2018 MBP Deck Tip Sheet�MyBui ldi ngPermit.com a service of eCityGov.net Construction Tip Sheet 05 Basic Deck This tip sheet reflects code requirements of the 2018 International Residential Code (IRC) with Washington State Amendments. Typical Deck This document provides building code information applicable to prescriptive residential wood deck design. You may need to hire a licensed architect or engineer to design a deck where any of the following conditions apply: • The deck serves other than a one- or two-family dwelling building • The deck design includes more than one level • The deck will support a hot tub, spa or other heavy object, including heavy deck covering (such as pavers) • The walking surface is more than 14 feet above grade • The deck ledger is attached to house overhangs, bay windows, bricks, stone, or concrete block • The deck is bearing on ground with a slope greater than 1 foot horizontal for every 1 foot vertical • The deck is self-supporting (not attached to an exterior wall) See Detail f for ledge connection options Joist Joist Decking Von fy span ratings of ptoposod docking. Joist Overhang 24" maximum. Joist Spacing F See span table and footing schedule. `f\mil 4x4 min up to 8' 0' height 5x6 min. up to 10'0' hoight Non -corrosive metal post/beam connector Continuous solid blocking between joists Beam Overhang 24" maximum January 14, 2022 See Page 6 for Ledger Attachment � J i y Joist Span See span IADIe Beam Note: Guards are See span table required when the deck walking surface is more Footing than 30" above grade. Soo span table and g footing schedule. MyBuildingPermit.com I Basic Deck eCityGounet M05 -2 eCllyGovAlliance /�MyBui ldi ngPermitxom a service of eCftyGov.net Construction Tip Sheet 05 Deck Construction Notes • Design loading for decks is based on 60 pounds per square feet (PSF) live load, 10 PSF dead load, and 1500 PSF soil -bearing capacity. • The illustrations and information in this tip Sheet may be used for decks whether or not they require a permit. See Tip Sheet 0 for when a permit is required. • All wood must be pressure -treated or naturally resistant to decay. Treat cuts, holes, and notches with end -cut solution. • Fasteners, hangers, nails, etc., must be stainless steel, hot -dipped galvanized, or as specifically required for the specified wood preservative used. The coating weights for zinc -coated fasteners to be in accordance with ASTM A 153. Provide documentation in the field showing the required fastener protection for the wood chosen for your deck. • You may modify any components of this Tip Sheet using accepted engineering practices. Any modifications must be reviewed prior to permit issuance. All attachments must be per manufacturer's installation instructions. • Visit MyBuildingPerm it.com for additional Tip Sheets for stairs, handrails, and notching and boring. January 14, 2022 36" minimum high guard with intermediate rails Attachment of spaced so that a sphere pre -manufactured guardail Existing building 4" in diameter cannot ssystems to onents hdall be per manufaceck turer. pass through (See Tip Flashing Sheet 3). Special blocking details may be required by the reviewer. See detail 1 on page 6 for ledger Refer table on page attachment options 3 for Joist Sizes See page 8 for guardrail post connection Decking and Spans Secure ballusters with (1) #8d wood screw top & bottom Refer o Table on ge 3 for Yy" spacing J recommended ` f BeamSizeand Spans Note: for drainage Contractor to field verify adequacy of Knee braces are required if solid lumber for ledger distance from grade to top of connection. If an exit or egress from post exceeds 48". See detail on page 7 the existing building passes under the proposed deck, or if there For post size and maximum allowable height, see page 4 Is an existing patio under the proposed deck, 6'-8" minimum clearance must be maintained. Please Indicate openings In existing wall in elevation Manufactured post base cast in footing view. Refer to Table on page 4 for Footing Size 3,000 psi concrete (no special inspection required) Finished grade 1"clear Minimum =1�111 i1�IlHll—II II-�.. - (2) h4 ea. way, 3" clear depth of footing 12" �I�II�II-1 IE311�11=111� °. _ tobottom offootin I - Fooling to bear on AWN I 9 ARmi-L„—_r— II undisturbed earth. MyBuildingPermit.com I Basic Deck eCityCounet M05 -�' aCllyGovAllianca �MyBui ldi ngPermitxom a service of eCityGov.net Construction Tip Sheet 05 When using the tables below, interpolation is allowed, extrapolation is not allowed. Sizing of Structural Elements Maximum Deck Joist Span a,c Joist Joist Spacing b inches Joist Back Span Size 12 1 16 1 24 4 6 8 10 12 14 1 16 18 Allowable Joist Span Maximum Cantilever (feet inches Adjacent Joist Span feet 2x6 7-11 7-1 5-9 1-0 1-6 NP NP NP NP NP NP 2x8 10-5 9-5 7-8 1-0 1-6 2-0 2-1 NP NP NP NP 2x 10 13-3 11-6 9-5 1-0 1-6 2-0 2-6 2-8 NP NP NP 2x12 15-5 13-4 10-11 1-0 1-6 2-0 2-6 3-0 3-3 NP NP a. Includes Incising Factor. b. When using composite decking, refer to manufacturer's installation instructions for maximum spacing of joists. c. Spans based on Doug Fir -Larch, Hem Fir and Spruce -Pine -Fir, No. 2 grade, wet service factor. Minimum Beam Size Deck Joist Span feet 6 8 10 12 1 14 16 18 Beam Size c,d,e Maximum Beam Span a,b,d (feet -inches) 4x6 5-2 4-6 4-0 3-5 3-1 2-10 2-7 4x8 6-11 6-0 5-3 4-7 4-1 3-8 3-5 4x10 8-5 7-4 6-6 5-10 5-2 4-9 4-5 4x12 9-10 8-6 7-7 6-11 6-4 5-9 5-4 6x6 6-6 5-7 5-0 4-7 4-2 3-9 3-5 6x8 8-8 7-6 6-8 6-1 5-6 5-0 4-7 6x10 10-7 9-2 8-2 7-6 6-11 6-4 5-10 6x12 12-4 10-8 9-7 8-9 8-1 7-7 7-1 a. Spans based on Doug Fir -Larch, Hem Fir and Spruce -Pine -Fir, No. 2 grade, wet service factor. b. If 2x built up beams to make 4x or 6x beams, they shall be fastened with two rows of 10d (3-inch x 0.128-inch) nails minimum at 16 inches on center along each edge (507.5) c. Beam depth shall be equal to or greater than the depth of intersecting joist for a flush beam connection. d. Beam cantilevers are limited to the adjacent beam's span divided by 4. e. Includes incising factor. January 14, 2022 MyBuildingPermit.com I Basic Deck eCityGounet 2d05 � aCllyGavAlliance ,000w�'yBui ldi ngPermit.com a service of e0tyGov.net Construction Tip Sheet 05 Maximum Deck Post Height Tributary Area e Post 20 40 60 80 1 100 120 140 160 Size c,d Maximum Deck Post Height a feet -inches 4x4 10-0 10-0 8-7 7-0 5-8 4-1 N P N P 4x6 14-0 13-10 11-1 9-5 8-2 7-3 6-4 5-4 6x6 14-0 14-0 14-0 14-0 14-0 13-3 10-9 6-11 8x8 14-0 14-0 14-0 14-0 14-0 14-0 14-0 14-0 a. Measured from the underside of the beam to top of footing. b. Based on Doug Fir, Hem Fir and Spruce -Pine -Fir, No. 2 grade, wet service factor. c. Notched deck posts shall be sized to accommodate beam size. d. Includes incising factor. e. Area, in square feet, of deck surface supported by post and footing. Footing Size a Tributary Area b Side of Square Footing (inches) Diameter of a Round Footing inches Thickness (inches) 5 7 8 6 20 12 14 6 40 18 20 6 60 21 24 8 80 25 28 9 100 28 31 11 120 30 34 12 140 33 37 13 160 35 40 1 15 a. Footing dimensions shall allow complete bearing of the post. b. Area, in square feet, of deck surface supported by post and footings. 12" min. frost depth in allowable soils Grade III „� 1 21 III 6 Thickness per Table Q Note: Posts must be Width centered on or in footing per Table January 14, 2022 — Manufactured post connector 12" t1" d a G d 112" diameter through -bolts in both 4" gravel directions Note: not screws MyBuildingPermit.com I Basic Deck Typical P.T. post Min. 12" of embedment eCityCounet M05 � aC11VCovA 1ianca �MyBui ldi ngPermitxom a service of eCityGov.net Deck Ledger and Connections Construction Tip Sheet 05 Deck Ledger Connection to Band Joist On -Center Spacing of Fasteners inches Joist Span c (feet) '/2-inch diameter lag screw with 1/2-inch maximum sheathing b,c,e '/2-inch diameter bolt with '/2-inch maximum sheathing c '/2-inch diameter bolt screw with 1-inch maximum sheathing d 6 22 36 35 8 16 31 26 10 13 25 21 12 11 20 17 14 9 17 15 16 8 15 13 18 7 13 11 a. Ledgers shall be flashed in accordance with Section R703.4 to prevent water from contacting the house band joist. b. The tip of the lag screw shall fully extend beyond the inside face of the band joist. c. Sheathing shall be wood structural panel or solid sawn lumber. d. Sheathing shall be permitted to be wood structural panel, gypsum board, fiberboard, lumber, or foam sheathing. Up to 1/2-inch thickness of stacked washers shall be permitted to substitute for up to 1/2-inch of allowable sheathing thickness where combined with wood structural panel or lumber sheathing. e. For on -center spacing of specialized fasteners refer to the manufacturer's installation instructions. Placement of Lag Screws and Bolts in Ledgers and Band Joists Minimum End and Edge Distance and Spacing Between Rows Top Edge Bottom Edge Ends Row Spacing Ledger a 2 inches d 3/4 inch 2 inches b 1-5/8 inches b Band joist ` 3/4 inch 2 inches e 2 inches b 1-5/8 inches b a. Lag screws or bolts must be staggered from the top and bottom along the horizontal run. See figure below. b. Maximum 5 inches. c. For engineered rim joists, the manufacturer's recommendations govern. d. The minimum distance from the bottom row to the top edge of the ledger must be in accordance with figure below. e. 2 inches may be reduced to 3/4-inch when the band joist is directly supported by a mudsill, header, or by double top wall plates. January 14, 2022 MyBuildingPermit.com I Basic Deck eCityGounet 2d05 � aCllyGavAlliance �MyBui ldi ngPermitxom a service of eCityGov.net EXTERIOR SHEATHING EXISTING STUD WALL Existing 2x BAND JOIST OR ENGINEERING RIM BOARD Construction Tip Sheet 05 2" MIN o DECK JOIST S MAX LAG SCREWS OR BOLTS 2' MIN • ='t'• : �'/�•. I JOIST HANGER Lag screw or bolt 2" min. 5" max. "2" min. Minimum edge distance for specialized screws. See manufacturer's technical bulletin. Hold-down or tension device with 1500 # capacity Flashing Dock Joist January 14, 2022 Ledger Stagger fasteners in 2 rows S 112" min. for 2x8 6 112" min. for 2x10 7 112" min. for 2x12 ' ­1, 3/4" min. Distance can be reduced to 4 112" if lag screws are used or if bolt spacing is reduced to that of lag screws to attach 2x8 ledgers to 2x8 band joists Detail 1 — Ledger Attachment for Lateral Loads (Knee braces are required on posts greater than 4 feet in height.) Option # 1 Floor sheathing nailing at 6' o.c. (max) to joist with hold-down. Sheathing Siding Flashing Decking Joists Joist Hangers Treated 2x ledger FloorMst 750# capacity holddown device at 4 locations evenly distributed along the deck and within 2 ft of each end. Install per manufacturer Fully threaded 3/8" diameter lag screw) predrilled with a minimum of 3 in Option # 2 embedment into solid framing. MyBuildingPermit.com I Basic Deck 2' min. Floor joists eCityGounet 2d[l5 � aCllyGavAlliance �My6ui ldi ngPermitxpm a service of eCityGov.net Construction Tip Sheet 05 Connections and Fasteners (All fasteners, nails, bolts, screws, and connectors must be corrosion resistant.) Type of Connection: Notes: Manufactured Connectors Follow manufacturer's instructions Post to Footing Post base is required Post to Footing (High Winds) Consult with jurisdiction about additional uplift loads where wind exposure is greater than Risk Category B Post to Beam Connector is required Ledger to House Framing See information on Sheet 5 and Sheet 6 Joist to Beam or Girder 3 8d — Toe nailed Blocking or Bridging to Joist (2) 10d — Toe nailed at each end Wooden Deck Boards 2 8d threaded nails OR 2 No. 8 screws Composite Decking Follow manufacturer's instructions Post to Beam Connection with Knee Brace (Knee braces are required on posts greater than 4 feet in height.) or 113 the height of the post. whichever Is greater Beam spllces must occur aver pasts witlr 1-112" min- bearing Corroslon resistant, rnin. metal columns cap. Girder beam Fallow rnanufacturer's zi Installation instruct,ions, 45� 4 x 4 knee brace {11 } 318" diameter Mru-bolt or 112 " Alternate knee Brace Detail: lag screws with washers, top 8. bottom 2x4 knee brace face nailed ea- side of ` (typical) post and beam with 4-1$¢ nails at each Pressure treated face and connection woad post January 14, 2022 MyBuildingPermit.com I Basic Deck eCityGounet 2d05 � aCllyGavAlliance ,000w�'yBui ldi ngPermit.com a service of eCityGov.net Construction Tip Sheet 05 Guards & Attachment Guards are required when the deck is more than 30 inches above grade.) 2x2 Baluster, typical 6-0" max. spacing 2x5 or 5/4 board ail cap: attach to guard post with (3) #12 by 3" long screws or (3) 15d threaded nails with 0.148 nominal diameter 2x4 top and bottom; attach to guard post with (2) 8d threaded nails or (2) #8 wood screws 2 1/2" long on inside face 4x4 guard post, typical Do Not Notch 2 x 8 nominal rim or outside joist, minimum 2 5/8" diameter openings shall Attach balusters at top and bottom with through -bolts not allow the (1) #8 wood screw or (2) 8d post -frame and washers passage of a 4" threaded nails with 0.135 nominal diameter sphere diameter 16. max A O.D. galvanized bolt or threaded rod w/ nuts & washers 2'/i' min a ad 5" max Min. 1800# tension device 5/s" O D. galvanized bolt or threaded rod wl nuts & washers 2x8 min. deck 2"min I joists & rims 2,�minand 5"max" 2"min 4x4 min. post @ 60" o.c. max., Typ 2"min Section A 2x8 min. blocking 2"min Now: Use above details for guard connections or provide engineered Min. 1800# tension straps design that shows Guards can resist a single concentrated load of 200 Ibs applied in any direction at any point along the top and Section B have attachment devices and supporting structure to transfer this load to appropriate structural elements of the building per IBC sec 1607.7.1.1 January 14, 2022 MyBuildingPermit.com I Basic Deck eCityCounet M05 � aCIIVGavA Iianca