REVIEWED BLD2022-1689+Manufacturer_Specifications_and_Installation_Instructions+12.6.2022_1.54.19_PM+3254936RECEIVED
Dec 13 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2022-1689
Job: 21-1559
Copper Pot Main St Commons
Copperpot Bakery
550 Main St S.
Edmonds, WA 98020
wWILCOX
I1/M CONSTRUCTION INC
Spec Section Title:
Submittal Title: HVAC Hood and Fan
Contractor:
WILCOX CONSTRUCTION, LLC
Mike Mclsaac
Owner (Primary):
Casey Cooper
Approved per Casey Cooper, per
email 08/08/22.
S INC E IS 6 3
Submittal
REVIEWED
BY
CITY OF EDMONDS
Spec Section No:
Submittal No: 03
Revision No: 0
Sent Date: 2/21/2022
Contractor's Stamp
Project Name X WILCOX
Copperpot Bakery 21-1559 CONSTRUCTION INC
❑ FOR RECORD AND USE ❑ REVIEWED AS NOTED
❑ REVISE & RESUBMIT ❑✓ REVIEWED
BY David Thompson DATE 2/21/2022
SUBMITTAL# 03 SPEC 15-500
This review is only for general conformance of the project and general
compliance. Corrections or comments made on these drawings during this
review do not relieve Contractor/Subcontractor from compliance with the
requirements of the plans and specifications. Contractor is responsible for all
dimensions and fabrication to be confirmed and correlated at the job site
Architect's Stamp
Engineer's Stamp
��3HVI33Aa
.7iA ni 9uIsV pnibliu8 �
LMGREENHECK
Building Value in Air.
Printed Date: 11/16/2021
Job: Copper Pot Bakery
Mark: EF-1
Model: CUE-160-VG
O 28.88
Model: CUE-160-VG
Direct Drive Upblast Centrifugal Roof Exhaust
Fan
Drnvinnchi• CIIF_1R1_I/!:
Dimensional
Quantity
1
Weight w/o Acc's (lb)
73
Weight w/ Acc's (lb)
79
Weight w/ Acc's and Curb (lb)
98
Standard Curb Cap Size (in.)
22 x 22
Roof Opening (in.)
18.5 x 18.5
Performance
Requested Volume (CFM)
2,400
Actual Volume (CFM)
2,400
Total External SP (in. wg)
0.327
Fan RPM
974
Operating Power (hp)
0.36
Elevation (ft)
30
Airstream Temp.(F)
70
Air Density (lb/ft3)
0.075
Tip Speed (ft/min)
4,241
Static Eff. (%)
34
Misc Fan Data
Fan Eff. Index (FEI) -
Outlet Velocity (ft/min) 1,395
Motor
Motor Mounted
Yes
Size (hp)
1/2
Voltage/Cycle/Phase
115/60/1
Enclosure
ODP
Motor RPM
1000
Efficiency Rating
High
Windings
1
FLA (Amps)
6.4
Min. Circuit Ampacity (MCA)
8
Max. Overcurrent Protection (MOP)
15
Short Circuit Current Rtg (SCCR)
5 kA
Sound Power by Octave Band
29.75
19.56 41.75
1.75
(12.00)
22.00 SO
OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR, ADAPTER, AND/OR
HINGE BASE.
1.2
0.9
3
c
a) 0.6
U)
a)
d
0
0.3
'�8�
0.4
0.3
Q
0.2 3
0
a
a�
co
0.1 m
0.0
0 3 6 9 12 15 18 21 24 27 30
Volume (CFM) x 100
Z�, Operating Bhp point
C) Operating point at Total External SP
Fan curve
- - - - System curve
------- Brake horsepower curve
Sound
62.5
125
250
500
1000
2000
4000
8000P74
EP
A
Sones
Data
Inlet
72
78
75
71
68
65
59
56
11.5
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on dB
I
a no
attenuation per Octave band at 5 ft -dBA levels are not
W.Mc
WORLDWIDE
licensed by AMCA International
OEinniD
Sones - calculated using ANSI/AMCA 301 at 5 ft
RRTIRCd
nlrt ¢�
movnmenr °.
nnccalmm °a°
mmcmnon °•
InTERnnTlOnnI. IIIC.''°9
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
LMGREENHECK
Building Value in Air.
Printed Date: 11/16/2021
Job: Copper Pot Bakery
Mark: EF-1
Model: CUE-160-VG
Model: CUE-160-VG
Direct Drive Upblast Centrifugal Roof Exhaust Fan
Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Aluminum curb cap
with prepunched mounting holes - Drain trough - Ball bearing motors (sizes
85-300 and all Vari Green), sleeve bearing motors (sizes 60-80) - Motor isolated
on shock mounts - Corrosion resistant fasteners
Selected Options & Accessories:
Motor - Vari-Green EC motor
Control - Dial for balancing
Standard Curb Cap Size - 22 Square
UL/cUL 705 Listed - "Power Ventilators"
Switch, NEMA-1, Toggle, Shipped with Unit
Junction Box Mounted & Wired
Foam Curb Seal (Factory Applied)
Birdscreen: Aluminum, nom. 86% Free Area
Unit Warranty: 1 Yr (Standard)
Selected Sub Marks
See individual submittals for full details
GPI-22-G12
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
LMGREENHECK
Building Value in Air.
Vari-Green
Motor & Control Options
Printed Date: 11 /16/2021
Job: Copper Pot Bakery
Mark: EF-1
Model: CUE-160-VG
An EC motor that uses AC input power and internally converts it to DC power. Potentiometer (dial) mounted on the
motor enclosure adjusts the speed (RPM) down 80%. Vari-Green motors feature a soft -start and inherent thermal
and current protection built into each unit. Inrush current at start up is eliminated and the motor will automatically
reduce speed or turn off if overloaded or it becomes too hot.
Motor Configuration
Input Voltage: 115
Speed Reference: Dial on Motor
Permanent Dial: Yes
Control Configuration
Control Type: N/A
Transformer: None
POWER INPUT
BLACK 115 VAC
NEUTRAL
GROUND
JUMPER CLOSED
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
LMGREENHECK
Building Value in Air.
20.50 20.50
12.00
24.50 24.50
General
Printed Date: 11 /16/2021
Job: Copper Pot Bakery
Mark: EF-1
Model: GPI-22-G12
Model: GPI
Roof Curb
Standard Construction Features:
- Roof Curb fits between the building roof and the fan mounted directly to the roof
support structure - Constructed of either 18 ga galvanized steel or 0.064 in.
aluminum - Straight Sided without a cant - 2 in. mounting flange - 3 lb density
insulation - Height - Available from 12 in. to 42 in. as specified in 0.5 in.
increments. Notes: - The maximum roof opening dimension should not be
greater than the "Actual' top outside dimension minus 2 in.. - The minimum roof
opening dimension should be at least 2.5 in. more than the damper dimension or
recommended duct size. - The Roof Opening Dimension may or may not be the
same as the Structural Opening Dimension. - Damper Tray is optional and must
be specified. Tray size is same as damper size. - Security bars are optional and
must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded
to the frame and the frame is welded to the curb.
Tag
Qty
Model
Sizing
Method
Undersizing
(in.)
Weight
(lb)
Shipped
Assembled
1
GPI-22
Nominal
1.5
19
Yes
Dimensions
Nominal
Nominal
Actual I Actual
Actual
Actual
Hinge
Hinge
Curb
Outside
Outside
Outside Outside
Inside
Inside
Flange
Flange
Base
Base
Height
Width
Length
Width Length
Width
Length
Width
Length
Width*
Length*
(in.)
(in.)
(in.)
(in.) (in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
12
22
22
20.5
20.5
17
17
24.5
24.5
21
21
May not be applicable
Accessories
Material
Security
Bars
Liner
Insulation
(in.)
Galvanized
No
No
1
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
��3HVI33Aa
.7iA ni 9uIsV pnibliu8 �
LMGREENHECK
Building Value in Air.
GO Type 2, Heat and Condensate Hood
Printed Date: 11 /16/2021
Job: Copper Pot Bakery
Mark: H-1
Model: GO - 144.00 - S
Hood
Exhaust
Exhaust SP
Condensate
Model
Width (in.)
Height (in.)
Volume
Gutter
Length (in.)
(in. w.g.)
Baffle
(CFM)
GO
144
48
24
2400
0.077
No Baffle
No
Selected Opti
Option or Ac
Mounting Height
Section Data:
ns & Accessories:
80 in. off Finished Floor
Material: 430 SS 100% Construction
(Hanger brackets - galvanized steel)
Features:
Stainless Steel Finish for Higher Corrosion Resistance
Section
I Length
Weight
Volume
Drain
Light
Light Type
Foot
Num.
(in.)
(LBS)
(CFM)
SP(in. w.g.)
Qty
Candles
1
144.00
1 226.000
2400.0
0.077
None
0
na
Exhaust Collar Data:
Section
I Collar TCollar
Size (LxW) in.
Pos. Off
Pos. Off
Velocity
Mounting Option
Num.
Num.
I or Diameter (in.)
Left (in.)
Back (in.)
(fpm)
1
1
1 36 x 12 1
72
24
800
Factory Mounted Exhaust Collar(s)
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
LMGREENHECK
Building Value in Air.
0
C6
0
N
1
C7
0
N
r`
0
N
r—
NSF®
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
Generated by: robert@dorse.com
Printed Date: 11 /16/2021
Job: Copper Pot Bakery
Mark: H-1
Model: GO - 144.00 - S
COOKING APPLIANCES
Z
O
U�
LL1 LU
Z
2 0
Y
W
2 W
7
X
0
G)C
m C
C
m C�
v D
�W y
�0
o
m o
(� m
Q�
o �
o
0 W
o m
3 m
cQ
ci
4.0
24.0
I111ARf,
80.0
ABOVE
FINISHED
FLOOR
MARK: H-1
NOTE: All dimensions are in units of in.
Hanger Bracket Locations
Sec
#
Brkt
#
Distance Off
Left (in)
Distance Off
Front (in)
1
1
3.50
2.50
1
2
47.95
2.50
1
3
95.90
2.50
1
4
140.50
2.50
1
5
3.50
45.50
1
6
47.95
45.50
1
7
95.90
45.50
1
8
140.50
45.50
Bracket Mounting Position
for an 8 Bracket Hood
5 6 7 8
BACK
FRONT
1 2 3 4
ic L �•
O a r�•r
CL .. M
CD n r
G) 70v
o CD
0
� � O
U_(C N
��3HVI33Aa
.7iA ni 9uIsV pnibliu8 �
LMGREENHECK
Building Value in Air.
Model: GRSR
Printed Date: 11 /16/2021
Job: Copper Pot Bakery
Mark: IH-1
Model: GRSR
Standard Construction Features:
- Aluminum housing. - Aluminum curb cap with prepunched mounting holes. -
Recommended roof opening dimension is at least 2.5 in. larger than the damper
size.
1.75
Dimensions
Curb Cap
Curb Cap
Model Size
Width
Length
Weight
ID#
Tag
City
Model
(in.)
A (in.)
B (in.)
C (in.)
D (in.)
E (in.)
F (in.)
(in.)
(in.)
(lb)
2-1
1
GRSR-24
24
34
38.25
12.75
4
N/A
24.5
34
34
44
Performance
Throat
Volume
Throat Area
Velocity
ID#
Tag
Qty
(CFM)
SP (in. wg)
(ft2)
min)
2-1
1
2,400
0.065
3.24
741
Construction
ID#
Flashing
Flange
Installation
Type
Insect
Screen
Birdscreen
Material
Unit
Material
2-1
No
Non -Ducted
No
Galvanized
Aluminum
Accessories
Hood
Hinged
Insulation
Tie Down
ID#
Curb Cap
Curb Seal
(in.)
Points
2-1
No
No
None
No
Roof Curbs
ID#
Model
Height
(in.)
Width
(in.)
Length
(in.)
2-1
GPI
12
34
34
Width Length Blade Frame Actuator Actuator End Damper
ID# Model (in.) (in.) Action Type ctuator Type Quantity Mounting I Switch Mounting
2-1 1 VCD-231 24 1 24 1 Parallel I Channel 1 115 1 Internal I No I Ship Separa
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
LMGREENHECK
Building Value in Air.
Control Damper
Model: VCD-23
DRIVE
SIDE
1.25
Max.
Printed Date: 11/16/2021
Job: Copper Pot Bakery
Mark: IH-1
Model: GRSR
Standard Construction Features:
- Model VCD-23 is a well built low leakage control damper
for automatic control or manual balancing applications -
Galvanized 16 ga channel frame - Galvanized blades with
reinforcements - Side mounted steel linkage is concealed in
the frame to prevent additional pressure drop - Axles are
steel and 0.5 in. dia.- Synthetic axle bearings - Width and
height furnished approximately 0.25 in. undersized - Field
wiring is required to individual components
Damper Configuration:
ID #: I Tag: Quantity: W (in.): H (in.): Act Qty:
2-1 1 1 24 24 1
Notes: All dimensions shown are in units of in.
Width And height furnished approximately 0.25 in. undersize
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com
LMGREENHECK
Building Value in Air.
Model: GPI
Printed Date: 11 /16/2021
Job: Copper Pot Bakery
Mark: IH-1
Model: GPI
Roof Curb
Standard Construction Features:
- Roof Curb fits between the building roof and the fan mounted directly to the roof
support structure - Constructed of either 18 ga galvanized steel or 0.064 in.
aluminum - Straight Sided without a cant - 2 in. mounting flange - 3 lb density
insulation - Height - Available from 12 in. to 42 in. as specified in 0.5 in.
increments. Notes: - The maximum roof opening dimension should not be
greater than the "Actual' top outside dimension minus 2 in.. - The minimum roof
opening dimension should be at least 2.5 in. more than the damper dimension or
recommended duct size. - The Roof Opening Dimension may or may not be the
same as the Structural Opening Dimension. - Damper Tray is optional and must
be specified. Tray size is same as damper size. - Security bars are optional and
must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded
to the frame and the frame is welded to the curb.
General
ID#
Tag
Qty
Model
Sizing
Method
Undersizing
(in.)
Weight
(lb)
Shipped
Assembled
2-1
1
GPI-34-G12
Nominal
1.5
32
Yes
Dimensions
Nominal
Nominal
Actual
Actual
Curb
Outside
Outside
Outside
Outside
Flange
Flange
Height
Width
Length
Width
Length
Width
Length
ID#
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
2-1
12
34
34
32.5
32.5
36.5
36.5
Accessories
ID#
Material
Security
Bars
Liner
Insulation
(in.)
2-1
Galvanized
No
No
1
Z:\Robert\CAPS Jobs\Copper Pot Bakery.gfcj
CAPS 4.36.1264 Generated by: robert@dorse.com