APPROVED FIR2023-0056+Fire_Sprinkler_Plan+6.2.2023_5.24.46_AM+3583117GENERAL NOTES - NFPA 13D (2016): 1. SPRINKLER PIPE TO BE CONCEALED BY OTHERS. 2. SPRINKLERS SHALL BE INSTALLED IN ALL AREA EXPECT WHERE INDICATED BELOW AND UNLESS OTHERWISE NOTED. SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS LOCATED WITHIN DWELLING UNITS WHERE THE AREA DOES NOT EXCEED 55 ft2 (5.1 m2). SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WITHIN DWELLING UNITS THAT MEET ALL OF THE FOLLOWING CONDITION: a) THE AREA OF THE SPACE DOES NOT EXCEED 24 ft2 (2.2 m2). b) THE WALLS AND CEILING ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS AS DEFINED BY NFPA 220. SPRINKLERS SHALL NOT BR REQUIRED IN GARAGED, OPEN ATTACHED PORCHES, CARPORTS, AND SIMILAR STRUCTURES. SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS WITH OR WITHOUT STORAGE, PENTHOUSE EQUIPMENT ROOMS, ELEVATOR MACHINE ROOMS, CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT, CRAWL SPACES, FLOOR/CEILING SPACES, ELEVATOR SHAFTS WHERE ELEVATOR CARS COMPLY WITH ANSI At 7.1, AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES OR STORAGE AND DO NOT CONTAIN FUEL -FIRED EQUIPMENT. WHERE THE FUEL -FIRED EQUIPMENT IS ABOVE ALL OF THE OCCUPIED AREAS OF THE DWELLING UNIT, NO SPRINKLER PROTECTION SHALL BE REQUIRED IN THE CONCEALED SPACE. WHERE FUEL -FIRED EQUIPMENT IS BELOW OR ON THE SAME LEVEL AS OCCUPIED AREA OF THE DWELLING UNIT, AT LEAST ONE QUICK -RESPONSE INTERMEDIATE TEMPERATURE SPRINKLER SHALL BE INSTALLED ABOVE THE EQUIPMENT OR AT THE WALL SEPARATING THE SPACE WITH THE FUEL -FIRED EQUIPMENT FROM THE OCCUPIED SPACE. SPRINKLERS SHALL NOT BE REQUIRED IN COVERED, UNHEATED PROJECTIONS OF THE BUILDING AT ENTRANCES / EXITS AS LONG AS THE DWELLING UNIT HAS ANOTHER MEAN OF EGRESS. SPRINKLERS SHALL NOT BR REQUIRED IN CLOSETS IN GARAGES AND EXTERIOR CLOSETS (REGARDLESS OF SIZE) LOCATED ON EXTERIOR BALCONIES, EXTERIOR BREEZWAYS / CORRIDORS, OR ACCESSED FROM OUTDOORS WHERE THE CLOSET DOES NOT HAVE DOORS OR UNPROTECTED PENETRATIONS DIRECTLY INTO THE DWELLING UNIT. SPRINKLERS SHALL BE INSTALLED IN ANY CLOSET USED FOR HEATING AND / OR AIR-CONDITION EQUIPMENT, WASHERS AND / OR DRYERS, OR WATER HEATERS. SPRINKLERS SHALL NOT BE REQUIRED FOR CEILING POCKETS THAT MEET THE FOLLOWING CONDITIONS: a) THE TOTAL VOLUME OF ALL UNPROTECTED CEILING POCKETS IN A COMPARTMENT DOES NOT EXCEED 100 ft3 (2.8 m3). b) THE ENTIRE FLOOR UNDER THE UNPROTECTED CEILING POCKETS IS PROTECTED BY THE SPRINKLERS AT THE LOWER CEILING ELEVATION. c) THE INTERIOR FINISH IF THE UNPROTECTED CEILING POCKET EXCLUDING DECORATIVE TREATMENT IS NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE MATERIAL. d) SKYLIGHTS NOT EXCEEDING 32 ft2 (3 m2) SHALL BE PERMITTED TO HAVE A PLASTIC COVER. SPRINKLER PIPING SHALL BE SEPARATED FROM AREA SERVED BY THE SPRINKLER SYSTEM, AND FROM ANY OTHER FIRE COMPARTMENT, BY CEILING, WALLS OR SOFFITS CONSISTING OF AS A MINIMUM: a) LATH AND PLASTER. b) GYPSUM BOARD NOT LESS THAN 0.347 in. THICK OR c) A SUSPENDED MEMBRANE CEILING WITH, i) STEELS SUSPENSION GRIDS AND ii) LAY -IN PANELS OR TILES HAVING A MASS NOT LESS THAN 1.7 kg/m2. SPRINKLER PIPING MAY BE LOCATED ABOVE CEILING, PROVIDED THAT THE DISTANCE BETWEEN THE EDGE OF ANY CEILING OPENING THAT IS NOT PROTECTED AS ABOVE MENTIONED AND THE NEAREST SPRINKLER IS NOT MORE THAN 11 in. 3. ALL ABOVEGROUND PIPING TO BE CPVC. FIRE PROTECTION DESIGN NOTES 1.1 CODES, STANDARDS AND APPROVALS DESIGN, INSTALLATION, AND TEST SHALL CONFORM TO THE FOLLOWING STANDARDS: 1. LOCAL BUI LDI NG CODE 2. NATIONAL FIRE PROTECTION ASSOCIATION #13 D (2016) 1.2 DESCRIPTION OF WORK THE FOLLOWING FIRE PROTECTION SYSTEMS ARE INCLUDED IN THIS SECTION OF WORK: 1. NEW WET PIPE SYSTEM 1.3 PIPING AND FITTINGS BLAZEMASTER CPVC PIPE AND FITTINGS TO BE ULC LISTED FOR FIRE PROTECTION USE. 1.4 HANGERS AND SUPPORTS ALL HANGERS AND SUPPORTS SHALL BE uLC LISTED FOR FIRE PROTECTION USE AND MEET THE NFPA REQUIREMENTS. ALL HANGER AND SUPPORTS TO BE INSTALLED IN ACCORDANCE WITH NFPA AND THE MANUFACTURER'S SPECIFICATIONS. 2.1 SPRINKLER HEADS: ULC LISTED SPRINKLERS TO BE INSTALLED PER LISTING AND MANUFACTURER'S REQUIREMENTS. SPRINKLER HEAD GUARD SHALL BE INSTALLED ON SPRINKLERS WHICH ARE SUBJECT TO MECHANICAL DAMAGE. SPRINKLER HEAD LOCATIONS TO BE CO-ORDINATED WITH ARCHITECTURAL CEILING PLAN. 2.2 SPARE SPRINKLERS THE NUMBER OF SPRINKLERS SHALL BE PROVIDED AS FOLLOWS: FOR SYSTEMS WITH A TOTAL NUMBER OF SPRINKLERS 200 OR LESS: PROVIDE NO LESS THAN 6 SPARE SPRINKLERS. FOR SYSTEMS WITH A TOTAL NUMBER BETWEEN 300AND 1000 SPRINKLERS, PROVIDE NO LESS THAN 12 SPARE SPRINKLERS. FOR SYSTEMS WITH A TOTAL NUMBER OF SPRINKLERS OVER 100, PROVIDE NO LESS THAN 24 SPARE SPRINKLERS. PROVIDED IN A STEEL CABINET TO BE LOCATED IN THE SPRINKLERVALVE ROOM 3.1 ACCEPTANCE AND TESTING SUPPLY AND INSTALL SPRINKLER SYSTEMS AS SPECIFIED IN ACCORDANCE WITH THE LISTED CODES, STANDARDS, AND LOCAL AUTHORITIES APPROVALS. TESTING OF THE SPRINKLER SYSTEM SHALL BE TO LISTED REQUIREMENTS AND A CERTIFICATE SHALL BE FURNISHED, BY THE CONTRACTOR, STATING THAT SUCH TESTING HAS BEEN CARRIED OUT AND ACCEPTED BY THE LOCAL BUILDING AUTHORITY. 3.2 FLUSHING OF SPRINKLER SYSTEM UNDERGROUND MAINS AND SIAMESE SUPPLY LINES SHALL BE FLUSHED BEFORE CONNECTING TO THE SPRINKLER SYSTEM. FLUSH UNTIL EFFLUENT IS CLEARAND FREE OF DEBRIS. AFTER CONSTRUCTION ALL SPRINKLER PIPING SHALL BE FLUSHED TO ENSURE THAT NO DEBRIS IN THE MAIN OR PIPING SYSTEM IS PRESENT THAT MIGHT OBSTRUCT THE SPRINKLER HEAD ORIFICES. ALL FLUSHING IN ACCORDANCE WITH NFPA 13. 3.3 ELECTRICAL REQUIREMENTS ELECTRICAL CONNECTIONS TO FLOW SWITCHES, PRESSURE SWITCHES, SUPERVISORY SWITCHES AND ALARM PANEL SHALL BE PERFORMED BY OTHERS (DIV.16) AND IS NOT PART OF THE FIRE SPRINKLER CONTRACTORS SCOPE OF WORK. Heat Source Minimum Distance from Edge of Source to Ordinary Temperature in. mm Minimum Distance from Edge of Source to Intermediate Temperature in. mm Side of open or recessed fireplace 36 914 12 305 Front of recessed fireplace 60 1524 36 914 Coal -or wood -burning stove 42 1067 12 305 Kitchen range 18 457 9 229 Wall oven 18 457 9 229 Hot air flues 18 457 9 229 Uninsulated heat duct 18 457 9 229 Uninsulated hot water pipe 12 305 6 152 Side of ceiling- or wall -mounted hot air 24 610 12 305 diffusers 36 914 18 457 Front of wall -mounted hot air diffusers 6 152 3 76 Hot water heater or furnace Light fixture 6 152 3 76 0 W - 250 W 12 305 6 152 MINIMUM DISTANCE FOR ORDINARY AND INTERMEDIATE TEMPERATURE RESIDENTIAL SPRINKLER Ceiling Obstruction A Maximum Allowable Distrance of Distance from Sprinklers to Side Deflector Above Bottom of of Obstruction (A) Obstruction (B) (in.) Less than 1 ft 0 1 ft to less than 1 ft 6 in. 0 1 ft 6 in. to less than 2 ft 1 2 ft to less than 2 ft 6 in. 1 2 ft 6 in. to less than a ft 1 a ft to less than 3 ft 6 in. 3 3 ft 6 in. to less than 4 ft 3 4 ft. to less than 4 ft 6 in. 5 4 ft 6 in. to less than 5 ft 7 5 ft to less than 5 ft 6 in. 7 5 ft 6 in. to less than 6 ft 7 6 ft to less than 6 ft 6 in. 9 6 ft 6 in. to less than 7 ft 11 7 ft and graeter 14 OBSTRUCTION TABLE FOR RESIDENTIAL UPRIGHT 1 PENDENT SPRAY SPRINKLER TO AVOID OBSTRUCTION Table 10.4.3(a) Pressure Losses in psi in Water Meters Flow (gpm) Meter Size (in.) 18 or less 23 26 31 39 52 5/8 9 14 18 26 38 3/4 7 11 14 22 35 1 2 3 3 4 6 10 11/2 1 1 2 2 4 7 2 1 1 1 1 2 3 For SI units, 1 gpm = 3.785 L/min; 1 in. = 25.4 mm; 1 psi = 0.0689 bar. *Above maximum rated flow of commonly available meters. THREADED ROD DETAIL THE CLOSEST HANGER TOASPRINKLER DROP SHOULD BE RESTRAINED AGAINST VERTICAL LIFT UP. 1 TYPICALLYAS SHOWN HERE THEALLTHREAD ROAD » SHOULD BE INSTALLEDTO 1/16"ABOVE THE PIPE. 6 NOTE: THE ROD SHALL NOT COME IN CONTACT WITH THE CPVC WHEN INSTALLED Cut Perpendicular to Seat I i 0I Cut -F-� Seat I Top View Side View Field Modification for Riser Collar for Vertical Use WOOD SCREW PIPE 1000 PIPE CPVC PIPE HANGER DETAIL SCALE: N.T.S. Maintain vertical piping in straight alignment with supports at each floor level, or at 10 feet (3.05 m) intervals, whichever is less. Snug but Plastic Coupling not (Tight or Collar Adhered to Pipe -Strut to Wall Coupling Modification for Riser Collar - PIPE WOOD OFFSET PIPE SCREW HANGER WOOD OFFSET PIPE HANGER DETAIL SCALE: N.T.S. 1/2 JOIST 1/2 JOIST DEPTH DEPTH MAX. MAX. Branches Branches I'll Supported with /( Supported withBlocking j Hangers 1-3/4" 1-3/4" MAX. MAX. BRANCHLINE SUPPORT AND SPRINKLER DEFLECTOR -G - G - W Maple Street SITE PLAN SCALE: 1 /1611=11-0 W SS End not Found Sprinkler Legend - Total Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature Note Viking VK468 FREEDOM 22 4.9 Pendent '/2 Fast White 155°F 16' x 16' Total = 22 j_\� Ceiling B IObstruction D A A>_(D-8in.)+B j Wall [A>_(D-0.2m)+B] jwhere: D < 30 in. (0.76 m) Elevation View FIGURE 8.2.5.3.3(a) Positioning of Sprinkler to Avoid Obstruction Against Walls (Residential Upright and Pendent Spray Sprinklers). Unheated Blown -in attic insulation space Tenting material Tent' space keeping insulation above piping Heated space BLOWN -IN INSULATION DETAIL NEW BLAZEMASTER PIPE HANGER SPACING FOR CPVC PIPES TABLE SEE TABLE SEE TABLE A B 12" MAX B HANGER HANGER HANGER MAX 12" FROM THE SPRINKLER HEAD TEE T FINISH CEILING TABLE A TABLE B NOM. PIPE SIZE(IN.) HANGER SPACING NOM. PIPE SIZE(IN.) HANGER SPACING 3/4" 6" 3/4" 4'-0" 1" 9" 1" 5'-0" 1 1 /4" 12" 1 1 /4" 6'-0" 1 1/2"-3" 12" 1 1/2"-3" T-0" TRANSITION BETWEEN CPVC AND STEEL PIPE T STEEL PIPE BLAZEMASTER 2000 CPVC FEMALE ADAPTER VIC #75 GROOVED CPLG-\ STEEL PIPE BLAZEMASTER 2000 CPVC �; ROOVED COUPLING ADAPT W W Approved D F M c lhr's -F,u.rt South County Fire Date: 06/14/2023 06-14-2023 PLAN REVIEW NOTES: APPROVED WITH CONDITIONS: 1. Approved set of plans must be on site at the time of inspection. Failure to provide the approved plan may result in a re -inspection fee. System drain(s): SEE CONDITION NOTED AT RISER. If riser is above lowest grade, 2nd drain required and signage at riser indicating location is required. Systems required signage IAW NFPA 13D. 2. Coverage required to the following areas: Clothes closets, linen closets and pantries exceeding 24 square feet in area, with the smallest dimension greater than 3' and having wall and ceiling surfaces of gypsum board. Bathrooms more than 55 square feet in area. When fuel fired equipment is present on covered decks or porches, or if living space above, at least one quick -response intermediate temperature sprinkler shall be installed above equipment or area under living space. All fuel fired appliances except attics if above all living areas. 4. A red placard with one and one half 1/2" white lettering reading "THIS VALVE SHUTS OFF THE DOMESTIC WATER AND FIRE SPRINKLER SYSTEM" is to be permanently installed at the main valve location and any additional signs required by NFPA 13D. 5. Double check valves to be in the open position and handles to be removed at final. DFM Burt ASSEMBLY DETAIL RIGHT WRONG I f i, Iw THREAD THE SPRINKLER INTO DO NOT PRE -ASSEMBLE THE THE ADAPTOR FITTING ONLY DROP ASSEMBLY WITH THE AFTER THE RECOMMENDED SPRINKLER HEAD PRIOR TO CURE TIME CEMENTING ALL JOINTS Dayton St o Q Salish Sea Brewing Co & Restaurant ® © Las Bnsas Gracie Barra Edmonds h9'.- ." �BrazilianJiuJitsu n m Gelato Caffe ®Cananno 1« Cie- - S First Church of Christ, Scientist Q • Maple St sin. roc Vanity Lash Lounge y & Aesthetics Alder St Alder St idio 0 Beck's Tribute Center Beck Ln Beck L,.- Beck Ln LOCATION MAP SCALE: N.T.S. N SCOPE OF WORK: NEW RESIDENTIAL FIRE PROTECTION SPRINKLER SYSTEM FOR NEW CONSTRUCTION. RESIDENTIAL SPRINKLER NOTES: RESIDENTIAL PENDENT SPRINKLER 1) MAXIMUM SPRINKLER COVERAGE NOT TO EXCEED 16' x 16' (sgft). 2) MINIMUM DISTANCE BETWEEN SPRINKLERS TO BE 8'-0". 3) MAXIMUM DISTANCE FROM ANY WALL SHALL NOT EXCEED 8'-0". 4) PENDENT SPRINKLER SHALL BE LOCATED AT LEAST T-0" FROM OBSTRUCTIONS SUCH AS CEILING FANS AND LIGHT FIXTURES. 5) FOR OTHER OBSTRUCTIONS REFER TO OBSTRUCTION TABLES. 0 ISSUED FOR PERMIT 06/01/23 No REVISIONS DATE (M M/DD/YY) STAMP REVIEW OF THIS DRAWING IS RESTRICTED TO THE NEW WORK ONLYAS IDENTIFIED IN THE SCOPE WITHIN THE CONTRACT STANDARD REFERENCE SYSTEM IS DESIGNED TO NFPA 13D (2016) SYSTEM PIPE MAINS LINES WET DRY ❑ SCH.40 ❑ ❑ SCH.10 ❑ ❑ PREACTION ❑ DELUGE ❑ GALV. ❑ ❑ CPVC ANTI -FREEZE ❑ FOAM -WATER ❑ FITTINGS C.I. ❑ ❑ M.I. ❑ ❑ BLACK ❑ ❑ GALV. ❑ ❑ CPVC 0 0 POL/GOL ❑ ❑ VICTAULIC ❑■ ❑■ MECH-T ❑ ❑ PAINTED ❑ 1 ❑ WATER SUPPLY INFO. FIRE PUMP INFO. WATER FLOW TEST BY: RAIN CITY FIRE PROTECTION FIRE PUMP: DIESEL ICI ELECTRIC ICI N/A DATE: 05/30/2023 STATIC: 83 PSI RATED FLOW: GPM RESIDUAL: PSI WATER FLOW: GPM RATED PRESSURE PSI IMPORTANT OWNERS TO PROVIDE SUFFICIENT HEAT (MIN. 40°F/5°C) THROUGHOUT AREAS WHERE "WET" SYSTEM ARE INSTALLED TO PREVENT FREEZING OF WATER UNLESS AN ANTI -FREEZE SYSTEM IS PROVED. RAIN CITY FIRE PROTECTION 82201NTERLAKE AVE N. SEATTLE, WA 98103 FI R2023-0056 PROJECT NAME/ADDRESS: PICKERING EDMONDS RECEIVED Jun 07 2023 304 6TH AVE SOUTH CITY OF EDMONDS DEVELOPMENT SERVICES EDMONDS, WA DEPARTMENT 98020 DESCIPTION: INSTALLATION OF NEW RESIDENTIAL FIRE PROTECTION SPRINKLER SYSTEM CONTRACT No DATE 1 JUNE 2023 SCALE DRAWING No AS NOTED 1 OF 3 DRAWN BY REVISION CM 0 CHWD BY GR SCOPE OF WORK: NEW RESIDENTIAL FIRE PROTECTION SPRINKLER SYSTEM FOR NEW CONSTRUCTION. RESIDENTIAL SPRINKLER NOTES: L'4= SILIIBMJ[SIMIE�JWAILI OUMLC: 114 = I -U Sprinkler Legend - Second Floor Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature Note Viking VK468 FREEDOM 14 4.9 Pendent 1/2 Fast White 155•F 16' x 16' Total = 14 NEW BLAZEMASTER PIPE RIgFR ❑_01FAARI V INU I I U OUALL RESIDENTIAL PENDENT SPRINKLER 1) MAXIMUM SPRINKLER COVERAGE NOT TO EXCEED 16' x 16' (sq.ft.). 2) MINIMUM DISTANCE BETWEEN SPRINKLERS TO BE V-0". 3) MAXIMUM DISTANCE FROM ANY WALL SHALL NOT EXCEED 8-4-. 4) PENDENT SPRINKLER SHALL BE LOCATED AT LEAST T-0" FROM OBSTRUCTIONS SUCH AS CEILING FANS AND LIGHT FIXTURES. 5) FOR OTHER OBSTRUCTIONS REFER TO OBSTRUCTION TABLES. 0 ISSUED FOR PERMIT 06/01/23 No REVISIONS DATE (M M/DD/YY) STAMP REVIEW OF THIS DRAWING IS RESTRICTED TO THE NEW WORK ONLYAS IDENTIFIED IN THE SCOPE WITHIN THE CONTRACT srrrrrrrsrarrr rn sr ■•Irrrrr�srs wNiii1li4RI WrAva !f1l. !•ROTiC?'�+ON! amFPR.M#K.li�'t .�'�: (O STANDARD REFERENCE SYSTEM IS DESIGNED TO NFPA 13D (2016) SYSTEM PIPE MAINS LINES WET DRY ❑ SCH.40 ❑ ❑ SCH.10 ❑ ❑ PREACTION ❑ DELUGE ❑ GALV. ❑ ❑ CPVC ❑■ ❑■ ANTI -FREEZE ❑ FOAM -WATER ❑ FITTINGS C.I. ❑ ❑ M.I. ❑ ❑ BLACK ❑ ❑ GALV. ❑ ❑ CPVC 0 0 POUGOL ❑ ❑ VICTAULIC ❑■ ❑■ MECH-T ❑ ❑ PAINTED ❑ 1 ❑ WATER SUPPLY INFO. FIRE PUMP INFO. WATER FLOW TEST BY: RAIN CITY FIRE PROTECTION FIRE PUMP: ❑ DIESEL ❑ ELECTRIC N/A RATED FLOW: GPM RATED PRESSURE PSI DATE: 05/30/2023 STATIC: 83 PSI RESIDUAL: " PSI WATER FLOW: ' GPM IMPORTANT OWNERS TO PROVIDE SUFFICIENT HEAT (MIN. 40°F/5°C) THROUGHOUT AREAS WHERE "WET" SYSTEM ARE INSTALLED TO PREVENT FREEZING OF WATER UNLESS AN ANTI -FREEZE SYSTEM IS PROVED. RAIN CITY FIRE PROTECTION 82201NTERLAKE AVE N. SEATTLE, WA 98103 ALL WIRING DONE SMOKE DETECTORS INSTALLEDDRAIN THROUGHOUTTHE Fuut 1i I i ty / I I I 'j/ / I IIIj/ / .=1 DOUBLE Laun CHECKVALVE P i �,I�III %I / / I , � d �_ 1 PROJECT -• NAME/ADDRESS: FLOW DEL 950XLOSY SWITCH I j I�I j i�l%� j/�IRECEIVED -00 . DOMESTIC ♦ • I / j/ III / I/I / / /I - • SHIR Jun 1 2023 HYDRANT HIGH TEMP C? HIGH TEMPI /I/I//I REQUIRED] - - CITY OF EDMONDS 1 "WATER METER EDMONDS, WA DEVELOPMENT SERVICES ■ 1 �97)' !li �!ill_ l/ 1 (TYPEINCOMING 1" COPPER PIPE OTHERS • URUUNU �LUUR - FLAN SCALE 1 /411=1'-0 Sprinkler Legend - Ground Floor Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature Note Viking VK468 FREEDOM 15 4.9 Pendent '/2 Fast White 155•F 16' x 16' Total = 15 NEW BLAZEMASTER PIPE INSTALLATION OF NEW RESIDENTIAL FIRE PROTECTION SPRINKLER SYSTEM CONTRACT No DATE 1 JUNE 2023 SCALE DRAWING No AS NOTED 2 OF 3 DRAWN BY REVISION CM 0 CHK'D BY GR SCOPE OF WORK: NEW RESIDENTIAL FIRE PROTECTION SPRINKLER SYSTEM FOR NEW CONSTRUCTION. RESIDENTIAL SPRINKLER NOTES: THIRD FLOOR - PLAN SCALE: 1 /4" =1'-0 Sprinkler Legend - Third Floor Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Orifice Finish Temperature Note Viking VK468 FREEDOM 25 4.9 Pendent 1/ Fast 0" White 155°F 16' x 16' Total = 25 NEW BLAZEMASTER PIPE Hydraulic Information Remote Area 1 OCCUPANCY CLASSIFICATION Residential DENSITY (gpm/ft2) 0.05 - Entire Room(Max 2 Heads) TOTAL HEADS FLOWING 2 K-FACTOR 4.9 TOTAL WATER REQUIRED 26.33 TOTAL PRESSURE REQUIRED 61.858 SAFETY MARGIN (psi) +20.296 (24.7%) RESIDENTIAL PENDENT SPRINKLER 1) MAXIMUM SPRINKLER COVERAGE NOT TO EXCEED 16' x 16' (sq.ft.). 2) MINIMUM DISTANCE BETWEEN SPRINKLERS TO BE 8'-0". 3) MAXIMUM DISTANCE FROM ANY WALL SHALL NOT EXCEED 8'-0". 4) PENDENT SPRINKLER SHALL BE LOCATED AT LEAST T-0" FROM OBSTRUCTIONS SUCH AS CEILING FANS AND LIGHT FIXTURES. 5) FOR OTHER OBSTRUCTIONS REFER TO OBSTRUCTION TABLES. 0 ISSUED FOR PERMIT 06/01/23 No REVISIONS DATE (M M/DD/YY) STAMP REVIEW OF THIS DRAWING IS RESTRICTED TO THE NEW WORK ONLYAS IDENTIFIED IN THE SCOPE WITHIN THE CONTRACT srrrrrrrsrarrr ri ■s.awirrrrr�srs WNiii1liN:940" WrAva C=wrwwJiiTw'&w 0,004raymomw !f1li& lROTiO?'�+ON! a�PR.M#K.liAt .�'�: 04 a r„ 04 (O STANDARD REFERENCE SYSTEM IS DESIGNED TO NFPA 13D (2016) SYSTEM PIPE MAINS I LINES WET DRY ❑ SCH.40 ❑ ❑ SCH.10 ❑ ❑ PREACTION ❑ DELUGE ❑ GALV. ❑ ❑ CPVC ❑■ ❑■ ANTI -FREEZE ❑ FOAM -WATER ❑ FITTINGS C.I. ❑ ❑ M.I. ❑ ❑ BLACK ❑ ❑ GALV. ❑ ❑ CPVC 0 0 POUGOL ❑ ❑ VICTAULIC ❑■ ❑■ MECH-T ❑ ❑ PAINTED ❑ ❑ WATER SUPPLY INFO. FIRE PUMP INFO. WATER FLOW TEST BY: RAIN CITY FIRE PROTECTION FIRE PUMP: ❑ DIESEL ❑ ELECTRIC N/A RATED FLOW: GPM RATED PRESSURE PSI DATE: 05/30/2023 STATIC: 83 PSI RESIDUAL: " PSI WATER FLOW: ' GPM IMPORTANT OWNERS TO PROVIDE SUFFICIENT HEAT (MIN. 40°F/5°C) THROUGHOUT AREAS WHERE "WET" SYSTEM ARE INSTALLED TO PREVENT FREEZING OF WATER UNLESS AN ANTI -FREEZE SYSTEM IS PROVED. RAIN CITY FIRE PROTECTION 82201NTERLAKE AVE N. SEATTLE, WA 98103 PROJECT NAME/ADDRESS: PICKERING EDMONDS 304 6TH AVE SOUTH EDMONDS, WA 98020 DESCIPTION: RECEIVED Jun 07 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT INSTALLATION OF NEW RESIDENTIAL FIRE PROTECTION SPRINKLER SYSTEM CONTRACT No DATE 1 JUNE 2023 SCALE DRAWING No AS NOTED 3 OF 3 DRAWN BY REVISION CM 0 CHK'D BY GR