BLD2020-1000+LIGHTING+9.28.2020_8.54.40_AM2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
General Info Project Title: Firdale Village Fire Restoration
Date 9/28/2020
PROJ-SUM form Project Street Address: 9617 Firdale Ave - Unit 9631
For Building Department Use
shall be provided as Project City, County, Zip: Edmonds, WA 98020
a cover sheet for all
compliance form Project Owner or Rep: Jesse Binford
submittals. Project
Title shall match Jurisdiction: City of Edmonds
project plans title
block.
Project Description
New Construction and Additions
Select all that apply to the
❑ New Building ❑Building Addition
scope of project.
Select Addition + Existing
Existing Building Retrofit
or Alteration + Existing if
the existing building will be❑
Alteration ❑ Change of Occupancy ❑ Change in Space Conditioning
combined with the addition
or alteration to demonstrate
❑ Historic Building
compliance per Section
C502.1 or C503.1.
Building Elements Scope - Select all that apply
❑ All❑ Building Envelope ❑ Mechanical Systems
❑ Service Hot Water Systems ❑ Lighting Systems ❑ Electrical Systems
All Commercial a Group R - R2, R3, & R4 (D Mixed Use
over 3 stories and all R1
Occupancy Type
P Y YP
Mixed Use - Building is greater than three stories above grade and it has both Commercial and Group
R occupancies.
Mixed Occupancy - Building is three stories or less above grade and it has both Commercial and
Group R2, R3 or R4 occupancies. Select All Commercial to document compliance for the commercial
areas of the building. The residential spaces shall comply with the WSEC Residential Provisions.
Select all that apply to the scope of project
❑ Fully Conditioned ❑ Semi-heated2 ❑ Refrigerated Spaces
(Warehouse and/or Walk-in')
❑ Low Energy Space Category3
Space Conditioning
Eligible Low Energy Spaces
Categories
❑ Unconditioned ❑ Low energy heating/cooling capacity
Wireless service ❑ Greenhouse4 ❑ Equipment building
equipment shelter
Floor Area and
Floors Above
Grade
Building Gross Conditioned Floor Area
Project Gross Conditioned Floor Area
Stories
2
9,198
651
Compliance Method 1 - General C Compliance Method 2 - Total Building
Compliance Method 1 - Projects shall demonstrate compliance with all applicable mandatory and
General Compliance
prescriptive requirements of this code. Refer to C401.2, Item 1 for more information. Compliance forms to
include with a Prescriptive submittal: All applicable ENV, LTG, and MECH.
Path
Compliance Method 2 - Projects complying via total building performance (TBP) shall include a summary
of results from a whole building energy model per Section C407 and shall demonstrate compliance with all
applicable mandatory provisions in this Code. Refer to Section C401.2, Item 2 for more information.
Compliance forms to include with a TBP submittal: PROJ-SUM, ENV-CHK, LTG-EXT, LTG-CHK, and all
MECH forms except MECH-ECONO and MECH-VENT (pending).
Note 1 - Refrigerated Spaces - They shall comply with the envelope and refrigeration equipment requirements in Section C410. Warehouse
coolers and freezers shall also comply with the envelope requirements in C402. C410 takes precedent for overlapping requirements.
Note 2 - Semi -heated Spaces - If heated with equipment other than electric resistance may take an exemption for wall insulation. All other
envelope assemblies shall comply with the thermal envelope provisions.
Note 3 - Exemptions For Low Energy Spaces - Low Energy spaces are exempt from all provisions in WSEC Section C402 Building Envelope,
however all other applicable provisions in the Code do apply including lighting, mechanical, service water heating, etc.
Note 4 - Eligible Space Conditioning For Low Energy Greenhouses - Greenhouses are defined as spaces that maintain a specialized sunlit
environment that is used exclusively for cultivation, protection and maintenance of plants. Cooling with outside air and/or evaporative
cooling, and any form of heating equipment, are allowed under the Low Energy Greenhouse category. Greenhouses with cooling
equipment that requires a condensing unit are NOT eligible.
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
General Info
I Project Title: Firdale Village Fire Restoration
Date 9/28/2020
C406 Additional
Building level efficiency options:
Current Scope
Previous Projects
C406.8 Enhanced envelope performance
❑
❑
Efficiency Package
Options Summary
C406.9 Reduced air infiltration
❑
❑
A minimum of two Options are
required for new construction,
C406.5 On -site renewable energy
❑
❑
Building area level efficiency options
and change in space
conditioning or occupancy
C406.2 More efficient HVAC equipment
❑
❑
projects.
Select all Options included in
C406.6 Dedicated outside air systems (DOAS)
❑
❑
the current project scope.
Also select Options complied
C406.7 Reduced energy use in service water heating
❑
❑
with under previous projects
(shell and core, other tenant
C406.3 Reduced lighting power
❑
❑
spaces in building, etc)
Buildings with multiple tenant
C406.4 Enhanced digital lighting controls
❑
❑
spaces may comply with
different options (mix &
C406 Comments:
match).
Options are required for all
space conditioning categories.
Include discipline specific
information for C406 options
in ENV -SUM, LTG -SUM and
Refer to SBCC website for
official interpretations
regarding C406 provisions.
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
Project Info
Project Title: Firdale Village Fire Restoration
Date 09/28/2020
Applicant Info.
Company Name: BC Investigative Engineers
For Building Department Use
Company Address: 3605 C St NE, Auburn, WA 98002
Provide contact
information for
Applicant Name: Jesse Binford
individual who can
respond to inquiries
about information
lApplicant Phone: 253-833-5557
provided.
Applicant Email: jbinford@bcie.net
Project Description
❑ New Building ❑ Addition 0 Alteration ❑ No Envelope Scope
Envelope Project Scope
Q All Commercial ❑ Group R - Commercial ❑ Mixed Use - Commercial + Group R
Select all that apply.
❑ Semi -heated ❑ Refrigerated Cooler ❑ Refrigerated Freezer ❑ Equipment Building
Envelope Description
Fire Damage repair: Smoke seal & paint. Isolated ceiling and wall repairs
Provide brief description of the project and
relevant supporting documentation.
If project includes multiple Target Insulation
Allowance areas, and/or is demonstrating
compliance as an Addition + Existing,
Alteration + Existing, or
Addition + Alteration + Existing project,
provide a brief summary of the approach to
whole building compliance.
Air Barrier Testing
❑ Air barrier testing per Section C402.5.1.2 included in project scope
Air barrier testing is required for all new
construction projects. Testing criteria is 0.40
❑ Additional Efficiency Package Option - C406.9 Reduced Air Infiltration
cfm/ft2 under test pressure of 0.3 inch w.g.
Fire Damage repair. Only exterior work is roof replacement.
To comply with C406.9, demonstrate that
Q Testing not required. Explanation, No changes to existing envelope.
measured air leakage of building envelope
Compliance Documentation Scope and Method
Scope of This Calculation
❑ New Building ❑ Addition ❑� Alteration ❑ No Envelope Scope
Target Insulation Allowance
O Fully Conditioned - Commercial, Group R, Mixed Use
Sets the title and calculations in the
compliance forms. Selection required
❑ Semi -heated ❑ Refrigerated Cooler ❑ Refrigerated Freezer
to enable forms.
If project includes more than one Target Insulation Allowance area, and/or if project includes
addition and alteration areas complying independently, for each area complete an ENV -SUM
form Rows 16-46 and either an ENV -PRESCRIPTIVE form, or ENV-UA + ENV-SHGC forms if
demonstrating compliance via component performance.
Envelope Compliance Path
Q Prescriptive ❑ Component Performance
Selection required to enable forms.
Component Performance
❑ Change of Occupancy (C503.2) / Conditioning (C505) - 10% higher UA allowed
Calculation Adjustments
❑ Additional Efficiency Package Option - C406.8 Enhanced Envelope - 15% lower UA required
Additions ❑ Addition stand alone ❑ Addition + Existing
Addition stand alone - Complete Vertical Fenestration and Skylight Area Calculation. Enter total existing -to -remain wall, roof, vertical
fenestration and skylight areas as EXISTING. Enter total addition envelope assembly areas as NEW. If resulting total building WWR exceeds
30% and/or SSR exceeds 5%, refer to C502.2.1 and C502.2.2 for prescriptive compliance alternatives. If complying via component
performance, complete ENV-UA per instructions for addition stand alone projects.
Addition + existing - Complete ENV-UA per instructions for addtion + existing projects.
Alterations - ❑ Replacement windows only, or resulting ❑ Total building WWR increased by
Fenestration and Skylight total building WWR <_ original WWR
❑ Replacement skylights only, or resulting ❑ Total building SRR increased by alteration
total building SRR <_ original SRR
WWR and SRR not increased - Vertical Fenestration and Skylight Area Calculation not required.
WWR and/or SRR increased - Complete Vertical Fenestration and Skylight Area Calculation. Enter total existing -to -remain wall, roof, vertical
fenestration and skylight areas as EXISTING. Enter total altered envelope assembly areas as NEW. If resulting total building WWR exceeds
30% and/or SSR exceeds 5%, refer to C503.3.2 and C503.3.3 for prescriptive compliance alternatives. If complying via component
performance, complete ENV-UA per instructions for alteration + existing projects.
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
Project Title: Firdale Village Fire Restoration
Date 09/28/2020
Vertical Fenestration and
Skylight Area Calculation
Total Vertical
Fenestration Area
(rough opening)
NET Exterior
Above Grade
Wall Area
Total Skylight Area
(rough opening)
NET Exterior Roof
Area
Prescriptive Path - Enter envelope sf
values directly into this section of ENV -SUM
New
20
0
0
0
Existing
40
116
0
651
for vertical fenestration, skylights, net walls
and roof. For Additions and Alterations, refer
to these sections in ENV -SUM for further
instructions.
Total
60
116
0
651
Component Performance - When this
Envelope Compliance Path is selected,
write -protection of this section is enabled.
Enter envelope sf values for all assemblies
into the ENV-UA form. Envelope information
from ENV-UA will auto -fill into this section of
Vertical u
Fenestration -to- 34.1 /o
Wall Ratio (WWR)
Skylight -to -Roof
Ratio (SRR)
SRR
Project exceeds maximum vertical fenestration area allowed for Prescriptive compliance.
Vertical Fenestration Area Compliance
May comply prescriptively using a vertical fenestration alternate or via Component
Performance with Target Area Adjustment.
NO SKYLIGHT PROPOSED. COMPILIES WITH MAXIMUM ALLOWANCE.
Skylight Area Compliance
Vertical Fenestration
D High performance fenestration U-factors and SHGC per C402.4.1.3
Alternates
C) Dedicated outdoor air system per C402.4.1.4 and C403.6
Show locations of qualifying daylight zone i) In buildings >_ 3 stories, 25% or more of NET floor area is in DLZ per C402.4.1.1
(DLZ) areas and ft2 on project plans.
In buildings < 3 stories, 50% or more of CONDITIONED floor area is within DLZ per
For Daylight Zone Area Calculations - C402.4.1.1
a) Sidelight areas include primary+ Daylight Zone Calculations
secondary daylight zone areas. Not Selected. No Calculations Sidelight Daylight Toplight Daylight Percent Daylight
b) Include overlapping toplight and sidelight Required Zone Area Zone Area Zone Area
daylight zone areas under Toplight.
c) Net floor area definition in Chapter 2.
Spaces in Single Story List all enclosed spaces that exceed 2,500 W, have ceiling height greater than 15 ft, and are
Building Requiring Skylights space types required to comply with this provision. Indicate aperture with 'AP" prefix (AP 1.1 %)
In these spaces a minimum of 50% of the Space Space Area (ft2) DLZ Area (ft) SRR or Aperture Exception
floor area shall be within a skylight daylight
zone (DLZ). Refer to C402.4.2 for
requirements.
SRR = Skylight to roof ratio
Envelope Exemptions
Low Energy and Semi -heated
Spaces
Low energy spaces per C402.1.1 Item 1 are exempt from the thermal envelope provisions.
Semi -heated spaces heated by systems other than electric resistance are exempt from wall
insulation provision only per C402.1.1.1.
Complete Low Energy and Semi -Heated Spaces table in MECH-SUM to verify eligibility based
on installed peak heating and cooling capacity per sf.
Equipment Buildings
Wall Insulation
R-Value
Roof Insulation
R-Value
Overall Average
U-Factor
Equipment buildings are exempt from the
thermal envelope provisions per C402.1.2.
Equipment Building Envelope
Electronic equipment power (watts/sf)
The following shall be met to be eligible:
building size <_ 500 sf, average wall/roof U-
factor <_ U-0.20, electronic equipment load >_
Heating system output capacity (Btu/hr)
7 watts/sf, heating system output capacity <_
Cooling capacity (Yes/No)
17, 000 btu/h. Cooling system capacity not
limited.
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
Minimum Requirements This table summarizes prescriptive compliance requirements for opaque elements and fenestration. Refer
for Prescriptive Compliance to Tables C402.1.3, C402.1.4 and C402.4 in the 2015 WSEC for important footnotes that apply to
these tables. Refer to Section C402 for all applicable requirements for each envelope element type and
applicable exceptions. Refer to Section C410 for all applicable information for refrigerated spaces.
Prescriptive Path
Table C402.1.3 Notes 1,7
Insulation Minimum R-Value
Table C402.1.4 Notes 1,2
Assembly Maximum U-factor
Occupancy Group
All Other Group R
All Other Group R
Opaque Elements
Roofs
Insulation Entirely above Deck
R-38 c.i.
R-38 c.i.
U-0.027
U-0.027
Metal Building with thermalspacer block Note 3
R-25 + R-11 Ls
R-25 + R-11 Ls
U-0.031
U-0.031
Attic and Other
R-49
R-49
U-0.021
U-0.021
Joist or single rafter
R-49
R-49
U-0.027
U-0.027
Walls, Above grade
Mass
R-9.5 c.i. Note 6
R-13.3 c.i.
U-0.104 Note 6
U-0.078
Mass transfer deck slab edge
No R-Value for prescriptive compliance
U-0.200
U-0.200
Metal Building
R-19 c.i.
R-19 c.i.
U-0.052
U-0.052
Steel Framed
R-13 + R-10c.i.
R-19 + R-8.5 c.i.
U-0.055
U-0.055
Wood Framed and Other
R-21 w/ int. frame
R-21 w/ int. frame
U-0.054
U-0.054
Below Grade Wall Note 4
Same as above grade
Same as above
grade
Floors
Mass
R-30 c.i.
R-30 c.i.
U-0.031
U-0.031
Steel Joist
R-38 + R-10 c.i.
R-38 + R-10 c.i.
U-0.029
U-0.029
Wood Framed and Other
R-30
R-30
U-0.029
U-0.029
Slab -On -Grade Floors
Unheated
R-10 for 24 in. (from top of slab)
F-0.54
F-0.54
Heated Note 5
R-10 perimeter & under entire slab
F-0.55
F-0.55
Opaque Doors
Swinging
No R-Value for prescriptive compliance
U-0.37
U-0.37
Nonswin in(Roll-up or sliding)
R-4.75 I R-4.75
U-0.34
U-0.34
Table C402.4 - 0-30% of wall area, or
30%-40%per Section C402.4.1.1 DLZ
or Section C402.4.1.4 DOAS
Section C402.4.1.3 High Performance
Fenestration Option - 0-40% of wall area
Fenestration
Assembly Maximum U-factor Notes 1,2
Vertical Fenestration
Nonmetal framing
U-0.30
U-0.30
U-0.28
U-0.28
Metal framing (fixed)
U-0.38
U-0.38
U-0.34
U-0.34
Metal framing (operable)
U-0.40
U-0.40
U-0.36
U-0.36
Entrance doors
U-0.60
U-0.60
U-0.60
U-0.60
Skylights
Skylights
U-0.50 U-0.50 U-0.50 U-0.50
Fenestration
Assembly Maximum SHGC Factor
Vertical Fenestration
PF<0.2: north - SHGC=0.53;
all other SHGC=0.4
0.25 PF < 0.5: north - SHGC-0.58;
all other - SHGC-0.48
PF >_ 0.5: all orientations - SHGC-0.64
PF<0.2: north - SHGC=0.46;
all other SHGC=0.35
0.25 PF < 0.5: north - SHGC-0.51;
all other - SHGC-0.42
PF >_ 0.5: all orientations - SHGC-0.56
Skylights
SHGC-0.35
SHGC-0.35
C410.2 Refrigerated Spaces Insulation
Insulation Minimum R-Value
Assembly Maximum U-factor
Freezers - Walk-in and Warehouse
Roof / Ceiling
R-32
U-0.030
Wall
R-32
U-0.030
Door
R-32
U-0.030
Door - transparent reach -in
triple -pane, heat -reflective treated or gas
Floor
R-28
U-0.035
Coolers - Walk-in and Warehouse
Roof / Ceiling
R-25
U-0.039
Wall
R-25
U-0.039
Door
R-25
U-0.039
Door - transparent reach -in
double -pane, heat -reflective treated &
gas fill, or comply with freezer door req.
Floor
I No Requirement
5 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
Ls = Liner system -- A continuous membrane installed below the purlins and uninterrupted by framing members. Uncompressed, unfaced
insulation rests on top of the membrane between the purlins. Refer to Section A102.2.5.4.
c.i. = Continuous insulation -- Insulation that is continuous across all structural members without thermal bridges other than service
openings and penetrations by metal fasteners with a x-sectional area of less than 0.04% of the opaque surface area of the assembly.
Components with more than 0.04% metal penetrations may be eligible to follow the alternate CI values below.
int = Intermediate framing -- Includes insulated headers, corners and interior partition wall to exterior wall intersections. Refer to Section
A103.2 for framing definitions.
ootnote Summary:
Each table in the 2015 WSEC has footnotes applicable to specific information provided in the table. This footnote summary provides only
abbreviated details from these footnotes. Refer to 2015 WSEC for complete footnote information.
Note 1 - Assembly descriptions can be found in Chapter 2 and Appendix A.
Note 2 - Use of assembly U-factors, C-factors and F-factors from Appendix A and Chapter 3 are required unless otherwise allowed
by the provisions of this Code.
Note 3 - For metal building roofs where using R-value compliance method, a thermal spacer block with minimum thickness of 1/2-inch
and minimum R-value of R-3.5 is required. Otherwise use the U-factor compliance method.
Note 4 - Where heated slabs are below -grade, they shall comply with the F-factor requirements for slab -on -grade heated slabs.
Note 5 - Heated slab F-factors shall be determined specifically for heated slabs. Unheated slab F-factors shall not be used.
Note 6 - CMU walls in all occupancies other than Group R may be eligible for reduced insulation if all provisions stated in applicable
footnote are met. Refer to Footnote D in Table C402.1.4 or Footnote C in Table C402.1.3 for eligibility requirements.
Note 7 - Components with continuous insulation but with metal penetrations / connections may be eligible for alternate continuous
insulation R-values if all provisions in applicable footnote are met. Refer to alternate prescriptive R-values in table below
and Footnote G in Table C402.1.3 for eligibility requirements.
Alternate continuous insulation nominal R-values
This alternate nominal R-value compliance option is allowed for projects complying with all of the following:
1. The ratio of the cross -sectional area, as measured in the plane of the surface, of metal penetrations of otherwise continuous
insulation to the opaque surface area of the assembly is greater than 0.0004 (0.04%), but less than 0.0012 (0.12%).
2. The metal penetrations of otherwise continuous insulation are isolated or discontinuous (e.g., brick ties or other
discontinuous metal attachments, offset brackets supporting shelf angles that allow insulation to go between the shelf
angle and the primary portions of the wall structure). No continuous metal elements (e.g., metal studs, z-girts, z-channels,
shelf angles) penetrate the otherwise continuous portion of the insulation.
3. Building permit drawings shall contain details showing the locations and dimensions of all the metal penetrations (e.g.,
brick ties or other discontinuous metal attachments, offset brackets, etc.) of otherwise continuous insulation. In addition,
calculations shall be provided showing the ratio of the cross -sectional area of metal penetrations of otherwise continuous
Assemblies with
C9nCnLU 4U:
1¢'.u]7r100 {'.ea
dafinioonJ
#lte mote uptim for assemblies with
m etal Re Detl3&.05, greater 1h3n
0.04a13 bat less than108"
Alternate uptiun EDY assemblies with
metal Pe¢e tr A Lions, Brea ter than of
equal to 0.084!13 bit Less thsa0.12EA
P- 4.5a
R-11.9€i
R-13ci
R-11.4d
R-14.3€i
1-15.7€i
R-1.336
R-16.6ci
R-18.3d
R-15.2d
R-19.0d
R-2ld
R-30d
R-38d
R42d
R-38d
R-tSd
R-53ci
R-13+R-7.5d
R-13+R-9.4d
R-13+R-10.3d
R-13 + R-10d
R-13 + F. 12.5ci
R-13 +R-13.8€i
R-13 + R-12.5 c:
R-13 + R-15.60
R-13 +R-17.2d
R-13 + R-13ci
R-13 + R-16.3d
R-13 +R-17.9d
R-19+R4.5d
R-19+R-10.6d
R-19+R-11.7d
R-19 + R-14€i
R-19 + R-17.5ci
R-19 +R-19.2d
R-19+R-1&i
R-19+R-20ci
R-19+R-22ci
R-20 + R-3.6d
R-24 + R4.8d
R-20 .+R-53ci
R-21 +R-56
R-21 + Rfi.3d
R-21 + R-6.4d
End of Envelope Requirements Summary
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
Project Title: Firdale Village Fire Restoration
Date 09/28/2020
Target Insulation Allowance
For Building Department Use
Fully Conditioned Space - Commercial, Group R, Mixed Use
Fenestration Area as % gross above -grade wall area 34.1 % Max. Target: 30.0%
Skylight Area as % gross roof area 0.0% Max. Target: 5.0%
Vertical Fenestration Alternates: None Selected on ENV -SUM
User Note
Prescriptive compliance of envelope assemblies may be accomplished by providing insulation R-values per Table C402.1.3 or U-factors / F-
factors
per Tables C402.1.4 and C402.4. A single project may comply via R-values for some envelope assemblies and U-factors / F-factors for others.
U-Facto r/F-Factor Method for
Building Component
R-Value Method for Prescriptive Compliance
Prescriptive Compliance
on inuous
o Area ot Metal
Cavity Ins.
Ins. (Cl)
Penetrations
Assembly
Provide plan/detail # of assembly and description
R-Value
R-Value'
in Cl'
U-Factor
U-Factor Source3
Y
O
N
m
O
O
O
L
O
L_
O
U
Q
Dtl A/A3.0 & A/A3.1 - Ceiling below vented attic
R-49
0.027
Table A102.1
0
U)
-o
m
m
0
—
�
>
Dtl A/A3.0 & A/A3.1
R-15
0.076
Table A103.3.1(3)
�O
Wood -lap siding, PWD sheathing, 2x4 Studs
Q
0 O
=
m
o
�
0
m
O
N
m
c
m
H
—
o
m
U)
O
(7
@
a
Dtl A/A3.0 & A3.1
Existing,
E
6" Concrete Basement wall, 2x4 furring studs, existing
Assumeedd
0.054
Table A104.1
o
insulation and sheetrock
o
a
v
m
0
o
n
a
CO
o
(7
m
0
o
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1 Revised Dec 2019
Project Title: Firdale Village Fire Restoration
Date 09/28/2020
Fenestration Area as % gross above -grade wall area 34.1% Max. Target: 30.0%
For Building Department Use
Skylight Area as % gross roof area 0.0% Max. Target: 5.0%
If vertical fenestration or skylight area exceeds maximum allowed per C402.4.1, then the project must
comply via Component Performance and provide ENV-UA and ENV-SHGC forms.
Building Component
R-Value Method for
U-Facto r/F-Factor Method for
Prescriptive Compliance
Prescriptive Compliance
Perim. Ins.
Full Slab Cl
Provide plan/detail # of assembly and description
R-Value
R-Value
F-Factor
F-Factor Source10
Detail A/A3.0 & A/A3.1
Unheated conc slab. Existing condition. Unknown if
0.730
Table A106.1
insulation was placed below slab when building was
m
c
originally constructed
0
0
a
m
U
0
m
0
2
Ins.
Assembly
,�
Provide ID from door schedule and description
R-Value
U-Factor
U Factor Source
0
Door Schedule ID 'V on Sheet A1.0.
a
Nonmetal Door, 50% Glazed
0.550
Table C303.1.3(1)
0
0
a)U
.3
)
0
m
O
Q)
L
O
Solar Heat Gain Coefficient (SHGC)
U-Factor for Prescriptive Compliance
rolec ion
Unentation
Factor (PF)
(N or
Assembly
Assembly
Provide ID from window schedule and description
if applicable 12
SEW)13
SHGC14
U-Factor
U-Factor Source 14
@
No windows are being replaced
0
0
z
0
0
0
.x
w
m
m
c
LL
a)
a
U_
0_
p
N
(6
C
N
derri�ath a slab -on -grade or exposed floor, this floor shall be thermally broken from the surrounding floor area with the same amount of insulation as re
0
0-
01
T
CO
Q
Miscellaneous - Refrigerated Spaces
Ins.
Assembly
Provide plan/detail # of assembly and description
R-Value
U-Factor
U-Factor Source
�B �-
N
O O
N
_O
LL LL
Cooler /
Double
Triple Pane
Inert Gas
Heat Reflective
Provide ID from window schedule and description
Freezer
Pane Glass
Glass
Filled
Treated Glass
`o
0
p
s=
s=
N
@
O
L
N
Note 1- Insulation that is continuous except for fasteners may be entered here if the cross -sectional area of metal penetration through otherwise
continuous insulation is less than 0.12%.
Note 2 - Alternate prescriptive continuous insulation R-values per Table C402.1.4, Footnote F may be used if the cross sectional area of metal
penetrations exceeds 0.04% but is less than 0.12%. Calculations are required to use these alternate R-values.
Note 3 - Opaque assembly U-factors shall come from Appendix A or calculated per approved method as specified in C402.1.5.1. Specify the
table number or calculation page number.
Note 4 - Thermal spacer blocking and liner system are required for prescriptive R-Value compliance in metal building roof assemblies. Note thermal
spacer thickness and R-value in roof assembly description.
Note 5 - Intermediate framing is required for prescriptive R-Value compliance in wood -framed wall assemblies.
Note 6 - Proposed CMU mass walls in non -Group R that meet Table C402.1.4 Footnote C requirements can enter the target prescriptive
U-value of 0.104.
Note 7 - Mass transfer slab edges must be covered with an assembly having an overall U-factor of 0.2.
Note 8 - Refer to Table C402.1.3, Footnote E for prescriptive R-Value requirement for steel floor joist assemblies.
Note 9 - Prescriptive slab -on -grade insulation shall extend from top of slab to minimum length per an approved method as defined in C402.2.6.
Note 10 - Slab -on -grade F-Factors shall come from Appendix A or calculated per approved method as specified in C402.1.5.1.
Note 11 - Opaque door U-factors shall come from Appendix A or calculated per approved method as specified in C402.1.5.1. A door is defined as
opaque if less than 50% of the door area has glazing.
Note 12 - Refer to Equation C4-6 Projection Factor Calculation.
Note 13 - N = Oriented within 45 degrees of true north, SEW = All other orientations.
Note 14 - Fenestration assembly U-Factor and SHGC shall be the manufacturer's NFRC product rating, which includes the glazing and frame, or
shall be the default value per Section C303.1.3.
Note 15 - List all above -grade Group R mass walls and steel frame walls in Group R Walls section. List commercial above grade walls and all other
Group R above grade walls in Opaque Walls - Above Grade.
Note 16 - Refrigerated Coolers - All cooler roof, wall and door assemblies shall comply with the prescriptive R-values or U-factors per C410. Enter
proposed information under the most similar assembly type. Slab edge insulation for slab -on -grade floors shall comply with C402. Floors
that
separate a cooler from a non -cooler space (unconditioned and conditioned) shall be insulated per C402. Vertical fenestration (not within
cooler doors) shall comply with the prescriptive R-values or U-factors per C402. Enter only the opaque portion of refrigerated space doors.
Windows within doors and reach -in display case doors shall comply with C410 prescriptive requirements.
Note 17 - Refrigerated Freezers - All freezer roof, wall and door assemblies shall comply with the prescriptive R-values or U-factors per C410. Enter
proposed information under the most similar assembly type. Freezer floor insulation shall comply with C410. Insulation is required under the
entire freezer floor. If the freezer floor assembly rests on top of a standard floor, the vertical edge of the freezer floor shall be entered as and
comply with the requirements for a freezer wall. If freezer floor insulation is installed as integral to or applied underneath a slab -on -grade or
exposed floor, this floor shall be thermally broken from the surrounding floor area with the same amount of insulation as required for a