APPROVED BLD PLN RESUB 1-BLD2023-0991+Architectural Plans+9.14.2023_12.23.19_PM+3783331BUILDING ENVELOPE GENERAL NOTES, DESIGN CI�ITEf�IA � LEGEND
GENERAL NOTES
I . DRAWINGS ARE INTENDED TO DESCRIBE REQUIREMENTS OF THE BUILDING
ENVELOPE ASSEMBLY WITH RESPECT TO AIR CONTROL, VAPOR CONTROL, AND
WATER MANAGEMENT.
2. WORK IS TO BE COMPLETED IN ACCORDANCE WITH REGULATIONS AND CODE PER
THE AUTHORITIES HAVING JURISDICTION. NOTIFY CONSULTANT IMMEDIATELY IF A
CONFLICT IS FOUND BETWEEN ENVELOPE DRAWINGS AND CODE. GENERALLY THE
MORE STRINGENT CODE REQUIREMENT APPLIES.
3. PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL NOTIFY THE
CONSULTANT OF DISCREPANCIES BETWEEN THE BUILDING ENVELOPE DRAWINGS
AND SITE CONDITIONS, MANUFACTURER RECOMMENDATIONS, CODES OR
REGULATIONS OF AUTHORITIES HAVING JURISDICTION.
4. DO NOT SCALE DRAWINGS. FIELD VERIFY ALL DIMENSIONS. CLADDING
REQUIREMENTS TO BE VERIFIED.
5. THE DRAWINGS ARE TO BE INTERPRETED IN CONJUNCTION AND IN A
COMPLIMENTARY MANNER WITH SPECIFICATIONS.
6. DO NOT SUBSTITUTE BUILDING ENVELOPE MATERIALS SPECIFIED WITHOUT
RECEIVING WRITTEN APPROVAL FROM THE CONSULTANT.
7. REFER THE MATERIAL DATA SHEETS AND MANUFACTURERS INSTRUCTIONS WITH
RESPECT TO COMPATIBILITY BETWEEN MATERIALS.
AIR BARRIERS AND ENVELOPE THERMAL PERFORMANCE
I . AB CALL -OUTS DENOTE AIR BARRIER COMPONENTS.
2. IDENTIFICATION MARK SHALL BE APPLIED TO ALL INSULATION MATERIALS AND
INSULATION INSTALLED SUCH THAT THE MARK IS READILY OBSERVABLE DURING
INSPECTION.
3. FENESTRATION PRODUCTS SHALL BE LABELED WITH NFRC U-FACTOR, SHGC, VT
AND LEAKAGE RATING.
4. PROJECT CLOSE OUT DOCUMENTATION IS REQUIRED INCLUDING APPLICABLE
CALCULATIONS, WSEC ENVELOPE COMPLIANCE REPORTS, AND FENESTRATION NFRC
RATING CERTIFICATES.
FIELD TESTING REQUIREMENTS
I . THE FOLLOWING TABLE PROVIDES REQUIRED FIELD TESTING OF BUILDING ENVELOPE
COMPONENTS, SYSTEMS AND ASSEMBLIES.
TESTED SYSTEM OR ASSEMBLY
QUANTITY
REFERENCE
WINDOW WATER PENETRATION RESISTANCE
TBD
ASTM E 1105
SEALANT PULL -TAB ADHESION
TBD
ASTM C 1193
WI N DOWS � DOORS
I .PER SBC 17 10, WINDOWS AND DOORS SHALL BE TESTED AND LABELED AS
CONFORMING TO THE NORTH AMERICAN FENESTRATION STANDARDS (NAPS)
AAMA/WDMA/CSA I 0 I /IS2/A440 UNLESS EXEMPTED BY CODE.
2. THE FOLLOWING LIST PROVIDES RECOMMENDED SITE VISITS FOR MOCK-UP REVIEW
THAT WE ANTICIPATE WILL BE REQUIRED. THIS LIST IS NOT EXHAUSTIVE AND
SHOULD BE USED AS A GUIDE. MORE MOCK-UPS MAY BE REQUESTED BY THE
CONSULTANT.
2. I . WINDOW INSTALLATION
3. MINIMUM PERFORMANCE GRADE OF WINDOWS AND DOORS IS AS FOLLOWS:
CORNER: PG LC 65 (WITHIN 6.5 FT OF CORNER)
FIELD: PG LC 35.
WATER AND AIR BARRIERS (WRB)
ABBREVIATIONS:
I . WRB TO BE INSTALLED BOTH AS A MOISTURE BARRIER AND AS A CONTINUOUS AIR
AB
AIR BARRIER
LAM
LIQUID APPLIED MEMBRANE
BARRIER AS SHOWN IN THE PROJECT DOCUMENTS.
ABLT
ANCHOR BOLT
LOC
LOCATION
ACOUS
ACOUSTICAL
LVR
LOUVER
2. THE FOLLOWING LIST PROVIDES SITE VISITS FOR MOCK-UP REVIEW PRIOR TO
AD
AREA DRAIN
MAS
MASONRY
CONCEALMENT WITH CLADDING THAT WE ANTICIPATE WILL BE REQUIRED. THIS LIST
AFF
ABOVE FINISH FLOOR
MB
MOISTURE BARRIER
IS NOT EXHAUSTIVE AND SHOULD BE USED AS A GUIDE. MORE MOCK-UPS MAY BE
AL
ALUMINUM
MECH
MECHANICAL
REQUESTED BY THE CONSULTANT.
ARCH
ARCHITECTURAL
MEMB
MEMBRANE
BETW
BETWEEN
MH
MANHOLE
BITUM
BITUMINOUS
NIC
NOT IN CONTRACT
2. I . TYPICAL MOUNTING BLOCK
BLDG
BUILDING
NTS
NOT TO SCALE
2.2. TYPICAL ELECTRICAL FIXTURE
BLKG
BLOCKING
0/
OVER
2.3. TYPICAL PLUMBING FIXTURE
BLW
BELOW
OC
ON CENTER
2.4. TYPICAL PIPE PENETRATION
BSMT
BASEMENT
OD
OVERFLOW ROOF DRAIN
2.5. TYPICAL VENT HOOD INSTALLATION
CB
CATCH BASIN
POLY
POLYETHYLENE
CC
CLOSED CELL
PPT
PRESERVATIVE PRESSURE TREATED
2.6. TYPICAL KNIFE PLATE PENETRATION
CIP
CAST IN PLACE
PROP
PROPERTY
CL
CENTERLINE
PSF
POUNDS PER SQUARE FOOT
FURRING AND CLADDING
COL
COLUMN
PSI
POUNDS PER SQUARE INCH
CONC
CONCRETE
PT
PRESSURE TREATED
I .ALL FURRING TO BE MINIMUM BORATE TREATED AWPA UC-2 UNLESS OPEN JOINT
CONT
CONTINUOUS
PTD
PAINTED
CAVITIES EXIST
CTR
CENTER
PVC
POLYVINYL CHLORIDE
DEMO
DEMOLITION
RD
ROOF DRAIN
DIA
DIAMETER
RET
RETAINING
2. PROVIDE NON -CORROSIVE MESH INSECT SCREEN AT TOP AND BOTTOM OF
DS
DOWNSPOUT
RWL
RAIN WATER LEADER
RAINSCREEN WALL CAVITIES OR WHERE DEPICTED.
DWG
DRAWING
SAM
SELF ADHERED MEMBRANE
EL
ELEVATION
SBS
STYRENE BUTADIENE
3. THE FOLLOWING LIST PROVIDES RECOMMENDED SITE VISITS FOR MOCK-UP REVIEW
ELEC
ELECTRIC
SOG
SLAB ON GRADE
THAT WE ANTICIPATE WILL BE REQUIRED. THIS LIST IS NOT EXHAUSTIVE AND
ELEV
ELEVATOR
SF INSUL
SPRAY FOAM INSULATION
SHOULD BE USED AS A GUIDE. MORE MOCK-UPS MAY BE REQUESTED BY THE
EM
ELASTOMERIC MEMBRANE
SR INSUL
SEMI -RIGID INSULATION
CONSULTANT.
EC
ELASTOMERIC COATING
SS
STAINLESS STEEL
EW
EACH WAY
STAG
STAGGERED
3. I . BASE OF WALL
EXH
EXHAUST
STC
SOUND TRANSMISSION CLASS
3.2. TOP OF WALL
EXST
EXISTING
STL
STEEL
EXT
EXTERIOR
STRUCT
STRUCTURAL
3.3. OUTSIDE CORNER
FC
FIBER CEMENT
TB
TOP OF BEAM
3.4. INSIDE CORNER
FD
FLOOR DRAIN
TC
TOP OF CURB
3.5. THROUGH WALL FLASHING
FDN
FOUNDATION
TD
TRENCH DRAIN
3.6. WINDOW TRIM
FF
FINISHED FLOOR
TF
TOP OF FOOTING
3.7. DOOR TRIM
FG
FIBERGLASS
TJ
TOP OF JOIST
3.8. TYPICAL JOINT TRIM
FM
FACTORY MUTUAL
TOC
TOP OF CONCRETE
3.9. SOFFIT TRIM
FOC
FACE OF CONCRETE
TOP
TOP OF PARAPET
FOS
FACE OF STUD
TOS
TOP OF STEEL
3. 10. PENETRATION TRIM
�
FOOT OR FEET
U/
UNDER
FTG
FOOTING
VB
VAPOR BARRIER
4. PROVIDE ADDITIONAL VISUAL MOCK-UPS AS REQUIRED BY ARCHITECT FOR COLOR
GA
GAUGE
VENT
VENTILATION
AND AESTHETIC PURPOSES.
GALV
GALVANIZED
VERT
VERTICAL
GL
GLASS
WD
WOOD
GLB
GLUE -LAMINATED BEAM
WGL
WIRE GLASS
GLZ
GLAZING
WWM
WELDED WIRE MESH
GWB
GYPSUM WALL BOARD
WP
WATERPROOF
HB
HOSE BIB
�/RB
WEATHER RESISTIVE BARRIER
HC
HOLLOW CORE
HRW
HT
HOT RUBBER WATERPROOFING
HIGH TEMPERATURE
EXTERIOR JOINT SEALANTS
HVAC
HEATING, VENTILATION, AIR CONDITIONING
IN
INCHES
I .JOINT SEALANTS TO BE INSTALLED WHERE SHOWN ON DRAWINGS AND WHERE
INCL
INCLUDING
REQUIRED
INSUL
INSULATION
2. MOCK-UP TESTING TO BE PROVIDED FOR ALL SUBSTRATE CONDITIONS, TO VERIFY
THAT ADHESION IS OBTAINED AND TO DETERMINE NECESSARY PRIMERS. IT IS
RECOMMENDED THAT THE SEALANT PULL TESTS BE PERFORMED BY THE
MANUFACTURER OR AN AUTHORIZED REPRESENTATIVE.
3. SEALANT JOINT APPLICATIONS WITH CLOSED -CELL BACKER RODS (WHERE
MOVEMENT IS ANTICIPATED) ARE TO BE INSTALLED WITH THE FOLLOWING
GUIDELINES FOR PROPER GEOMETRY OF SEALANT JOINT:
UNLESS OTHERWISE NOTED, WIDTH -MINIMUM 3/8", MAXIMUM I/2"
DEPTH TO WIDTH RATIO -NOT LESS THAN 2: I (WIDTH :DEPTH) OR AS
RECOMMENDED BY MFR
4. SEALANT IS TO BE INSTALLED CONTINUOUSLY AT INTERIOR PERIMETERS OF
WINDOWS AND DOORS FROM FRAME TO AIR BARRIER ELEMENT CONTINUITY OF AIR
BARRIER AS DEPICTED ON THE ENCLOSURE DRAWINGS.
5. THE FOLLOWING SEALANT SCHEDULE PROVIDES RECOMMENDED SEALANT TYPES
BASED ON DIFFERENT SUBSTRATE CONDITIONS, UNLESS OTHERWISE NOTED IN
SPECIFICATIONS. THIS LIST IS NOT EXHAUSTIVE AND SHOULD BE USED AS A GUIDE.
FINAL SEALANT SELECTIONS AND PRIMERS TO BE DETERMINED IN CONJUNCTION
WITH THE MANUFACTURER DURING MOCK-UP TESTING.
SUBSTRATE I
SUBSTRATE 2
SEALANT
CONCRETE
CONCRETE OR MASONRY
DOW CORNING 790
MASONRY
CONCRETE OR MASONRY
DOW CORNING 790
PAINTED METAL
PAINTED METAL
DOW CORNING 795
PVC
PAINTED METAL
DOW CORNING 795
TYVEK COMMERCIAL WRAP
OTHER
DOW CORNING 758
FIBER -CEMENT
OTHER
BASF MASTERSEAL NP 150
SYMBOLS
DRAIN MAT
GATT INSULATION
_ WRB / AI R BARRI ER
SAM
SBS
HOT RUBBER WP
— LIQUID -APPLIED MEMB.
-------- ELASTOMERIC COATING
— � — � — BENTONITE WP
VAPOR BARRIER
CONCRETE
STEEL
MASONRY UNIT ' �'
PLYWOOD SHEATHING
GYPSUM WALL BOARD /SHEATHING
FIBER CEMENT BOARD
PPROVED
I I INSECT SCREEN
�J
� GASKET SEALANT
�«« BACKER ROD � SEALANT
XX DETAIL DWG NUMBER
A-x.xx PAGE NUMBER
x.x ASSEMBLY NUMBER
SPRAY FOAM INSULATION
SEMI -RIGID MINERAL WOOL INSULATION
RIGID INSULATION
MORTAR NET
DRAIN ROCK
PRESSURE TREATED WOOD
PLANS MUST BE
ON JOB SITE
PROJECT INFORMATION:
PROJECT NAME
SOUND VIEW PLAZA
PROJECT ADDRESS:
130 2ND AVENUE SOUTH, EDMONDS, WA 98020
CONTACT INFORMATION
PROJECT MANAGER:
CAELUM ROBERTS, ASSOC. AIA LEED AP
CAELUMR@TEAM4EA.COM
PRINCIPAL IN CHARGE:
BRAD CARMICHAEL, PE, ASSOC. AIA , CPHC®
BRADC@TEAM4EA.COM
SKEET INDEX:
SHEET
DRAWING TITLE
BE 100
NOTES AND INDEX
BE I 0 I
SITE PLAN
BE200
LEVEL I FLOOR PLAN
BE201
LEVEL 2 FLOOR PLAN
BE202
PENTHOUSE � MAIN ROOF PLAN
BE203
PENTHOUSE ROOF PLAN
BE300
SOUTH AND EAST ELEVATIONS
BE301
NORTH AND WEST ELEVATIONS
BE400
WINDOW � DOOR SCHEDULE
BE500
WALL � WINDOW DETAILS
BE501
ROOF DETAILS
APPROVED BY PLANNING
�� � ����
Oct 20 2023
pproval on pertains to the re -roof and
►ctension of the parapet only.
City Of Edmonds
Building Department
/ork RE -ROOF
ddress 130 2ND AVE S
owner SOUNDVIEW PLAZA
pproved Date rj
uilding Official : E1�1.(i
�--�--�--�--�--�-� BLD2023-0991
rmit Number
ALL WORK SUBJECT
TO FIELD
CODE COMPLIANCE
Building Science
12721 30th Ave. NE, 2nd Flrrr, Seattle, WA
9>�125
206.728.2358 I team4ea.crm
9�805
REG�STE�Eb
AR E
FREY 1. PE RT
STATE OF W HiNGTON
RESUB
Sep 14 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
PERMIT SET
Nn.
ISSUE / REVISION TITLE
Date
1
ISSUED FAR PERMIT
09-13-2023
ALL RIGHTS RESERVED, PROPERTY OF 4EA
BUILDING SCIENCE, USE OR REPRODUCTION
PROHIBITED WITHOUT PRIOR WRITTEN
PERMISSION.
SOUND VIEW PLAZA REPAIRS
NOTES AND INDEX
DATE: 09-13-2023
DRAWING Nn:
g E 100
SCALES
DESIGNEDs
CR
DRAWNs CR
PRQJECT NPs 1
S E230 14
REVIEWED.
R1
SLOPE
I :48 MIN.
R1� o--
NEW FASCIA
MOUNTED
RAILING
NEW PMMA
NEW 2X STRUCTURE MEMBRANE
0/ RAILING
KNIFEPLATE
� NEW MULTI PLY SBS
ROOF MEMBRANE
SLOPE
I :48 MIN.
R1
�� �� �� �� �� �� �� �� �� �� �� C
� � � �
� � � �
8 ROOF STEP
NEW MULTI PLY SBS
ROOF MEMBRANE
6 � EACH MAIN DRAIN � OVERFLOW LOCATION TO
BE BUMPED
�'
NEW DECKING
NEW PMMA
SBS ROOF
I/4" SLOPE MIN.
�------ I
I I
I
I I
I
I �_J
8" MIN
�I'I'�'lllll
������������� I�I I ����
6 ROOF PARAPET
NEW 22 GA PREFINSHED
PARAPET COPING
NEW HT SAM -
EXTEND 0/ ROOFING
TERMINATIONS AND
LAP OVER WRB AT EXTERIOR
NEW SELF ADHERED WRB (AB)
NEW FC PANEL TRIM
EXISTING FRAMING
5 ROOF -NIGH PARAPET SUPPORT
NEW SEALANT
NEW PMMA MEMBRANE AT DRAIN SUMP, TYP.
ORT
JLLY-
gSHING
SLOPE
I :48 MIN.
�"�" '"' "�NETRATION CAP
AINUM PIPE PENETRATION
ZE TO PIPE � SET INTO
OP TARGET BASE PLY MEMB.
�-APPLIED FULLY -REINFORCED
THING
1FR MASTIC @END OF FIELD
SET MEMBRANES
)RCING TARGET PLY
STACK FLASHING FLANGE
PLY SBS
1BRANE
3 PLUMBING STACK VENT, TYP.
v I
�I I
_ _
� \I
I1=_ I
_--
��
II
___ ��
�
I1- I
I1- I
K�-=== ��
� _ �
-
- _ _ �.., �
I�- I EXIST. STUCCO CLADDING,
� _ — y
I - CUT ABOVE ROOF MEMBRANE
I ,.� _ _
�
'
EXIST. WRB LAP � SEAL 0/ SBS
�_
— _ _ � I
� BASE PLY SHEET
I
I �
NEW MTL FLASHING, ATTACHMENT
_
— _
— — �I
TUCKED BEHIND STUCCO CLADDING
I
�..� —_
j NEW MULTI PLY SBS
I
ROOF MEMBRANE
= _ _ `�I
V
��
_ z �
�
I
_
���-�
I
/f
r
r � _ �
j R1
yy /I
I��—_-- �
\���
I
I
I_i � �_I
�---------------------
2 ROOF -BASE OF WALL
NEW��� ��� ��� ��� ��� �� �� ��� ��� ��� ��� ��� �� �� ��� ��� ��� ���� ��� �� �� ��� ����� ����
EXIST
� /I - - I� / ;��� � /I -_ _- I� / R1 MULTIPLE PLY (SBS)
\/ \/ \/ \/ • NEW 2 PLY SBS ROOF MEMBRANE
/\ �\ / \ I /\ �\ / /� /\
/ � I �/ �/ I / � � I / � I � OOF SHEATHING • NEW COVER BOARD
• NEW TAPERED RIGID INSULATION FOR SLOPE
• NEW 6" RIGID INSULATION
N TE: • EXIST PLYWOOD EXTERIOR ROOF SHEATHING
PROVIDE LOW PROFILE DRAINS � / \ _/ \ / \ / MAIN ROOF � OVERFLOW
STRAINERS AT DRAIN LOCATIONS DRAIN, OVERFLOW DRAIN
UNDER ELEVATED DECKS � TO HAVE "RING. DO NOT REPAIR AS NECESSARY
• EXIST STRUCTURE
� TIE OVERFLOW DRAINS . EXIST GATT INSULATION
INSULATION IN ROOF CAVITY � INTO MAIN DRAIN • EXIST INTERIOR GYPSUM CEILING
NOT SHOWN FOR CLARITY � PLUMBING
4 f�00 F D f�Al N
� f�00� ASSEMBLY
NOTE:
BULLETS ARE TOP TO BOTTOM
STAGGER JOINTS OF INSULATION
WHERE 2 OR MORE LAYERS ARE
USED.
Building Science
12721 30th Ave. NE, 2nd Flrrr, Seattle, WA
9�125
206.728.2358 I team4ea.crm
9�805
REG�STE�Eb
AR E
FREY 1. PE RT
STATE OF W HiNGTON
RESUB
Sep 14 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
PERMIT SET
Nn.
ISSUE / REVISION TITLE
Date
1
ISSUED FAR PERMIT
09-13-2023
ALL RIGHTS RESERVED, PROPERTY OF 4EA
BUILDING SCIENCE, USE OR REPRODUCTION
PROHIBITED WITHOUT PRIOR WRITTEN
PERMISSION.
SOUND VIEW PLAZA REPAIRS
ROOF DETAILS
DATE: 09-13-2023
DRAWING Nn:
g E501
SCALES
DESIGNEDs
CR
DRAWNa CR
PRQJECT NPs 1
S E230 14
REVIEWED.