APPROVED BLD PLN BLD2023-0386+PLANS+3.30.2023_11.03.18_AM+34533237 6 l�7 4 3 �a F 3 A SCOPE OF WORK: REMOVE OUTDATED 20 TON SPLIT SYSTEM HVAC. 20 TON UNIT IN BASEMENT WILL NEED TO BE BROKEN DOWN AND REMOVED TO GET OUT. AND 940LB CONDENSER ON ROOF WILL BE REPLACED WITH (2) NEW CONDENSERS. NEW CONDENSERS WILL BE MOVED BACK FROM THE EDGE OF THE ROOF AND A SUPPORT STRUCTURE COMPLETE WITH BEAUTY /SOUND /SAFETY FENCE PUT IN PLACE TO PREVENT SERVICING TECHS FROM REACHING EDGE OF ROOF. SUPPORT STRUCTURE WILL ALSO DISPERSE THE WEIGHT OF CONDENSERS AND STRUCTURE OVER A LARGER AREA OF THE ROOF. NEW UNITS WILL BE (2) 10 TON AIR HANDLERS TETHERED BY EMS AND SET UP TO RAMP UP VFD DRIVEN MOTORS SIMULTANEOUSLY. THE DUCTWORK WILL HAVE NEWLY INSTALLED DAMPERS ON SUPPLY BRANCHES AS WELL AS FRESH AIR INTAKE AND RETURN AIR DUCTS. SYSTEM HAS AN NEWER 100,000 BTU DUCT FURNACE THAT WILL BE USED FOR MAKE UP HEATING WHEN REQUIRED. THE NEW CONDENSERS ON THE ROOF ARE 375LBS AND WILL BE TIED TO THE SUPPORT STRUCTURE FOREMENTIONED AND ALL WILL BE TI-' -� STRUCTURE. ALL WORK TO BE DONE IN ACCORDANCE WITH EPA, WSE� MANUFACTURE SPECS. ,..,�� . - .. � r r - - - - r r r � }�.r�T � ��� ��� ' � � � ' ,• 1 T . � � _ — , � � � ■ .� � � } r - '�� �� �- �. :� �� * }� �i - APPROVED BY PLANNING ! �� Apr 18 2023 7 ARE/ OCC ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE 6 �� M ��r��f�r� � � ��� � l.L� L� �� r� 1PPROVED PLANS MUST BE 5 ON JOB SITE 4 Edmonds Hobby Shap� ROOF TOP RCU BEING REPLACED AND MOVED BACK TOWRDS CENTER OF ROO F City Of Edmonds Building Department Work RTU Address 140 4TH AVE S Owner ' - US BANK Approved Date 041'f 11�023 Building Official Er%Ci Permit Number BLD2023-0386 3 :��' ai min �� r��� aaytgn S# y P O RECEIVED Apr 05 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SITE OVERVIEW (MONO) PRCONFIDEN1rIpL D UNLESS OTHERWISE SPECIFIED: NAME DATE SITE: US BANK 8302, 140 4TH AVE S DIMENSIONS ARE IN INCHES TOLERANCES: DRAWN BAP 22 OCT 2022 CHECKED THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF COOLSYS COMMERCIAL AND INDUSTRIAL SOLUTIONS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF COOLSYS COMMERCIAL AND INDUSTRIAL SOLUTIONS IS PROHIBITED. FRACTIONAL± 1/16" ANGULAR:± 1 DEG ONE PLACE DECIMAL ± b" TWO PLACE DECIMAL ± 1" �*� • • � COOLSYS COMMERCIAL AND INDUSTRIAL � Brian Pritchard (253)329-0512 • b rltchard@COOTS S com �'�"jOICJI l � 1524 45th ST E, STE 103 L+vv �J Sumner, WA 98390 • WWW.COOLSYS.COM � ��� � • � - A ENG APPR. PARCEL: 27032300404900 LEGAL: SEC 23 TWP 27 RGE 03 RT-68) BEG NW COR 4TH & DAYTON STS TH W 73FT TO TPB TH W 63FTTH N 120FTTHE 42FTTH S 18FT THE 21 FT TH S 102FT TO N LN DAYTON ST TPB TGW BEG NW COR 4TH 8 DAYTON STS TH N 120FTTH W 94FT TH S 18FT THE 21 FT TH S 102FT TO N LN DAYTON ST TH E 73FT TO POB INTERPRET GEOMETRIC TOLERANCING PER: CITY EDMONDS SIZE B DWG. NO. US BA N K 8302 D W GS REV A COUNTY SNOHOMISH DO NOT SCALE DRAWING SCALE: 1:20 SHEET 1 OF 6 2 1 SCOPE OF WORK BY PHILLIPS STRUCTURAL ENGINEERING, PLLC (PSE): 00 PSE HAS REVIEWED THE EXISTING CONDITIONS WHERE AN EXISTING HVAC UNIT IS BEING REMOVED AND REPLACED WITH (2) LIGHTER UNITS. ENGINEERING CALCULATIONS HAVE BEEN PERFORMED FOR GRAVITYAND LATERAL LOADS FROM THE PROPOSED HVAC UNITS PER THE 2018 INTERNATIONAL BUILDING CODE (IBC). w ALL FRAMING SHALL BE PER COMMON AND LOCAL STANDARDS. w WHILE MINOR PENETRATIONS OF THE ROOF WILL OCCUR, ALL WATERPROOFING SHALL BE THE RESPONSIBILITY OF OTHERS. 00 ALL TIMBERLOK, OLYLOG AND LEDGERLOK FASTENERS INDICATED SHALL BE PER OMG, INC. PER ICC REPORT ESR-1078. 00 PSE HAS NOT PERFORMED AN ALL INCLUSIVE REVIEW/DESIGN OF THE EXISTING STRUCTURE WHICH REMAINS THE RESPONSIBILITY OF OTHERS. PLAN VERACITY: Every attempt has been made to insure the accuracy of these engineered documents, site conditions, product availability, etc. All information listed above must be verified prior to construction and fabrication. Any changes or deficiencies on or to the plan must be transmitted to Phillips Structural Engineering, PLLC for written approval. LICENSE OF ENGINEERING DOCUMENTS: 1. Grant of License: Phillips Structural Engineering, PLLC grants the Licensee a nonexclusive Right of Use for the purpose of constructing a single structure (use) from this engineering package. Future uses of this drawing set are permitted when accompanied by an originally stamped "Site Specific Re -Use Letter" for each additional site and payment has been made to Phillips Structural Engineering, PLL 2. Ownership of Engineering Calculations and Drawings: Phillips Structural Engineering, PLLC shall retain "Title 17 USC Rights and Ownership" of the Copyright Law of The United States of America of these Engineering Documents and all subsequent copies of the engineering. The Licensee is not permitted unlimited reuse of these documents without prior consent. 3. Copy and Transfer Restrictions: Unauthorized copying of the Engineering documents is strictly forbidden. The Engineering is permitted to be used by the Licensee only, and may not be transferred to a 3rd party without prior written consent of Phillips Structural Engineering, PLLC. GENERAL NOTES: The Structure has been designed to resist code -required vertical and lateral forces after the construction of all structural elements have been completed. Stability of the structural elements prior to completion is the sole responsibility of the General Contractor. Builder is to verify all dimensions prior to starting work. All changes to structure must be reviewed and approved by Phillips Structural Engineering. All materials, methods, and workmanship shall be in accordance with the International Building Code (IBC) 2018 Edition. The Builder is responsible for using safe work practices and conforming to all safety ordinances. STANDARDS: All methods, materials and workmanship shall conform to the 2018 International Building Code (IBC) as amended and adopted by the local Building Official or applicable jurisdiction. DESIGN LOADS ROOF LOAD: SNOW 25 PSF, DEAD 15 PSF FLOOR LOADS: N/A WIND SPEED: Vs 3-Sec= 97 MPH , Iw=1.0, EXPOSURE "B" SEISMIC: Ss = 1.29; SDC = N/A; Rp = 6 SOILS: Allowable soil bearing pressure of 1500 PSF is assumed per E.O.R. drawings. It is the contractors responsibility to verify that all footings bear on firm, undisturbed earth or compacted "Structural Backfill" that meet or exceed allowable soil bearing pressure. WOOD FRAMING AND CARPENTRY: General Requirements: Provide minimum nailing per 2018 IBC table 2304.10.1 or as indicated on the drawings. Do not notch or drill structural members, except as permitted by the engineer. Framing Connectors: Only ICC approved connectors shall be used in framing applications as manufactured by Simpson Strong -Tie or equivalent. Provide maximum size and quantity of fasteners shown in the manufacturer's catalog U.N.O. Fasteners: Bolts shall be per ASTM A-307 with standard cut washers or malleable iron washers. Post -installed anchors require engineering confirmation prior to installation. Contact Phillips Structural Engineering for possible alternatives. Nails shall be common wire nails or equivalent pneumatically drive nails (P-nails), American or Canadian manufacturer only as indicated below. P-nails shall be installed per the manufacturer's quidelines. COMMON HIRE NAIL DIAMETER (INCHES) MINIMUM LENGTH (NCHES) Nµ APPLICATION 8d COMMON 0.131 VC SHEATHING 10d COMMON 0.148 2)4" SHEATHING N/A 0.131 3" FRAMING 12d COMMON 0.148 34" FRAMING 16d COMMON 0.162 3W FRAMING Studs: All studs shall be kiln dried (KD) or surface dried (SD). Each stud shall bear the stamp of the West Coast Lumber Inspection Bureau (WCLIB) or Western Wood Products Association (WWPA) showing grade mark or approved equal. All studs shall 2x minimum material and Hem -Fir meeting the following minimum strength properties: Fb= 675psi, Fv=150psi, E=1,200,000psi. Preservative Treatment (P.T.): All exposed framing including lumber, plywood and deck materials shall be pressure treated with 0.25#/cf pentachlorophenol per AWPA specification P-5 or other approved treatment. All cutting and boring after pressure treatment shall be cared for in accordance with AWPA specification M-4. Exposed framing includes, but is not limited to: 1. Joists, girders and subfloor that is closer than 18" to exposed ground in crawl spaces. 2. Wood framing (including sheathing) that rest on exterior foundation stem walls and is 8" or less from exposed earth. 3. Any other wood product in direct contact with concrete or masonry. Wood Connectors at P.T. Conditions: Metal connectors which are in contact with pressure treated wood shall be protected with on of the following: Simpson "ZMAX" G185 Galvanization, Triple Zinc Coated, hot Dipped Galvanized or other approved method. BLD2023-0386 RECEIVED Apr 05 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 3/30/2023 • - J LU w w J Q J u� D J C F- 0- m Z o F- LU J N to LU D- Z_ o = J � o J (D xd = Z 0 m w o a CD CV 0 U)00 . a) W Q Q 2 t/j Z Z C:)O W ULLI _ > fn Q = 0 Z YO Z J Co W CL CA Z) 8 7 6 5 � 4 3 2 1 F I E I D I CI B I AI ROOF TOP RCU BEING REPLACED AND MOVED BACK TOWRDS CENTER OF ROO F _ � r �� -� �_ �' � I r ■ ' i ' r ' _ � i F ` � � rn� � � _ � — F .� - - - � �� -_ ., � ,t � r• 1 I �� � IVE D Apr 05 2023 � CIYY OF EDMONDS I D LOPMENT SERVICES DEPARTMENT �� r +J ■ 1 ■ ' ROOF TOP RCU BEING REPLACED AND MOVED BACK TOWRDS CENTER OF ROOF �� �. i CRANE PACEMENT AND OPERATIONAL RADIUS 1 ,� �'� � � �' � ����, 1 — ' r T c r ' � ` r � ti � ■ s ' r, 7 6 5 4 3 SITE OVERVIEW (COLOR) D PRCONFIDEN UNLESS OTHERWISE SPECIFIED: NAME DATE SITE: US BANK 8302, 140 4TH AVE S �pL DIMENSIONS ARE IN INCHES TOLERANCES: DRAWN BAP 22 OCT 2022 CHECKED THE INFORMATION FRACTIONAL± 1/16" ANGULAR:± 1 DEG �*� • � � COOLSYS COMMERCIAL AND INDUSTRIAL ENG APPR. CONTAINED IN THIS ONE PLACE DECIMAL ± b" � Brian Pritchard (253)329-0512 A • DRAWING IS THE SOLE TWO PLACE DECIMAL ± 1" b rltchard@cools S com 1524 PARCEL: 27032300404900 PROPERTY OF �'�"jOICJI l � 45th ST E, STE 103 L+vv INTERPRET GEOMETRIC COOLSYS COMMERCIAL AND �J Sumner, WA 98390 • INDUSTRIAL SOLUTIONS. ANY TOLERANCING PER: LEGAL: � WWW.COOLSYS.COM ► � •�� REPRODUCTION IN PART OR SEC 23 TWP 27 RGE 03 RT-68) BEG NW � � i AS A WHOLE COR 4TH 8 DAYTON STS TH W 73FT TO TPBTH W 63FTTH N 120FTTH E42FTTH S CITY EDMONDS SIZE DWG. NO. REV WITHOUT THE WRITTEN 18FT THE 21 FT TH S 102FT TO N LN PERMISSION OF DAYTON ST TPB TGW BEG NW COR 4TH & DAYTON STS TH N 120FTTH W 94FT TH � U BA N K 8302 D W GS A COOLSYS COMMERCIAL AND COUNTY SNOHOMISH S 18FT THE 21FT TH S 102FT TO N LN V INDUSTRIAL SOLUTIONS IS DAYTON ST TH E 73FT TO POB DO NOT SCALE DRAWING SCALE: 1:20 SHEET 2 OF 6 PROHIBITED. 2 1 N 0 M 00 Z Q I I I Im ty Gl I� cn D I� � r I� m I� zCD I ci W W O N O N W 4 i 38'-0' CA V) H £ 3 ty d� m-i'--u pr C-)D DD Ll t:j0 V)�RJ — (� i{7 TI � v -- 00m y O ;az (n o�x .-. ,.� - 0% I. n a bd X a: Z�� O-9;aro -0 � I znx Z-t- mm0% Vi3�o �� EDGE OF BUILDING 1-0 o = -----------------J�X D------ — — — ---� D X cTI70-P, n TI �� bd�ft$C I Z3 Z Z LIDS •~-� I Z �� ofll W � r0, o r�°x rm� x � =DW V)�X I i V) . � (E)5/2"x22/2" GLB ro \ cn 00 0 to _ D C --I V) m X tyCD ty 3 r td (E)5/2"x22/2" GLB 7 _ x o 0% 7� N r 0 ow 1'-8" 2'-8' v � r� ox D X O o (E)5/2"x22/2" GLB U) z^ UJ O O TI (E)5/2"x22/2" GLB v N m D T <- ' 1' °°j 0 aK° O �Z0 m zm�x0 N - z O <<o N wm v I I I I I I 0 I (VERIFY) �Vo O` 61 I I I m 7K ., D I m x o v= I O ZM X �bd� Ito C 0'X� I d 3°' o 0r� I z r ��d I c� D 0 m Z n tJI D U 7� (n H D C� z v Gl I U I -171z-- - - ;;a c� z £ I SCOPE OF WORK BY PHILLIPS STRUCTURAL ENGINEERING, PLLC (PSE): 00 PSE HAS REVIEWED THE EXISTING CONDITIONS WHERE AN EXISTING HVAC UNIT IS BEING REMOVED AND REPLACED WITH (2) LIGHTER UNITS. ENGINEERING CALCULATIONS HAVE BEEN PERFORMED FOR GRAVITY AND LATERAL LOADS FROM THE PROPOSED HVAC UNITS PER THE 2018 INTERNATIONAL BUILDING CODE (IBC). 00 ALL FRAMING SHALL BE PER COMMON AND LOCAL STANDARDS. 00 WHILE MINOR PENETRATIONS OF THE ROOF WILL OCCUR, ALL WATERPROOFING SHALL BE THE RESPONSIBILITY OF OTHERS. 00 ALL TIMBERLOK, OLYLOG AND LEDGERLOK FASTENERS INDICATED SHALL BE PER OMG, INC. PER ICC REPORT ESR-1078. 00 PSE HAS NOT PERFORMED AN ALL INCLUSIVE REVIEW/DESIGN OF THE EXISTING STRUCTURE WHICH REMAINS THE RESPONSIBILITY OF OTHERS. DRAWN BY: TMP PLAN NAME: 140 4TH AVE. S. EDMONDS, WA 98020 PHILLIPS STRUCTURAL ENGINEERING, PLLC SHEET NO: S-1 DRAWING DATE: MAR30,2023 US BANK HVAC (EDMONDS) SCALE: N.T.S. (U.N.O.) P.O. BOX 108, MILTON, WA 98354 Phone (253) 344-1666 PSE NUMBER: PSE 23.044 m v ;u m W p v m w x p > c� Q = X D 90 L) p n O$ V 0 3� vli0 Ci�r t1 m— Z=Nw m 3 p Mm , D D Z 3 o` zid r42' m--, pr- x � r �� =C tJS 70bd f03 3 UI �� to D -� X D Dmx ZW X (7m DX 5 " 70�D � 41c:— r LE 3 N p � �j bd � D D � DE p x r-iQ HO�� Z CID� CS a0�\p p N N Z N x X X (Ts r D UU rID p w Z 70 D N -1:1 Z m p c� .D (7 D o r 90 £ Q p D \ Z D 'o D w MA V)z 3> CD Q m m D L7 r z D _ Z p D r VJ MA rD p Z r D r C m �{7 MA LVA w o 0 D w £ D m - \� rD TI R)n �W m 4 Z m r� �r Mp o- w tJ m ro p� r N r X w cn OD p 3'-6" �� <X 5'-0" MAX. SCOPE OF WORK BY PHILLIPS STRUCTURAL ENGINEERING, PLLC (PSE): 00 PSE HAS REVIEWED THE EXISTING CONDITIONS WHERE AN EXISTING HVAC UNIT IS S O BEING REMOVED AND REPLACED WITH (2) LIGHTER UNITS. ENGINEERING CALCULATIONS HAVE BEEN PERFORMED FOR GRAVITY AND LATERAL LOADS FROM THE PROPOSED HVAC UNITS PER THE 2018 INTERNATIONAL BUILDING CODE (IBC). W p 00 ALL FRAMING SHALL BE PER COMMON AND LOCAL STANDARDS. O " ' 1� N 00 WHILE MINOR PENETRATIONS OF THE ROOF WILL OCCUR, ALL WATERPROOFING SHALL r" t" CD BE THE RESPONSIBILITY OF OTHERS. N c,� o D 1 ' 1 ALL TIMBERLOK, OLYLOG AND LEDGERLOK FASTENERS INDICATED SHALL BE PER OMG, o < ,-Do INC. PER ICC REPORT ESR-1078. $ p m 00 PSE HAS NOT PERFORMED AN ALL INCLUSIVE REVIEW/DESIGN OF THE EXISTING 1P z o C7i STRUCTURE WHICH REMAINS THE RESPONSIBILITY OF OTHERS. zm0 N �xz O <<o N m wm v /1 1 /1 /1 /1 /1 _ /1 DRAWN BY: TMP PLAN NAME: 140 4TH AVE. S. PHILLIPS STRUCTURAL ENGINEERING, PLLC SHEET NO: DRAWING DATE: MAR30,2023 US BANK HVAC