YHJF Heat Pump specs (EXISTING)561923-YTG-F-0114 Physical and Electrical Data MODEL YHJF18 S41S1 YHJF24 S41S1 YHJF30 S41S1 YHJF36 S41S4 YHJF42 S41S5 YHJF48 S41S5 YHJF60 S41S1 Unit Supply Voltage 208-230V, 1 �, 60Hz Normal Voltage Range 1 187 to 252 Minimum Circuit Ampacity 11.9 17.6 17.3 19.7 23.7 28.5 35.3 Max. Overcurrent Device Amps 2 20 30 30 30 40 50 60 Min. Overcurrent Device Amps 3 15 20 20 20 25 30 40 Compressor Type Scroll Scroll Scroll Recip Scroll Scroll 2-Stage Scroll Compressor IRated Load 9.0 13.4 12.8 14.7 17.9 21.8 35.3 Amps ILocked Rotor 48.0 58.3 64.0 74.0 112.0 117.0 118.0 Crankcase Heater No No No Yes No No No Factory External Discharge Muffler Yes Yes Yes Combined DM/CV Yes Yes Yes Factory External Check Valve No No No No No No HS Kit Required with TXV 4 No No No Yes No No No Fan Motor Amps IRated Load 24 22 24 24 24 24 24 Fan Diameter Inches 1/10 1/8 1/4 1/4 1/4 1/4 1/4 Rated HP 0.7 0.8 1.3 1.3 1.3 1.3 1.3 Fan Motor Nominal RPM 825 1075 850 850 850 850 850 Nominal CFM 2000 2000 3900 3800 3600 3500 3800 Face Area Sq. Ft. 15.72 19.17 23.58 23.58 23.58 23.58 23.58 Coil Rows Deep 1 1 1 1 1 2 2 Fins / Inch 22 22 22 22 22 18 18 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 3/4 7/8 7/8 1-1/8 Unit Charge (Lbs.-Oz.)5 6-15 7-14 9-14 10-6 11-4 13-1 14-2 Charge Per Foot, Oz. 0.62 0.62 0.62 0.62 0.67 0.67 0.75 Operating Weight Lbs. 145 145 176 193 198 248 290 1. Rated in accordance with AHRI Standard 110-2012, utilization range "A". 2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection. 3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection. 4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model. 5. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub- tract the amount of refrigerant, using the difference in length multiplied by the per foot value. Unit Dimensions (Inches) Refrigerant Connection Service Valve Size Model A B C Liquid Vapor 18 28-1/4 34 34 3/8 3/4 24 40-1/4 29-1/2 29-1/2 30 40-1/4 34 34 36 40-1/4 34 34 42 40-1/4 34 34 718 48 40-1/4 34 34 60 40-1/4 34 34 7/8 * Adapter Fitting Required for 1-1/8" Lilneset. All dimensions are in inches and are subject to change without notice. Overall height is from bottom of base pan to top of fan guard. Overall length and width include screw heads. Johnson Controls Unitary Products