REVIEWED BLD2021-0520+Interior_Lighting_Summary+4.12.2021_9.32.48_AM+2139725Firefox
https://waenergycodes.com/print_project summary_f6nn.php?k=aWQ...
BLD2021-0520 RECEIVED
LIGHTING COMPLIANCE SUMMARY DESE E1PMEN3ER�VCES
2018 WSEC Compliance Forms for Commercial Buildings including Group R2, R3 & R4 over 3 stories and all RI Administered by: 02021 NEEA, All rights reserved
Project & Applicant
Information
Project Title
Edmonds WWTP - 2018 WSEC
For Building Department Use: Date' Apr 02, 2021
Project Address
200 2nd AVE S
Edmonds, WA 98020
Applicant Name
Marcus Eidal
Applicant Phone
206-200-5211
Applicant Email
Meidal@ameresco.com
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
General Occupancy
All Commercial
General Building
Utility/Equip,
Building Cond.
4,126
Use Type
Other
Floor Area
New Building
Project Cond. Floor
4,126
or
Alteration
Interior Lighting
Area
Floors Above Grade
1
General Project Types
Alteration
Addition
Lighting
Exterior Lighting
Compliance Method
Compliance Method 1
Lighting
Scope
Scope
- General
This project includes replacements of existing fixtures with LED fixtures. All revised interior fixtures are sealed for (NEC 500)
Lighting Project Description
Class II, Division 2 hazardous environment. Existing fixtures are 2 x 32W T8 to be replaced with 37W/fixture. Exterior fixtures
provide task lighting for modified process areas for new equipment.
Project
Interior / Exterior
Luminaire Replacement
Compliance
LPA Calculation
Compliance
Lighting Compliance
YP
Type
(Interior includes both interior &
parking)P
Scope
Method
Adjustment
J
Verification
Scope
and Method
Alteration
Interior Lighting
50% or more replaced
Building area
No Calculation Adjustments
allowed J
COMPLIES
Alteration
Exterior Lighting
less than 50% replaced
Not applicable to exterior
COMPLIES
Additional Efficiency
Options Included
Project Title Edmonds WWTP - 2018 WSEC Date Apr 02, 2021
Lighting Power Calculation ALTERATION - INTERIOR LIGHTING (50% or more Compliance COMPLIES
replaced) Verification
Compliance Method Building area LPA Calculation Adjustment none
Interior Lighting Power Allowance - Building Area
Building Areas
Gross Interior Area (SF)
LPA (Watts/SF)
Total Watts Allowed
Total Proposed Watts
Compliance Status by
(SF x LPA x 1)
By Building Area
Building Area
Manufacturing facility
1 4,126
1 0.82
1 3,383
1,275
COMPLIES
Proposed Lighting Power Density
Watts per
Total Watts
Fixture
Fixture
New or
Quantity of Fixtures, CLDs
Fixture, CLD or
Total
Watts per
Proposed
Type/Application
ID
Building Area
Existing -to-
or
I
Linear
Linear
(#F x WpF)
Remain
Luminaires (#F)
(WpF�Ce
Feet (LF)
Foot (WpLF)
or
(LF x WpLF)
Individual Fixtures
Troffer
XP2
Manufacturing
New
51
25
1,275
facility
Project Title
Edmonds WWTP - 2018 WSEC
Date
Apr 02, 2021
Proposed Fixtures Details
ALTERATION - INTERIOR LIGHTING (50% or more replaced)
Fixture Type/Application
Fixture ID
Location in Documents
Lamp Type
Building Area
New or
Existing -to -Remain
Individual Fixtures
Troffer
XP2
E-9, E-11,E-12
LED
Manufacturing facility
New
Fixture Description: Sealed, Classified Area Linear FIxture
Are these fixtures located within a daylight zone?: No
Do these fixtures require specific application lighting controls?: None required
Project Title
Edmonds WWTP - 2018 WSEC
Date
Apr 02, 2021
Lighting Power Calculation
ALTERATION - EXTERIOR LIGHTING (less than 50%
Compliance
COMPLIES
replaced)
Verification
Exterior Lighting Power Allowance
Category
Tradable and
Non -Tradable Categories
Existing Lighting -Wattage
Prior to Alteration
Total Watts Allowed
Total Proposed Watts
Compliance Status
Existing Lighting
Building entrances and exits
350
350
Existing Lighting
Building grounds
5,150
5,150
1 of 2 4/2/2021, 6:09 AM
Firefox
Ri=r-FniFn
https://waenergycodes.com/print_project summary_f6nn.php?k=aWQ...
Proposed Exterior Lighting Pow
Spaces with less than 50% fixtures replaced
CItt OFE-01IDS
OEVELOPMENTSE
Quantity of
VICES
Watts per
Total Watts
Fixture Type
Fixture ID
Tradable and
New or DE- Fixtures
Fixture, CLD or
Total Linear
Watts per Linear
Proposed
Non -Tradable Categories
Existing -to -Remain
CLDs or
Luminaire (WpF)
Feet (LF)
Foot (WpLF)
(#F x WpF) or
Luminaires (#F)
(LF x WpLF)
Individual Fixtures
Wall -mounted
GG
New
3
59
177
Wall -mounted
HH
New
4
43
1
1
1 172
Proposed Total LPD
1 349
Project Title
Edmonds WWTP - 2018 WSEC
Date
Apr 02, 2021
Proposed Fixtures Details
ALTERATION - EXTERIOR LIGHTING (less than 50% replaced)
Fixture Type/Application
Fixture ID
Location in Documents
Lamp Type
Tradable and
Non -Tradable Categories
New or
Existing -to -Remain
Individual Fixtures
Wall -mounted
GG
E-4, E-8
LED
New
Fixture Description: Hazardous Area, Wall Pack Photoeye
Wall -mounted
HH I E-4, E-8 LED
New
Fixture Description: Normal Area, Exterior Wall pack with photoeye control
2 of 2 4/2/2021, 6:09 AM