REVIEWED -BLD2023-0196+Manufacturer_Specifications_and_Installation_Instructions+2.15.2023_3.26.15_PM+3371818...............................................RECEIVED BY Feb 16 2023 MYORK° CITY of EDMOND$ cLOPM EDMONDS DEVELOPMENT SERVICES e BUILDING DEPARTMENT' DEPARTMENT YORK Tech n ica I Guide: H M H7 Series -17 SEER Horizontal Discharge Modulating Heat Pump BLD2023-0196 R-410A 2 to 5 Nominal Ton .. I im York International Corporation, 5005 York Drive, Norman, OK 73069 2021-03-25 } 6062825-YTG-A-0321 Supersedes: Nothing A Johnson Controls Ducted Systems YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Contents Description...................................................................................................................................................... 5 Certification..................................................................................................................................................... 5 Warrantysummary........................................................................................................................................ 6 Features........................................................................................................................................................... 6 Nomeclature................................................................................................................................................... 7 Physicaland electrical data........................................................................................................................... 8 Dimensions..................................................................................................................................................... 9 Systemcharge................................................................................................................................................ 9 Chargingprocedure.......................................................................................................................... 10 Systemcapacity............................................................................................................................................ 11 Applications and accessories...................................................................................................................... 11 Soundpower ratings................................................................................................................................... 12 Mechanical specifications........................................................................................................................... 12 Manufacture and certifications........................................................................................................ 12 Typicalinstallation............................................................................................................................. 13 Typicalfield wiring............................................................................................................................. 14 Alternative installation clearances.................................................................................................. 15 Performancedata - 2 ton............................................................................................................................ 16 Cooling performance data - 2 ton................................................................................................... 16 Heating performance data - 2 ton.................................................................................................. 16 Performancedata - 3 ton............................................................................................................................ 17 Coolingperformance data - 3 ton................................................................................................... 17 Heating performance data - 3 ton.................................................................................................. 18 Performancedata - 4 ton............................................................................................................................ 18 Coolingperformance data - 4 ton................................................................................................... 18 Heating performance data - 4 ton.................................................................................................. 19 Performancedata - 5 ton............................................................................................................................ 20 Cooling performance data - 5 ton................................................................................................... 20 Heating performance data - 5 ton.................................................................................................. 20 YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump 3 Johnson Controls Ducted Systems YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Description The HMH7 horizontal discharge modulating heat pumps are the outdoor section of a high - efficiency heating and cooling system. The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Each unit is to be matched with one ducted indoor unit and is not designed for application in a ductless configuration. Sweat connect units are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 ft of field -supplied lines. Figure 1: Installation certification map For installation in all US regions and Canada* 'r'k� Installation ally *Not currently certified for installation in localities requiring hurricane certification. Check local codes for specific requirements. Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.simplygettingthejobdone.com and www.york.com . Additional rating information can be found at www.ahridirectory.or Certification The units are tested in accordance with the following: c us usTED Intertek fs *". � O� SS")Rp ISO 9001 Certified Quality Management System YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Warranty summary Extended 10-year limited parts warranty. Extended 10-year limited compressor warranty. Extended parts and compressor warranties require online registration within 90 days of purchase for replacement or closing for new home construction. Warranty does not apply to R-22 models, 3-phase models, or Internet sales. See the Limited Warranty certificate in the User's Information Manual for details. Features • 360 DC inverter driven technology: With 360 all DC inverter driven technology, compressor rotation direction and speed is controlled optimizing energy usage and compressor stability through the spectrum of operating conditions. This guarantees optimal space temperature control while providing quiet operation. • Pressure sensor: This unit contains pressure sensing technology, which detects low pressure in cooling mode and high pressure in heating mode to protect the system from damage. Intelligent control can also be realized by calculating the indoor coil temperature from system suction pressure. • Smaller outdoor form factor for installation flexibility: This side -discharge outdoor unit saves roughly 35% space over traditional air conditioners. It offers the flexibility of wall, yard or roof installation. • Stable temperature control means optimal comfort: The DC inverter is able to provide full capacity at startup to cool/warm quickly and adjusts speed to prevent temperature fluctuation and energy loss. • Agency Listed: Safety certified by CSA to UL 1995/CSA 22.2. Performance certified to ANSI/ AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program. YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Nomeclature Table 1: Horizontal discharge AC and HP Configuration H H = Horizontal discharge Stages 1 1 = 1 stage 2=2stage 3=3stage M = Modulating V = Variable capacity Product type C C = Air conditioner H = Heat pump Efficiency 7 3 = 13 SEER 4 = 14 SEER 5 = 15 SEER 6 = 16 SEER 7 = 17 SEER 8 = 18 SEER 9 = 19 SEER Voltage 2 2 = 208/230-1-60 3 = 208/230-3-60 4 = 460-3-60 Refrigerant B B = R-410A D = R-454B Capacity 24 12 = 1 ton 18 = 1.5 ton 24=2ton 30=2.5ton 36=3ton 42=3.5ton 48=4ton 60=5ton Generation 1 1 = 1 st Generation 2 = 2nd Generation Control strategy S C =Communicating B = Wireless (communicating) S = Standard (conventional) W = Wireless (conventional) Style A A = Style A B = Style B YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Physical and electrical data Table 2: Physical and electrical data Model HMH7262415 HMH72B361S HMH7264815 HMH7213601S Unit supply voltage 208/230 V, 1 phase, 60 Hz 208/230 V, 1 phase, 60 Hz 208/230 V, 1 phase, 60 Hz 208/230 V, 1 phase, 60 Hz Normal voltage range (V) 198 to 253 198 to 253 198 to 253 198 to 253 Minimum circuit ampacity (A) 15 23 36 37 Maximum overcurrent device (A) 25 35 50 50 Minimum overcurrent device (A) 15 23 36 37 Compressor type Twin rotary Twin rotary Twin rotary Twin rotary Compressor rated load (A) 11.0 16.1 26.0 26.5 Compressor locked rotor (A) n/a n/a n/a n/a Crankcase heater (base heater) Yes Yes Yes Yes Factory discharge muffler Yes Yes Yes No HS kit required with TXV N/A N/A N/A N/A Fan motor type ECM ECM ECM ECM Fan motor quantity 1 1 2 2 Fan motor rated HP 1 /12 1 /6 1 /6 1 /6 Fan motor nominal RPM 880 810 850 850 Fan motor nominal CFM 1,825 2,350 3,525 3,525 Coil face area (sq. ft) 6.1 8.3 14.0 14.0 Coil rows deep 2 2 2 2 Coil fins per inch 18 19 17 18 Liquid lineset outdoor (field installed) 3/8 3/8 3/8 3/8 Vapor lineset outdoor (field installed) 5/8 3/4 7/8 7/8 Unit charge (lb-oz) 4-7 6-3 8-15 8-9 Charge (oz/ft) 0.38 0.38 0.60 0.60 Operating weight (lb) 112 157 227 251 O Note: • The normal voltage range is rated in accordance with AHRI Standard 110-2012, utilization range A. • Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection. • Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection. • The unit charge provided is less than the system total charge required. Select the appropriate indoor section and lineset length charge additions to calculate additional charge required and total system charge. • For applications with non-standard vapor line sizes, see Applications and accessories. YORK Technical Guide: HMH7 Series -17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Dimensions Table 3: Dimensions Unit model Dimensions (in.) Refrigerant connections service valve size (in.) A B c Liquid Vapor HMH726241S 263/8 337/8 121/4 3/8 5/8 HMH726361S 33 373/8 133/8 3/4 HMH726481 S 54 5/8 37 3/8 13 3/8 7/8 HMH726601 S 54 5/8 37 3/8 13 3/8 7/8 O Note: • All dimensions are in inches and are subject to change without notice. • Overall length and width include screw heads. Figure 2: Dimensions A1440-001 System charge Table 4: System charge table Outdoor unit HMH7213241S HMH7213361S HMH7213481S HMH7213601S Required TXV BA1 BC1 BC1 BC1 Indoor unit additional charge (oz) AE18B AE24B AE30B - - AE36(C,B) 2 9 AE42C AE43C - - AE48(C,D) AE60(C) - - AE60(D) 7 8 AVC18B AVC24B - - AVC30B - - AVC36(B,C) 2 9 YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Table 4: System charge table Outdoor unit HMH72B241S HMH72B361S HMH72B481S HMH72B601S AVC42C AVC48(C,D) AVC49(C) AVC60(C) - - AVC60(D) 7 8 CF/CM/CU18(A,B) - - CF/CM/CU24(B,C) CF/CM/CU30(A,B,C) - - CF/CM/CU36(B,C,D) 2 9 CF/CM/CU42(B,C,D) - - CF/CM/CU48(C,D) CF/CM/CU60(C,D) - - CF/CM64D 7 8 O Note: • For applications requiring a TXV, use the S1-1TVM*** series kit. • It is necessary to use a TXV kit with these indoor units to obtain system performance. • Systems matched with furnaces or air handlers not equipped with blower -off delays may require blower Time Delay Kit S1-2FD06700224. • It is not possible to use CF and CU coils in horizontal applications. • Charge adders shown above do not indicate that coils are rated for every application. See Physical and electrical data for actual performance for specified system matches. Obtain certified system ratings from www.ahridirectory.org. Charging procedure 1. Check the unit factory charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and 15 ft of interconnecting line tubing. 2. Verify the TXV and additional charge required for the specific matched indoor unit in the system using System charge. 3. Add additional charge for the amount of interconnecting line tubing greater than 15 ft at the rate specified in Physical and electrical data. 4. For indoor matches requiring additional charge, weigh in the refrigerant for the specific matched indoor unit and the actual lineset length. 5. After weighing in the charge adders for the matched indoor unit and lineset, verify the system operation against the temperatures and pressures in the charging chart for the outdoor unit. Locate the charging charts on the outdoor unit and also in the Service Data Application Guide on www.simplygettingtheiobdone.com. Follow the charging procedure in the Installation Manual according to the type of indoor metering device in the system, and allow 10 min after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the charging chart. 6. For downflow installations and horizontal right installations, some indoor units require additional charging adjustments to ensure correct equipment operation. Refer to the Installation Manual for the outdoor unit. 10 YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems 7. Permanently stamp the unit nameplate with the total system charge, which is defined as follows: total system charge = base charge (as shipped) + charge adder for matched indoor unit + charge adder for actual lineset length + charge adjustments to match the charging chart. System capacity Table 5: System capacity - single piece and modular air handlers Unit model Air handler Coil model Rated Cooling Heating Model Width Net MBH SEER EER Net MBH HSPF HSPF region V COP Total Sens. 470F OD 170F OD 470F OD 170F OD HMH7213241S AE36CX21 21.0 850 22.2 17.0 17.50 10.00 22.0 14.7 9.00 7.60 3.36 2.54 HMH7213361S AE36CX21 21.0 1200 36.0 26.5 18.00 10.00 36.8 25.4 10.50 8.75 3.40 2.74 HMH7213481S AE60DX21 24.5 1500 48.0 34.3 18.00 10.50 46.0 32.8 9.50 8.00 3.34 2.72 HMH72B601S AE60DX21 24.5 1700 58.5 20.7 17.00 8.50 56.5 40.0 10.00 8.45 3.24 2.74 Note: • Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI/AHRI Standard 210/240. • Cooling MBH is based on 80°F entering air temperature, 50% RH (relative humidity), and rated airflow. EER (energy efficiency ratio) is the total cooling output in BTUs at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (seasonal energy efficiency ratio) is the total cooling output in Btu during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. • Heating MBH is based on AHRI standards of 70°F DB (dry bulb) entering indoor air, 72% RH (relative humidity) outdoor air with 25 ft of interconnecting piping and no supplemental electric heat operation. HSPF (heating seasonal performance factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. COP (coefficient of performance) equals heating MBH output divided by (total kW input x 3.412). Applications and accessories Table 6: Minimum and maximum operating limit conditions Ambient temperature limits Outdoor coil °F (°C) DB cool DB heat Minimum 35 (2) -5 (-21) Maximum 122 (50) 75 (24) O Note: The maximum lineset equivalent length is 200 ft. The following accessories are compatible with H Series heat pumps: YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump 11 Johnson Controls Ducted Systems H Series - Horizontal Discharge Modulating Heat Pump Compatibility Kit (HMH7AK001): The H Series outdoor section is designed for lower airflow when outdoor terminal S1 is energized and does not function correctly without this kit. TXV Kits (S1-1TVM*): Thermal expansion valves precisely meter refrigerant for optimum performance over a wide range of conditions. See Table 4 for the TXV part number for each model. Sound power ratings Table 7: Sound power - cooling Model Octave band sound power level (dB re. 1 pW) dBA SQI number 63 125 250 500 1000 2000 4000 8000 HMH72B241S 70 70 63 62 61 55 50 43 65 19.1 HMH72B361S 72 71 67 63 64 58 56 50 68 19.1 H M H72B481 S 73 70 67 64 65 60 57 48 69 19.2 HMH72B601S 78 79 71 66 66 62 64 52 73 19.0 Table 8: Sound power - heating Model Octave band sound power level (dB re. 1 pW) dBA SQI number 63 125 250 500 1000 2000 4000 8000 HMH72B241S 70 72 64 62 61 55 50 42 65 19.1 HMH72B361S 68 71 68 65 66 62 60 56 70 19.1 H M H72B481 S 74 72 70 67 67 63 59 53 71 19.2 HMH72B601S 77 77 73 70 68 63 61 52 73 19.0 Mechanical specifications Manufacture and certifications • Units shall be manufactured in an ISO 9001 certified facility. • Units shall be certified by ETL to UL 1995 and performance certified to ANSI/AHRI Standard 210/240. • Units shall be sound tested according to ANSI/AHRI Standard 270. • Certified matched system ratings will be available for downloadfrom the AHRI online directory at www.ahridirectory.org Unit application • Units shall be approved for cooling operation between 35°F and 122°F without modification. • Units shall be approved for linesets up to an equivalent length of 164 ft for HMH72B241 S and 246ftfor HMH72B361S, HMH7213481S, and HMH72B601Swithout modification. • Units shall be approved for installation within 8 in. (long side) and 6 in. (short side) of a flat vertical wall without modification, according to the instructions in the technical literature. • Units shall be designed to 73 dBA or less to minimize sound pollution. Unit access • Units shall be factory leak checked, run tested, and shipped with a holding charge of R-410A refrigerant. • Unit cabinet components shall be G90 equivalent steel finished with powder -coat paint rated at a minimum of 1,000 h under ASTM 13117 testing. 12 YORK Technical Guide: HMH7 Series -17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems • Units shall be constructed with a high pressure switch for system protection. • Units shall be constructed with all badging and labels applied at the factory. Unit components • Compressor shall be hermetic with internal electrical overload protection and internal overpressure protection. • Compressor shall be mounted on neoprene vibration isolators that do not require the removal of transportation clips or brackets. • Outdoor fan shall be direct drive with horizontal air discharge for low sound levels. • Outdoor fan blades shall be swept -wing to minimize sound (applies to select models). • Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors approved for vertical shaft applications. • Outdoor fan motor shall be ECM construction with permanently lubricated ball bearing motors approved for vertical shaft applications. Unit warranties • Unit manufacturer shall provide a 5-year compressor warranty without a requirement for unit registration. Typical installation Figure 3: Minimum clearances when selecting a location 24k/36k: Over 12 in. 300 mm O�,L 48k/60k: Over 24 in. 600 mm Owe 0 Q CAUTION ('350 ��i A1436-661 Caution Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip line due to a partial overhang. YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems 13 Typical field wiring Figure 4: Typical field wiring - HMH7213241S and HMH7213361S USE COPPER SUPPLY WIRES POWER TERMINAL PANEL L1 BRN AC-LIN(CN501) FG(CN901.1) L2 BLU AC-NIN (CN502) Vsp(CN901.2) Vcc(CN901.3) 6YEL/GR EARTH (CN503) GND(CN901.4) +310V(CN901.6) CONNECTION TERMINAL PANEL BLU — RED — WHT — BLK — YEL — FOUR WAY VALVE LOPTIONAL_ _ _ _ _ J Heating Belt 0# L OPTIONAL _ J LHeating L OPTIONAL — J INDUCTOR COMPRESSOR k RED WHT BLU YEL� N X12.4 X12.3 Control Board X12.2 X12.1 CN803 X3 4— WAY (CN507) Heating Belt (CN509) EEV(CN510) Heating (CN508) HPS(X2) L1(CN201) L2(CN202) OVER.H(CN704) U (CN103) V (CN102) W(CN101) ROOM(CN703) COIL(CN702) DISS(CN701) DC FAN MOTOR FG v�� FM GND +310 V EARTH [YEL/GRN -I I (J I OPTIONAL DISPLAY BOARD ELECTRONIC EXPANSION Lvr M VALVE =j HIGH PRESSURE OVERHEAT 7 --�� PROTECTOR OPTIONAL OUTDOOR TEMP. COIL TEMP. DISCHARGE TEMP. 14 YORK Technical Guide: HMH7 Series -17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Figure 5: Typical field wiring - HMH7213481S and HMH72136O1S Power Taninal Panel IPM BOARD iN BL CN12 NIN Lt BRN r InN RN ON11 LIN L2 BLU %NIIN FILTER BOARD ® VTR CN8 ON CN17 CN18 CN16 CN15 CN14 CU5 CV6Cw %t Rrct L1 L2 F 11. rTj= F 2 1AN1 1 a YLW/GRN VLw/GRN t a 1 M IHt BU1 1NgIL1BR 77 M USE COPPER SUPPLY WIRES DC FAN1 MOTOR DC FAN2 MOTOR t OWRESSBR nw/BRN t 1 2 3 1 Connection Terminal panel L2&alja x7 x1 x1a c PTC Power X24 X4 Pressure sensor SV FAN2 FAN1 IPM-SI BLUE B RED X12 SI W K Control Board sl YLW X8 H X3 X6 X5 X16 X15 X19 X17 X20 X18 X23 X11 Base heater HEAT-L HEAT-N H-PRESS L-PRESS HEAT -PRO DISS SUC OUTDOOR COIL DEF VALVE 1 2 4 4 i i i i i i i M _ crankcase high low superheat discharge suction ambient coil defrost base heater heater pressure pressure Protection sensor sensor sensor sensor sensor electronic expansion valve switch switch switch Alternative installation clearances Figure 6: Alternative installation clearances Wall — Fence — Inline installation not allowed A1499-001 YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump 15 Johnson Controls Ducted Systems Performance data - 2 ton Cooling performance data - 2 ton Table 9: Cooling performance data - 2 ton - air temperature (IF) entering outdoor unit Outdoor unit model: HMH7213241S Air ID CFM 600 800 1000 temp (`F) ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 T.C. 22.7 24.1 24.6 26.3 27.5 24.1 25.7 26.1 28.1 29.9 26.8 27.4 27.6 29.8 32.4 S.C. 22.2 19.6 16.7 16.8 12.7 24.1 22.3 18.8 18.4 14.2 26.3 25.0 20.9 20.0 15.7 kW 1.3 1.4 1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.7 1.5 1.5 1.5 1.5 65 T.C. 21.8 23.0 23.3 25.1 26.1 23.2 24.5 24.9 26.7 28.4 25.5 26.1 26.5 28.4 30.7 S.C. 21.3 19.4 16.3 16.3 12.4 23.2 21.8 18.4 18.0 13.7 25.0 24.2 20.5 19.7 14.9 kW 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.9 1.7 1.7 1.7 1.7 75 T.C. 20.9 22.0 22.1 23.9 24.7 22.3 23.4 23.7 25.4 26.9 24.3 24.8 25.4 26.9 29.1 S.C. 20.4 19.0 15.9 15.8 12.0 22.3 21.1 18.0 17.5 13.1 23.8 23.3 20.0 19.3 14.1 kW 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0 1.9 1.9 1.9 1.9 85 T.C. 20.0 20.9 20.8 22.7 23.3 21.4 22.2 22.5 24.1 25.4 23.0 23.6 24.2 25.4 27.4 S.C. 19.6 18.7 15.5 15.2 11.6 21.4 20.5 17.4 17.0 12.5 22.5 22.3 19.4 18.8 13.4 kW 2.0 2.0 2.0 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 95 T.C. 19.2 19.9 19.5 21.5 21.9 20.4 21.1 21.3 22.7 23.9 21.7 22.3 23.1 24.0 25.8 S.C. 18.7 18.2 14.9 14.7 11.2 20.4 19.8 16.9 16.5 11.9 21.3 21.4 18.9 18.3 12.6 kW 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4 105 T.C. 18.3 18.8 18.3 20.2 20.5 19.5 19.9 20.1 21.4 22.3 20.5 21.0 21.9 22.5 24.1 S.C. 17.8 17.8 14.3 14.1 10.7 19.5 19.1 16.3 15.9 11.3 20.0 20.4 18.3 17.7 11.8 kW 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.6 2.7 2.7 115 T.C. 17.4 17.7 17.0 19.0 19.1 18.5 18.8 18.9 20.1 20.8 19.2 19.8 20.8 21.1 22.5 S.C. 17.0 17.2 13.7 13.4 10.2 18.5 18.3 15.7 15.2 10.6 18.8 19.4 17.6 17.1 11.0 kW 2.6 2.6 2.6 2.7 2.8 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.9 2.9 Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). Heating performance data - 2 ton Table 10: Heating performance data - 2 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH7213241S Air temperature (°F) ID CFM 600 800 1000 Entering outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 60 60 24.6 3.61 2.00 26.7 3.89 2.01 28.7 4.17 2.02 70 22.8 3.31 2.02 24.2 3.61 1.96 25.6 3.94 1.90 80 24.2 2.87 2.47 27.4 3.34 2.40 30.5 3.83 2.34 47 60 22.6 3.16 2.10 24.1 3.43 2.06 25.6 3.72 2.01 70 20.9 2.91 2.10 22.1 3.14 2.06 23.2 3.38 2.01 80 22.1 2.55 2.54 24.8 2.92 2.49 27.4 3.30 2.43 40 60 21.5 2.93 2.15 22.7 3.20 2.08 23.9 3.48 2.01 70 19.8 2.71 2.15 20.9 2.91 2.11 22.0 3.11 2.07 80 20.9 2.38 2.58 23.4 2.70 2.53 25.8 3.04 2.48 30 60 19.9 2.63 2.22 20.7 2.87 2.11 21.4 3.14 2.00 70 18.4 2.44 2.21 19.3 2.59 2.18 20.2 2.74 2.16 80 19.3 2.15 2.63 21.3 2.41 2.60 23.4 2.68 2.56 17 60 17.9 2.26 2.32 18.1 2.46 2.16 18.3 2.68 2.00 70 16.4 2.10 2.29 17.2 2.21 2.28 17.9 2.31 2.27 80 17.2 1.86 2.71 18.7 2.05 2.68 20.3 2.24 2.65 16 YORK Technical Guide: HMH7 Series -17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Table 10: Heating performance data - 2 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH72B241S Air temperature (•F) ID CFM 600 800 1000 Entering outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 10 60 16.8 2.08 2.37 16.7 2.24 2.18 16.6 2.44 1.99 70 15.4 1.93 2.33 16.0 2.01 2.33 16.7 2.09 2.33 80 16.0 1.71 2.75 17.3 1.86 2.73 18.7 2.02 2.71 0 60 15.2 1.83 2.44 14.7 1.94 2.21 14.2 2.09 1.99 70 13.9 1.70 2.40 14.4 1.75 2.41 14.9 1.80 2.42 80 14.4 1.50 2.80 15.3 1.61 2.79 16.3 1.72 2.78 O Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). Performance data - 3 ton Cooling performance data - 3 ton Table 11: Cooling performance data - 3 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH7213361S Air ID CFM 900 1200 1500 temp (•F) ID DB (•F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 ID WB (•F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 T.C. 31.3 37.1 38.1 41.6 45.5 36.7 39.2 39.7 43.2 46.9 40.0 41.2 41.2 44.8 48.3 S.C. 31.3 30.1 26.4 26.4 21.7 36.7 34.8 29.8 29.8 24.0 40.0 39.4 33.1 33.2 26.3 kW 2.07 2.46 2.47 2.50 2.53 2.59 2.59 2.60 2.62 2.65 2.70 2.72 2.73 2.75 2.77 65 T.C. 30.8 35.7 36.5 39.8 43.6 35.6 37.6 37.9 41.3 44.9 38.5 39.5 39.4 42.7 46.2 S.C. 30.8 29.6 25.8 25.8 21.0 35.6 34.2 29.2 29.2 23.4 38.5 38.7 32.6 32.6 25.7 kW 2.46 2.78 2.79 2.83 2.88 2.91 2.91 2.92 2.96 3.00 3.03 3.05 3.06 3.09 3.13 75 T.C. 30.3 34.3 34.9 38.1 41.7 34.3 36.0 36.2 39.4 42.9 37.0 37.7 37.5 40.7 44.0 S.C. 30.3 29.0 25.1 25.1 20.4 34.3 33.4 28.6 28.5 22.7 37.0 37.7 32.0 32.0 25.1 kW 2.85 3.09 3.11 3.17 3.22 3.24 3.24 3.25 3.30 3.35 3.36 3.38 3.39 3.44 3.49 85 T.C. 29.8 32.9 33.2 36.3 39.8 33.1 34.4 34.4 37.5 40.8 35.4 35.9 35.6 38.7 41.8 S.C. 29.8 28.4 24.4 24.4 19.7 33.1 32.2 27.9 27.8 22.0 35.4 35.9 31.3 31.2 24.4 kW 3.25 3.41 3.42 3.50 3.57 3.56 3.56 3.57 3.64 3.71 3.69 3.71 3.71 3.78 3.84 95 T.C. 29.3 31.5 31.6 34.6 37.9 31.8 32.8 32.7 35.6 38.8 33.9 34.1 33.7 36.7 39.7 S.C. 29.3 27.8 23.7 23.6 19.0 31.8 31.0 27.1 27.0 21.3 33.9 34.1 30.5 30.4 23.6 kW 3.64 3.73 3.74 3.84 3.91 3.88 3.88 3.89 3.98 4.06 4.03 4.04 4.04 4.13 4.20 105 T.C. 28.8 30.1 30.0 32.8 36.0 30.5 31.2 30.9 33.7 36.7 32.4 32.4 31.8 34.6 37.5 S.C. 28.8 27.1 22.9 22.8 18.2 30.5 29.7 26.2 26.1 20.5 32.4 32.4 29.6 29.5 22.8 kW 4.03 4.04 4.06 4.17 4.26 4.21 4.21 4.21 4.32 4.41 4.36 4.37 4.37 4.47 4.55 115 T.C. 20.8 23.9 21.9 23.2 27.9 24.4 24.8 22.2 23.4 25.7 S.C. 20.8 23.5 18.6 23.2 15.6 24.4 24.5 20.6 23.4 18.2 kW 3.00 3.60 3.19 3.11 3.42 3.66 3.66 3.32 3.23 3.46 3.27 3.73 3.45 3.35 3.51 Q Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). • Drive output is limited in the shaded area. Performance may vary and interpolation is not permissable. YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump 17 Johnson Controls Ducted Systems Heating performance data - 3 ton Table 12: Heating performance data - 3 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH72B3615 Air temperature ('F) ID CFM 900 1200 1500 Entering outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 60 60 41.6 3.51 3.47 43.6 3.81 3.36 45.7 4.12 3.25 70 39.1 3.03 3.78 40.2 3.23 3.65 41.3 3.45 3.51 80 38.5 2.78 4.07 40.7 3.02 3.95 42.9 3.28 3.83 47 60 36.4 3.27 3.26 38.2 3.51 3.19 40.1 3.77 3.13 70 34.4 2.85 3.55 35.4 3.00 3.45 36.3 3.16 3.36 80 33.7 2.60 3.80 35.6 2.80 3.72 37.4 3.01 3.64 40 60 33.5 3.12 3.15 35.3 3.34 3.10 37.2 3.56 3.06 70 31.9 2.73 3.42 32.7 2.87 3.35 33.6 3.00 3.28 80 31.2 2.49 3.66 32.8 2.67 3.60 34.4 2.85 3.54 30 60 29.5 2.90 2.99 31.2 3.08 2.97 32.9 3.25 2.96 70 28.3 2.56 3.24 29.0 2.66 3.20 29.7 2.75 3.16 80 27.5 2.33 3.46 28.9 2.47 3.43 30.2 2.61 3.40 17 60 24.3 2.57 2.78 25.8 2.70 2.81 27.3 2.82 2.84 70 23.7 2.31 3.01 24.2 2.35 3.01 24.7 2.40 3.01 80 22.7 2.08 3.20 23.7 2.17 3.21 24.7 2.26 3.21 10 60 21.5 2.37 2.66 22.9 2.47 2.72 24.3 2.58 2.77 70 21.2 2.15 2.88 21.6 2.18 2.90 21.9 2.20 2.92 80 20.1 1.93 3.06 21.0 1.99 3.09 21.8 2.05 3.11 0 60 17.5 2.05 2.50 18.8 2.13 2.59 20.0 2.20 2.67 70 17.6 1.91 2.70 17.8 1.90 2.76 18.1 1.89 2.81 80 16.5 1.69 2.86 17.0 1.71 2.91 17.6 1.74 2.97 © Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). Performance data - 4 ton Cooling performance data - 4 ton Table 13: Cooling performance data - 4 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH72B4815 Air ID CFM 1200 1500 1800 temp (°F) ID DB ('F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 ID WB ff) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 T.C. 41.2 50.0 49.7 55.2 58.7 44.7 49.9 51.0 57.7 61.6 48.3 49.8 52.2 60.1 64.4 S.C. 41.2 31.9 35.7 36.3 28.0 44.7 40.9 39.2 39.5 30.3 48.3 49.8 42.7 42.8 32.6 kW 2.92 2.96 2.96 3.00 3.08 3.06 3.08 3.08 3.12 3.18 3.21 3.21 3.19 3.23 3.28 65 T.C. 39.2 46.9 47.1 52.5 56.4 41.6 46.4 48.1 54.7 58.8 44.0 45.9 49.2 56.9 61.2 S.C. 39.2 30.1 34.7 35.0 27.2 41.6 38.0 38.3 38.3 29.5 44.0 45.9 41.8 41.6 31.7 kW 3.31 3.35 3.35 3.40 3.51 3.46 3.48 3.48 3.52 3.62 3.60 3.61 3.60 3.65 3.73 75 T.C. 37.3 43.7 44.4 49.7 54.0 38.5 42.9 45.3 51.7 56.0 39.8 42.0 46.2 53.6 58.1 S.C. 37.3 28.2 33.6 33.7 26.5 38.5 35.1 37.2 36.9 28.6 39.8 42.0 40.8 40.2 30.8 kW 3.70 3.75 3.75 3.79 3.94 3.85 3.88 3.88 3.93 4.06 4.00 4.01 4.01 4.06 4.18 85 T.C. 35.3 40.6 41.7 47.0 51.7 35.4 39.4 42.5 48.7 53.3 35.6 38.1 43.3 50.4 54.9 S.C. 35.3 26.3 32.4 32.3 25.7 35.4 32.2 36.0 35.5 27.7 35.6 38.1 39.5 38.7 29.8 kW 4.09 4.14 4.14 4.19 4.37 4.24 4.27 4.28 4.33 4.50 4.39 4.41 4.42 4.47 4.63 95 T.C. 33.3 37.4 39.0 44.2 49.3 32.3 35.8 39.7 45.7 50.5 31.4 34.2 40.3 47.2 51.7 S.C. 33.3 24.4 31.1 30.8 24.9 32.3 29.3 34.6 34.0 26.8 31.4 34.2 38.1 37.2 28.7 kW 4.48 4.53 4.53 4.58 4.79 4.64 4.67 4.68 4.73 4.93 4.79 4.81 4.83 4.89 5.07 18 YORK Technical Guide: HMH7 Series -17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Table 13: Cooling performance data - 4 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH72B481S Air ID CFM 1200 1500 1800 temp (•F) ID DB (•F) 80 80 75 8o 80 80 80 75 80 80 80 80 75 80 80 ID WB (•F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 105 T.C. 31.4 34.3 36.4 41.5 47.0 29.3 32.3 36.8 42.7 47.8 27.1 30.3 37.3 43.9 48.6 S.C. 31.4 22.5 29.7 29.3 24.0 29.3 26.4 33.1 32.4 25.8 27.1 30.3 36.5 35.4 27.5 kW .C. S.C. 4.87 36. 4.93 31.1 31.1 4.93 35.3 29.3 4.97 38. 28.0 5.22 5.03 .1 27.9 5.07 28.0 28.0 5.08 36.3 32.9 5.14 39.2 31.2 5.37 5.18 1 5.21 20.0 19.6 1 5.24 5.30 1 5.52 kW 5.30 5.36 5.40 5.34 5.21 5.44 5.50 5.55 5.52 5.29 5.57 1 5.64 11 5.70 5.70 5.36 O Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). • Drive output is limited in the shaded area. Performance may vary and interpolation is not permissable. Heating performance data - 4 ton Table 14: Heating performance data - 4 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH7213481S Air temperature (•F) ID CFM 1200 1500 1800 Entering outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 60 60 41.6 2.93 4.15 53.5 3.90 4.02 53.4 4.02 3.89 70 51.0 3.30 4.53 52.7 3.51 4.41 54.4 3.73 4.28 80 50.1 3.01 4.87 50.8 3.14 4.74 51.5 3.28 4.60 47 60 46.0 3.44 3.92 46.3 3.54 3.83 46.6 3.65 3.75 70 43.7 3.00 4.26 45.1 3.17 4.18 46.6 3.34 4.09 80 42.8 2.75 4.57 43.4 2.84 4.48 44.0 2.94 4.39 40 60 41.9 3.23 3.80 42.4 3.33 3.73 43.0 3.43 3.67 70 39.7 2.83 4.11 41.0 2.97 4.05 42.4 3.11 3.99 80 38.9 2.59 4.41 39.4 2.66 4.34 39.9 2.74 4.27 30 60 35.9 2.91 3.62 36.9 3.01 3.59 37.9 3.12 3.56 70 34.0 2.56 3.90 35.2 2.66 3.87 36.4 2.77 3.85 80 33.4 2.34 4.18 33.8 2.39 4.14 34.2 2.44 4.10 17 60 28.3 2.45 3.38 29.7 2.56 3.40 31.2 2.67 3.42 70 26.6 2.15 3.63 27.6 2.22 3.64 28.6 2.29 3.66 80 26.1 1.97 3.88 26.4 1.99 3.88 26.7 2.01 3.88 10 60 24.1 2.17 3.26 25.8 2.29 3.30 27.6 2.41 3.35 70 22.7 1.91 3.48 23.5 1.96 3.52 24.3 2.00 3.56 80 22.2 1.75 3.72 22.4 1.76 3.74 22.6 1.76 3.77 0 60 18.2 1.73 3.08 20.3 1.88 3.16 22.4 2.03 3.24 70 17.0 1.52 3.27 17.7 1.55 3.34 18.3 1.57 3.42 80 16.6 1.40 3.49 16.7 1.39 3.54 16.9 1.37 3.60 Q Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump 19 Johnson Controls Ducted Systems Performance data - 5 ton Cooling performance data - 5 ton Table 15: Cooling performance data - 5 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH7213601S Air ID CFM 1500 1750 2000 temp (`F) ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 T.C. 55.2 60.6 60.4 64.4 67.7 56.8 61.7 61.7 65.2 68.2 59.1 63.3 63.7 66.4 69.0 S.C. 53.7 47.1 41.2 39.8 32.6 55.8 49.0 42.6 41.0 33.5 59.1 51.9 44.8 42.8 34.8 kW 4.39 4.41 4.42 4.47 4.50 4.47 4.51 4.50 4.55 4.58 4.58 4.66 4.63 4.68 4.70 65 T.C. 53.0 57.8 57.5 61.5 64.7 54.6 58.9 58.7 62.3 65.2 56.9 60.5 60.5 63.5 66.0 S.C. 52.7 46.6 40.3 39.1 32.1 54.3 48.7 41.9 40.4 32.9 56.9 51.7 44.3 42.3 34.1 kW 4.85 4.88 4.88 4.96 5.01 4.93 4.98 4.97 5.05 5.10 5.05 5.14 5.11 5.18 5.23 75 T.C. 50.8 55.1 54.6 58.6 61.7 52.4 56.1 55.7 59.4 62.2 54.6 57.6 57.3 60.5 62.9 S.C. 50.8 46.0 39.4 38.2 31.5 52.4 48.2 41.1 39.6 32.2 54.6 51.4 43.6 41.7 33.3 kW 5.32 5.35 5.35 5.45 5.52 5.40 5.46 5.45 5.55 5.61 5.52 5.62 5.59 5.69 5.76 85 T.C. 48.6 52.3 51.7 55.7 58.8 50.2 53.3 52.6 56.4 59.2 52.4 54.8 54.1 57.5 59.8 S.C. 48.6 45.2 38.3 37.3 30.8 50.2 47.5 40.1 38.7 31.5 52.4 50.8 42.7 40.9 32.5 kW 5.78 5.82 5.81 5.94 6.02 5.86 5.93 5.92 6.04 6.13 5.99 6.10 6.07 6.20 6.29 95 T.C. 46.4 49.5 48.7 52.8 55.8 48.0 50.5 49.6 53.5 56.2 50.2 52.0 50.9 54.5 56.7 S.C. 46.4 44.3 37.1 36.2 30.0 48.0 46.6 38.9 37.7 30.6 50.2 50.1 41.7 40.0 31.5 kW 6.24 6.28 6.28 6.44 6.53 6.33 6.40 6.39 6.54 6.64 6.46 6.58 6.55 6.70 6.81 105 T.C. 43.2 45.0 44.3 48.5 49.5 44.5 45.0 44.5 48.1 49.1 46.6 45.0 44.9 47.5 48.5 S.C. 43.2 41.9 35.4 34.4 28.2 44.5 43.1 37.0 39.7 36.3 46.6 45.0 39.5 47.5 48.5 kW 6.44 6.64 6.73 6.74 6.50 6.46 6.67 6.76 6.73 6.29 6.50 6.72 6.79 6.72 5.97 S.C. S.C. 34.6 34.6 33.9 33�9kW 30.7 30.1 21.8 35.4 34.1 32.1 32.8 27.8 36.6 34.5 34.1 36.8 36.8 5.38 5 5.32 5.46 5.32 5.44 5.47 5.42 5.51 5.13 5.55 5.50 5.57 5.59 4.85 O Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). • Drive output is limited in the shaded area. Performance may vary and interpolation is not permissable. Heating performance data - 5 ton Table 16: Heating performance data - 5 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH72136015 Air temperature ff) ID CFM 1500 1750 2000 Entering outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 60 60 62.4 3.69 4.95 63.1 3.80 4.87 63.9 3.91 4.79 70 59.6 3.29 5.30 60.8 3.41 5.23 64.0 3.64 5.16 80 58.6 3.02 5.69 61.4 3.18 5.65 64.2 3.35 5.62 47 60 54.9 3.41 4.72 55.8 3.51 4.67 56.8 3.61 4.61 70 52.1 3.04 5.02 53.2 3.13 4.98 54.3 3.22 4.94 80 50.4 2.76 5.36 53.2 2.91 5.36 56.0 3.06 5.36 40 60 50.9 3.25 4.59 51.9 3.34 4.55 52.9 3.43 4.52 70 48.1 2.89 4.87 49.1 2.97 4.85 52.2 3.18 4.82 80 46.0 2.60 5.19 48.8 2.75 5.20 51.5 2.89 5.22 30 60 45.1 3.00 4.40 46.3 3.09 4.39 47.5 3.18 4.38 70 42.4 2.67 4.66 43.3 2.72 4.65 46.4 2.92 4.65 80 39.7 2.35 4.94 42.5 2.50 4.98 45.2 2.64 5.02 20 YORK Technical Guide: HMH7 Series -17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems Table 16: Heating performance data - 5 ton - air temperature (OF) entering outdoor unit Outdoor unit model: HMH72B601S Air temperature (°F) ID CFM 1500 1750 2000 Entering outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 17 60 37.6 2.65 4.16 39.0 2.73 4.18 40.4 2.82 4.20 70 34.9 2.34 4.38 35.7 2.37 4.41 38.7 2.56 4.43 80 31.5 2.00 4.62 34.3 2.14 4.69 37.0 2.28 4.76 10 60 33.6 2.44 4.04 35.1 2.52 4.07 36.6 2.61 4.11 70 30.9 2.14 4.23 31.6 2.17 4.27 34.6 2.35 4.31 80 27.1 1.79 4.45 29.9 1.93 4.53 32.6 2.07 4.62 0 60 27.8 2.12 3.85 29.5 2.21 3.91 31.1 2.30 3.97 70 25.2 1.84 4.02 25.7 1.85 4.08 28.7 2.03 4.14 80 20.8 1.45 4.20 23.6 1.60 4.31 26.3 1.75 4.42 O Note: • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump 21 Johnson Controls Ducted Systems Subject to change without notice. Published in U.S.A. Copyright © 2021 by Johnson Controls. All rights reserved. Johnson Controls Ducted Systems