REVIEWED BLD2023-0054+Manufacturer_Specifications_and_Installation_Instructions+1.12.2023_7.05.09_PM+3312982DnUBLF WALL FACTORY BUILT DUCTWORK - ALL DUCTWORK IS REQUIRED TO BE INSTALLED WITH THE MAXIMUM SUPPORT SPACING LISTED BELOW. - FOR A COMPLETE LIST OF APPROVED SUPPORT METHODS, SEE THE ENTIRE INSTALLATION AND OPERATION MANUAL - DUCTWORK SHALL SLOPE NOT LESS THAN 1/16' PER LINEAR FOOT TOWARDS THE HOOD OR AN APPROVED GREASE COLLECTION RESERVOIR. - WHERE HORIZONTAL DUCTS EXCEED 75 FEET IN LENGTH, THE SLOPE SHALL NOT BE LESS THAN 3/16' PER LINEAR FOOT. HORIZONTAL DUCT DIAMETER SUPPORT SPACING (FT) 5' 7' 6' 7' 7' 7' 8' 7' 10, 7' 12, 7' 14' 7' 16' 7' 18, 5' 20' 5' 22, 5' 24' 5' 26' 5' 28' 5' 30' 5' 32' 5' 34' 5' 36, S' VERTICAL TYPE WALL SUPPORT (FT> CURB SUPPORT (FT) FLOOR SUPPORT (FT) 2R & 2R HT (5'-16') 20, 24' 24' 2R (18') Is, 24' 24' & 3Z (5'-24') 1 10' 24' 24' 3Z C26' -36') 10' 20' 20' D❑ NOT LEAK TEST USING SMOKE BOMBS C❑NTAINING CHL❑RINES/CHL❑RIDES. CONSULT WITH CAPTIVEAIRE FOR PROPER LEAK TESTING METHODS, DUCTWORK #1 FRONT VIEW JOB Johnny Mo's Pizza - Edmonds WA LOCATION Edmonds, WA, 98020 O�DATE 10/25/2022-TOB 570 i��- wir DWG 1 6 DRAWN BY JDC DUCTWORK #1 SIDE VIEWDUCTWORK #1 TOP VIEW f� 21.50' 39.05' I P18 I I 18 I P4 P3 P5 P7I.P9 P17 P17 =39'01'-" DUCTWORK #1 SE VIEW 130'MAX 129'MAX 103.5' 102.5' 90.5'MIN 89.5'MIN 191,5'MAX 139.5' 114.5'MIN P15 P4 P3 P5 L P7 ,1.5'MAX 39.0 ' 36' 24'MIN P2 PI 12 228' 22.51' 16.51' 16.51' 90.35' 1'iA131717X.9RIZILNX 419[onII1I411090JE 191.5'MAX 139,5' 114.5'MIN 129'MAX 102.5' 89.5'MIN 1 P16 P15 P12 EM P4 P3 61.5'MAX 61.5'MAX 61.5'MAX P5 36' 36' 36' P13 24'MIN 24'MIN P2 24'MIN P2 P14 P1 IF ORDERED, CAS SERVICE WILL PERFORM A SYSTEM DESIGN VERIFICATION (SDV) ONCE ALL EQUIPMENT HAS HAD A COMPLETE START UP PER THE OPERATION AND INSTALLATION MANUAL, TYPICALLY, THE SDV WILL BE PERFORMED AFTER ALL INSPECTIONS ARE COMPLETE. ANY FIELD RELATED DISCREPANCIES THAT ARE DISCOVERED DURING THE SDV WILL BE BROUGHT TO THE ATTENTION OF THE GENERAL CONTRACTOR AND CORRESPONDING TRADES ON SITE. THESE ISSUES WILL BE DOCUMENTED AND FORWARDED TO THE APPROPRIATE SALES OFFICE. IF CAS SERVICE HAS TO RESOLVE A DISCREPANCY THAT IS A FIELD ISSUE, THE GENERAL CONTRACTOR WILL BE NOTIFIED AND BILLED FOR THE WORK. SHOULD A RETURN TRIP BE REQUIRED DUE TO ANY FIELD RELATED DISCREPANCY THAT CANNOT BE RESOLVED DURING THE SDV, THERE WILL BE ADDITIONAL TRIP CHARGES. DURING THE SDV, CAS SERVICE WILL ADDRESS ANY DISCREPANCY THAT IS THE FAULT OF THE MANUFACTURER, SHOULD A RETURN TRIP BE REQUIRED, THE GENERAL CONTRACTOR AND APPROPRIATE SALES OFFICE WILL BE NOTIFIED. THERE WILL BE NO ADDITIONAL CHARGES FOR MANUFACTURER DISCREPANCIES, M N 6 0 N t' J N 0 N \ P9 P12 P13 P14 JOB Johnny Mo's Pizza - Edmonds WA LOCATION Edmonds, WA, 98020 DATE 10/25/2022 JOB # 5700745 -ir - DWG A 7 DRAWN BY JDC-85 LOCATION Edmonds, WA, 98020 ��- - =_� DATE 10/25/2022 JOB 5700745 w� DWG d 8 DRAWN BY JDC-85 DUCTWORK 8f PARTS - JOBd5700745 DOUBLE WALL TAG PART # CFM GPM ZONE CDVEREDBY SP WEIGHT VELOCITY QTY DESCRIPTION P1 DW06RISER 0.98 1 SINGLE WALL DUCT RISER FOR WELDED HOODS, 6' DIA DUCT. STAINLESS STEEL, DOUBLE WALL ADJUSTABLE DUCT - 6' INNER DUCT - 2 LAYERS REDUCED CLEARANCE - 10, P2 DWO647DWAJD-LR-S 51.69 1 STAINLESS STEEL OUTER SHELL. MIN LENGTH = 11' / MAX LENGTH = 50.5' / ADJUSTMENT = 32.5' / ADJUSTABLE SECTION MAY NEED TO BE CUT. INCLUDES SINGLE AND DOUBLE WALL 'V' CLAMPS. P3 OW06DWTEASY-2R-S 1 14,74 1 DOUBLE WALL DUCT - 6' INNER TEE DUCT - 2 LAYERS REDUCED CLEARANCE - 10, ASSEMBLED V/P4 STAINLESS STEEL OUTER SHELL. P4 DW06DVACCDOORCOV-2R-S 11.89 1 DOUBLE WALL DUCT - 6' INNER ACCESS DOOR & 10' ACCESS DOOR COVER WITH CLAMPS - 2 ASSEMBLED W/P3 O=S LAYERS REDUCED CLEARANCE - 10' STAINLESS STEEL OUTER SHELL. P5 DW06070WLT-2R-S 4.57 1 DOUBLE WALL DUCT - 6' INNER DUCT, 7' LONG - 2 LAYERS REDUCED CLEARANCE - 10' STAINLESS STEEL OUTER SHELL. P6 DW0608DWRNDADPEC2ASY-2R-S 9.12 1 COULD NOT DRAW, P7 DW08DWTEASY-PR-S 1 21.48 1 DOUBLE WALL DUCT - 8' INNER TEE DUCT - 2 LAYERS REDUCED CLEARANCE - 12' STAINLESS STEEL OUTER SHELL. P8 DW0608DWRNDADPEC2ASY-2R-S 9.12 1 COULD NOT DRAW. P9 DW0607DWLT-2R-S 4.57 1 DOUBLE WALL DUCT - 6' INNER DUCT, 7' LONG - 2 LAYERS REDUCED CLEARANCE - 10' STAINLESS STEEL OUTER SHELL. DUCT - HORIZONTAL SADDLE SUPPORT KIT, USED WITH 10' OD - INCLUDES UNI-STRUT CUT TO P10 DW1014SADKIT 4.58 1 LENGTH, 12 GRADE 5 HEX NUTS, 8 GRADE 5 WASHERS. PARTS PULLED FROM PLANT INVENTORY. DUCT - HORIZONTAL SADDLE SUPPORT KIT, USED WITH 10' OD - INCLUDES UNI-STRUT CUT TO P11 DW1014SADKIT 4.58 1 LENGTH, 12 GRADE 5 HEX NUTS, 8 GRAVE 5 WASHERS. PARTS PULLED FROM PLANT INVENTORY, P12 DWO690DWASY-2R-S 10.42 1 DOUBLE WALL DUCT - 6' INNER 90 DUCT - 2 LAYERS REDUCED CLEARANCE - 10' STAINLESS STEEL OUTER SHELL. DOUBLE WALL ADJUSTABLE DUCT - 6' INNER DUCT - 2 LAYERS REDUCED CLEARANCE - 30' P13 DWO647DWAJD-2R-S 51.69 1 STAINLESS STEEL OUTER SHELL. MIN LENGTH = 11' / MAX LENGTH = 50.5' / ADJUSTMENT = 32.5' / ADJUSTABLE SECTION MAY NEED TO BE CUT. INCLUDES SINGLE AND DOUBLE WALL 'V' CLAMPS. P14 DW06RISER 0.98 1 SINGLE WALL DUCT RISER FOR WELDED HOODS, 6' DIA DUCT. STAINLESS STEEL. P15 DWO823DWLT-2R-S 19.51 1 DOUBLE WALL DUCT - 8' INNER DUCT, 23' LONG - 2 LAYERS REDUCED CLEARANCE - 12' STAINLESS STEEL OUTER SHELL. DOUBLE WALL ADJUSTABLE DUCT - 8' INNER DUCT - 2 LAYERS REDUCED CLEARANCE - 12' P16 OW0847DWAJD-2R-S 63.04 1 STAINLESS STEEL OUTER SHELL. MIN LENGTH = 11' / MAX LENGTH = 50.5' / ADJUSTMENT = 32.5' / ADJUSTABLE SECTION MAY NEED TO BE CUT. INCLUDES SINGLE AND DOUBLE WALL 'V' CLAMPS. P17 OV084550DWLTTP-2R-S 38.44 1 DOUBLE WALL DUCT - 8' INNER DUCT, 45.5' LONG - 2 LAYERS REDUCED CLEARANCE - 12' ASSEMBLED W/P18 STAINLESS STEEL OUTER SHELL - USED WITH TRANSITION PLATE. PIB OW1906TP 6.62 1 DUCT TO CURB TRANSITION, 19-1/2' CURB TO 8' DUCT, 16 GA ALUMINIZED STEEL. MISC. ASSEMBLED W/P37 NON-STANDARD TRANSITION PLATE. FOR USE WITH EXHAUST FAN. 3M-2000PLUS 0.80 3 DUCT - 3M FIRE BARRIER 2000 PLUS SILICONE - USED AS SEALANT TO SEAL DUCT JOINTS. DW06CLASY 0.39 2 DUCT 'V' CLAMP, 6' DUCT WITH NEW DESIGN 14 GA SLOTTED BRACKETS, 2 PIECE, ASSEMBLY. OV06DVCLASY-2R-S 3.87 4 DUCT - 6' DUCT - 10' DOUBLE 'V' CLAMP - 2R INSULATION & SINGLE 'V' CLAMP INCLUDED - REDUCED CLEARANCE. DW08DWCLASY-SR-S 4.93 3 DUCT - 8' DUCT - 12' DOUBLE 'V' CLAMP - 2R INSULATION & SINGLE 'V' CLAMP INCLUDED - REDUCED CLEARANCE. ADDITIONAL PARTS SINGLE WALL DUCT RISER WITH RETAINING RINGS, 8' DUCT, USED ON FIELD INSTALLATIONS. Field Riser DWOBFRISER 3.31 2 INCLUDES 1/4-20 HARDWARE (8) NUTS (8) BOLTS - W SINGLE BOTTOM RING (2) TOP RINGS 2 PIECES PER ASSEMBLY. TOTAL WEIGHT 368.09 JOB Johnny Mo's Pizza - Edmonds WA AM ��� �� LOCAT70N Edmonds, WA, 98020 ���- DATE 10/25/2022 JOB 570 � - -- -- DWG 4 DRAWN BY JDC O SINGLE WALL FACTORY BUILT DUCTWORK - ALL DUCTWORK IS REQUIRED TO BE INSTALLED WITH THE MAXIMUM SUPPORT SPACING LISTED BELOW. - FOR A COMPLETE LIST OF APPROVED SUPPORT METHODS, SEE THE INSTALLATION AND OPERATION MANUAL. - DUCTWORK SHALL SLOPE NOT LESS THAN 1/16' PER LINEAR FOOT TOWARDS THE HOOD OR AN APPROVED GREASE COLLECTION RESERVOIR. - WHERE HORIZONTAL DUCTS EXCEED 75 FEET IN LENGTH, THE SLOPE SHALL NOT BE LESS THAN 3/16' PER LINEAR FOOT. DUCT DIAMETER HORIZONTAL SUPPORT <FT) VERTICAL WALL SUPPORT (FT) VERTICAL CURB SUPPORT (FT) 5' 10, 10, 24' 6' 10, 10, 24' 7' 10, 10, 24' 8' 10, 10, 24' 10, 10, 10, 24' 12, 10, 10' 24' 14' 10' 10, 24' 16' 10, 10' 24' 18, 10, 10, 24' 20' 10, 10, 24' 22' 10, 10, 24' 24' 10, 10, 24' 26' 10, 10, 24' 28' 10, 10, 24' 30, 10, 10' 24' 32' 10, 10' 24' 34' 10, 10, 24' 36' 10, 10, 24' JOB Johnny Mo's Pizza - Edmonds WA n �� a�w �� _ = LOCATION Edmonds, WA, 98020 �luW O� 1 �= DATE 10/25/2022 JOB ¢ 5700745 -- DWG # 5 DRAWN BY JDC-85 FOR QUESTIONS, CALL THE Seattle Office REGION 85 PHONE. (425) 212-5996 EMAIL. reg85BcaptWealre.com FAN UNIT TAG QTY FAN UNIT MODEL # MANUFACTURER CFM ESP RPM MOTOR HP BHP PHASE I VOLT ILA DISCHARGE WEIGHT SONES NO ENCL VELOCITY (LBS) 1 EF 1 CASREI3BD CAPTIVEAIRE 400 0500 993 ODP O500 0.1420 1 115 7.6 417 FPM 247 - FAN UNIT NO TAG OTY DESCRIPTION 1 RE13BD - HIGH TEMPERATURE HEAT & SMOKE OPTION 1 UTILITY SET GREASE CUP 1 EXTRA SET OF BELTS I EF 1 FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS I RE11/13 - RAIN CAP ASSEMBLY - INCLUDES HARDWARE AND GASKET 1 2 YEAR PARTS WARRANTY EXHAUST SUPPLY FAN UNIT NO TAG GREASE GRAVITY WALL SIDE GRAVITY MOTORIZED WALL CUP DAMPER MOUNT DISCHARGE DAMPER DAMPER MOUNT I EF YES NG FAN TAG I EIGHT ITEM SIZE 1 # 1 EF 30 LHS CURB 19.500'W X 19.500'L X 24.000'H ALONG LENGTH, RIGHT VENTED. I= AIN CAP OPTION. 34 3/8' a m m 221 JOBJohnny Mo's Pizza - Edmonds WA __ LOCATION Edmonds, WA, 98020 DATE 10/25/2022 JOB 570 O �I - DWG 0 1 1 DRAWN BY JDC 14 3/4' f0' 13 7/8' ' !4 7/8' 2l' TOP VIEW W13 ' SPRING PIN.19 2' DR4' DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN (BY OTHERS). 19' 19 1/2' 19 1/2' VENTED 1\ CUR& 20 GAUGE STEEL CONSTRUCTION. 3' FLANGE. ` ROOF OPENING 19' DIMENSIONS. 19' PITCHED CURBS ARE AVAILABLE 0' FOR PITCHED ROOFS. 0' SPECIFY PITCH. 12' EXAMPLE. 7/12 PITCH - 30' SLOPE. FEATURES: ROOF MOUNTED FANS. - RESTAURANT MODEL. - UL762 AND ULC-S645. - HIGH HEAT OPERATION BELT DRIVE 500'F (260'0 - HEAT SLINGER. - GREASE CLASSIFICATION TESTING. - TILT OUT WHEEL. - LOCKING PIN FOR POWER PACK. - MOTOR WEATHER COVER. - INTERLOCKED DISCONNECT SWITCH. - NEMA 4X SAFETY DISCONNECT SWITCH. EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 500'1 (260'0 UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE OPERATION. EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING BURNING GREASE VAPORS AT 600'F <3C) 16'FOR A PERIOD OF 15 MINUTES WITHOUT THE FAN BECOMING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE CONDITION. OPTIONS - RE13BD - HIGH TEMPERATURE HEAT & SMOKE OPTION. - 572•F CONTINUOUS. - UTILITY SET GREASE CUP. - EXTRA SET OF BELTS. - FAN BASE CERAMIC SEAL - INSTALLED AT PLANT - FOR GREASE DUCTS. - RE11/13 - RAIN CAP ASSEMBLY - INCLUDES HARDWARE AND GASKET. - 2 YEAR PARTS WARRANTY. juffionnny mo's rizza - Lamonas w(A 0% ��� -� _ n LOCATION Edmonds, WA, 98020 an AvDATE 10/25/2022 JOB 5700745 - O � I W � - DWG # 2 DRAWN BY JDC-85 Rry I arAT.F z/a' = 1-n Exhaust Fan Wiring JOB 5700745 - Johnny Mo's Pizza - Edmonds WA DRAWING NUMBER EXH5700745-1 SHIP DATE 10/25/2022 MODEL CASREI3BD Installed Uotions 1 2 Component Identification 3 �BK--- BK Label Description Location ;WH -__:I n4 WH MT-01 I R 4 SW-01 - MT-01 Fan Motor 131 OGR ---� 5 SW-01 Main disconnect switch 131 6 7 8 9 10 11 12 13 14 15 16 MOTOR INFO EXHAUST 0.5HP-115V-1P-7.6FLA 17 18 ELECTRICAL�NFIIRMATION MOP. MOTOR/CTRJ�L 1. 19 20 NOTES - DENOTES FIELD WIRING 21 DENOTES INTERNAL WIRING 22 WIRE COLOR BK - BLACK YW -YELLOW BL - BLUE GR - GREEN BR - BROWN GY - GRAY 23 OR - ORANGE PR - PURPLE RD - RED PK - PINK WH - WHITE U-1 C) A CD T 4 � '0 LA 441A � '4 O 4d'i yO } C C J N Lfi 4 Y Fk O C7 r L+1 � 36534 �EGI�STE� �10NAL ES U) LU LL - 0 LL - 0 LU Z)r^ W VJ N N O N \ ti N (N r BLD2023-0054 ECEIVED Jan 12 2023 CITY OF EDMONDS )EVELOPMENT SERVICES DEPARTMENT VJJ / O r� V J E N N p > N bi Q J 00 E vJ ^�,, i M I^, W �M '^ V! > > O Lo -0 _ _ � L J LU DATE 12/27/2022 DRAWN 7DB CKED MTW =1f31x0M.I.a CONTRACT DRWG. REF. DRAWING NO. M2.10 OF