REVIEWED RESUB1 DEF SUB1 BLD2021-1482+Structural_Plan+8.19.2022_5.49.51_PM+3062918SHEARWALL SCHEDULE SW EXP Notes apply as called out in table below. 1 See detail SWB. 4 See detail SWR. Letter designations a, b, & c refer to specific conditions. 5 See detail SWB. 6 Abutting panel edges require a 2-2x (lamination connection same as WALL BASE PLATE), 3x, or greater stud. 7 See detail DSW. 8 The plate washer shall extend to within 1/2" of the edge of the bottom plate that receives the sheathing or rim. At double -sided shearwalls, stagger on both plate edges. SHEAR FLOW CONNECTIONS / SPACING S' SILL -TO - ROOF -TO - WALL BASE PLATE CALL FOUNDATION 1 WALL 4 5 OUT HILTI X-CP 72 P8 S23 #A35 @ *LS50 @ 16d @ 4"oc A @ 8"oc 16"oc 24"oc 4b HILTI X-CP 72 P8 S23 #A35 @ *LS50 @ 16d @ 3"oc B @ 6"oc 8 16"oc 16"oc 4b HILTI X-CP 72 P8 S23 #A35 @ #LS50 @ 2-16d @ 3"oc to 4x @ 3"oc 8 8"oc 8"oc 4c rim/blkg HILTI X-CP 72 P8 S23 #A35 @ *LS50 @ 2-16d @ 2"oc to 4x D @ 2"oc 8 6"oc 8"oc 4c rim/blkg HOLDOWN SCHEDULE fV WALL SHEATHING CALL OUT SHEATHING THICKNESS EDGE NAILS 6 15/32" 10d @ 6"oc 4 15/32" 10d @ 4"oc 3 15/32" 6 10d @ Y oc 2 15/32" 6 10d @ 2"oc 22 15/32" both sides 6, 7 10d @ 2"oc 1 Deepen the foundation as needed to provide the required holdown embedment into the foundation wall. See Detail MHE 2 Fasten to the end framing members of the shearwall, u.n.o. 3 FOUNDATION ANCHOR may be extended with threaded rod and coupler as required. 4 Provide the minimum embedment and edge distances specified by the manufacturer. 5 Attach to (2) 2x studs minimum (lamination connection same as WALL BASE PLATE; stagger nails), u.n.o. 6 See detail HDNfor installation. HOLDOWN / STRAP FOUNDATION 1, 2, 4, 6 FASTENERS 5 ANCHOR 1, 3, 4, 6 COMMENTS :#HTT5KT 26 - *SD #10x21/2 #SB5/8"x24 MSTC40 36-16d sinker N/A equal number of nails to both connected elements #MSTC66 68-16d sinker N/A equal number of nails to both connected elements TESTS AND INSPECTIONS INSPECTIONS PER IBC 110: Foundations, footings, underslab systems and framing are subject to inspection by the building official in accordance with IBC 110.3 the contractor shall coordinate all required inspections with the building official. In addition to inspections required by IBC 110, special inspections shall be done in accordance with the "statement of special inspections" per sections 1704 and 1705. SPECIAL INSPECTORS: Special inspectors shall be employed by the owner to provide special inspections for the project. A special inspector shall be a qualified person who works for an approved agency and demonstrates competence, to the satisfaction of the building official. The special inspector shall keep records of inspections and furnish them to the building official and the engineer of record on a regular basis. A final report documenting required special inspections and the correction of any discrepancies shall be provided prior to the completion of building finishes. Where fabrication of structural components and assemblies is being performed on the premises of a fa shop, special inspection of the fabricated items shall be required except where the fabricator is regis a roved to do such work without special inspection in accordance with IBC section 1704.2.5. Perio s ectio _ , pp Pe Pe P The following documentation shall be available o allows inspection at intervals necessary to confirm that work requiring special inspection i pl e with site for the building inspector: requirements. Continuous special inspection requires that the inspector be on site at that w requiring special inspection is performed. ! ❑ COE APPROVED ARCHITECTURAL PLAN SET Statement of special inspections per IBC sections 1704 and 1705: ■ Special inspections are required by sections 1704 and 1705 for the items summarized in th cial inspection COE APPROVED STRUCTURAL PLAN SET schedule located on this sheet: COE REVIEWED CALCULATION PACKET ENERGY CREDIT WORKSHEET SITE PLAN CIVIL PLAN ■ Original set of plans RX X❑ additional structral plans dated Aug. 22, 2022 ■ CITY OF EDMONDS BUILDING DEPARTMENT 2021 REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION W. W OfILCLIL BUILDING OFFICIAL Aug 30 2022 APPROVED DATE I ■ ■ I I Please see sheets S2.1 and S3.1. APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE Special Inspections, Testing & Structural Observation Schedule INSPECTION ITEMS CONTINUOUS PERIODIC TESTING Cdncrete Construction (IBC 1705.3� Cdncrete strength Reinforcing placement X Anchor bolts & holdowns X Embedded items X Preparation of test specimens X X Concrete placement X X Steel Construction (IBC 1705.2 & AISC 360) Fabrication X Erection X High -Strength Bolts (IBC 1704.3.3) X Welding (IBC 1705.2, AISC 360, & AWS D1.1) Single -pass fillet < 5/16" X Welded headed studs X Stair & railing X Light gage metal X Embedded plate X Anchoring Systems (IBC 1705.3) Powder -actuated fasteners X Wood Construction (IBC 1705.51 Sill plate anchor bolts X Floor diaphragm nailing X Shearwall nailing X Drag strut installation X Holdown installation X Structural Observation (IBC 1704.61 Concrete construction X Wood construction X INSPECTION SCHEDULE NOTES: "i. Items marked with an "x" shall be inspected in accordance with IBC 1704 by a certified special inspector from an agency approved by the jurisdiction. F2. Special inspection shall not be required for work done in an approved farricator's shop per IBC1704.2.5. verify approval with jurisdiction prior to fabrication. `3. Continuous special inspection requires the inspector shall be on site at all times that work requiring special inspection is performed. periodic special inspection shall allow inspection at the intervals necessary to confirm that work requiring special inspection is in compliance with the requirements. F4. All welds shall be visually inspected. '5. All complete penetration welds shall be tested ultrasonically. '6. Periodic special inspection shall be allowed. "7. All complete penetration welds shall be tested ultrasonically. STRUCTURAL STEEL NOTES STRUCi RAL STEEL shall meet the following minimum properties: Section Grade F ksi Fu ksi E x 106 (psi) W-Shapes ASTM A992 50 65 29 L-Shapes ASTM A36 36 58 29 HSS Shapes ASTM A500 46 58 29 C-Shapes ASTM A36 36 58 29 Plates ASTM A36 36 58 29 Bolts ASTM A325 Anchor Bolts ASTM A307 All welding shall conform to the latest edition of the A.W.S. D1.1 "Structural Welding Code". All welds shall be 3/16" minimum u.n.o. Welding electrodes shall be E70XX low hydrogen electrodes for maual shielded metal -arc welding or equal electrode for other welding processes. Welded joints shall conform to A.W.S. prequalified joint details for welded construction. All welding shall be performed by W.A.B.O. certified welders. Fabricators of steel items shall be approved per section 1704.2.2 of the CODE. All structural steel not embedded in concrete or masonry shall receive one coat of an approved primer after fabrication and one finish coat after erection. Field burning of holes is not allowed without approval and/or inspection. Provide washers on all bolted connections. Structural bolts shall be A325-X Typical U.N.O. REFERENCE STA NDA RDS: Steel construction shall conform to the AISC "specification for the design, fabrication and erection of structural CONCRETE CONCRETE REQUIREMENTS: Location Strength Max W/C Ratio Footings 2500 psi @ 28 days 0.55 Isolated Footings 2500 psi @ 28 days 0.55 Continuous Footings 2500 psi @ 28 days 0.55 Slabs -on -grade 2500 psi @ 28 days 0.55 Walls 3500 psi @ 28 days 0.45 AIR CONTENT: Concrete exposed to weather shall contain 5% +/-1% entrained air. MD( DESIGN: Shall be based on field experience or trial mixtures in conformance with the specifications. Mix designs shall be submittd to the Building Official two weeks prior to ttheir first use. MATERIAL REQUIREMENTS: Cement: ASTM C150 Admixt Aggregates: ASTM C33 Water: PLACING REQUIREMENTS: PLACING: Place concrete as nearly as practi< the concrete shall not exceed 5 fe( DEBRIS: Remove all debris from forms prio CONSOLIDATION: Consolidate concrete by suitable rr corners of forms. CURING: Concrete shall be main a WEATHER CONDITI Adequate pr s s RCIIVG BARS: Us ormed bars conforming to ASTM A615, grade 60, except as noted on the drawings. WELDED WIRE FA BRIC: Smooth fabric shall conform to ASTM A185. All WWF shall be 6x6 W2.9xW2.9 U.N.O. Lap reinforcemnt 8" minimum FABRICATION AND PLACING REOL IREMENTS: BENDING: Bars shall be bent cold. Bars partially embedded in concrete shall not be field bent unless noted or shown otherwise or authorized by the engineer. PLA CINIG: Reinforcement shall be supported and tied to prevent displacement by construction loads or by placing of concrete. Maximum spacing of supports shall be T-6". CONCRETE COVER: Minimum concrete cover for reinf. Shall be as follows, unless noted otherwise: Concrete cast against earth 3" Concrete cast against forms and exposed to earth 2" WELDING: Do not weld reinforcing bars. WET SETTINGS: Reinforcement anchor bolts, or any embedded item within the concrete, may not be set into the concrete after it has been poured within the forms. LA P SPLICES: Provide the following lap lengths: #4 bars 24" #5 bars 30" SHOP DRAWING REVIEW Once the contractor has completed his review, the Engineer of Record (EOR) will review the submittal for general conformance with the design concept and the contract documents for the building and will stamp the submittal accordingly. Redmarks or comments shall not be construed as relieving the contractor from compliance with the project plans and specifications. The Engineer of Record will review shop drawings for design intent only. Verification of dimensions and quantities are the responsibility of the contractor. Components primarily designed by the Manufacturer shall be stamped by a licensed engineer. A cursory review for design loads used and their impact on the structure shall be performed. Shop drawings shall be reviewed and signed by the contractor prior to the Engineer's review. A copy shall be provided for the Engineers record as well as any plans required for signature. Shop drawings are an aid for field placement and are superseded by the structural drawings. It shall be the contractors responsibility to make certain all construction is in agreement with latest structural drawings. GENERAL STRUCTURAL NOTES CODE All conditions, materials and construction shall conform to the code specified in the DESIGN CRITERIA, or other codes required by the governing jurisdiction. PROTECTION Through maintenance and current best practices, provide a building envelope that will preserve the integrity of the structure throughout it's lifetime. INSPECTIONS Notify Building Department for inspections required by local jurisdiction. SOILS Bearing capacity of soil shall be per DESIGN CRITERIA or greater. Footing shall bear on solid undisturbed level soil devoid of any organic material and below indicated frost line. FOUNDATIONS AND RETAINING WALLS Extend footings to undisturbed bearing soil. Do not backfill until all slabs and/or horizontal diaphragms are constructed, otherwise provide temporary bracing to resist movement. There shall be no machine compaction on the retaining side of the structure for a distance equivalent to 2/3rds the wall height. SILL PLATES Use pressure treated 2x plates u.n.o. Embed anchor bolts at least 7" (expansion anchors 4"). Use 3"x3"x0.229" washers. There shall be a minimum of two bolts per piece spaced not more than 6 feet apart, with one bolt located not more than 12" or less than 4" from each end of each piece. CONCRETE Fc = 3000 psi minimum for environmental exposure (2500 psi used in structural design, or unless greater psi indicated on the plans). 5 1/2 sacks of cement per cubic yard of concrete and a maximum of 6 gallons of water per 94 lb sack of cement. Maximum slump is 4". Segregation of materials shall be prevented through proper handling and placement. REINFORCING STEEL #4 bars and larger shall be Grade 60 deformed bars, and #3 bars shall be Grade 40 (u.n.o.), in accordance with ASTM A-615. Lap splices 32 bar diameters u.n.o. Welded wire fabric shall conform to ASTM A-185 and shall be 6x6 -W 4. Lap one full mesh at splices. CLEAR COVER 3" clr when cast against Earth and 2" clr in all oth cations, u.n.o. See applicable detail(s): RI FOOTING DRAINAGE Footing drainage per Building Code se 5.4.2 & Residential Code section R405.1. WOOD FRAMING in contact with concrete aso or exposed to w r, shall be pressure treated. Numbers in parenthesis, IE (1-1), refer to cor on ngineeri calcu ations. CONNECTORS AND FASTENS ner lu ashers, and connectors in contact with pressure treated shal inc galvanized. EXCEPTION: P e ten ding nuts and washers, in SBX/DOT and zinc borate preservative ted woo an rior, environment shall be permitted. SOLIDSAWN L R shall the owing minimum grades (u.n.o.) conforming to "WWPA GRADING RLAdMOR WEST UMBE test edition: 1FX and wider DF#1 4X DF#2 and greater DF#2 x 8 and smaller DF#2 or 2x DF#2 ENGINEERED WOOD shall meet the following minimum properties: Callout E x 106 (psi) Fb(psi) Fc par (psi) Fc perp (psi) Fv(psi) LVL 2.0E 3100 3000 750 285 Engineered wood products shall be protected from moisture to preserve their structural integrity. Provide temporary bracing to avoid permanent deflections resulting from drying under construction dead loads. WALL FRAMING & BEARING Walls shall be 2x studs at 16"oc max with double 2x top plate, and 2x base plate (exterior walls shall be 2x6 u.n.o. & interior walls shall be 2x4 u.n.o.). Party walls shall be parallel walls with a 1" gap between. Each wall shall be framed with 2x4 studs at 16"oc max with double 2x top plate, and 2x base plate. Block all supports solid to the foundation. See applicable detail(s): BHS TPS BEAM PENETRATIONS Allowable beam penetrations shall be made in the middle third of the span and the middle third of the depth. Contact this office for any penetration outside the allowable area. See applicable detail(s): BP POF WOOD STRUCTURAL PANELS shall meet the performance standards of the "APA" DOC PS1 and PS2 for their intended application (group 5 species not allowed). SHEARWALLS are indicated on the plans with a bold dashed line and labeled SW. The following letter designation refers to the Shearwall Schedule's SHEAR FLOW CONNECTIONS / SPACING table, and the number designation refers to the WALL SHEATHING table. Multiple combinations of letter and number designations may be present. Wall Line numbers, shown inside triangles, refer to corresponding engineering calculations. Attach rated sheathing (indicated below) to 2x min STUDS spaced no more than 16"oc, u.n.o. See Shearwall Schedule for minimum thickness and fasteners (thickness at point of fastened edges governs shear values). All panel edges shall be blocked. Nail intermediate supports @ 12"oc. Do not penetrate nails past flush. Install squash blocks under the ends of all shearwalls where the framing below does not provide full bearing. Construct cripple walls same as the shearwall above, and gable -ends same as the shearwall below. Rated sheathing: 15/32" CIS rated with a 24/16 span rating. See applicable detail(s): SWE ROOF DIAPHRAGM Install either OSB or CD sheathing: 15/32 OSB rated sheathing with a 24/16 span rating; panel clips required when spacing is greater than 20" oc. Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half the long dimension. Nail all boundaries and supported edges with 8d @ 6"oc and interior supports with 8d @ 12"oc, blocking not required u.n.o. ROOFTOP DECK DIAPHRAGM Install minimum 23/32" rated Sturd-I-Floor T&G with a 24oc span rating Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half the long dimension. Glue and nail all boundaries and supported edges with 10d @ 6"oc and interior supports with 10d @ 12" oc, blocking not required u.n.o. COLLECTORS Diaphragms shall be nailed continuously to rims, drag struts, drag trusses and other collector elements at boundary spacing, u.n.o. See applicable detail(s): DTC CONNECTIONS and fasteners shall be per CODE Table 2304.10.1 u.n.o. The symbol, "*", indicates a hardware connector from the most current Simpson Strong -Tie Catalog. Hardware with equivilent or greater capacities from other manufacturers may be substituted, example you can use USP's Dual Specification Chart to make an equivilent or greater capacity selection. Install per the manufacturer instructions. Fasteners and hardware in contact with pressure treated wood shall be hot -dipped zinc -coated galvanized. P PP NAILS All nails shall be "Standard Common" size per the latest edition of the National Design Specification for Wood Construction (NDS) u.n.o. HOLDOWNS See the HOLDOWN SCHEDULE. See applicable detail(s): HDN HOC POST CAPS Provide a post cap on isolated columns that most nearly matches the actual member size(s) U.N.O. Each connection shall have a minimum of (3)10d to the post and (3)10d to the beam. HANGERS Model numbers will be specified on the plans for conditions that require more than minimum capacity, otherwise see CONNECTIONS. When a hanger is not specified on the plans, use any size specific model number that fits that member. Always use MAX NAILING. Hanger to match member size. Notching or shimming of beam not allowed unless specified. JOBSITE SAFETY Sound Structural Solutions Inc has not been retained or compensated to provide design and/or construction review services related to the contractor's safety precautions or to means, methods, techniques, sequences or procedures for the contractor to perform their work. The undertaking of periodic site visits by the ENGINEER shall not be construed as supervision of actual construction and not make him responsible for providing a safe place for the performance of work by the contractor, subcontractors, suppliers or their employees, or for access, visits, use work, travel, or occupancy by any person. OWNERSHIP OF DOCUMENTS These drawings and calculations are the intellectual property of Sound Structural Solutions Inc. These drawings may not be used in whole or in part by any person without permission of Sound Structural Solutions Inc. MISCELLANEOUS The contractor shall verify dimensions and conditions at job site. The contractor shall provide temporary bracing as required until all permanent connections and stiffenings have been installed. Do not scale drawings. Pre -fabricated items to be handled and installed per manufacturer's recommendations. PLAN INSTRUCTIONS READ THIS FIRST These plans are organized so that more detailed or specific information is found in the same way by following the direction shown below: GENERAL STRUCTURAL NOTES SCHEDULES, DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES for more specific information. SCHEDULES DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES and SCHEDULES for more specific information. DETAILS PLANS will often refer to GENERAL STRUCTURAL NOTES, SCHEDULES and DETAILS for more specific information. PLANS See the SYMBOL LEGEND as well as ABREVIATIONS AND ACRONYMS for other additional information used on the PLANS. The term, TYPICAL (or TYP), used with a detail callout or plan note, indicates that the information specified shall apply in all similar conditions. IF YOU HA VEA NY QUESTIONS OR CONCERNS CONTA CT US IMMEDIA TEL Y.l We can be reached immediately by phone: (425) 778-1023 For less pressing questions, email us: inbox@ssseng.com Please help us get to your plans by having this job number handy: s2105014 ABBREVIATIONS AND ACRONYMS ABV ABOVE E.S. EACH SIDE O.C. ON CENTER A. B. ANCHOR BOLT E.W. EACH WAY P.T. PRESSURE TREATED BLW BELOW EA EACH REINF REINFORCEMENT BILK BLOCK E.N. EDGE NAILING REQD REQUIRED BLKG BLOCKING EMBED EMBEDMENT SCHED SCHEDULE B.N. BOUNDARY NAILING EXIST EXISTING SIM SIMILAR BTM BOTTOM FDN FOUNDATION STD STANDARD BRG BEARING FLR FLOOR STRUCT STRUCTURAL BTWN BETWEEN FRMG FRAMING SW SHEARWALL CLR CLEAR FTG FOOTING THRU THROUGH CLTR COLLECTOR G.T. GIRDER TRUSS T.R. THREADED ROD CONIC CONCRETE GR GRADE TYP TYPICAL CONN CONNECTION HORIZ HORIZONTAL U.N.O. UNLESS NOTED CONT CONTINUOUS MAX MAXIMUM OTHERWISE CTR CENTER MFG MANUFACTURED VERT VERTICAL DBL DOUBLE MIN MINIMUM w/ WITH DET DETAIL o/ OVER w/o WITHOUT E.E. EACH END oc ON CENTER W.W.F. WELDED WIRE FABRIC DESIGN CRITERIA Governing Code 18 IBC Risk Category II Wind Design Data Basic Wind Speed (3 sec gust) mph 98 Surface Roughness B Wind Exposure Category D Earthquake Design Data Seismic Importance Factor, 1, 1.00 Site Classification D Short Period Acceleration, S, 1.288 1-Second Acceleration, S1 0.454 Seismic Design Category D Spectral Response Coefficient, SIDS 0.859 Spectral Response Coefficient, Sol 0.559 Gravity Load Data Internal Pressure Coefficient +/- 0.18 Topographic Factor, KA 1.00 Ground Elevation Factor, K, 1.00 Seismic Force Resisting System ITable 12.2-1: A-15 2016 Equiv. Lateral Force Procedure Response Modification Factor, R 5 Transverse 5 Longitudinal Seismic Response Coefficient, C, 0.132 Transverse 0.132 Longitudinal Seismic Base Shear, V 91795 Ibs Roofs: loads are psf Dead Live Snow Roof Decking4 -Pitches < 8:12 18 0 25 Rafters' -Pitches < 8:12 15 0 25 •OccupiableZ 20 60 25 Floors: loads are psf Dead Live Snow Decking3 65 40 0 Decks: loads are psf Dead Live Snow Decking3 65 60 25 Notes apply as called out in table above. 1 Rafters of sawn lumber or wood I -joists. 2 Roof has direct access and is intended to be used by occupants as living space. 3 Concrete composite steel decking. 4 Steel roof decking. Soil Data Allowable Soil Bearing 2000 psf Passive Earth Pressure 1225 pcf Active Soil Pressure 1 35 pcf Coefficient of Friction 10.40 At -Rest Soil Pressure 1 55 pcf Unit Weight of Soil 125 pcf Company: Cobalt Geosciences Report #: N/A Date: 5/27/21 WNG WARNING N.T.S. THIS IS INTENDED TO DRAW ATTENTION TO FREQUENTLY EXPERIENCED DIFFICULTIES IN CONSTRUCTION: • LONG LEAD ITEMS • DIFFICULT FIELD RETROFITS • LIMITED OPTIONS FOR RETROFITS WNG SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture ro t.n rV Q � O H 0 J p w t� (V J W z O V U C V) p z 1 w Lei U O N V) U0 O wAsy��c��9� a z ran l 2 00373 d� C'STERE-� �a S�ONALE� This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT bld2021-1482 ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 silo EXTENT OF SHEARWALL SWE SHEARWALL ELEVATION N.T.S. EXTENT OF SHEARWALL r rn ,,, .ram f TPS SWF SWR %.nlFFLL JI UU UnJL FLnIL 1OIf you can't lap the sheathing then you DIAPHRAGM PER must install the A35's as shown (Not Optional) STRUCT NOTES DIAPHRAGM PER STRUCT NOTES PROVIDE BLK'G @ 48"oc RAFTER #A35 PER SW SCHED GABLE RAFTER BLKG EDGE NAILS - O EDGE NAILS #H2.5 @ ALL ROOF MEMBERS # A35 PER SW SCHED SHEARWALL w/ RAFTER BEARING SHEARWALL w/ RAFTER PARALLEL SWRI SHEARWALL ROOF CONNECTIONS N.T.S. FDN WALL ANCH PER SW SCHED 2x SILL U.N,O. PER SW SCHED SHEARWALLS TO FOUNDATION X-CP 72 P8 S23 HILTI POWDER ACTUATED FASTENERS, SPACING PER SHEAR WALL SCHEDULE SHEAR WALL PER PLAN P.T. 2x SILL PLATE SHEAR WALL EDGE NAILS d . CONCRETE SLAB & DECKING SHEARWALLS TO SLAB SWB SHEARWALL BASE PLATE &FOUNDATION CONNECTIONS N.T.S. (8)16d EVENLY SPACED, TYP U.N.O. 4N SPLICE TOP PLATE SPLICE 16d @ 16" oc TYP FACE NAILS MIN 2x DISCONTINUOUS DBL TOP PLATE POST SWBA BEAM #CS16 w/, (13) 8d NAILS EA END DISCONTINUOUS DBL TOP PLATE DOUBLE TOP PLATE SPLICE N.T.S. TPSA SWRB BOUNDARY NAIL ALONG LENGTH OF COLLECTOR COLLECTOR BOUNDARY NAIL ALONG LENGTH OF rnI I [rTnn L DIAPHRAGM PER STRUCT NOTES INTERMEDIATE FRAMING ABUTTING PANEL EDGES DIAPHRAGM TO COLLECTOR N.T.S. DTCA 4x6 MIN ADJACENT TO 2x4 PARTY WALLS SHEATHING PER SCHED WALL FRMG ALL PLAN VIEW SHEATHING PER SCHED DSW DBL SIDED SW AT ADJOINING WALLS N.T.S. DSWB BOTTOM PLATE FLOOR SHEATHING DBL TOP PLATE #PSPN516 w/ 8-16d NAILS II TOP PLATE, E. — PLUMBING #PSPN58 w/ 1-8d NAIL INTO BASE PLATE, E,S. NOTCH AS REQUIRED WALL STUD, TYP WALL STUD, 7 TYP PENETRATION OF FRAMING - EXTERIOR WALL N.T.S. 4 6" #HTT5KT II (2) 2x6 U.N.O. 56 116 HTT5KT- A HDN HOLDOWNS N.T.S. DBL 2x STUD EDGE NAILING HOLDOWN EMBEDDED STRAP STUDS PER HOLDOWN SCHED EDGE NAILING 2x STUD #MSTC STRAP (2) 2x STUDS U.N.O. MSTC STRANA) SW SHEATHING STRAP SHOWN AROUND CORNER HOLDOWN AT CORNER N.T.S. HOCA DEPTH DO NOT MAKE PENETRATIONS OR NOTCHES IN THE SHADED AREA OF THE BEAM WITHOUT PRIOR APPROVAL OF THE ENGINEER i MIN CLEAR SPACING SHALL BE 2x THE DIAMETER OF THE LARGER HOLE PENETRATIONS IN THIS AREA DO NOT REQUIRE APPROVAL FROM THE ENGINEER DEPTH ) O 01 DEPTH SPAN % SPAN % SPAN SAWN SPAN HOLE DIAMETER SHALL NOT EXCEED 2" U.N.O. HOLE DIAMETER FOR LSL BEAMS SHALL BE: 3" FOR 93/2" DEPTH 3 8" FOR 11%" DEPTH 4 8" FOR 14"-16 DEPTH DO NOT MAKE PENETRATIONS OR NOTCHES MIN CLEAR SPACING IN THE SHADED AREA OF THE BEAM WITHOUT SHALL BE 2x THE PRIOR APPROVAL OF THE ENGINEER DIAMETER OF THE PENETRATIONS IN THIS AREA DO NOT LARGER HOLE REQUIRE APPROVAL FROM THE ENGINEER %DEPTH _E_ DEPTH % DEPTH Q O 0:1 :1 DEPTH PSL & LVL HOLES PERMITTED IN MIDDLE % SPAN ONLY DEPTH LSL ALLOWED HOLE ZONE DEPTH SPAN MAX HOLE DIAMETER SHALL NOT EXCEED 2" U.N.C. MAX HOLE DIAMETER FOR LSL BEAMS SHALL BE: PSL LVL &LSL 3" FOR 91/" DEPTH 3%" FOR 117/8" DEPTH A 4 8" FOR 14"-16 DEPTH A BEAM PENETRATIONS, TYPICAL DETAIL N.T.S. BPAA ­1 & #CS16 6)10d TOWN REQD STUDS REQUIRED STUDS BEAM 2x4 WALL 2x6 WALL 4x & 2-2x (SAWN) 3%x (GLB) (2) 2x4 (2) 2x6 3%x (MANF) 6x & 3-2x (SAWN) 5%x (GLB) (3) 2x4 (3) 2x6 5%x(MANF) 8x (SAWN) 6%x (GLB) (4) 2x4 (4) 2x6 7x (MANF) GIRDER TRUSS (3) 2x4 (3) 2x6 REQUIRED TRIMMERS HEADER 2x4 WALL 2x6 WALL 4x & 2-2x (SAWN) 3%x (GLB) 2x4 2x6 3%x (MANF) 6x & 3-2x (SAWN) 5%x (GLB) ---- (2) 2x6 5%x(MANF) REQD TRIMMERS NOTE: BEAR BEAMS ON THE FULL WIDTH AND BREADTH OF THE MINIMUM SUPPORTS PER TABLES ABOVE UNLESS NOTED OTHERWISE ON THE PLANS BHS BEAM &HEADER SUPPORTS N.T.S. SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M LO-) N Q � O H ' � fY � J � p w ^ Lon Ln N UJ z O 0) V) U) z 11 p u, Lei U 0) C N Ln Ln O _O C LES0 wAsy��c��9� a z ran l 2 00373 d� TERE-� �a S�ONALE� This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S210 0 LA 0 N ru �I ru Ln Ln fV _i N N BUILT-UP CURB/RAIL PER ARCHITECTURAL BUILT-UP CURB/RAIL DIAPHRAGM X ENP POWDER ACTUATED FASTENERS PER ARCHITECTURAL BOUNDARY NAILS ROOF DECKING CONTINUOUS BEAM AT EAVE CONTINUOUS BEAM AT EAVE L3x3x % w/ %" O x 4%" #SDS @ 12"oc MAX (4) BAYS OF FULL -DEPTH 2x PARAPET PARAPET PARAPET BLK'G w/ DIAPHRAGM BOUNDARY NAILS @ 4 oM 2 ROWS E 4 x #SDS, TOP () JOIST w/ DIAPHRAGM BOUNDARY NAILS @ 6"oc DIAPHRAGM 2x LEDGER w/ 1 �� 1 �� (2) ROWS / 4 x 4/ #SDS TOP PLATE TO BEAM @ 16"oc MAX BLK'G OCCURS @ 48"0c MAX � 16 PLATE TO BEAM @ 16"oc MAX OCCURS @ 48 oc MAX � BOUNDARY NAILS � %"4 x 4%" #SDS @ 16"oc MAX #DTT2Z w/ (8) %" 0 x 1%" #SDS, OCCURS @ 48"oc (4) BAYS OF FULL -DEPTH 2x BLK'G w/ DIAPHRAGM BOUNDARY NAILS @ 4"oc, BLK'G OCCURS @ 48"oc MAX #BP% BEARING #BP% BEARING #BP% BEARING PLATE, TYP #L( PLATE, TYP ' PLATE, TYP Op Tppp Ug�F #DTT2Z w/ HANGER 2x10 LEDGER w/L �TF 2x10 LEDGER w/ (2) %" O x 4%" #SDS @ 16"oc MAX (8) %" O x 1%" #SDS, OCCURS @ 48"oc 2x10 LEDGER w/ #DTT2Z w/ (2) %"4 x 4%" #SDS @ 16"oc MAX (8) %"4 x 1%" #SDS, �pS r r, 8dN 16v (2) %" 4 x 4%" #SDS @ 16"oc MAX OCCURS @ 48"oc MINFN��FN�T BALLOON -FRAMED WALL FROM BALLOON -FRAMED WALL FROM y LEVEL 2 TO TOP OF PARAPET BALLOON -FRAMED WALL FROM LEVEL 2 TO TOP OF PARAPET A LEVEL 2 TO TOP OF PARAPET A A DIAPHRAGM CONNECTION N.T.S. DIAPHRAGM CONNECTION N.T.S. 0 REVISION: STAIR DESIGN, 8/19/2022 36" MAX INFILL BY OTHERS, 4" SPHERE SHALL NOT FIT BETWEEN INFILL %" x 2%" A36 FLAT BAR MIN 3/16 TYP %" x 2" A36 FLAT BAR 48"oc MAX SPACING 0 A -A 13" WIDE x 41" LONG x 3%" THICK WOOD STAIR TREADS, MINIMUM STRUCTURAL PROPERTIES: Fb = 1000 psi G=0.5 Fv = 180 psi Fc F = 625 psi DIAPHRAGM CONNECTION N.T.S. DESIGN NOTE THIS RAIL IS DESIGNED TO RESIST THE FOLLOWING LOADS: GUARD RAIL POST - 200 LB CONCENTRATED LOAD IN ANY DIRECTION AT TOP TOP RAIL - 50 POUNDS PER LINEAL FOOT LOAD IN ANY DIRECTION ALONG ENTIRE LENGTH GUARDRAIL INFILL COMPONENTS - 50 PSF APPLIED HORIZONTALLY NORMAL TO THE INFILL A36 %" x 5" x 5" w/ (4) 8" 0 x 3" LAG SCREWS INTO WOOD TREAD SECTION A -A 511 0 0 5" i 3" 4 3" 4 (4) %" 4 HOLES GUARDRAIL POST APPLICATION - ELEVATION VIEW N.T.S. GUARD POST ATTATCHMENT TO TREAD, REFERENCE DETAIL GPA A -A 13" WIDE x 41" LONG x 3%" THICK WOOD STAIR TREADS, MINIMUM STRUCTURAL PROPERTIES: Fb =1000 psi G=0.5 Fv = 180 psi Fc F = 625 psi STAIR TREAD CONNECTION N.T.S. WBC I WIND BEAM CORNER (ISOMETRIC) N.T.S. BEAM OR'^" T HANGEF UF0I 1 IV—, BEAM INVERTED HANGER AT CANTILEVER N.T.S. 11" 1" 5" 5" I1" 11n IHCA • ll I AI Ill i-B II w/ 'LAG SCREWS SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q � O H 0 fY Cb J � p w N w Z 0 V � U CC 0) V) p z w Lei U p1 C N V) X 0 C 100373 �Pf_1STER�� rAs FSS�OW. 19 This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 T8/19/2022 S211 SLAB r 12�I#4 CONT @ 8"oc a . 3" CLR —III—III—III—III— I I —III —III I —III—III—I I 16" WIDE BRIG TYP U.N.O. SOIL NOTE: WHEN THICKENED SLAB IS ISOLATED, #4 BARS SHALL BE PLACED EACH WAY TSF THICKENED SLAB FOOTING N.T.S. TSFA BAR LAP #3 24" #4 32" #5 40" LAP REBAR REBAR REBAR LAP SPLICE N.T.S. NON -SHRINK GROUT: SHALL MEET ASTM C 1107 2000psi in 24 hours 6000psi in 28 days PLACEMENT: Use a mixer large enough to permit continuous placement before any part of the grout has set. Place the grout quickly. Rodding the grout lightly will help move material. Avoid vibration which can cause bleeding and segregation. The air, mix & substrate temperatures should all be between 40°F (4.4°C) and 90°F nInnI rUnThiv rnnl PT TOP OF FDN i 1" GROUTED BASE PLATE N.T.S. SLAB ON GRADE a d � a d a ° a a DEPTH PER ARCHITECTURAL 4'-0" MAX 5" TYP U.N.O. #4 HORIZ AT TOP OF WALL a a a d a°. a ° Q a e d d d ° a d d 4 d a d d 4 ° d - - - ° d. d ° - ° d a 4 ° dd. 9 d d ° ° d a ° d d ° d d.. a d d °- d .. ° d d d a ° ° .d.- ° d d °d d d da a d A d d a d- °- °. ae d p d ° d a ° 4 °d a as a °d ° a a a d °. ° ad d <4 4Q d a d °d a a ° d d ° a d a d ° ° $$ d ° d ° d dJ ° d 6" FOUNDATION DIMENSION PER ARCHITECTURAL #5 @ 12"oc VERT CENTERED, DOWEL INTO FTG w/ STD HOOK, TYP U.N.0. #5 @ 16" cc HORZ, TYP U.N.O. FOOTING d G d d A °, d a a a' d a. d. #5 @ 10"oc EA WAY EP ELEVATOR PIT - SECTION VIEW N.T.S. #5 HORIZ @ 16"oc #5 VERTS @ 16"oc, STD HOOK INTO FOOTING (4) #5 VERTS @ EACH END, SPACING @ 3"oc, STD HOOK INTO FOOTING 3500 psi CONCRETE SHEAR WALL 6" STEMWALL d ° ° 4 ° ° a d d a a .. a d a d 2" CLR _ d _ - d d ^ d 4. d ° ° _ Q _ d _ 4 d ° - Q d . d a ° ° d d. ° d Q -° d d ° 4 a d ° d d ° d ° d CONT BARS 3 PER SECTION CLR SPECIAL CONCRETE SHEAR WALL ELEVATION VIEW I #4 @ 12"oc BARS @ T01 (6) #5 C01` @ T01 GRAC 3'-4" U.N.O. -0" MAX TOP OF 3TEMWALL TO GRADE BEAM #4 CONT w/in P.T. SILL PLATE TOP 12" OF WALL & A.B. CONC SLAB CONIC STEM WALL ON GRADE CTRD ON FTG, U.N.O. 6" U.N. \ FINISH GRAD>,/\ 2 -0 MAX 4'-6" MAX / BETWEEN 16" MIN #4 @ 48"oc i GRADES VERT / #4 @ 48"oc #4 AT BTM / /\ DOWELS w/ 14" EXTENSION \oil INTO WALL & STD HOOK IN FTG CONICFTG 16" x 16" w/ • (4) #4 CONT, U.N.O. GBP �- 3" CLR BRIG SOIL =11 I II NOTES: -CENTER VERTS AND DOWELS IN STEM WALL -DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN EMBEDMENTS EP D 4d or 2%" MIN. BAR D #3 1 %" #4 2" #5 2%" #6 4%" #7 5%" #8 6" LEGEND d = BAR DIAMETER D = FINISHED BEND DIAMETER Note: 1. STANDARD HOOKS SHALL CONFORM TO ACI 318 SECTION 25.3 12d 2. REINFORCING SHALL BE COLD BENT. STANDARD HOOKS N.T.S. SHA FOOTING SCHEDULE CENTER UNDER CONCENTRATED LOAD U.N.O. FOOTING SIZE RE9 ORCEMENT ID WIDTH (Transverse) LENGTH (Longitude) THICKNESS LONGITUDE TRANSVERSE F2.5 2'-6" 2'-6" 16" 5 #4's F5 5'-0" 5'-0" 16" (6) #5's (6) #5's F6 6'-0" 6'-0" 1 16" (7) #5's (7) #5's F3-5 T-0" T-O" 16" (4) #5's (6) #5's LONGITUDE REINF TRANSVERSE REINF POST TO FTG FTG @ WALL THICKNESS LENGTH WIDTH(LONGITUDE)FTG @ WALL CORNER (TRANSVERSE) \/v/ —1 PLYNTH ON FTG FOOTING, TYPICAL FOUNDATION WALL MI REQUIREDTRED ANCHORAG HOLDOWN SCH HOLDOWN HOLDOWN ANCHOR e ANCHOR e EMBEDDED STRAP e I // j/ EMBEDDED STRAP VEMBEDMENTS DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN L — — — INTO WALL MINIMUM HOLDOWN EMBEDMENT N.T.S. MHE WALL SHALL Y' DEEP MIN (2) #4 HORIZ CONT @ TOP OF WALL 1Z" CLC, TYP n REINFORCED FOUNDATION ANCHOR 3/4" = V-0" STD 900 HOOK INTO INTERSECTING GR BEAM • • GR BEAM FOOTINGS REINF MATCH HORIZ REINF V-6" CORNER BAR @ ALL OUTER REINF r REINF STD 900 HOOK INT MATCH HORIZ \ INTERSECTING GR BEAM REINF ALTERNATE EA BAR V-6" CORNER BAR @ ALL OUTER REINF REINFORCEMENT AT INTERSECTIONS N.T.S. I I N.T.S. FTGA U N.T.S. RIAA SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q N CD H Ce J C� `U Ln i.n N J uL z E O V H U 01 LV) U) p z Lu Lei U p1 C N O I.ESC/£ � O z ran l 2 00373 d� C'STERE-� �a %ZONAL This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S2,2 BFl I BEAM TO FOUNDATION BEARING N.T.S. GROUT AFTER INSTALLATION R X"X10"X10"W/ (4) 8" 0 A325-N BOLTS GAGE = 5" 5" 8" MIN EMBED 4 a d d a a a COLUMN TO FOUNDATION n — W10x49 -v A -A r SLAB ON GRADE EACH 1/4 SIDE v ° d a 4 GBP Z-1 a S2.2 DBL NUT w/ #BP 5/8 BRIG PLATE, ° TYPICAL a 4 FOOTING PER PLAN SECTION A -A 21' 5" z SECTION A -A i ■ 511 (2) %" 0 A.B. 8" MIN EMBED BF2 BEAM TO FOUNDATION BEARING N.T.S. COLUMN TO FOUNDATION SECTION A -A DF1 S2.6 d a 1'-6" 3" MIN44 a a d a d 4° a 8" 5" 4 SECTION A -A 411 4 (2) %" 0 A.B. 8" MIN EMBED BEAM TO FOUNDATION BEARING N.T.S. W8x18 GROUT AFTER SLAB ON GRADE INSTALLATION 77A-A IF%" x 5%" x 8%" w/ $ EACH �1/4SIDE (4) 8" 0 A325-N BOLTS GAGE = 3%" G 4 G GBP 8" MIN 52.2 EMBED a � d ° DBL NUT w/ #BP 5/8 BRIG PLATE, Q TYPICAL FOOTING PER PLAN COLUMN TO FOUNDATION N.T.S. LJ N.T.S. I I N.T.S. HSS4x4x %6 GROUT AFTER INSTALLATION A A SLAB ON GRADE R 8"x7"x7"w/ 15 I / a ° 14 (4) 8" 0 A325-N BOLTS GAGE = 5" > d d 4 a GBP a a 8" MIN EMBED DBL NUT w/ ° d #BP 5/8 BRIG PLATE, a TYPICAL FOOTING PER PLAN COLUMN TO FOUNDATION SECTION A -A 1 J 1 1" 5" 4 31' I � Z 1� 311� 2 � COLUMN TO FOUNDATION N.T.S. I I N.T.S. EACH SIDE SECTION A -A SECTION A -A 4 SECTION A -A 1" J4 1" 2 0 0 11� 8 2„ 0 0 25 SECTION A -A - MIDWALL $„ $„ 4 3" HSS3x3x %6TN7 4 2 ® U 0 4 2" I I 2 %"0 AB ( ) s 1/4 12" MIN EMBED NW 4" 4" A -A 1GBP1 FOUNDATION S2.2 v p D v D v D D v v pp D v DBL NUT w/ #BP 5/8 BRG PLATE, TYPICAL F6 COLUMN TO FOUNDATION N.T.S. SECTION A -A - CORNER 11 1 64 I I 1, 4 L 2" SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q N O H Ln Ce J Lon N J LW Z E O V H CC � Lon V) z � Lei Lu O U p1 C N V) O C I.ES f C/£ ~ owAsy��c100�9� a zm l 2 00373 �a S�ONALE� � This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S213 SSS Number: s2105014 Project Name: BEAM CONTINUES OVER 332 Sunset Ave. N SECTION A -A SECTION A -A SUPPORT WHERE APPLICABLE SECTION A -A BEAM CONTINUES OVER SECTION A -A a BEAM CONTINUES OVER W14x68 ¢ SUPPORT WHERE APPLICABLE ¢ SUPPORT WHERE APPLICABLE W1005 W10x45 W1005 W10x45 Owner: [Ron Colwill] 1i z 1" 1i GAP 5" z 5" 6" 6„ Project Location: 332 Sunset Ave N, Edmonds, WA ��Zzzz _E0 A $. I n ] n n I I n ] n n I n ] n n V, q / x 5/z x 7 w/ LLJJI 1�, q / x3/ x7 w/ I I I I q / x4/ x8 w/ TYP (4) %" 0 A325-N BOLTS q %" x 4%" x 8" w/ TYP (2) %" 0 A325-N BOLTS GAGE = 5" 3„ 3/16 I I 1 6 „ I I 1i %3116 TYP (2) %"� A325 N BOLTS 3/16 Design Professional: 1 GAGE = 5 3„ GAGE = 6" 1„ Blake Fisher 3Z" 24 TYP (2) / 0 A325-N BOLTS 3/16 3z 14 4 24 I C I HSS3x3x%6 I I I HSS4x4x%6 Architecture GAGE = 6" 2i„ I � I � I� I I� I 5 4" HSS3x3x/6JL�L I � I HSS4x4x %6 BC1 BEAM COLUMN BEARING BC2 BEAM COLUMN BEARING BC3 BEAM COLUMN BEARING BC4 BEAM COLUMN BEARING M N.T.S. N.T.S. N.T.S. N.T.S. z N00 N o Ce J n Ln Lon N J Lu Z E O V U SECTION A -A _ ~ W1000 SECTION A -A SECTION A -A SECTION A -A Y2"FULL-DEPTH ¢ BEAM CONTINUES OVER BEAM CONTINUES OVER q STIFFENER E.S. ¢ q %" FULL -DEPTH ¢ SUPPORT WHERE APPLICABLE C z SUPPORT WHERE APPLICABLE STIFFENER E.S. W10MATCH BEAM WIDTH MATCH BEAM WIDTH W10x30 Z x W10x45 W10x45 Lu 32" 5" 1" TYP EACH EACH 2" 141 1 1/4 SIDE 1/4 SIDE E TYP i GAP p II U I 4 4�� TYP 4�� 3q TYP -8 p1 1 q %" x 5%" x 7" w/ T�,p (4) %" 0 A325-N BOLTS 3i I GAGE = 3%" 1„ I 3/16 @� I 2- 3- q Y8" x 5Y4" x 8y8" w/ � X 4 14 I Z HSS3x3x %6 2�� q jx g�� x g�� w/ �� q %" x 8" x 8" wl �� TYP I I (4) %" A325 N BOLTS TYP I (4) %" 0 A325-N BOLTS 1 I I (4) %" 0 A325-N BOLTS GAGE - 4" GAGE = 4" TYP GAGE = 3%" C II - EACH II 1" OFFSET EACH II 2" OFFSET EACH — II W801, SEE PLAN FOR 1/4 SIDE II 1SIFFENER q 1/4 SIDE II 1SIFFENER 1/4 SIDE COLUMN ORIENTATION W8x18 W8x31, SEE PLAN FOR COLUMN ORIENTATION �.� I.ESC�F.Q BC51 BEAM COLUMN BEARI BC6 BEAM COLUMN BEARING BC7 BEAM COLUMN BEARING BC81 BEAM COLUMN BEARING �'�`` ��f wAsy%��9 N.T.S. N.T.S. N.T.S. N.T.S. z m l 2 00373 V This space reserved for BEAM CONTINUES OVER governing jurisdiction stamps q %" FULL -DEPTH ¢ SUPPORT WHERE APPLICABLE STIFFENER E.S. SECTION A -A MATCH BEAM WIDTH SECTION A -A R E S U B W14x68 ¢ W14x68 W14x68 I SECTION A -A Aug 22 2022 W1000 W1000 DEVELOPMENTCITY OF E SERVICES EACH DEPARTMENT 1/4 SIDE 2i 2q' 1 z GAP -75"Z' GAP TYP z " 5" 5" 2Z" 5" 3"' 2�" 5" TYP a TYP $ I q %"x10"x10"w/ q %"x54"x8%"w/ s I (4) %" 0 A325-N BOLTS 1 I I q / x 10 x 10 w/ (4) %" O A325-N BOLTS ORIGIN DATE: 10/20/2021 2Z GAGE = 5" EACH TYP GAGE = 3%" 2q„ (4) %" A32GAGE = 5" CH TYP I 16" OFFSET 1/4 SIDE II 1/4 SIDE TYP I I 1/4 SIDE REVISED: 1/25/2022 SIFFENER W10x49, SEE PLAN FOR II W8x18 I I W10x49, SEE PLAN FOR COLUMN ORIENTATION COLUMN ORIENTATION o N N �I BC9 BEAM COLUMN BEARING BC10 BEAM COLUMN BEARING BC11 BEAM COLUMN BEARINGru Ln Ln N.T.S. L_J N.T.S. N.T.S. , �I 0 N N SSS Number: s2105014 Project Name: SECTION A -A SECTION A -A 332 Sunset Ave. N CSC SECTION A -A SECTION A -A s „ 1 "S2 "6 WsX18 CSC I 4 I 5 CSC COLUMN ORIENTATION CSC 2/ x 4/ x 8 w/ I 01, SEE PLAN FOR I HSS4x4x /6 S2.6 4" I (2)%"0 A325-N BOLTS 21" I I 14 I I 52.6 I S2.6 Owner: 4 EACH GAGE = 6" 1i R $" x 3%" x 7" w/ HSS3x3x %6 2 %" x 54" x 8%" w/ EACH I [Ron Co Iwi I I ] TYP I I _ 13 3z I 1 (2) %" A325 N BOLTS 4 1 I I (4) %" 0 A325-N BOLTS 1/4 SIDE 1/4 SIDE 2„ R %" x 8" x 8" w/ ��� 1/4 GAGE - 5" GAGE = 34" �� I (4) %" 0 A325-N BOLTS 16 / I I TYP I I 1/4 TYP II TYP I GAGE = 4" rr'tE41I Le i Project Location: 332 Sunset Ave N, 6" 2" 1 4 2„ 4" Edmonds,, WA 5" 34" 48 TYP TYP 4 EACH EACH 1/4 SIDE Design Professional: 1/4 SIDE Blake Fisher Architecture I W10x45 R %" FULL DEPTH W10x30 R /" FULL DEPTH W10x45 BEAM CONTINUES BEAM CONTINUES STIFFENER E.S. BEAM CONTINUES STIFFENER E.S. W14x68 ¢ WHERE APPLICABLE MATCH BEAM WIDTH WHERE APPLICABLE WHERE APPLICABLE MATCH BEAM WIDTH BEAM CONTINUES a WHERE APPLICABLE FCB1 COLUMN BEAM BEARING CB2 COLUMN BEAM BEARING CB3 COLUMN BEAM BEARING CB4 COLUMN BEAM BEARING M �_J �_J �_J �_J N.T.S. N.T.S. N.T.S. N.T.S. zLn 00 o J � p w ton Ln N J W Z E SECTION A -A SECTION A -A v o CSC COLUMN SEE PLAN FOR CSC $2.6 HSS3x3x%6 W14X68, 2" 2" W10X30, � COLUMN ORIENTATION S2.6 I s �� �� �� EACH 14 I 14 I COPE T&B FLANGES COPE TOP FLANGE C z 21z' R/x10x10w/ 1 R%x7x7w/ 1 1" TYp I (4) %" 0 A325-N BOLTS 1/4 SIDE 3g I (4) %" 0 A325-N BOLTS 3g 22 TYP I I 1 GAGE = 5" I I O W I I GAGE = 5" 5q" TYP 1/4 1z" TYP 1Z', TYP 3", TYP I 3", TYP OV al „ 2Z" 1s" OFFSET C 5 TYP 5 5 SIFFENER I 3/16 V) 3/16 (�J EACH O tX�771 1/4 SIDE W14x68 2 R %"O"O" w/ W14X68 R %"K' 6" w/ C (3) 4" 0 A325-N BOLTS (2) /" 0 A325-N BOLTS R %" FULL -DEPTH BEAM CONTINUES STIFFENER E.S. W14x68 W1468 WHERE APPLICABLE ¢ MATCH BEAM WIDTH I.ESC/£ FCB5 COLUMN BEAM BEARING CB6 COL E IN BB1 BOLTED BEAM CONNCECTION - SHEAR TAB BB2 BOLTED BEAM CONNCECTION - SHEAR TAB �'�``� °f LJ L_J N.T.S. T. N.T.S. N.T.S. z m l 2 0037.3 This space reserved for governing jurisdiction stamps 2" 2" SR- fl RES U B 2" w14x68, Aug2 2022 W10 PER PLAN COPE T&B FLANGES W10 PER PLAN g 2 2 COPE T&B FLANGES CITY 2 2 2 COPE T&B FLANGES DEVELOPMENT FEDSOERVICES W1OX3O 3„ DEPARTMENT 4 STIFFENER EACH SIDE 54 PER COLUMN DETAIL STIFFENER EACH SIDE 12„ TYP 3 TYP 12„ TYP PER COLUMN DETAIL I%" MIN, TYP ---3/16 311 3. I 3" � 3", TYP 3/16 3/16 1Z', TYP W10 PER PLAN R %"x4"x6" w/ s R x4 x6 w/J W10 PER PLAN (2) s/a" 0 A325-N BOLTS, (2) 4" 0 A325 N BOLTS W14x68 (3) 4" 0 A325-N BOLTS, (2) 4" 0 A325-N BOLTS BEAM TO STIFFENER, W14x68 LR %"x4"x9" w/ ORIGIN DATE: 10/20/2021 ONE OR BOTH SIDES PER PLAN 4" 0 A325-N BOLTS W16x26, BEAM TO STIFFENER, Wsx31 COLUMN (3) REVISED: 1/25/2022 ONE OR BOTH SIDES PER PLAN COPE TOP FLANGE 0 Lin ('V N �I ru BB3 BOLTED BEAM CONNCECTION - SHEAR TAB BB4 BOLTED BEAM CONNCECTION - SHEAR TAB BB5 BOLTED BEAM CONNCECTION - SHEAR TAB BB6 BOLTED BEAM CONNCECTION - SHEAR TAB 'BB71 BOLTED BEAM CONNCECTION - SHEAR TAB Ln Ln N.T.S. L_J L_J N.T.S. N.T.S. N.T.S. N.T.S. , �I 0 ('V ('V ROOF DECKING SHEAR WALL / EDGE NAILS J SHEAR WALL R %" x 3" x 3'-6" w/ PER PLAN 3/16 1- 32 %" 0 x 3" #SDS %" x 3" x CONT. w/ SCREWS @ 4"oc %" 0 x 4%" #SDS W14x68 SCREWS @ 12"oc, SHEAR WALL )RIVEN AT AN ANGLE SECTION A -A EDGE NAILS, TYP 5/16'0 x %" SLOTTED HOLES DOUBLE SIDED IZEE BEAM FLANGE SHEAR WALL 18" Z' CLR PER PLAN A 18 J i1 J 4 SHEAR WALL TO ROOF ATTACHMENT N.T.S. ROOF DECKING %" 0 x 33/2" #SDS SCREWS @ 12"oc SHEAR WALL EDGE NAILS SHEAR WALL PER PLAN SHEAR WALL TO ROOF ATTACHMENT N.T.S. SHEAR WALL PER PLAN BASE PLATE NAILS PER SW SCHEDULE SHEAR WALL EDGE NAILS x 6" x V-0" @ 32"oc w/ (2) 8" 0 CARRIAGE BOLTS PER EACH PLATE SPACED 8"oc, NOTCH SOLE PLATE AROUND STEEL PLATE 3/16 V 1- 5 L6 x 3% x % CONTINUOUS OR FORM CLOSURE 3/16 2 - 36 ° ° a a ° a_ a d DF1 STEEL BEAM PER PLAN SHEAR WALL TO FLOOR ATTACHMENT STAGGERED 311 9 2j11 4 511 J 211 8 8 3/16 V 2 -16 W14x68 4 SECTION A -A %6'O x%" SLOTTED HOLES BEAM FLANGE d" ND STAGGERED 1-36 X" 0 x 3%" #SDS SCREWS @ 8"oc, STAGGERED SHEAR WALL TO ROOF ATTACHMENT N.T.S. SHEAR WALL PER PLAN BASE PLATE NAILS PER SW SCHEDULE SHEAR WALL EDGE NAILS x 6" x V-0" @ 32"oc w/ (2) 8" 0 CARRIAGE BOLTS PER EACH PLATE SPACED 8"oc, NOTCH SOLE PLATE AROUND STEEL PLATE 3/16 V 1- 5 R x8"xCONT 3/16 2 - 36 ° ° n I STEEL BEAM PER PLAN SHEAR WALL TO FLOOR ATTACHMENT (2) #10 x i%" SELF -TAPPING SCREWS @ 8"oc. TYP U.N.0, SHEAR WALL DECKING SHEAR WALL TO ROOF ATTACHMENT N.T.S. SPAN BREAK WHERE OCCURS, (2) FASTENERS AT BUTTED CONDITION (1) FASTENER AT CONT. CONDITION C6x10.5 TYPICAL ALONG ENTIRE LENGTH OF BEAM, MIN LENGTH SHALL BE 6'-0" 1/4 V 2 24 DECK FASTENING N.T.S. SPAN BREAK WHERE OCCURS HSS3x2x % TYPICAL ALONG ENTIRE LENGTH OF BEAM, MIN LENGTH SHALL BE 6-0" 1/4 I2-24 DECK FASTENING DECK PER PLAN, FASTEN TO CHANNEL w/ X-ENP-19 L15 POWDER ACTUATED FASTENERS 1/4 V 2 24 W1005 OR W14x68 DECK PER PLAN, FASTEN TO CHANNEL w/ X-ENP-19 L15 POWDER ACTUATED FASTENERS W10x30 1/4 I2-24 MIN CONCRETE SLAB ON Cnn"A ncry ncn nl AM FORM DECK FASTENING N.T.S. T-0" MAX OVERHANG HSS3x2x% FOR CANTILEVERED PORTION, 6-0" MIN CONTINUO' Ir TnT"' ' `nirTu INTERIOR/EXTERIOR TRANSITION EACH SIDE OF EACH SIDE CHANNEL, TYP 3/16 2 -12 OF HSS, TYP 3/16 2 -12 ° a ° ° d . HSS3xlY2x % J C6x10.5 STEEL BEAM PER PLAN 6'-0" MIN CONT. LENGTH EACH SIDE OF HSS, TYP 3/16 2 -12 EACH SIDE OF END OF HSS 3/16 2 - 24 CHANNEL, TYP --------- — — — — — — — ------------------- ROA I ROOF OVERHANG ATTACHMENT N.T.S. STEEL COLUMN CONCRETE SLAB AT COLUMN N.T.S. I J N.T.S. I J N.T.S. I J N.T.S. J I LLL ULlll I PER PLAN STEEL CHANNEL PER PLAN TYPICAL ALONG ENTIRE LENGTH OF BEAM STEEL BEAM PER PLAN SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q � O H 0 � fY � J � p w ^ Lon N p�J LJI z E O U I� 6 V) U) p z w Lei U 0) C N V) U0 A -0 O C wAsy'00�9� a z ran l 2 00373 d� C'STERE-� �a S�ONALE� This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S216 CANTILEVER CONDITION l 2" TYP (6) #SDS 4" 0 x3" (3) ON EACH SIDE OF WEB, STAGGERED mr1 TArnTn® rMc rrAnA FLOOR DECKING ATTACHMENT N.T.S. SECTION A -A DELTAGRIP® SIDE SEAM CONNECTION @ 24"oc, TYP JI—UL—lF—FUMY RDA I ROOF DECKING ATTACHMENT N.T.S. D SIDE OF SHEATHING J (WHERE OCCURS) %" 0 WELDED THREADED STUDS @ 12"oc w/ %6 WELD ALL AROUND, TYP U.N.O. COUNTERSINK OK, 4" MAX DEPTH 4x6 NAILER, TYP U.N.O. R I A T I rrl -r^ r-rr-r-1 tN^l 111►AR1 Im! BEAM PER PLAN 4x6 SHEAR WALL END POST • (2) ROWS 4" 0 x 6" NS1 #SDS SCREWS @ 10"oc S2.7 . (2) ROWS OF EDGE NAILS HSS PER I I ON EACH 4x6 MEMBER PLAN • SHEAR WALL PER PLAN WSD WOOD SHEAR WALL DISCONTINUI N.T.S. (2) ROWS SHEAR 6x6 NAILER WALL EDGE NAILS %" 0 WELDED THREADED STUDS @ 16"oc w/ %6 WELD ALL AROUND, TYP U.N.O. COUNTERSINK OK, 4" MAX DEPTH STEEL COLUMN J H \— WOOD SHIM AS REQ'D NAILER TO STEEL COLUMN N.T.S. 54" x 117/8" LVL WIND BEAM e %II STIFFENER (2) 4" 0 CARRIAGE BOLTS, STAIR SIDE ONLY WBA WIND BEAM ATTACHMENT DDn\ITnc rnl IDI cD c I.— r - nrnl ITnrm nil iT o_ non CDI Trr DCDMTTTCn TnI nnl IQI C TOD %" 0 WELDED THREADED STUDS @ 12"oc w/ %6 WELD ALL AROUND, TYP U.N.O. rnI Ih1TCnrTKIV nV i" nAAV nCnTLI 6) TC NAILER TO STEEL COLUMN N.T.S. X-ENP-19 L15 POWDER ACTUATED FASTENERS @ 12"oc CONCRETE SLAB 7 d ° ° d ° ° ° ° STEEL DECKING L4x3x % x 61-6" LEDGER w/ %" 4 x 4" #TITEN HD @ 36"oc SHEAR WALL EDGE NAILS HSS3x3, TYP U.N.O. CSF2 I SHEAR WALL TO FLOOR CONNECTION N.T.S. L-i N.T.S. CONCRETE SLAB METAL DECKING, ¢ 1'-0" TYP ORIENTATION PER PLAN SHEAR WALL TO FLOOR CONNECTION N.T.S. X" 4 x 4%II HEADED STUD -, //— 5/16 l 4" o x V2" '6. HEADED STUDJ.�°. ° 4" ° A d' CONCRETE WALL SECTION A -A d e s /" x 3" x CONT. 5/16 SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N o H 0 fY � J � p w ^ N J w z O I� 01 V) p z w V7 O U p1 C (IJ M V) O I.ES f C/£ owAsy��c100�9� a zm l 2 00373 d4 �s'�fC15TERE-� �a S70NALE� � This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S2,7 F5 r I W10x49 I (1-104) I I L----J (- W1009 ' (1-101) J- L FOUNDATION PLAN - FOOTINGS, WALLS & GRADE BEAMS 3/16" = V-0" SYMBOL LEGEND SLEXP #HOLDOWN MODEL HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE. CONCRETE WALL AND CONTINUOUS FOOTING See CONCRETE and REINFORCING BAR specifications per DETAIL FWS. L -1 F2 SPREAD FOOTING See CONCRETE and REINFORCING BAR specifications per DETAIL FTG. L J DO NOT SCALE - VERIFY ALL DIMENSIONS WITH ARCHITECTURAL SHEETS PRIOR TO CONSTRUCTION `' " HSS3x3x %6 � S2,3 (1-123) ------------- -------------I I � I I I I SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q � O H o fY � J � p w ^ N p�J w z O v � U 0) V) p z w > V1 > O U p1 C N V) X O C wAsy00�9� a z ran l 2 00373 `STERE-� �a S�ONALE� This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S310 SYMBOL LEGEND SLEXP ------------------- DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM. POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like. the plans. - - - - - - - - - - SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections k \ \ \ INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL per the SHEARWALL SCHEDULE. FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. #HOLDOWN MODEL _1L_ u HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE. STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan. JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are spacing between members will be indicated in bold type with a symbol which is representative of the layout of the indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 (or 4x6) U.N.O. entire level. on the plan. WALL WALL WALL WALL LINE LINE LINE LINE A B C D OREVISION: STAIR DESIGNI 8II19 2022 BOTH SIDES $2 5 W1009 (1-110) W10x49 W10x49 BB4 (1 104) $" BASE PLATE $2 5 (1 111) S2.5 r------------------ ------------------------------------ 1------,T ---_ row BB4 W14x68 (1-1) W14x68 (1-19)1 1 I DF3 S2.61 1 BIB 2 MII S2.5 Ilu IIII III III 0E E 11 Jill ill 4 I IIIIJill I uL OSD ES L�B213BC9 W14x68 (1-2) $2.5 W10x49 nur BLOCKOUT END OF (1 103) IIIIII WALL AROUND BEAM, 1" CLR TYP ALL SIDES LI III DECK LOAD: ul DEAD LOAD 65 PSF MAX III LIVE LOAD 60 PSF MAX Hill SNOW LOAD 25 PSF MAX (IIII III Jill Ill CB5 BC9 IIIIII LB213g4 BOTH SIDES S2.5 S2.4 IIII W14x68 (1-31) W10x49 -- Jill IIII (1102) Jill C$F1 00 'I 10 IH � III 1 11 1 11 1 11 IrH BB4 4n nn nu S2.5 IIII Jill W14x68 (132) CB5 BC9 W10x49 S2.5 11 S2.4 (1101) N CS a M a 3 M 00 BC 2.5 S2. Iiil S21 STAIR STRINGER W LDED SS4x4x %TO BEAM BY A ABO CONT, FROM CERTIFIED W LDER FND TO ROOF-•----------------- I I I II FDA BC9 TYP S2.7 S2.4 r7 I I _ BOTH SIDES BB4 W10x49 (1-105) HSS3x3x %6 STUD ABOVE, TYP (4) LOCATIONS* I!P (4) CB6 z 0 I W10x49 (1-106) CB5 S2.5 W10x49 ABOVE Z..ti ----------- - BB4 B H S] S2.5 = BLOCKOUT END ---_-_ OF WALL AROUND BEAM, I" CLR TYP M ALL SIDES 10 WALL WALL LINE LINE E F BB4 WIND BEAM 52.5 CB5 WBA WBA NS2 BC9 w� S2.5 2.7 52.7 LSL7J S2.4 (1- 54" x 117/s" LVL 'r \ I �I I I I I I I I I i tsi I 1 A ,l�l 1"1 % tTAIR StRINGE�i � W14x68 (1 20) +- I I I I'k�SS1b4 I 1 1 I I I I I j� < I [ I I I I I I I � CB5 I I< � � 1 ����-------- 3: 3 1 -----------------\��j I BB1 STC GPA W14x68 (13) BB1 BB WALL LINE G BB 2 BB3 $2.5 S2.5 \� BC5 W1000 (1-9) HSS3x3x %6 2.4 (1-127) O �_ x O_ s7_ yn BB3X� �\� ii y(_______I ill II S2.5 CSF1 BF1 IS2.3 -------- rT==____ wlox3o (1 11) rn I $2.7 BB2 I BB5 I I C2 11 I L_S2.4 !S215� W14x68 CONT. (1-5) I , IIIIL -7BB1 II t 52.5 6 II HSS4x4x/671 11 (1122) DF1 TYPICAL FOR ALL I BC5 +:. ' I S2,6 BEAMS, U.N.O. 1 $2 5 W10x30 (18) 52.4 IL------------------------------- - - - - - - - - - - - - - - - - - - - - I - - - - - - L-------------------------------- --r--------------------- FLOOR LOAD: ii I 6 -----------------1L� i `- HSS3x3x DEAD LOAD 65 PSF MAX i LIVE LOAD 40 PSF MAX W8x31 SNOW LOAD 0 PSF MAX ABOVE W10x49 (1-107) W14x68 CONT. (1-6) _BC_ -------FL-----� HSS4x4x %6 BC9 ABOVE $2.4 C61 , I W10x49 L`J C CSF1 S2.7 00 r-L----- rl I I 10 " I I c r-----� I I r - - - - - - - - - I o I I I I I I I BB1 i l --1�---------1�----- -----I=====3------- SIM. STIFFENER CB5 BF1 PLATE NOT RE( CSF1 52.7 i L - HSS4x4x%6 (1-118) r - BC2 II i i BF2 CB5 $2.5 ' W14x68 CONT. (17) $2.4 i i i i $2.3 $2.5 __-________________ ----- ----- -- -- I I ---- W10x49 ABOVE BC2 52.4 HSS4AX %6 (1 119) $F1 TYPICAL AT S2 6 EXTERIOR WALL K LEVEL 1 SHEARWALLS & FRAMING ABOVE 3/16" = V-0" $F2 TYPICAL FOR ALL DF2 x30 1' S2.6 W1000 BEAMS $2.6 BC4 CB3 w8x18 W8x18 Ii W10x30 CONTINUOUS (121) ABOVE $2.4 $2.5 ABOVE ��-----------------------------------------------I----- BC8 CB3 BB6 I w8x1s BC8 CB3 Hss4x4x%6 CSF1 CF5 52.4 S2.5 S2.5 (1114) S2.4 S2.5 (1117) S2.7 S2.3 0�7 �0`1 tstib HSS3x3x%6 S2.4 52.5 S2.5 ABOVE W801 CB2 (1-113) S2.5 ----------------- BF3 CB4 r-i BC3 $2.4 BC4 HSS3x3x %6 W801 S2.4 ` ABOVE ABOVE J� W10x45 CB4 BF3 J CONTINUOUS (1-22) 1 I S2.5 II I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I W8x31 ABOVE 'I I I I HSS4x4x %6 I I I (1-116) W10x45 CONTINUOUS (1-23) I I ' 1 -------------1 ---i------- TYPICAL AT BC4 CB4 EXTERIOR WALL HSS4x4x %6 (1-120) DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS W801 I MUM IEEL WALLE LLIN H I Ij 3 6 BALLOON -FRAMED WALL AT II S2 HSS3x3x /6 STAIRS w/ 1 4" x 5%" @ 12"oc (1-123) M r -----T #HTTSKT `f I I v I I I I �' I N$1 I I I `4. I /I I I I I �' I I `�41 y" l� I I I L' I I #HTT5KT i t I I I I I CSF1 LLPONLFgMEq I III II #HTTSKT r�1 21x611211IRGLNA1 ��\\I HS63x3x%6 W10x45(1-26) C F1 I BF3 ^¢z pl (1 �24) BB3 J�' i S2.5 S I'7 I I------- i I I II I I I II I I I II I I I II I I I II I I I II I T, n I I II I o Ir�II I I I I I BB BC71 II I� S2,41 S2 5 W10x45 (127) I 1 i W8x31 -J 1=------------------------------- (1-125) it------------------------ ---- I K K K � SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M t.� N Q � O H 0 � fY � J � p w Lon N U JI V � Lon V) rn z � U Lei U 0) c a� O E A ~ � n c*� 100373 �PfGISTER�� rAs FSS�ONAI. 19 This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 8/19/2022 0 LA ru N N I ru Ln Ln kn �I 00 0 N N rAl IIUM AQrnIC TVe LEVEL 2 - SLAB REINFORCING PLAN 3/16" = V-0" DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS (1) #4 CONTINUOUS SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q � O H 0 fY � J � p w ^ N J w z O V � U 0) V) p z w V7 O U p1 C N M V) X O C wAsy00�9� a z z ran l 2 00373 d� C'STERE-� �a S�ONALE� This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S3,2 SYMBOL LEGEND SLEXP ------------------- DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM. POS dicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are is in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like. SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Ins TERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL per the SHEARWALL SCHEDULE. P,FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. #HOLDOWN MODEL -11 L- u HOLDOWN Represents holdowns which are located at m of the wal led out. Connections are HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL wall-to-wall or wall -to fdn u.n.o. Connections per the WN EDULE. STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan. JOIST, TRUSS, OR RAFTER R 'tiveUesypo he direction of the span. The type, size and max BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are spacing between member ill be ateith a symbol which is representative of the layout of the indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 2-2x6 (or 4x6) U.N.O. entire level. on the plan. 6x8 NAILER TO HSS NO SPLICE PERMITTED J LEVEL 2 SHEARWALLS & FRAMING ABOVE 3/16" = V-0" DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS #HUC #MSTC40 I i 6x12 WIND BEAM AT BASE OF PARAPET I #� MSTc40 I N I� I� Ix I BALLOON -FRAMED UP TO PARAPET 6x6 w/ #CCQ @ TOP (2) #A35 @ BTM TYPICAL (4) #HUC SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q � O H o fY � J � Ln p w N w Z E O U V) p z w V7 O �U-{� V , W Ln Ln O C I.ES0 of wAs��9� a � zm l 2 00373 d� �0'f,C15TERE-� �a S�ONALE� � This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S313 CONTIN0 DECKING, WHI SHALL NOT BI TWO SEPA SHADED SING[ HATCH BE MUL PANELS SHALL ALT SINGLE AN ROOF DECKING LAYOUT PLAN 1/8" = V-0° FLOOR DECKING LAYOUT PLAN 1/8" = V-0° DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS I I I I I I I I I I I I I I I I I I I I I I I I I SSS Number: s2105014 Project Name: 332 Sunset Ave. N Owner: [Ron Colwill] Project Location: 332 Sunset Ave N, Edmonds, WA Design Professional: Blake Fisher Architecture M � N Q � O H o fY � J � Ln p w N J w z E O I� C1 V) p z w V7 O U p1 C N Ln Ln X O C wAsy00�9� a z ran l 2 00373 d� C'STERE-� "'a SZONALEN ?� This space reserved for governing jurisdiction stamps RESUB Aug 22 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 10/20/2021 REVISED: 1/25/2022 S3,4