA518AO03
(1) ARI LISTED WITH STANDARD FEATURES, INSTALLATION ACCESSORIES AND COMPRESSOR SHORT CYCLING
PROTECTION, FILTER DRIER, REFRIGERANT LINE FILTER, LIQUID SOLENOID VALVE AND SAFETY PRESSURE SWITCHES.
INSTALL REFRIGERANT TUBING AND LENGTH IN STRICT ACCORDANCE WITH MANUFACTURERES RECCOMENDATIONS.
(2) WITH FACTORY OPTION DISCONNECT.
(3) PROVIDE ALL REQUIRED ACCESSORIES FOR LONG -LINE AND LOW -AMBIENT APPLICATIONS.
(4) ROUTING OF REFRIGERANT LINES FROM INDOOR TO OUTDOOR UNITS NOT SHOWN ON PLANS. CONTRACTOR TO
FIELD COORDINATE ROUTING.
HEAT PUMP COIL (1)
EQUIP NO.
SERVICE
COIL
CONFIGURATION
SUPPLY FAN
COOLING
CAPACITY,
TONS
AUX ELEC
HEAT
KW (@ 230 V)
ELECTRICAL DATA
WEIGHT,
LBS
BASIS OF DESIGN
AIRFLOW,
CFM
ESP,
IN WC
MIN OSA
(CFM)
MOTOR
HP
VOLTAGE
MOCP
FCU-222
RM 222
VERTICAL
600
0.5
75
1/3
1.5
2.3
208V/1P
20
120
CARRIER FJ4DNXA18L00
FCU-313
RM 313
VERTICAL
600
0.5
75
1/3
1.5
2.3
208V/1P
20
120
CARRIER FJ4DNXA18L00
NOTES: (1) PROVIDE CONDENSATE DRAIN TO NEAREST APPROVED RECEPTOR. PROVIDE CONDENSATE PUMP IF REQUIRED.
Unit Report For 1.5T SS HP-SEER2
'roject: Sunrise Edmonds-1.5T SS HP 05/15/202:
'repared By:
Performance Summary For 1.5T SS HP-SEER2
'roject: Sunrise Edmonds-1.5T SS HP 05/15/202,
'repared By:
System Performance
System:
25SC:A/FJ4D
Actual Clg Airflow:
600.0
CFM
System Quantity:
1
Standard Clg Airflow:
600.0
CFM
_
Altitude:
0.0 ft
Total Net Clg Capacity:
17.20
MBH
i .
Linear Pipe Length:
0.0 ft
Net Sensible Clg Capacity:
13.10
MBH
COP @ 47 F:
3.56
Htg HP Capacity:
17.50
MBH
COP @ 17 F:
2.42
Htg HP Integrated Capacity:
17.50
MBH
j
SEER2 @ ARI Conditions:
14.3
Total System Power:
1.44
kW
EER2 @ ARI Conditions:
12.0
HSPF2 @ ARI Conditions:
7.5
System Parameters
Outdoor Unit Parameters
Indoor Coil Parameters
Unit Model: 25SCA
Unit Model: FJ4D
Outdoor Unit Parameters
Indoor Coil Parameters
Unit Size: 1.5 Tons (Size 18)
Unit Size: 18,000 Btuh (Size 18)
Unit Model:
25SCA518A003
Unit Model:
FJ4DNXA18L00
Voltage: 208/230-1-60 V-Ph-Hz
Cabinet Width: TXV/ 14 Inches Cabinet
Unit Size (Nominal):
1.5 Tons (Size 18)
Unit Size (Nominal):
18,000 Btuh (Size 18)
Voltage: 208-1-60
V-Ph-Hz
Voltage:
208/230-1-60 V-Ph-Hz
Voltage:
208-1-60
V-Ph-Hz
Heating Size: No Heat
Clg Ent Air DB Ambient:
95.0 °F
Ent Air DB:
80.00
°F
Htg Ent Air DB Ambient:
47.0 °F
Ent Air WB:
67.00
°F
Outdoor Unit Dimensions and Weight
Indoor Coil Dimensions and Weight
Ent Enthalpy:
31.44
BTU/lb
Unit Length: 31.1875 in
Unit Length: 22.0625
in
Lvg Air DB:
59.78
°F
Unit Width: 31.1875 in
Unit Width: 14.3125
in
Lvg Air WB:
58.06
°F
Unit Height: 28.6875 in
Unit Height: 42.6875
in
Lvg Enthalpy:
25.07
BTU/lb
Unit Shipping Weight: 170. lb
Unit Shipping Weight: 120.
lb
Htg Ent Air DB:
70.0
°F
Htg Lvg Air DB:
97.0
°F
RESIDENTIAL APPLICATIONS
Heating Size (Nominal):
No Heat
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions
and
Total External Static Pressure: 0.50
in wg
below. The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.
Limited Warrant Years
Item
Original Owner
Subsequent Owner
Parts
10* or 5
5
Compressor
10* (or 5)
5
'If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that
prohibit warranty benefits conditioned on registration). See Warranty Conditions below.
OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is
not available for subsequent owners.
Ordering Information
Part Number
Description
Quantity
Outdoor Unit
25SCA518AO03
25SCA Comfort Single Stage Heat Pump with Puron Refrigerant 1.5
Tons Cooling
1
15 SEER @ ARI Conditions
Accessories
KAACH1701AAA
Crankcase Heater for Outdoor Unit
1
KSAFT0101AAA
Evaporator Freeze Thermostat for Outdoor Unit
1
Indoor Coil
FJ4DNXA181-00
FJ41D Base Series Fan Coil with Puron 18000 BTU Cooling 208/230-1-
60
1
TXV/ 14 Inches Cabinet
Aluminum
Accessories
Residential Carrier Products Bldr 1.37
rdye '3 u1 I I
Electrical Data
Outdoor Electrical Data
Indoor Electrical Data
Unit Voltage:
208/230-1-60
V-Ph-Hz
Unit Voltage:
208-1-60
V-Ph-Hz
Fan Motor FLA:
0.50
Amps
Motor HP:
1/3
HP
MCA:
13.4
Amps
Motor FLA:
2.9
Amps
Max Fuse:
20
Amps
Operating Range Min:
197
V
Accessory Electric Heater Data
Operating Range Max:
253
V
EH Part Number: KFFEH8401NO3
Compressor RLA:
10.3
Amps
Electric Heater kW:
2.3
kW
Compressor LRA:
45.7
Amps
For 2 wire operation (single circuit):
Heater Amps:
10.7
Amps
Heater + Motor MCA:
17
Amps
Heater + Motor MOCP:
20
Amps
Accessory Voltage:
208-1-60
V-Ph-Hz
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product
literature and the AHRRI directory at www.ahridirectory.org for the most up-to-date information.
Residential Carrier Products Bldr 1.37
UNIT DATA
r oyc J VI I I
GENERAL NOTES
1. DRAWINGS FOR MECHANICAL WORK WITHIN THE
EXISTING BUILDING SPACE AND ROOFTOP ARE
DIAGRAMMATIC AND INTENDED TO CONVEY SCOPE
AND GENERAL ARRANGEMENT ONLY. THE ACCURACY
AND COMPLETENESS OF THE DESIGN CONTENT
REQUIRES FIELD VERIFICATION FOR ALL LOCATIONS
AND DIMENSIONS PRIOR TO START OF MECHANICAL
WORK.
2. MECHANICAL SCOPE OF WORK BOUNDED BY
BUILDING EXTERIOR WALLS AND ROOF, UNLESS
NOTED OTHERWISE. ALL WORK SHALL BE PARALLEL
AND PERPENDICULAR TO BUILDING COLUMN LINES.
3. THE NEW SPLIT SYSTEMS ARE REPLACING THE SAME
TYPE AND CAPACITY SPLIT SYSTEMS IN THE SAME
LOCATIONS, UTILIZING EXISTING POWER SUPPLY AND
DUCTWORK.
4. NEW OUTDOOR HEAT PUMPS ARE SAME WEIGHT AS
EXISTING.
Acoustic Summary For 1.5T SS HP-SEER2
'roject: Sunrise Edmonds-1.5T SS HP 05/15/202,
3repared By:
Outdoor Unit Parameters:
Unit Model:
Unit Size:
Variations:
25SCA
1.5 Tons (Size 18)
Standard
Octave Band Center Frequency, Hz
125
250
500
1 k
2k
4k
8k
dBA
Sound Power,dB
70.2
66.4
65.1
67.4
62.8
58.2
52.5
A -Weighted Sound Power, dBA
71.0
Indoor Coil Parameters:
Unit Model:
Unit Size:
Cabinet Width:
FJ4D
18,000 Btuh (Size 18)
TXV/ 14 Inches Cabinet
Octave Band Center Frequency, Hz 63 1 125 1 250 1 500 1 1 k I 2k 1 4k
Sound Power,dB 1 70.8 1 66.8 1 62.8 1 59.8 1 57.8 1 55.8 1 51.8
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product
literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.
Residential Carrier Products Bldr 1.37
r oyc v vi I I
y
A •. QFC45976 FO .•' ��
��,osoalloaoNo���B- 6 23
EXPIRES: 10/25/24
RECEIVED
Aug 11 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
MOm2
EQUIPMENT
SCHEDULES &
DATA SHEETS
PROJECT NO. 020-078B
COPYRIGHT 2023
PINEHURST ENGINEERING, PLLC
0 4' 8' 16'
I
SCALE: 1/8" = V-0"
8/6/23
Certified Drawing For 1.5T SS HP-SEER2;
Project: Sunrise Edmonds-1.5T SS HP 05/15/2023
Prepared By:
Outdoor Model
Unit Model:
Unit Size:
Voltage:
SEER:
PartNumber:
A
AIR DISCHARGE
FIELD POWERCONN.
Y!B"ftt.2I ROSE rII
.,I
AIR IN-
1H
118"1�28.6F KNOCKOUT
FIELD CONTROL S PPLt CONK.
O TIS't 22.2) HOLE
.5)
0318.109Lj
K
LIOUIO LINE CONN.
3
191,0) IBT.9t
I H
-
F•- Y so --'� "jT
OC,APOR LINE CDNN.I
1 131tfi• i�
116.1) 11 / j" G
j-
NOTES:
X SO. t
1, ALLOW 24' I609.6) CLEARANCE TO SERVICE
SIDE OF UNIT, 4V (1218.2)ABOVE UNIT. 2 CENTER OF GRAVITY 2 1311i
6" (162.4)ON ONE SIDE, 12" (364.8) ON REMAINING SDI, AND 24" (609.6) BETWEEN 1 T1. I1
UNITS FOR PROPER AIRFLOW.
1 SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER
25SCA
1.5 Tons (Size 18)
208/230-1-60 V-Ph-Hz
15
25SCA518AO03
Shipping Dimensions and Weights
Outdoor Unit
Height
33.94 in
Width
34.25 in
Length
34.25 in
Operating Weight
140.lb
Shipping Weight
i170. Ib
Dimensions
A
B
C
D
E
F
G
H
I
J
K
31.19 in
28.69 in
0.63 in
6.56 in
24.70 in
9.13 ini
1.13 ini
3.81 in
14.75 in
16.25 in
13.50 in
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at
***.ahridirectory.org for the most up-to-date information.
Residential Carrier Products Bldr 1.37
Page 7 of 11
Certified Drawing For 1.5T SS HP-SEER2.
Project: Sunrise Edmonds-1.5T SS HP 05/15/2023
Prepared By:
NOTES:
I, CONDENSATE PAN DRAIN CAN NOT SHOWN FOR CLARITY,
2. ALL DIMENSIONS ARE IN 'INCHES" UNLESS NOTED.
112'
TYP.►
i18"
TYP./
Indoor Coil
Unit Model:
Unit Size:
Voltage:
PartNumber:
PRIMARY ORA
SECONDARY DRAIN-
HORIZ, LEFT
(AS SHIPPED)
PRIMARY DRAI
SECONDARY DRAI
113116'
TYP. t
1 114'
1511 r"
TrP.11 -
1518'
2 718' 2 9YIS"
TYP,
(2 PLACES)►
FJ4D
18,000 Btuh (Size 18)
208-1-60 V-Ph-Hz
FJ4DNXA18L00
SLOPE COIL
1116' TYP.
'IIFL: 12 PLACES))
I' TYP.
l2 PLACES)i
AIRFLOW + 1116" iYP.
PLACES)+
PRIMARY DRAI
SECONDARY DRAIN
5116,
TYP.1
SECONDARY DRAI
® PRIMARY DRAINJ'
�2 118" El'
1, I
� 1116' TYP.
IN"II L 2 9116" l2 PLACES)' r U PLACESII 113116' -
i 114 TYP.1
UPFLOW DOWNFLOW
(AS SHIPPED) (FIELD CONVERTED)
1
!
2'IV
1114" TYP.2) 118'
F TYP.1
HORIZ. RIGHT
(FIELD CONVERTED)
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at
***.ahridirectory.org for the most up-to-date information.
Residential Carrier Products Bldr 1.37
Page 9 of 11
Certified Drawing For 1.5T SS HP-SEER2;
Project: Sunrise Edmonds-1.5T SS HP 05/15/2023
Prepared By:
UNIT CONNECTION SIZES
SUCTION: 118 6 111 - 5/8' I.D. SWEAT
030 6 036 - 3/�' I.D. 5.EAT
042 THRU 060 - 718" I.D. SWEAT
LIQUID: 3/8' I.D. SWEAT
CONDENSATE: 3/4' FPT
8
5/t6" C
-DISCONNECT OR
CIRCUIT BREAKER
-
LOCATION
LOWER, CONTROL,
6 ELECTRIC HEATER
ACCESS PANEL
PANELACCESS
2 5l8'
INEL- IDUID LINE CONNECTION
PANEL
SUCTION LINE CONNECTION
0
10
6 3f16"
FILTER ACCESS
OPENING PANEL
D
INLET AIR
FRONT VIEW
SHOWN WITH "A' COIL DETAILS CONNECTION
LOCATIONS FOR UPFLOW OR HORI2. AP LIC A T T:•.t
Indoor Coil
I F NOTE:
1. SERIES DESIGNATION IS THE 14TH POSITION
OF UNIT PRODUCT NUMBER
I. ALL DIMENSIONS ARE IN "INCHES' UNLESS NOTED.
2118--
2' DIA. K.O.'S
FOR RICH VOLTAGE
POWER WIRING
T/8"DIA. N.O.
1 718" FOR LOW VOLTAGE
CONTROL WIRING
ALTERNATE
7!8'DIA. N.O.
TOP VIEW
1 15/16' FOR LOw VOLTAGE
1 3l8' CONTROL WIRING
INLET AIR A
Unit Model: FJ4D
Unit Size: 18,000 Btuh (Size 18)
Voltage: 208-1-60 V-Ph-Hz
Cabinet Insulation: TXV/ 14 Inches Cabinet
PartNumber: FJ4DNXA18L00
SLOPE COIL DETAILS
CONNECTION LOCATIONS SHOWN
FON UPFLOW ON HONII.
LEFT APPLICATIONS
ACCESS PANEL CONFIG, FOR
SLOPE COILS
DOWNFLOW OR NORIZ.
RIGHT APPLICATIONS
AND
"A" COILS
DOWNFLOW APPLICATIONS
tau
iiHAY
NOTE: ALLOW Zt' FROM FRONT
FOR SERVICE
22 t116'
D 3116"
1' OUTLET AIR r 31 4"
--ALTERNATE
7/81,1 3E132".2'DIA. K.O.'S NOTE: MODULAR
FOR HIGH VOLTAGE UNITS WILL HAVE
POWER WIRING A TWO-PIECE
OPPOSITE SIDE CABINET
OPTIONAL FIELD CONVERTED
RIGHT SIDE RETURN OPENING
(SLOPE COIL UNITS OPEN)
t tJ2'
I•
� I
� i
I FOR
t9' I NODJLAR UNITS
L - - - - -
OPENING
19 13/16" 2 10'
RIGHT SIDE VIEW
INLET AIR
Dimensions and Weights
Indoor Coil
Height
42.69 in
Width
14.31 in
Length
22.06 in
Shipping Weight
120. lb
Dimensions
A
B
C
D
E
F
G
H
J
42.69 ini
14.31 ini
12.44 in
1 12.31 in
1
18.13 in
1 18.63 in
I --1
12.00 in
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at
***.ahridirectory.org for the most up-to-date information.
Residential Carrier Products Bldr 1.37 Page 8 of 11
25SCA5
Comfort" Series Single -Stage Air Conditioner i
with Fulron( Refrigerant
1-1/2 To 5 Tons Turn to the experts
11
Product Data
�1ll,I,I.,I,�l9RI1I��I�1���
lijjII[)�-IIyI lll4ji I�:i14F�1�1�1� II
UI
anti ���llf �{� I' Illilja�ll lillllll�'N
y � R!I 'I�l9�lUlllll�
01
This Trait has been desipned utilizing Carrier's non-ozme depleting
Ptron$ refrigerant Heat pumps with Pull refrigerant provide a
coliecticu of features unmatched by any other family of equupmenr.
NOTE: Ratings contained in this document are subject to change at any
time. Always refer to the AHM directory (vmr r.ahridirecto--y-org) 6or
the most up--to-date ratings Labormation
Industry leading
Features r Benefits
Efficiency
14-3-1S2SEER" r 11.0-12.5EER217.5-9.1HSPF2
(depending on unit sine and indoor combination installed)
Micratube tecUnology refrigeration system
• Indoor air quality accessories mmilable
Sound
Sound levels as low as 69 dBA with accessory sound blanket
Comfort
System supports proer7a71 m ble or suaudard thermostat controls
Reliability
• Non -ozone depleting PuromM refrigerant
Scroll compressor
Internal pressure relief valve
• Internal thermal overload
• Loss of charge switch
Filter drier
Balanced refrigeration system for Tylaslilum relic-baity
Durability
WeatherA> lil Protection Package:
Satid, durable sheet metal consmicaon
• Dense nire coil guard
Applications
Lang -line - up to 250 feet (76.20 m) tote[ equivalent Ll up to 200
feet (60.96 m) condenser above evaporator, or up to 80 ft- (24.38 m)
evaporator above condenser (See LrnnghnA Guide for mare
information-)
Lear ambient tooling (dawn to O■F,1-17.8'C) with approved Low
ambient accessory kits
Residential Carrier Products Bldr 1.37 Page 10 of 11
UNIT DATA
SUE3JE'IT TO CHANGE WITHOUT NOTICE
o
C
F
LLJ
C
L
U) CD
M
J
C!D 00
M
CV F
"T
Q 2!=
C
�O
C/�
0 cV
C
Z 0
c�
G
O L
Lo
00
w Q oO
U
UJ CJ
.
LJJ
CV
J -
Cn C
;E:i
p�
W
LLJ
U
`
IL�~
3
O m
a�
Lo00
p>
o
Lo
Z
7 [1? � Wn� •9�
A •. % 45976 FO .•' ��
• ISTER•.. �. O
��Opss�ONAL ENGp _ 6 23
ooc7oc P 8
EXPIRES: 10/25/24
STANDARD FEATURES
■ Multi -tap ECM (electronic commutating motor) motors - all sizes
■ Integrated motor controls, with 90-sec off TDIR function,
have replaced integrated circuit board
• Five available speed tags to meet a wide range of applications
■ Large, grooved tube, louvered fin coils O
N Efficient, quiet, time -tested bknvrer housings and diffusers ^ 1
• Sturdy, drainable condensate pans
�. ■ Cabinet construction features innovations designed to prevent
cabinet sweating
- Tested for condensate disposal in much tougher conditions than W
Air Conditioning and Refrigeration Institute requirements
■ Super -thick R-4.2 insulation with vapor barrier
• Pre -painted galvanized steel cabinet (taupe metallic) W
■ Cabinet air leakage of less than 2% at 0-5 in.W .C. and cabinet air O
leakage less than 1.4% at 0.5 in- W.C. whlen tested in accordance
with ASHiRAE 193 standard -
Instal lation-flexible, multipoise units
■ Horizontal hanging provisions on cabinet W
■ No tools required to access fitter
• Newly improved fitter rack area filter door insulation W W V 1
added for improved air seal r vul O
ro11
1 'M MWNI I■dWOn ■
,K,,,�ei■r„ Factory -installed heater packages available on select
�YN models (5-through 15 kW) 1
dva■M�"hd4m.I 3- through 30-kW accessory heaters - field installed v
� or�DNy
- Factory -supplied power plug T 1 ^ O
■ Easy plug-in provisions for heater installation H
• Entry options for high and low voltage wiring hook-up
J - Leak -preventing sweat connections O N••j
U ' Thermostatic expansion valve, TXV, on sill sizes
.juLdir. O
■ Designed for manufactured housing applications
- LIMITED WARRANTY* P.0
ArmorT13C 10 year parts to original purchaser upon timely registration, !�I
otherwise 5 years
'For resklentlal appfle0ons. see warrdrrty for tuE detalls. ISSUE:
Trrs doct mrr~ aws) not mnlain techrl= data cortrulled by tlNe EAR or )TAR.
Residential Carrier Products Bldr 1.37 Page 11 of 11
RECEIVED
Aug 11 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
MOm3
EQUIPMENT
DATA SHEETS
PROJECT NO. 020-078B
COPYRIGHT 2023
PINEHURST ENGINEERING, PLLC
0 4' 8' 16'
I
SCALE: 1/8" = V-0"
8/6/23
a
COPYRIGHT 2023
PINEHURST ENGINEERING, PLLC
TN�ROOF PLAN -MECHANICAL
SCALE: 1/8" = 1'-0° / / _Zsy
GENERAL NOTES
1. DRAWINGS FOR MECHANICAL WORK WITHIN THE
EXISTING BUILDING SPACE AND ROOFTOP ARE
DIAGRAMMATIC AND INTENDED TO CONVEY
SCOPE AND GENERAL ARRANGEMENT ONLY.
THE ACCURACY AND COMPLETENESS OF THE
DESIGN CONTENT REQUIRES FIELD
VERIFICATION FOR ALL LOCATIONS AND
DIMENSIONS PRIOR TO START OF MECHANICAL
WORK.
2. MECHANICAL SCOPE OF WORK BOUNDED BY
BUILDING EXTERIOR WALLS AND ROOF, UNLESS
NOTED OTHERWISE. ALL WORK SHALL BE
PARALLEL AND PERPENDICULAR TO BUILDING
COLUMN LINES.
3. THE NEW SPLIT SYSTEM UNITS ARE REPLACING
THE SAME TYPE AND CAPACITY SPLIT SYSTEM
IN THE SAME LOCATION, UTILIZING EXISTING
DUCTWORK AND POWER SUPPLY.
PLAN NOTES
01 STAGING OF EQUIPMENT AND CRANE
LOCATIONS TO BE COORDINATED AND
APPROVED PRIOR TO CONSTRUCTION.
O2 NEW UNIT SHALL BE INSTALLED IN SAME
LOCATION AS EXISTING
O3 EXISTING ROOFTOP HVAC EQUIPMENT NOT IN
SCOPE OF WORK (EXISTING TO REMAIN).
® NEW OHP-222 & OHP-313 REPLACEMENT
1.5-TON UNITS ARE THE SAME TYPE, WEIGHT
AND OUTPUT CAPACITY AS EXISTING. NO NEW
ROOF PENETRATIONS ARE REQUIRED FOR THIS
WORK. RE -USE THE EXISTING ELECTRICAL
DISCONNECT SWITCHES AS APPLICABLE.
RE -USE EXISTING CONTROL WIRING.
0 4' 8' 16'
SCALE: 1/8" = 1'-0"