FIR2023-0089+Fire_Alarm_Battery_Calculations+9.13.2023_9.57.41_AM+3779887PANEL FACP (GWF-7075) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURRENT (AMPS)
PANEL COMPONENTS
QTY
PART NO.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
1
GWF-7075 Main Board
Intelligent Fire Alarm Control
Panel Main Board
0
0
0
0
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL (A)
FACP•ANN
F^^
1
RA-1000
Remote annunciator for use
with GWF-7075
0.03
0.03
0.065
0.065
OP
20
ASD-PL3 / B300-6 BASE
Addressable, Photo, Det.
0.0003
0.006
0.0003
0.006
FACP•L1
0
4
ATD-L3R / B300-6 BASE
ADDRESSABLE 1357 ROR
HEAT DETECTOR
0.0003
0.0012
0.0003
0.0012
0
1
MS-7ASF
Addressable Pull Station
0.0003
0.0003
0.007
0.007
®4 WID
1
P2RK
Horn/Strobe,WP,Wall, 30cd
0
0
0.116
0.116
3
PC2WL
Horn/Strobe, Ceiling, 15cd
0
0
0.071
0.213
FACP•N1
1
PC2WL
Horn/Strobe, Ceiling, 30cd
0
0
0.09
0.09
1
PC2WL
Horn/Strobe, Ceiling,75cd
0
0
0.143
0.143
xi
1
SCWL
Strobe, Ceiling, 15cd
0
0
0.041
0.041
®4 WP
1
P2RK
Horn/Strobe,WP,Wall , 110cd
0
0
0.221
0.221
4
PC2WL
Horn/Strobe, Ceiling, 15cd
0
0
0.071
0.284
FACP•N2
2
PC2WL
Horn/Strobe, Ceiling, 30cd
0
0
0.09
0.18
1
PC2WL
Horn/Strobe, Ceiling, 75cd
0
0
0.143
0.143
x<
1 5
1 SCWL
Strobe, Ceiling, 15cd
0
1 0
1 0.041
1 0.205
TOTAL STANDBY (A)
1 0.0375
1 TOTAL ALARM (A)
1 1.7152
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A)
0.0375
24
1 0.9
SECONDARY ALARM LOAD (A)
1.7152
0.08
1 0.14
STANDBY AND ALARM SUBTOTAL (AMP HOURS)
1.04
DERATING FACTOR
1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
1.25
PROVIDE (2) 12V 7AH BATTERIES
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.28
FACP N1 POINT-TO-POINT REPORT
Min. Operational Voltage:
16
End Of Line Voltage:
20.12
Max. Circuit Current (A):
2.5
Voltage Drop Percent:
1.38 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.603
Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded
Total Circuit Length (Ft):
129
Spare Current (A):
1.897
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0):
0.793052
Spare Current (A) Percent:
75.88 %
Device Label
Part No.
Description
Device Current
Remaining
Dist. From
Resistance From
Voltage Drop From
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
(A)
Current (A)
Previous (Ft)
Previous (0)
Previous
Nl-001
SCWL
Strobe, Ceiling, White 15cd
0.041
0.603
7
0.045751
0.03
20.37
0.03
0.14 %
Nl-002
PC2WL
Horn/Strobe, Ceiling,
0.071
0.562
22
0.132709
0.07
20.3
0.1
0.50 %
White 15cd
Nl-003
PC2WL
Horn/Strobe, Ceiling,
0.143
0.491
18
0.109087
0.05
20.24
0.16
0.76 %
White 75cd
Nl-004
P2RK
Horn/Strobe,WP,Wall ,
0.116
0.348
40
0.246455
0.09
20.16
0.24
1.18 %
Red 30cd
Nl-005
PC2WL
Horn/Strobe, Ceiling,
0.071
0.232
11
0.069696
0.02
20.14
0.26
1.26 %
White 15cd
Nl-006
PC2WL
Horn/Strobe, Ceiling,
0.071
0.161
16
0.096179
0.02
20.13
0.27
1.34 %
White 15cd
N1.007 EOL
PC2WL
Horn/Strobe, Ceiling,
0.09
0.09
15
0.093175
0.01
20.12
0.28
1.38 %
White 30cd
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (D/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.72
FACP N2 POINT-TO-POINT REPORT
Min. Operational Voltage:
16
End Of Line Voltage:
19.68
Max. Circuit Current (A):
2.5
Voltage Drop Percent:
3.55 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
1.033
Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded
Total Circuit Length (Ft):
211
Spare Current (A):
1.467
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (f2):
1.292853
Spare Current (A) Percent:
58.68 %
Device Label
Part No.
Description
Device Current
Remaining
Dist. From
Resistance From
Voltage Drop From
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
(A)
Current (A)
Previous (Ft)
Previous (0)
Previous
N2.001
PC2WL
Horn/Strobe, Ceiling,
0.071
1.033
30
0.1842
0.19
20.21
0.19
0.93 %
White 15cd
N2.002
SCWL
Strobe, Ceiling, White
0.041
0.962
12
0.075828
0.07
20.14
0.26
1.29 %
15cd
Horn/Strobe, Ceiling,
N2.003
PC2WL
White 75cd
0.143
0.921
13
0.082137
0.08
20.06
0.34
1.66 %
Strobe, Ceiling, White
N2.004
SCWL
15cd
0.041
0.778
23
0.141139
0.11
19.95
0.45
2.20 %
N2.005
PC2WL
Horn/Strobe, Ceiling,
0.071
0.737
9
0.056303
0.04
19.91
0.49
2.40 %
White 15cd
N2.006
SCWL
Strobe, Ceiling, White
0.041
0.666
9
0.05526
0.04
19.87
0.53
2.58 %
15cd
N2.007
P2RK
Horn/Strobe,WP,Wall ,
0.221
0.625
8
0.047984
0.03
19.84
0.56
2.73 %
Red 110cd
N2.008
PC2WL
Horn/Strobe, Ceiling,
0.09
0.404
31
0.188358
0.08
19.77
0.63
3.10 %
White 30cd
N2.009
PC2WL
Horn/Strobe, Ceiling,
0.071
0.314
24
0.145104
0.05
19.72
0.68
3.33 %
White 15cd
Strobe, Ceiling, White
N2.010
SCWL
15cd
0.041
0.243
4
0.023411
0.01
19.72
0.68
3.35 %
N2.011
PC2WL
Horn/Strobe, Ceiling,
0.071
0.202
11
0.068704
0.01
19.7
0.7
o
3.42 /o
White 15cd
N2.012
SCWL
Strobe, Ceiling, White
0.041
0.131
20
0.125623
0.02
19.69
0.71
3.50 %
15cd
N2.013 EOL
PC2WL
Horn/Strobe, Ceiling,
0.09
0.09
16
0.098802
0.01
19.68
0.72
3.55 %
White 30cd
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (f)/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
BATTERY & VOLTAGE DROP CALCULATIONS
N2.007
N2.013 EOL N2.012 N2.011 N2.010 N2.009 N2.008 110cd N2.006 N2.005 N2.004 N2.003 N2.002 N2.001
30cd 15cd , _ ,15cd 15cd , _ ,15cd _ , 30cd WP 15cd , _ ,15cd 15cd , _ , 75cd 15cd , _ ,15cd
L1•DO13 L1•DO14 L1•DO15 L1•DO16 L1•DO17 L1•DO18 L1•DO19 L1•D020 L1•D021 L1•D022 L1•D023 L1•D024
---------------------------------- SECOND FLOOR
INSTALLATION KEY NOTES
O
A DEDICATED 120VAC POWER CIRCUITS IS REQUIRED FOR THE FACP AND AES RADIO. COORDINATE CONNECTIONS OF
DEDICATED POWER WITH THE E.C.
O
OUTDOOR HORN/STROBE TO BE INSTALLED IN A LOCATION THAT IS SERVICEABLE AND CLEARLY VISIBLE FOR
APPROACHING EMERGENCY VEHICLES.
3a)
ADDITIONAL OUTDOOR HORN/STROBE PROVIDED FOR PLAYGROUND AREA OCCUPANT NOTIFICATION.
CABLE - WIRE LEGEND
LINE TYPE
LABEL
CABLE TYPE
AWG
RESIST.
(- /Kft)
DESCRIPTION
A
14/2 FPLR
14
3.07
NAC : NOTIFICATION APPLIANCE CIRCUIT
D
18/4 FPLR
18
7.77
SBUS : ANNUNCIATOR
U
18/2 FPLR
18
7.77
SLC : SIGNALING LINE CIRCUIT
FIRE PROTECTION INC.
17410 Ash Way, Ste 8
Lynnwood, WA 98037
425-290-9600
FPISEATTLE.COM
VSOTEC;LU
NFP
CFPS
#1473
(AA QB QC QD QE a
W
I >
_ _ _ _- W
I w CO) CO zv �
FTE
Cn
EMPLOYEE oCKI
LUNCH RM®® 2 c9
®® !2a N
OFFICE � >- W a
L1•D018 1 H N•00 oC'j >-ww
_ 1351_ 75cd _ _ _ - � � o LL U)0
cd T2A Z�w JUG
�: �- w
1A L1•D021 ' ' s L1•D017 a W 5 Q- O
s 1 U N2.002 0 z W wui -j a o
N2.010 H I N2.009 s 1•D020 15cd REVISION RECORD
15 15cd U 2A
N21 S UI-FICE DATE / DESCRIPTION
�` -50 N 001 lA:DN TO TH ACP
s •D021 1A L1•D01 L1•DO16 15cd ATTC
L1•DU s s H L°EJ
H �1•D01 s s L1•DO13 1U:DN TO THE FACP
H N2.008 1A
N2.013 EOL ' 30cd N2.004 2A FFICE
30cd 1U N2.005
- - - - - - H 15cd
OFFICE OFFI E
D015 i 135°
I N-006 2A
2 N2.007_ _
110cd
WP
I I I
I I I FIR2023-0089
SECOND FLOOR PLAN
SCALE: 1 /8" = 1'
I I I I
' N' •004
--�- ❑-O WW -- o
-�- - ---
(1 MAN
(1)
VAN
FFICE OFF, ICE
I
1A
Lj •DO
2
s
L1•DO09
s
N 1.006 H s
15cd
1L
OFFICE
L1•D011 s
I
H
Nl-007 EOL `
30cd '
RECEPTION
I
N 1.004 ®°A.® Ca�U,T FAA
N1.007 EOL Nl-006 Nl-005 30cd Nl-003 Nl-002 Nl-001
30cd 15cd 15cd WP 75cd 15cd 15cd L1•M001 L1•D001 L1•D002 L1•D003 L1•D004 L1•D005 L1•D006 L1•D007 L1•D008 L1•D009 L1•D010 L1•D011 L1•DO12
H H H H FACP '
5 -�
oii u
I
FIRST
-----------------------------------------------------------------------FLOOR
II
(1) MA 1U
C�FFIC'.F
s L1•D001
1.0
BREA ROOM
OFFICE
T
15cd
H
1A
001
I
F Doc
,
L1•DO03
FACP I AES 1A
s-
-
- -
•D007
1D
35°
N1.01
15cd
1 U
A
002
0
S H
L1•DO04
Nl-002
15cd II
1D
II
-
- I
- -
In
1A: UP TO 2ND FLOOR
1 D012
I I L
Nl-003
_ _ _ Jam_ OUTLINEOF
CLOSET ABOVE
L1•DO05
75cd
1 U: UP TO 2ND FLOOR
s S
L1•D006
I
91
-
-IORK JREA
i i BEAM
I I
I
I I
I
RECEIVED
Sep 13 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
DATE:
1 09.01.23
PROJECT NAME
W
LU
-
LU
V
cc
W
CN
O
V
00
Q
Q
O
C
ti
0
O
Z
r
O
r
Q
N
Q
LL
LLB
O
Z
SHEET TITLE
FIRE ALARM
INSTALLATION
SINGLE LINE RISER DIAGRAM
FIRST FLOOR PLAN
SCALE: 1 /8" = 1'
SHEET NUMBER I
FA 1m0