APPROVED BLD-BLD2023-0040+Architectural_Plan+1.10.2023_4.15.28_PM+33078481
2
3
M
5
d
7
F
E
FBI
C
LEGEND OF SYMBOLS
DETAIL 1 ACOUST
1 DETAIL IDENTIFICATION A101 — ACSF
A101 IDENTIFICATION ACT
SHEET IDENTIFIER f l
SHEET IDENTIFIER l I
DETAIL DETAIL VIEW BUBBLE ADJ
AFF
VIEW NUMBER VIEW IDENTIFICATION AL
1 1 A LT
Al AXXX
A101 A101 �/— SHEET LOCATION ANOD
/
APPROX
BUILDING SECTION SHEET IDENTIFIER MATCH LINE REFERENCE ARCH
ASPH
DETAIL IDENTIFICATION __ DETAIL IDENTIFICATION BD
1 1 BIT
A101 A101 BLDG
SHEET IDENTIFIER !` SHEET IDENTIFIER BLK'G
WALL SECTION DETAIL SECTION BM
1 Ref BO
1 DETAIL IDENTIFICATION DETAIL i m BOTBTWN
A101 SHEET IDENTIFIER IDENTIFICATION 1 A101 1 CAB
- SHEET CB
EXTERIOR ELEVATION INTERIOR ELEVATION IDENTIFIER CEM
1 Ref C G
ROOM NUMBER Room nam a Cl
101 CIP
AREA CJ
DOOR NUM BERS
ROOM NAM E& NUMBER CL
C LG
C LR
CMU
1tCID COL
CONIC
WINDOW NUMBER EQUIPMENT TAG CONN
CONST
CONT
1 CORR
CPT
1 I
CR
KEY NOTES WALL TYPE CT
C U FT
LEVEL NAME DDEPT
IRV 0'-0" AFF DIA
DIM
DATUM ELEVATION REVISION DELTA & CLOUD q1 DISP
DN
DS
+O'-O 11 DTL
DWG
EA
DATUM INDICATOR SPOT ELEVATION EFS
EIFS
EXIT END — SEGMENT DISTANCE
45'-0"
EJ
Exit Corridor EXIT PATH EXTENT OF EL
EXIT END WORK ELEC
EXIT ROUTE EXIT PATH NAME EXTENT OF WORK ELEV
EPT
EPX
VIEW SCALE EQ
NUMBER 1 (OPTIONAL) EQUIP
0' 20' 40' EW
VIEW TITLE DETAIL SCALE EWC
EW H
EXH
A A EXIST
NEW GRID EXISTING EXP
GRID EXT
GRID LINE BUBBLE FAC FIN
FD
FDN
NON RATED PROJECT NORTH - FE
FEC
1-HOUR RATED ORIENT TO BUILDING FF
2-HOUR RATED FF&E
3-HOUR RATED TRUE NORTH
4-HOUR RATED FIN
FLR
PARTITION FIRE RATINGS NORTH ARROW FO
FO C
FO F
M ATERIALS FO IC
FO 10
FO S
ACOUSTICAL TILE GRAVEL FRP
FRT
ALUMINUM 0 GYPSUM BOARD FS
FT
BATT INSULATION PLYWOOD FTG
FU RN
FU RR
CM OR BRICK RIGID INSULATION FWP
GA
CONCRETE SOUND INSULATION GALV
GB
0 EARTH STEEL GC
GI
FINISHED WOOD WOOD BLOCKING GL
GWB
GYP
WOOD M EMBER HB
HC
HDWR
HG
HM
DEFERRED SU BM ITTALS HORIZ
HP
HT
HTR
HVAC
IBC
ID
IE
IN
INSUL
INT
JAN
JT
L
LAM
LB
LF
ABBREVIATIONS
ACOUSTICAL
LIQ
LIQUID
ACCESS FLOORING
LMC
LINEAR METAL CEILING
ACOUSTICAL CEILING TILE
LP
LOW POINT
OR PANEL
LT
LIGHT
ADJACENT
LT WT
LIGHT WEIGHT
ABOVE FINISHED FLOOR
MAS
MASONRY
ALUMINUM
MAX
MAXIMUM
ALTERNATE
MECH
MECHANICAL
ANODIZED
MEZZ
MEZZANINE
APPROXIMATE
MFCR
MANUFACTURER
ARCHITECTURAL
M H
MANHOLE
ASPHALT
MHO
MAGNETIC HOLD OPEN
BOARD
MIN
M INIM UM, M INUTES
BITUMINOUS
MISC
MISCELLANEOUS
BUILDING
MO
MASONRY OPENING
BLOCKING
MR
MOISTURE RESISTANT
BEAM
MTD
MOUNTED
BOTTOM OF
MTG
MOUNTING
BOTTOM
MTL
METAL
BETWEEN
MULL
MULLION
CABINET
NA
NOT APPLICABLE
CATCH BASIN
NIC
NOT IN CONTRACT
CEMENT
NO
NUMBER
CORNERGUARD
NOM
NOMINAL
CAST IRON
NITS
NOT TO SCALE
CAST IN PLACE
CA
OVERALL
CONSTRUCTION JOINT,
OC
ON CENTER
CONTROL JOINT
OD
OUTSIDE DIAM ETER
CENTERLINE
OH
OVERHEAD
CEILING
0PN'G
OPENING
CLEAR
OPP
OPPOSITE
CONCRETE MASONRY UNIT
PERP
PERPENDICULAR
COLUMN
PL
PROPERTY LINE, PLATE
CONCRETE
PLAM
PLASTIC LAMINATE
CONNECTION
PLAS
PLASTER
CONSTRUCTION
PLBG
PLUMBING
CONTINUOUS
PLT
PLATE
CORRIDOR
PLYWD
PLYWOOD
CARPET
PNL
PANEL
CARD READER
PR
PAIR
CERAMIC TILE
PREFIN
PREFINISHED
CUBIC FEET
PRESS T
PRESSURE TREATED
DEPARTM ENT
PROJ
PROJECT
DRINKING FOUNTAIN
PT
POST -TENSIONED,
DIAMETER
POINT, PAINT
DIMENSION
QT
QUARRY TILE
DISPENSER
QTR
QUARTER
DOWN
R
RADIUS, RISER
DOWNSPOUT
RB
RESILIENT BASE, RUBBER BASE
DETAIL
RCP
REFLECTED CEILING PLAN
DRAWING
RD
ROOF DRAIN
EACH
REC'D
RECEIVED
EXTERIOR FINISH SYSTEM
REF
REFERENCE
EXTERIOR INSULATION
REFR
REFRIGERATOR
& FINISH SYSTEM
REIN F
REINFORCING
EXPANSION JOINT
REQ'D
REQUIRED
ELEVATION
RF
RUBBER FLOORING
ELECTRICAL
RM
ROOM
ELEVATOR
RO
ROUGH OPENING
EPDXY PAINT
ROW
RIGHT OF WAY
EPDXY -QUARTZ FLOORING
SAN
SANITARY
EQUAL
SC
SOLID CORE
EQUIPMENT
SCHED
SCHEDULE
EACH WAY
SECT
SECTION
ELECTRIC WATER COOLER
SF
SQUARE FEET
ELECTRIC WATER HEATER
SHT
SHEET
EXHAUST
SHT MTL
SHEET METAL
EXISTING
SIM
SIM ILAR
EXPOSED STRUCTURE
Si
SCORE JOINT
EXTERIOR
SPEC
SPECIFIED, SPECIFICATION
FACTORY FINISH
SQ
SQUARE
FLOOR DRAIN
SS
SANITARY SEWER
FOUNDATION
SST
STAIN LESS STEEL
FIRE EXTINGUISHER
ST
STONE MASONRY OR TILE
FIRE EXTINGUISHER CABINET
STD
STANDARD
FINISHED FLOOR
STL
STEEL
FURNITURE, FIXTURES
STOR
STORAGE
& EQUIPMENT
STRUCT
STRUCTURAL
FINISH
SUSP
SUSPENDED
FLOOR
SYM
SYMMETRICAL
FACE OF
SYS
SYSTEM
FACE OF CONCRETE
T
TOP,TREAD
FACE OF FINISH
T&B
TOP AND BOTTOM
FU RN ISH ED BY OW N ER
T&G
TONGUE & GROOVE
INSTALLED BY CONTRACTOR
TBD
TO BE DETERM INED
FURNISHED BY OWNER
TEL
TELEPHONE
INSTALLED BY OWN ER
TEMP
TEMPORARY
FACE OF STUD
TER
TERRAZZO
FIBER REINFORCED PLASTIC
TOC
TOP OF CONCRETE
FIRE RETARDANT TREATED
TOJ
TOP OF J OIST
FLOOR SINK
TOM
TOP OF MASONRY
FOOT/FEET
TOP
TOP OF PARAPET
FOOTING
TOS
TOP OF STEEL / STUD
FURNISHED
TOW
TOP OF WALL
FURRING
TYP
TYPICAL
FABRIC WRAP WALL PANEL
UL
UNDERWRITER'S LABORATORIES
GAUGE
LINO
UNLESS NOTED OTHERWISE
GALVANIZED
UTL
UTILITY
GRAB BAR
VAR
VARNISH
GENERAL CONTRACTOR
VB
VINYL BASE
GALVANIZED IRON
VCT
VINYL COMPOSITION TILE
GLASS
VERT
VERTICAL
GYPSUM WALLBOARD
VEST
VESTIBULE
GYPSUM
VIF
VERIFY IN FIELD
HOSE BIBB
VP
VENEER PLASTER
HOLLOW CORE
VT
VINYL TILE
HARDWARE
VTF
VINYL TILE FLOORING
HARDWAREGROUP
W/
WITH
HOLLOW METAL
W/O
WITHOUT
HORIZONTAL
WB
WOOD BASE
HIGH POINT
WC
WATER CLOSET, WALL COVERING
HEIGHT
WD
WOOD
HEATER
WDC
WOOD CEILING
HEATING, VENTILATION
WDP
WOOD PANELING
& AIR CONDITIONING
WF
WOOD FLOORING
INTERNATIONAL BUILDING CODE
WIN
WINDOW
INSIDE DIAMETER
WOM
WALK OF MAT OR CARPET
INVERT ELEVATION
WP
WATERPROOF,OR WORK POINT
INCH
W R
WATER RESISTANT
INSULATION
WRB
WEATHER RESISTANT BARRIER
INTERIOR
W S
WEATHERSTRIP
JANITOR
WSCT
WAINSCOT
JOINT
WT
WEIGHT
LENGTH, LONG
WWF
WELDED WIRE FABRIC
LAM INATE
YD
YARD
POUND
LINEAR FEET
PROJ ECT SCOPE
ADDRESS:
PARCEL NUMBER:
OWNER:
LEGAL DESCRIPTION:
N U M BER O F STO RIES
LOT SIZE:
ZONING:
JURISDICTION:
PROJECT DATA
SINGLE-FAMILY HOUSE INTERIOR REMODELS, INCLUDING THE
EXISTING MASTER BEDROOM, BATHROOM, AND KITCHEN
REMODELING, EXISTING OPENINGS ALTERATION, AND
CONVERTING THE EXISTING WOOD BURNING FIREPLACETO GAS.
NO GROUND DISTURBING ACTIVITY.
23519 78TH AVEN UE W, EDMON DS, WA 98026
00465600001200
BLACKER AUSTIN/J UTILA STEPHAN D
HARVEYS ADD BLK 000 D-00 - LOT 12
1
0.19 ACRES
RS-8
CITY OF EDM ONDS
BUILDING AREA
EXISTING MAIN FLOOR (SF): 1724
EXISTING DETACHED GARAGE (SF): 280
NO EXTERIOR WORK IS PROPOSED
CODE INFORMATION
PROJ ECT IS TO M EET REQUIRED NATIONAL, STATE, AND LOCAL CODES
AND ORDINANCES ADOPTED INCLUDING THE FOLLOWING:
INTERNATIONAL BUILDINGS CODE, IBC 2021
2018 WASHINGTON STATE ENERGY CODE
EDMONDS CITY CODE
ENERGY ANALYSIS
PRESCRIPTIVE PATH PER TABLE R402.1.1:
R402.12 WOOD FRAME WALL: R-21 INTERMEDIATE FRAMING / U-0.056
R402.12 CEILINGS: R-49 / U-0.026
R402.1.2 BASEMENT WALLS:R-10 CONTINUOUS INSULATION ON THE EXTERIOR OF
THE WALL, R-15 CONTINUOUS INSULATION ON THE INTERIOR OF THE WALL
R402.12 SLAB: R-10,2 FT./ F- FACTO R - 0.54
R402.12 FEN ESTRATION:U-0.30
2018 WASH INGTON STATE ENERGY CODE REQUIREM ENTS
SEC.401.3 POST ENERGY CODE CO PLIANCE CERTIFICATE WITHIN
3 FT. OF ELECTRICAL PANEL
SEC. 402.4.12 PROVIDE DOOR BLOW ER TEST AFFIDAVIT BY FINAL
BUILDING INSPECTION
SEC. 403.1.1 PROVIDE (1) PROGRAMMABLE THERMOSTAT
SEC. 403.3.3 PROVIDE DUCT SEALING AFFIDAVIT BY FINAL INSPECTION
SEC. 404.1 A M INIM UM OF 90% OF ALL INTERIOR LIGHTING SHALL BE
OF HIGH EFFICIENCY
VIC IN ITY MAP
DRAWING INDEX
Sheet Name
A001
GENERAL INFORMATION
A002
CODE NOTES
A200
EXISTING MAIN FLOOR
A201
PROPOSED MAIN FLOOR
A300
EXISTING ELEVATIONS
A301
PROPOSED ELEVATIONS
A302
DETAILS
City Of Edmonds
Building Department
Work INTERIOR REMODEL
Address 23519 78TH AVE W
Owner BLACKER
Approved Date 2/17/2023
Building Official te4x4 �/px jelal
Permit Number BLD2023-0040
OBTAIN ELECTRICAL
PERMIT FROM
STATE LABOR &
INDUSTRIES
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
-- — - — - — - — - — - — - — - — -
APPROVED INSTALL ALL EQUIPMENT PER ,
PLANS MUST BE MANUFACTURERS
ON JOB SITE ' SPECIFICATIONS. HAVE ALL
MANUFACTURERS '
--------------------� DOCUMENTATION ON SITE.
I SEPARATE PLUMBING PERMIT
REQUIRED FOR THIS PROJECT. I L-_-_-_-_-_-_-_-_-I
L-- — - — - — - — - — - — - — - — - — -
Interconnected Smoke Alarms Are A Requirement;;
Of This Permit In Accordance With R314.2.2
PROJECT DIRECTORY
OWNER DESIGN
BLACKER AUSTIN/J UTILA STEPHAN D GO.Design
208.597.5143 Olena Gaivoronska
stephanjutila@com cast.net 425.595.0691
23519 78TH AVENUE W Gaivoronska.olena@gm ail.com
EDMONDS, WA 98026 2002 101ST AVE SE
LAKE STEVENS, WA 98258
GENERAL CONTRACTOR
HOM E CARE CONTRACTORS
ALEX N IKITEN KO
206-446-5656
alexn@hom ecarecontractors.com
10634 E RIVERSIDE DR SUITE 250
BOTHELL, WA 98011
STRUCTURAL
NEW APPROACH
EN G IN E E R I N G,LLC
Ruslan M aksim enko
425.777.5635
newapproachengineering@gm ail.com
GENERAL NOTES
1. DO NOT SCALE THE DRAW ING
2.VERIFY FIELD DOCUMENTS PRIOR TO COMMENCEMENT OF EACH PORTION OF THE WORK
3.THE CONTRACTOR SHALL COORDINATE ALL PORTIONS OF THE WORK AS DESCRIBED IN
THECONTRACT DOCUMENTS. NOTIFY THE ARCHITECT FOR RESOLUTION OFALL
DISCREPANCIES PRIORTO CONSTRUCTION.
4.DIMENSIONSARETO THESTRUCTURAL GRID ORTO FACEOF STUD. UNLESS OTHERWISE
INDICATED.
5.DOORSAND CASED OPENINGS INDICATED NEARBY WALL INTERSECTIONS SHALL BE
LOCATED SO THAT THE EDGE OF THE FINISH OPENING IS 4 INCHES FROM THE FACE OF THE
NEARBY WALL UNLESS OTHERWISE INDICATED. ALL OTHER DOORS AND CASED OPENINGS
SHALL BECENTERED BETWEEN ADJACENT WALL INTERSECTIONS.
0on
HCC
oct[inq thn sstan-d8rd
SERVICES@HOM ECARECONTRACTORS.COM
206.984.4543
Oe design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SINGLE- FAMILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVENUE W
EDM ON DS, WA 98026
All rights reserved. No part of this document maybe reproduced in any
form or by any means without permission in writing from GO.design
NO. DATE DESCRIPTION
GENERAL
INFORMATION
Project N u m ber 2215
Date 01/08/23
Drawn By GO.design
60ft
1 1 2 1 3 1 4 1 5 1 6 1 7 1
A001
1 2
3
d
7
F
E
FBI
C
C
IT
Division 1
GENERAL REQUIREMENTS
01000 GENERAL
1.This coversheet has been prepared in a generic outline form following the standards set by the Construction Standards
Institute (CSI). It is for the convenience of the Contractor/Owner. This outline is intended to work with a m aterial selection
list following the (CSI)form at. Not all items are necessarily required to complete this specific project. Coordinatewith
Contractor/Owner for com plete listing of specifications. W ithin this coversheet it will state, "Coordinate with m aterials
finish selection schedule".
2. These drawings are copyrighted. GO.design retains all rights, ownership and copyright of this design under the federal
copyright act. Reproductions of illustrations or working drawings in any form is by authorization of GO.design only.
3. Authorized reproductions m ust bear the nam e of GO.design
4.Construction/working drawings by their very nature are diagram m atic and do not purport to show all details or
conditions of construction. Questions generally arise to the architectural/design intent and to construction technical
detailing within these drawings. As clarifications, interpretations, and revisions are all part of the construction process
GO.design, therefore shall not be liable for any direct, indirect, or consequential damages as a result of not participating in
the construction process.
5. Do not vary or m odify the work shown, except with written instruction from GO.design.
Report discrepancies and/or om issions to the architect im m ediately.
6. Due to the nature of construction and the building process there will be bidder design and Contractor/Owner selection
of the building products, com ponents, and assem blies. This set of working drawings is considered a "builder set" and does
not include specifications or building m aterials list. Therefore it is the Contractor/Owners responsibility to provide and
coordinate specifications, including product selection and installation or assem bly. GO.design assumes no liability or
responsibility for discrepancies or conflicts which occur through Contractor/Owner specified m aterials and their respective
installation. GO.design assum es no liability or responsibility for any item s,which m ay be called out or referred to by
manufacturer as brand name. Items called out are done so for convenience only.
7. Do not scale these drawings for critical dim ensions. Verify all dimensions and datum 's before com m encing work and be
responsible for their accuracy. Report discrepancies and/or om issions to the architect immediately.
8. The Contractor/Owner is responsible for coordinating work with all trades to ensure proper and adequate interface of all
trade works. The contractor shall be responsible for all required safety precautions and procedures required to do this
work.
9. Except as specifically defined otherwise, interpretation for all definitions, abbreviations, and supplemental definitions shall
follow accepted referenced standards.
10. All work within this contract shall represent that of industry standards for the respective trades in the location in which
the project is built.
ALL REFERENCES TO I.R.C, I.B.C.,AND W.S.E.0 ARE REFERENCES TO THE 2018 CODE UPDATES & WA STATE
AMENDMENTS
01002 MISCELLANEOUS ASSEMBLY REQUIREMENTS
1. CRAWL SPACE
Provide crawl space access, m inim um 18" x 24" unobstructed access through the floor, 16" x 24" through perimeter walls
and below grade access, per I.R.C. section R408.4.Insulate and weather-strip per W.S.E.0 R4022.4.Allow 18" m inim um
space under wood joists and 12" m inim um space under wood girders.
2. ATTIC SPACE
Provide attic access, m inim um 22" x 30" with 30" m inim um headroom ,at unobstructed readily accessible opening, per
I.R.C. section R807.1. Insulate and weather-strip per W SEC R402.2.4. requirem ents.
3. PROVIDE VENTILATION PER I.R.C.:
• Crawl space ventilation: M inim um net area shall be not less than 1 s.f. per 300 s.f. under floor area. Required
openings shall be evenly placed to provide cross ventilation of the space except one side of the building shall be
perm itted to have no ventilation openings per section R4082.
• Attic ventilation: Minim um net area shall be not less than 1 s.f. per 150 s.f. of attic area or 1 s.f. per 300 s.f.of attic
area if at least 40 percent, and not m ore than 50 percent, of the required ventilating area is provided by
ventilators located in the upper portion of the space to be ventilated, and is no m ore than 3 feet below the ridge
or highest point of the space. The balance of required ventilation to be provided by eave or cornice vents per
I.R.C.section R8062 and W.S.E.C. requirements.
4. PROVIDE SLOPE:
All decks, walks, driveways, exterior door landings, and patios sloped away from building: Minim um 1/4" per foot.
5. SIGNAGE:
Provide approved num bers or addresses in such a position as to be plainly visible and legible from the street or road
fronting the property per I.R.C.section R319.1.
6. GARAGE/HOUSE SEPARATION:
• Garage ceilings separating attic spaces shall be protected with 1/2" G.W.B. When garages are beneath habitable
room s, the ceilings shall be covered with 5/8" type "x" GWB on the garage side. Where the separation is a
floor/ceiling assem bly, the structure shall be protected with 1/2" G.W.B. per I.R.C. table R302.6.
• Door between garage and house shall be a self closing solid wood core, honeycom b core steel, or 20-minute fire
rated door having a minimum thickness of 1-3/8" per I.R.C.section R302.5.1.
• Ducts in the garage and ducts penetrating the walls or ceilings separating the dwelling from the garage shall be
constructed of a minimum No.26 gage sheet steel or other approved material and shall have not openings into
the garage per I.R.C. R302.52.
• Garage floor shall slope to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway.
7. STAIR ASSEMBLY:
• Minimum headroom height 6'-8" per I.R.C.section R311.72.
• Minimum stair tread depth 10" with a 36" minimum width, measured above handrail height.
Maximum riser height 7-3/4" per I.R.C. sect ions R311.7.5
• Top of handrail shall be 34" minimum and 38" m axim um above tread nosing and not less than 1-1/2" from
the wall. Return rail ends to wall per I.R.C. section R311.7B.
• Install fire blocking between stringers at the top and bottom of each run per I.R.C.section R302.11.
• Cover usable space under stairs with 1/2" GWB per I.R.C.section R302.7.
• Required railings shall not have openings that allow passage of a sphere 4 inches in diam eter from the
walking surface to the required railings height.
• Railings shall be designed to resist a concentrated load of 200 lb.
• Railings shall be designed to resist a linear load of 50 pounds per linear foot.
• Interm ediate rails, balusters,and panel fillers shall be designed to resist a concentrated load of 50 pounds.
8. LAUNDRY CHUTES& DUMBWAITER SHAFTS:
Provide 5/8" type "x" GWB or 26 gage sheet metal with lock joints on all openings to shaft surfaces shall be self closing solid
core door 1-3/8".
9. FIREBLOCKING SHALL BE PROVIDED IN WOOD -FRAME CONSTRUCTION, AS FOLLOWS:
• In concealed spaces of stud walls and partitions, including furred spaces and parallel rows of studs or staggered
studs, as follows:
1. Vertically at the ceiling and floor levels.
2. Horizontally at intervals not exceeding 10 feet.
• At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings
and cove ceilings.
• In concealed spaces between stair stringers at the top and bottom of the run. Enclosed spaces under stairs shall
comply with Section R302.7.
• At openings around vents, pipes, ducts, cables and wires at ceiling and floor level, with and approved m aterial to
resist the free passage of Elam a and products of com bustion.
• For the fireblocking of chim neys and fireplaces, see Section R1003.19.
• Fireblocking of cornices of a two-fam ily dwelling is required at the line of swelling unit separation.
10. FIREBLOCKING SHALL CONSIST OF THE FOLLOWING MATERIALS PER I.R.C.R302.11.1.
• 2" nominal lumber.
• Two thickness of 1" nom inal lum ber with broken lap joints.
• One thickness of 22/32" wood structural panels with joints backed by 23/32" wood structural panels.
• One thickness of 3/4" particleboard with joints backed by 3/4" particleboard.
• One 1/2" gypsum board.
• One 1/4" cem ent-based m illboard.
• Batts or blankets of mineral wool or glass fiber or other approved materials installed in such a manner as to be
securely retained in place.
11. STRUCTURAL DESIGN CRITERIA:
These notes are provided for convenience only and do not im ply that complete structural analysis has been done on this
structure.
• Truss Loading: (U.N.O.)
Top chord live load: 25psf
Top chord dead load: 7psf (15 psf, if tile)
Bottom chord live load: 10 psf without storage, 20psf if lim ited storage, 30 psf if sleeping room
TOTAL LOAD:42psf or 52psf or 62psf
• Roof live load: 25 psf (U.N.O.)
• Floor live load: 40 psf (U.N.O.) Deck Live Load 60 psf U.N.O.
• Stair and corridor live load: 40 psf
• Mechanical units: weights provided by manufacturer
• Wind: 110 mph (U.N.O.)
• Seism is Design Category: D(2) (U.N.O.)
• Allowable soil pressure: Unless a soils report by a qualified engineer is provided,all footings and foundations shall
be on assum ed 1,500 psf bearing capacity unless otherwise noted on drawing.
• Equivalent fluid pressure 35 pcf. (U.N.O.)
• All footings to be located below the frost line depth: 18" (U.N.O.)
12. PREFABRICATED FIREPLACES AND SOLID FUEL BURNING APPLIANCES PER I.M .C. & I.R.C. CHAPTER 101:
• Solid fuel burning appliances include airtight stoves, fireplace stoves, room heaters/fireplace stoves,factory
built fireplaces, and fireplace inserts,and all shall com ply with the provisions of I.M.C.
• Metal Chim neys shall be enclosed above the story in which the appliance served is located, in walls having one
hour fire resistance rating, and with a space on all sides between chimney and enclosing walls sufficient for
exam ination and repair for entire chim ney. Walls shall be without openings per I.M G.
• Provide fireblocking at chim ney per I.R.C. section R302.11.
• Install m etal fireplace with hearth and surrounds per m anufacturers specifications.
• Prefabricated fireplaces, chimneys, and related com ponents to bear U.L.or ICBO seal of approval and be installed
per manufacturers requirements.
13. SAFETY GLAZING:
• Provide safety glazing per 2018 International Residential Code (IRC)
• Where safety glazing is required, each pane m ust be provided with a m anufacturer's label defining the type of
glass and safety glazing standard to which it com plies. The label m ust be perm anently etched, fired, or em bossed,
on the glass or be a type that once applied cannot be rem oved without being destroyed.
14. SMOKE DETECTORS:
• Install sm oke detectors in all sleeping room s and adjacent areas, and at ceiling height changes greater than 24".
Smoke detectors to be hard wired and interconnected, with battery backup per code.Sm oke detectors:
* Shall be 110 v interconnected w/ battery backup
*Shall be installed on each floor and in all bedrooms
* Shall be installed in each location where there is ceiling change greater than 24"
• Carbon monoxide detectors are required if an attached garage and/or fuel fired equipm ent is present.
15.INTERIOR FINISHES
All interior finishes to m eet m inim i--n flam a spread index and sm oke developm ent index as required by 2018 IRC2
01060 REGULATORY REQUIREMENTS
• All construction shall conform to the 2018 International Residential Code (I.R.C.),
2018 International Building Code (I.B.C.),2018 International Fire Code (I.F.C.),
2018 International Mechanical Code (I.M.C.), 20 18 Uniform Plum bing Code (U.P.C.),
2018 Washington State Energy Code (W.S.E.C.) and be in accordance with all State Laws and Regulations and
various codes imposed by jurisdictional requirements and local authorities.
• Arrange inspections that are m andatory due to jurisdictional requirements.
0 150 0 CONSTRUCTION FAG ILIT IES AN D TEM PORARY C 0 N TRO LS
• Provide Tern porary Facilities - including electricity, water, and tem porary toilet, per jurisdictional requirem ents.
• Provide Contem porary Controls - including erosion sedim ent and surface water control and entrapm ent during
construction per jurisdictional requirem ents.
Division 2
02200 EARTHWORK
• Rough grading: 4" below finish grading unless otherwise specified.
• Finish grading: Landscaping division 02900.
• Excavation, backfilling, and com pacting for structures as needed.
• Excavation, backfilling, and com pacting for pavement as needed.
• Hauling and disposal of excavated material as needed.
• Importing of material as needed.
• Rock rem oval as needed.
02500 PAVING AND SURFACING
PART 2-PRODUCT
1. Walk, road, and parking paving:
A. Asphalt 2", class B, over 3" crushed rock or 2" ATB.
B. Crushed rock 5/8" minus.
C. Concrete per Division 3:
1. Finish and color: Coordinate with m aterials finish selection schedule.
2. Unit Pavers: Coordinate with materials finish selection schedule.
3. Pavem ent m arking: Coordinate with m aterials finish selection schedule.
02700 SEWAGE AND DRAINAGE
• Subdrainagesystems:
A. Foundation drainage 4" SDR 35 or sched.40 rigid PVC perforated pipe em bedded in pea gravel or clean
crushed rock and wrapped in filter fabric.
• Storm sewage systems:
A. Exterior catch basins, grates, and frames: Coordinate with materials finish selection schedule.
B. Culverts: Coordinate with m aterials finish selection schedule.
C. Drain pipe: 4" ADS non -perforated tight line.
• Sanitary sewage systems:
A. Sewage collection lines 8" PVC unless cast iron is noted.
B. Septic system: Per drawings of bidders designer.
• Subdrainage system :
A. Slope to drain and surround in well draining material per details.
• Surface drainage per I.R.C. section R401.3.
02800 SITE IM PROVEM ENTS
• Irrigation system : Bidder design
• Fences and gates: Bidder design
02900 LANDSCAPING
Bidder Design
Division 3
CONCRETE
03100 CONCRETE FORMWORK
• Form work and bracing for structural cast -in place concrete shall be by subcontractor and m eet the
requirements of the drawings and industry standards.
• All formwork shall be placed in such a m anner as to allow cast -in place concrete to be placed on solid substrate
and to allow structural support m em bers to sit below the frost line.
03200 C ON C RETE REIN FORC IN G
• Reinforcing steel: Deformed bar sizes and locations per plans and details.Grade 60, Fy'
= 60ksi per I.R.C.section R404.1.3.3.7.1. Unless otherwise noted per Engineer.
• Welded wire fabric: at locations per plans and details: 6x6, W 1.4x1.4WWF.
• A m inim um lap for all bars shall be 40 diam eters taken from the sm allest bar. Provide corner bars to m atch
horizontal reinforcement. Minimum coverage per details and I.R.C.section R404.1.3.3.7.4.
03250 CONCRETE ACCESSORIES
• Anchor bolts: 1/2"-- triple zinc ZMAX (G185 per ASTM A653) hot dipped galvanized steel (ASTM 153 for
Anchors), with a minimum 7" em bedm ent, per I.R.C. section R403.1.6.,unless otherwise noted per Engineer.
• Washers:3"x3"x1/4" sq.triple zinc ZMAX (G185 per ASTM A653) hot dipped galy. steel (ASTM 153 for Anchors),
plate washers per I.R.C.section R602.11.1. Unless otherwise noted per Engineer.
• Anchor bolts at 6'-0" o.c. m ax.for one story & 4'-0" o.c.for buildings over two stories in height, 12" from corners
and joints,with a m inim um em bedm ent of 7". Provide a m inim um of (2) bolts per plate section per I.R.C.section
R403.1.6.
03300 CAST -IN -PLACE CONCRETE
• Structural concrete: Design f'c = 2500 psi m in 5-1/2 sacks of cem ent per cubic yard of concrete and a
maximum of 6.0 gallons of water per 941b sack of cement at 28 days. Max slump is 4". segregation of materials
to be prevented. Use f'c = 3000 psi concrete at 28 days with air entrainm ent only for concrete exposed to
weather,in accordance with I.R.C. Tab le R402.2. Special inspection not required unless noted otherwise per
Engineer.
• Architectural concrete:for exposed aggregate finish (washed), Fc = 2000 psi at 28 days,with 3/8" round
aggregate.
03300 CAST -IN -PLACE CONCRETE
• All concrete shall have water reducing adm ixtures except for footings.
• Air entrainm ent shall be 5-7% in all concrete exposed to weather, I.R.C. Table R402.2
• Coloring agent: Coordinate with m aterials finish selection schedule.
Division 4
MASONRY
04100 MORTAR
• Per I.R.C.section R6062
04150 MASONRY ACCESSORIES
• Anchors and Ties: To be corrosion -resistant m etal ties per I.R.C. section R703.8.4.
• Joint reinforcement: Standard strand no.9 U.S.gagewire per I.R.C.section R703.8.
• Execution Per I.R.C. Chapter 7.
04200 UNIT MASONRY
• Brick m asonry:
A. Exterior locations: nam e/m fg: Coordinate with m aterials finish selection schedule (by others).
B. Interior locations: nam e/m fg: Coordinate with m aterials finish selection schedule (by others).
C. Pavers/planters: nam e/m fg: Coordinate with m aterials finish selection schedule (by others).
• Concrete m asonry units:grade N-1 CM U, unless otherwise indicated sizes per drawings.
A. Special units: Coordinate with m aterials finish selection schedule (by others).
• Glass m asonry units: (glass block) Per I.R.C. section R607.
A. Exterior locat ions: nam e/m fg: Coordinate with m aterials finish selection schedule (by others).
B. Interior locations: nam e/m fg: Coordinate with m aterials finish selection schedule (by others).
• Brick and Veneer:
A. Brick veneer shall be supported on footings, foundation, or other non-com bustible supports. It shall have 15#
felt backing and N o.9 gauge, non corrosive ties at 1 per each 2 s.f. of veneer. Provide 1" m inim um air space
between veneer and backing. Provide approved flashing at base of veneer with 3/16" m in.round weepholes at
33" o.c. m ax., located im m ediately above the flashing, extending from the air space to the exterior. Veneer shall
support no load other than its own weight and the vertical dead lead of veneer above. Provide angle iron support
at doors,windows,and other openings per R606.10.
• Concrete masonry unit (CM U)
A. Concrete m asonry unit walls shall be constructed to conform to ASTM C90. It shall be laid up, reinforced,
and anchored as shown on drawings.
04400 STONE
• As shown on drawings.
A. Exterior locations: name/mfg: Coordinate with materials finish selection schedule (by others).
B. Interior locations: name/mfg: Coordinate with m aterials finish selection schedule (by others).
• Stone VeneerAdhered per m anufacturer's installation instructions and in accordance with I.R.C. R703.12.1
A. On exterior stud walls, adhered m asonry veneer shall be installed:
1. Minimum of 4 inches above the earth.
2. M inim um of 2 inches above paved areas. or
3. M inim um of 1/2 inch above exterior walking surfaces which are supported by the Sam e
foundation that supports the exterior wall.
B. Flashing at foundation - A corrosion-risistant screed or flashing of a m inim um 0.019-inch or 26-gage
galvanized or plastic with a minimum vertical attachment flange of 3\ inches shall be installed.
3
4 1 5
Division 5
Division 8
METALS
DOORS AND WINDOWS
05050 METAL FASTENINGS
08200 WOOD DOORS
Bolts: Use sizes and shapes per dwgs, or as needed for intended purposes. Bolts, nuts and cut washers in contact
Panel wood doors: - Coordinate with m aterials finish selection schedule (by others).
with treated wood to be triple zinc ZMAX (G185 per ASTM A653) hot dipped galvanized steel (ASTM 153 for
Flush wood doors:- Coordinate with m aterials finish selection schedule (by others).
Anchors).
Stile and rail(store door): - Coordinate w/m aterials finish selection schedule (by others).
• Patio door - Coordinate with m aterials finish selection schedule (by others).
05500 METAL FABRICATION
Other - Coordinate with m aterials finish selection schedule (by others).
Handrails and guardrails: Provide in sizes and locations as shown per dwg.
08300 SPECIALTY DOORS
Division 6
Sliding glass door:- Coordinate with m aterials finish selection schedule (by others).
WOOD AND PLASTICS
Garage door: (m ake/style): (see division 11450)- Coordinate with materialsfinish selection
schedule (by others).
06100 ROUGH CARPENTRY
• Framing Lumber: Framing lumber shall be marked in conformance with the United States Dept. of
08600 WOOD/VINYL WINDOWS
Com m erce, Standard Reference No. PS 20 (DOC PS 20) standards. All Kiln dried m inim um 19%.
Note: Egress -
A. J oist and rafters: (2x6 and larger) Hem -Fir #2 or better.
A. Every sleeping room shall have at least one operable window with a net clear opening of
B. Beam s and stringers: (4x and larger) Doug -Fir #2 or better.
5.7 s.f. The net clear opening height shall be a m inim um of 24", with a m inim um net clear
C. Post and tim bers: Doug -Fir # 1.
width of 20", and a finished sill height of not m ore than 44" above the floor, per I.R.C. section
D. Studs, plates,and m isc. light fram ing: Hem -Fir #2 or better.
R310.
E. " I " Joists and Engineered beam s: Per m anufacturer.
B. Safety glaze per I.R.C. section R308.
F. Glue lam inated tim ber:
C. See plans for egress and operation.
1. Sim ple span: 24F V4 DF/N3WN
Manufactured by:
2. Continuous or cantilever:24F V8 DF/DF
A. Color:- Coordinate with m aterials finish selection schedule (by others).
G. All other lum ber: Hem -Fir Standard or better.
B. Style - Coordinate with m aterials finish selection schedule (by others).
H. Plywood/oriented strand board (O.S.B.):APA graded.
I. Wall sheathing: see "TYPICAL BUILDING MATERIALS" list on the dwgs.
08700 HARDWARE
J. Floor sheathing: see "TYPICAL BUILDING MATERIALS LIST"on the dwg.
Type: A. Coordinatewith m aterials finish selection schedule (by others).
K. Other:As noted on drawings.
Weather Stripping:A. Coordinatewith materials finish selection schedule (by others).
. All wood m em bers in contact with exposed concrete to be pressure treated m em bers.
Thresholds: A. Coordinate with m aterials finish selection schedule (by others).
• Particle Board: A.PA.graded
A. Underlayment
08800 GLAZING
1. Floors: 5/8" (U.N.O.)
Glass thickness to be determ fined by size and wind loading per I.R.C.section R308.
2. Sheet vinyl: 1/4" (U.N.O.)see division 9
Safety glaze per I.R.C.section R308.
3. Cabinet surfaces 3/4" (U.N.O.)
Mirrors to be silvered 1/4" float plate glass.
• Trusses:
A. Prefabricated connector plate wood roof trusses shall be designed and stamped by the manufacturer
Division 9
in accordance with the "design specification for m etal plate connected wood trusses". Design drawings
FINISHES
and details to be available upon request.
B. See "Roof Fram ing Notes" on drawings.
09250 GYPSUM WALLBOARD
C. Roof design, layout, loading, and bracing shall be by m anufacturer.
Walls: See the "TYPICAL BUILDING MATERIALS" list on the drawings.
D. Field alterations of truss must be designed by manufacturer.
A. Finish: 1. Coordinate with Contractor/Owner m aterial selections.
• Fasteners and adhesives: All nails shall be com m on wire of sizes for intended purpose per I.R.C. table
Ceiling: See the "TYPICAL BUILDING MATERIALS" list on the drawings.
R602.3(1). Attach tim ber joists to flush headers and beam s with Sim pson "U" hanger series or equal to
A. Finish: 1. Coordinate with materials finish selection schedule.
suit intended purpose. Sim pson connectors at other locations as outlined per drawings. Bolt heads, nuts,
Wall and ceiling finishes shall have a Elam a spread index of not greater than 200,and a
and cut washers per Division 5. Connectors and fasteners in contact with treated wood to be triple zinc
sm oke-developed index of not greater than 450 per I.R.C. R302.9.
ZMAX (G185 per ASTM A653) hot dipped galv. steel (ASTM 153 for Fasteners), stainless steel, silicone
Code required areas:
bronze,or copper as required per dwgs.
A. Type "X:GWB as required.
• Post to m at footing connection. Provide pressure treated post and positive connection to footing per
1. See division 01002 m isc. assem bly requirem ents.
I.R.C.section 502.9.
B. Waterproof GWB as req'd at wet or dam p locations per I.R.C.section R702.4.2.
• All exposed glue lam inated wood, if not protected by a roof or eave, m ust be preservative -treated.
Wonderboard or duroc at all tile locations (U.N.O.)
• Metal corner bead profile:
• The following will apply unless shown on drawings. All wood fram ing details shall be constructed to the
1. Coordinate with m aterials finish selection schedule.
m inim um standards in the I.R.C. All Pram ing shall conform to the requirements of Chapters 5,6, and 8 of
Apply as required in I.R.C. Chapter 7 and Table R702.1(3). Nail or screw in place per table.
the I.R.C. Minimum nailing shall conform to table R602.3(1) of the I.R.C. Height and spacing of studs shall
conform to table R602.3(5) of the I.R.C.
09300 TILE
06200 FINISH CARPENTRY
• Cabinets: Coordinatewith materialsfinish selection schedule (byothers).
• M illwork and casing: Coordinate with m aterials finish selection schedule (by others).
• Paneling: Coordinate with m aterials finish selection schedule (by others).
• Stair and handrail by:
A. Coordinatewith materials finish selection schedule (by others).
B. See division 01002.7 m isc. assem bly requirements.
• Bookcases and built-in shelves: Coordinate with m aterials finish selection schedule (by others).
• Plastic laminate and solid surface material: Coordinate with m aterials finish selection schedule (by others).
Division 7
THERMAL AND MOISTURE PROTECTION
07150 WATERPROOFING & DAMP PROOFING
• Part 2 - Product
er I.R.C. sect ion R406.
• Part 3 - Execution
Per I.R.C.section R406.
07190 VAPOR AN D AIR RETARDER
• Ground cover:6 mil polyethylene: black,with 12" m inim um lap.
• Building wrap: see the "TYPICAL BUILDING MATERIALS" list on the drawings.
• See Division 17, Energy Requirem ents.CC
07200 INSULATION
• Fiberglass or m ineral wood batts, bloom m ineral wool, and extruded polystyrene:
A. Walls: 1. See the "TYPICAL BUILDING MATERIALS" list on the dwgs.
B. C eiling: 1. See the "TYPICAL BUILDING MATERIALS" list on the dwgs.
C. Floor: 1. See the "TYPICAL BUILDING MATERIALS" list on the dwgs.
D. Slab on Grade: R-10 (per W.S.E.C.Table R402.1.1).
• Insulating foam :A. Standard sealant foam.
• See division 17: energy requirements
• Provide insulation m arkers for blown -in or sprayed insulation every 300 sq ft.
Markers shall face the attic access per IECC Sec 303.1.1.1
• Crawl Space/Cantilevered floors: Insulation shall be installed to maintain permanent contact with the
underside of the sub -floor decking. Insulation supports shall be installed so spacing is no m ore than 24"
on center. Cantilevered floor vents shall be placed below the lower surface of the floor insulation.
07300 ROOFING MATERIAL
• Shingles and roofing tiles:
A. See the "TYPICAL BUILDING MATERIALS" list on the drawings
• M em brane roofing: A. 3-ply hot m opped.
• Install per manufacturer's recommendation and Chapter 9 of the I.R.C.
07460 SIDING MATERIAL
• Install per manufacturer's recommendation and Chapter 7 of the I.R.C.
• Siding: See the "TYPICAL BUILDING MATERIALS" list on the drawings.
• Trim: Seethe "TYPICAL BUILDING MATERIALS" list on the drawings.
• Soffits: See the "TYPICAL BUILDING MATERIALS" list on the drawings.
• Other: See the "TYPICAL BUILDING MATERIALS" list on the drawings.
07600 FLASHING AND SHEET METAL
• M in.26 Gauge galvanized, prefinished.
• Install per Chapter 7 and 9 of the I.R.C:
Flashing against a vertical sidewall shall be by the step -flashing m ethod.The flashing shall be a
m inim um of 4" high and 4" wide. At the end of the vertical sidewall the step flashing shall be turned out
in a m anner that directs water away from the wall and onto the roof and/or gutter, Per I.R.C. R903.2.1
• Approved corrosion -resistive flashing shall be provided in the exterior wall envelope in such a manner as
to prevent entry of water into the wall cavity or penetration of water to the building structural Pram ing
com ponents.The flashing shall extend to the surface of the exterior wall surface and shall be installed to
prevent water from reentering the exterior wall envelope.
07700 ROOFING SPECIALTIES
• Vents:
A. Ridge vent: manufactured by: 1. Coordinate with m aterials finish selection schedule (by others).
B. Mushroom vent: manufactured by: 1. Coordinate with m aterials finish selection schedule (by others).
• Gutters:
A. Continuous alum.precoated:
1. Style: K profile
2. Color: Match fascia
• Downspouts:
A. 2x3 rectangular aluminum precoated:
1. Color: Match fascia & trim
B. Tie to 1 drain system .
07800 SKYLIGHTS
• Skylights to conform with I.R.C. section R308.6.
• M anufacturer: A. Coordinate with m aterials finish selection schedule (by others).
07900 SEALANTS AND CAULKING
• Caulking - Styrene butadene caulking (SBR)
• Color - Match siding
N
5
• Ceram ic, quarry, and marble tiles - Coordinatewith materials finish selection schedule (by
others).
• Refer to manufacturer's recom m endations.
09550 WOOD FLOORING
Type - Coordinate with m aterials finish selection schedule (by others).
09650 RESILIENT FLOORING
Type - Coordinate with m aterials finish selection schedule (by others).
09680 CARPETING
Carpet and Pad - Coordinate with m aterials finish selection schedule (by others).
09900 PAINTING
Painting over prepared surface per m anufacturer's recom m endations - Coordinate with m aterials
finish selection schedule (by others).
09950 WALL COVERINGS
Type - Coordinate with m aterials finish selection schedule (by others).
Division 10
SPECIALTIES
10200 LOUVERS AND VENTS
• Hardware cloth screen 1/4" x 1/4" on soffit vents as detailed.
• Continuous 2" performed metal soffit vent as detailed.
• Roof vent (See Division 07700)
• Other vents as noted per plans.
10300 PREFABRICATED FIREPLACES
• Location/Model/Accessories:- Coordinate with m aterials finish selection schedule (by
others).
• See division 01002.12 for m isc. assem bly requirem ents for fireplaces.
10400 IDENTIFYING DEVICES
• Building num bers:- Coordinate with m aterials finish selection schedule (by others)
• Install in location per jurisdictional requirements.
10800 TOILET AND BATH ACCESSORIES
Toilet and bath accessories - Coordinate with m aterials finish selection schedule (by others).
10900 WARDROBE AND CLOSET SPECIALTIES
• Storage Closet:- Coordinate with m aterials finish selection schedule (by others).
• Clothes Closets - Coordinate with m aterials finish selection schedule (by others)
• Pantry.
Division 11
11010 MAINTENANCE EQUIPMENT
• Vacuum cleaning system - Coordinate with m aterials finish selection schedule (by others).
11450 RESIDENTIAL EQUIPMENT
• Garage door opener(s)- Coordinate with m aterials finish selection schedule (by others).
• Ironing board cabinet (or drawer).- Coordinate with materials finish selection schedule (by
others).
• Free-standing appliances - Coordinate with m aterials finish selection schedule (by others).
Division 12
FURNISHINGS
12500 WINDOW TREATMENT
Window treatm ent - Coordinate with m aterials finish selection schedule (by others).
Division 13
SPECIAL CONSTRUCTION
13150 POOLS
Bidder design
13156 HOT TUB
Coordinate with m aterials finish selection schedule (by others).
Division 14
CONVEYING SYSTEMS
14100 DUMBWAITER
Dumbwaiter: Manufacturer/model num ber- Coordinate with m aterials finish selection schedule (by
others).
6
Division 15
MECHANI,
15000 GENERAL
• Mechanical system to be bidder design.
• Regulatory requirements:
A. Refer to Division 1 General Requirements.
B. See plans for total m axim um Btu.
C. Heating and cooling equipm ent shall be sized based on building loads calculated in
accordance with ACCA manual J or other approved heating and cooling calculation
m ethodologies. Per M 1401.3
• Contractor work out plum bing and HVAC diagram layout - Coordinate with other trades.
15400 PLUMBING
• Pipes and Fittings:
A. W aste & soil:ABS plastic of sizes req'd for the intended purpose.
1. Provide cast iron with compression neoprenejoints per locations shown on the
drawings.
2. Provide clean -outs at bends.
B. Vents:ABS
C. Gas: Per code, verify location of appliances.
1. Provide an approved earthquake shutoff valve installed in the building supply line
im m ediately after the gas m eter. The valve shall be located outside of the structure
and be accessible.
D. Water Line:
1. Below Grade: 1 1/4" type K with/hard solder
2. Above Grade:Type L w/soft solder
• Plumbing equipment:
A. Hot water heater: (Duals in tandem)
1. Size per U.P.C.501 and Table 501.1 and jurisdictional amendments.
2. Coordinate with owner's m aterial selection (by others).
B. Hose bib, frost proof type: Mansfield units
C. Main shut-off valve in garage.
D. Plumbing fixtures- Coordinatewith owners material selection (by others).
• Irrigation: (bidder design)
A. Provide "T" connection in main line in garage by main shut-off valve with separate shut-off
and drain valve.cc
• Automatic Sprinkler System :(bidder design)
• The installer to design the system to appropriate jurisdictional requirem ents and function in a
manner consistent with industry standards. Refer to general requirements.
15500 HVAC
• Forced Air:
A. Furnace system - Coordinate with m aterials finish selection schedule (by others).
B. Duct work and insulation - Coordinate with m aterials finish selection schedule (by others).
C. Air cleaner - Coordinate with materials finish selection schedule (by others).
D. Controls - Coordinate with m aterials finish selection schedule (by others).
E. Registers with adjustable supply - Coordinate with materials finish selection schedule (by
of hers).
F. Provide firestopping at 'B' vent location per I.R.C. sections R302.11.
• Fans: see division 17 energy requirements.
• See floor plans for Whole House Ventilation requirements.
• Vents - Coordinate with m aterials finish selection schedule (by others).
• Exhaust Ducts:
A.Term inate outside building and equip with backdraft dampers per I.R.C.section M 1507.3.3.
• Dryer Ducts:
A. Cloths Dryers shall be exhausted in accordance with manufactures instructions &
I.R.0 . M 15 0 2.
B. Protective shield plates shall be placed per I.R.C. M 1502.5.
• The installer to design the system to appropriate jurisdictional requirements and function in a
manner consistent with industry standards. Refer to general requirements.
Division 16
ELECTRICAL
16000 GENERAL
• Electrical systems to be bidder designed.
• Regulatory requirements: refer to Division 1- General Requirements.
• Contractor to provide electrical diagram m ing layouts, design circuitry: follow lighting plan if
provided.
A. Coordinatewith other trades.
16200 POWER
• Wire and Boxes.
A. Volt: 12 6A (3) Wire
1. GFI @ Damp Locations
B. Low voltage: standard type
• Panels: Circuit breaker box fully labeled
A. Capacity: Bidder Design
B. Circuitry: Bidder Design
• Grounding:
A. Provide (1) 2 1/2" schedule 80 PVC conduit at concrete stem wall for electrical service and
(1) 5/8" diam eter x 8'0" long galvanized rod (& Ufer ground) for electrical grounding.
• Smoke Detectors:
A. Provide and install per I.R.C. sect ion R314.
• Fire alarm :
A. Provide and install per N.E.C.and as required by governing fire marshal.
• The installer to design the system to appropriate jurisdictional requirem ents and function in a
manner consistent with the industry standards. Refer to general requirements and I.R.C.
16200 COMMUNICATIONS
• Intrusion alarm and security detection systems - Coordinate with m aterials finish selection
schedule (by others).
• Phone system - Coordinate with m aterials finish selection schedule (by others).
• Intercom m unicat ion system s - Coordinate with m aterials finish selection schedule (by others).
• Stereo system - Coordinatewith m aterials finish selection schedule (by others).
16500 LIGHTING
• Fixtures: Coordinate with m aterials finish selection schedule (by others).
Note: A m inim um of 90% of all lum inaries shall be high efficiency per W.S.E.C. R404.1.
• Control:A. Switches: Coordinate with m aterials finish selection schedule.
• Dim m ers: Coordinate with m aterials finish selection schedule (by others).
• Boxes: Coordinate with m aterials finish selection schedule (by others).
• Other: Coordinatewith m aterials finish selection schedule (by others).
• The installer to design the system to appropriate jurisdictional requirements and function in a
manner consistent with the industry standards. Refer to general requirements.
Division 17
ENERGY REQU IREM EN TS
WASHINGTON STATE ENERGY CODE:
General Notes:
• Per W SEC R402.4. The building Envelope shall be constructed to lim it the air leakage rate not
to exceed 5 air changes per hour. The results of the test shall be signed by the party
conducting the test and provided to the code official (R402.4.12).
• Per W SEC R403.1.1. at least one thermostat per dwelling unit shall be capable of controlling the
heating and cooling system on a daily schedule.
• Per W SEC R403.3.2. ducts, air handlers, and filter boxes shall be sealed.
• The certificate should be com pleted by the builder or other approved party and posted in the
space where the furnace is located, a utility room , or another approved location in the building.
• Fenestration to be N FRC 100, labeled and certified by the m anufacturer
• M INIM LIM INSULATION VALUES UN LESS NOTED OTHERWISE:
R402.1.2 - Wood Fram e W all: R-21 intermediate Pram ing / U-0.056
R402.1.2 - Ceilings: R-49 / U-0.026
R402.1.2 - Basement Walls: R-10 continuous insulation on the exterior of the wall, R-15
continuous insulation on the interior of the wall.
R402.1.2 - Slab: R-10, 2 ft. / F-factor - 0.54
R402.1.2 - Fenestration: U-0.30
• Vapor retarder shall be installed on the conditioned room side of the insulation.
• Headers to be insulated to a m in of r-10.
• Provide 1/2" airspace between sub -grade concrete walls and fram ing/insulation.
wrap all hot water supply pipes with self -adhered pipe -wrap foam insulation.
7
0am
HCC
nati inw thin standard
SERVICES@HOM ECARECONTRACTORS.COM
206.984.4543
GO• design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SINGLE- FAMILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVENUE W
EDM ON DS, WA 98026
All rights reserved.No part of this docum ent may be reproduced in any
form or by any means without permission in writing from GO.design
N0. DATE DESCRIPTION
CODE NOTES
Project Num ber 2215
Date 01/08/23
Drawn By GO.design
A002
F
E
D
C
B
A
1 2 3 I 4 5 6 7
HCC
oct[inq thn sstan-d8rd
SERVICES@HOM ECARECONTRACTORS.COM
A300 206.984.4543
2
(E) 27' - 0" (E) 20' - 4 1/2" (E) 2' - 7 1/2"
GO* design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
0
0
w
0
0
w
A300 3
(E) 24' - 0"
EXISTING MAIN FLOOR
1/4" = 1'-0"
1
A300
0
w
4 A300
SYMBOLS AND LEGEND
NEW WALL
0 EXISTING WALL
E DEMOLISHED
WF WHOLE -HOUSE FAN TO RUN CONTINUOUS & CONFORM
TO IRC, M 1505A. FAN SIZE PER PLAN.
FAN RATE TO BE ADJ USTED BY A FACTOR OF 1.5 FOR A NON
BALANCED NON DISTRIBUTED SYSTEM. FRESH AIRTO BE PROVIDED
BY THE FORCED AIR SYSTEM DUCTS PER SECTION M 1505A.1. FAN
TO HAVEA SONE RATING OF 1.0 OR LESS
MEASURED AT 0.1 INCHES WATER GAUGE
❑FAN- DIRECT VENT TO OUTSIDE
F BATHROOM S/LAUNDRY 50 CFM MIN.
KITCHEN EXHAUST HOOD TO BE MIN.OF 100CFM.
IF EXHAUST HOOD EXCEEDS 400 CFM MAKE UP AIR
M UST BE PROVIDED PER SECTION M 1503.6.
110v SM OKE ALARM PER I.R.C. R314 WITH BATTERY BAC KUP
�S INTERCONNECTED PERR314A & R315.5. USE COMBINATION
J SMOKE/CARBON MONOXIDEALARM WHEN NOTED
MECHANICAL,PLUMBING,AND ELECTRICAL SYSTEM FORUNITS:
PER DIV.15,16 SEE SHEET A-001
FU RN W H
A. PROVIDE 6" DIAMETER FRESH AIR INTAKE FROM OUTSIDE TO RETURN AIR
PLENUM AT FURNACEWITH MOTORIZED FLOW DAMPERS.
B. PROVIDE THERMAL EXPANSION TAN K AT WATER HEATER.
C. STRAP WATER HEATER TO FRAMING TOP AN D BOTTOM.
D. PROVIDE PRESSURE RELIEF LINE PLUMBED TO OUTSIDE.
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SINGLE- FAMILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVENUE W
EDM ON DS, WA 98026
All rights reserved. No part of this document maybe reproduced in any
form or by any means without permission in writing from GO.design
NO. DATE DESCRIPTION
EXISTING MAIN FLOOR
Project Num ber 2215
Date 01/08/23
Drawn By GO.design
1 1 2 1 3 1 4 1 5 1 6 1 7 1
A200
F
E
FBIN
C
1 1 2 1 3 1 4 1 5 1 6 1 7 1
O
0
w
0
,
0
w
WINDOW SCHEDULE
MARK
OPERATION
WIDTH
HEIGHT
Sill Height
U-Value
Comments
W 1
SLIDING
2'- 7"
2' - 8"
4'- 0"
0.30
SAFETY GLAZING
W2
SLIDING
5'- 9 1/2"
3'- 0"
3'- 6"
0.30
EGRESS
W3
SLIDING
2'-6"
2'-10"
3'-6"
0.30
W4
SINGLE -HUNG
2'- 0"
3'- 0"
3'- 6"
0.30
W5
FIXED
4'- 8"
6'- 6"
2' - 0"
0.30
SAFETY GLAZING
W6
SLIDING
4' - 8"
1' - 0"
1' - 0"
0.30
SAFETY GLAZING
W7
FIXED
5'- 3"
6'- 6"
1' - 0"
0.30
SAFETY GLAZING
W 8
FIXED
3' - 0"
1' - 0"
7'- 6"
0.30
W9
SLIDING
6'- 0"
3'- 10 1/2"
3'- 6"
0.30
EGRESS
W 10
SLIDING
5'- 9"
3'- 0"
4'- 0"
0.30
EGRESS
W 11
SLIDING
6'- 4"
3'- 0"
3'- 6"
0.30
EGRESS
W 12
SLIDING
2'- 0"
2'- 10"
3'- 6"
0.30
W13
SINGLE -HUNG
2'-0"
2'-7"
3'-6"
0.30
W 20
FIXED
5' - 3"
1' - 0"
7'- 6"
0.30
(E) CONCRETE
PAD
(E) COVE
DECK
O
i� D4
(E) 27' - 0"
DOOR SCHEDULE
MARK
FUNCTION
TYPE
WIDTH
HEIGHT
COMMENTS
D 1
Interior
SWING
2'- 6"
6'- 8"
D2
Interior
POCKET
2'- 6"
6'- 8"
D3
Interior
SWING
2'- 6"
6'- 8"
D4
Exterior
SLIDING DOOR
6'- 0"
6'- 10"
SAFETY GLAZING
D5
Interior
SWING
2'- 6"
6'- 8"
DEMOLISHING NOTES
1 WALL TO BEDEMOLISHED
2 OPENING TO BEDEMOLISHED
AND FRAMED IN
(E) 20' - 4 1/2"
A301
2
(E) 2' - 7 1/2"
(E) STORAGE W2
N EGRESS r
(N) WIC
W4
WALK-IN SHOWER 9'- 11 1/2" 10'- 0 1/2"
01
VERIFY
SAFETY GLAZING
PER I.R.C., SECTION R308
2
EXISTING DOOR TO BE REPLACED (E) BEDROOM
IN EXISTING OPENING 1 �F CV
(E)DOORTO REPLACE -
WITH N WINDOW I - - / 1'- 6" ,N, /
(N) KITCHEN CABINETS I p
BY OTHERS W1
(N) RANGE HOOD (E) BATH_,z 1 (S1
o r
(E) STORAGE co 0
D5
(N) CABINETS BY OTHERS C)1 \ ° ° O H
c 1 8'- 5 1/2"
L
° o o , REF 2
CY) N
-1 2'-0" 2'-9" 1'-0" 4'-0" 1'-0" 3'-6" 1'-0"
SHELVES BY OTHERS (E) DINING _
of N LO
° M (E) KITCHEN (E) LIVING RM
(E) UTILITY CONVERT AN EXISTING
0 (N) KITCHEN ISLAND FIREPLACE INTO A -
' BY OTHERS DIRECT VENT
A301 3 DOUBLE SIDED GAS
5'- 0" FIREPLACE
p 3'- 6" 8' - 0"
------------
I AN OPENING OF NOT LESS
THAN 100" SHALL BE
W12
D wH W
WH
M
I PROVIDED IN THE LAUNDRY
I
O
' CLOSET AND UTILITY ROOM
I ENCLOSURE OR MAKEUP
i
o
O
0
' AIR SHALL BE PROVIDED BY
®
OTHER APPROVED MEANS O
O
\
t----------
C)
(S 1
M
(E) BATH
w
(E) WATER
HEATER
(E) C LOSET
(E)LIN EN
TO BE RELOCATED
EXISTING WINDOW
\/6
TO BE REPLACED
IN EXISTING OPENING
(E) BEDROOM W9
W
w11 ff_)C LO SET (E) CLOSET
POST PER
STRUCTURAL,TYP
(E) BEDROOM
W10
(E) 24' - 0"
(E) BEDROOM
1
PROPOSED MAIN FLOOR
1/4" = 1'-0"
EGRESS
W10
W7
(W6I W6 W6
7cv
5 W5 W5
(E) 10' - 0" (E) 16' - 0"
EXISTING WINDOW
TO BE REPLACED
IN EXISTING OPENING
SAFETY GLAZING
PER I.R.C., SEC R308
EXISTING WINDOW
ABOVETHE DOOR TO BE REPLACED
EXISTING WINDOW
TO BE REPLACED
IN EXISTING OPENING
EXISTING WINDOW
TO BE REPLACED
IN EXISTING OPENING
1
A301
(N) WINDOW
ALTER EXISTING OPENING
(N)WINDOW
CD - - - - - - - - - - - - - - - - - - - - - - - - -
I INSULATION REMOVED FROM EXTERIOR WALL CAVITIES AS PART OF i
w THE REMODEL TO BE REPLACED WITH MINIMUM R-15 IN EXTERIOR
12X4 WALLS AND R-21 IN EXTERIOR 2X6 WALLS.- - - - - - - - - J
EXISTING WINDOW
TO BE REPLACED
IN EXISTING OPENING
18" MIN NON-COM BUSTIBLE
FLOOR PROTECTOR
4 A301
0
,
(N) GAS FIREPLACE
BY OTHERS
POST PER
STRUCTURAL, TYP
(N)SLIDING WINDOW
BELOW, TYP
EXISTING WINDOW
TO BE REPLACED
IN EXISTING OPENING
SAFETY GLAZING
PER I.R.C., SECTION R308
GENERAL NOTES
1.CONTRACTOR TO VERIFY ALL DIMENSIONS AND CONDITIONS OF PROJECT AND REPORT ANY
OMISSIONS/DISCREPANCIES TO DESIGNER PRIORTO COMMENCING WORK.
2. REFER TO STRUCTURAL SHEETS FOR SHEAR WALL SCHEDULEAND ENGINEERING PLAN WHICH
CONTAIN REFERENCES AND/OR INSTRUCTIONS PERTAINING TO EACH SHEARWALL INDICATED IN
THIS PLAN
3.A WRITTEN REPORT OF THE AIR LEAKAGE TEST RESULTS, SHALL BE SIGNED BY TESTING PARTY
AND PROVIDED TO THE BUILDING INSPECTOR, PRIOR TO CALL FOR FINAL INSPECTION
4. DESIGN PROFESSIONAL OR BUILDER SHALL COM PLETE AND POST AN "INSULATION CERTIFICATE
FOR RESIDENTIAL CONSTRUCTION" WITHIN 3'-0" OF ELECTRICAL PANEL PRIOR TO FINAL INSPECTION
5. FENESTRATION TO BENFRC 100,LABELED AND CERTIFIED BY THE MANUFACTURER
6. REQUIRED RAILINGS SHALL NOT HAVE OPENINGS THAT ALLOW PASSAGE OF A SPHERE 4 INCHES
IN DIAM ETER FROM THE WALKING SURFACE TO THE REQUIRED RAILINGS HEIGHT.
7. RAILINGS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT.
8. RAILINGS SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 200 LB.
9. INTERMEDIATE RAILS, BALUSTERS,AND PANEL FILLERS SHALL BE DESIGNED TO RESIST A
CONCENTRATED LOAD OF50 POUNDS.
10. PROVIDE SAFETY GLAZING PER 2018 INTERNATIONAL RESIDENTIAL CODE (IRC)
11.WHERE SAFETY GLAZING IS REQUIRED, EACH PANE MUST BE PROVIDED WITH A MANUFACTURER'S
LABEL DEFINING THETYPEOFGLASS AND SAFETY GLAZING STANDARD TO WHICH IT COM PLIES.THE
LABEL M UST BE PERMANENTLY ETCHED, FIRED,OR EMBOSSED,ON THE GLASS OR BEA TYPETHAT
ONCE APPLIED CANNOT BE REMOVED WITHOUT BEING DESTROYED.
12.ALLTHE APPLIANCES SHALL BE NEW AND INSTALLED IN THE DWELLING UNIT TO MEET ENERGY
STAR STANDARDS
TYPICAL FLOOR NOTES:
1. INSTALL SMOKE DETECTORS IN ALL SLEEPING ROOMS AND ADJACENT AREAS,AND AT CEILING
HEIGHT CHANGES GREATER THAN 24".SMOKE DETECTORS TO BE HARD WIRED AND
INTERCONNECTED,WITH BATTERY BACKUP PERCODE.SMOKE DETECTORS:
* SHALL BE 110 V INTERCONNECTED W/ BATTERY BACKUP
* SHALL BE INSTALLED ON EACH FLOOR AND IN ALL BEDROOMS
* SHALL BE INSTALLED IN EACH LOCATION WHERE THERE IS ACEILING CHANGE GREATER THAN 24"
2. INSTALL CARBON MONOXIDE SENSORS ADJACENT TO SLEEPING AREAS.
3. CARBON M ONOXIDE DETECTORS ARE REQUIRED IF AN ATTACHED GARAGE AND/OR FUEL FIRED
EQ U IPM EN T IS PRESEN T.
4.THE MAIN ELECTRICAL SERVICE FEEDER PANEL FOR EACH DWELLING UNIT SHALL HAVE
REVERSED SPACE TO ALLOW INSTALLATION OF A DUAL POLE CIRCUIT BREAKER FOR FUTURE SOLAR
ELECTRIC INSTALLATION AND SHALL BE LABELED "FOR FUTURE SOLAR ELECTRIC"
5.PROVIDE A PROGRAM MABLETHERMOSTAT FOR THE PRIMARY SPACE CONDITIONNING SYSTEM
WITHIN THE DWELLING UNIT.
6.ALL INTERIOR WALLS TO BE 2X4 @ 16' O.C. (U.N.O.)
7.ALL EXTERIOR WALLS TO BE 2X6 @ 16' O.C. (U.N.O.)
8. WINDOW SIZES ARE NOMINALROUGH OPEN ING,WIDTH AND HEIGHT.
9.PROVIDE A VENTED WINDOW IN EACH HABITABLE ROOM. THE FOLLOWING ARE NOT CONSIDERED
HABITABLE ROOM S: BATHROOM S, TOILET ROOM S, CLOSETS, HALLS, STORAGE OR UTILITY SPACES
AND SIMILAR.
10.APPROVED CORROSION -RESISTIVE FLASHING SHALL BE PROVIDED IN THE EXTERIOR WALL
ENVELOPE IN SUCH A MANNER AS TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR
PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENTS.THEFLASHING
SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL SURFACE AND SHALL BE INSTALLED TO
PREVENT WATER FROM REENTERING THE EXTERIOR WALL ENVELOPE.
11.ALL INTERIOR FINISHES TO MEET MINIMUM FLAME SPREAD INDEX AND SMOKE DEVELOPEM ENT
INDEXAS REQUIRED BY 2018 IRC.
12.GARAG E SHALL BE SEPARATED FROM THE RESIDENCEAND ITS ATTIC AREA BY NOT LESS THAN
5/8" TYPE X GW B APPLIED TO THE GARAGE SIDE. WHERE THE SEPARATION IS A FLOOR -CEILING
ASSEM BLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY NOT
LESS THAN 5/8" TYPE X GW B OR EQUIVALENT.
13.0PEN INGS BETWEEN THE GARAGE AND RESIDENCESHALL BEEQUIPPED WITH SOLID WOOD
DOORS NOT LESS THAN 1 3/8" IN THICKNESS, SOLID OR HONEYCOMB CORE STEEL DOORS NOT LESS
THAN 1 3/8" THICK, OR 20-M INUTE FIRE -RATED DOORS.
14. DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILING SEPARATING THE
DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED 0 F A MINIMUM N226 GAUGESHEET STEEL
OR OTHER APPROVED MATERIALS AND SHALL HAVE NO OPEN INGS INTO THE GARAGE.
SYMBOLSAND LEGEND
NEW WALL
0 EXISTING WALL
E DEMOLISHED
WF WHOLE -HOUSE FAN TO RUN CONTINUOUS & CONFORM
TO IRC, M 1505.4. FAN SIZE PER PLAN.
FAN RATE TO BE ADJ USTED BY A FACTOR OF 1.5 FOR A NON
BALANCED NON DISTRIBUTED SYSTEM. FRESH AIRTO BE PROVIDED
BY THE FORCED AIR SYSTEM DUCTS PER SECTION M 1505.4.1. FAN
TO HAVEA SONE RATING OF 1.0 OR LESS
M EASURED AT 0.1 INCHES WATER GAUGE
FAN- DIRECT VENT TO OUTSIDE
F BATHROOM S/LAUNDRY 50 CFM MIN.
KITCHEN EXHAUST HOOD TO BE MIN.OF 100CFM.
IF EXHAUST HOOD EXCEEDS400 CFM MAKE UP AIR
M UST BE PROVIDED PER SECTION M 1503.6.
110vSMOKEALARM PERI.R.C.R314 WITH BATTERY BACKUP
(S INTERCONNECTED PERR314.4 & R315.5. USEA COMBINATION
SMOKE/CARBON MONOXIDEALARM WHEN NOTED
MECHANICAL,PLUMBING,AND ELECTRICAL SYSTEM FOR UNITS:
PER DIV. 15,16 SEE SHEET A-001
FU RN W H
A.PROVIDE6" DIAMETER FRESH AIR INTAKE FROM OUTSIDETO RETURN AIR
PLENUM AT FURNACEWITH MOTORIZED FLOW DAMPERS.
B. PROVIDE THERMAL EXPANSION TANK AT W ATER HEATER.
C.STRAP WATER HEATERTO FRAMING TOPAND BOTTOM.
D. PROVIDE PRESSURE RELIEF LINE PLUMBED TO OUTSIDE.
0we
HCC
netting the rtnn-d8rd
SERVICES@HOM ECARECONTRACTORS.COM
206.984.4543
Oe design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SIN G LE- FAM ILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVEN U E W
EDM ON DS, WA 98026
All rights reserved. No part of this docum ant may be reproduced in any
form or by any m eans without perm ission in writing from GO.design
NO. DATE DESCRIPTION
PROPOSED MAIN
FLOOR
Project N um ber 2215
Date 01/08/23
Drawn By GO.design
A201
1 1 2 1 3 1 4 1 5 1 6 1 7 1
F
E
D
C
B
A
1 1 2 1 3 1 4 1 5 1 6 1 7 1
1
EXISTING WEST ELEVATION
1/4" = 1'-01
1
EXISTING EAST ELEVATIONS
1/4" = 1'-0"
EXISTING NORTH ELEVATIONS
1/4" = 1'-0"
EXTERIOR MATERIAL LEGEND
SH IN G LE SID IN G
CONCRETE
LAPSIDING
BRICK
0we
HCC
nr_t[inq tho sstondard
SERVICES@HOM ECARECONTRACTORS.COM
206.984.4543
GO* design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SIN G LE-FAM ILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVEN U E W
EDM ON DS, WA 98026
All rights reserved. No part of this document maybe reproduced in any
form or by any means without permission in writing from GO.design
NO. DATE DESCRIPTION
EXISTING ELEVATIONS
Project N um ber 2215
Date 01/08/23
Drawn By GO.design
4
EXISTING SOUTH ELE
1/4" = 1'-0"
1 I 2
VATION
1 3 1 4 1 5 1 6 1 7 1
A300
1 1 2 1 3 1 4 1 5 1 6 1 7 1
F
E
D
C
B
A
PROPOSED WEST ELEVATIO
NPER I.R.C., SECTION R308
Q/ Fr 11 V L 11N V
PER I.R.C., SECTION R308
PRO POSED EAST ELEVATIONS
PROPOSED NORTH ELEVATIONS
1/4" = 1'-011
EXTERIOR MATERIAL LEGEND
SH IN G LE SID IN G
CONCRETE
LAP SIDING
BRICK
PROPOSED SOUTH ELEVATION
••
■■
HCC
nr_t[inq tho sstondard
SERVICES@HOM ECARECONTRACTORS.COM
206.984.4543
GO* design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SINGLE-FAMILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVEN U E W
EDM ON DS, WA 98026
All rights reserved. No part of this document may be reproduced in any
form or by any means without permission in writing from GO.design
NO. DATE DESCRIPTION
PROPOSED
ELEVATIONS
Project N um ber 2215
Date 01/08/23
Drawn By GO.design
1/4" = if-
011
1 2 I 3 4 5 6 7
A301
1 I 2 I 3 I 4
5
6 I 7
GLAZING NOTES:
F
E
FBI
C
C
n
NAILER
GWB
HEADER PER
STRUCTURAL
PLACE STAINLESS
STEEL FASTENERS
FORTRIM AWAY
FROM WINDOW FLANGE
WINDOW HEAD, TYP
3" = 1'-0"
GWB
NON -CORROSIVE
FASTENERS @
WINDOW FLANGE
STAINLESS STEEL
FASTENERS @ TRIM
(E)WOOD FRAMING
W/MIN R-21INSULATION
WINDOW SILL, TYP
311 = 11
- 0 1'
2 '
AlyA
EXT SHEATHING
WATER RESISTIVE
BARRIER
EXTERIOR SIDING
FLASHING
MEMBRANE
EXT SHEATHING
WATER RESISTIVE BARRIER PLACED
UNDER FLASHING MEMBRANE
BLDG PAPER OVER HEAD FLASHING
MEMBRANE& WINDOW FLANGE
FLASHING MEMBRANE
EXTERIOR SIDING
PER ELEVATION
METAL FLASHING
TRIM PER ELEVATION
1/2" SHIM
WINDOW PER PLAN
WITH A MAXIMUM
U-FACTOR 0.30
WINDOW PER PLAN
WITH A MAXIMUM U-FACTOR0.30
CAULK JOINT
TRIM
PER ELEVATION
FLASHING MEMBRANE
BEHIND WINDOW FLANGE
EXTERIOR SIDING
PER ELEVATION
WATER RESISTIVE BARRIER PLACED
UN DER FLASHING M EM BRAN
EXT SHEATHING
(E)WOOD FRAMING
W/MIN R-21INSULATION
WINDOW WITH A MAXIMUM U-FACTOR0.30
CAULK JOINT
TRIM TO MATCH EXISTING
NOTES:
- INSTALL SIDING PER MANUFACTURER'S SPECIFICATIONS
- DO NOT NAIL TRIM OR FLASH IN THROUGH WINDOW FLANGE
- REPAIR OR REPLACE WINDOW IF FLANGE BREAKS
- CAULK ALL SEAM S,J0INTS & CORNERS OF FLASH INGS
C WINDOW JAMB,TYP
311 = 11
- 0 1'
GWB
(E) WOOD FRAMING
EXTERIOR WALL, TYP
311 = 11
- 0 1'
EXTERIOR SIDING
TO MATCH EXISTING
WATER RESISTIVE BARRIER
w/ UPPER LAYER HORIZONTALLY
OVER -LAPPING LOWER LAYER
2"MINIMUM & VERTICAL JOINTS
OVER -LAPPING 6" MINIMUM
MIN R-21FRAMING INSULATION
1 LAYER 5/8 GYPSUM BOARD
WOOD FRAMING
C5 INTERIOR WALL, TYP
311 = 11
- 0 1'
1. ALL GLAZING TO BE (2) PANE INSULATED GLASS ORB ETTER UNLESS NOTED OTHERWISE.
2. SLIDING DOOR TO BE SAFETY GLASS, LAM INATED GLASS, OR TEMPERED GLASS.
3. SHOWER DOORS AND ENCLOSURES TO BE SAFETY GLASS, LAMINATED GLASS, OR TEMPERED GLASS.
4.WHERE SAFETY GLAZING IS REQUIRED, EACH PANE MUST BE PROVIDED WITH A MANUFACTURER'S LABEL
DEFINING THE TYPE OF GLASS AND SAFETY GLAZING STANDARD TO WHICH IT COMPLIES. THE LABEL MUST BE
PERMANENTLY ETCHED, FIRED, OR EMBOSSED, ON THE GLASS ORBEA TYPE THAT ONCE APPLIED CANNOT BE
REMOVED WITHOUT BEING DESTROYED.
GENERAL DOOR NOTES:
1.THRESHOLDS SHALL NOT EXCEED 1/2" HEIGHT MAX. (TYP.).
EXTERIOR THRESHOLDS SHALL BE SET IN SEALANT
2. DOOR THRESHOLD SHALL BE SET IN SEALANT AND CONTINUE OVER ENTIRE WIDTH OF WALL ASSEM BLY.
3. DOOR FRAMES SHALL BE PAINTED UNLESS INDICATED OTHERWISE
4. FORCE FOR PUSHING OR PULLING OPEN DOORS OTHER THAN FIRE DOORS SHALL BE 5.0 POUNDS MAXIM UM
FOR INTERIOR HINGED AND DOORS AND 10.0 POUNDS MAXIM UM FOR EXTERIOR HINGEDAND SLIDING DOORS.
FOR FIRE DOORS,THE DOOR LATCH SHALL RELEASE WHEN SUBJ ECTED TO A 15 POUND FORCE.THE DOOR
SHALLBE SET IN MOTION WHEN SUBJECTED TO A 30 POUND FORCE.THEDOOR SHALL SWING TO A FULL -OPEN
POSITION WHEN SUBJECTED TO A 15 POUND FORCE.
MOISTURE PROTECTION NOTES
1. PROVIDE PRESSURE TREATED PLATES BETWEEN CONCRETE AND FRAMING.
2. PROVIDE A M IN OF 12" CLEAR WOOD GIRDERS AND EARTH.
3.PROVIDE A MIN OF 18" CLEAR BETWEEN WOOD JOISTS AND EARTH.
4. PROVIDE M IN OF 8" CLEAR BETWEEN WOOD POSTS AND EARTH.
5. PROVIDE M IN OF 1" CLEAR BETWEEN WOOD POSTS AND CONCRETE FLOORS.
6. CAULK ALL OPENINGS THOROUGHLY.
7. FLASS ALL OPENINGS WITH A M IN OF 26 GAUGE GALVANIZED STEEL TO ACCEPTABLE INDUSTRY
STANDARDS.
8. M ETAL COPING AT PARAPET TO M E M IN OF 22 GAUGE GAALVAN IZED STEEL.
VENTILATION NOTES
1.ALL WORK TO COMPLY WITH THE2018 IRC CHAPTER 15 WITH JURISDICTION AMENDMENTS.
2. SOURCE SPECIFIC FANS SHALL BE LOCATED IN ALL KITCHENS, BATHROOM S,WATER CLOSETS AND LAUNDRY
FACILITIES.VENTILATION CAPACITY SHALL BEAT LEAST 50 C.F.M. FOR BATHROOM AND LAUNDRY ROOMS AND
100 C.F.M. FOR KITCHENS. DUCTING SHALL TERM INATEOUTSIDE THE BUILDING AND SHALL BEEQUIPED WITH
BAC KD RAFT DAMPERS.
3. WHOLE HOUSE VENTILATION SYSTEM SHALL BE CAPABLE OF ,35 AIR EXCHANGES PER HOUR BUT NO M ORE
THAN ,50 AIR EXCHANGES PER HOUR UNDER NORMAL OPERATING CON DITIONS.OUTDOOR AIR SHALL BE
PROVIDED TO ALL HABITABLE ROOM S. FAN SHALL HAVE A STONE RATING OF 1.5 OR LESS M EASURED AT 0.1
INCHES WATER GAUGE.
4. DUCT WORK SHALL CONFORM TO TABLE M 1508.6.2 AND 1506.1 OF THE'2015 IRC CHAPTER 15, WITH
JURISDICTION AMENDMENTS.
5. DUCT SHALL BE INSULATED TO AM IN OF R-4.
6. PROVIDE A MIN NET AREA OF 1 SQ. FT OF VENTILATION AREA FOR EACH 150 SQ. FT OF CRAWL SPACE AREA.
PLACE OPEN INGS AS NEAR AS TO CORNERS AS PRACTICABLE AND SHALL PROVIDE CROSS VENTILATION.
7.ALL CRAWL SPACE VENTS TO BE PROVIDED WITH 1/4" NON -CORROSIVE WIRE MESH.
8. PROVIDE A MIN NET AREA OF 1 SQ. FT OF VENTILATION AREA FOR EACH 150 SQ. FT OF ATTIC AREA. PROVIDE A
CONTINIOUS 1INCH MIN AIRSPACE ABOVE INSULATION FOR CROSS VENTILATION.
9.ALL ATTIC VENTS TO BE PROVIDED WITH 1/4" NON -CORROSIVE W IRE MESH ORAPPROVED SOFFIT VENTS.
10. EXHAUST FAN VENTS SHALL TERMINATE OUTDOORS AND NOT IN ATTICS, SOFFITS, RIDGE VENTS, OR CRAWL
SPACES.
11. KITCHENS, BATHROOM SAND LAUNDRY EXHAUST TERM INATIONS TO EXIT THE STRUCTURE W ITH
CLEARANCES MEETING SRC M1506.3:NOT LESS THAN 3 FEET FROM PROPERTY LINES,3 FEET FROM OPERABLE
OPENINGS INTO THE BUILDING AND 10 FEET FROM MECHANICAL AIR INTAKES
ENERGY NOTES
1. ALL WORK TO COM PLY W ITH WASH INGTON STATE ENERGY CODE W ITH J URISDICTION AM EN DM EN TS W HERE
APPLICABLE. USE PRESCRIPTIVE OPTION UNLESS NOTED OTHERWISE.
2.HEATING UNITS TO MAINTAIN 70 D EG REES FAREN H EIT AT 36" ABOVE FLOO R W H EN 0UTSIDETEMPERATUREIS
24 D EG REES FA REN H EIT, O R C U RREN T REQ U IREM EN TS.
3.CAULK ALL J0INTSAROUND EXTERIOR 0 PEN IN G S AN D ALL J 0 INTS IN SIDINGAND FLASHING WHERE
INFILTRATION MAY BE POSSIBLE.
4. SEAL ALL TEARS AND JOINTS IN INSULATION W ITH APPROVED TAPE.
5.SHOW ERFLOW CO NTRO L LIM ITED TO 2.5 GALLO N S PER M IN UTE, 0 R C U RRENT REQ U IREM ENTS.
6. ALL CRAW LSPACES TO HAVE A M INIM UM OF 6 M IL BLACK VISQUEEN GROUND COVER EXTENDED OVER THE
TOP OF THE FOOTINGS. LAP ALL JOINTS 12" M IN.
7. FIREPLACE(S) SHALL HAVE TIGHT FITTING DAM PERS AN D SHALL BE PROVIDED W ITH A M IN OF 6 SQUARE
INCHES OF OUTSIDE COM BUSTABLE AIR SUPPLY.
8. M ETAL DUCTS OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED TO R-8 M IN PER'2018 WASH INGTON
STATE EN ERGY C O D E", TABLE 5-11 W ITH J U RISD ICTIO N AM EN D M EN TS. PROVID E W EATH ER BARRIER IF LOCATED
ON THE EXTERIOR OF THE BUILDING.
9. SERVICE WATER PIPES LESS THAN 2" IN DIAM ETER SHALL BE WRAPPED W ITH 1" M IN LAYER IF INSULATION.
10. WATER HEATERS TO M EET 1987 NATIONAL APPLIANCE ENERGY CONSERVATION ACT AND SEATTLE ENERGY
CODE TABLE C404.2 AND EFFICIENCY VERIFIED THROUGH APPROVED CERTIFICATION PROGRAM WHEN
APPLICABLE.
11.MINIMUM INSULATION VALUES UNLESS NOTED OTHERWISE:
R402.1.2 - WOOD FRAM E WALL: R-21 IN TERM EDIATE FRAM IN / U-0.056
R402.1.2 - CEILINGS: R-49 / U-0.026
R402.1.2 - BASEM ENT WALLS: R-10 CONTINUOUS INSULATION ON THE EXTERIOR OF THE WALL, R-15
CONTINUOUS INSULATION ON THE INTERIOR OF THE WALL.
R402.1.2-SLAB:R-10,2 FT./ F-FACTOR-0.54
R402.1.2 - FENESTRATION:U-0.30
12.VAPOR RETARDER SHALL BE INSTALLED ON THE CONDITIONED ROOM SIDE OF THE INSULATION.
13. HEADERS TO BE INSULATED TO A MIN OF R-10.
14.PROVIDE 1/2" AIRSPACE BETWEEN SUB -GRADE CONCRETE WALLS AND FRAMING/INSULATION.
15.WRAPALL HOT WATER SUPPLY PIPES WITH SELF -ADHERED PIPE -WRAP FOAM INSULATION.
HCC
netting the rtnn-d8rd
SERVICES@HOM ECARECONTRACTORS.COM
206.984.4543
GOe design
GAIVORONSKA.OLENA@GMAIL.COM
425.595.0691
RECEIVED
Jan 25 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SING LE-FAM ILY
HOUSE INTERIOR
REMODEL
DESIGN
PROPOSAL
BLAC KER
AUSTIN/J UTILA
STEPHAN D
23519 78TH AVEN U E W
EDM ON DS, WA 98026
All rights reserved. No part of this docum ant may be reproduced in any
form or by any m eans without perm ission in writing from GO.design
NO. DATE DESCRIPTION
DETAILS
Project N um ber 2215
Date 01/08/23
Drawn By GO.design
1
2
3
5
6 I 7
A302