REV1 APPROVED BLD BLD2021-0111+Structural_Plan+1.18.2022_7.45.22_AM+2625381SHEARWALL SCHEDULE
SWEXP
Notes apply as called out in table below.
1 Anchor bolts embedded at least 7", or expansion anchors embedded at least 4". See detail SWB.
2 #MASAP can be installed instead of sill bolts with washers. When replacing 1/2"0 sill bolts use 7-10dx11/2"
nails (minimum nailing) and when replacing 5/8"0 sill bolts use 9-10dx11/2" nails (maximum nailing).
3 See detail SWF. Connections vary depending on condition. 3a Substitute 16d toe nails @ 8"oc for *A35.
4 See detail SWR Letter designations a, b, & c refer to specific conditions. For gable -end roof
connections see detail SWF.
5 See detail SWR
6 Abutting panel edges require a 2-2x (lamination connection same as WALL BASE PLATE), 3x, or greater stud.
7 See detail DSW.
8 The plate washer shall extend to within 1/2" of the edge of the bottom plate that receives the sheathing or rim.
At double -sided shearwalls, stagger on both plate edges.
SHEAR FLOW CONNECTIONS / SPACING
S
SILL -TO -
FLOOR -TO -
ROOF -TO -
WALL BASE PLATE
CALL
FOUNDATION 1, 2
SILL &WALL
WALL 4
5
OUT
5/8"0 @ 60"oc or
#A35 @
*H1 @
16d @ 10"oc
A
7/2"0 @ 60"oc
48"oc 3a
24"oc 4a
5/8"0 @ 60"oc or
#A35 @
#LS50 @
16d @ 6"oc
B
1/2"0 @ 40"oc
24"oc
36"oc 4b
5/8"0 @ 40"oc or
#A35 @
#LS50 @
16d @ 4"oc
1/2"0 @ 24"oc
16"oc
24"oc 4b
5/8"0 @ 32"oc or
#A35 @
#LS50 @
16d @ 3"oc
D
7/2"0 @ 24"oc 8
16"oc
16"oc 4b
5/8"0 @ 24"oc or
#A35 @
#LS50 @
16d @ 2"oc
C
G
1/2"0 @ 16"oc 8
12"oc
12"oc 4b
5/8"0 @ 12"oc or
#A35 @
#LS50 @
2-16d @ 2"oc to 4x
F
1/2"0 @ 8"oc 8
6"oc
8"oc 4c
rim/blkg
HOLDOWN SCHEDULE
n/
WALL SHEATHING
CALL
OUT
SHEATHING
THICKNESS
EDGE
NAILS
6
7/16"
8d @ 6"oc
4
7/16"
8d @ 4"oc
3
7/16" 6
8d @ 3"oc
2
7/16" 6
8d @ 2"oc
22
7/16" both
sides 6, 7
8d @ 2"oc
1 Deepen the foundation as needed to provide the required holdown embedment into the foundation wall.
See Deatil MHE
2 Fasten to the end framing members of the shearwall, u.n.o.
3 FOUNDATION ANCHOR may be extended with threaded rod and coupler as required.
4 Provide the minimum embedment and edge distances specified by the manufacturer.
5 Attach to (2) 2x studs minimum (lamination connection same as WALL BASE PLATE; stagger nails), u.n.o.
6 See detail HDNfor installation.
HOLDOWN / STRAP
FOUNDATION
1, 2, 4, 6
FASTENERS 5
ANCHOR 1, 3, 4, 6
COMMENTS
:#STHD14/14RJ
30-16d sinker
N/A
:#HTT5KT
26 - #SD #10x21/2
#SB5/8"x24
:#HDU8-SDS2.5
20 - #SDS1/4x21/2
7/8"�T.R.
4x6 Min Post, See detail RFA
#HDU11-SDS2.5
30 - *SDS1/4x21/2
1"r¢T.R.
6x6 Min Post, See detail RFA
:#HDU14-SDS2.5
36 - *SDS1/4x21/2
1 T.R.
6x6 Min Post, See detail RFA
#MSTC40
36-16d sinker
N/A
equal number of nails to both connected
elements
#MSTC66
68-16d sinker
N/A
equal number of nails to both connected
elements
# MST60
46-16d sinker
N/A
equal number of fasteners to both
connected elements. 4x6 Min Post
#MSTC661133
56-10d sinker
N/A
See detail SB
(2) :#MSTC66B3
56-10d sinker
N/A
see detail SB6x8 Min Post
GENERAL STRUCTURAL NOTES
CODE All conditions, materials and construction shall conform to the code specified in the DESIGN CRITERIA, or
other codes required by the governing jurisdiction.
PROTECTION Through maintenance and current best practices, provide a building envelope that will preserve
the integrity of the structure throughout it's lifetime.
INSPECTIONIS Notify Building Department for inspections required by local jurisdiction.
SOILS Bearing capacity of soil shall be per DESIGN CRITERIA or greater. Footing shall bear on solid undisturbed
level soil devoid of any organic material and below indicated frost line.
COMPACTED FILL shall consist of predominately Well -Graded, granular soil, free of organic material and
debris. Fill should be placed in maximum 8" loose lifts and compacted to a minimum of 95 percent
of the maximum density at optimum moisture content determined by ASTM D-1557 test procedures.
BACKFILL shall be free draining and without organic material and debris from one of the following soil
classes SM-SC, SM, SID, SW, GC, GM, GP, and GW.
FOUNDATIONS AND RETAINING WALLS Extend footings to undisturbed bearing soil. Do not backfill until all
slabs and/or horizontal diaphragms are constructed, otherwise provide temporary bracing to resist movement.
There shall be no machine compaction on the retaining side of the structure for a distance equivalent to 2/3rds
the wall height.
SILL PLATES Use pressure treated 2x plates u.n.o. Embed anchor bolts at least 7" (expansion anchors
4"). Use 3"x3"x0.229" washers. There shall be a minimum of two bolts per piece spaced not more than 6
feet apart, with one bolt located not more than 12" or less than 4" from each end of each piece.
CONCRETE fc = 3000 psi minimum for environmental exposure (2500 psi used in structural design, or
unless greater psi indicated on the plans). 5 1/2 sacks of cement per cubic yard of concrete and a maximum
of 6 gallons of water per 94 lb sack of cement. Maximum slump is 4". Segregation of materials shall be
prevented through proper handling and placement.
REIINIFORCINIG STEEL #4 bars and larger shall be Grade 60 deformed bars, and #3 bars shall be
Grade 40 (u.n.o.), in accordance with ASTM A-615. Lap splices 32 bar diameters u.n.o. Welded
wire fabric shall conform to ASTM A-185 and shall be 6x6 - W1.4xW1.4. Lap one full mesh at splices.
CLEAR COVER 3" clr when cast against Earth and 2" clr in all other locations, u.n.o.
See applicable detail(s): RI
FOOTING DRAINAGE Footing drainage per Building Code section 1805.4.2 & Residential Code section
R405.1.
WOOD FRAMING in contact with concrete or masonry, or exposed to weather, shall be pressure treated.
Numbers in parenthesis, IE (1-1), refer to corresponding engineering calculations.
CONNECTORS AND FASTENERS Fasteners, including nuts and washers, and connectors in contact
with pressure treated wood shall be hot -dipped zinc -coated galvanized.
EXCEPTION: Plain carbon steel fasteners, including nuts and washers, in SBX/DOT and zinc borate
preservative treated wood in an interior, dry environment shall be permitted.
SOLID SAWN LUMBER shall meet the following minimum grades (u.n.o.) conforming to "WWPA GRADING
RULES FOR WESTERN LUMBER", latest edition:
BEAMS, POSTS, RAFTERS, JOIST
6X and wider DF#1
4X DF#2
2x 10 and greater DF#2
2x 8 and smaller HF#2
WALL STUDS
2x HF#2
ENGINEERED WOOD shall meet the following minimum properties:
Callout E x 106 (psi) Fb(psi) Fc Dar (psi) Fc DerD (psi) Fv(psi)
GLB 1.8E 2400 1650 650 240
All cantilevered and multi -span glue -laminated beams (GLB) shall be V8 unless noted otherwise,
additionally cantilevered beams shall have zero camber.
24F-V4 shall be cambered with a 3500' radius u.n.o.
LSL 1.55E 1900 2050 900 310
PSL 2.2E 2900 2900 625 290
Engineered wood products shall be protected from moisture to preserve their structural integrity.
Provide temporary bracing to avoid permanent deflections resulting from drying under construction
dead loads.
I -JOISTS Connect I -joist to plate using one 10d (0.131" x 3") nail on each side of bottom flange; drive nails
at an agle at least 1 1/2" from end. Connect 1 1/4" LSL rim to I -joists with one 10d (0.131" x 3") nail into
top and bottom flange. Full -depth blocking between joists over shearwalls shall be 1 1/4" min LSL.
TRUSSES Manufactured trusses are a deferred submittal item designed per CODE section 2303.4 and shall
be designed for all loads and load combinations per the CODE. All connections per manufacturer, u.n.o.
If truss layout is changed by manufacturer, please notify this office.
Trusses which require drag forces shall be designed for a drag force of:
Indicated on the plan
OVER -FRAMING Unless noted otherwise by truss manufacturer, overframe with 2x4 rafters @ 24" oc.
Post down w/ 2x4 @ 48" oc, staggered. Brace posts over 6-0" tall perpendicular to wide face.
WALL FRAMING & BEARINIG Walls shall be 2x studs at 16"oc max with double 2x top plate, and 2x base
plate (exterior walls shall be 2x6 u.n.o. & interior walls shall be 2x4 u.n.o.).
Party walls shall be parallel walls with a 1" gap between. Each wall shall be framed with 2x4 studs at 16"oc
max with double 2x top plate, and 2x base plate.
Block all supports solid to the foundation.
See applicable detail(s): BHS TPS
Full cavity blocks shall be required where party walls intersect exterior walls.
See applicable detail(s): EPI
BEAM PENETRATIONS Allowable beam penetrations shall be made in the middle third of the span and the
middle third of the depth. Contact this office for any penetration outside the allowable area.
See applicable detail(s): BP POF
THIS IS INTENDED TO DRAW ATTENTION TO
FREQUENTLY EXPERIENCED DIFFICULTIES IN CONSTRUCTION:
• LONG LEAD ITEMS
• DIFFICULT FIELD RETROFITS
• LIMITED OPTIONS FOR RETROFITS
WNG I WARNING
N.T.S.
GENERAL STRUCTURAL NOTES continued
WOOD STRUCTURAL PANELS shall meet the performance standards of the "APA" DOC PS1 and PS2 for their
intended application (group 5 species not allowed).
SHEARWALLS are indicated on the plans with a bold dashed line and labeled SW. The following letter
designation refers to the Shearwall Schedule's SHEAR FLOW CONNECTIONS / SPACING table, and the
number designation refers to the WALL SHEATHING table. Multiple combinations of letter and number
designations may be present. Wall Line numbers, shown inside triangles, refer to corresponding
engineering calculations.
Attach rated sheathing (indicated below) to 2x min STUDS spaced no more than 16"oc, u.n.o. See
Shearwall Schedule for minimum thickness and fasteners (thickness at point of fastened edges governs
shear values). All panel edges shall be blocked. Nail intermediate supports @ 12"oc. Do not penetrate
nails past flush. Install squash blocks under the ends of all shearwalls where the framing below does not
provide full bearing. Construct cripple walls same as the shearwall above, and gable -ends same as the
shearwall below.
Rated sheathing:
7/16" OSB rated with a 24/16 span rating.
1/2" CD with a 32/16 span rating.
See applicable detail(s): SWE
ROOF DIAPHRAGM Install either OSB or CD sheathing:
7/16" OSB rated sheathing with a 24/16 span rating;
panel clips required when spacing is greater than 20" oc.
1/2" CD rated sheathing with a 32/16 span rating.
Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows
half the long dimension. Nail all boundaries and supported edges with 8d @ 6"oc and interior supports with
8d @ 12"oc, blocking not required u.n.o.
ROOF -TOP DECK DIAPHRAGM Install minimum
23/32" rated Sturd-I-Floor T&G with a 24oc span rating
Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half
the long dimension. Glue and nail all boundaries and supported edges with 10d @ 6"oc and interior
supports with 10d @ 12" oc, blocking not required u.n.o.
FLOOR DIAPHRAGM Install minimum
23/32" rated Sturd-I-Floor T&G with a 24oc span rating.
Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half
the long dimension. Glue and nail all boundaries and supported edges with 10d @ 6"oc and interior
supports with 10d @ 12" oc, blocking not required u.n.o.
COLLECTORS Diaphragms shall be nailed continuously to drag struts, drag trusses and other collector
elements at boundary spacing, u.n.o.
See applicable detail(s): DTC CS
CONNECTIONS and fasteners shall be per CODE Table 2304.10.1 u.n.o. The symbol, "#", indicates a hardware
connector from the most current Simpson Strong -Tie Catalog. Hardware with equivilent or greater capacities
from other manufacturers may be substituted, example you can use USP's Dual Specification Chart to make an
equivilent or greater capacity selection. Install per the manufacturer instructions.
Fasteners and hardware in contact with pressure treated wood shall be hot -dipped zinc -coated galvanized.
NAILS All nails shall be "Standard Common" size per the latest edition of the National Design Specification
for Wood Construction (NDS) u.n.o.
HOLDOWNS See the HOLDOWN SCHEDULE.
See applicable detail(s): HDN HOC
POST CAPS Provide a post cap on isolated columns that most nearly matches the actual member size(s)
U.N.O. Each connection shall have a minimum of (3)10d to the post and (3)10d to the beam.
HANGERS Model numbers will be specified on the plans for conditions that require more than minimum
capacity, otherwise see CONNECTIONS. When a hanger is not specified on the plans, use any size specific
model number that fits that member. Always use MAX NAILING. Hanger to match member size. Notching or
shimming of beam not allowed unless specified.
JOBSIfE SAFETY Sound Structural Solutions Inc has not been retained or compensated to provide design
and/or construction review services related to the contractor's safety precautions or to means, methods,
techniques, sequences or procedures for the contractor to perform their work. The undertaking of periodic site
visits by the ENGINEER shall not be construed as supervision of actual construction and not make him responsible
for providing a safe place for the performance of work by the contractor, subcontractors, suppliers or their
employees, or for access, visits, use work, travel, or occupancy by any person.
OWNERSHIP OF DOCUMENTS These drawings and calculations are the intellectual property of Sound Structural
Solutions Inc. These drawings may not be used in whole or in part by any person without permission of Sound
Structural Solutions Inc.
MISCELLANEOUS The contractor shall verify dimensions and conditions at job site. The contractor shall
provide temporary bracing as required until all permanent connections and stiffenings have been installed.
Do not scale drawings. Pre -fabricated items to be handled and installed per manufacturer's recommendations.
WNG
REVISED PLAN APPROVED
CITY OF EDMONDS BUILDING DIVISION
W. W OfkaIL
BUILDING OFFICIAL
FAh nA 7n77
/_1»:Za1TI01slsL`VAIM
APPROVED
PLANS MUST BE
ON JOB SITE
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
Basic Wind Speed (3 sec gust) mph 110
Surface Roughness B
Wind Exposure Category B
PLAN INSTRUCTIONS
READ THIS FIRST
These plans are organized so that more detailed or specific information is found in the same
way by following the direction shown below:
GENERAL STRUCTURAL NOTES
SCHEDULES, DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES for more
specific information.
SCHEDULES
DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES and SCHEDULES for more
specific information.
DETAILS
PLANS will often refer to GENERAL STRUCTURAL NOTES, SCHEDULES and DETAILS for more
specific information.
PLANS
See the SYMBOL LEGEND as well as ABREVIATIONS AND ACRONYMS for other additional
information used on the PLANS. The term, TYPICAL (or TYP), used with a detail callout or plan note,
indicates that the information specified shall apply in all similar conditions.
IF YOU HA VEA NY QUESTIONS OR CONCERNS CONTA CT US IMMEDIA TEL Y.l
We can be reached immediately by phone: (425) 778-1023
For less pressing questions, email us: inbox@ssseng.com
Please help us get to your plans by having this job number handy: s2005012
ABBREVIATIONS AND ACRONYMS
ABV ABOVE E.S. EACH SIDE O.C. ON CENTER
A. B. ANCHOR BOLT E.W. EACH WAY P.T. PRESSURE TREATED
BLW BELOW EA EACH REINF REINFORCEMENT
BLK BLOCK E.N. EDGE NAILING REQD REQUIRED
BLKG BLOCKING EMBED EMBEDMENT SCHED SCHEDULE
B.N. BOUNDARY NAILING EXIST EXISTING SIM SIMILAR
BTM BOTTOM FDN FOUNDATION STD STANDARD
BRG BEARING FLR FLOOR STRUCT STRUCTURAL
BTWN BETWEEN FRMG FRAMING SW SHEARWALL
CLR CLEAR FTG FOOTING THRU THROUGH
CLTR COLLECTOR G.T. GIRDER TRUSS TYP TYPICAL
CONC CONCRETE GR GRADE U.N.O. UNLESS NOTED
CONN CONNECTION HORIZ HORIZONTAL # OTHERWISE
CONT CONTINUOUS MAX MAXIMUM VERT VERTICAL
CTR CENTER MFG MANUFACTURED w/ WITH
DBL DOUBLE MIN MINIMUM w/o WITHOUT
DET DETAIL o/ OVER W.W.F. WELDED WIRE FABRIC
E.E. EACH END oc ON CENTER
DESIGN CRITERIA
Governing Code 15 IBC Risk Category H
Wind Design Data
Earthquake Design Data
Gravity Load Data
Roofs: loads are psf
Dead Live Snow
Rafters'
-Pitches < 8:12 15 0 25
Trusses (pitched)
-Pitches < 8:12
Top Chord 10 0 25
Bottom Chord 5 0 0
Floors: loads are psf
Dead Live Snow
Joists 12 40 0
Notes apply as called out in table above.
1 Rafters of sawn lumber or wood I -joists.
5 Joists of sawn lumber or wood I -joists.
Soil Data
Allowable Soil Bearing 2000 psf
Seismic Importance Factor, Ie
PLAN INSTRUCTIONS
READ THIS FIRST
These plans are organized so that more detailed or specific information is found in the same
way by following the direction shown below:
GENERAL STRUCTURAL NOTES
SCHEDULES, DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES for more
specific information.
SCHEDULES
DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES and SCHEDULES for more
specific information.
DETAILS
PLANS will often refer to GENERAL STRUCTURAL NOTES, SCHEDULES and DETAILS for more
specific information.
PLANS
See the SYMBOL LEGEND as well as ABREVIATIONS AND ACRONYMS for other additional
information used on the PLANS. The term, TYPICAL (or TYP), used with a detail callout or plan note,
indicates that the information specified shall apply in all similar conditions.
IF YOU HA VEA NY QUESTIONS OR CONCERNS CONTA CT US IMMEDIA TEL Y.l
We can be reached immediately by phone: (425) 778-1023
For less pressing questions, email us: inbox@ssseng.com
Please help us get to your plans by having this job number handy: s2005012
ABBREVIATIONS AND ACRONYMS
ABV ABOVE E.S. EACH SIDE O.C. ON CENTER
A. B. ANCHOR BOLT E.W. EACH WAY P.T. PRESSURE TREATED
BLW BELOW EA EACH REINF REINFORCEMENT
BLK BLOCK E.N. EDGE NAILING REQD REQUIRED
BLKG BLOCKING EMBED EMBEDMENT SCHED SCHEDULE
B.N. BOUNDARY NAILING EXIST EXISTING SIM SIMILAR
BTM BOTTOM FDN FOUNDATION STD STANDARD
BRG BEARING FLR FLOOR STRUCT STRUCTURAL
BTWN BETWEEN FRMG FRAMING SW SHEARWALL
CLR CLEAR FTG FOOTING THRU THROUGH
CLTR COLLECTOR G.T. GIRDER TRUSS TYP TYPICAL
CONC CONCRETE GR GRADE U.N.O. UNLESS NOTED
CONN CONNECTION HORIZ HORIZONTAL # OTHERWISE
CONT CONTINUOUS MAX MAXIMUM VERT VERTICAL
CTR CENTER MFG MANUFACTURED w/ WITH
DBL DOUBLE MIN MINIMUM w/o WITHOUT
DET DETAIL o/ OVER W.W.F. WELDED WIRE FABRIC
E.E. EACH END oc ON CENTER
DESIGN CRITERIA
Governing Code 15 IBC Risk Category H
Wind Design Data
Earthquake Design Data
Gravity Load Data
Roofs: loads are psf
Dead Live Snow
Rafters'
-Pitches < 8:12 15 0 25
Trusses (pitched)
-Pitches < 8:12
Top Chord 10 0 25
Bottom Chord 5 0 0
Floors: loads are psf
Dead Live Snow
Joists 12 40 0
Notes apply as called out in table above.
1 Rafters of sawn lumber or wood I -joists.
5 Joists of sawn lumber or wood I -joists.
Soil Data
Allowable Soil Bearing 2000 psf
Seismic Importance Factor, Ie
1.00
! .
The following documentation shall be available on
'
site for the building inspector:
! x❑ COE APPROVED ARCHITECTURAL PLAN SET
'
x❑ COE APPROVED STRUCTURAL PLAN SET
;
COE REVIEWED CALCULATION PACKET �
! []ENERGY CREDIT WORKSHEET
SITE PLAN
■ 1
;
CIVIL PLAN
CITY OF EDMONDS BUILDING DEPARTMENT 2021 �
■ 1
� ❑ 1
■ ;
Seismic Force Resisting System
Table 12.2-1: A-15
2010 Equiv. Lateral Force Procedure
Response Modification Factor, R
6.5 Transverse
6.5 Longitudinal
SSS Number:
s2005012
Project Name:
22814 Edmonds Way00
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
0 N
This space reserved for
governing jurisdiction stampsLn
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
N_
O
0
a
N
N
�I
C
Q
C/)
u-)
I
0
0
N
Internal Pressure Coefficient
0.18
Topographic Factor, Kt
1.00
Wind Importance Factor, I
1.00
COMPRESSION BLOCK ROOF DIAPHRAGM #LS50 @ SHEARWALLS
PER SCHED
PER STRUCT NOTES
STRAP
COLLECTOR EDGE NAILS F��SS����
#LSTA24 w/��I1�������Il�� 1 �������
MIN (9) -10d x 1 %" COLLECTOR
#LSTA24 w/ MIN (9) -10d FASTENERS PER MEMBER �E
DIAPHRAGM FASTENERS PER MEMBER DIAPHRAGM U.N.O. WALL SOLID #H2.5A MIN #H1 @ #H2.5A @
U.N.O. BLKG @ALL ROOF SHEARWALLS ALL ROOF
WALL MEMBERS MEMBERS
VIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIAIIIIIA
U.N.O. @
SHEARWALLS
COLLECTOR COLLECTOR COLLECTOR COLLECTOR/RIM
BEAM SPLICE OPTIONAL STRAP SHEARWALL w/ TRUSS OR RAFTER BEARING a b-
LOCATION
CS COLLECTOR SPLICE CS2 COLLECTOR SPLICE SWR SHEARWALL ROOF CONNECTIONS
N.T.S. CSAB N.T.S. CSAC N.T.S. SWRA
A-12
SSS Number:
NAILING PER SHEARWALL s2005012
BASE NAILING
HOLDOWN LOCATED ON DIAPHRAGM PER NAILS PER
Project Name:
ADJACENT WALL STRUCT NOTES SW SCHED WALL BASE
WALL BASE EDGE NAILS PLATE CONN 22814 Edmonds Way
SHEARWALL EDGE NAILING FLAT BLOCK FLR RIM/BLKG PLATE CONN (SW ABOVE) (SW ABOVE)
(OR ROOF GABLE) SOLID BLKG OR DIAPHRAGM PER
COLLECTOR STRUCT NOTES Owner:
71
SHEARWALL
MIN (5) 2x � RIM/BLKG Kisan Enterprise LLC
x EDGE NAILS
0R 8
PROVIDE #A35 PER EDGE NAIL PROVIDE
SW SCHED (SW BELOW)
HIC HOEDOWN INSIDE CORNER BLKG @ 48"oc BLKG @48" oc
DTc w/JOIST-WALL DOUBLE -SIDED SHEARWALLS w/ JOIST -WALL Project Location:
HICB SHEARWALL INTERIOR SHEARWALLS, &
N.T.S. PARALLEL PARALLEL 22814 Edmonds Way
EXTERIOR SHEARWALLS EXT SHEARWALLS @ CANTILEVERS SHEARWALL TO FLOOR TO SHEARWALL Edmonds, WA 98020
FRMG COLLECTOR SWF SHEARWALL FLOOR CONNECTIONS Design Professional:
TRUSS COLLECTOR
0 THREADED ROD STRAP STRAP N.T.S. Michel Design
SHEARWALL SWFA
COLLECTOR,
TYP 5/8" O x 8"
LAGS @ 6 oc
WALL BASE WALL
WALL PLATE CONN
BEAM DOUBLE STRAP CONDITION ANCH PER PER SW SCHED STRUCT NOTES
DIAPHRAGM R
SB STRAP TO BEAM CTS COLLECTOR TO SHEARWALL SW SCHED RIM/BLKG ANCH PER �, N
O v�
#DTT2Z
CTSBA 2x SILL U.N.O. SW SCHEDO
,--�
t1.ELOW �_i �_i
PER SW SCHED EDGE NAILS 0
H
2x SILL U.N.O.
FDN FDN PER SW SCHED J
p w Ln
CTP2 COLLECTOR TO TOP PLATE
J W
N.T.S. CTPB DBL 2x STUD SHEARWALLS TO FOUNDATION SHEARWALLS TO FLOOR TO FOUNDATION
z E
EDGE NAILING SW SHEATHING SWBJ SHEARWALL BASE PLATE & FOUNDATION CONNECTIONS ~ o
V H
0)
ZI C:
N.T.S. SWBA Q)
BOUNDARY NAILS HOLDOWN cn V)
EMBEDDED im z
COLLECTOR GIRDER WALL STRAP Q
COLLECTOR TRUSS 20 BLOCKS HIP GIRDER TRUSS TRUSS #CS16 STRAP w/ V7 w
TRUSS (13) 0.148" x 2 %" NAILS STRAP SHO
MIN. TO EACH MEMBER SHEATHING PER AR UND COR ER (8)16d EVENLY SPACED, 16d @ 16" oc
SCHED TYP U.N.O. TYP FACE NAILS BEAM U
HOEDOWN SCHED
0.148" x 3 %" NAILS STUDS PER #CS16 w/,
DISCONTINUOUS
SW SHEATHING DBL TOP PLATE
@ 3 oc TYP (13) 8d NAILS EA END
3 -0 EDGE NAILING I POST Ln
MATCH TO m ¢ SHEATHING PER 2x STUD
ROOF SHEATHING ¢ SCHED MIN 2x
#CS16 STRAP w/
O
(13) 0.148" x 2 %" NAILS
MIN. TO EACH MEMBER WALL FRMG O 4'-0" MIN
SECTION A -A SECTION B-B SPLICE
HOEDOWN
2x STUD ANCHOR TOP PLATE SPLICE DISCONTINUOUS DBL TOP PLATE
CSB2 COLLECTOR SPLICE TO BLOCKING PLAN VIEW SCHETHING PER ,
N,T.s. -- __J
DSWJ DBL SIDED SW AT ADJOINING WALLS HOC HOLDOWN AT CORNER TPS DOUBLE TOP PLATE SPLICE
N.T.S. DSWA N.T.S. HOCA N.T.S. TPSA 2A
BOUNDARY NAIL ALONG BOUNDARY NAIL ALONG -r LENGTH OF COLLECTOR LENGTH OF COLLECTOR *' 10NA L� 'JL
C'
EXTENT OF EXTENT OF
COLLECTOR SHEARWALL CRIPPLE STUD SHEARWALL DOUBLE TOP PLATE TPS SWF SWR
DIAPHRAGM PER MSTC 5
STRAP 4/6 This space reserved for
STRUCT NOTES X
7%6" HTT5KT governing jurisdiction stamps M
INTERMEDIATE FRAMING ABUTTING PANEL EDGES I o
2Y" REVISION
------ 7 6x6 HDU14
HEADER HEADER Jan 18 2022
DTC DIAPHRAGM TO COLLECTOR STRAP MAY BE CITY OFEDMONDS
LOCATED DEVELOPMENT SERVICES
N.T.S. DTCA ON INSIDE DEPARTMENT
MSTC STRAP -(A) HDU14- A HTT5KT- A WINDOW
OPENING
DOOR BLD2021-0111
PARTY WALL MST ENI
TOP PLATE 3 (3)2x STUDS U.N.O. 6Y8" 4Y� STRAP
WALL STUD OR POST — KING STUD
(4x MIN) 2 0 ��� 1 4 T o � TRIMMER STUD
ADJACENT TO 2x4 CONTINUOUS t _
PARTY WALLS TOP PLATE; NO 6x6 HDU8 4x MIN ORIGIN DATE: 6/15/2020
PARTY WALL
GAP BREAK AT GAP
STHD14 HDU11 4x6 U.N.O.
A.A EXTERIOR TOP PLATE END STUD
coNsrRucT REVISED: 1/12/2022
IS CONTINUOUS EXTERIOR WALL
PARTY WALLS TO ACROSS GAP FIRE BLOCKING 4" x 4" IS THE MAXIMUM PENETRATION CRIPPLE STUD BASE PLATE SWB SWF o
EXTERIOR WALL STH D 14- A H DU 11- A HDU8- A MST STRAP -(A) OR HOLE THAT CAN BE ADDED TO A SHEARWALL a
PLAN VIEW ELEVATION VIEW - SECTION A -A
EPI EXTERIOR WALL & PARTY WALL INTERSECTION HDN HOLDOWNS SWE SHEARWALL ELEVATION
Ln
N.T.S. N.T.S. HDNA N.T.S. DRDDD of
0
N
DIAPHRAGM NAILING (TYP)
x 6 #SDS SCREW @ 16" oc
DOUBLE TOP PLATE TO 4x
BLKG AT SHEARWALL
TRUSS
#A35 @ 48" oc
1" OSB BLOCK IN
PARTY WALL GAP
ROOF DIAPHRAGM
TRUSS
#A35 PER SW
SCHEDULE
NAIL SHEATHING TO
4x4 BLKG w/ 0.148 x 3"
NAILS @ 6" oc
SHEARWALL
SHEATHING
PWR I PARTY WALL SHEARWALL @ ROOF
NTS
WALL BASE PLATE NAILS
1" GAP
WALL BASE PLATE NAILS
DIAPHRAGM NAILING
SHEARWALL ABOVE
DIAPHRAGM NAILING
DIAPHRAGM
3/4 x 6 #SDS SCREW @ 16" oc
% x 6 #SDS SCREW @ 16" oc
RIM JOIST TO DOUBLE TOP
RIM JOIST TO DOUBLE TOP
PLATE AT SHEARWALL
PLATE AT SHEARWALL
JOIST
JOIST #A35 PER SW JOIST
SCHEDULE
2- 2x RIM/SOLID BLOCK 2- 2x RIM/SOLID BLOCK
�IjII SHEARWALL
SHEATHING
STEP LESS THAN 12"
PARTY WALL SHEARWALL
1" GAP
SHEARWALL ABOVE
DIAPHRAGM
JOIST
#A35 PER SW
SCHEDULE
I �Ij�ll SHEARWALL
SHEATHING
12" DIAPHRAGM STEP
FLUSH RIM HEADER,
SEE SYMBOL LEGEND
LSL RIM IS NOT INCLUDED
IN THE FLUSH RIM HEADER
BEAR OVER
STUDS PER
INTERSECTING JOISTS
SHALL BEAR IN HANGERS
OVER OPENINGS
RIM OVER OPENING
l FLUSH RIM HEADER, TYP
N.T.S.
""I & #CS16
6)10d
TOWN
Q STUDS
►o:
REQUIRED STUDS
BEAM
2x4 WALL
2x6 WALL
4x & 2-2x (SAWN)
33/8x (GLB)
(2) 2x4
(2) 2x6
3%x(MANF)
6x & 3-2x (SAWN)
5%x (GLB)
(3) 2x4
(3) 2x6
5%x (MANF)
8x (SAWN)
6%x (GLB)
(4) 2x4
(4) 2x6
7x (MANF)
GIRDER TRUSS
(3) 2x4
(3) 2x6
REQUIRED TRIMMERS
HEADER
2x4 WALL
2x6 WALL
4x & 2-2x (SAWN)
3%x (GLB)
2x4
2x6
3%x(MANF)
6x & 3-2x (SAWN)
5%x (GLB)
----
(2) 2x6
5%x (MANF)
REQD
TRIMMERS
NOTE: BEAR BEAMS ON THE FULL WIDTH AND BREADTH OF THE MINIMUM
SUPPORTS PER TABLES ABOVE UNLESS NOTED OTHERWISE ON THE PLANS
1 BEAM & HEADER SUPPORTS
12" MIN 48" MIN
11 #CS16 TO
BEAM & BLOCKING
BEAM OR
TOP CHORD OF
TRUSS
2X FLAT BLKG
GIRDER TRUSS
TOP CHORDS
CSBJ COLLECTOR SPLICE TO BLOCKING
N.T.S.
FOR PSL & LSL, HOLES MUST BE ROUND AND ARE LIMITED TO 2" DIA. UNLESS APPROVED BY THE ENGINEER
DO NOT MAKE PENETRATIONS OR NOTCHES MINIMUM SPACING
IN THE SHADED AREA OF THE BEAM WITHOUT SHALL BE 2x THE PENETRATIONS IN THIS AREA DO NOT
PRIOR APPROVAL OF THE ENGINEER DIAMETER OF THE REQUIRE APPROVAL FROM THE ENGINEER
LARGER HOLE
DEPTH
DEPTH % DEPTH[:I E
O
DEPTH
SPAN % SPAN —
SPAN
BEAM PENETRATIONS, TYPICAL DETAIL
SPAN
NTS � N.T.S. � N.T.S. BPAA
EACTEW DnArE TA A..A DI Vr ...1 /L\ n 1A0 .. 711 LIATI C
GIRDER
TRUSS
GIRDER TRUSS BRACE
M AnUn"r"" EnrE "I"TI Tnlr
W11I1IVIV 1 RVJJ — +LVJ HMNULRJ J%LLU FVR
PER MANUFACTURER BOTTOM CHORD OF TRUSS
RAFTER TO TRUSS
N.T.S. � N.T.S.
BEAM PER PLAN
FLOOR DIAPHRAGM
4x12 BTM FLUSH @ LANDING
— #HUC HANGER
4x STUD MIN
SECTION A -A
BHB I BEAM HUNG FROM BEAM
WING
BOTTOM PLATE
FLOOR SHEATHING
#PSPN58
PLUMBING
FLOOR
#PSPN516
DBL TOP PLATE
#PSPN516 w/
8-16d NAILS I
TOP PLATE, E
— PLUMBING
#PSPN58 w/
1-8d NAIL INTO
BASE PLATE, E.S.
NOTCH AS
REQUIRED
WALL STUD, TYP WALL STUD,
TYP
TOP PLATE NOTCH BOTTOM PLATE NOTCH
PLAN VIEW PLAN VIEW
PENETRATION OF FRAMING - EXTERIOR WALL
N.T.S.
FLOOR DIAPHRAGM
FRMG
STEPS
BEAM
PER PLAN 4x4 CAN'
CRIPPLE STUD
4x12 BTM FLUSH
#CS14 COILED STRAP w/ #CS14 COILED STRAP w/
(30) 0.148 x 2 % NAILS (30) 0.148 x 2 % NAILS LANDING FRMG
4x4
CRIPPLE STUD
LANDING
12" MIN
no
#CS14 COILED STRAP w/
(24) 0.148 x 2 % NAILS
#MSTC48B3 BENT STRAP w/
(56) 0.148 x 3 NAILS
FRAMING HUNG FROM FRAMING ABOVE
N.T.S. N.T.S. FHFA
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H 0
C w Ln
[.� f V
W
z E
o
~ U
V_ H
CC 0)
V)
Q Z
� q w
to tel
E
O
U
p1
C
N
U)
Ln
V)
O
C
�J 4
f NA L
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S3
STD 900 HOOK INTO
INTERSECTING GR BEAM
•
•
GR BEAM
REINF
MATCH HORIZ
REINF
1-6 CORNER BAR @ ALL
OUTER REINF
SAE aI I ^
REINF
STD 900 HOOK INT MATCH HORIZ
INTERSECTING GR BEAM REINF
ALTERNATE EA BAR 1-6" CORNER BAR @ ALL
OUTER REINF
REINFORCEMENT AT INTERSECTIONS
N.T.S. RIAA
FOOTING SCHEDULE
CENTER UNDER CONCENTRATED LOAD U.N.O.
FOOTING SIZE
REINFORCEMENT
ID
WIDTH
LENGTH
THICKNESS
LONGITUDE
TRANSVERSE
(Transverse)
(Longitude)
F2
2'-0"
2'-0"
10"
(3) #4's
(3) #4's
LONGITUDE REINF
TRANSVERSE REINF POST TO FTG
FTG @ WALL
THICKNESS
LENGTH
WIDTH (LONGITUDE) FTG @ WALL CORNER
(TRANSVERSE)
PLYNTH ON FTG
:TG FOOTING, TYPICAL
N.T.S. FTGA
HOLDOWN
HOLDOWN ANCHOR e ANCHOR
e
EMBEDDED
STRAP
e I //
FOUNDATION WALL EMBEDDED STRAP
MINIMUM STEM HEIGHT I I\
REQUIRED TO ACCOMMODATE
ANCHORAGE PER
HOLDOWN SCHEDULE
FOOTING I DEEPEN FOUNDATION AS REQD TO
ACCOMODATE FOR HOLDOWN
L — — — EMBEDMENTS INTO WALL
FMHD MINIMUM HOLDOWN EMBEDMENT
N.T.S.
1Z" CLC,
TYP
g
a
MHE
HOLDOWN POST
32 �--
lI' An DER PLAN
8"
REINFORCED FOUNDATION ANCHOR
3/4" = V-0"
— W
AB�
6" MIN & 18" MAX
,v.
HORIZ
VERT
2 CLR @
VERT &
DOWEL
DOWEL w/
STD HOOK
FWC I CANTILEVERED FOUNDATION WALL
N.T.S.
SLAB F 121—(2)#4 CONT
0
3" CLR
e
16" BRIG
SOIL
TSFJ THICKENED SLAB FOOTING
N.T.S. TSFA
P.T. SILL PLATE
(2)#4 CONT
& A.B.
@ TOP OF WALL
CONC STEM WALL
8" U.N.O.
CTRD ON FTG, U.N.O.
#4@16oc
VERT
FINISH GRADE
4'-6" MAX
#4 @ 16"oc 2'-0"
30" MIN #4 CONT
DOWELS w/ MAX14"
@ 10" oc HORIZ
EXTENSION BETWEEN
CONIC SLAB
INTO WALL & STD GRADES 18"
ON GRADE
HOOK IN FTG MIN
(2)#4 CONT
@ BTM OF WALL
CONIC FT•`►-6..
16" x 8" w/ 3" CLR
(3) #4 CONT, I I BRIG SOIL �I I III I
U.N.O.
NOTES:
-CENTER VERTS AND DOWELS IN STEM WALL
-DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN
EMBEDMENTS
-DEEPEN EXCAVATION TO PROVIDE MINIMUM FOOTING DEPTH
FWX I FOUNDATION WALL - STEM
UITEM WALL SHALL N.T.S. FWX
3E 2'-0" DEEP MIN
:2) #4 HORIZ CONT
P.T. SILL PLATE
TOP OF WALL
#4 CONT w/inIfFINISH
& A.B.
TOP 12 OF WALL
CONIC STEM WALL
1Z X" x 3" x 3"
8 U.N.O.CTRD
ON FTG, U.N.O.
436 BRIG PLATE
n1 DBL NUT
GRADE
n
(4) #4 x I I
4'-6" MAX #4 @ 48"oc
VERT
#4 @ 48"oc 2'-0"
4„
16" MIN
DOWELS w/ MAX
#4 AT BTM
14" EXTENSION BETWEEN
CONIC SLAB
INTO WALL & STD GRADES 18"
ON GRADE
HOOK IN FTG j MIN
RFAC
SCHEDULE
ACI 318-14 FWC-BA ( 45 2000 350 0.45 8H) (BSFO S40 SLO.35-0.5 AFO)
DIMENSIONS
H
E
S
D
K
A
B
C
W
(FT -IN)
(FT -IN)
(IN)
(IN)
(IN)
(IN)
(IN)
(IN)
(IN)
8-0
7-8
4
10
0
50
8
8
66
6-0
5-8
4
10
0
32
8
8
48
4-0
3-8
4
10
0
20
8
8
36
REINFORCEMENT *1
DOWE
VERT
H
LAP
HORIZ
LONG
TOE
HEEL
KEY
(FT -IN)
(IN)
(IN)
(IN)
(IN)
(IN)
(IN)
(IN)
(IN)
8-0
#5@7
24
#5@14
#4@12
#4@8
#5@7
NR
NR
6-0
#4 @ 8
20
#4 @ 12
#4 @ 12
#4 @ 8
#4 @ 8
NR
NR
4-0
#4 @ 10
20
#4 @ 10
#4 @ 12
#4 @ 8
NR
NR
NR
* NOTE:
1 Clear cover requirements u.n.o. - 3" to soil, 2" to forms in all other locations
2 DOWEL and VERT may be the same piece provided the size and spacing of the DOWEL is
used.
3 Extend the DOWEL to within 2" of the TOE edge
FWCB
CONC FTG' g�
16" x 8 " w/�/ 3" CLR
(2) #4 CONT, BRG SOIL— I I=1 I I
U.N.O. —I NOTES:
-CENTER -CENTER VERTS AND DOWELS IN STEM WALL
-DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN
EMBEDMENTS
FWS FOUNDATION WALL - STEM
N.T.S. FWSC
8" U.N.O.
#4 CONT w/in
TOP 12" OF WALL
16" MIN
DEEPEN AS
REQUIRED
FOR HOLDOWN
ANCHORS
P.T. SILL PLATE
& A.B. CONIC SLAB
ON GRADE
CONIC STEM WALL
CTRD ON FTG, U.N.O.
#4 @ 48"oc
DOWELS w/
14" EXTENSION
INTO WALL & STD
HOOK IN FTG
CONC FTG I
30" x 10" w/
(3) #4 CONT, 3" CLR
U.N.O..
III
NOTES:
-CENTER VERTS AND DOWELS IN STEM WALL
-DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN
EMBEDMENTS
FWSP FOUNDATION WALL - STEM (@ PARTYWALL)
N.T.S. FWSI
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Lon f V
Q � O
H00
J
C w L^
J w
Z E
O
~ U
V_ H
CIC
can
Ln
p z
w
V7
O
U
0"
C
N
O
+ 2 ]
15tf
10 NA L
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S4
LENGTH
DIAMETER
LENGTH
1 � 36
HS
HS ON HIGH
STRENGTH MODELS
HEAVY HEX NUT
FIXED IN PLACE ON
ALL WSW -AB ANCHOR BOLTS
EAVY HEX NUT
PLATE WASHER
HEAVY HEX NUT
WSWH
MODEL NO.
DIAMETER
LENGTH
le
PANEL MODEL
WSWH18
WSWH-AB1x30
1"
30"
21%"
FROM SIMPSON "https://embed.widencdn.net/pdf/plus/ssttoolbox/zi9rub5hpl/WSW1.pdf"
SWAB STRONG WALL ANCHOR BOLT
N.T.S.
STRONG WALL DESIGN NOTES
1. STRONG -WALL®/ HIGH STRENGTH WOOD SHEARWALL IS MANUFACTURED AND TRADEMARKED BY "SIMPSON
STRONG -TIE COMPANY INC." HOME OFFICE: 5956 W. LAS POSITAS BLVD., PLEASANTON, CA 94588 TEL: (800)
999-5099, FAX: (925) 847-1597. "SIMPSON STRONG -TIE COMPANY INC." IS AN ISO 9001-2008 REGISTERED COMPANY.
2. USE OF THIS PRODUCT IS SUBJECT TO THE APPROVAL OF THE LOCAL BUILDING DEPARTMENT.
3. THIS PRODUCT IS PART OF THE OVERALL LATERAL FORCE RESISTING SYSTEM OF THE STRUCTURE. DESIGN OF
THE BUILDING'S LATERAL FORCE RESISTING SYSTEM, INCLUDING THE LOAD PATH TO TRANSFER LATERAL FORCES
FROM THE STRUCTURE TO THE GROUND, IS THE RESPONSIBILITY OF THE DESIGNER.
4. ENGINEER OF RECORD IS PERMITTED TO MODIFY DETAILS FOR SPECIFIC CONDITIONS.
5. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDITIONS, ELEVATIONS, ETC. PRIOR TO INSTALLATION OF
ANY COMPONENTS FOR THE STRONG -WALL SB SYSTEM. IF ANY DISCREPANCIES ARE FOUND, THEY SHALL BE
BROUGHT TO THE ATTENTION OF THE DESIGNER FOR CLARIFICATION PRIOR TO CONSTRUCTION.
6. INSTALLATION OF PRODUCT SHALL BE DONE IN CONFORMANCE TO THESE DRAWINGS. THE PERFORMANCE OF
MODIFIED PRODUCTS OR ALTERED INSTALLATION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE DESIGNER.
7, SIMPSON STRONG -TIE COMPANY INC. RESERVES THE RIGHT TO CHANGE SPECIFICATIONS, DESIGNS, AND MODELS
WITHOUT NOTICE OR LIABILITY FOR SUCH CHANGES.
8. ALL HARDWARE CALLED OUT IS SIMPSON STRONG -TIE.
9. SEE ICC-ES ESR-2652 OR CITY OF LOS ANGELES RR25730 AS APPLICABLE FOR ADDITIONAL INFORMATION.
EDGE DRILL ZONE
MIDDLE % OF PANEL THICKNESS
HOLES
• MAX. THREE HOLES IN FACE
AND THREE IN EDGE.
• %"-DIAMETER HOLES, MAX.
• 6" O.C., MIN.
8" MIN STEM WALL PER DETAIL FWX
INSET STRONGWALL
TEMPLATE 2"
2" MIN COVER
2'4' MIN
3" COVER • I •
NO EDGE HOLES
ALLOWED IN LOWER
26" OF PANEL
NO HOLES ALLOWED IN TOP 8" OF
PANEL
MAINTAIN 1%" MIN. EDGE DISTANCI
FROM CHASE AND OUTSIDE EDGE,
TYPICAL.
NO FACE HOLES
ALLOWED IN LOWER
46" OF PANEL
HOLES
• 4%"-DIA. HOLES, MAX.
• MAX, OF TWO 45/8"-DIA. HOLES OR
ONE 43/4"x12" HOLE.
• NO MINIMUM ON -CENTER SPACING
REQUIRED.
NO HOLES ALLOWED IN TOP 8" OF
PANEL
FACE DRILL ZONE
CENTER 4 8" OF PANEL FACE AS
SHOWN
12" ABOVE EXISTING HOLE, MIN.
22"
2411
HOLES FOR
WSWH24X7 PANEL ONLY
• MAX. OF ONE 4%"x6" HOLE
• 8" FROM TOP OF PANEL, MIN.
ALLOWABLE SMALL HOLES ALLOWABLE LARGE HOLES
FACE AND EDGE DRILL ZONES IN ADDITION TO ALLOWABLE SMALL
NOTES: HOLES
1. FOR HEIGHTS NOT LISTED, ORDER THE NEXT TALLEST PANEL AND TRIM TO FIT. MINIMUM TRIMMED HEIGHT
FOR ALL PANELS IS 741/2".
2. ALL PANELS COME WITH TWO PRE -ATTACHED HOLDOWNS, TWO STANDARD HEX NUTS, TWO STRUCTURAL
WASHERS, TWO #WSW -TOW PLATES AND INSTALLATION INSTRUCTIONS.
3. ALL PANELS ARE 31/2" THICK.
(2) #4 HOOKS @ 6" APART CENTERED AT
EACH STRONGWALL ANCHOR LOCATION
(TOTAL OF 4 PER STRONGWALL)
2" MIN COVER EA SIDE OF ANCHOR REINFORCEMENT
3 I.D. I 10" MIN
FTG THICKNESS
6" MIN
EXTENSION
(TYP)
24" FTG WIDTH U.N.O.
SWARI STRONG WALL ANCHOR REINFORCEMENT
N.T.S.
TRIM ZONE AND ALLOWABLE HOLES
N.T.S.
DO NOT INSTALL
#WSWH w/o
TEMPLATE
RONGWALL
'LATE 2"
nCCTr-M MnTC
WSWH DESIGNED TO PROVIDE %"
GAP BETWEEN LSL AT BASE OF WSW
AND CONCRETE. ENSURE CONCRETE
IS LEVEL AND SMOOTH BENEATH
PANEL. GRIND OR FILL AS NECESSARY.
THE STRONGWALL PANEL MUST BE
INSET 2" FROM THE OUTSIDE FACE
OF THE CONCRETE STEM.
#WSWH-TP18 FASTENER QUANTITY:
SWS16150: 26
SWS25600: 4
ATTACH #WSWH-TP PLATE (PROVIDED) ON ONE SIDE
ONLY WITH A COMBINATION OF #SDS %" x 6" AND
#SWS16150 CONNECTOR SCREWS.
LSL COLLECTOR
DOUBLE TOP PLATE
%" MAX WOOD SHIM
OPTIONAL 1" 1
COUNTERBORE
ALIGN #WSWH-TP NOTCHES WITH
BOTTOM OF TOP PLATE
#SWS16150
INSTALL WSWF
ON EXTERIOR F
#SDS
1" DIAMETER
BY%" DEEP
COUNTERBORE
SWT I STRONG WALL TOP CONNECTION
N.T.S.
#WSWH STRONG WALL INSTALLED ON
ANCHOR BOLTS PER MANUFACTURER'S
RECOMENDATIONS
HEX NUT AND
STRUCTURAL WASHER
i%"COVER
V-4" MIN OVERLAP
OFANCHOR
REINFORCING
10"x 24" MIN FOOTING
PER DETAIL SWAR
INSTALL #SDS %" x 6" SCREWS @ AN
Amri THAT PREVENTS THEM FROM EXITING
IDE OF FRAMING; APPROX 300, TYP
LSL COLLECTOR
;WH PER PLAN
SECTION
PLACE WSW12x8 OVER THE ANCHOR BOLTS AND SECURE WITH
WASHER AND HEX NUTS (PROVIDED). SNUG TIGHT FIT REQUIRED;
DO NOT USE AN IMPACT WRENCH. USE 1%" WRENCH FOR 1" NUT
(2) PAIRS OF #3 HAIRPINS @
4%" oc PER HAIRPIN PLAN
3" MIN EDGE DISTANCE
TO END OF CONCRETE
STEM WALL
EACH #WSWH ANCHOR
INSTALLED BETWEEN A
PAIR OF ANCHOR
REINFORCEMENT HOOKS
8" MIN STEMWALL
PER DETAIL FWX
SWFC STRONG WALL FOUNDATION CONNECTION
N.T.S.
MINIMUM EXTENSION OF
ANCHOR SPACING + 2"
FIELD TIE AND SECURE HAIRPINS
DURRING CONCRETE PLACEMENT
HAIRPIN PLAN
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H 0
J
p w Ln
J w
z E
O
U
CC 0)
V)
p z
w
toel 3:
O
U
0)
C
N
U)
V)
O
19
g
0 21 4< 7
NA
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S5
De
DO
FOUNDATION PLAN
1/4° = V-0° DO NOT SCALE - VERIFY ALL DIMENSIONS WITH ARCHITECTURAL SHEETS PRIOR TO CONSTRUCTION
SYMBOL
LEGEND SLEXP
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
CONCRETE WALL AND CONTINUOUS FOOTING
See CONCRETE and REINFORCING BAR specifications per DETAIL FWS.
F_ -1 F2
SPREAD FOOTING
See CONCRETE and REINFORCING BAR specifications per DETAIL FTG.
L_ — J
CONCRETE WALL AND CONTINUOUS FOOTING
See CONCRETE and REINFORCING BAR specifications per DETAIL FWX.
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
z E
O
~ U
V_ H
CC 0)
V)
p z
w
V7
E
O
U
pl
C
N
u7
�u7
X
O
C
0
g
J 1 4< 7
10NA L
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S611
SYMBOL
LEGEND SLEXP
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
CONCRETE WALL AND CONTINUOUS FOOTING
See CONCRETE and REINFORCING BAR specifications per DETAIL FWS.
F_ -1 F2
SPREAD FOOTING
See CONCRETE and REINFORCING BAR specifications per DETAIL FTG.
L_ — J
— — —
CONCRETE WALL AND CONTINUOUS FOOTING
See CONCRETE and REINFORCING BAR specifications per DETAIL FWX.
FOUNDATION PLAN
1/4° = V-0° DO NOT SCALE - VERIFY ALL DIMENSIONS WITH ARCHITECTURAL SHEETS PRIOR TO CONSTRUCTION
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
z E
O
~ U
V_ H
CC 0)
V)
p z
w
V7
E
O
U
pl
C
N
u7
�u7
X
O
C
0
g
J 1 4< 7
10NA L
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S6,2
F>
1st FLOOR SHEARWALLS & FRAMING ABOVE
1/4" = V-0"
DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS
SYMBOL LEGEND SLEXP
-------------------
DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM.
DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like.
SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections
per the SHEARWALL SCHEDULE.
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
19
POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on
the plans.
INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL
FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan.
BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 at dropped
condition u.n.o. Flush headers (FRH) shall be 2-2x12 at joists u.n.o. Reference detail FRH for installation of the
flush rim header.
_JAL - u
HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL
STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan.
JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max
spacing between members will be indicated in bold type with a symbol which is representative of the layout of the
entire level.
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
Z E
O
~ U
V_ H
CC 0)
Ul)
V)
p Z
w
V7
E
O
U
0"
C
N
�u7
X
O
C
+ ] 47
Is
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S711
1st FLOOR SHEARWALLS & FRAMING ABOVE
1/4" = V-0"
DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS
SYMBOL LEGEND SLEXP
-------------------
DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM.
DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like.
SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections
per the SHEARWALL SCHEDULE.
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
19
POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on
the plans.
INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL
FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan.
BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 at dropped
condition u.n.o. Flush headers (FRH) shall be 2-2x12 at joists u.n.o. Reference detail FRH for installation of the
flush rim header.
_JAL - u
HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL
STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan.
JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max
spacing between members will be indicated in bold type with a symbol which is representative of the layout of the
entire level.
A
NA
Mq
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
Z E
O
~ U
V_ H
CC 0)
Ul)
V)
p Z
w
V7
E
O
U
0"
C
N
�u7
X
O
C
-ca
4�7
Is
10NA
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S712
2nd FLOOR SHEARWALLS & FRAMING ABOVE
1/4" = V-0"
DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS
SYMBOL LEGEND SLEXP
-------------------
DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM.
DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like.
SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections
per the SHEARWALL SCHEDULE.
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
19
POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on
the plans.
INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL
FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan.
BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 at dropped
condition u.n.o. Flush headers (FRH) shall be 2-2x12 at joists u.n.o. Reference detail FRH for installation of the
flush rim header.
_J I L_ u
HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL
STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan.
JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max
spacing between members will be indicated in bold type with a symbol which is representative of the layout of the
entire level.
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
[.e) (V
w
Z E
O
~ U
V_ H
CC 0)
Ul)
V)
p Z
w
V7
E
O
U
0"
C
N
�u7
X
O
C
+ ] 47
Is
10f4A
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S811
2nd FLOOR SHEARWALLS & FRAMING ABOVE
1/4" = V-0"
DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS
SYMBOL LEGEND SLEXP
-------------------
DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM.
DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like.
SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections
per the SHEARWALL SCHEDULE.
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
19
POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on
the plans.
INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL
FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan.
BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 at dropped
condition u.n.o. Flush headers (FRH) shall be 2-2x12 at joists u.n.o. Reference detail FRH for installation of the
flush rim header.
_J I L_ u
HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL
STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan.
JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max
spacing between members will be indicated in bold type with a symbol which is representative of the layout of the
entire level.
M
Md
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
Z E
O
~ U
V_ H
CC 0)
Ul)
V)
p Z
w
V7
E
O
U
0"
C
N
�u7
X
O
C
-ca
4�7
Is
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S8,2
R>
2-2x6
TRIMMERS
2-2x6
TRIMMERS
3rd FLOOR SHEARWALLS & FRAMING ABOVE
1/4" = V-0"
DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS
SYMBOL LEGEND SLEXP
-------------------
DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM.
DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like.
SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections
per the SHEARWALL SCHEDULE.
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
19
POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on
the plans.
INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL
FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan.
BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 at dropped
condition u.n.o. Flush headers (FRH) shall be 2-2x12 at joists u.n.o. Reference detail FRH for installation of the
flush rim header.
_JAL - u
HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL
STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan.
JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max
spacing between members will be indicated in bold type with a symbol which is representative of the layout of the
entire level.
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
Z E
O
~ U
V_ H
CC 0)
Ul)
V)
p Z
w
V7
E
O
U
0"
C
N
�u7
X
O
C
+ 21 44 7Is
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S911
3rd FLOOR SHEARWALLS & FRAMING ABOVE
1/4" = V-0"
DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS
SYMBOL LEGEND SLEXP
-------------------
DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM.
DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like.
SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections
per the SHEARWALL SCHEDULE.
#HOLDOWN MODEL
HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are
wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE.
19
POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on
the plans.
INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL
FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan.
BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are
indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 at dropped
condition u.n.o. Flush headers (FRH) shall be 2-2x12 at joists u.n.o. Reference detail FRH for installation of the
flush rim header.
_JAL - u
HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL
STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan.
JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max
spacing between members will be indicated in bold type with a symbol which is representative of the layout of the
entire level.
<1
A
1
SSS Number:
s2005012
Project Name:
22814 Edmonds Way
Owner:
Kisan Enterprise LLC
Project Location:
22814 Edmonds Way
Edmonds, WA 98020
Design Professional:
Michel Design
M
Q � O
H o
p w Ln
c.n
(V
w
Z E
O
~ U
V_ H
CC 0)
Ul)
V)
p Z
w
V7
E
O
U
0"
C
N
�u7
X
O
C
-ca
4�7
Is
10NA
This space reserved for
governing jurisdiction stamps
REVISION
Jan 18 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0111
ORIGIN DATE: 6/15/2020
REVISED: 1/12/2022
S9,2