FIR2023-0089+Fire_Alarm_Battery_Calculations+9.13.2023_9.57.41_AM+3779887PANEL FACP (GWF-7075) BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) PANEL COMPONENTS QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL 1 GWF-7075 Main Board Intelligent Fire Alarm Control Panel Main Board 0 0 0 0 CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) FACP•ANN F^^ 1 RA-1000 Remote annunciator for use with GWF-7075 0.03 0.03 0.065 0.065 OP 20 ASD-PL3 / B300-6 BASE Addressable, Photo, Det. 0.0003 0.006 0.0003 0.006 FACP•L1 0 4 ATD-L3R / B300-6 BASE ADDRESSABLE 1357 ROR HEAT DETECTOR 0.0003 0.0012 0.0003 0.0012 0 1 MS-7ASF Addressable Pull Station 0.0003 0.0003 0.007 0.007 ®4 WID 1 P2RK Horn/Strobe,WP,Wall, 30cd 0 0 0.116 0.116 3 PC2WL Horn/Strobe, Ceiling, 15cd 0 0 0.071 0.213 FACP•N1 1 PC2WL Horn/Strobe, Ceiling, 30cd 0 0 0.09 0.09 1 PC2WL Horn/Strobe, Ceiling,75cd 0 0 0.143 0.143 xi 1 SCWL Strobe, Ceiling, 15cd 0 0 0.041 0.041 ®4 WP 1 P2RK Horn/Strobe,WP,Wall , 110cd 0 0 0.221 0.221 4 PC2WL Horn/Strobe, Ceiling, 15cd 0 0 0.071 0.284 FACP•N2 2 PC2WL Horn/Strobe, Ceiling, 30cd 0 0 0.09 0.18 1 PC2WL Horn/Strobe, Ceiling, 75cd 0 0 0.143 0.143 x< 1 5 1 SCWL Strobe, Ceiling, 15cd 0 1 0 1 0.041 1 0.205 TOTAL STANDBY (A) 1 0.0375 1 TOTAL ALARM (A) 1 1.7152 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SECONDARY STANDBY LOAD (A) 0.0375 24 1 0.9 SECONDARY ALARM LOAD (A) 1.7152 0.08 1 0.14 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 1.04 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 1.25 PROVIDE (2) 12V 7AH BATTERIES CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.28 FACP N1 POINT-TO-POINT REPORT Min. Operational Voltage: 16 End Of Line Voltage: 20.12 Max. Circuit Current (A): 2.5 Voltage Drop Percent: 1.38 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.603 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 129 Spare Current (A): 1.897 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.793052 Spare Current (A) Percent: 75.88 % Device Label Part No. Description Device Current Remaining Dist. From Resistance From Voltage Drop From Voltage At Device Total Voltage Drop Voltage Drop Percent (A) Current (A) Previous (Ft) Previous (0) Previous Nl-001 SCWL Strobe, Ceiling, White 15cd 0.041 0.603 7 0.045751 0.03 20.37 0.03 0.14 % Nl-002 PC2WL Horn/Strobe, Ceiling, 0.071 0.562 22 0.132709 0.07 20.3 0.1 0.50 % White 15cd Nl-003 PC2WL Horn/Strobe, Ceiling, 0.143 0.491 18 0.109087 0.05 20.24 0.16 0.76 % White 75cd Nl-004 P2RK Horn/Strobe,WP,Wall , 0.116 0.348 40 0.246455 0.09 20.16 0.24 1.18 % Red 30cd Nl-005 PC2WL Horn/Strobe, Ceiling, 0.071 0.232 11 0.069696 0.02 20.14 0.26 1.26 % White 15cd Nl-006 PC2WL Horn/Strobe, Ceiling, 0.071 0.161 16 0.096179 0.02 20.13 0.27 1.34 % White 15cd N1.007 EOL PC2WL Horn/Strobe, Ceiling, 0.09 0.09 15 0.093175 0.01 20.12 0.28 1.38 % White 30cd Calculation Methods: Resistance From Previous (0) = Wire Resistance (D/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.72 FACP N2 POINT-TO-POINT REPORT Min. Operational Voltage: 16 End Of Line Voltage: 19.68 Max. Circuit Current (A): 2.5 Voltage Drop Percent: 3.55 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 1.033 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 211 Spare Current (A): 1.467 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (f2): 1.292853 Spare Current (A) Percent: 58.68 % Device Label Part No. Description Device Current Remaining Dist. From Resistance From Voltage Drop From Voltage At Device Total Voltage Drop Voltage Drop Percent (A) Current (A) Previous (Ft) Previous (0) Previous N2.001 PC2WL Horn/Strobe, Ceiling, 0.071 1.033 30 0.1842 0.19 20.21 0.19 0.93 % White 15cd N2.002 SCWL Strobe, Ceiling, White 0.041 0.962 12 0.075828 0.07 20.14 0.26 1.29 % 15cd Horn/Strobe, Ceiling, N2.003 PC2WL White 75cd 0.143 0.921 13 0.082137 0.08 20.06 0.34 1.66 % Strobe, Ceiling, White N2.004 SCWL 15cd 0.041 0.778 23 0.141139 0.11 19.95 0.45 2.20 % N2.005 PC2WL Horn/Strobe, Ceiling, 0.071 0.737 9 0.056303 0.04 19.91 0.49 2.40 % White 15cd N2.006 SCWL Strobe, Ceiling, White 0.041 0.666 9 0.05526 0.04 19.87 0.53 2.58 % 15cd N2.007 P2RK Horn/Strobe,WP,Wall , 0.221 0.625 8 0.047984 0.03 19.84 0.56 2.73 % Red 110cd N2.008 PC2WL Horn/Strobe, Ceiling, 0.09 0.404 31 0.188358 0.08 19.77 0.63 3.10 % White 30cd N2.009 PC2WL Horn/Strobe, Ceiling, 0.071 0.314 24 0.145104 0.05 19.72 0.68 3.33 % White 15cd Strobe, Ceiling, White N2.010 SCWL 15cd 0.041 0.243 4 0.023411 0.01 19.72 0.68 3.35 % N2.011 PC2WL Horn/Strobe, Ceiling, 0.071 0.202 11 0.068704 0.01 19.7 0.7 o 3.42 /o White 15cd N2.012 SCWL Strobe, Ceiling, White 0.041 0.131 20 0.125623 0.02 19.69 0.71 3.50 % 15cd N2.013 EOL PC2WL Horn/Strobe, Ceiling, 0.09 0.09 16 0.098802 0.01 19.68 0.72 3.55 % White 30cd Calculation Methods: Resistance From Previous (0) = Wire Resistance (f)/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) BATTERY & VOLTAGE DROP CALCULATIONS N2.007 N2.013 EOL N2.012 N2.011 N2.010 N2.009 N2.008 110cd N2.006 N2.005 N2.004 N2.003 N2.002 N2.001 30cd 15cd , _ ,15cd 15cd , _ ,15cd _ , 30cd WP 15cd , _ ,15cd 15cd , _ , 75cd 15cd , _ ,15cd L1•DO13 L1•DO14 L1•DO15 L1•DO16 L1•DO17 L1•DO18 L1•DO19 L1•D020 L1•D021 L1•D022 L1•D023 L1•D024 ---------------------------------- SECOND FLOOR INSTALLATION KEY NOTES O A DEDICATED 120VAC POWER CIRCUITS IS REQUIRED FOR THE FACP AND AES RADIO. COORDINATE CONNECTIONS OF DEDICATED POWER WITH THE E.C. O OUTDOOR HORN/STROBE TO BE INSTALLED IN A LOCATION THAT IS SERVICEABLE AND CLEARLY VISIBLE FOR APPROACHING EMERGENCY VEHICLES. 3a) ADDITIONAL OUTDOOR HORN/STROBE PROVIDED FOR PLAYGROUND AREA OCCUPANT NOTIFICATION. CABLE - WIRE LEGEND LINE TYPE LABEL CABLE TYPE AWG RESIST. (- /Kft) DESCRIPTION A 14/2 FPLR 14 3.07 NAC : NOTIFICATION APPLIANCE CIRCUIT D 18/4 FPLR 18 7.77 SBUS : ANNUNCIATOR U 18/2 FPLR 18 7.77 SLC : SIGNALING LINE CIRCUIT FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM VSOTEC;LU NFP CFPS #1473 (AA QB QC QD QE a W I > _ _ _ _- W I w CO) CO zv � FTE Cn EMPLOYEE oCKI LUNCH RM®® 2 c9 ®® !2a N OFFICE � >- W a L1•D018 1 H N•00 oC'j >-ww _ 1351_ 75cd _ _ _ - � � o LL U)0 cd T2A Z�w JUG �: �- w 1A L1•D021 ' ' s L1•D017 a W 5 Q- O s 1 U N2.002 0 z W wui -j a o N2.010 H I N2.009 s 1•D020 15cd REVISION RECORD 15 15cd U 2A N21 S UI-FICE DATE / DESCRIPTION �` -50 N 001 lA:DN TO TH ACP s •D021 1A L1•D01 L1•DO16 15cd ATTC L1•DU s s H L°EJ H �1•D01 s s L1•DO13 1U:DN TO THE FACP H N2.008 1A N2.013 EOL ' 30cd N2.004 2A FFICE 30cd 1U N2.005 - - - - - - H 15cd OFFICE OFFI E D015 i 135° I N-006 2A 2 N2.007_ _ 110cd WP I I I I I I FIR2023-0089 SECOND FLOOR PLAN SCALE: 1 /8" = 1' I I I I ' N' •004 --�- ❑-O WW -- o -�- - --- (1 MAN (1) VAN FFICE OFF, ICE I 1A Lj •DO 2 s L1•DO09 s N 1.006 H s 15cd 1L OFFICE L1•D011 s I H Nl-007 EOL ` 30cd ' RECEPTION I N 1.004 ®°A.® Ca�U,T FAA N1.007 EOL Nl-006 Nl-005 30cd Nl-003 Nl-002 Nl-001 30cd 15cd 15cd WP 75cd 15cd 15cd L1•M001 L1•D001 L1•D002 L1•D003 L1•D004 L1•D005 L1•D006 L1•D007 L1•D008 L1•D009 L1•D010 L1•D011 L1•DO12 H H H H FACP ' 5 -� oii u I FIRST -----------------------------------------------------------------------FLOOR II (1) MA 1U C�FFIC'.F s L1•D001 1.0 BREA ROOM OFFICE T 15cd H 1A 001 I F Doc , L1•DO03 FACP I AES 1A s- - - - •D007 1D 35° N1.01 15cd 1 U A 002 0 S H L1•DO04 Nl-002 15cd II 1D II - - I - - In 1A: UP TO 2ND FLOOR 1 D012 I I L Nl-003 _ _ _ Jam_ OUTLINEOF CLOSET ABOVE L1•DO05 75cd 1 U: UP TO 2ND FLOOR s S L1•D006 I 91 - -IORK JREA i i BEAM I I I I I I RECEIVED Sep 13 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT DATE: 1 09.01.23 PROJECT NAME W LU - LU V cc W CN O V 00 Q Q O C ti 0 O Z r O r Q N Q LL LLB O Z SHEET TITLE FIRE ALARM INSTALLATION SINGLE LINE RISER DIAGRAM FIRST FLOOR PLAN SCALE: 1 /8" = 1' SHEET NUMBER I FA 1m0