REVIEWED RESUB1 BLD2023-0794+Structural_Analysis_or_Calculations+10.25.2023_12.08.10_PM+3860679RESUB Oct 25 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2023-0794 ............................................... REVIEWED BY CITY OF EDMONDS BUILDING DEPARTMENT. Project: Janetta Lee 9309 236th St. SW Edmonds, WA 98020 REVISED - Foundation Loading Calculations and Pier Calculations Contractor: Robbins & Company 818 SW 142nd Street BURIEN, WA 98166 Calculations Prepared by: Kevin T. Moore, PE Washington License No. 54108 K t TODD b� Y'� sJF WAS o'Qcfi �� FGfSn Z;ZNALE� 2 Date: August 18, 2023 Digitally signed by Kevin Moore DIN: c=US, st=Mississippi, 1=Columbia, o=Hayman reEngineering, Inc., cn=Kevin Moore, email=kmoore@HaymanEngineering.com Date: 2023.08.18 11:22:22-05'00' Hayman Engineering, Inc Board of Engineers -Firm License (COA) 2625 1923 N. Broadway Ave. Springfield, MO 65803 (417) 831-5550 hfeorders@haymanengineering.com HE23060007 Page 1 of 8 Design Notes Owner: Janetta Lee Address: 9309 236th St. SW City, State, ZIP: Edmonds, WA 98020 PN: HE23060007 1 These calculations provided in support of a contract between the contractor and the owner. The calculations are to provide engineering design and review of the proposed scope of work provided in the terms of the contract. This design represents a proposed solution agreed upon in the contract used to address the areas of concern identified to the engineer. The owner should be alert to possible changes to the condition of the structure and continue to monitor the building's condition. 2 Hayman Engineering warrants that this design is based on sound engineering principles but makes no warranty or guarantee regarding the work performed by the Contractor. 3 This design is based on information supplied by the Contractor. Field verify that no system's placing violates the notes in this drawing set. 4 Install the system shown in accordance with the manufacturer's recommendations. 5 The building weight assumptions used to calculate pier load are estimates. 6 Drive each pier until a slight lifting of the building occurs to indicate that the structure's load has transferred from the soil to the pier. Do not lift or drive past the load transfer point as damage may occur to the foundation or to interior and exterior finishes. Page 2 of 8 Foundation Load Calculation Owner: Janetta Lee Address: 9309 236th St. SW City, State, ZIP: Edmonds, WA 98020 PN: HE23060007 Calculate linear load on foundation Condition: Endwall ❑ Half Width 6 Stories 1 ==MM- Fndn Ht 2.00 - Load, ref ASCE-7- Backfill Ht 1.50 Ce: 1 Table 7-2 Side wall Ht 9 Ct: 1 Table 7-3 Roof pitch in 12 3 I: 1 Table 1.5-1 rafter length +1 7.2 Pf = 25.0005 psf Ps = Cs x Pi Sloped Roof Snow Load, Eq 7.4-1 -7.4.2, assume 1.0 to be conservative = s ❑RUNNING TOTAL ROOF ITEM: Comp Shingle mat'I psf: 2 mat'I plf: 14.4 Deck Rafter Snow 1.88 2.6 25.001 13.5 18.7 150.0 ATTIC No steps LL Ins Sheetrock Joists mat'I psf: 10.0 3.0 2.5 1.6 mat'I plf: 30.0 9.0 7.5 4.8 1 st: 2nd: SIDEWALLS Siding None Studs Sheetrock Ins. 1 Levels of framing mat'I psf: 1.3 0.0 1.6 2.5 2.5 mat'I plf: 11.3 0.0 14.4 22.5 22.5 FLOORS Living LL Finish Finish Joists Sub 2nd flr mat'I psf: 40 1 st flr mat'I psf: 40 9 2.6 2.25 mat'I plf: 120.0 27.0 7.8 6.8 FNDN WALL Conc CMU Clay Brick Limest Footing ht width Thickness= 8 8 18 OVERBURDEN (lip in inches) Bkfill above Backfill wedge Wedge angle: Wedge wt: 200.0 0.0 0.0 0.0 150.0 Assumed footer size 5 (half the difference between ftr width and wall thickness) 1 Bkfill Ht 2: 0 ft Wedge: 68.8 0.0 0.0 (Enter 0 in 'Bkfill above" for full excavation) No 30 degrees 197 51 71 162 350 69 0.0 Ibs ❑ F Page 3 of 8 Foundation Load Calculation Owner: Janetta Lee Address: 9309 236th St. SW City, State, ZIP: Edmonds, WA 98020 PN: HE23060007 Calculate linear load on foundation Condition: Front ❑ Half Width 14 Stories 1 r n n Mow =.=7gZ, Fndn Ht 2.00 .-Load, ref ASCE-7- Backfill Ht 1.50 Ce: 1 Table 7-2 Side wall Ht 9 Ct: 1 Table 7-3 Roof pitch in 12Ll 3 I: 1 Table 1.5-1 rafter length +1.4 Pf = 25.0005 psf Ps = Cs x Pi Sloped Roof Snow Load, Eq 7.4-1 ROOF ITEM: Comp Shingle mat'I psf: 2 mat'I plf: 30.9 qn,,.M-7.4.2, assume 1.0 to be conservative RUNNING Deck Rafter Snow 1.88 2.6 25.001 29.0 40.1 350.0 TOTAL ATTIC No steps LL Ins Sheetrock Joists mat'I psf: 10.0 3.0 2.5 1.6 mat'I plf: 70.0 21.0 17.5 11.2 1 st: 2nd: SIDEWALLS Brick None Studs Sheetrock Ins. 1 Levels of framing mat'I psf: 38.0 0.0 1.6 2.5 2.5 mat'I plf: 342.0 0.0 14.4 22.5 22.5 FLOORS Living LL Finish Finish Joists Sub 2nd flr mat'I psf: 40 1 st flr mat'I psf: 40 9 2.6 2.25 mat'I plf: 280.0 63.0 18.2 15.8 FNDN WALL Conc CMU Clay Brick Limest Footing ht width Thickness= 8 8 18 OVERBURDEN (lip in inches) Bkfill above Backfill wedge Wedge angle: Wedge wt: 200.0 0.0 0.0 0.0 150.0 Assumed footer size 5 (half the difference between ftr width and wall thickness) 1 Bkfill Ht 2: 0 ft Wedge: 68.8 0.0 0.0 (Enter 0 in 'Bkfill above" for full excavation) No 30 degrees 450 120 401 377 350 69 0.0 Ibs ❑ WRRY��� Page 4 of 8 Calculate moment and shear strength in wall to get max spacing, Condition Front t r r I' o c l I t Ise here t l f 1 6 I Calculate Strength of Unreinforced Section Foundation dimensions (Note: For thickened slab, enter thickening as footer and slab as wall) T = 8 in (thickness of wall) H = 24 in (ht of wall) S = 8 in (ht of footer) B = 18 in (width of footer) D = 32 in (total ht of foundation) Centroid, c = sum (AiYi)/ sum(Ai) = d-(d^2 * t + s^2 8 (b-t))/(2 * (b * s + h * t)) = 18.86 in Moment of Inertia (1) _ I stem = parallel axis I footer = parallel axis 0 f'c = Mn= Mu= 9,216 InA4 9,028 InA4 768 InA4 12,037 InA4 31,049 In A 4 1,647 inA3 - I/c 2,500 psi — (assume 2,500 for conc) 34,303 ft I - 5 x sgrt(f'c) x S 22,297 ft lb - 0.65 x Mn Calculate Strength of Reinforced Section Note: This analysis neglects the "ears" of the footer, using wall thickness as "b" and assumes 3" clear to the steel. fy: 40,000 psi k1: 0.85 As: 0 inA2, assume none phi: 0.9 qmax = 0.371 = 0.6375*k1*(87,000/(87,000+fy) q = 0.000 = [As/b*d]*fy/f'c Mu = 0 ft lb, phi*As*fy*d(1-0.59q) Ma = 0 ft lb allowable, Mux0.65 Mx = 22,297 ft lb, Max of unreinforced and reinforced Calculate maximum span to achieve Moment strength Mx = (wl^2)/8 L allow = 10.05 ft - sgrt(8M/w) Page 5 of 8 Check shear for foundation section (assumes no shear reinforcing), Condition Front Concrete: Vc=4/3xphi x(sgrtf'c)xbxh Sect above Phi = 0.65 (sqrt f'c) = 50 (min of f'c^0.5 and 100) Footer shear strength: Hf = s-2 6 in (reduction accounts for uneven excavation) Bf = 18 in (from above) Vf = 4,680 lb Wall shear: Hw = 24 in (from above) Bw = 8 in (from above) Vw = 8,320 lb Page 6 of 8 Hayman Engineering Project: Janetta Lee Address: 9309 236th St. SW Edmonds, WA 98020 PN: HE23060007 Belowground Portion: Chimney W: 6.666667 ft Chimney D: 2 ft Wall Thickness 0.67 ft, min, assumed Chimney Area: 13.33 sf, WxD Flue Area: 3.52 sf, min, assumed Chimney Net Area: 9.82 sf, area — flue area Chimney H: 2 ft, depth below grade, assume frost depth if unknown Chimney Vol: 19.64 cf, net area x ht Concrete density: 150 pcf (use 150, if concrete) Chimney wt: 2,945 lb Backfill ht: 1 ft, footing assumed to be 12" thick per IRC) Lip of footing: 6 in, (assumed to be 6" unless known otherwise) Overburden? 1 - 0 for full excavation, 1 otherwise Overburden wt: 1,012 lb Below grnd wt: 3,957 lb Lower Portion: Chimney W: 6.666667 ft Chimney D: 2 ft Wall Thickness 0.67 ft, min, assumed Chimney Area: 13.33 sf, WxD Flue Area: 3.5156 sf, min, assumed Chimney Net Area: 9.82 sf, area — flue area Chimney H: 6 ft Chimney Vol: 58.91 cf, net area x ht Brick density: 120 pcf Chimney wt: 7,069 lb Upper Portion: Chimney W: 3.5 ft Chimney D: 2 ft Wall Thickness 0.33 ft, min, assumed Chimney Area: 7.00 sf, WxD Flue Area: 3.8056 sf, min, assumed Chimney Net Area: 3.19 sf, area — flue area Chimney H: 8 ft Chimney Vol: 25.56 cf, net area x ht Chimney wt: 3,067 lb Total Weight: 14,093 No Piers: 4 Wt/ pier: 3,523 Ib Page 7 of 8 Pier Load Calculations Owner: Janetta Lee Address: 9309 236th St. SW City, State, ZIP: Edmonds, WA 98020 PN: HE23060007 Calculate Individual Pier Loadings and Drive Requirements Pier Model: GTPP Bracket/Cap: FP3BA Pier Type: Push Factor of Safety: 1.5 standard for this pier type Eff Head Area (EH) 9.62 sq in, drive head area for 3.5 in drive cylinder Shaft Allow. Ld: 16,500 Ibs, per mfr literature Bracket Allow. Ld: 30,000 Ibs, per mfr literature Use Allow. Ld: 16,500 Ibs, min of shaft or bracket Pier Allow. T: 0 ft-lb, allowable torque if helical, 0 if push Max Pier Space: 18.35 ft; min of (Use Allow/w) and L allow Max Rec Space: 8 ft unless noted otherwise ..Linear... Load EMU Max: 1 5 1 OK 1 6,1851 1 9,277 964 Note that system capacities given are for galvanized, corroded brackets. Push Page 8 of 8