Window, Skylight and Door Schedule
Project Information Contact Information
Chris and Lisa Burdett Blake Fisher, AIA
332 Sunset Ave. N blake blakefisherarchitecture.com
Edmonds, WA 98020 206-852-5054
Ref. U-factor
Exempt Swinging Door (24 sq. ft. max.)
Exempt Glazed Fenestration (15 sq. ft. max.)
Vertical Fenestration (Windows and doors)
Component
Description Ref. U-factor
Western Windows Series 600 WindowWall
A
0.30
Western Windows Series 600 WindowWall
B
0.30
Western Windows Series 600 WindowWall
C
0.30
Western Windows Series 600 WindowWall
D
0.30
NOT USED
E
Mil and Ultra Series C650 PICT. series 3310
F
0.27
Mil and Ultra Series C650 PICT. series 3310
G
10.27
l and Ultra Series C650 SLIDER series 3110
H
0.27
l and Ultra Series C650 SLIDER series 3110
J
0.27
l and Ultra Series C650 SLIDER series 3110
K
0.27
Mil and Ultra Series C650 CASEMENT
L
0.27
Mil and Ultra Series C650 CASEMENT
M
0.27
Mil and Ultra Series C650 PICT. series 3310
N
0.27
Mil and Ultra Series C650 PICT. series 3310
P
10.27
l and Ultra Series C650 SLIDER series 3110
Q
0.27
l and Ultra Series C650 SLIDER series 3110
R
0.27
Mil and Ultra Series C650 PICT. series 3310
S
0.27
Mil and Ultra Series C650 PICT. series 3310
T
0.27
Mil and Ultra Series C650 PICT. series 3310
U
0.27
l and Ultra Series C650 SLIDER series 3110
V
0.27
Mil and Ultra Series C650 PICT. series 3310
W
10.27
l and Ultra Series C650 SLIDER series 3110
X
0.27
Mil and Ultra Series C650 PICT. series 3310
Y
0.27
Mil and Ultra Series C650 PICT. series 3310
Z
0.27
Mil and Ultra Series C650 PICT. series 3310
AA
0.27
Mil and Ultra Series C650 PICT. series 3310
BB
0.27
l and Ultra Series C650 SLIDER series 3110
CC
0.27
Western Windows Series 600 MultiSlide Dr.
1
0.33
NOT USED
2
0.33
Western Windows Series 600 MultiSlide Dr.
3
0.33
Custom Solid Core Pivot Entry Door
4
0.33
Western Windows Series 600 MultiSlide Dr.
5
0.33
e Door - Northwest Door Modern Class Line or
6
0.28
e Door - Northwest Door Modern Class Line or
7
0.28
Renlita Nufold Bi-fold door
8
0.28
Solid Core Entry Door
9
0.33
Glazed Patio Door
10
0.28
int. doors marked on door schedule
Width Height
Qt. Feet In" Feet I"°h Area UA
0.0 0.00
0.0 0.00
Width Height
Sum of Vertical Fenestration Area and UA
Vertical Fenestration Area Weighted U = UA/Area
12079.61 602.75
0.29
Overhead Glazing (Skylights)
Component Width Height
Description Ref. U-factor Qt. Feet In" Feet 1-1, Area UA
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
Sum of Overhead Glazing Area and UA 1 0.01 0.00
Overhead Glazing Area Weighted U = UA/Area 0.00
Total Sum of Fenestration Area and UA (for heating system sizing calculations) 2079.E 602.75
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
:UNI UNTA0•J
BY
CITY OF EDMONDS
simple I-leating system size: wasningion state
This heating system sizing calculator is based on the Prescriptive Requirements of the 2018 Washington State Energy Code (WSEC) and ACCA
Manuals J and S. This tool will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling loads.
Please complete the green drop -downs and boxes that are applicable to your project. As you make selections in the drop -downs for each section, some
values will be calculated for you. If you do not see the selection you need in the drop -down options, please contact the WSU Energy Program at
energycode@energy.wsu.edu or (360) 956-2042 for assistance.
Project Information Contact Information
Chris and Lisa Burdett Blake Fisher, AIA
332 Sunset Ave. N blake@blakefisherarchitecture.com
Edmonds, WA 98020 206.852.5054 AM
Heating System Type: O All Other systems Ce Heat Pump
To see detailed instructions for each section, place your cursor on the word "Instructions"
Design Temperature
Instructions Design Temperature Difference (AT)
Edmonds A AT = Indoor (70 degrees) - Outdoor Design Temp
Area of Building
Conditioned Floor Area
Instructions Conditioned Floor Area (sq ft)
6,223
Average Ceiling Height
Conditioned Volume
Instructions Average Ceiling Height (ft)
10.01
62,230
Glazing and Doors
U-Factor
X Area =
UA
Instructions
u-o.zB
.
0.280
2,079
582.12
Skylights
U-Factor
X Area =
UA
Instructions
0.50
F—E-1
---
Insulation
Attic
U-Factor
X Area =
UA
Instructions Select R-Value
No Selection
F_ 0 1
---
Single Rafter or Joist Vaulted Ceilings
U-Factor
X Area
UA
Instructions R-38 Vented
W
0.027
3,485
94.10
Above Grade Walls (see Figure i)
U-Factor
X Area
UA
Instructions
R-21 Intermediate
0.056
5,409
302.90
Floors
U-Factor
X Area
UA
Instructions
�1
0.029
574
16.65
Below Grade Walls (see Figure i)
U-Factor
X Area
UA
Instructions
R-21 Interior
ri
0.042
Slab Below Grade (see Figure 1)
F-Factor
X Length
UA
Instructions in
No Slab Below Grade
�
0.303
�
---
this project.
Slab on Grade (see Figure 1)
F-Factor
X Length
UA
Instructions R-10 Fully Insulated
0.360
3,695
1330.20
Location of Ducts
Instructions
Duct Leakage Coefficient
Conditioned Space
1.00
Sum
of UA
2325.97
Figure 1.
Above Grade
46
Envelope Heat Load 106,994
Btu / Hour
Sum of UA x AT
Air Leakage Heat Load 30,916
Btu / Hour
Volume x 0.6 x AT x 0.018
Building Design Heat Load 137,910
Btu/Hour
Air leakage + envelope heat loss
Building and Duct Heat Load 137,910
Btu/Hour
Ducts in unconditioned space: sum of building heat loss x 1.10
Ducts in conditioned space: sum of building heat loss x 1
Maximum Heat Equipment Output 172,388
Btu / Hour
Building and duct heat loss x 1.40 for forced air furnace
Building and duct heat loss x 1.25 for heat DumD
(07101113)