Loading...
Commissioning Report,&COFFMAN ENGINEERS January 31, 2024 Executive Summary Project: Port of Edmonds Administration Building Edmonds, Washington CEI Project No: 211615 INTRODUCTION The purpose of commissioning is to verify mechanical, electrical, plumbing, and lighting systems to meet LEED requirements, WSEC requirements and to verify selected systems are operational, maintainable, and commissionable. The CxA was present during the functional testing and witnessed all or part of each activity. A. Commissioning Scope of Services: ✓ Review OPR, BOD, Construction Documents, Submittals, and O&M materials. ✓ Design and Construction phase issues log maintenance and resolution. ✓ Develop and revise the Commissioning Plan. ✓ Coordinate commissioning work. ✓ Develop and perform pre -functional and installation checks (PFC) of mechanical, electrical, and plumbing equipment. ✓ Develop and perform functional performance tests (FPT). ✓ Witness ductwork and piping testing & +Id/or flushing, and HVAC Testing, Adjusting and Balancing as necessary. ✓ Verification Owner training was performed and documented. ✓ 10-month warranty visit to satisfy LEED EA Cr. 3 for enhanced commissioning. B. Systems Commissioned: 1. DOAS dedicated outside air (energy recovery) & Associated Fans 2. MAU & Associated Fans 3. VRF Heat Recovery Systems 4. Two Split systems for Server and Elevator Mach room 5. Domestic Water Heaters 6. Hot Water Recirculating Pumps 7. Domestic Cold Water 8. Lighting Control systems 9. Water & Electrical Meters 1101 Second Avenue, Suite 400 1 Seattle, WA 98101 Phone 206.623.0717 www.coffman.com POE Admin Bldg Executive Summary January 31, 2024 Page 3 E. Issues Discovered Which Were Not Resolved and Their Potential Impact: 1. None. F. Recommendation: 1. 10-Month warranty review. Sincerely, r94��C ERGBrent Wittke, C.E.M. M #28026 G) —11 — w- EXP.06/30/2026 X Brent Wittke COFFMAN ENGINEERS, NC CCW PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST DOMESTIC WATER HEATING SYSTEM Project No, 210887 Dale: 01/19/2024 4 of 4 tests signed off TEST NARRATIVE: This test is used to verify the operation of the domestic water heating system, including the water heater, circulation pump and mixing valve assembly. Executed By: B W ittke Witnessed By. Scott Sweetwem FUNCTION TO BE INITIAL COFFMAN TEST p TESTED TEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS TEST DATE COMPLETE ISSUE SIGN OFF/ REMARKS DATE 1) PFCs are complete or (if not complete) have been documented (i.e., issues log). 2) Equipment start-up is complete and documents have been 1) Pass collected. 1) PFCs complete or open discrepancies are documented in Issues Log, 2) Pass PRE -TEST 3) All safety features have been installed per water heater detail 2) Documents collected. 3) Pass 10/12/2023 1P9/2024 1/19/2024 VERIFICATIONS on plumbing drawing. 3) Saffies are installed. 4) N/A 4) Point-to-point (P2P) Is complete. 4) P2P is complete. 5) Pass 5) TAB of domestic water system is complete. TAB scope may 5) TAB report collected. include balancing of domestic hot water recirculation valves, auto flow valves pressure verifications, etc. 1) Manipulate plumbing fixtures and/or drain valves so that the system experiences moderate flow demand of hot water, 1) Common pipe downstream of water heaters but upstream of mixing 1) Pass Maintenance Bay restrooms: Mixing Valve Confirm one domestic water heater operates per manufacturers valve holds steady at setpoint (120 F). Mixing valve is set to 120 F. Maintenance bay (under -sink) requires adjustment. Hot water DHW SYSTEM control system and regulates constant supply water temperature restrooms mixing is at valve, mixing valve delivering 61.2deg OPERATION - while system is subjected to various moderate flow rates. 2) 2) 10/12/2023 1/19/2024 valve setting 1Y2a/2024 water after 5min. WATER HEATER 1 a. Time to achieve 120`F IAW design documents. 2a) 5 seconds adjustment. 2) Open all remote HW valves for water heaters. Record the time b. Water temperature remains constant for 15 minutes with the all remote 2b) Pass 1124 - Connected, HW within 10 seconds (in seconds) from opening to achieve 120°F. Run for 15 minutes, HW valves open. record any deviation from 12WR DHW SYSTEM 1) With system operating normally, verify operation of 1) CP-1 operates continuously at constant speed. OPERATION - recirculation pump CP-1. 1) Pass 4.Bgpm RECIRCULATION 2) Balancing valve modulates to maintain DHW building supply 10/12/2023 1/19/2024 1/19/2023 120deg F throughout PUMPS AND 2 ) Verif y operation of balancing valve downstream of WH-1. temperature setpoint of 120°F. (Record actual temp in Test Results 2) Pass MIXING VALVE column) TRAP PRIMERS 1) Manifold is located in Mechanical Room. Initiate a primer fill by 1) Each trap tested fill s with water when initiated. i) Pass 10/12/2023 1/19/2024 1/19/2023 hitting test switch for each unit or cycling power. END OF TEST FOR DOMESTIC HOT WATER SYSTEM DHW System PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST Exhaust Fans: Elec RM Project No: 210887 Date: 1/1912024 2 of 2 tests signed off TEST NARRATIVE: This testing of the Unit assumes Pre -functional and Start-up testing have been completed. The test verifies operation of EF-1. Executed By: Brent W ittke - CEI Witnessed By: Jeff Hayes - Morgan Mechanical Date Completed: 111912024 TEST p FUNCTION TO BE TEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT INITIAL TEST MEETS CRITERIA RESPONSIBLE FOR DATE REMARKS TESTED DATE YIN RESOLUTION COMPLETE PRE -TEST 1) Start-up is complete and documents have been collected. 1) Documents collected. 1) Pass 1 2) PFCs are complete or Of not complete) have been documented (i.e., 2) PFCs complete or open discrepancies are 2) Pass 1/19/2024 Y 1/1912024 VERIFICATIONS issues log). documented in issues log. 1) While circuit is energized at the breaker panel and local disconnect la) Fan Is running and is not part of any building 1a) Pass switch is ON observe EF-1 operation. HVAC timer or has any relays installed to interrupt operation. NORMAL 2) Switch OFF local disconnect. Observe EF-1 operation. Re- 1 b) While fan is running the fan wheel appears in 1b) Pass 2 OPERATION energize fan once observation is complete. balance running smoothly. ON 1/19/2024 Y 1/19/2024 2) Fan is disabled via the disconnect. 2) Pass END OF TESTING Page 1 of 17 1 a) Fan runs continuously at a constant speed. 1a) Pass - 1) Adjust the active heating setpoint so it's above the current space 1 b) Compressor cycles to maintain active 1 b) Pass temperature for a few zones. Adjust the active cooling setpoint so it's heating/cooling setpoint. below current space temperature for remaining zones. 1c) Cooling is present in zone with cooling demand and 1c) Pass Heating is present in remaining zones. 2) With space temperature satisfied. 1d) Outside Temperature is to) 40 le) FCU-1 DAT is _ DegF, Setpoint is _DegF 1e) 90 175 3) Return active cooling setpoint to 73 and heating to 68 deg, or as 10 FCU-2 DAT is _ DegF, Setpoint is _DegF 1f) 95170 MIXED HEATING prescribed by Cwner. 1g) FCU-3 DAT is _ DegF, Setpoint is _DegF 1g) 107 181 4 AND COOLING 1 h) FCU-4 DAT is _ DegF, Setpoint is _DegF 1 h) 103 183 ON 1/1912024 Y 1/19/2024 OPERATION 1 i) FCU-12a DAT is _ DegF, Setpoint is _DegF 1 i) 112183 1j) FCU-121b DAT is _ DegF, Setpoint is _DegF 1j) 108183 1 k) FCU-12c DAT Is _ DegF, Setpoint Is _DegF 1 k) 110 183 2) Unit does not operate and fan is off. 2) Pass 3) Setpoints have been adjusted. 3) Pass List any alarms and how they were verified/tested here. If no alarming 1) then just write N/A. ALARMING 1) NIA 2) N/A N/A No Alarming 2) WA END OF TEST ta) Fan runs continuously at a constant speed. 1a) Pass 1) Adjust the active heating setpoint so it's above the current space 1 b) Compressor cycles to maintain active 1 b) Pass temperature for a few zones. Adjust the active cooling setpoint so it's heatfng/cooling setpoint. below current space temperature for remaining zones. 1c) Coolfng is present in zone with cooling demand and 1c) Pass Heating is present in remaining zones. 2) With space temperature satisfied. 1 d) Outside Temperature is 1d) 40 le) FCU-5 DAT is _ DegF, Setpoint is _DegF 1e) 115 181 3) Return active cooling setpoint to 73 and heating to 68 deg. or as 10 FCU-6 DAT is _ DegF, Setpotnt is _DegF 10 110181 MIXED HEATING prescribed by Owner. tg) FCU-7 DAT is _ DegF, Setpoint is _DegF 1g) 115 182 AND COOLING th) FCU-8 DAT is _ DegF, Setpoint is _DegF 1h) 105 182 ON 1/19/2024 Y 1/19/2024 OPERATION 1i) FCU-9 DAT is _ DegF, Setpoint is _DegF 1i) 101 182 1j) FCU-10 DAT is _ DegF, Setpoint is _DegF 1j) 99 182 1 k) FCU-11 DAT Is _ DegF, Setpoint is _DegF 1 k) 120 182 2) Unit does not operate and fan is off. 2) Pass 3) Setpoints have been adjusted. 3) Pass List any alarms and how they were verified/tested here. If no alarming 1) then just write N/A. 5 ALARMING 1) N/A 2) N/A WA No Alarming IIIIIIIIIIIIIIIIIIArm 2) N/A END OF TEST PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST SS-1: Elev Machine Rm. Project No: 210887 Date: 1/19/2024 5 of 5 tests signed off TEST NARRATIVE: This test is used to verify mechanical heating, cooling and other features of the split system heat pump unit. The manufacturer's control panel controls all aspects of the heat pump. Executed By: Brent W ittke - CEI Witnessed By: Jeff Hayes - Morgan Mechanical Date Completed: 111912024 TESTY FUNCTION TO BE TESTED TEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT INITIAL TEST DATE MEETS CRITERIA YIN RESPONSIBLE FOR RESOLUTION DATE COMPLETE REMARKS List any alarms and how they were venfied/tested here. If no alarming 1) then just write N/A. 5 ALARMING 1)N/A 2) N/A N/A 2) N/A END OF TESTING Page 7 of 17 PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST SS-2: 212 SERVER Project No: 210887 Date: 1/19/2024 5 of 5 tests signed off TEST NARRATIVE: This test is used to verify mechanical heating, cooling and other features of the split system heat pump unit. The manufacturers control panel controls all aspects of the heat pump. Executed By: Brent Wittke - CEI Witnessed By: Jeff Hayes - Morgan Mechanical Date Completed: 1/19/2024 TEST If FUNCTION TO BE FUNCTIONTEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT INITIAL TEST DATE MEETS CRITERIA YIN RESPONSIBLE FOR RESOLUTION GATE COMPLETE REMARKS List any alarms and how they were verified/tested here. If no alarming 1) then just write N/A. 5 ALARMING 1)N/A 2) WA N/A 2) N/A END OF TESTING Page 9 of 17 1 Operate MAU-1 in occupied made with EF-2 operating 1) Equipment i5 operating normally with no alarms 1) Pass normally. 2a) Alarm for CO/N2 is displayed 2a) Pass 2) Manipulate CO/N2 sensor, to verify VRF ConVoller EF-2 Ope2tes for 30 minutes or until alarm clears. 2b) Pass Auto 1/19/2024 V 1/24/2024 displays Hlgh level alarms.2b) 11111111P 3 Remove overrides or Test Gas from sensor. 3) Equipment is operating normally with no alarms 3) Pass 1) Room temperature trends are running. 1) Pass No local front end. Trane virtual online Verify all trends are active per DOP. rg perature Vend is runnm 2 MAU discha a air lem - g, ) 2 Passdays Auto 1/19/2024 Y 1/24/2024 access only (or trentls. 1-week stored for 30- Verify, all alarms are set based on DOP. 1) Room temperature deviation alarms are clear. 1) Yes Auto 1/19/2024 Y 1/24/2024 END OF TEST Page 11 Record as found static pressure setpoint prior to start of procedure. confirm it matches that recorded In the final TA report by the balancing contractor. 1) Set duct static pressure at 0.05" below current setpoint and record time to stabilize at new setting. 1) Achieve selpoinl and stabilize within 3 minutes 1) Pass 2) Set duct static pressure at 0.05" above current setpoint 2) Achieve setpoint and stabilize within 3 minutes. 2) Pass and record time to stablfize at setting. - 3) Verify setpoint has been restored to value indicated in final TAB report 3) Pass 3) Return duct static pressure setpoint to as found setting, by balancing contractor. 4) Simulate filter load of the unit filters in filter housing by 4a) Record DP across unit filters on provided gauge poor to simulating 4a) Pass DUCT STATIC placing pieces of cardboard across the filter surface, filter loading, assuming filters are clean. Verify against final TAB report 5 PRESSURE Monitor OP as cardboard is added as not to exceed 2X by balancing contractor. Auto 1/19/2024 Y 1/24/2024 CONTROL clean filter DP. 4b) Place clean dry pieces of cardboard across the inlet side of the unit 4b) Pass (FILTER LOADING) filters till no more than 2X dean filter DP is achieve. or supply fan is 5) Simulate dirty filter in filter housing by placing cardboard operating at 601-1z. 4c) Pass across filter surface and exceed nominal clean filter OP to 4c) Supply fan begins to speed up to compensate for filter loading and activate alarm. achieve static pressure selpoint. 5) Pass 5) Unit reports Dirty Filter In alarms on Unit controller and in BM$. 6) Pass 6) Remove cardboard, secure unit and return to normal 6) Unit alarms are cleared, and Supply fans begin to slow down to operation. operate as programmed by balancing contractor. DO NOT EXCEED 2X CLEAN FILTER DP OR FILTER RACK/FRAME IS LIKELY TO BE DAMAGED BECAUSE OF THE EXCESSIVE FORCE ON STRUCTURE. 1) Start test with system running normally in Occupied 1a) Heal element is not activated. 1a) Pass mode and no heating demand. 1b) Record starting DAT, and space temperature, and OA. tb) Pass DAT 72 6 OCCUPIED MODE - Auto 1/192024 Y 1/24/2024 space RH 38% HEATING CONTROL 2) Manipulate system so that there is a heating demand by 2a) Electric heater m activated supply heating heating Record DAT, 2a) Pass 2b) Pass outside RH 40% adjust selpoint 2 degrees above current space temperature at demand, 2b) When space temperature satisfies demand, and space temperature, and OA. and 1) Start lest with system running normally in Occupied 1a) Heat element is not activated. 1a) Pass mode and no heating demand- 1b) Record starting DAT, and space RH, and Outside RH. 1 b) Pass ' DEHUMIDIFCATION DOAS activates dehumidification mode, lowering moisture content in 2a) Pass Auto 1119I2024 Y 1242024 DAT 72 space RH 36% MODE 2) Manipulate system so that there is higher moisture unit. unit. outside RH 40 content registered by sensor to activate dehumidification 2b) When space temperature satisfies heating demand, Record DAT, 2D) Pass I mode and space RH, and Outside RH. 8 UNOCCUPIED 1) Continuing from previous test, manipulate the system so 1a) Unoccupied mode is initiated. Supply and exhaust fans shut down. 1a) Pass Auto 1/19/2024 Y 1/24/2024 MODE that MAU goes Into Unoccupied Mode. 1b) Outside air and exhaust air dampers close. 1b) Pass DOAS 1) Having completed test above, the system should operate 1) In deadband mode fan should continue to run and unit controls 1) Pass DISCHARGEISPACE In deadband mode. modulate heating and cooling to maintain the deadband (free air) 9 TEMPERATURE setpoints. Auto 111M024 Y 1/24/2024 CONTROL- 2) Release any overrides, setpoints adjustments, etc. that 2) Pass DEADBAND were made to perform the above tests. 2) Overrides, setpoints, etc. are back to their normal state. HEATED SPACE 1st 1) Start lest with system running normally in Occupied 1a) Heat element is not activated. 1a) Pass DAT 95 Space 68 OCCUPIED MODE - mode and no heating demand. tb) Record starting DAT, and space temperature, and OA. 1b) Pass OA 52 10 COOLING 2a) Electric heater is activated to supply heating demand. 2a) Pass Auto 1/192024 Y 1/24/2024 CONTROL 2) Manipulate system so that there is a heating demand by When space temperature satisfies heating demand, Record DAT, 2b) Pass Occupied mode adjust point 2 degrees above current Spam temperature. adjset eg p2b) and space temperature, and CA. DAT 71 space 70 OA 52 Page 13 PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST DOAS-2, CF41-4): Maint. Bays/Shop Ventilation Project No: 210887 Date: 1242024 17 of 17 tests signed off TEST NARRATIVE: This test is used to verify mechanical heating, cooling and other features of the DOAS Executed By: Brent Wittke. CEI Witnessed By: Kevin Henry, Trane Date 1/24/2024 TEST It FUNCTION TO BE FUNCTIONTEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT INITIAL TEST MEETS CRITERIA RESPONSIBLE FOR COMPLET REMARKS DATE YIN RESOLUTION SYSTEM 1) Review system install against design drawings. 1) Install matches intent of design, deviations marked upon as builts. 1) Yes 1 INSPECTION AND 2) Review startup report from contractor for each piece of 2) MAU(s), EF(s), and VFD(s) startup complete. 2) Yes Auto 1/19/2024 Y 1/24/2024 DOCUMENT equipment. 3) Matches intent of design, deviations marked up on as builts and 3) Yes REVIEW 3) Review balance report for compliance with design. approved by CEI engineering. NOTE TO TESTING PERSONNEL: THESE TEST FUNCTIONS AND ASSOCIATED PROCEDURES ARE DESIGNED TO BE CONDUCTED WITH TWO INDIVIDUALS. ONE IS TO BE A WITNESS OF RTU/EF OPERATION AT THE EQUIPMENT AND OTHER TO OPERATE PROGRAMMABLE THERMOSTATS AND SENSORS IN SPACE OR THRU THE BMS. DURING ACTUAL FUNCTIONAL TESTING COMMISSIONING AGENT WILL BE THE WITNESS AT THE EQUIPMENT AND SUPPORTING MECHANICAL CONTRACTOR WILL ASSIST BY PERFORMING PROCEEDURES WITHIN THE SPACE SERVED. 1a) Outside air dampers open and end switch activates starting of la) Pass DOAS. Fan is prevented from starting until damper is proven open and EF(s) are enabled. EF(s) and MAU(s) must ramp up simultaneously while maintain room pressure relationship. 1b) Pass 1 b)Imedocked motorized damper begins to open, while exhaust fan(s) remain disabled. Once the interlocked motorized damper is approximately 75% open then exhaust fan(s) are enabled and slowly ramps up. 1c) Pass 1) Verify proper startup sequence mru occupied programmed 1c) Verify associated dampers open, fans start according to their schedule. respective start up sequences. 1d) Pass START/STOP VIA 1d) While supply fan(s) and exhaust fans start, verify room pressures OA 50 2 DOC 2) Shutdown MAU(S) and EF(s) thm occupied programmed remain in proper direction and do not exceed double their respective Auto 1/19/2024 Y 1/24/2024 SA 70 schedule. design values. le) Pass EA 72 2a) Interlocked motorized damper begins to spring closed, while 2a) Pass exhaust fan remains enabled. Once the interlocked motorized damper is approximately 75% open the exhaust fan(s) are disabled and slowly decelerate to a stop. 2b) While supply and exhaust fans stop, verify room pressures remain In 2b) Pass proper direction and do not exceed double their respective design values. 2c) Pass 2c) When fans stop, the OA dampers close. 2d) Pass 1) Interlocked motorized damper begins to dose to about 75% blades 1) Pass when exhaust fan EFs Is disabled. Intedocked motorized damper close 1) While the VFD is in AUTO select HAND OFF on the VFD tightly (no gap in damper blades). keypad. 2) Interlocked motorized damper is opened and when blades 2)Pass 2) While the VFD is off in HAND via the VFD keypad, select approximately 75% open, the exhaust fan EFs is enabled. Dampers 3 EF(S) DAMPER HAND ON. continue to open fully. Auto 1/19/2024 Y 1242024 INTERLOCK 3) Disconnect power to the interlocked motorized damper 3.a) Damper fails to a fully closed to outside air (Normally Closed) 3a) Pass while open. position. Supply fan is disabled when blades are about 75% closed. 3.15) Re -energize power to interlocked motorized damper. Damper 3b) Pass Repeat procedure for each exhaust fan. blades begin to open to approximately 75% when the exhaust fan EFs i m-enabled. 1) While exhaust is enabled it is being controlled to a fix 1a) Record the speed of EF(s) constant speed setpoint asset by the 1a) Y See TAB report speed to obtain design airflow rates as set by the balancing balancing contractor in the VFD parameters to obtain required alrflow 4 F(S) SPEED ONTROL contractor. rate 1b) The fan Is operating at the speed setpoint set in VFD Parameter. 1b) Y See TAB report Auto 1/192024 Y 1242024 1c) The speed setpoint set in VFD parameter matches that recorded in 1c) Y See TAB report TAB final report. Page 15 1) Verify unit is able to hold space temperature between 63°F and 67°F continuously. Record: Outside air temperature at start and finish. Min space temp and max space temperature during this test period. STEADY STATE i) Trend unit operation for 3 hours in the morning when 2) Verify unit is able to hold space temperature between 63°F and 67°F 1) Pass 11 TEMPERATURE Outside Air is below 50°F. continuously. Auto 1/19/2024 V 1/24/2024 CA start finish 52 CONTROL Outside air temperature at stag and finish. temperature start finish Space stag to finish 68 68 PERFORMANCE 2) Trend unit operation for 3 hours in the afternoon when hein space temp and max space temperature during this test period. 2) Pass Outside Air is above 50°F. IF THESE TESTS FAIL, CONSULT WITH VENDOR ON SETPOINT CHANGES IN THE CONTROLLER TO IMPROVE TEMPERATURE CONTROL PERFORMANCE, MAKE ADJUSTMENTS AND REPEAT - _ THE TEST AS NEEDED UNTIL SUCCESSFUL. 1) Turn on ceiling fans through their associated speed controller. Operate fan at lowest speed, then continue to 1a) Ceiling fan responds speed controller selection_ 1a) Yes cycle through speed selection and observe operation. smoothly without 1b) Ceiling fan operates smoothly without wobble. 1b) Yes 12 CF-1 OPERATION 2) Turn off ceiling fans through their associated speed Auto 1/19/2024 Y 1/19/2024 controller. 2) Celling fan turns off. 2) Yes Repeat test for each fan. 1) Turn on ceiling fans through their associated speed controller. Operate fan at lowest speed, then continue to 1a) Ceiling fan responds correctly to speed controller selection. la) Yes cycle through speed selection and observe operation. 1b) Ceiling fan operates smoothly without wobble. 1b) Yes 13 CF-2 OPERATION 2) Turnoff ceiling fans through their associated speed Auto 1/19/2024 Y 1/1912024 controller. 2) Ceiling fan turns off. 2) Yes Repeat test for each fan. 1) Turn on ceiling fans through their associated speed controller. Operate fan at lowest speed, then continue to 1a) Ceiling fan responds correctly speed controller selection. 1a) Yes cycle through speed selection and observe operation. 1b) Ceiling fan operates smoothly wi without wobble. ib) Yes 14 CF-3 OPERATION 2) Turnoff ceiling fans through their associated speed Auto 1/19/2024 Y 1/19/2024 _ controller. 2) Ceiling fan turns oft. 2) Yes Repeat test for each fan. 1) Turn on ceiling fans through their associated speed controller. Operate fan at lowest speed, then continue to 1a) Ceiling fan responds comectly to speed controller selection. 1a) Yes cycle through speed selection and observe operatlon. 1b) Ceiling fan operates smoothly without wobble. 1b) Yes 15 CF-4 OPERATION 2) Turnoff ceiling fans through their associated speed Auto 1/19/2024 Y 1/19/2024 controller. 2) Celllng fan turns off. 2) Yes Repeat test for each fan. winning, 1) Room temperature trends are running. RoomDOAS 1) Pass No local front end. Trane virtual online 16 TRENDS Verify all trends are active per DOP 2) discharge air temperature trend is running, 2) Pass Auto 1/1912024 Y 1/24/2024 access only for trends. 1-week stored for 30-days 17 ALARMS Verify all alarms are set based on DOP. 1) Room temperature deviation alarms are clear. 1) Yes Auto 1/19/2024 Y 1/24/2024 END OF TEST Page 17 PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST Electric Heater: EH-3 (Fire Riser Rm) Pmject No: 210887 Date: 01/19/2024 2 of 2 tests signed off TEST NARRATIVE: This testing of the Unit assumes Pre -functional and Start-up testing have been completed. The test verifies heating and cooling operation. Executed By., Brent Wittke - CEI Witnessed By., Jeff Hayes - Morgan Mechanical Date Completed., 1/19/2024 FUNCTION TO BE INITIAL TEST MEETS RESPONSIBLE DATE TEST# TESTED TEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT DATE CRITERIA FOR COMPLETE REMARKS YIN RESOLUTION PRE -TEST 1) Start-up is complete and documents have been collected. 1) Documents collected. 1) Pass 1 VERIFICATIONS 2) PFCs are complete or (if not complete) have been documented (i.e., 2) PFCs complete or open discrepancies are 2) Pass 1/19/2024 Y 1/19/2024 issues log). documented in issues log. 1) Adjust the unit's internal thermostat so heating is enabled. 1a) EH-3 enables and modulates to achieve 1a) Pass setpoint. 1 b) Record maximum discharge temperature. 1 b) Pass 2 HEATER 2) Return Heater to origlnal setpoint. set 65°F 1/19/2024 Y 1/19/2024 OPERATION 2) Heater turns off as it crosses room 2) Pass 3) Set room dial to 65'F temperature. 3) T-slat set at 65°F 3) Set END OF TESTING Page 3 of 7 PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST Electric Heater: EH-7 (1046 RR) Project No: 210887 Date: 0111912024 2 of 2 tests signed off TEST NARRATIVE: This testing of the Unit assumes Pre -functional and Start-up testing have been completed. The test verifies heating and cooling operation. Executed By: Brent Wittke -CEI Witnessed By: Jeff Hayes - Morgan Mechanical Date Completed., 1/19/2024 FUNCTION TO BE INITIAL TEST MEETS RESPONSIBLE DATE TESTA TESTED TEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT DATE CRITERIA FOR COMPLETE REMARKS YIN RESOLUTION PRE -TEST 1) Start-up is complete and documents have been collected. 1) Documents collected. 1) Pass 1 VERIFICATIONS 2) PFCs are complete or (if not complete) have been documented (i.e., 2) PFCs complete or open discrepancies are 2) Pass 1/19/2024 Y 1/19/2024 issues log). documented in issues log. 1) Adjust the unit's internal thermostat so heating is enabled. 1 a) EH-3 enables and modulates to achieve 1a) Pass setpoint. tb) Record maximum discharge temperature. 11b) 86 F 2 HEATER 2) Return Heater to original setpoint. Set 65 10/12/2023 Y 10/12/2023 Set to 80F for lest OPERATION 2) Heater turns off as it crosses room temperature. 2) Pass 3) Set room dial to 65'F 3) T-scat set at 65°F 3) Pass END OF TESTING Page 5 of 7 PORT OF EDMONDS: FUNCTIONAL PERFORMANCE TEST Electric Radiant Heater: ERH-7 THROUGH ERH-12 (Double HT. Maint Shop) Project No: 210887 Date: 1/19/2024 5 of 5 tests signed off TEST NARRATIVE: This testing of the Unit assumes Pre -functional and Start-up testing have been completed. The test verifies heating and cooling operation. Executed By: Brent Wittke - CEI Witnessed By: Jeff Hayes - Morgan Mechanical Date Completed: 1/19/2024 FUNCTION TO BE INITIAL TEST MEETS RESPONSIBLE DATE TESTA TESTED TEST PROCEDURE CRITERIA FOR ACCEPTANCE TEST RESULTS AS -LEFT DATE CRITERIA FOR COMPLETE REMARKS YIN RESOLUTION PRE -TEST 1) Start-up is complete and documents have been collected. 1) Documents collected. 1) Pass VERIFICATIONS 2) PFCs are complete or (if not complete) have been documented (i.e., 2) PFCs complete or open discrepancies are 2) Pass In Service 1/19/2024 Y 1/19/2024 issues log). documented in issues log. 1a) EH-7/8 enables and modulates to achieve 1a) Pass 1) Adjust the unit's internal thermostat so heating is enabled. setpoint. HEATER 1 b) Record maximum discharge temperature. tb) 520 & 541 2 OPERATION 2) Return Heater to original setpoint. 2) Heater tums off as it crosses room 2) Pass In Service 1/19/2024 Y 1/19/2024 (ERH-7/8) temperature. 3) Set room dial to 65°F 3) Return setting to 65°F 3) Set 1a) EH-9/10 enables and modulates to achieve Ia) Pass 1) Adjust the units Internal thermostat so heating is enabled setpoint. HEATER 1b) Record maximum discharge temperature. 1b) 523 & 564 3 OPERATION 2) Return Heater to original setpolnt. In Service 1/19/2024 Y 1/19/2024 (ERH-9/10) 2) Heater turns off as it crosses room 2) Pass 3) Set room dial to 65°F temperature. 3) Return setting to 65°F 3) Set ta) EH-11112 enables and modulates to achieve 1a) Pass 1) Adjust the unit's internal thermostat so heating is enabled. setpoint HEATER 1b) Record maximum discharge temperature. 1b) 563 & 534 4 OPERATION 2) Return Heater to original setpoint. In Service 111912024 Y 1/19/2024 (ERH-11112) 2) Heater turns off as it crosses room 2) Pass 3) Set room dial to 65°F temperature. 3) Return setting to 65°F 3) Set 1a) EH-7112 enables and modulates to achieve la) Pass 1) Adjust the units Internal thermostat using Wireless Connection Hub setpoint. HEATER to control all heaters so heating is enabled. 1b) Record maximum discharge temperature. lb) 563°F highest DAT 5 OPERATION 2 Return Heaters to original set ) Point. Heater rums off as it crosses room 2) Pass In Service 10/12/2023 Y 1/19/2024 (EH-7-12) temperature. to 3) Set room dial to 65°F 3) Return setting to 65°F 3) Set ' END OF TESTING Page 7 of 7