Loading...
FIR2023-0093+Fire_Sprinkler_Equipment_Specification_Sheets+9.21.2023_1.39.08_PM+3797336Bulletin 074 January 2023 Rel ® F1 FR56 Series Quick Response Sprinklers K-factor 5.6 (80) Features • Standard coverage quick -response sprinklers • Upright, pendent, horizontal sidewall, and vertical sidewall deflectors • Low profile, compact design • Available in a wide variety of finishes Product Description Reliable Model F1 FR56 series sprinklers are quick -response standard spray automatic fire sprinklers utilizing a sensitive 3.0 mm glass bulb thermal element. Pendent and horizontal sidewall sprinklers may be installed exposed or surface mounted using escutcheons such as the Reliable Models B, C, or HB (reference Technical Bulletin 204). When installed recessed or concealed, the Model F1 FR56 series sprinklers are specifically listed with and may only be installed with listed Reliable escutcheons and cover plates. Refer to the technical information on the following pages for specific listings for recessed and concealed installations and refer to Figures 5 and 6 for dimensional information. When fitted with an approved water shield, these sprinklers may considered intermediate sprinklers for use in racks, below grated walkways, and other areas where intermediate level sprinklers are required. Table A provides a summary of the approvals and availability of specific Model F1 FIR series sprinkler configurations. Additional technical information for each sprinkler model is provided on the following pages. F1 FR Series Sprinkler Summary Model F1 FR56 Pendent Model F1 FR56 Upright Model F1 FR56 Vertical Sidewall Model F1 FR56 Horizontal Sidewall Note: Not all versions of the product are shown. Note: This bulletin may contain information on New and Legacy sprinklers that reflects a dimensional change only. Sprinkler Iden- tification Number (SIN), application, performance, and listings/ approval are not otherwise affected. Sprinklers with New frames will include the suffix "N" in the order. Sprinkler K-Factor gpm/psi'/2 Orientation Listings & Approvals Max. Working Pressure Sprinkler Identification Model (Ipm/bar'/2) psi (bar) Number (SIN) Upright cULus, FM, _PCB, VdS, 175 (12) RA1425 Intermediate Upright EC, WM, UKCA 250 (17) (cULus only) Pendent cULus, FM, LPCB, VdS, 175 (12) RA1414 EC, WM, UKCA 250 (17) (cULus only) Concealed Pendent cULus, VdS, EC, WK 175 (12) RA1414 F1 FR56 5.6(80) UKCA 250 (17) (cULus only) Horizontal Sidewall cULus, FIV 175 (12) 250 (17) (cULus only) RA1435 Vertical Sidewall cULus, FM, LPCB, 175 (12) RA1485 UKCA www.reliablesprinkler.com Technical Specifications Style: Upright, Intermediate Upright Threads: 1/2" NPT or ISO 7-R1/2 Nominal K-Factor: 5.6 (80 metric) Max. Working Pressure: 175 psi (12 bar) 250 psi (17 bar) (cULus only) Material Specifications Thermal Sensor: 3 mm Glass Bulb Sprinkler Frame: Brass Alloy Cap: Bronze Alloy Sealing Washer: Nickel with PTFE Load Screw: Copper Alloy Deflector: Brass Alloy Sprinkler Finishes (See Table B) Sensitivity Quick response Temperature Ratings 135°F (57°C) 155°F (68°C) 175°F (79°C) 200-F(93°C) 286°F (141°C) Guards & Shields (New Frames) Factory Water Shield (cULus, FM) F-1 Guard (cULus, FM) F-3 Guard with Shield (cULus, FM) Guards and Shields (Legacy Frames) Factory Water Shield C-1 Guard (FM) C-3 Guard with Shield (cULus, FM) D-1 Guard (cULus) D-3 Guard with Shield (cULus) Sprinkler Wrench Model W2 Model J (New frame with guard installed) Model JD (Legacy frame with guard installed) Listings and Approvals cULus Listed FM Approved -PCB VdS EC WM U KCA: 0832-U KCA-CPR-S5045 Model F1 FR56 Upright Sprinkler Components and Dimensions Deflector Glass Bull (3 mm Wrench FIB Threads -�d Screw F1FR-HALF-UPRAT Cap/Seal Assem 3 1/4" [83mm] Shown with Optional Factory Installed Water Shield ( Intermediate Upright) mm] Bulletin 074 Reliable Page 2 of 9 January 2023 www.reliablesprinkler.com Technical Specifications Style: Pendent Recessed Pendent Concealed Pendent Threads: 1/2" NPT or ISO 7-R1/2 Nominal K-Factor: 5.6 (80 metric) Max. Working Pressure: 175 psi (12 bar) 250 psi (17 bar) (cULus only) Material Specifications Thermal Sensor: 3 mm Glass Bulb Sprinkler Frame: Brass Alloy Cap: Bronze Alloy Sealing Washer: Nickel with PTFE Load Screw: Copper Alloy Deflector: Brass Alloy Sprinkler Finishes (See Table B) Sensitivity Quick response Temperature RatingsM 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F(93°C) 286°F (141°C) Recessed Escutcheons Model F1 (cULus, LPCB, VdS, CE, WM) Model F2 (cULus, FM, LPCB, VdS, CE, WM) Model FP (cULus, VdS, CE, WM) Cover Plate Model CCP (cULus, VdS(2), CE(2)) Guards & Shields (New Frames)(3) F-1 Guard (FM) F-5 Guard/Shield Kit (FM) F-7 Guard (cULus) F-8 Guard/Shield Kit (cULus) S-1 Shield (cULus, FM) Guards & Shields (Legacy Frames)(3) C-1 Guard (FM) C-5 Guard/Shield Kit (FM) D-1 Guard (cULus, FM) D-4 Guard/Shield Kit (FM) D-5 Guard/Shield Kit (cULus, FM) S-1 Shield (cULus, FM) Sprinkler Wrenches Model W2 (pendent) Model W4 (recessed or concealed) Model J (New frame with guard installed) Model JD (Legacy frame with guard installed) Listings and Approvals(') cULus Listed FM Approved LPCB VdS EC WM U KCA: 0832-U KCA-CPR-S 5045, 0831-UKCA-CPR-5072 (CCP) Notes: 1. 286°F (141 °C) temperature rated sprinkler not listed for recessed or concealed use. 2. VdS and CE approval for CCP concealed use is for 155°C (68°C) sprinkler ONLY. 3. Not suitable for recessed or concealed pendent installations. 4. When used surface mounted or exposed. See Recessed Escutcheon and Cover Plate section for specific approvals when installed recessed or concealed. Model F1 FR56 Pendent Sprinkler Components and Dimensions Threads Wrench Flat Glass Bulb (3 mm) Deflector F1FR_HALF _PEND_INT Cap/Seal Assembly — Screw Note: Please refer to Figure 8 for recessed and concealed installation. 3 1/4" [83mm] Sit 2 1/4" [57mm] 1" [25mm] Shown with Optional S-1 Water Shield (Ordered Separately) Bulletin 074 Reliable Page 3 of 9 January 2023 www.reliablesprinkler.com Technical Specifications Style: Horizontal Sidewall Recessed Horizontal Sidewall Threads: 1/2" NPT or ISO 7-R1/2 Nominal K-Factor: 5.6 (80 metric) Max. Working Pressure: 175 psi (12 bar) 250 psi (17 bar) (cULus only) Material Specifications Thermal Sensor: 3 mm Glass Bulb Sprinkler Frame: Brass Alloy Cap: Bronze Alloy Sealing Washer: Nickel with PTFE Load Screw: Copper Alloy Deflector: Brass Alloy Sprinkler Finishes (See Table B) Sensitivity Quick response Temperature Ratings ' 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F(93°C) 286°F (141°C) Recessed Escutcheons(2) Model F1 (cULus) Model F2 (cULus, FM) Model FP (cULus) Guards & Shields (New Frames)(3) F-4 Guard (FM) F-7 Guard (cULus) Guards & Shields (Legacy Frames)(') C1 Guard (FM) D1 Guard (cULus) Sprinkler Wrenches Model W2 (non -recessed) Model W4 (recessed) Model J (New frame with guard installed) Model JD (Legacy frame with guard installed) Listings and Approvals cULus Listed(4) FM Approved(') Notes: 1. 286°F (141 °C) temperature rated sprinkler not listed for recessed use. 2. FM approved recessed installation when used with Model F2 escutcheon ONLY. 3. Not suitable for recessed horizontal sidewall installations. 4. cULus Listed for Light and Ordinary Hazard when installed exposed or surface mounted installed recessed. 5. FM Approved for Light Hazard ONLY. Model F1 FR56 Horizontal Sidewall Sprinkler Components and Dimensions Deflector Glass Bul (3 mn Wrench R Note: Please refer to Figure 9 for recessed installation. iad Screw Frame F1FR_HALF_HSW Cap/Seal Assembly Threads Listed for Light Hazard ONLY when 1 1/8" [28mm] 2 3/4" [70mm] Bulletin 074 Reliable Page 4 of 9 January 2023 www.reliablesprinkler.com Technical Specifications Style: Upright Vertical Sidewall Pendent Vertical Sidewall Threads: 1/2" NPT or ISO 7-R1/2 Nominal K-Factor: 5.6 (80 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm Glass Bulb Sprinkler Frame: Brass Alloy Cap: Bronze Alloy Sealing Washer: Nickel with PTFE Load Screw: Copper Alloy Deflector: Brass Alloy Sprinkler Finishes (See Table B) Sensitivity Quick response Temperature Ratings 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F(93°C) 286°F(141°C) Guards & Shields (New Frames) F-2 Guard (FM) Guards & Shields (Legacy Frames) C1 Guard (FM) Sprinkler Wrenches Model W2 Model J (New frame with guard installed) Model JD (Legacy frame with guard installed) Listings and Approvals0) cULus Listed FM Approved LPCB(2) UKCA:0832-UKCA-CPR-S5045 Notes: 1. Listed and approved for Light Hazard ONLY. 2. -PCB approved for use in pendent position ONLY. Model F1 FR56 Vertical Sprinkler Components and Dimensions • - Deflector Glass Bulb (3 mm) Wrench Flat -- 1 Screw Frame F1FR_HALF_VSW Cap/Seal Assembly Threads 1 1/2" [38mm] 2 1/4" [57mm] RA CCU Bulletin 074 Reliable Page 5 of 9 January 2023 www.reliablesprinkler.com Recessed and Concealed Installation: Pendent Sprinklers 2-1/4" (57 mm) Dia. Hole in Ceiling 1-15/16" (49 mm) Dia. r I I 1-3/4" (44 mm) Minimum Recess 2-7/8" (72 mm) Dia. Models F1 & F1 FIR Pendent Sprinkler with Model F1 Recessed Escutcheon 3/4" (19mm) Nominal Adjustment 2-1/2" (64 mm) Dia. Hole in Ceiling 2-5/16" (59 mm) Dia. Vented Cup Reducing Fitting Face of Fitting to Face of Ceiling 1-1/8" (29 mm) at Max. Recess 3/8" (10 mm) at Min. Recess 1" (25 mm) Maximum Recess F1_REC PEND CCP Reducing Fitting Face of Fitting to Face of Ceiling 1-1/2" (38 mm) at Max. Recess 1" (25 mm) at Min. Recess (25 mm) 1/2" (12 mm) Minimum Recess 3-3/16" (78 mm) Dia. Maximum Recess Models F1 & F1 FIR Pendent Sprinkler with Model FP Recessed Escutcheon 1/2" (13mm) Nominal Adjustment Note: Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area. Ensure that the openings in the Model FP cup are unobstructed following installation. F1 Escutcheon (F2 Similar) 2-1/4" (57 mm) Dia. Hole in Ceiling 1-15/16" (49 mm) Dia. 1-3/4" (44 mm) Minimum Recess 2-7/8" (72 mm) Dia. Models F1 & F1 FIR Pendent Sprinkler with Model F2 Recessed Escutcheon 1/2" (13mm) Nominal Adjustment 2-1/2" (64 mm) Dia. Hole in Ceiling 2-5/16" (59 mm) Dia. Vented Cup 1" (25 mm) Minimum Recess Reducing Fitting Face of Fitting to Face of Ceiling 7/8" (22 mm) at Max. Recess 3/8" (10 mm) at Min. Recess 1-1/4" (32 mm) Maximum Recess Reducing Fitting Face of Fitting to Face of Ceiling 1-1/2" (38 mm) at Max. Recess 1" (25 mm) at Min. Recess 1/2" (12 mm) Maximum i3-5/16" (84 mm) Dia. Recess Model F1 FR56 CCP Conical Concealed Sprinkler 1/2" (13mm) Nominal Adjustment (Nominal Cover Plate Projection is 1" (25 mm)) Note: Model CCP concealed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area. Ensure that the openings in the Model CCP cup are unobstructed following installation. FP Escutcheon CCP Cover Plate Bulletin 074 Reliable Page 6 of 9 January 2023 www.reliablesprinkler.com Recessed Installation: Horizontal Sidewall Sprinklers 1/2" (12 mm) Reducing +/ 3/8" (10 mm) 1-3/8" (35 mm) Maximum Recess Fitting Face of fitting to face of wall 1 4,� _ 12" (102 mm - 305 mm) Deflector to ceiling 2-1/4" 1-15/16" 2-7/8" (57 mm) (49 mm) - - - - (73 mm) Dia. Hole Dia. Dia. 1 9/16" [14mm] F1 Recessed escutcheon 3/4" (19 mm) Adjustment E 2 1/8" (54 mm) Minimum Recess Model F1FR Horizontal Sidewall Sprinkler with Model F1 Recessed Escutcheon 3/4" (19mm) Nominal Adjustment HFR REC-HSW 3/8" (16 mm) ReducingN/ 1/4" (6 mm) FittingFace of fitting 1-5/8" (42 mm) Maximum Recess o face of wall 1 4'- _ 12" (102 mm - 305 mm) T9/16- Deflector to ceiling 2-1/4" 1-15/16" 2-7/8" (57 mm) (49 mm) - - - - - (73 mm) Dia. DIA. Dia. Hole14mm] F2 Recessed escutcheon 1/2" (13 mm) Adjustment 2-1/8" (54 mm) Minimum Recess Model F1 FR Horizontal Sidewall Sprinkler with Model F2 Recessed Escutcheon 1/2" (13mm) Nominal Adjustment 1-1/4" (32 mm) Reducing +/- 1/4" (6 mm) Fitting Face of fitting 7/8" (22 mm) Maximum Recess to face of wall 1 4" _ 12" (102 mm - 305 mm) Deflector to ceiling 2-5/8" 2-5/16" 3-1/4" (67 mm) (58 mm) - - - - (83 mm) Dia Dia. Dia. Hole. 9/16" [14mm] Vented Cup 1-3/8" (35 mm) Minimum Recess Model F1FR Horizontal Sidewall Sprinkler with Model FP Recessed Escutcheon 1/2" (13mm) Nominal Adjustment Note: Model FP recessed assemblies may not be used where the pressure in the space behind the sprinkler is positive with respect to the space in the protected area. Ensure that the openings in the Model FP cup are unobstructed following installation. Bulletin 074 Reliable Page 7 of 9 January 2023 www.reliablesprinkler.com Model W2 (upright, pendent) Model J (New frame with guard installed) Model JD (Legacy frame with guard installed, similar but with zinc finish) Finishes') Model W4 (recessed, concealed pendent) Standard Finishes Special Application Finishes Sprinkler F1, F2 and FPM Escutcheons CCP Cover Plate(2) Sprinkler F1, F2 and FP(2) Escutcheons CCP Cover Plate(2) Bronze Brass Chrome Electroless Nickel PTFE(3)(4) Bright Brass Bright Brass Chrome Chrome White Paint Bright Brass(-') Satin Chrome Satin Chrome White Polyester(3) White Polyester Satin Chrome Custom Color Polyester Custom Color Paint Custom Color Polyester(3) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Model FP escutcheons and Model CCP sprinklers utilize a galvanized steel cup with a finished trim ring or cover plate. 3. cULus Listed as corrosion resistant. 4. FM Approved as corrosion resistant. 5. For 200T (93°C) maximum temperature rated sprinklers only. Installation Model F1 FIR Series sprinklers must be installed in accordance with NFPA13 and the requirements of all applicable authorities having jurisdiction. Model F1 FIR Series sprinklers must be installed with the Reliable sprinkler installation wrench identified in this Bulletin. Any other wrench may damage the sprinkler. The Models W2 and W4 wrenches have two sets of jaws. Use the smallest set of jaws that fit on the wrench flats of the sprinkler. A leak tight sprinkler joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N•m). Do not tighten sprinklers over the maximum recommended installation torque. Exceeding the maximum recommended installation torque may cause leakage or impairment of the sprinkler. Glass bulb sprinklers have orange bulb protectors or protective caps to minimize bulb damage during shipping, handling and installation. Reliable sprinkler installation wrenches are designed to install sprinklers with bulb protectors in place. Remove the bulb protector at the time when the sprinkler system is placed in service for fire protection. Removal of the bulb protector before this time may leave the bulb vulnerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Maintenance Reliable Model F1 FIR series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25, as well as the requirements of any Authorities Having Jurisdiction. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause improper operation or non -operation. Do not clean sprinklers with soap and water, ammonia liquid or any other cleaning fluids. Remove dust by gentle vacuuming without touching the sprinkler. Replace any sprinkler which has been painted (other than factory applied). A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Failure to properly maintain sprinklers may result in inadvertent operation or non -operation during a fire event. Bulletin 074 Reliable Page 8 of 9 January 2023 www.reliablesprinkler.com Guarantee For the guarantee, terms, and conditions, visit www. reliablesprinkler.com. Ordering Information Specify the following when ordering: Model F1FR56 Deflector/Orientation • Upright • Intermediate Upright • Pendent • CCP Concealed Pendent • Horizontal Sidewall • Vertical Sidewall Temperature Rating • See sprinkler technical specifications Sprinkler Finish • See Table B Recessed EscutcheonO)(2) • F1 • F2 • FP Escutcheon Finish • See Table B CCP Cover Plate Temperature Rating • 135°F (57°C) [For use with 135°F (57°C) and 155°F (68°C) sprinklers.] • 165°F (74°C) [For use with 175°F (79°C) and 200oF (93°C) sprinklers.] CCP Cover Plate Finish • See Table B Sprinkler Wrench • Model W2 • Model W4 (recessed, concealed) • Model J (New frame with guard installed) • Model JD (Legacy frame with guard installed) Notes: 1. 286°F (141°C) sprinklers are not listed to be used recessed or concealed. 2. For FM, recessed sprinklers must use the Model F2 escutcheon. co N co 0 rn rn rn rn rn :1 Bulletin 074 Reliable Page 9 of 9 January 2023 www.reliablesprinkler.com