Loading...
FIR2021-0139+Fire_Alarm_Battery_Calculations+12.6.2021_2.42.03_PM+2555791WOODWAY ELEMENTARY SCHOOL FIRE ALARM SYSTEM REPLACEMENT/UPGRADE SHEET INDEX FA0.01 GENERAL NOTES, CODE INFORMATION, MATRIX FA0.02 FIRE ALARM: WIRE DESIGNATIONS, SYMBOL LIST FA0.03 FIRE ALARM: SYSTEM CALCULATIONS FA0.04 FIRE ALARM: SYSTEM DETAILS FA0.05 FIRE ALARM: SYSTEM DETAILS FA1.01 FIRE ALARM: SITE PLAN FA4.01 FIRE ALARM: BUILDING G FA4.02 FIRE ALARM: BUILDING A FA4.03 FIRE ALARM: BUILDING E FA4.04 FIRE ALARM: BUILDING F FA4.05 FIRE ALARM: BUILDING B FA4.06 FIRE ALARM: BUILDING D FA4.07 FIRE ALARM: BUILDING F FA4.08 FIRE ALARM: PORTABLES, FACP AREA DETAIL CODE/PROJECT INFORMATION v Q L 0 Handy `� r ® v 'oodwa 0 Q 237th PI SW id Salon 0 S o Subsurface Construction 238th St SW s a y d D 2381h St svi 238th St SW are Center Ao repair shop SW O I T�. w t M 240th St SW 240th St SW A 9 Angry Fish P 190 240th PI SW 2401h PI SW 240th PI SW O 0 9 T. a m P - Z41 st PI SW n f 240th St SW 241 st PI SW Andy's automotive 0 521 240th St SW, dmonds. WA 98020 Elementary '36th St SW Madrona K-8 School 19 OWNER: EDMONDS SCHOOL DISTRICT #15, LPROJECT SITE LYNNWOOD, WA GENERAL CONTRACTOR: PACIFIC MOBILE STRUCTURES, MARYSVILLE WA ELECTRICAL CONTRACTOR: SCOTT'S ELECTRIC SERVICE, MONROE, WA TAX ID/PARCEL: 27033600404600 FIRE ALARM AUTHORITY: CITY OF EDMONDS FIRE ALARM PERMIT: TBD OCCUPANCY: CLASS: MIXED, PRIMARILY E LOAD: MAIN BUILDING PER ARCH PLANS, PORTABLES EACH < 100 CONSTRUCTION: TYPE: PER ARCH PLANS SPRINKLED: NO CODES: CITY OF EDMONDS MUNICIPAL CODE: 14.07 IFC (2015ed) NFPA72 (2016ed) WAC 51-54A-0907 SCOPE RESPONSIBILITIES: WASHINGTON ALARM TO FURNISH/INSTALL ALL EQUIPMENT SHOWN (UNLESS NOTED), INCLUDING DETECTION AND CONTROL PANELS. LOW VOLTAGE WIRING, 120VAC WIRING, AND FIELD TRIM PROVIDED BY SCOTTS ELECTRIC SERVICE. PROJECT DESCRIPTION: MAIN BUILDINGS: REPLACEMENT OF EXISTING MANUAL, PARTIAL AUTOMATIC, PREVIOUSLY ACCEPTED FIRE ALARM SYSTEM, ADD VOICE SYSTEM, EMPLOYING FULL EVACUATION ONLY. PORTABLES: NEW MANUAL AND AUTOMATIC COVERAGE CONNECTED TO MAIN BUILDING, WITH FULL OCCUPANT NOTIFICATION. FIRE ALARM PATHWAY CLASS DESIGNATIONS: NOTIFICATION APPLIANCE CIRCUIT(S): B SIGNALING LINE CIRCUIT(S): B INITIATION DEVICE CIRCUIT(S): SPRINKLER WATERFLOWS=B, ALL OTHERS=B SURVIVABILITY: 0 (NONE REQUIRED) COMMUNICATION METHOD: GENERAL INSTALLATION NOTES 1. NOT ALL GENERAL NOTES MAY BE IN EFFECT FOR THIS INSTALLATION AND SCOPE OF WORK. 2. FOR THE PURPOSE OF THIS INSTALLATION, SPRINKLER MONITORING AND FIRE ALARM ARE INTERCHANGEABLE AND EQUAL. SEE SCOPE/PROJECT NARRATIVE. 3. PER IFC (2015ed/2018ed) 907.1.3, ALL WIRE AND DEVICES CONNECTED TO THE FIRE ALARM SYSTEM SHALL BE LISTED BY AN APPROVED LISTING AGENCY (TYPICALLY UL OR FM,) COMPATIBLE, AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS AND INSTRUCTIONS. INSTALLATION SHALL BE IN ACCORDANCE WITH ALL AUTHORITIES HAVING JURISDICTION (AHJ), NFPA, IFC, NEC, WAC, MUNICIPAL CODE, AND CONTRACT DOCUMENTS. 4. INSTALLING CONTRACTOR(S) SHALL PROVIDE WASHINGTON ALARM WITH A LEGIBLE, CLEAN, AND ACCURATELY NOTED DRAWING FOR "AS BUILT" PURPOSES. THE DRAWINGS SHALL INCLUDE PERTINENT WIRE RUNS, CONDUIT SIZES/LOCATIONS, JUNCTION BOXES, SIGNIFICANT DEVICE LOCATION CHANGES, MOUNTING HEIGHTS THAT DIFFER FROM LISTED HEIGHTS, AND 120VAC POWER CIRCUIT PANEL LOCATIONS/CIRCUIT NUMBERS. 5. FIRE ALARM DOCUMENTATION SHALL NOT BE STORED IN THE FIRE ALARM CONTROL UNIT PER NFPA72 (2019ed) 7.7.2.3. AN APPROPRIATE RECORDS ENCLOSURE SHALL BE SUPPLIED. 6. PROTECTED PREMISES FIRE ALARM (NFPA72, 2016ed: 3.3.103.4, OR NFPA72, 2019ed: 3.3.111.4) SYSTEMS SHALL BE MONITORED BY A LISTED SUPERVISING STATION (NFPA72, 2016ed: 3.3.280 OR NFPA72, 2019ed 3.3.290) IN ACCORDANCE WITH IFC (2015ed/2018ed) 907.6.6. COMMUNICATION METHODS SHALL BE IN ACCORDANCE WITH NFPA72 (2016ed/2019ed) 26.6. COMMUNICATION VIA DACT (2 "POTS" LINES) ALONE IS NOT ACCEPTABLE WITHOUT APPROVAL BY ALL AHJ 'S PER NFPA72 (2016ed/2019ed) 26.6.4.1.4. MONITORING MAY BE SUBJECT TO DEFERRED CONTRACT, AND MAY BE PERFORMED BY OTHERS BEYOND THE CONTROL OF WASHINGTON ALARM. 7. ALL 120VAC WIRING TO CONTROL UNITS AS DEFINED BY NFPA72 (2016ed) 3.3.60, 3.3.100, 3.3.196 OR NFPA72 (2019ed) 3.3.63, 3.3.108, 3.3.206 SHALL BE PERMITTED (SEPARATELY IF REQUIRED BY AHJ AND INSTALLED BY AN ELECTRICAL CONTRACTOR LICENSED TO PERFORM SUCH WORK. ALL 120VAC WIRING TO CONTROL UNITS AND POWER SUPPLIES SHALL BE DEDICATED, LABELED, AND INSTALLED WITH A BREAKER LOCK (SPACE AGE ELOCK-FA OR EQUAL). ALL CONTROL UNITS AND POWER SUPPLIES SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF WASHINGTON ALARM STAFF. ALL 120VAC WIRING ENTERING FIRE ALARM CABINETS SHALL BE THROUGH DEDICATED KNOCKOUTS, AND SHALL MAINTAIN A MINIMUM OF 0.25" SEPARATION FROM POWER LIMITED/LOW VOLTAGE WIRING. 8. THIS PROJECT MAY EMPLOY A SEPARATE ELECTRICAL CONTRACTOR AND FIRE ALARM CONTRACTOR IN A JOINT VENTURE. UNLESS OTHERWISE NOTED BY ANY CONTRACT DOCUMENTS, THE ELECTRICAL CONTRACTOR SHALL PERMIT (SEPARATELY, IF REQUIRED BY THE AHJ), FURNISH AND INSTALL ALL BACKBOXES, RACEWAY, AND WIRE PER WASHINGTON ALARM SPECIFICATIONS. ELECTRICAL CONTRACTOR SHALL INSTALL ALL SPECIALTY BACKBOXES, ENCLOSURES, FIRE ALARM TERMINAL CABINETS PROVIDED BY WASHINGTON ALARM. PLEASE ALLOW FOR A MINIMUM TWO WEEK LEAD TIME ON ALL WASHINGTON ALARM SUPPLIED EQUIPMENT. 9. WIRING SHALL BE PER DESIGN WITH RESPECT TO CONDUCTOR SIZE AND/OR CABLE TRAY. TYPE, QUANTITY, COLOR CODE AND CONDUCTORS SHALL BE PERMANENTLY AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. ELECTRICAL CONTRACTOR SHALL MAINTAIN THE CLEANLINESS OF ALL INSTALLED BOXES/ENCLOSURES. DIRT/DEBRIS SHALL BE CLEANED PRIOR TO TRIM. 10. WIRING SHALL CUT FOR IN/OUT. WIRING SHALL NEVER BE LOOPED THROUGH DEVICES, ALL SPLICED WIRE POSSESSING SHIELD SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. 11. WIRING SHALL RUN CONTINUOUS FROM SOURCE TO FIRST DEVICE ON CIRCUIT THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACKBOXES OF DIFFERENCT CIRCUITS. 'IT -TAPPING" OF CONVENTIONAL INITIATION (IDC'S) OR NOTIFICATION APPLIANCE CIRCUITS (NAC'S) WILL RESULT IN A NON FUNCTIONAL SYSTEM, AND IS STRICTLY PROHIBITED. 12. WIRING SHALL BE METERED AND VERIFIED TO BE CONTINUOUS, FREE FROM GROUND, SHORTS, OR ANY OTHER FAULTS. 13. WIRING SHALL BE IN CONDUIT, OR CONCEALED/HIDDEN. SURFACE MOUNT WIRING INSTALLATION ALLOWABLE WHEN APPROVED BY OWNER, OWNER REP., OR PROJECT TEAM AND COMPLIANT WITH ADOPTED CODES. 14. NUMBERS ADJACENT TO NOTIFICATION SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS, OR NOTIFICATION SETTING. EXAMPLE DEVICE SC1-9 WOULD BE NINTH DEVICE ON SIGNAL CIRCUIT 1, FOLLOWED BY A MINIMUM CANDELA RATING SETTING. NOTIFICATION CIRCUIT WIRING IS SUPERVISED. PARALLEL BRANCHING IS NOT PERMISSIBLE. 15. WALL MOUNT SIGNALLING APPLIANCES SHALL BE INSTALLED PER THE HEIGHTS LISTED BY THE SYSTEM DESIGNER/WASHINGTON ALARM IN ORDER TO ACHIEVE CURRENT COMPLIANCE AS WELL AS POTENTIAL MANUFACTURING DESIGN CHANGES IN THE FUTURE. COMPLIANCE WITH NFPA72 (2016ed/2019ed)18.5.5 WHERE THE ENTIRE LENS OF STROBE IS NOT LESS THAN 80" AND NOT GREATER THAN 96" ABOVE FINISHED FLOOR. SEE ALSO NFPA72 CHAPTER 18 FOR LOW WALL HEIGHT, SLEEPING AREA, OR CEILING MOUNTING INSTALLATIONS. 16. DO NOT DEVIATE FROM CIRCUIT RUNS SHOWN ON PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM DESIGNER/WASHINGTON ALARM. SYSTEM SHALL BE INSTALLED WITH MINIMUM 20% SPARE CAPACITY (SUBJECT TO ADDITIONAL CONTRACT REQUIREMENTS) PER IFC (2015ed/2018ed) 907.5.2.3.1. FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ENGINEERING, ADDITIONAL COMPONENTS, ETC... SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR DICTATING AS BUILT ROUTING. 17.NOTIFICATION APPLIANCES SHALL PRODUCE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE THE AMBIENT NOISE LEVELS AND REMAIN IN COMPLIANCE WITH WASHINGTON STATE ADMINISTRATIVE CODE (WAC) 51-54A-0907. NON VOICE SYSTEMS SHALL SOUND IN THE STANDARD TEMPORAL THREE PATTERN AT THE LOWEST DECIBEL SETTING (90dB) UNLESS OTHERWISE NOTED ON PLANS. ALL VISUAL DEVICE CANDELA RATINGS ARE DETERMINED IN ACCORDANCE WITH NFPA72 (2016ed/2019ed) 18.5.5.4. 18. RISER ROOMS CONTAINING FIRE ALARM CONTROL UNITS SHALL BE SIZED APPROPRIATELY IN ACCORDANCE WITH IFC 901.4.6. ALL DEVICES SHALL BE ACCESSIBLE OR MADE ACCESSIBLE (BY WAY OF HATCH, CATWALK ABOVE CEILING GRID, REMOVABLE PANELS) FOR ALL CURRENT AND FUTURE INSTALLATION, TESTING OR MAINTENANCE REQUIREMENTS. ACCESSIBILITY SHALL BE IN ACCORDANCE WITH NFPA72 (2016ed/2019ed) 3.3.1 - 3.3.4. 19. ANY POST CONTRACT ISSUANCE CHANGES TO CONSTRUCTION, INCLUDING THE LOCATION AND TYPE OF WALLS, CEILINGS, PERMANENT FIXTURES MAY AFFECT DESIGN, AND SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE SYSTEM DESIGNER/WASHINGTON ALARM, AS A RE -REVIEW BY ALL AHYS MAY BE REQUIRED. 20.SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 36" FROM AN AIR SUPPLY DIFFUSER. 21.DO NOT INSTALL SMOKE DETECTOR HEADS UNTIL FINAL CLEANING, OR IF UNPRACTICAL DUE TO CONSTRUCTION SCHEDULES, SMOKE DETECTORS SHALL BE PROTECTED FROM CONSTRUCTION DUST AND OTHER ENVIRONMENTAL CONCERNS. 22.ALL DETECTORS SHALL BE RATED FOR THE TEMPERATURE AND ENVIRONMENT FOR THE LOCATION IN WHICH THEY ARE INSTALLED. 23.IN ACCORDANCE WITH IFC (2015ed/2018ed) 907.2 AND NFPA72 (2016ed/2019ed) 23.8.5.1.2, MANUAL PULL STATIONS INSTALLED IN A SPRINKLER RISER ROOM SHALL BE ACTIVE AT ALL TIMES INCLUDING DURING SPRINKLER OR AUTOMATIC DETECTION IMPAIRMENT, OR WHEN SYSTEM IS IN "TEST". APPROPRIATE WARNING SIGNAGE SHALL BE PLACED ADJACENT. 24. WASHINGTON ALARM TO PROVIDE RECORD OF COMPLETION (SEE NFPA EDITION ADOPTED BY JURISDICTION) DOCUMENT AT FIRE ALARM FINAL INSPECTION WITH AHJ. EDMONDS, WASHINGTON FIRE ALARM OPERATION MAT U J J U_ -- J J J J 0 J Q z z z z z z Q 2 O O O O O 0 Of z o 0 Q Q Q Q Q Q 0 ZO � O O D w U V) V) V) V) V) V) z m U 0 U W U oCU L J J J>_ J J � J � V Q LL WU °Cz o LQU Uo z z>- p z- z z� z N H- a OUTPUT 0 J O W O z d O -- p W W� W> W W W W~ Q Z Q z d W Q U 0 0 0� W U U= U w �~„ �� _O z � Q J� m� �� � �> �� � �� F ~a Q 0 N m� o� o ow oLA o o= o wa �a J N-'J �N LU >J .�.�� �~ �O a~ 0 2 W 2LU2H-�W�� W W U W J W� W H-� NW zoC �0 W J W J W0 0Z O� OC� OCN �z �m c� �N Z W N ~� L U< ~H- Q N L U LU ~--0 Q W �� O Q O N O t f O O O U O V) �_ D INPUT Q� Qof >� t:! QQ >V �Q oc� JJ Q JQ J�--� C) JU JW v, JLU � �L_U N QZQ U- 0 U U N U N W O z L U z L:L.i z L:L.i z L:L.i z L:L.i z L:L.i O W Q d °C w LU U W LQ W > , L? >- �? � �? � �? � �? � W W O Q Q U z Q r-r U ` Q G O d ->_ Un [ Un H- V) H- V) H- V) H- V) H- d OC J LL ALARM: ANY AREA SMOKE DETECTION X X X X X ALARM: ANY HEAT DETECTION X X X X X ANY MANUAL PULL STATION ACTIVATION X X X X X ALARM STATE: FACP REMOTE MIC KEY X X NORMAL STATE: FACP REMOTE MIC KEY X X ALARM STATE: SILENCE BUTTON PRESSED X X X X X X ALARM STATE: RESET BUTTON PRESSED X X X COMPONENT/DEVICE TROUBLE, OPEN CIRCUIT SHORT ON SLC/DATA CIRCUIT WIRING 4 4 4 COMPONENT/DEVICE TROUBLE, OPEN CIRCUIT SHORT ON NAC CIRCUIT WIRING X X X COMMUNICATION FAIL/TROUBLE 2 2 X AC FAILURE 1 1 X OPERATIONS MATRIX NOTES NOTE 1: AC FAIL DELAY 3-6 HOURS NOTE 2: SYSTEM WILL TRANSMIT IF ABLE NOTE 3: COORDINATE WITH HVAC CONTRACTOR GLOBAL/INDIVIDUAL SHUTDOWNS NOTE 4: SYSTEM EMPLOYS ISOLATION MODULES TO LIMIT DATA CIRCUIT FAULT PER NFPA72 (2019ed) 23.6 NOTE 5: COORDINATE LOCKDOWN RESPONSE WITH SECURITY VENDOR, PROJECT TEAM, AND OWNER. Approved by Fire 12/13/2021 AFM k_/F�tterer On Building 'G' Plan FA4.01: 1. Add a ANN panel, to be located inside double doors to gym. 2. Exterior WP HS needs to be near double doors and add a Knox type keybox, installed for access to ANN panel. 3. Add exterior WP HS outside entrance to room with FACP located inside and add a Knox type keybox for access to PACP. WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 12 APR 2021 RO-INITIAL DESIGN Sheet Title FIRE ALARM SYSTEM INFORMATION Prepared By Nicet Review E. Hamerski E. Hamerski 118193 FIR2021-0139 Expires 12/1/21 Sheet Number FA0.00 I RECEIVED Dec 08 2021 CITY OF EDMONDS © 2021, WASHINGTON ALARM DEVELOPMENT SERVICES DEPARTMENT EXISTING ONE WAY PRIVATE RADIO IN ACCORDANCE WITH NFPA72 (2016/2019ed) 26.6.3.3.2, TO REMAIN. MONITORED BY NW ALARM MONITORING, 800-487-0118. FIRE ALARM WIRE LEGEND WIRE LEGEND CIRCUIT TYPE WINDY CITY GENESIS SOUTHWIRE WEST PENN A 4 COND. 16AWG FIRE RATED CABLE RED SBUS CIRCUIT (FAA) 76138 4512 G50370 60164B D 1 PAIR 16AWG FIRE RATED CABLE RED SLC/DATA ISO CIRCUIT 7613 4511 G50032 60991 B H 1 PAIR 16AWG FIRE RATED CABLE RED W/ GREEN STRIPE MAGNETIC DOOR HOLD CIRCUIT 7613 4511 G50032 60991 B P 1 PAIR 16AWG FIRE RATED CABLE RED W/ CYAN STRIPE GENERIC AUX POWER CIRCUIT 7613 4511 G50032 60991 B Sx 1 PAIR 14AWG FIRE RATED CABLE WHITE ALL STROBE CIRCUITS 7613 4511 G50032 60991 B Vx 1 PAIR 14AWG SHIELDED FIRE RATED CABLE RED ALL SPEAKER (AUDIO) CIRCUITS 7679 4608 G60025 60992B Z 1 PAIR 16AWG FIRE RATED CABLE RED CONVENTIONAL IDC CIRCUIT 7679 4608 G60025 60992B NOTES 1 "e" IN FRONT OF LETTER SIGNIFIES CIRCUIT CABLE EXISTING, TO REMAIN AND MAY DIFFER FROM SPECIFIED CALLOUT. 2 = HASH MARK QUANTITY SIGNIFIES QUANTITY OF DESCRIBED WIRE 3 ALL WIRE PERMITTED, FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR LISTED IN THIS SUBMITTAL. 4 WIRE MANUFACTURER IS FOR REFERENCE ONLY. ENSURE PROPER CROSS REFERENCE WHEN USING DIFFERENT MANUFACTURER. 5 BY DEFAULT-WASHINGTON ALARM SPECIFIES FPLP WIRING. ELECTRICAL CONTRACTOR SHALL ENSURE CABLE TYPE CONSISTENT WITH NEC REQUIREMENTS. 6 STRIPING -WHEN APPLICABLE -IS NOT REQUIRED AND IS RECOMMENDED FOR EASE OF CIRCUIT IDENTIFICATION. ALL CIRCUITRY SHALL BE UNIQUELY AND LOGICALLY LABELED. 7 ALL FIRE ALARM WIRING TYPES SHALL MAINTAIN SEPARATION FROM EACH OTHER, AND FROM AC CIRCUITRY. FIRE ALARM SYMBOL LIST CITY SYMBOL DESCRIPTION MANUFACTURER MODEL BACKBOX MOUNTING HEIGHT NOTE 1 FACP FIRE ALARM SILENT KNIGHT 6820EVS PROVIDED BY 72" A.F.F. CONTROL PANEL SILENT KNIGHT TO TOP 2 VPSx 0 FIRE ALARM SILENT KNIGHT EVS50W PROVIDED BY ADJ. TO AMPLIFIER SILENT KNIGHT FACP 3 BPSx 0 BOOSTER POWER SILENT KNIGHT PS10 / PS6 PROVIDED BY FIELD DETERMINE SUPPLY SILENT KNIGHT 1 LOC 0 LOCAL OPERATOR CONSULE/ANN SILENT KNIGHT EVSLOC PROVIDED BY SILENT KNIGHT 60" A.F.F. TO TOP 1 DOC DOCUMENT ENCLOSURE SPACE AGE SS000625 SELF CONTAINED ADJ. TO FACP 1 FCC FIRE ALARM COMMUNICATOR EXISTING AES (BY GUARDIAN) TO REMAIN AS REQ 0 FTC FIRE ALARM TERM CABINET SPACE AGE SS000635 SELF CONTAINED FIELD DETERMINE OR EQUAL 52 O P PHOTOELECTRIC SMOKE DETECTOR SILENT KNIGHT PHOTOW EXISTING CONDITIONS TO REMAIN 1 O MULTI CRITERIA SMOKE DETECTOR SILENT KNIGHT PTIRW EXISTING CONDITIONS TO REMAIN Mc 10 O F FIXED TEMPERATURE HEAT DETECTOR SILENT KNIGHT HEATW EXISTING CONDITIONS TO REMAIN 25 F ❑ FIRE ALARM MANUAL PULL SILENT KNIGHT PULLSA SBIO BY HONEYWELL EXISTING 1 NOTIFICATION SPEAKER/STROBE SYSTEM SENSOR SPCWL SBBSPWL BY SYSTEM SENSOR 84" A.F.F. TO CENTER 1 WEATHERPROOF NOTIFICATION SYSTEM SENSOR SPSRK PROVIDED BY 84" A.F.F. SPEAKER/STROBE SYSTEM SENSOR TO CENTER 83 E4 WALL MOUNT NOTIFICATION SYSTEM SENSOR SPCWL SBBSPWL BY SYSTEM SENSOR CEILING SPEAKER ONLY 2 EmCEILING MOUNT NOTIFICATION SYSTEM SENSOR SPCWL SBBSPCWL BY CEILING SPEAKER ONLY SYSTEM SENSOR 11 Elm CEILING MOUNT NOTIFICATION SYSTEM SENSOR SPCRK PROVIDED BY CEILING SPEAKER ONLY SYSTEM SENSOR 3 NORIFICATION OBE SYSTEM SENSOR P2WL EXISTING CONDITIONS TO REMAIN WEATHERPROOF 1 NOTIFICATION SYSTEM SENSOR P2RK EXISTING CONDITIONS TO REMAIN HORN/STROBE 24 NOTIFICATION STROBE ONLY SYSTEM SENSOR SWL 4S DEEP W/1 G RING 84" A.F.F. TO CENTER 1 ADDRESSABLE SINGLE CONTROL MODULE SILENT KNIGHT CONTROL 4S DEEP FIELD DETERMINE 2 AIM ADDRESSABLE SINGLE INPUT MODULE SILENT KNIGHT MINIMON 4S DEEP FIELD DETERMINE INSIDE BPS1 , BPS2 1 HT HIGH SENSOR MP WINLAND TA2 FIELD DETERMINE J ❑ PERTINENT JUNCTION BOX LOCATE AS REQUIRED -- NOT ALL J—BOXES APPEAR ON PLANS END OF LINE RESISTOR WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT #15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN Sheet Title FIRE ALARM SYSTEM INFORMATION Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1/21 FA0.02 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 00 2021, WASHINGTON ALARM FIRE ALARM VOLTAGE DROP CALCULATIONS n C r z Om z m O cn Z n Z T m'" D m m N 70 to D C Z mm p T 0 c z _ cn O n O rn O D 0 C z Un F"w In n 0 rp) O D 0 C z cn O O rp) O 0) D 0 C z = 0) O O rp) O O D 0 C z cn Ln O rp) O O D 0 C z U) Ln n O n O v D O c z cn 7o N F" O n O n O D O c z � cn z N w Ln n O rn O D 0 c z � Ln z N oo In n O rn O v D n m 0 C z cn Ln O rp) O D n m 0 C z cn w O n O rp) O 0) D n m 0 C z Ln 0)N O n O @) O F" D n m 0 C z cn In n O O F" D () m 0 C z Ln Ln n O O U.) D M z G) O c z cn z N Ln n O n O Ln D M z Gl O c z cn 7o N in O n O rn O oo D M z C) O c z --1 to z N � 14 n O rn C) Ili D D O C Z _ Ln In O r N D � m O N D � m O -0 m D m N @) O 0') -0 m D m @) LA) ~ ^iOy N O O D - M NN -I m G) " O m m z O O C 0 C F rD z Q' Tn F, C)m Dr) , SC 0.1 FACP G BOILER GYM/BLDG G STROBES 4.7k 450 14 2.823 0 4 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 0.279 2.541 0.709 19.69 SC 0.2 FACP G BOILER GYM/BLDG G STROBES 4.7k 450 14 2.823 0 1 0 0 0 0 0 0 0 2 0 0 0 4 0 0 0 1 0 0 0 0 8 0.818 2.541 2.078 18.32 SC 0.3 FACP G BOILER NOT USED 4.7k 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 0.4 FACP G BOILER NOT USED 4.7k 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 0.5 FACP G BOILER NOT USED 4.7k 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 0.6 FACP G BOILER FACP HIGH TEMP 4.7k 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 1.1 BPS1 G BOILER BLDG A STROBES 5.1k 275 14 2.823 0 4 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 0.764 1.553 1.186 19.21 SC 1.2 BPS1 G BOILER BLDG B STROBES 5.1k 350 14 2.823 0 4 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 0.764 1.976 1.510 18.89 SC 1.3 BPS1 G BOILER BLDG C BPS3 ACT 5.1k 500 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.823 0.000 20.40 SC 1.4 BPS1 G BOILER BLDG D STROBES 5.1K 400 14 2.823 0 4 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 0.764 2.258 1.725 18.67 SC 1.5 BPS1 G BOILER BLDG E STROBES 5.1k 275 14 2.823 0 5 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 0.807 1.553 1.253 19.15 SC 1.6 BPS1 G BOILER BLDG F STROBES 5.1k 400 14 2.823 0 8 0 0 0 0 2 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0.862 2.258 1.947 18.45 SC 2.1 BPS2 G BOILER EXTSTROBES 5.1k 450 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 6 0.942 2.541 2.393 18.01 SC 2.2 BPS2 G BOILER EXTSTROBES 5.1k 450 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 4 0.628 2.541 1.596 18.80 SC 2.3 BPS2 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 2.4 BPS2 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 2.5 BPS2 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 2.6 BPS2 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 3.1 BPS3 C MECH BLDG C STROBES 5.1k 150 14 2.823 0 2 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 5 0.539 0.847 0.456 19.94 SC 3.2 BPS3 C MECH BLDG C STROBES 5.1k 150 14 2.823 0 2 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 5 0.539 0.847 0.456 19.94 SC 3.3 BPS3 C MECH NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 3.4 BPS3 C MECH PORTABLES 5.1k 350 14 2.823 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 4 0.628 1.976 1.241 19.16 SC 3.5 BPS3 C MECH NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 SC 3.6 BPS3 C MECH NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 VC 1.1 VPS1 G BOILER BLDG A SPEAKERS 47K 550 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 0 0 12 0.192 3.105 0.596 19.80 VC 1.2 VPS1 G BOILER BLDG B SPEAKERS 47K 600 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 0 0 12 0.192 3.388 0.650 19.75 VC 1.3 VPS1 G BOILER BLDG C SPEAKERS 47K 650 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 0 0 12 0.192 3.670 0.705 19.70 VC 1.4 VPS1 G BOILER BLDG D SPEAKERS 47K 600 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 0 0 12 0.192 3.388 0.650 19.75 VC 1.5 VPS1 G BOILER BLDG E SPEAKERS 47K 550 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 0 0 0 12 0.192 3.105 0.596 19.80 VC 1.6 VPS1 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 VC 1.7 VPS1 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 VC 1.8 VPS1 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 VC 2.1 VPS2 G BOILER BLDG F SPEAKERS 47K 700 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17 0 0 0 17 0.272 3.952 1.075 19.33 VC 2.2 VPS2 G BOILER BLDG G SPEAKERS 47K 350 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 10 6 0 0 16 0.352 1.976 0.696 19.70 VC 2.3 VPS2 G BOILER EXTERIOR CANOPIES 47K 700 14 2.823 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 9 0 0 11 0.32 3.952 1.265 19.14 VC 2.4 VPS2 G BOILER NOT USED N/A 0 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.000 0.000 20.40 FIRE ALARM SECONDARY POWER SUPPLY CALCULATIONS X X X SECONDARY POWER SUPPLY CALCULATI❑N X X X JOB NAME: W❑❑DWAY ELEMENTARY SCHOOL PANED VBS1=V❑ICE SYSTEM BOOSTER 1 L❑CATI❑N: BLDG G B❑ILER DATE PERFORMED: 2021-06-07 QTY. DEVICE INFO QUICENT(A) ALARM(A) ------------------------------------------------------------------- 1 EVAC: EVS50W (25V) 0.0850 0.5250 1 EVAC: EVSCE4 0.0200 0.0180 1 LOAD: 15 WATTS 0.0000 0.6750 ------------------------------------------------------------------- T❑TALS = 0.1050 1.2180 X X X SECONDARY POWER SUPPLY CALCULATI❑N X X X JOB NAME: W❑❑DWAY ELEMENTARY SCHOOL PANED VBS2=V❑ICE SYSTEM BOOSTER 1 L❑CATI❑N: BLDG G B❑ILER DATE PERFORMED: 2021-06-07 QTY. DEVICE INFO QUICENT(A) ALARM(A) ------------------------------------------------------------------- 1 EVAC: EVS50W (25V) 0.0850 0.5250 0 EVAC: EVSCE4 0.0200 0.0000 1 LOAD: 15 WATTS 0.0000 0.5850 ------------------------------------------------------------------- T❑TALS = 0.1050 1.1100 FIRE ALARM SECONDARY POWER SUPPLY CALCULATIONS SECONDARY POWER SUPPLY CALCULATI❑N )K )K )K 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E JOB NAME: W❑❑DWAY ELEMENTARY SCHOOL PANED FACP=FIRE ALARM CONTROL PANEL L❑CATI❑N: BLDG G B❑ILER DATE PERFORMED: 2021-06-07 QTY. DEVICE INF❑ QUICENT(A) ALARM( A) 1 FACP: - ------------------------- 6820EVS 0, 1900 0, 2500 1 SBUS: 586OR 0, 0200 0, 0250 1 SBUS: EVSL❑C 0, 1000 0, 1000 2 SBUS: EVS50W 0, 0200 0, 0200 1 SBUS: EVSVCM 0, 0700 0, 0700 52 SMK: PH❑T❑W 0, 0104 0, 0104 1 SMK: PT I RW 0, 0003 0, 0003 6 HEAT: HEATW 0, 0020 0, 0020 25 PULL: PAD 10OPSSA 0, 0094 0, 0094 2 MOD: MINIM❑N 0, 0008 0, 0008 1 MOD: CONTROL 0, 0004 0, 0004 1 NAC: SC 1 0, 0000 0, 2790 1 NAC: SC2 0, 0000 0, 8180 1 NAC: SC3 0, 0000 0, 0000 1 NAC: SC4 0, 0000 0, 0000 1 NAC: SC5 0, 0000 0, 0000 1 NAC: SC6 0, 0000 0, 0000 ------------------------------------------------------------------- T❑TALS = 0, 4233 1, 5849 QUICENT LOAD = 0,424 AMPS ALARM LOAD = 1,585 AMPS QUICENT TIME = 24 HRS. ALARM TIME = 0,25 HRS. ------------------------------- QUICENT = 10,176 AMP)KHRS ----------------------------- ALARM = 0,397 AMP)KHRS TOTAL = QUICENT + ALARM = 10, 176 + 0, 397 = 10,573 AMP)KHRS DE -RATING FACTOR OF 257 ---> 10, 573 )K 1, 25 = 13, 217 MINIMUM BATTERY SIZE = 13,22 AMPERE)KH❑URS )K INSTALL 2 12V 18AH BATTERIES (PART NUMBER: SLA1117) SECONDARY POWER SUPPLY CALCULATI❑N )K )K )K 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E 31E JOB NAME: W❑❑DWAY ELEMENTARY SCHOOL PANED BPS1=B❑❑STER POWER SUPPLY 1 L❑CATI❑N: BLDG G B❑ILER DATE PERFORMED: 2021-06-07 QTY. DEVICE INF❑ QUICENT(A) ALARM(A) 1 BPS1: - ------------------------- PS 10 0.1560 0.1850 1 NAC: SIC 1. 1 0, 0000 0, 7640 1 NAC: SIC 1. 2 0, 0000 0, 7640 1 NAC: SIC 1. 3 0, 0000 0, 0000 1 NAC: SIC 1. 4 0, 0000 0, 7640 1 NAC: SIC 1. 5 0, 0000 0, 8070 1 NAC: SIC 1. 6 0, 0000 0, 8620 1 NAC: SIC 1. 7 0, 0000 0, 0000 ------------------------------------------------------------------- T❑TALS = 0.0600 2.9670 QUICENT LOAD = 0,060 AMPS ALARM LOAD = 2,967 AMPS QUICENT TIME = 24 HRS. ALARM TIME = 0,25 HRS, ------------------------------- QUICENT = 1,440 AMP)KHRS ----------------------------- ALARM = 0,742 AMP)KHRS TOTAL = QUICENT + ALARM = 1.440 + 0.742 = 2,182 AMP)KHRS DE -RATING FACTOR OF 257 ---> 2, 182 X 1, 25 = 2, 728 MINIMUM BATTERY SIZE = 2,73 AMPERE)KH❑URS )K X SECONDARY POWER SUPPLY CALCULATI❑N X X JOB NAME: W❑❑DWAY ELEMENTARY SCHOOL PANED BPS2=B❑❑STER POWER SUPPLY 2 L❑CATI❑N: BLDG G B❑ILER DATE PERFORMED: 2021-06-07 QTY. DEVICE INFO QUICENT(A) ALARM(A) ------------------------------------------------------------------- 1 BPS2: PS 10 0, 1560 0, 1850 1 NAC: SC2. 1 0, 0000 0, 9420 1 NAC: SC2. 2 0, 0000 0, 6280 1 NAC: SC2. 3 0, 0000 0, 0000 1 NAC: SC2. 4 0, 0000 0, 0000 1 NAC: SC2. 5 0, 0000 0, 0000 1 NAC: SC2. 6 0, 0000 0, 0000 1 NAC; SC2. 7 0, 0000 0, 0000 ------------------------------------------------------------------- T❑TALS = 0.0600 2.9710 QUICENT LOAD = 0,060 AMPS ALARM LOAD = 3,759 AMPS QUICENT TIME = 24 HRS. ALARM TIME = 0,25 HRS. QUICENT = 1,440 AMP)KHRS ALARM = 0,743 AMP)KHRS TOTAL = QUICENT + ALARM 1.440 + 0.743 = 2.183 AMP)KHRS DE -RATING FACTOR OF 25% ---> 2, 183 )K 1, 25 = 2, 728 MINIMUM BATTERY SIZE = 2,73 AMPERE)KH❑URS )K INSTALL 2 12V 7AH BATTERIES SECONDARY POWER SUPPLY CALCULATI❑N )K WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT #15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN QUICENT LOAD = 0,105 AMPS ALARM LOAD = 1,218 AMPS QUICENT LOAD = 0,105 AMPS ALARM LOAD = 1,110 AMPS JOB NAME: W❑❑DWAY ELEMENTARY SCHOOL QUICENT TIME = 24 HRS. ALARM TIME = 0, 25 HRS. QUICENT TIME = 24 HRS. ALARM TIME = 0, 25 HRS. PANED BPS3=B❑❑STER POWER SUPPLY 3 Sheet Title ---------------------------------------------------------------------------------- ------------------------ --------- _ _ _ _ ----- � FIRE ALARM QUICENT 2,520 AMP)KHRS ALARM 0,305 AMP)KHRS QUICENT 2,520 AMP)KHRS ALARM 0,278 AMP)KHRS DATE PERFORMED: 2021-06-07 TOTAL = QUICENT + ALARM 2.520 + 0.305 2,825 AMP)KHRS DE -RATING FACTOR ❑F 257 ---> 2.825 X 1.25 = 3.532 X X X MINIMUM BATTERY SIZE = 3,54 AMPERE)KH❑URS X X X INSTALL 2 12V 7AH BATTERIES TOTAL = QUICENT + ALARM 2.520 + 0.278 2,798 AMP)KHRS DE -RATING FACTOR ❑F 257 ---> 2.798 X 1.25 = 3.498 X X X MINIMUM BATTERY SIZE = 3,50 AMPERE)KH❑URS X X X INSTALL 2 12V 7AH BATTERIES QTY. DEVICE INFO -------------------- 1 BPS2: ------------------QUICENT(A)--------ALARM(A) PS6 0, 1560 0, --- 1850 1 NAC: SC3. 1 0, 0000 0, 5390 1 NAC: SC3. 2 0, 0000 0, 5390 1 NAC: SC3. 3 0, 0000 0, 0000 1 NAC: SC3. 4 0, 0000 0, 6280 1 NAC: SC3. 5 0, 0000 0, 0000 ------------------------------------------------------------------- T❑TALS = 0.0600 2.9710 QUICENT LOAD = 0,060 AMPS ALARM LOAD = 3,759 AMPS QUICENT TIME = 24 HRS. ALARM TIME = 0,25 HRS. ------------------------------- QUICENT = 1,440 AMP)KHRS ----------------------------- ALARM = 0,743 AMP)KHRS TOTAL = QUICENT + ALARM = 1.440 + 0.743 = 2,183 AMP)KHRS DE -RATING FACTOR OF 257 ---> 2, 183 )K 1, 25 = 2, 728 MINIMUM BATTERY SIZE = 2,73 AMPERE)KH❑URS )K INSTALL 2 12V 7AH BATTERIES SYSTEM INFORMATION Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1/21 Sheet Number FA0e03 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 00 2021, WASHINGTON ALARM LOCATE SILENT KNIGHT 5820XL BOARD HERE, SEE DETAIL 2 THIS PAGE LOCATE SILENT KNIGHT EVS-VCM BOARD HERE, SEE DETAIL 3 THIS PAGE REMOTE MICROPHONE, AS PART OF DOOR ASSEMBLY NO WIRES INTO BOTTOM OF ENCLOSURE 20.25" SILENT KNIGHT 6820XLEVS ENCLOSURE DETAIL SCALE: NONE 26.75" pcW R O .e m SUdRERV�SQRY O O 4ROUBM sib NOIE® O O O 0 0 CD CD O 0 O CD CD =O© 000 o ��lul coo off® 000 o 000 40 Y.YLR ®O cowvna� O oO O o0 O o0 O oO O o0 O o0 O oO O oO O oO O oO O oO O oO O oO O o0 O o0 O oO O o0 O o0 O oO O oO O oO SILENT KNIGHT 6820 FRONT SCALE: NONE manapnHo PA�®O 68220EYS FOREIURMCEbIC#ROCERICV LLL 60G�R9MPdOC�Q400P7 bS7R4CBA SBUS ADDRESS DIPSWIT SET TC NOTE: THE SILENT KNIGHT EVS-RCM (SBUS03) IS CONFIGURED EQUALLY TO THE EVS-VCM SEE ALSO SILENT KNIGHT EVS-VCM (SBUS01) DETAIL SCALE: NONE S LOOP S LOOP S LOOP S LOOP S LOOP TO 1, SEE ALSO FA0.09 WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT #15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN Sheet Title Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1/21 Sheet Number FA0004 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT © 2021, WASHINGTON ALARM r101A7■lA\rn". .IIall WIFNW SAT&1ONIONIOff" 0FA12% OWN .XNANOWATAM0rNO110115" WWII F1 AES COMMUNICATOR INSTALLATION NOTES aO. CO M M U NICATIO N METHOD AND EQUIPMENT SUBJECT TO SEPARATE DEFERRED CONTRACT WITH END OWNER. OWNER MAY BE CONTRACT MONITORING VIA A THIRD PARTY MONITORING COMPANY, RENDERING EQUIPMENT SHOWN AS PROVIDED BY OTHERS. FIELD VERIFY/AS BUILT CONDITIONS. al. WIRING BETWEEN FCC AND TRANSFORMER (IF APPLICABLE) SHALL BE SIZED PER MANUFACTURER RECOMMENDATION, AND INSTALLED IN RACEWAY. TRANSFORMER ENCLOSURE SHALL BE INSTALLED. _1 \A/TMTA I/ MrT\A/rrA1 1-A/M AA1111- `/ (I I A I I MI- 11/" A AATAITAAI IAA TA I!" A111-1 TA1 A!"/'l'1 M1 AAI! I-IA/TTII A A A A I IJFACTU RER MUST BE SILENT KNIGHT 6820 DETAIL ( 2 EXISTING AES DETAIL E,Yy_14=01lei ►12 [•Yy_1I=61lei ►1: A QUIRE AND WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN Sheet Title FIRE ALARM SYSTEM INFORMATION Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1/24 Sheet Number FAO,005 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT © 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE FROM AS BUILT CONDITIONS. 1 Gc DEMO EXISTING HC LOOP INTEGRIT` Gd Ge Gf Gg SEE FA4.08, DETAIL 1 G1 G2 G3 G4 G5 G6 Nn 9 G7 15'-0' 15'-0' 15'-0' 15'-0' 15'-0' 10'-0' 5'-0' Boiler Kitchen Stor. Restroom G306 G305 G304 G303 7:s016 FEX 97:s020 (IffX EX _ SC01-e Qs RE QsPREX Os REX 110 D 97:s016P 97:s017 97:s018P ❑ Restroom G302 SC0.1-e SC0.1- 15CD 15CD 97:m015 F R EX H REX Qs PREX J 97:s0 9 97:s014 SC0.1-e 75CD Foyer 7:m011 r'_'FAC G301 P LJYl SIFC0.1-e REX !1r= RMCCORDANCE EMO EXISTING SMOKE DETEC1 OR, IN 110CD WITH NFPA72 (2)16ed) aintl0ffice DEMO EXISTIN HORN/STROBE, MAINTAIN 17.7.3.2.4.2 (5). MAINTAIN CIR UIT J LOOP INTEGRIT , AND PROVIDE COVER INTEGRITY, AND PROVIDE COVER PLATING G307 PLATING AS REQUIRED. AS REQUIRE QHPREX O 97:s011 Stor. G308 RN/STROBE, , AND PROV J PLATING AS EQUIRED. Gym 9300 Qs REX 97:s012P Stage/Class G309 QH REX O 97:s013F DEMO EXISTING HORN/STROBE, MAINTAIN LOOP INTEGRITY, AND PROVIDE COVER Stor. PLATIN G AS REQUIRED. G310 REX J 97 013 F X F 97:m014 J DEMO EXISTING HORN/STROBE, MAINTAIN LOOP INTEGRITY, AND PROVIDE COVER G1 G2 83 FLAI11NCi A5 KLQUIKLU. G5 G6 G7 PROJECT NORTH FIRE ALARM: BUILDING G, EXISTING SYSTEMS SCALE: 1/8" = 1' Ga Gb Gc Gd Ge Gf Gg CCC rA A n0 fICTATI 'I Keybox FIRE ALARM: BUILDING G, NEW CIRCUITS SCALE: 1/8" = 1' PROJECT NORTH WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN n HE u D C E F B A Area of view Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,001 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT © 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE FROM AS BUILT CONDITIONS. (Al) A2 C C R C R C HV SI, 6 EXISTING WIRI SLAB, THROUC J BOX C A3 A4 �._0. 17._0' IT-O. a REX wP SC2.1-e 75CD b Classroom 97: 022 REX SC1.1-e A103 c J F SC X 15 . -e D an/Stor REX sP97:s027 REX Al anlStor s�P97:s R X Al 97:s02 d CD REX SC1.1-e Classroom 'stroom F X 110CD A102 Al e SC1.1-e X 110CD .stroom 11RLsc.1-e A106 REX f 97:s02 ACIMech REX QH F97:s 25 EX 97:m021 Classroom A101 Al =X DATA, ;NAL TOS REMAIN E SC.1e J FEX 15 9 VG UNDER H CMU TO -60" A.F.F. E SC1.1-e 110CD REPLACE EXISTING HORN/STROBE WITH STROBE ONLY, TYPICAL h Classroom SC2.1-e A100 75CD wPRE �i Al A2 A3 A4 Aa C Ab Ac C J ( J Ad R Ae C R Af C HV ( Ag A C Ai C PROJECT NORTH FIRE ALARM: BUILDING A, EXISTING SYSTEMS SCALE: 1/8" = 1' Al A2 A3 A4 9._6. 17'_0• 17,_0. EC1.1 H MERUN TO FACP AREA, SEE FA4.xx a V1 1 C1.1-1 s /4W b V1.1 LEC1.1 Classroom A103 c -V1.1 an/Stor C1.1-3 /4W 1 A109 V1 an/Stor C1.2-4 1/4 s J A108 d V1.1 )stroom 1.2- ]�Eci. 1-5 1MW V1.1 Classroom A102 A107 s e S 1.2-6 J V1.1 V1.1 4W EC1.1-8 s 1/4W )stroom V.1 Al ,f 711.2-94 s J ACIMech V1 1 C1.1-10 /4W Classroom A101 A105 V1 1 g s EC1.1-11 1 /4W C. V.1 C. h s C1.1-12 MW Classroom A100 V w �i WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Aa Ab Ac Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 9521 240TH ST SW Ad EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN Ae Af Ag Ah PROJECT NORTH FIRE ALARM: BUILDING A, NEW CIRCUITS SCALE: 1/8" = 1' n P3 P2 Pl D C E F B G Area of view Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,002 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE E2 FROM AS BUILT CONDITIONS. L0 R C R C HV ( Si E EXISTING WI SLAB, THROU( JBOk 11 E3 E4 -6• 17'-0' 17•-0. a E Isolatic REx SC2.1-e SC1.5-e X 15CD E103 75CD b E Classroom 97: 035 REX SC1.5-e E103 c J F SC X 15 . -e D E an/Stor REX Os P97:s036 REX E109 anlStor QS P97:s 35 R X E108 97:s03 d I CD SC1.5-e Classroom 'str00m X 110CD E102 E107 e E C 1.5-e X is10CD )stroom RE SC1.5-e E106 REX f 97:s03 I ACIMech REX OH F97:s 34 97:m034 L4E Classroom E101 E105 =X DATA, INAL TO REMAIN SC 15 .5 e gG f UNDER j H CMU TO -60" A.F.F. REX SC1.5-e 110CD REPLACE EXISTING HORN/STROBE WITH STROBE ONLY, TYPICAL h I Classroom SC2.1-e E100 75CD RE :i E1 E2 E3 E4 � C n D C C J ( J ( D C R C R _: C HV ( C �h C =D C PROJECT NORTH FIRE ALARM: BUILDING E, EXISTING SYSTEMS SCALE: 1/8" = 1' E1 E2 E3 E4 9'-6• 17'-0• 17'-0• a f Isolatic W E103 C1.5-12 s MW b f V1.5 EC1.5-11 s 1/4w Classroom E103 c f V1 5 an/Stor C1.5-10 MW E109 V1 5 13 an/Stor EC ille .5-9 s J W 13 E108 d f V1.5 Classroom EC1.5-8 ,,stroom 1.5- s 1/4W TV)15 E102 13 E107 s e f S J V1.5 V1. 1.5-6 4W EC1.5-5 13 s 1/4W ;stroom V .5 13 E106 f UdI C .5-4 / s W J 13 ACIMech V1 5 Classroom E105 C1.5-3 /4W 101 E 2 5 g f EC1.5-2 s 1 /4W V.5 h I Classroom C1.5-1 s MW E100 V1 5 :i EC1.5 HOMERUN TO FF�CP AREA, SEJE FA4.08 E1 E2 E3 E4 WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 :D n :. Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 d 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN :_ PROJECT NORTH FIRE ALARM: BUILDING E, NEW CIRCUITS SCALE: 1/8" = 1' n P3 P2 Pl D C Area of view F B A G Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4.03 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE FROM AS BUILT CONDITIONS. 1 aq EXISTINC P C F3 F4 17'-0' 17'-0" 9'-6' a E. F SC2.2- 75CD REX Library 97:ssl29 F210 s REXP b FI 9 :s128 R S XP 97:m 9 7 �M REX SC1.6-e V c F 97:s127 (4 SC1.6-e F 97:m104 110CD R Office 7:s125 Office REXP F208 97:s123 REX P F211 REX s d 97:s109 (4 REX 97:s126 7:s124 REP F209 F 97:00 s REX SC1.6-e IF X 15CD Work F EX 97:s116 s SC1.6 e REXP 15CD- 5CD REX Stor F206 97:s122 s REXO` F212 97:m10 F e Stor Work 97:00 s REX 97: s 120 REQ SC1.6-e F205 e 15CD F213 15CD REX UNDERGROU STUB UPS/JB SC1.6-e 15CDAr 97:sl 19 �S REX' 97:s114 F F214 QF REX i SC1.6-e 00 Break F204 E SIGNALTOL REMADIF216 rincipal SC 1.6-e 97:s10 s RE REX 97:s118(4 Restroorr F 7 15CD R F218 15CD REX 9 97:m101 F REX F SC 1.6-e 185CD REX REX :s 05®P 97:s1044 Office F203 h -e 5CD REX F 9 :s 01�4 SC2.2- REX 75CD Office REX F200 S 1 .6-e Book Rm D RE F201 ok R ni F202 i F Restroom F201A F2 F3 F4 J J J I P REPLACE EXIST NEW LOCATIC l H� FAC P, PROJECT NORTH FIRE ALARM: BUILDING F, EXISTING CIRCUITS SCALE: 1/8" = 1' C F1 F2 F3 F4 17'-0" 17'-0* 9'-6- a F EC2.1-15 1/4W s CM EC2.1-17 Library 1/4W F210 EC2.1 s M b V2.1 FI F c Office EC2.1-16 cm 1/4W V2.1 Office F208 V2.1 F211 d Work EC2.1-14 1/4W s V2.1 EC2. 1/4W s V2.1 -11 s C2.1-12 V2.1 F209 F Stor F206 F212 F Stor e Work EC2.1-9 1/4W J s EC2.1-10 1/4W s V2.1 EC2. -8 s 1/4 F205 F213 2,1 tF214 estroo F216 V2.1 .1-6 s V2.1 EC2.1-7 s 1/2W Break F204 F rincipal N WITH EXISTI CONDITIO VB G S. EC2.1-5 1/4W s � estroo H 4 V2.1 RUN TO SEE FA4.08 LOC V .1 EC2.1-4 1/2W s Office F203 F h Office EC2.1-3 1/4W s V2. EC2.1-2 1/4W Book Rm F201 s 1-1 1 4 B4 ok Rni F202 F V2. F200 i Restroom F201A EC2.1 TO F OMERUN P AREA, F F2 '¢��, UQ F4 7 J 7 7 PROJECT NORTH FIRE ALARM: BUILDING F, NEW CIRCUITS SCALE: 1/8" = 1' WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 9521 240TH ST SW EDMONDSI WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN n P3 P2 Pl D C Area of view E B A G Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,004 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOAC� FROM AS BUILT CONDITIONS. EXISTING WI SLAB, THROI JBC PROJECT NORTH FIRE ALARM: BUILDING B, EXISTING SYSTEMS SCALE: 1/8" = 1' a� L J ( R i LE HV ( LE 11 B1 B2 NO 9'-6' 17'-0' 17'-0" 4 N LU W C1.2-12 MW S b V1.2 LEC1.2-11 Classroom B103 C V1 2 an/Stor C1.2-10 1MW B109 V1 2 an/Stor 1 1/ .2 9 s J W B108 d V1.2 astroom 1.2- S 1 4W EC1.2-8 S 1/4W V1.2 Classroom B102 B107 e S 1.2-6 J V1. V1.2 4W EC1.2-5 S 1/4W )stroom IV .2 B106 f C .2-4 AC/Mech V1 2 B105 C1.2-3 MW Classroom B101 V1 2 9 EC1.2-2 S 1/4W V .2 h C1.2-1 S MW Classroom B100 V1 2 MERUN TO 3i EC1.2 H FACP AREA, SEE FA4.08 B1 B2 u FIRE ALARM: BUILDING B, NEW CIRCUITS SCALE: 1/8" = 1' u WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 01 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 Bd 9521 240TH ST SW D EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN n HE Pl DBf Area of view D C E F B9 A G Sheet Title FIRE ALARM Bh SYSTEM PROJECT NORTH DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,005 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE D2 FROM AS BUILT CONDITIONS. 1 C J ( R C II N HV ( Si EXISTING WIRI SLAB, THROUC J BOX I I 11N D4 -6• 17'-0' IT-O. a REX SC2.1-e 75CD IT Classroom 97: 059 REX SC1.4-e 110CD D103 C J F X 15.D-e an/Stor REX SOP 97:s060 REX D 109 anlStor QS P97:s REX D108 �.,�97:sO6kt dREY CD SC1.4-e Classroom .stroom F X 110CD D102 D107 e .4-e T10X1 CD )stroom . LSCI& -e D106 fREX REX 97:s06 ACIMech D105 =X DATA, INAL TO REMAIN REX (1F97:s 158 58 LZ4EX Classroom D101 SC 15 Ae iu-N D E R H CMU TO -60" A.F.F. NE SC1A-e JkX 110CD REPLACE EXISTING HORN/STROBE WITH STROBE ONLY, TYPICAL h Classroom SC2.1-e D100 75CD RE )i D1 D2 IN D4 Da C DD C Dc C J ( R De C R Df C[ HV ( Dg C Dh C PROJECT NORTH FIRE ALARM: BUILDING D, EXISTING CIRCUITS SCALE: 1/8" = 1' D1 D2 11N D4 9'-6• 17'-0• 17'-0• a v LU u, C1.4-12 MW S D V1.4 ECI A-11 S 1/4W Classroom La D103 c V1 4 an/Stor C1.4-10 /4W D109 4 V1 an/Stor EC 1, .4-9 s W J D108 d V1.4 astroom 'J IJ 1.4- S 1 14W EC1.4-8 S 1/4W V1.4 Classroom D102 D107 e .4-6 1S J V1. V1.4 4W EC1.4-5 S 1/4W )stroom V .4 D106 If C /w .4-4 s J ACIMech V1 4 C1.4-3 /4W Classroom D101 D105 V1 4 9 Ij s EC1.4-2 1/4W V.4 h C1.4-1 S /4W Classroom D100 V1 4 MERUN TO )i EC1.4 H FACP ARE 4, SEE FA4.08 D1 D2 IN O WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 Dd 9521 240TH ST SW D EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN De Df 01 Dh 11 PROJECT NORTH FIRE ALARM: BUILDING D, NEW CIRCUITS SCALE: 1/8" = 1' Key Tian P3 P2 Area of view P 1 C E F B A G Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,006 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE C2 FROM AS BUILT CONDITIONS. el 1 R ( C HV ( C SEE FA4.08, DETAIL 2 I 4 C4 17'-0' 16'-11 1/2' a RELOCATE EOL FOR REX SC2.2 TO LAST DEVICE SC3.2-4 (FIELD DETERMINE) 75CD C REWIRE CIRCUITS WIT IN EXISTING RACEWAY T INCORPORATE EXTERIOR STROBE AS PART OF S 3.2 Classroom C103 97: 068 REX SC3.2-3 C J F SC X 15 FREX . -2 D an/Stor 97:s069 REX C109 QS anlStor P97:s C108 REX 97:s07 dLEY Lae CD euS3.1 �euD.c EXSC3.2-5 Classroom .stroom 110CD C102 C107 e 7 c SC3.1-5 R X 110CD REPLACE EXISTING 'str00m HORN/STROBE WITH RELSC.1-1 STROBE ONLY, TYPICAL C106 R I X 97:s07 :f CON I FA.4.08, D AIL 2 ACIMech Classroom C105 C101 F SC .1 EX 15 9 REX SC3.1-3 110CD REWIRE CIRCUITS WITHIN EXISTING RACEWAY TO INCORPORATE EXTERIOR STROBE AS PART OF SC3.1 h Classroom C100 SC3.1-4 75CD RE ;i C1 C2 C3 C4 Ca C CC C CC C J ( J ( Cd C R ( Ce C R Cf C( HV ( Cg C SEE FA4.08, DETAIL 2 Ch C( Ci C PROJECT NORTH FIRE ALARM: BUILDING C, EXISTING SYSTEMS SCALE: 1/8" = 1' C1 C2 C4 g'_g• 17•-0' 16'-11 1/2' - C3.4 TO PORTABLES, SEE FA4.08, DETAIL 3 a LU UTILIZE EXISTING WEATHERHEAD,� C1.3-12 TRANSITION TO AERIAL s /4W C V1.3 EC1.3-11 s 1/4W Classroom C103 c V1 3 an/Stor C1.3-10 /4W 3 C109 V1 an/Stor EC 1/ .3-9 s W J C108 � d V1.3 Classroom EC1.3-8 .stroom T1/4WC1071.3-. s 1 4W e S V1.3 ls�)� 4W .3-5 1/4W )stroom V .3 C106 C .3-4 / W s J D.cp S3.4 ACIMech cl� I V1 3 Classroom INST, C105 C1.3-3 MW C101 CONI EXTEI V1 3 BPS3 9 EC 1.3-2 S 1/4W V.3 h------- Classroom C1.3-1 s /4W C100 V1 3 :i EC1.3 1iOMERUN TO F CP AREA, SEE FA4.08 C1 C2 C3 C4 WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Ca Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 Cd 9521 240TH ST SW D EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN Ce Cf kLL WIRING IN NEW )UIT UNDER ,IOR AWNINGS Cg Ch Ci PROJECT NORTH FIRE ALARM: BUILDING C, NEW CIRCUITS SCALE: 1/8" = 1' n P3 P2 Area of view P 1 D E F B A G Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,007 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM FIRE ALARM - SYSTEM NOTES 0-NEW WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL 0 AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS. 1-GOOD FAITH EFFORT WAS PROVIDED TO DEMONSTRATE EXISTING CONDITIONS. FIELD VERIFY ALL LOCATIONS AND 1� DEVICES. A GOOD FAITH EFFORT SHALL BE UNDERTAKEN TO AS BUILT ALL EXISTING AND NEW CONDITIONS AT THE END OF INSTALLATION. 2-EXISTING SIGNAL CIRCUIT ROUTING TO REMAIN AS IS, UNLESS 2� OTHERWISE NOTED. ALL SIGNAL CIRCUIT LOADS WILL DECREASE FROM AS BUILT CONDITIONS. N FIRE ALARM: BUILDING G, BOILER RM DETAIL SCALE: 1/4" = 1' PROJECT NORTH EX DATA TO REM LABEL EXISTIN( MODIFY IN F FIRE ALARM: BUILDING C, MECH RM DETAIL SCALE: 1/4" = 1' PROJECT NORTH FIRE ALARM: NEW 2021 PORTABLES SCALE: 1/8" = 1' PROJECT NORTH WASHINGTON ALARM P: 360.733.1330 1420 King St, Ste E Bellingham, WA, 98229 www.washingtonalarm.com WA Lic: WASHIA1282C3 Project Title WOODWAY ELEMENTARY SCHOOL EDMONDS SCHOOL DISTRICT # 15 9521 240TH ST SW EDMONDS, WA, 98020 Project Numbers 21684-2 Issue & Revision Dates 07 JUN 2021 RO-INITIAL DESIGN n Area of view fC E F B Area of view A G Sheet Title FIRE ALARM SYSTEM DRAWING Prepared By Nicet Review E. Hamerski E. Hamerski 118193 Expires 12/1 /21 Sheet Number FA4,008 RECEIVED Dec 08 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q 2021, WASHINGTON ALARM