BLD2024-0574_Manufacturer_Specifications_and_Installation_Instructions_5.1.2024_10.31.21_AM_4229816Job Name: W�
Tag# 6L DAkvKkqN
Submittal Data Sheet F XXR18TVJUW / RX18RMVJU9
1.5-Ton Wall Mounted Heat Pump System
Complete warranty details available from your local dealer or at
www.daikincomfort.com. To receive the 12-Year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Quebec.
If product is installed in a commercial application, limited warranty
period is 5 years.
Indoor Specifications
Airflow Rate (cfm)
Cooling
Heating
H
M
H
M
350
245
413
332
L
SL
L
SL
226
208
275
208
Sound(dBA)
H/M/L/SL
46/40/35/30
47/41/35/30
Dimensions (H x W x D)
(in)
11-15/16 x 39-5/16 x 8-3/8
Weight (Lbs)
27
Outdoor Specifications
Compressor
Hermetically Sealed Swing Type
Refrigerant
R-410A
Factory Charge (Ibs)
2.49
Refrigerant Oil
PVE (FVC50K)
Airflow Rate (cfm)
Cooling
Heating
H
2,461
H
2,553
Sound Pressure Level (dBA)
54/55
Dimensions (H x W x D) (in)
28-15/16 x 34-1/4 x 12-5/8
Weight (Lbs)
97
Efficiency
Cooling
Heating
SEER
14.5
HSPF
9.8
EER
9.6
COP
3.34
Performance
Cooling (Btu/hr)
Rated (Min/Max)
18,000 (5,800 / 21,200)
Sensible @ AHRI
11,590
Standard Operating Range
507 — 1157
Extended Operating Range*
-4*F— 115*F
Rated Cooling Conditions: Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
*With field settings and wind baffle
Heating (Btu/hr)
1:@ 47* Rated (Min/Max)
20,000 (5,800 / 21,200)
2: @ 17* Rated
13,300
3: @ S*
8,970
Operating Range
5F — 657
1: Rated Heating Conditions: Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
2: Rated Heating Conditions: Indoor: 70°F DB/60°F WB
Outdoor: 17°F DB/15°F WB
3: Heating Conditions: Indoor: 707 DB/607 WB
Outdoor: 5°F DB/5°F WB
Electrical
208/60/1
230/60/1
System MCA
12.8
12.8
System MFA
15
15
Compressor RLA
10.75
10.75
Outdoor fan motor FLA
.38
.38
Outdoor fan motor W
110
110
Indoor fan motor FLA
.21
.21
Indoor fan motor W
29
29
MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)
RLA: Rated load amps (A) W: Fan motor rated output (W)
Piping
Liquid (in)
1/4
Gas (in)
1/2
Drain (in)
11/16
Max. Interunit Piping Length (ft)
98.4
Max. Interunit Height Difference (ft)
65.6
Chargeless (ft)
32.8
Additional Charge of Refrigerant (oz/ft)
.21
Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without
notice and without incurring any obligations)
Submittal Revision Date: February 2019 Page 1 of 4
a
0
IFT)(RUT'WIM(:3
NOTE) 1,THE MARK: (--) SHOWS PIPING CIRE.CTIION, OPERATING STATE: REQUIRED SPACE
GENERAL RATING 1) OFF FOR INSTALLATION �1
NAMEPLATE
39-5/16(Mill; ) E,/Wii FLOW(INDUOR)
�• HEAII
-TERMINAL BLOCK
:. WITH EARTH TERMINAL
L:T —ME =� (INSIBIEI
8-3/81212) (SPACE FOR
!iEflYICE COVER FIXED B-jl/1f,(Y1,) INCLUDING
OPERATION)
SCRIEW(ON FRONT GRILLE) ---' MOUNTING PLATE
HO1
2) (IN
r-
TOM L�
Donor r:o:iic c:rcn cracv,c :NTELLICENTI SOT
11/1608)
(INSIDE PANEL) EYE SENSOR
MUL11-MONITOR LAMP --- ---
FLAPS, HER LAMP\ INTELLIGENT UP AND DOWN WIND
EYE LAMP DIHEC11011 CONTROL BLADE:
MOVABLE RANGE
-INDOOR UNIT ON/OFF SWITCH
`flD3M TEMPERATURE
SIGNAL RECEIVERY THERMISTOR(INNER)
SIGNAL TRANSMITTER
T/8,12I.il BLADEI AINGLE C
— —!UP/DOWII(AIITONATIC)
COOLING, DRY HEATING FAN �
E]
0100
30' (/ 3( r� 25' - ., LEFT/fllGHT
(AUTOMATIC)
y 1
5(1 65' 50'
WIRELESS RETIOT'E CONTROLLER l3 .
1'OM
1-T5,/16150)IgIN
(SPACE FOR -
OPERATION)
13-;I/4(350INIM 9-13/Ili(150)MIN e � ��
(SPACE FOR (SPACE FOIi I N==
RECEIVIIIG) RECEIVIN,
)%
GAS F'IPE. I/2((12 T))CUT
(THE LENG a OF PIPi OUTSIDE
THE UNIT: ABOUT 13-3/4(350)) \
m _
LIQUID PIPE 4 IPEO OUTSIDE DRAIN HOSE CONNECTING
(THE LENGTNI OP PIPE OUTSIDE
PAPT
THE UNIT: ABOUT 15-3/4(400))
THE H3SE LENGTH OF OUTSIDE
BA( :K $lDE V(IEN
THE UNIT IS APPROX. 18--5/16(465),
39-5/16(993)
cJ
26-9/'I6(674, 5)
_
_--7-1/8(200)
—
' 5-15/16(1) �r
F STANDARD LOCATIONS OF WALL HOLES_
--- — —
WALL HOLE
¢2 9/'6(65)
(ARC466A36) ,I.�i'T 'NALL HOLE
0 2-9/ 116 (65 :1
3D1055G9A
O
N
d
0
HANDLE 9116114) 34-11418701
4-HOLES FOR FOUNDATION BOLTS
(M8 OR M10)
SERVICE
PORT
LIQUID
STOP VALVE
(�114 (66.4) CUT)
GAS
STOP VALVE
(Q 1/2 (612.7) CUT)
cp N
v cc
6-13116 (173) IN CASE OF REMOVING
—�� STOP VALVE COVER AND
TERMINAL STRIP COVER
- 2.314 (70)
FI F(:TPIr. WIRF INTAKF OUTDOOR AIR THERMISTOR
23-5/8 (600) 4-15116 (125)
m o U MINIMUM SPACE FOR AIR PASSAGE WALL HEIGHT ON AIR OUTLET SIDE
=LESS THAN 47-1/4 (1200)
cor.o O
20-11/16 (525)
tt
DRAIN OUTLET
(I.D 05i8 (o15.9) HOSE FOR
t,CONNECTION WITH DRAIN JOINT) $ 8 Q
c r5
v
1-15116 (50) 7 `O 1-15116 (50) ch
M
m � �
UNIT: inch (mm)
C:3DO92224B
Optional Accessories 7 DA/K/N
Indoor Unit
Included
Part Number
Description
BRP072A43
Wireless Interface Adapter (S21 Adapter Included)
BRC944132-A08
Wired Remote Controller kit (Adaptor Required)
BRCW90IA08
Wired Remote Controller Cable — 25ft (Included in above kit)
BRCW901AO3
Wired Remote Controller Cable — 1Oft
KAF970A46
Titanium apatite photocatalytic air -purifying filter WITHOUT frame
DACA-CP1-1
Inline Condensate Pump (fits inside all Daikin wall & floor mount units)
DACA-CP4-1
External Condensate Pump
DACA-CPI-1
Inline Condensate Pump (Fits inside all Daikin wall & floor mount units)
DACA-CP4-1
External Condensate Pump
KRP928BB2S
Interface Adaptor for DIII-NET
Outdoor Uni
Included
Part Number
Description
DACA-WB-1
Powder -Coated Wall -Mounted Bracket
KEH063A4E
Drain Pan Heater
KKP937A4
Drain Plug for OD Unit
KPW063A4
Low Ambient Wind Baffle / Air Adjustment Grille (15/18 /24MBH)
KKG063A42
Back Protection Wire Net (15/18/24MBH)
Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without
notice and without incurring any obligations)
Submittal Revision Date: February 2019 Page 4 of 4