FIR2021-0039+Fire_Sprinkler_Equipment_Specification_Sheets+4.23.2021_11.50.06_AM+2161138NOR TNWES T FIRE SYSTEMS 2545 83,d Ave. ., Bldg D * Kent, WA 98032 Ph: 206.772.7502 * Fax; 206.772.7504 Www.nwfiresysterns.corn LIC # NORTHF59 8CR EQUIPMENT SUBMITTAL MAIN ST COMMONS FIRE SPRINKLER RETRO FIT EDMONDS, WA NWSF JOB NO. 05043C TABLE OF CONTENTS Rows to Form Type to print Number Abbr. x Section 1 - Pipe and Fittings x Comments x 01-009 G Victaulic_75-Flex_Coupling x 01-011 G Victaulic_744_Firelock Flange Adapter x 01-013 G Victaulic_Firelock Fittings 10.03 x 01-016 P Bull Moose Eddy Flow Pipe x 01-018 P Wheatland_Sch 10 & Sch 40 Pipe x x Section 2 - Hangers and Sway Bracinq x x 02-007 A Anvil _146_All Thread Rod x 02-010 A Tolco_130_TJI Beam Clamp x 02-027 EQ Tolco_980_Universal Sway Brace Attachment x 02-029 EQ Tolco_4a_Pipe Clamp For Sway Brace x 02-036 F Sammy_Sidewinders x 02-040 H Anvil _69_Hanger Ring x 02-054 EQ Tolco_1001_Fast Clamp Sway Brace Attachment x 02-063 Tolco Fig 25 Surge Restrainer x x Section 3 - Valves and Accessories x x 03-008 BV Tyco_BFV-N_ Grooved Butterfly Valve x 03-037 RM Tyco_RM-1 Riser Manifold x 03-047 CV Tyco_CV-1 F_Check Valve x x Section 4 - Alarms and Supervisory Devices x x 04-008 Potter_VSR-F_Waterflow Switch x x Section 5 - Fire Sprinklers x x 05-001 D Tyco_DS-1_QR,SR_EC Dry Horz Sw_K=5.6 x 05-059 SS Tyco_TY-FRB_QR_SSP,SSU,Rec Pend_K=2.8,5.6,8.0 All variations used 00-002 Table Of Contents.xls Page 1 of 1 4/6/2021 SECTION 1 PIPE AND FITTINGS Victaulic° Flexible Coupling ✓ctaulic® Style 75 06.05 1 — 87DN25 — DN200 1.0 PRODUCT DESCRIPTION Available Sizes • 1 — 87DN25 — DN200 Pipe Material • Carbon steel • Stainless steel Maximum Working Pressure • Accommodates pressures ranging from full vacuum (29.9 in Hg/760 mm Hg) up to 500 psi/3447 kPa/34 bar • Working pressure dependent on material, wall thickness and size of pipe Application • Joins standard roll grooved and cut grooved pipe, as well as grooved fittings, valves and accessories • Provides a flexible pipe joint which allows for expansion, contraction and deflection • Up to 50% lighter in weight than standard Victaulic Style 77 or Style 177N flexible couplings 2.0 CERTIFICATION/LISTINGS D& FM VdS LPCB fl- LISTED NOTES • Download publication 10.01 for Fire Protection Certifications/Listings Reference Guide. • See publication 02.06: Victaulic Potable Water Approvals ANSI/NSF for potable water approvals if applicable. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Submitted By Date U4421E1ir rnm Spec Section Paragraph Approved Date 06.05 1470 Rev P Updated 10/2017 © 2017 Victaulic Company. All rights reserved. 1 ✓ctaulic° victaulic.com 3.0 SPECIFICATIONS — MATERIAL Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12. Ductile iron conforming to ASTM A395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ❑ Standard: Orange enamel ❑ Optional: Hot dipped galvanized ❑ Optional: Contact Victaulic with your requirements for other coatings. Gasket: (specify choice') ❑ Grade "E" EPDM EPDM (Green stripe color code). Temperature range —30°F to +230°F/-34°C to +110°C. May be specified for hot water service within the specified temperature range plus a variety of dilute acids, oil -free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot +180°F/+82°C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR USE WITH PETROLEUM SERVICES OR STEAM SERVICES. ❑ Grade "T" Nitrile Nitrile (Orange stripe color code). Temperature range —207 to +180°F/-29°C to +82°C. May be specified for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; not compatible for hot dry air over +140°F/+60°C and water over +150°F/+660C. NOT COMPATIBLE FOR USE WITH HOT WATER. ❑ Others For alternate gasket selection, reference publication 05.01: Victaulic Seal Selection Guide - Elastomeric Seal Construction. 1 Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should always be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: (specify choice2) ❑ Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (metric). Carbon steel hex nuts meeting the mechanical property requirements of ASTM A563 Grade B (imperial - heavy hex nuts) and ASTM A563M Class 9 (metric - hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FE5, finish Type III (imperial) or Type II (metric). ❑ Optional (imperial): Stainless steel oval neck track bolts meeting the mechanical property requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy nuts meeting the mechanical property requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling reducing coating. 2 Optional bolts/nuts are available in imperial sizes only. 06.05 1470 Rev P Updated 10/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaulic° victaulic.com 4.0 DIMENSIONS Style 75 Pipe End Deflection from Size Separation3 Centerline Bolt/Nut Dimensions Weight Actual Outside Approx. Nominal Diameter Allowable Per Cplg. Pipe Qty. Size X Y Z (Each) inches inches inches inches/ft. imperial inches inches inches lb DN mm mm Degrees mm/m metric mm mm mm kg 1 1.315 0-0.06 0.57 31/8x 2 2.38 4.27 1.77 1.3 DN25 33.7 0-1.6 20 -43 48 2 M10 x 51 61 108 45 0.6 1 1/4 1.660 0-0.06 2 -10 0 0.45 2 3/8x 2 2.68 4.61 1.77 1.4 DN32 42.4 0-1.6 38 M10 x 51 68 117 45 0.6 1 1/2 1.900 0-0.06 10- 56 0.40 2 % x 2 2.91 4.82 1.77 1.5 DN40 48.3 0-1.6 33 M10 x 51 74 122 45 0.6 2 2.375 0-0.06 10 -31' 0.32 2 % x 2 3.43 5.22 1.88 1.7 DN50 60.3 0-1.6 26 M10 x 51 87 133 48 0.8 21/2 2.875 0-0.06 0 1 15' 0.26 2 1/8x 2 3.88 5.68 1.88 1.9 73.0 0-1.6 22 M10 x 51 98 144 48 0.9 3.000 0-0.06 1 -12 0 0.26 2 3/s x 2 4.00 5.90 1.88 1.9 DN65 76.1 0-1.6 22 M10 x 51 102 150 48 0.9 3 3.500 0-0.06 10- 2 0.22 2 1/2 x 2 3/4 4.50 7.00 1.88 2.9 DN80 88.9 0-1.6 18 M12 x 70 114 178 48 1.3 31/2 4.000 0-0.06 0 0 54' 0.19 2 1/2 x 2 3/4 5.00 7.50 1.88 2.9 DN90 101.6 0-1.6 16 M12 x 70 127 191 48 1.3 4 4.500 0-0.13 10- 36 0.34 2 1/2 x 2 3/4 5.80 8.03 2.13 4.1 DN100 114.3 0-3.2 28 M12 x 70 147 204 54 1.9 4.250 0-0.13 0.35 1/2 x 2 3/4 5.55 7.79 2.13 3.7 108.0 0-3.2 10 41 29 2 M12 x 70 141 198 54 1.7 5.000 0-0.13 0.25 1/8x 31/4 6.13 9.43 2.13 5.5 1 26 0 2 127.0 0-3.2 21 M16x83 156 240 54 2.5 5 5.563 0-0.13 10-18, 0.27 2 5/s x 3 1/4 6.88 10.07 2.13 5.8 141.3 0-3.2 23 M16x83 175 256 54 2.6 5.250 0-0.13 10-21' 0.28 2 5/s x 3 1/4 6.55 9.37 2.13 6.0 133.0 0-3.2 24 M16x83 166 238 54 2.7 5.500 0-0.13 10- 18 0.28 2 1/s x 31/4 6.80 9.59 2.13 6.3 DN125 139.7 0-3.2 24 M16x83 173 244 54 2.9 6.000 0-0.13 0 1 12 0.21 2 1/8x 31/4 7.38 10.48 1.88 6.2 152.4 0-3.2 18 M16x83 187 266 48 2.8 6 6.625 0-0.13 15 0 0.23 2 1/s x 31/4 8.00 11.07 2.13 7.0 DN150 168.3 0-3.2 18 M16x83 203 281 54 3.2 6.250 0-0.13 10-9, 0.24 2 1/s x 31/4 7.63 10.49 2.13 6.8 159.0 0-3.2 20 M16x83 194 266 54 3.1 6.500 0-0.13 17 0- 0.23 2 5/s x 31/4 7.84 10.66 2.08 6.6 165.1 0-3.2 58 M16x83 199 271 53 3.0 8.515 0-0.13 0 0 -51 0.18 2 3/4 x 41/4 10.19 13.75 2.32 13.2 216.3 0-3.2 46 M20 x 108 259 350 59 6.0 8 8.625 0-0.13 00 -50' 0.18 2 3/4 x 41/4 10.34 13.97 2.13 12.4 DN200 219.1 0-3.2 14 M20 x 108 263 355 1 59 1 5.6 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be reduced by: 50 % for 3/4 - 3 V2YDN20 - DN90; 25 % for 4YDN100 and larger. NOTE • Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. 06.05 1470 Rev P Updated 10/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com ✓ctaU1ii& victaulic.com 5.0 PERFORMANCE Style 75 Size Maximum Actual Outside Working Maximum Nominal Diameter Pressure4 End Load4 inches inches psi lb DN mm kPa N 1 1.315 500 680 DN25 33.7 3447 3,025 1 1/4 1.660 500 1080 DN32 42.4 3447 4,805 1 1/2 1.900 500 1420 DN40 48.3 3447 6,320 2 2.375 500 2215 DN50 60.3 3447 9,860 21/2 2.875 500 3245 73.0 3447 14,440 3.000 500 3535 DN65 76.1 3447 15,730 3 3.500 500 4800 DN80 88.9 3447 21,360 31/2 4.000 500 6300 DN90 101.6 3447 28,035 4 4.500 500 7950 DN 100 114.3 3447 35,380 4.250 450 6380 108.0 3103 28,395 5.000 450 8820 127.0 3103 39,250 5 5.563 450 10935 141.3 3103 48,660 5.250 450 9735 133.0 3103 43,325 5.500 450 10665 DN 125 139.7 3103 47,460 6.000 450 12735 152.4 3103 56,670 6 6.625 450 15525 DN 150 168.3 3103 69,085 6.250 450 13800 159.0 3103 61,405 6.500 450 14930 165.1 3103 66,412 1 8.515 450 25625 216.3 3103 113,986 -AM 8 8.625 450 26280 DN200 219.1 3103 116,945 4 Working Pressure and End Load are total, from all internal and external loads, based on ANSI B36.10 sized carbon steel pipe, grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. NOTE • WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1'/2 times the figures shown. 06.05 1470 Rev P Updated 10/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com il ✓ctaii victaulic.com 6.0 NOTIFICATIONS A WARNING • Victaulic RX roll sets must be used when grooving light-wall/thin-wall stainless steel pipe for use with Victaulic Couplings. Failure to use Victaulic RX roll sets when grooving light-wall/thin-wall stainless steel pipe may cause joint failure, resulting in serious personal injury and/or property damage. NOTICE • Victaulic RX grooving rolls must be ordered separately. They are identified by a silver color and the designation RX on the front of the roll sets. 7.0 REFERENCE MATERIALS 02.06: Victaulic@ Potable Water Approvals ANSI/NSF 05.01: Victaulic@ Seal Selection Guide - Elastomeric Seal Construction 06.15: Victaulic@ Pressure Ratings and End Loads for Victaulic Couplings on Steel Pipe 10.01: Victaulic@ Products for Fire Protection Pi inngs Systems - Regulatory Approval Reference Guide 17.01: Victaulic@ Pipe Preparation for Use on Stainless Steel Pipe With Victaulic Products 17.09: Victaulic@ Ductile Iron Grooved Couplings Performance Data for Stainless Steel Pipe 25.01: Victaulic@ Standard Groove Specifications 26.01: Victaulic@ Design Data 29.01: Victaulic@ Terms and Conditions of Sale 1-100: Victaulic@ Field Installation Handbook User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products Victaulic products for a particular end -use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations. instructions. Nothing in this or any other document, nor any verbal recommendation, Installation advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale, installation instructions of the product you are installing. Handbooks are included with each shipment guide, or this disclaimer. of Victaulic products, providing complete installation and assembly data, and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such Trademarks material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right. The terms "Patented" or "Patent Pending" refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. 06.05 1470 Rev P Updated 10/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 5 ✓ctaill CARBONIPS -• -•D10.04 MCTAWO'D ISM ISOMCIRI1FIEDO VRONY Style 744 FireLock° Flange Adapter VC;IC f! ftiwith Vic-PIusT"" Gasket System asket System PRODUCT DESCRIPTION 2 - 8" Sizes DIMENSIONS Style 744 Sizes 2 - 8" (50 - 200 mm) ANSI Class 125 and 150 Flange � 0�0 QA x YW OB° O®a Note: Gray area of mating face must be free from gouges, undulations or deformities of any type for effective sealing. Style 744 FireLock Flange adapter is designed for directly incorporating flanged components with ANSI CL. 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 2 - 8" (50 - 200 mm) are hinged for easy handling with integral end tabs which facilitate assembly. The design incorporates small teeth inside the key shoulder I.D. to prevent rotation. Because of the outside flange dimension, FireLock Flange adapters should not be used on FireLock fittings. When wafer or lug -type valves are used adjoining a Victaulic fitting, check disc dimensions to assure proper clearance. FireLock Flange adapters should not be used as anchor points for tie -rods across nonrestrained joints. Mating rubber faced flanges, valves, etc., require the use of a FireLock Flange washer. FireLock Flange adapters with Vic -Plus gaskets do not require lubrication. The gasket must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. Style 744 FireLock Flange Adapters with the Vic-PIUSTm Gasket System are designed and recommended for use ONLY on fire protection systems. Vic -Plus Gasket System: Victaulic® now offers a gasket system which requires no field lubrication on wet pipe systems. The Vic- PIuSTM System (patented) is dry, clean, and non -toxic. It reduces assembly time substantially and eliminates the mess and chance of over -lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (1-100) for supplemental lubrication requirements. UL ULC FM See Victaulic publication 10.01 for details. Sealing Surface Dimensions Pipe Size Max. Work Max.Incheslmm End Inches/millimeters Aprx wgt. Actual Nominal Outside Press.' Load° No. Bolt Each Diameter Diameter PSI Lbs. Bolts t Size t "A' 119, Lbs. InJmn In./nm kPa N Req'd Inches NLVL Min. w X Y Z kg 2 2.375 175 775 4 s s /$ X 2 /° 2.38 3.41 6.75 6.00 4.75 0.75 2.7 50 60,3 1200 3450 60 87 172 152 121 19 1,2 21/2 2.875 175 1135 4 s /8 X 3 2.88 3.91 7.88 7.00 5.50 0.88 4.2 65 73,0 1200 5050 73 99 200 178 140 22 1,9 3 3.500 175 1685 4 s /8 X 3 3.50 4.53 8.44 7.50 6.00 0.94 4.8 80 88,9 1200 7500 89 115 214 191 152 24 2,2 4 4.500 175 2780 8 s /8 X 3 4.50 5.53 9.94 9.00 7.50 0.94 7.1 100 114,3 1200 11045 114 141 252 229 191 24 3,2 5 5.563 175 4250 8 a /4 X 3 /2 5.56 6.71 11.00 10.00 8.50 1.00 8.3 125 141,3 1200 18920 141 171 279 254 216 25 3,8 6# 6.625 175 6030 8 a /4 X 3 /2 6.63 7.78 12.00 11.00 9.50 1.00 9.3 150 168,3 1200 26840 168 198 305 279 241 25 4,2 8# 8.625 175 10219 8 a /4 X 3 /2 8.63 9.94 14.63 13.50 11.75 1.13 13.9 200 219,1 1200 45475 219 252 372 343 298 29 6,3 *Refer to notes below. tTotal bolts required to be supplied by installer. Bolt sizes for conventional flange -to -flange connection. Larger bolts are required when Vic -Flange adapter is utilized with wafer -type valves. # Not available with Vic -Plus gasket system. Lubrication is required. NOTES * Working Pressure and End Load are total, from all internal and external loads, based on standard weight steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 Y2 times the figures shown. Style 744 FireLock Flange adapters provide rigid joints when used on pipe with standard roll or cut groove dimensions and consequently allow no linear or angular movement at the joint. WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. ® FEGISTSi®TPAD&W;KCFMCTAWC - © OCPYRGHT2004MCTAWC - FRNTEDINUS.A VidalicOmpanyofPrnaica• Rialel-800-RCKMC(1-800-742-5842)• Fac610-250-8817• errEil:0ckAc@Actaiiaoom MctaiicCorrparyofCaTada• RTona905-884-7444• Fac905-884-9774• errel:viccaneda@vidaaliacom MdalicEuope• RtateM-9-381-1500• Fac32-9-380-4438• e-rril:vioaro&ictaIicbe MdalicPrrieicaLdina• R1aTe610-559-3300• F3c610-559-3608• e-rrr3l:vid@daliccom MdalicPdaPadfic• RTona65-6235-3035• Fac65-6235-0535• e-rrt:i1:vica3&ctaIiccom 1477 REV D ZicCta�uli c°° 10.04 VIC-FLANGE ADAPTER NOTES 1 The Style 744 (2 - 8"/50 - 200 mm) design incorporates small teeth inside the key shoulder I.D. to prevent rotation. z FireLock Flange adapter should not be used on FireLock fittings. When wafer or lug -type valves are used adjoining a Victaulic fitting, check disc dimensions to assure proper clearance. 3 FireLock Flange adapters should not be used as anchor points for tie -rods across nonrestrained joints. Mating rubber faced flanges, valves, etc. require the use of a FireLock Flange washer. 4 Area A-B noted in the above drawing must be free from gouges, undulations or deformities of any type for effective sealing. s FireLock Flange adapter gaskets must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. s Flange Washers: FireLock Flange adapters require a smooth hard surface at the mating flange face for effective sealing. Some applications for which the Vic -Flange adapter is otherwise well suited do not provide an adequate mating surface. In such cases, it is recommended that a metal Flange Washer be inserted between the FireLock Flange adapter and the mating flange to provide the necessary sealing surface. Typical applications where a Flange Washer should be used are: A When mating to a serrated flange: a standard flat flange gasket should be used adjacent to the serrated flange and then the Flange Washer is inserted between the FireLock Flange adapter and the flange gasket. B When mating to a wafer valve: where typical valves are rubber lined and partially rubberfaced (smooth or not), the Flange Washer is placed between the valve and the FireLock Flange adapter. C When mating a rubber faced flange: the Flange Washer is placed between the FireLock Flange adapters and the rubber faced flange. D When mating AWWA cast flanges to IPS flanges: the Flange Washer is placed between two FireLock Flanges. The hinge points must be oriented approximately 90° to each other. If one flange is not a FireLock Flange adapter (e.g. flanged valve), then a standard flat flange gasket must be placed adjacent to that flange and the Flange Washer inserted between the flange gasket and the FireLock Flange adapter. E When mating to components (valves, strainers, etc.) where the component flange face has an insert: follow the same arrangement as in Application 1. F When mating to a Series 705-W Butterfly valve, Style 744 may only be used on one side of the connection. When ordering Flange Washers, always specify product style (Style 744) and size to assure proper Flange Washer is supplied. MATERIAL SPECIFICATIONS Flange Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Coating: Black enamel • Optional: Hot dipped galvanized Bolts/Nuts: Supplied by installer Gasket: • Grade "E" EPDM - Type A Vic -Plus Gasket System ❑ (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Ap- proved by Factory Mutual Research forwet and dry (oil free air) sprinkler services up to the rated work- ing pressure using the Grade "E" Type A Vic -Plus Gasket System, requiring no field lubrication for most installation conditions. Standard gasket approved for dry pipe systems to-40OF (-400C). Based on "typical' pipe surface conditions, supplemental lubricant is recommended for services installed below 07 (-18°C) and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water. Supplemental lubrication may also be rquired on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams. This product shall be manufactured by Victaulic Company. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Style 744 FireLock° Flange Adapter Victaulic° FireLockT" Fittings 1.0 PRODUCT DESCRIPTION Available Sizes • 11/a — 87DN32 — DN200 ✓ctaulic® 10.03 Maximum Working Pressure • Pressure ratings for Victaulic FireLockTM Fittings conform to the ratings of Victaulic Fire Lock EZTM Style 009N couplings (refer to publication 10.64 for more information). Application • FireLockTM fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. • Connects pipe, provides change in direction and adapts sizes or components Pipe Materials • Carbon steel 2.0 CERTIFICATION/LISTINGS D@LS F LPCB LISTED VdS C E EN 10311 Regulation (EU) No. 305/2011 3.0 SPECIFICATIONS — MATERIAL Fitting: Ductile iron conforming to ASTM A536, Grade 65-45-12. Fitting Coating: ❑ Orange enamel. ❑ Red enamel in Europe, Middle East, Africa, and India. ❑ Optional: Hot dipped galvanized. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Submitted By Date U442111ir rnm Spec Section Paragraph Approved Date 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. 1 ✓ctaulic° victaulic.com 4.0 DIMENSIONS �CtoE toE� p Cjto 0 0 to E]to J'F olo E No. 001 No. 003 No. 002 No. 006 No. 001 No. 003 No. 002 No. 006 90' Elbow 45° Elbow Straight Tee Cap Actual Approximate Approximate Approximate Approximate Nominal Outside Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each T Each inches inches inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg 11/4 1.660 - - - - - - 0.82 0.3 DN32 42.4 1.900 - - - - - - - - - 21 0.1 0.82 0.4 1 1/2 - - - DN40 48.3 - - - - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 DN50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 21/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 73.0 76 1.4 57 1.0 76 1.6 22 0.5 3.000 3.00 3.30 2.25 2.4 3.00 3.8 DN65 76.1 76 1.5 57 1.1 76 1.7 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 DN80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 4.250 4.00 5.7 3.00 5.1 4.00 7.5 108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 DN100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 141.3 124 5.7 83 3.8 124 7.1 25 1.9 5.500 4.88 12.4 3.25 8.2 4.88 15.4 DN125 139.7 124 5.6 82.6 3.7 124 6.9 6.250 5.50 12.6 3.50 9.2 5.50 17.9 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 DN150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 6.500 5.43 17.6 3.50 11.4 5.50 22.0 165.1 140 7.9 89 5.2 140 9.9 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 DN200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 8.515 6.81 23.1 - - 6.94 33.6 - - 216.3 173 10.5 - - 176 15.2 - - 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaulic® victaulic.com 5.0 PERFORMANCE Flow Data Size Frictional Resistance Equivalent of Straight Pipe' No. 002 Actual Elbows Straight Tee No.001 No.003 Nominal Outside Size Diameter 90° Elbow 45° Elbow Branch Run inches inches feet feet feet feet DN mm meters meters meters meters 1 '/4 1.660 - - DN32 42.4 - - - 1 '/2 1.900 - - - DN40 48.3 - - - 2 2.375 3.5 1.8 8.5 3.5 DN50 60.3 1.1 0.5 2.6 1.1 21/2 2.875 4.3 2.2 10.8 4.3 73.0 1.3 0.7 3.3 1.3 3.000 4.5 2.3 11.0 4.5 DN65 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 DN80 88.9 1.5 0.8 4.0 1.5 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 DN100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 141.3 2.6 1.3 6.4 2.6 5.500 8.3 4.1 20.6 8.3 DN125 139.7 2.5 1.3 6.3 2.5 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 DN 150 168.3 3.0 1.5 7.6 3.0 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 8 8.625 13.0 5.0 33.0 13.0 DN200 1 219.1 4.0 1.5 10.1 4.0 8.515 13.0 - 33.0 13.0 216.3 4.0 - 10.1 4.0 1 The flow data listed is based upon the pressure drop of Schedule 40 pipe. 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com ✓ctaulic® victaulic.com 6.0 NOTIFICATIONS General Notes NOTE: When assembling Fire Lock EZTM couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For Fire Lock EZTM Style 009N/009H couplings, use FireLockTm No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H/009N couplings. 7.0 REFERENCE MATERIALS 10.64: Victaulic@ FireLockTm Rigid Coupling Style 009N 10.02: Victaulic@ Firel-ockTm Rigid Coupling Style 005H with Vic-PIusTm Gasket System 29.01: Victaulic® Terms and Conditions of Sale User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products Victaulic products for a particular end -use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations. instructions. Nothing in this or any other document, nor any verbal recommendation, Installation advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale, installation instructions of the product you are installing. Handbooks are included with each shipment guide, or this disclaimer. of Victaulic products, providing complete installation and assembly data, and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such Trademarks material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right. The terms "Patented" or "Patent Pending" refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 4 ✓ctaill FM Approved and Fully Listed Sprinkler Pipe Wheatland's WLS steel fire sprinkler pipe is hot -dip galvanized to meet FM requirements for dry systems and is UL, C-UL and FM Listed. Approvals and Specifications The product meets or exceeds the following standards: • ASTM: A795, Type F, Grade A • ANSI/ASME B1.20.1 pipe threads • NFPA 13 Manufacturing Protocols WLS is subjected to the toughest possible testing protocols to assure the highest quality and long-lasting performance. Finishes and Coatings WLS is finished in black or hot -dip galvanized. Product Marking Each length of Wheatland fire sprinkler pipe is continuously stenciled to show the manufacturer, type of pipe, grade, size and length. Barcoding is acceptable as a supplementary identification method. PROJECT: ENGINEER: LOCATIONS: ❑ BLACK SPECIFICATIONS NPS NOM OD NOM ID UL CRR* WLS Schedule Schedule Schedule Nominal PCs./ PCs./ WLS 10 40 WLS 40 wt./ft. Lift21' Lift25' 1 1.315 1.087 N/A 1.049 .57 1.00 1.462 70 60 11/4 1.660 1.426 1.442 1.380 .46 1.00 1.928 55 45 1Y2 1.900 1.650 1.682 1.610 .64 1.00 2.370 45 40 2 2.375 2.125 2.157 2.067 .52 1.00 3.004 35 30 * Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category WZY. UL C UL F M APPROVED CONTRACTOR: SPECIFICATION REFERENCE: COMMENTS: ❑ HOT -DIP GALVANIZED DATE: SYSTEM TYPE: 4tWheatland Tube JMC STEEL GROUP IIIII3IIf6741 As the leading supplier of steel sprinkler pipe, we understand that there are no second chances in fire suppression. You need products of enduring quality and exceptional strength -plus reliable service. You need Bull Moose. 0.0. (In) 1.315 1.660 1.900 2.375 2.875 3.500 I I I I 4.500 6,625 8,625 I.O. (In) 1.097 1.442 1.682 2.157 2.635 3.260 4.260 6,357 8,249 Empty Weight (Ib/ft) 1,410 IiiI 1,810 2,090 2,640 3,530 4,340 5,620 91,11,290 16,940 Water Filled Welght (Ib/ft) 1,820 2,518 3,053 4,223 5,893 7,957 11,796 23,038 1 40,086 C.R.R. 15,27 9,91 7,76 5,27 4,92 3,54 2,50 1,158 1,805 PleCes per Uft 91 61 61 37 30 19 19 10 7 Uft Welght (Ibs) 21' lengths 2,695 2,319 2,677 2,051 2,224 1,732 2,242 1,951 2,490 Uft Welght (Ibs) 24' lengths 3,079 2,550 3,060 2,344 2,542 1,979 2,553 2,230 2,848 Uft Welght (Ibs) 25' lengths 3,208 2,760 3,187 2,442 2,648 2,062 2,670 SCHEDULE 10 R 40 ADVANTAGESt • UL listed (US & Canada) and FM approved • ASTM A135 and A795 Type E, Grade A Certified • Complies with NFPA-13,13R and 14 • Industry -leading hydraulic characteristics • CRR of 1.0 and greater • All pipe NDT weld tested c&us LISTED FM APPROVED d I 1,315 1,660 1,900 2,375 2,875 3,500 4.500 1,049 1,380 1,610 2,067 Z459 3,058 4,026 1,680 2,270 2,720 3,660 5,800 7,580 10,800 2,055 2,918 3,602 5,114 1875 10,783 16,316 1.00 1,00 1,00 1,00 1,00 1,00 1,00 70 51 44 30 30 19 19 2,470 2,431 2,513 2,306 3,654 3,024 4,309 2,822 2,778 2,872 2,535 4,175 3,455 4,925 2,940 2,894 2,992 2,745 4,350 3,601 5,130 9r -1111& OTHER BENEFITS/SERVICESt • We have the most stocking locations in the industry, for best delivery and availability • Plain end or roll groove • Eddy Guard II' bacterial -resistant internal coating • Custom length options • Hot dipped galvanization • Reddi-Pipe° red or black pipe eliminates field painting • Compatible for use in wet, dry, preaction and deluge sprinkler systems • The only maker with EPDs (to help earn LEED points). Ono A01L mm NFFW n:sw r»�.•.xw. rnr�rsw� 1p�4�11•r i•uc V ilon 800.325.4467 _ _ _5ales@BUIIMooselndustdes.eom SECTION 2 HANGERS AND SWAY BRACING HANGER RODS Z /ANVIL Fig. 146 Size Range:'/4 through 11/2" Stocked in six, ten, and twelve foot lengths. Other even foot lengths can be furnished to order. Material: Carbon steel or Stainless Steel Gr 304 Threads: National Coarse (USS), rod threaded complete length. Finish: ❑ Plain or❑ zinc Plated (Hot -Dip Galvanized optional) Maximum Temperature: 650' F. Ordering: Specify rod diameter and length, figure number, name and finish. Note: The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. 1,1111111111111111111111111�11111111�111111111111�11111111111111�11�1111111111111111111111111111�11111111111111111111�11111111�111111�111111111111�111111�111111�111111�11�11�11�11�111111�11�11�111111�111111111111111111111111�111111111111 Continuous Threaded Rod FIG.146: LOADS (LBS) • WEIGHTS (LBS) • DIMENSIONS (IN) Rod Size A Threads per Inch Max Load 650° F Weight per Ft. 'A 20 240 0.12 % 16 730 0.30 '/2 13 1,350 0.53 % 11 2,160 0.84 3/a 10 3,230 1.20 7/8 9 4,480 1.70 1 8 5,900 2.30 1'/a 7 9,500 3.60 1'/2 6 13,800 5.10 Note: Other rod sizes available upon request. Class 2 fit is available upon request. PROJECT1 1APPROVAL Project: []Approved Address: []Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.15 Seismic Bracing Fig. 980 - Universal Swivel Sway Brace Attachment - 3/8" to 3/4" Size Range: One size fits bracing pipe 1" (25mm) thru 2" 150mm), B-Line 12 gauge (2.6mm) channel, and all structural steel up to 1/4" 131.7mm) thick. Material: Steel Function: Multi -functional attachment to structure or braced pipe fitting Features: This product's design incorporates a concentric attachment opening which is critical to the performance of structural seismic connections NFPA 13 indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation: Fig.980 is the structural or transitional attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 4L, or other TOLCO approved attachment to pipe to form a complete bracing assembly. NFPA 13 guidelines should be followed. To Install: Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until the head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals: —Approved by Factory Mutual Engineering (FM). For UL Listed information refer to page 66. Note: Fig. 980 Swivel Attachment and Fig. 1000, 1001, 4L or other TOLCO approved attachment to pipe that make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association (NFPA) Finish: Plain, Electro-Galvanized or Stainless Steel. Contact B-Line for alternative finishes. Order By: Figure number and finish. Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174, Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730, Pat. #7,669,806 Designed to meet or exceed requirements of FM DS 2-8. Set Bolt Included Mounting Hardware Is Not Included Fig. 4L Fig. 980 Y u ■ M■ FM APPROVED Longitudinal Brace Part Mtg. Hdw. Mounting Hole Max. Design Load" (FM) Approx. Number Size A B D 30' - 44' 45' - 59' 60' - 74' 75' - 90* wt./100 in. (mm) in. (mm) in. (mm) in. (mm) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs. (kg) 980-3/8 3/8" (9.5) 51/4' (133.3) 17/8" (47.6) 13/32" (10.3) 149 (67.6) 980-1/2 * 1/2" (12.7) 51/4- (133.3) 17/8" (47.6) 17/32" (13.5) 1320 1970 2310 2550 148 (67.1) 980-5/8 5/8" (15.9) 51/4" (133.3) 17/8- (47.6) 11/16" (17.5) (5.87) (8.76) (10.27) (11.34) 147 (66.7) 980-3/4 3/4" (19.0) 51/4' (133.3) 17/8- (47.6) 13/16" (20.5) 146 (66.2) * Standard size. ** Installed with 1" or 11/4" Schedule 40 brace pipe. FM Approved design loads are based on ASD design method Eaton's B-Line Business seismic bracing components are designed to be compatible only with other B-Line bracing components, resulting in a listed seismic bracing assembly. B-Line's warranty for seismic bracing components will be the warranty provided in B-Line's standard terms and conditions of sale made available by B-Line, except that, in addition to the other exclusions from B-Line's warranty, Eaton's B-line Business makes no warranty relating to B-Line's seismic bracing components that are combined with products not provided by Eaton's B-Line Business. All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 67 lne by UJ-N Fig. 4A - Pipe Clamp for Sway Bracing Size Range — 4" thru 8" pipe. For sizes smaller than 4" use TOLCOO Fig. 4. Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada (cUL) 4" thru 8". Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). Installation Instructions — The Fig. 4A is the "braced pipe" attachment component of a longitudinal, lateral or riser brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO transitional and structural attachment component(s) to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 4A over the pipe to be braced. Attach TOLCO transitional fitting, either Fig. 980, 910 or 909, to the clamp ears. Tighten bolts and nuts; torque requirement is a minimum of 50 ft. lbs. Transitional fit- ting attachment can pivot for adjustment to proper brace angle. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size and finish Component of State of California OSHPD Approved C@US LISTED Seismic Restraints System Fig. 4A - Longitudinal Brace Fig. 4A - Lateral Brace R TOLCO® brand bracing components are desgined to be compatible ONLY with other TOLCOO brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance that such TOLCO® brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used. Dimensions • Weights Pipe Max. Horizontal Approx. Sizes A B C D Bolt Size Design Load Wt./100 4 81/2 9/16 33/8 311/16 1 /2 2015 221 5 93/4 9/16 37/8 43/8 1 /2 2015 253 6 111/2 5/8 5 51/8 112 2015 513 8 131/4 3/4 611/16 61/8 1 /2 2015 601 OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX 951.737.0330 m CUSTOMER SERVICE • 800.786.5266 www.tolco.com SIDEWINDERS 0 horizontal mount Screw Box V1wCase Size Wood Approvals Descriptions Qt= 5) Qty 1/4" 8018957 SWG 100 1/4 X 1 25 9.32 125 1/4" 8019957 SWG 200 1/4 X 2 25 10.78 125 UL 3/8" 8020957 SWG 10 1/4 X 1 25 7.88 125 ! UL 3/8" 8021957 SWG 20 1/4 X 2 25 9.45 125 UL 3/8" 8022925 SWG 25-380 3/8 X 2-1/2 25 12.54 125 3/8" 8023925 SWG 30 1/4 X 3 25 10.70 125 �{ Approvals Rod Part Model Screw Box eight Ste e Size No. Descriptions 2L. (per 125) 1/4" 8047957 SWD 100 1 /4-14 X 1 25 9.35 125 1/4" 8049957 SW DR 100 1/4-20 X 1 25 10.37 125 3/8" 8050957 SWD 10 _ 114-14 X 1 25 8.04 125_ 3/8" 8051957 SWD 15 1/4-14 X 1-1/2 25 8.47 125 �r— Part 4 8114910 3/877'1 8052957 ' SWD 20 ' 1/4-14 X 2 25r9.10 3/8" 8053957 SWD 516 5/16-18 X 1-1/4 25 8.94 125 UL-FM 3/8"�054957 ISWDR1-1/2 1/4-20X1-1/2 4^`1111 UL-FM 3/8" 8055957 SWDR 1 1/4-20 X 1 25 9.07 125 56957 - - 3/8" 8057957 SWT 15 12-24 X 1-1/2 25 8.28 125 Approvals Rod V Part M Screw Box W ht Cas Size No. Descriptions Qty. (per 125) Qty Concrete FM 1/4" 8062957 SWC 200 5/16 X 1-3/4 25 11.18 125 3/8" 8061957 SWC 20 5/16 X 1-3/4 25 9.81 125 May e-V41 & -4. S w SxeeQ rat Ott rat ,,� . Head'2MM01001111, Swivel Use with 3/8" '11 Part Screw Box Weight Case • Use #14 Nut Driver (black) Approvals No. Model Descriptions Qty. (per 125) Qty Part No. 8113910. UL-FM 8139957 SH-GST 20 1/4 x 2 25 8.94 125 • 17' deflection from vertical. UL-FM 8141957 SH-GST 30 1/4 x 3 25 10.15 125 U.S. Patent No. UL-FM 8137957 SH-DS roof. 25 125 ' Accommodates to 6,443,680 3-1/2 x 12 pitch roof. SAMMYX-PRESS' Use with 1/4" or : Rod Hang Threaded Rod Approvals Steel Ga. Part No. Model Screw Descriptions Rod Size Max Pipe Size Application Directly from L FM 12 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 4" Metal Deck Thin Gauge Metal Deck FM 12 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 4" Purlin & Purlin UL 22 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" Metal Deck EP = UL 18 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 3 112" Purlin o a UL t 16-12 ga. 8293957 SWXP 35 Sidewinder X-Press 35 3/8-16 3-1/2" Purlin Z UL 22-20 ga. 8294922 SXP 20 Swivel X-Press 20 3/8-16 2" Metal Deck a Ir UL 16-12 ga. 8295922 SXP 35 Swivel X-Press 35 3/8-16 3-1/2" Purlin m Approvals Concrete Part No. Model Screw Descriptions Rod Size Max Pipe Size Thickness Ihm Structural 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" 3000PSI a UL LWC Concrete 8150922 XP 20 Sammy X-Press 20 3/8-16 2-1/2" 35 PCF Approvals Steel Ga. Part No. Model Screw Descriptions Rod Size Load Rating - 22 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 185 lbs. UL 22 ga. 8153922 XP 35 Sammy X-Press 35 3/8-16 185 lbs. - 22 ga. 8181922 XP 200 Sammy X-Press 200 1/4-41 185 lbs. UL 16 ga. 8150922 XP 20 Sammy X-Press 20 3/8-16 250 lbs. 3 16 ga. =8153922 XP 35 Sammy X-Press 35 _/8-16 250 lbs. UL 16 ga. 8181922 XP 200 Sammy X-Press 200 1/4-20 250 lbs. Universal X-Press 8194910 UXPIT Universal X-Pr4s It Tool Installation Tool = 8 8151910 RXPIT Retro Socket for 8151910 - -10 XPDB 25/64 Drill Bit - JUL..,SAMMYS 0 ul eX vertical mount Approvals Screw Weight Case S��p Qty. (per 125) Qty 1/4" 8002957 GST 100 1/4 x 1 _ 25 7.12 125 1/4" 8003957 GST 200 114 x 2 25 8.64 125 80049L7§EILST, 1/4 x 3 25 9.91 125 3/8" 8006957 GST .75 1/4 x 3/4 25 6.24 125 80079577MOCST 10 1/4 x411111irW 25 6.68 125 UL • FM 3/8" 8008957 GST 20 1/4 x 2 25 8.17 125 /8" 80099250- GST 25-380 3/8 x 2-1/2 25 11.27 j&25 UL • FM 3/8" 8010957 GST 30 1/4 x 3 25 9.41 125 Part # 8113910 3/8" 8011925 111111j_ 1/4 x 4 25 10.01 _ 3/8" 8012925 GST 60 1/4 x 6 25 12.72 125 1/2" 8013925 � 1/4 X 2 25 8.99 _ 1/2" 8014925 GST 2.5-380 3/8 X 2-1/2 25 11.99 125 1/2" 8015925 jNEEE&1/4 X 3 25 10.22 125 1/2" 8016925 GST 4 1/4 X 4 25 13.25 125 1/2" 8017925 GS 25 13.69 125 Part # 8114910 Rod ScreA Box Weight Case 1W Model Steel Size Description Qty. (per 125) Qty 1/4" 8024957 DSTR 100 1/4-20 X 1 25 8.20 125 1/4" 8025957 DST 100 1/4-14 X 1 25 7.23 125 /4" Ej,DST 150 1/4-14 X 1-1/2� 125 1/4" 8027957 DST 200 1/4-14 X 2 25 8.31 125 wpm 8 ST 250 1/4-14 X 2-1/2 125 1/4" 8029957 DST 300 1/4-14 X 3 25 9.41 125 030 0 12-24 X 1� � 125 UL • FM 3/8" 8037957 DSTR 1-1/2 12-24 X 1-1/2 25 8.18 125 125 UL • FM 3/8" 8039957 DSTR 516 5/16-18 X 1-1A 25 9.35 125 8040957 -14 X 1 125 3/8" 8041957 DST 15 1/4-14 X 1-1/2 25 7.20 125 8042957 -14 X YjjW 125 3/8" 8043957 DST 25 1/4-14 X 2-1/2 25 8.42 125 8044957 4-14 X � 125 UL • FM 3/8" 8045957 DST 516 5/16-18 X 1-1/4 25 7.79 125 8046957 12-24 X 1' 125 _ 1/2" 8031925 DST 2.0 1 /4-14 X 2 25 8.61 125 I 8032925 4-14 X_� 125 1/2" 8033925 DSTR 1.0 1/4-20 X 1 25 8.61 125 f 2" 8034925 5/16-18 X 1-1A 125 1/2" 8035925 DST 5.16 5/16-18 X 1-1/4 25 8.51 125 M 1/2" 8036925 12-24 X 1-1/2 25 7.75 125 - Concrete Approvals Rod Part Model Screw �ffox Weight Case Size No. Descriptions Qty. (per 125) Qt 1/4" 8058957 CST 200 5/16 x 1-3/4 25 8.44 125 black nut FM 3/8" 8059957 CST 20 5/16 X 1-3/4 25 7.81 125 driver 1/2" 8060925 CST 2 5116 X 1-3/4 8.75 - -red nut driver I I Sammyss, Sammy Super Screws, Sammy Swivel Head'", Sammy X-Press®, Sammy X-Press ITs, Sidewinders®, 800-BUILDER 97 L Swivel X-Press'", and Sidewinder X-Press'" are trademarks of ITW Buildex and Illinois Tool Works, Inc. www.itwbuildex.com © 2007 Illinois Tool Works, Inc. SSS30 PIPE RINGS Z /ANVIL Fig. 69 Adjustable Swivel Ring, Tapped Per NFPA Standards Size Range:'/2" through 8" Material: Carbon steel Finish: ❑ Galvanized Service: Recommended for suspension of non -insulated stationary pipe line. Maximum Temperature: 650° F Approvals: Complies with Federal Specification A-A-1192A (Type 10) WW-H-171-E (Type 70), ANSI/MSS SP-69 and MSS SP-58 (Type 10). UL Listed and FM Approved (Sizes 3/4" - 811). Features: • Threads are countersunk so that they cannot become burred or damaged. • Knurled swivel nut provides vertical adjustment after piping is in place. • Captured swivel nut in the'/2" through 6" sizes. The capture is permanent in the bottom portion of the band, allowing the hanger to be opened during installation if desired, but not allowing the nut to fall completely out. Ordering: Specify size, figure number and name. Note: The acceptability of galvanized coatings at temperatures above 450°F is at the discretion of the end user. Metric nut available upon request. Non -captured nut also available upon request. A i F B C '/z" through 1" pipe through 8" pipe FIG. 69: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN) Pipe Size Max Load Weight Rod Size A B C F 1/2 300 0.10 % 2'/8 2 19/ 6 % 0.10 2% 17/8 16/16 1 0.10 29/ 6 111/ 6 1 11/4 0.10 2% 1 % 7/8 1 1/2 0.10 23/4 17/8 2 0.11 31/4 2% 11/8 21/2 525 0.20 4 2% 16/ 6 3 0.20 313/16 215/ s 13/ s 4 650 0.30 411/16 313/1s 5 1,000 0.54 1/2 5s/6 4% 19/,s 6 0.65 611/16 59/s 21/4 8 1.00 8 7 211/16 Note: Reflects changes in rod diameter from previously published data per recent revisions in MSS-SP-58 & 69 PROJECT INFORMATION Project: APPROVAL STAMP ❑ Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: Catalog PH-2008 Seismic Bracing Fig. 1001 - Sway Brace Attachment Size Range: Pipe size to be braced: 1" (25mm) thru 8" (200mm) IPS. Pipe size used for bracing: 1" (25mm) and 11/4" (32mm) Schedule 40 IPS. Material: Steel Function: For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a complete sway brace assembly. Features: Can be used to brace schedules 7 through 40 IPS. Field adjustable, making critical pre -engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note: Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads bottom out. A minimum of 1" (25mm) pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals: Approved by Factory Mutual Engineering (FM). For UL Listed information refer to page 70. Finish: Plain or Electro-Galvanized. Contact B-Line for alternative finishes and materials. Order By: Order by figure number, pipe size to be braced, followed by pipe size used for bracing (1" (25mm) or 11/4" (32mm)) , and finish. Important Note: Fig. 1001 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance, the FM Approval requires that Fig. 1001 must be used only with other TOLCO bracing products. Designed to meet or exceed requirements of FM IDS 2-8 Y u ■ M■ FM APPROVED Design Load - For Sch. 7, Sch.10, & Sch. 40 Pipe Pipe Part Number & Approx. Wt./100 Allowable Horizontal Capacity (Ibf) Per Installation 1.2,3 Size 1" (24mm) Brace Pipe 11/4" (32mm) Brace Pipe 30D-44° 45D-59° 60D-74° 75°-90° in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (M) Lbs. (kN) Lbs. (M) Lbs. (M) 1- (25) 1001-1 X 1 100.0 (45.3) 1001-1 X 11/4 118.0 (53.5) 1800 (8.00) 2550 (11.34) 3120 (13.88) 3490 (25.52) 11/4"(32) 1001-11/4 X 1 100.0 (45.3) 1001-11/4 X 11/4 114.0 (51.7) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58) 11/2"(40) 1001-11/2 X 1 100.0 (45.3) 1001-11/2 X 11/4 115.0 (52.1) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58) 2- (50) 1001-2 X 1 108.0 (49.0) 1001-2 X 11/4 121.0 (54.9) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58) 21/2"(65) 1001-21/2 X 1 138.6 (62.8) 1001-21/2 X 11/4 160.4 (72.7) 800 (3.56) 1130 (5.02) 1380 (6.14) 1540 (6.85) 3" (80) 1001-3 X 1 147.2 (66.7) 1001-3 X 11/4 168.7 (76,5) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29) 4- (100) 1001-4 X 1 160.9 (73.0) 1001-4 X 11/4 182.4 (82.7) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29) 6- (150) 1001-6 X 1 190.0 (86.2) 1001-6 X 11/4 211.4 (95.9) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40) 8- (200) 1 1001-8 X 1 217.4 (98.6) 1001-8 X 11/4 238.8 (108.3) . 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40) 1 FM Approved when used with 1 or 11/4 inch NPS Schedule 40 GB/T 3091,EN 10255H, or JIS G3451 steel pipe as the brace member. 2 Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as "Schedule 7". These ratings may also be applied when EN 10220 and GB/T 8163 steel pipe. 3 Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H, or JIS G3454, FM Approved Thinwall, or Schedule 40 steel pipes. Note: See UL load ratings in UL Listed Design Load chart shown under drawing. O X All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 71 lne by UJ-N Fig. 25 - Surge Restrainer Size Range — One size fits 3/4" thru 2" pipe. Material — Pre -Galvanized Steel Function — Designed to be used in conjunction with TOLCOO Band Hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer is easily and efficient- ly installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe. Approvals — Underwriters' Laboratories Listed only when used with TOLCO band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and Canada (cUL). Finish — Pre -Galvanized Order By — Figure number and TOLCO band hanger, size from 3/4" thru 2". Patent #5,344,108 C @US LISTED OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 1 www.tolco.com SECTION 3 VALVES AND ACCESSORIES tqC0 Fire &Building Products Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model BFV-N Butterfly Valve Grooved End 2-112 Inch - 10 Inch (DN65 - DN250) General Description The Model BFV-N Grooved End But- terfly Valves (Ref. Figure 1) are indicat- ing type valves designed for use in fire protection systems where a visual in- dication is required as to whether the valve is open or closed. They are used, for example, as system, sectional, and pump water control valves. They have cut groove inlet and outlet connections that are suitable for use with grooved end pipe couplings that are listed and approved for fire protection systems. For applications requiring supervision of the open position of the valve, the Gear Operators for the Model BFV-N Butterfly Valves are provided with two sets of factory installed internal switches each having SPDT contacts. The supervisory switches transfer their electrical contacts when there is move- ment from the valve's normal open po- sition during the first two revolutions of the handwheel. WARNINGS The Model BFV-N Grooved End But- terfly Valves described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Model BFV-N Sizes: ANSI Inches / DN 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250) Approvals The 2-1/2 through 10 inch (DN65 - DN250) Model BFV-N Grooved End Butterfly Valves are UL and C-UL List- ed and FM Approved. In addition, the Model BFV-N Grooved End Butterfly Valves are listed by the California State Fire Marshall under Listing No. 7770-1670:100. All laboratory listings and approvals are for indoor and outdoor use. Maximum Working Pressure • 2-1/2 - 8 Inch (DN65 - DN200): 300 psi (20,7) bar • 10 Inch (DN250): 175 psi (12,0 bar) Materials of Construction: Body Ductile iron conforming to ASTM A-395 Body Coating Polyamide Disc Ductile iron conforming to ASTM A-395 Disc Seal Grade EPDM "E" encapsulated rubber conforming to ASTM D-2000 Upper & Lower Stem Type 416 Stainless Steel conforming to ASTM 582 Lower Plug PVC Operator Gear operator with iron housing Friction Loss The approximate friction loss, based on the Hazen Williams formula and ex- pressed in equivalent length of pipe with C= 120, is as follows. The data is based on friction loss information col- lected at a typical flow rate of 15 feet persecond. • 6.9 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch valve. • 8.7 feet of 3 inch Sch. 40 pipe for the 3 inch valve. • 4.5 feet of 4 inch Sch. 40 pipe for the 4 inch valve. • 6.6 feet of 5 inch Sch. 40 pipe for the 5 inch valve. • 11.1 feet of 6 inch Sch. 40 pipe for the 6 inch valve. • 10.2 feet of 8 inch Sch. 30 pipe for the 8 inch valve. • 12.1 feet of 10 inch Sch. 30 pipe for the 10 inch valve. Page 1 of 4 MAY, 2008 TFP151O Page 2 of 4 TFP1510 Nominal Nominal Installation Dimensions in Inches and (mm) Weight Pipe Valve Sizes O.D. A B C D E IF H �k9) 2-1/2" 2.88 3.85 11.71 3.25 5.43 6.00 7.81 2.50 0 22 DN65 (73,0) (98,0) (297,4) (83,0) (137,9) (152,4) (198,4) (63,5) 0 (10,0) 3" 3.50 3.85 12.25 3.54 5.68 6.00 7.81 2.50 23 DN80 (88,9) (98,0) (311,1) (90,0) (144,2) (152,4) (198,4) (63,5) (10,4) 4" 4.50 4.56 13.95 4.35 6.58 6.00 7.81 2.50 0 28 DN100 (114,3) (116,0) (354,3) (110,0) (167,1) (152,4) (198,4) (63,5) (12,7) 5" 5.56 5.86 14.93 4.84 7.07 6.00 7.81 2.50 0 31 DN125 (141,3) (149,0) (379,2) (123,0) (179,6) (152,4) (198,4) (63,5) (14,1) 6" 6.63 5.86 17.31 5.93 8.35 6.00 7.81 2.50 0.67 41 DN150 (168,3) (149,0) (439,7) (151,0) (212,0) (152,4) (198,4) (63,5) (17,0) (18,6) 8" 8.63 5.26 19.20 6.87 9.29 6.00 7.81 2.50 5.86 53 DN200 (219,1) (134,0) (487,7) (174,0) (236,0) (152,4) (198,4) (63,5) (148,8) (24,1) 10" 10.75 6.29 25.11 9.17 11.50 9.00 7.68 3.00 7.41 88 DN250 (273,1) (160,0) (637,8) (233,0) (292,1) (228,6) (195,1) (76,2) (188,2) (40,0) F HANDWHEEL INDICATOR G FLAG 1/2" NPT CONDUIT ' — CONNECTION GEAR OPERATOR E O DISC c _ BODY D B 1 � , H } A FIGURE 1 MODEL BFV-N GROOVED END BUTTERFLY VALVE - NOMINAL DIMENSIONS - TFP1510 Page 3 of 4 Installation The Model BFV-N Grooved End But- terfly Valves may be installed with flow in either direction and can be posi- tioned either horizontally or vertically. The grooved end pipe couplings used with the Model BFV-N must be listed or approved for fire protection service and installed in accordance with the manufacturers instructions. The Model BFV-N Butterfly Valve may be installed with any schedule of pres- sure class of pipe or tubing that is list- ed or approved for fire protection. As applicable, refer to Figure 2 for the internal switch wiring diagram. Conduit and electrical connections are to be made in accordance with the authority having jurisdiction and/ or the National Electrical Code. With reference to Figure 2, the "supervi- sory switch" is intended for connec- tion to the supervisory circuit of a fire alarm control panel in accordance with NFPA 72. The "auxiliary switch" is in- tended for the unsupervised connec- tion to auxiliary equipment in accor- dance with NFPA 70, National Electric Code. NOTE For outdoor applications with inter- nal supervisory switches, it is recom- mended that wiring connections be made at a temperature above 15°F (-9°C), in order to insure sufficient flex- ibility of the wire lead insulation. Care and Maintenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and devic- es in accordance with the applicable standards of the National Fire Pro- tection Association (e.g., NFPA25), in addition to the standards of any au- thority having jurisdiction. The install- ing contractor or product manufac- turer should be contacted relative to any questions. Any impairment must be immediately corrected. It is recommended that automatic sprinkler systems be inspected, test- ed, and maintained by a qualified in- spection service. r------� SUPERVISORY SWITCH 1UU3: SWITCH SHOWN L J WITH VALVE FULL OPEN w 0 CD O J Q Q > 0 0 END OF LINE PANEL RESISTOR r------� AUXILIARY GND I SWITCH SWITCH SHOWN L J WITH VALVE — — FULL OPEN o W w w p U) 0 0 J 0 > 0 °' 0 z + 0 BELL POWER 0 + CONTACT RATING .... 1/2A @ 125 VDC 1/4A @ 250 VDC 15.1A/12HP @ 125,250 VAC 5A @ 125 VAC "L" FIGURE 2 MODEL BFV-N BUTTERFLY VALVE — INTERNAL SWITCH WIRING DIAGRAM — NOTE Before closing a fire protection system control valve for maintenance or in- spection work on either the valve or fire protection system which it controls, permission to shut down the affected fire protection systems must be ob- tained from the proper authorities and all personnel who may be affected by this decision must be notified. Page 4 of 4 TFP1510 Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warran- ty is given for products or components manufactured by companies not af- filiated by ownership with TFBP or for products and components which have been subject to misuse, improper in- stallation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protec- tion Association, and/or the standards of any other Authorities Having Juris- diction. Materials found by TFBP to be defective shall be either repaired or re- placed, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other ob- ligation in connection with the sale of products or parts of products. TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of merchantability and fitness for a par- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Grooved End Butterfly Valves: Specify: (specify inch size) Model BFV-N Grooved End Butterfly Valve with internal supervisory switches, P/N (specify). Valve Size Valve Part Number 2-1/2......................59-300-F-025N 3..........................59-300-F-030N 4..........................59-300-F-040N 5..........................59-300-F-050N 6..........................59-300-F-060N 8..........................59-300-F-080N 10......................... 59-300-F-100N © 2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 tqC00 Model RM-1 Riser Manifold Commercial and Residential General Description The TYCO commercial and residential Model RM-1 Riser Manifold provide the necessary waterflow alarm, pres- sure gauge, alarm test orifice, drain, and sight glass equipment in a single assembly for use in NFPA 13 com- mercial sprinkler systems and in NFPA 13D/13R residential sprinkler systems as follows: NFPA 13* • 1-1/2 in. (DN40) Male Thread x Female Thread • 2 in.-6 in. (DN50-DN150) Groove x Groove NFPA 13D • 1 in. (DN25) Female Thread x Female Thread NFPA 13R • 1-1/2 in. (DN40) Male Thread x Female Thread • 2 in. (DN50) Groove x Groove Although the Riser Manifold described in this techni- cal data sheet is intended for NFPA 13 sprinkler sys- tems, it may be used for NFPA 13D or 13R residential sprinkler systems, where a test orifice of 2.8K or 4.2K is acceptable. The variety of sizes and grooved end connections allow cost effective and easy transition to check valves, control valves, and system piping. The Model RM-1 Riser Manifolds may be installed either horizontally (flow switch on top) or vertically (flow going up) orientation, for both single sprinkler rises and floor control in high-rises. IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Optional Pressure Relief Kits feature a 175 psi pressure relief valve and trim components for convenient integration into commercial and residential riser manifold assemblies. The pressure relief valve, installed in manifold assemblies above the nor- mally closed test and drain or drain valve, automatically bleeds system pressure exceeding 175 psi through a flexible hose connected to the mani- fold drain outlet (Ref. Figure 5), reduc- ing system pressure to 175 psi. NOTICE The Model RM-1 Riser Manifolds described herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Technical Data Approvals UL and ULC Listed FM Approved Listed by California State Fire Marshall Maximum Working Pressure 300 psi (20,7 bar) Test Orifice 1 in.-3 in. (DN25-DN80) Manifolds: 2.8K 4in.-6 in. (DN100-DN150) Manifolds: 4.2K Finish Red Painted Worldwide I www.tyco-fire.com Contacts Page 1 of 8 AUGUST 2018 TFP963 TFP963 Page 2 of 8 Nominal Nominal End Nominal Dimensions Drain Riser Connections Inches Size Size (mm) Inches Inches (DN) (DN) Inlet Outlet A B C D E F G H 1-1/2 Thread Thread 10 15-1/2 2-1/4 5-5/8 8-3/8 15 4-3/8 1-1/4 (40) MNPT FNPT (254) (394) (57) (143) (213) (381) (111) (32) 2 Groove Groove 13 18 2-1/16 5-5/8 8-3/8 15-1/4 4-3/8 1-1/4 (50) (330) (457) (53) (143) (213) (388) (111) (32) 2-1/2 Groove Groove 13 18-1/16 2-1/16 5-5/8 8-3/8 15-1/4 4-3/8 1-1/4 (65) (330) (460) 1 (53) (143) 1 (213) (388) 1 (111) (32) 3 Groove Groove 13 18-1/16 2-1/16 5-7/8 8-5/8 15-3/4 4-3/8 1-1/4 (80) (330) (460) (53) (150) (219) (400) (111) (32) 4 Groove Groove 13 20-1/4 4-1/4 6-3/4 10-3/4 18-3/8 5-3/16 2 (100) (330) (514) (108) (172) (273) (467) (132) (50) 6 Groove Groove 13 20-1/4 4-1/4 7-3/4 11-3/4 21 6-3/4 2 (150) (330) (514) (108) (197) (300) (533) (172) (50) FIGURE 1 MODEL RM-1 COMMERCIAL RISER MANIFOLDS 1-1/2-6INCH (DN40—DN150) NO DESCRIPTION P/N 1 300 psi/2000 kPa Water Pressure Gauge. .90050001 2 Test and Drain Valve, Model TD-1: 1-1/2-3 Inch (DN40-DN80) Size Manifolds, 1-1/4", 2.81K Orifice..... A61 G0420 4-6 Inch (DN100-DN150) Size Manifolds, 2", 4.2K Orifice........ A61 G0601 3 Flow Switch, VSR-M: 1-1/2"(DN40)......... 91144815 2"(DN50)............ 91144802 2-1/2"(DN65)......... 91144825 3"(DN80)............ 91144803 4"(DN100)........... 91144804 6" (DN150) ...........91144806 4 Field Replaceable Retard/Switch ......... 91144800 TFP963 Page 3 of 8 3-7/8" (100 mm) OPTIONAL PRESSURE RELIEF TRIM 1" NPT CONNECTION (FEMALE) 2FF10" (254 mm) �� 1 2-1/2" NPT ll (64 mm) DRAIN 1 1V 0 (280 mm) NO DESCRIPTION P/N 1 300 psi/2000 kPa Water Pressure Gauge. .90050001 2 Ball Valve, 1" (DN25)....97111603 3 Flow Switch, VSR-M, 1"(DN25)............ 91144801 4 Field Replaceable Retard/Switch ......... 91144800 3-3/4" —X (96 mm) 1 " NPT 3, 4 4-5/8" (FEMALE) (118 mm) 10-1 /8" (257 mm) FIGURE 2 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1 INCH (DN25) OPTIONAL PRESSURE 1 RELIEFTRIM 1 NPT CONNECTION N (FEMALE) 10" (254 mm) 2 7/16" (11 mm) 13-1/4" (337 mm) i 3-7/8" 3-7/8" 3, 4 (100 mm) 1 (100 mm) 1-1/2" NPT NPT 4-3/4" (MALE) DRAIN (121 mm)~ 11-3/8" (290 mm) FIGURE 3 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1-112 INCH (DN40) NO DESCRIPTION P/N 1 300 psi/2000 kPa Water Pressure Gauge. . 90050001 2 Ball Valve, 1" (DN25).... 97111603 3 Flow Switch, VSR-M, 1-1/2"(DN40)......... 91144815 4 Field Replaceable Retard/Switch ......... 91144800 TFP963 Page 4 of 8 1 2'' (GROOVED) OPTIONAL PRESSURE O RELIEF TRIM CONNECTION T r 16' 0 (406 mm) NO DESCRIPTION P/N 13" / 1 300 psi/2000 kPa (330 mm) Water Pressure Gauge .. 90050001 2 Ball Valve, 1" (DN25)....97111603 3 Flow Switch, VSR-M, 2"(DN50)............ 91144802 2 4 Field Replaceable C Retard/Switch......... 91144800 1/2" (13 Imm) I 3-7/8" 4-1/8"' 3,4 (100 mm) V. (105 mm) 2" NPT 5" (GROOVED) DRAIN ~(127 mm)~ 11-7/8" _ (300 mm) FIGURE 4 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 2 INCH (DN50) Manifold Installation TYCO Model RM-1 Riser Manifold must be installed in accordance with this section. The Model RM-1 Riser Manifold may be installed either horizontally (flow switch on top) or vertically (flow going up). The inlet of the Riser Manifold may be con- nected directly to a shut-off control valve. Notes: Where applicable pipe thread sealant is to be applied sparingly. Use of a non -hardening pipe thread sealant is recommended. Never remove any piping component nor correct or modify any piping defi- ciencies without first depressurizing and draining the system. Provisions for an alarm test flow on Residential Models must be made. The alarm test flow is to be through an orifice having a flow capacity equal to or smaller than the smallest orifice sprinkler in the system. One of two options can be considered. The first option is to temporarily install a test orifice in the outlet of the drain line prior to performing the alarm test. The second option is to install an Inspec- tor's Test Connection downstream of the Waterflow Alarm Switch. Step 1. Install the manifold body with the flow arrow pointing in the down- stream position using threaded con- nections and/or listed mechanical grooved connections, as applicable. Step 2. Connect the drain line and on commercial manifolds set the Model TD-1 Test and Drain Valve to the OFF position or on residential manifolds close the drain valve. Step 3. Refer to Figure 6 for wiring guidance. All wiring must be performed in accordance with the authority having jurisdiction and/or the National Electri- cal Code. Step 4. Refer to Figure 5 for Optional Pressure Relief Trim installation. Step 5. Place the system in service by filling the system with water. When filling the system, partially open the control valve to slowly fill the system. Filling the system slowly will help avoid damaging the waterflow alarm switch. After the system is fully pressurized, completely open the control valve. Step 6. Secure all supply valves open. TFP963 Page 5 of 8 Commercial Riser Manifolds NO DESCRIPTION P/N 1 Pressure Relief Valve, 175 psi, 1/2" NPT.......... 1001184-01 2 112" x Close Nipple ........ 1001023-01 3 Flexible Hose: 1-1/2-3 Inch (DN40-DN80) Size Manifolds, 1/2" x 24.................. 1001266-02 4-6 Inch (DN100-DN150) Size Manifolds, 1/2"x 30..................1001266-01 4 Figure 323 Reducing Tee, Grooved x NPT Threaded: 1-1/2-3 Inch (DN40-DN80) Size Manifolds, 1-1/4" x 1-1/4" x 1/2 3231305GS 4-6 Inch (DN100-DN150) Size Manifolds, 2" x 2" x 112............... 3232005GS 5 Figure 577 Rigid Grooved Coupling: 1-1/2-3 Inch (DN40-DN80) Size Manifolds, 1-1/4 ..................... 57713AGCP 4-6 Inch (DN100-DN150) Size Manifolds, 2" ...................... 57720AGCP MODEL RM-1 COMMERCIAL RISER MANIFOLD Residential Riser Manifolds NO DESCRIPTION P/N 1 Pressure Relief Valve, 175 psi, 1/2" NPT.......... 1001184-01 2 1/2" x Close Nipple, Qty 2 ... 1001023-01 3 Flexible Hose, 1/2" x 16" .... 1001266-03 4 Figure 815 Threaded Reducing Tee, 1" x 1" x 1/2" NPT ......... 1001259-07 5 1" x Close Nipple .......... 1001025-01 MODEL RM-1 RESIDENTIAL FIGURE 5 MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLDS OPTIONAL PRESSURE RELIEF TRIM INSTALLATION Optional Pressure Relief Trim Installation Model RM-1 commercial and resi- dential riser manifold assemblies are designed to accommodate an optional pressure relief valve and trim compo- nents (Ref. Figure 5). Optional pressure relief trim must be installed in accordance with the follow- ing procedures. Notes: For assembly in Riser Manifolds installed and in service, verify the fire protection system is de -pressurized and drained. Close the system supply control valve, set commercial manifold test and drain valve to DRAIN or open residential drain valve to relieve resid- ual pressure and drain system. Make certain that drainage water will not cause any damage or injury. Refer to Care and Maintenance section for other requirements when closing a fire protection system control valve and placing system in service. Apply thread sealant or TEFLON tape on all threaded connections, with the exception of internally sealed flexible hose connections. Commercial Manifolds Refer to Figure 1 for commercial riser manifold features and Figure 5 for pres- sure relief trim components described in this procedure. Step 1. Remove 1/2 in. pipe plug from manifold tee. Inspect exposed female tee threads, remove thread sealant remnants or debris as necessary. Step 2. Install Pressure Relief Valve (1) in manifold tee, orienting valve outlet port perpendicular to and facing away from manifold body. Step 3. Install 1/2 in. x Close Nipple (2) in pressure relief valve outlet port. Step 4. Disconnect drain piping from grooved outlet of manifold TD-1 test and drain valve as applicable and install Figure 323 Grooved Reducing Tee (4) on valve outlet by securing with Fig- ure 577 Grooved Coupling (5), align- ing tee threaded branch outlet parallel with pressure relief valve outlet port. Reconnect drain piping to Figure 323 tee drain outlet as necessary. Note: Refer to Technical Data Sheet G901 for Figure 577 Grooved Coupling installation and assembly instructions. Step 5. Install Flexible Hose (3) by threading female ends onto 1/2 in. x close nipple installed on relief valve outlet port and onto Figure 323 reduc- ing tee branch outlet. Note: Assure Flexible Hose is not sus- ceptible to being caught or snagged by other moving equipment. Residential Manifolds Refer to Figures 2, 3 or 4 for residen- tial riser manifold features and Figure 5 for pressure relief trim components described in this procedure. Step 1. Remove 1/2 in. pipe plug from manifold tee. Inspect exposed female tee threads, remove thread sealant remnants or debris as necessary. Step 2. Install Pressure Relief Valve (1) in manifold tee, orienting valve outlet port perpendicular to and facing away from manifold body. Step 3. Disconnect drain piping from threaded outlet of manifold drain valve as applicable and install 1 in. x Close Nipple (5) in valve outlet. Step 4. Install Figure 815 Reducing Tee (4) onto 1 inch x close nipple, align- ing tee branch outlet parallel with pres- sure relief valve outlet port. Reconnect drain piping to Figure 815 tee drain out- let as necessary. Step 5. Install 1/2 in. x Close Nipples (2) in pressure relief valve outlet port and in Figure 815 reducing tee branch outlet. Step 6. Install Flexible Hose (3) by threading female ends onto 1/2 in. x close nipples installed on relief valve outlet port and Figure 815 reducing tee branch outlet. Note: Assure Flexible Hose is not sus- ceptible to being caught or snagged by other moving equipment. TFP963 Page 6 of 8 UNINSULATED LOOPED SECTION SINGLE CONDUCTOR CLAMPING \� PLATE \ TERMINAL IMPROPER CONNECTION METHOD WIRE NUT NEUTRAL WHITE �w U� SWITCH TERMINAL CONNECTIONS CLAMPING CAUTION: PLATE An uninsulated section of a TERMINAL single conductor is not permitted to be looped around the terminal and serve as two separate connections. The wire must be severed to serve as two separate connections, thereby providing supervision of the connection in the event that the wire becomes dislodged from the terminal. LOCAL WIRE NUT AUDIBLENISUAL ANNUNCIATOR TOR WHITE / \ BLACK BLACK (LINE/HOT) C CONTACT RATINGS: Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC J ISO Owz J O m Z O Z OQQ ( NO NC COM I i NC SEVERED STRIPPED ENDS SEPARATE CONDUCTORS INCOMING OUTGOING PROPER CONNECTION METHOD FIRE PANEL OR ADDRESSABLE MODULE NOTE: When connecting to a UL Listed control panel, use panel resistor rating for circuit supervision NOTE: For supervised circuits, see "Switch Terminal Connections" above. The Waterflow Alarm Switch has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. FIGURE 6 MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLD WIRING GUIDANCE TFP963 Page 7 of 8 DRAIN O 07 0 1O 00 O� 0ul Oo 00 00 5AAa LS� Nld11a OFF MARKING TEST MARKING DRAIN MARKING ON HANDLE ON HANDLE ON HANDLE POSITIONED POSITIONED POSITIONED O ON DETENT ON DETENT ON DETENT O ODEL TESTA Dt DRAIN VALVE O 4DRAIN o �" Oo ����SIGHT FLOW O O O O-- CONNECTION SET TEST DRAIN FRONT CONDITION CONDITION CONDITION VIEW FIGURE 7 MODEL RM-1 COMMERCIAL RISER MANIFOLD TD-1 TEST AND DRAIN VALVE OPERATION Care and Maintenance TYCO Riser Manifolds RM-1 must be serviced and maintained in accordance with this section. Before closing a fire protection system control valve for inspection or main- tenance work on the fire protection system that it controls, permission to shut down the effected fire protection system must first be obtained from the proper authorities and all person- nel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni- toring proprietary and/or central station alarms. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (e.g., NFPA 25), in addi- tion to the standards of any authority having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Note: No attempt is to be made to repair any Riser Manifold component in the field. Only the pressure gauge, waterflow alarm switch, or relief valve can be replaced. If any other problems are encountered the entire riser mani- fold must be replaced. The alarm/flow test procedure will result in operation of the associated alarms. Consequently, notification must be given to the owner and the fire department, central station, or other signal station to which the alarms are connected, and notification must be given to the building occupants. The following inspection procedure must be performed as indicated, in addition to any specific requirements of the NFPA, and any impairment must be immediately corrected: Alarm/Flow Test Procedure Step 1. Place the Model TD-1 Test and Drain Valve in the TEST position (Ref. Figure 7). On residential assemblies without a test orifice, temporarily install a test orifice in the drain outlet and fully open the Drain Valve. Make certain that drainage water will not cause any damage or injury. Step 2. Verify operation of associated alarms. Step 3. Verify that the residual (i.e., flowing) pressure indicated by the pres- sure gauge is no less that originally recorded for the system when it was first installed. Step 4. Close the Drain Valve on the Residential models and the Test and Drain valve on commercial models. Step 5. Verify that the static (i.e., not flowing) pressure indicated by the pres- sure gauge is no less that originally recorded for the system when it was first installed. TFP963 Page 8of8 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indi- cate the full product name, including description and part number (P/N). Riser Manifolds Specify: Size (specify) Connection Type (specify inlet x outlet) Model RM-1 Riser Manifold, P/N (specify): Commercial 1-1/2 in. (DN40) MT x FT .............. 40551 2 in. (DN50) G x G ................... 40601 2-1/2 in. (DN65) G x G ................ 40611 3 in. (DN80) G x G ................... 40621 4 in. (DN100) G x G .................. 40651 6 in. (DN150) G x G................... 40661 Residential 1 in. (DN25) FT x FT .................. 40671 1-1/2 in. (DN40) MT x FT .............. 40571 2 in. (DN50) G x G ................... 40591 Optional 175 psi Pressure Relief Kit Specify: Pressure Relief Kit, Model RM-1 Riser Manifold, (specify Commer- cial or Residential application), (specify size range), P/N (specify): Commercial 1-1/2 in. — 3 in. (DN40—DN80) 40721 4in. —6 in. (DN100—DN150) 40731 Residential 1 in.-2 in. (DN25—DN50) .............. 40711 Replacement Parts Specify: Model RM-1 Riser Manifold (specify part description), P/N (specify from Figures 1, 2, 3, 4 or 5) 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 m 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON Is a registered tratlemark of DuPont Johnson 01,to Controls tqCL7 Fire & Building Products Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Tyco Fire Products Model CV-1F Check Valve General Description The Tyco° Model CV-1 F Check Valve is a compact and rugged swing -type unit that allows water flow in one direction and prevents flow in the opposite di- rection. A resilient elastomer seal fac- ing on the spring loaded clapper en- sures a leak tight seal and non -sticking operation. The Model CV-1 F Check Valves are designed to minimize water hammer caused by flow reversal. The CV-1 F is furnished with grooved ends and can be installed using Grinnell° Grooved Couplings or Grin- nell Figure 71 Flange Adapters. The Model CV-1F Check Valves have been designed with a removable cover for ease of field maintenance. Valves in- stalled horizontally or inclined (flow up or down) are to be positioned with the cover facing up. Valves installed verti- cally may be positioned with flow up or down. A Maintenance Check Valve Kit (TFP1555) is available to allow the maintenance procedure of backflush- ing through the fire department con- nection without removing the Model CV-1 F Check Valve from the pipe line. The Model CV-1F Check Valves are a redesignation for the Central Figure 590F and Grinnell Figure 590F. The Model CV-1F Check Valve de- scribed herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Pro- tection Association, in addition to the standards of any authorities having ju- risdiction. Failure to do so may impair the performance of this device. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or manufac- turer should be contacted with any questions. Technical Data Sizes- Inches / DN 2 to 12 / DN50 to DN300 Maximum Working Pressure 300 psi (20,7 bar) Approvals UL, FM, and C-UL. Protective Coating Valve assembly • Non -lead paint Installation The Model CV-1 F Check Valves are to be installed in accordance with the fol- lowing instructions: Step 1. The arrow cast on the Body must point in the direction of the flow. Step 2. Valves installed vertically may be positioned with the flow up or down. Step 3. Valves installed horizontally or inclined (flow up or down) are to be positioned with the Cover facing up. Step 4. Grooved end pipe couplings used with the CV-1F must be installed in accordance with manufacturer's instructions. Care and Maintenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and devic- es in compliance with this document, as well as with the applicable stan- dards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authority hav- ing jurisdiction. The installing contrac- tor or product manufacturer should be contacted relative to any questions. Any impairments must be immediately corrected. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. After placing a fire protection system in service, notify the proper authorities and advise those responsible for mon- itoring proprietary and/or central sta- tion alarms. Page 1 of 4 JULY, 2008 TFP155O Page 2 of 4 TFP1550 B A - C O ♦ O.D. D 1/ NPT 1/2" NPT j E F FIGURE 2 NOMINAL DIMENSIONS MODEL CV-1F CHECK VALVES Nominal Pipe Size Nominal Dimensions- Inches (mm) Cover Bolt Torq. Approx. Weight ANSI O.D. Inches Inches A B C D E F i Lbs.-ft. (Nm) Lbs. (kg) DN (mm) 2 2.375 6.75 4.38 2.55 2.57 3.25 4.75 1.62 18 9.0 DN50 (60,3) (171,5) (111,3) (64,8) (65,3) (82,3) (120,7) (41,5) (25) (4,5) 2'/2 2.875 8.00 5.80 3.41 3.40 3.88 6.00 1.70 39 10.0 DN65 (73,0) (203,2) (147,3) (86,6) (86,4) (98,6) (152,4) (43,2) (54) (4,5) - - 8.00 5.80 3.41 3.40 3.88 6.00 1.70 39 10.00 DN65 (76,1) (203,2) (147,3) (86,6) (86,4) (98,6) (152,4) (43,2) (54) (4,5) 3 3.500 8.37 5.76 3.60 3.40 3.88 6.00 1.70 39 11.0 DN80 (88,9) (212,6) (146,3) (91,4) (86,4) (98,6) (152,4) (43,2) (54) (5,0) 4 4.500 9.63 6.74 4.61 3.63 4.56 7.13 1.84 50 25.0 DN100 (114,3) (244,6) (171,2) (117,1) (92,2) (115,1) (181,1) (46,7) (69) (11.3) - - 10.50 7.50 5.29 4.20 4.90 7.60 1.90 39 29.0 DN125 (139,7) (266,7) (190,5) (134,4) (106,7) (124,5) (193,0) (48,3) (54) (13.2) 5 5.563 10.50 7.50 5.29 4.20 4.90 7.60 1.90 39 29.0 DN125 (141,3) (266,7) (190,5) (134,4) (106,7) (124,5) (193,0) (48,3) (54) (13,2) - - 11.50 8.05 5.75 4.50 5.00 7.60 1.48 60 47.0 DN150 (165,1) (292,1) (204,5) (146,1) (114,3) (127,0) (193,0) (37,6) (82) (21,3) 6 6.625 11.50 8.05 5.75 4.50 5.00 7.60 1.48 60 47.0 DN150 (168,3) (292,1) (204,5) (146,1) (114,3) (127,0) (193,0) (37,6) (82) (21,3) 8 8.625 14.00 10.25 7.75 5.62 5.45 8.40 2.20 120 66.0 DN200 (219,1) (355,6) (260,4) (196,9) (142,7) (138,4) (213,4) (58,9) (164) (29,9) 10 10.750 18.00 13.00 10.21 6.38 7.50 10.50 3.00 130 109.7 DN250 (273,1) (457,2) (330,2) (259,3) (162.1) (190.5) (266,7) (76,2) (178) (49,4) 12 12.750 21.00 14.28 11.31 7.26 7.62 10.62 2.75 130 151.0 DN300 (323,9) (533,4) (362,7) (287,2) (184,4) (193,5) (269,7) (69.9) (178) (68,0) TFP1550 Page 3 of 4 4,16 / 2 3 0 Detail I Part I Material I Qty. 1 Body Ductile Iron 1 2 Cover Ductile Iron 1 3 Cover Gasket Nitrile Rubber 1 4 Hex Cap Steel, Zinc AR Screw Plated Clapper Stainless 2" - 8" Steel 5 1 Clapper Ductile Iron 10" - 12" 18 17 8 8 9 5 IFNI 2� 7 9 2" - 8" 2 7 5 10" - 12" (DN50-DN200) (DN250 - DN300) VIEW A 13 5 13 SEE / \ 11,16 DETAIL B lip 1 14,16 / 19 12 6 5 6 2" - 8" 10" - 12" (DN50-DN200) (DN250 - DN300) DETAIL B Detail Part Material Qty. 6 Clapper EPDM 1 Facing Grade "E" 7 Spring Stainless 1 Steel 8 Hinge Stainless 1 Shaft Steel 9 Retaining Stainless AR Ring Steel 11 Retention Stainless 1 Bolt Steel 12 Seal Ring Neoprene 1 FIGURE 2 MODEL CV-1F CHECK VALVES Detail Part Material Qty. 13 Retaining Stainless 1 Disc Steel 14 Locknut Stainless 1 Steel 15 Plug YZ Cast Iron 2 14 NPT 16 Adhesive Thread AR Sealer 17 Nameplate Aluminum 1 18 Rivet Steel 2 • 11 11 111 111 111 111 111 loll loll loll loll 1 WA ' o ■■■■■■■■� ��...■■o■■■■no■11111■..■■■u� �MMMM ■■■iiiiiiiiiiii■■ ■■iii MOW i■■■■i ■m■■■■■■jiff NMI iiii■■■■■i i■mi'■■ 1 1 Iuonnnu■ ME ■■■■■■OMM..■■nn��..■■■o■�onnm..■■■uo�.,..■ NErn.■.MEM.■■■nn..■■ .■v . ovunu v.■■���.■ ■ ' ,■ ■■■■■■■■ ■■■■■■■ • • I■ - FA MM■■■■M/M■■■ME, NoM■■■■■■II■■■1111111 MM■■II■■MII■■■ .■■■■1111 I-MMM■■■■MIIMMMMMII■■MMMM■■■■11■■11111111■■■■II■■■M/I■■■ ■ 1 ■E■■■■ ■E■■■ ■MEMO ■ ■ I■ '• I■III■111 I Mons ■ • Im■11111■■■■■ I■11 • II■MO■■IIM/M■■OIIIIMMM■■■■■11■III1111111M■■■�■III,MM■M I■■M■■11I�■■■■■►I■■■■■■■■■■I,�■■■■1111111■■■II■■■■II■■■■ IIM■■■I,M■■IMM■■■■■II■■1111111111■■I■■■■III■■■■ / I ■ ■MEMO / I I■■■■111 J■■NONE ■■ -■ ■II■■■■■■■■■■I■■11111111111■■/I■■■■h■■■■■ ■■ moon A I moll I •'llll■■■ 0 I■■III■■■■■I■IIIIIIIIIIIII■I■■II/1■■■■■ moons /■■III ■■II■ 11111 II■ I■IIII1111111111KE■■■III moons ■ • ■ , 1 ��....,. MMM Iu.r■ II■I ....... 11M■M■■■■■ ,■1 /M■■■■11� ...... . F..............■/MM.......��..M. M■FI■■■MMM ;■ MMM■7MMIi■IMMIA■M■■■■ 71111111E ■■■■ ■■■■M■■I .■■M■■1111 . 71 /1■■IIMME■■ • ■■■II■■Im■IMI,■■■■■■■■11�11111111 M■I.�■I.I■n1MII■■■■■■n11,111111111 I■■■ ■■■ I■■■■■■■■ I■■■moon■ '■■■■■■■■ • IEEE■■■III I■■■■■■11 �i11 /III . I■■■11M■■■■ ■■■11■■■■■ 1 1 , ■ ■■I■II■■■1■7■■■■■■■1/111111111■■II■■■ I■■■■■■■11 • 111 M■■■11■■■■■ 1 1 '■��■■■■III■■■■■■I/11111111111■I■■IIII�■■■■■■I ' moss■I III •,I■■■III■■■■■ 1 1 • g ■I.�■■■■III■■■■■■I/111111111111I/■■■I11'IEEE■■■■I I■■■■■■I dl ■. I■■■I111■■■■■ ...■■■■■��... 1 1 ' • 1 • .AEMM§■■■■I■r.r■r..■■I■■■■■■■1■1111..■.■■/I■��....■■■■■�....■■ iiiiiiEiiii ENNE pa iiiMENEM iv iiiiiiWii Aiiiiiii on niiiiiiiiiiiii 1 /. • g ' MMM■MI.M■■IMMMM'IMM■■11111111►�IMMMM��■IMMMMMMM■►IIMMM■MMM■■I�11 '/11M■MM■■IIMMM■M /IIII■■■M■■11MM■■■ ■ g MM■■IMM■■1MMMI■MM■■IIIIIIIIIII■■■■/I■11MM■■■■MI,�1MM■■■■M■■II111 MM■O■■■■■■MMII■■■■■■■111111/111■■■IM■IIMM■■■■■II■■MM■■■■■■I�IIIIIIIi1111■■■■■■IIMM■■■ ■��■■■■■■1■I■■■■■■■111111'/loll■■■11■■■1■■■■■■I4■1■■■■■■■�111111/,11111■■■■■■11■■■■■ 1 1 • 1 . ��■■■■■■■�'■■■■■■■■■1■11'llllll■■I■■■■1■■■■■■I■■■■■■■■■■11■■111/,111111■■■■■■■■■■■■■ —====no--:■■n:��:::::111I:::::::■C�:::::���� 1 / --- --------- -:::::::■■�:::::����: 11 I0 11 11 .00 oo$ o0$ 111 off .111 logo off 0 • Page 4 of 4 TFP1550 Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warran- ty is given for products or components manufactured by companies not af- filiated by ownership with TFBP or for products and components which have been subject to misuse, improper in- stallation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protec- tion Association, and/or the standards of any other Authorities Having Juris- diction. Materials found by TFBP to be defective shall be either repaired or re- placed, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other ob- ligation in connection with the sale of products or parts of products. TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure The Model CV-1F Check Valves: Specify: (specify size) Model CV-1 F Check Valve, P/N (specify) 2" (DN50) Valves .............. 59-590-0-020 2-1/2" (DN65) Valves ........... 59-590-0-025 DN65 (76,1mm) Valves.......... 59-590-0-076 3" (DN80) Valves .............. 59-590-0-030 4" (DN100) Valves .............. 59-590-0-040 DN125 (139,7) Valves ........... 59-590-0-139 5" (DN125) Valves ..............59-590-0-050 DN150 (165,1) Valves ........... 59-590-0-165 6" (DN150) Valves ..............59-590-0-060 8" (DN200) Valves .............59-590-0-080 10" (DN250) Valves ............. 59-590-0-100 12" (DN300) Valves ............ 59-590-0-120 Replacement Valve Parts Specify: (specify description) for use with (specify size) Model CV-11F Check Valve, P/N (specify) 2" (DN50) Valves Cover Gasket ...................976-705-01 Clapper Facing ..................976-709-01 2-1/2" (DN65) Valves Cover Gasket ...................975-618-01 Clapper Facing ..................975-621-01 3" (DN80) Valves Cover Gasket ...................975-618-01 Clapper Facing ..................975-491-01 4" (DN100) Valves Cover Gasket ................... 975-120-01 Clapper Facing ..................975-003-01 5" (DN125) Valves Cover Gasket ................... 975-120-01 Clapper Facing .................. 975-219-01 6" (DN150) Valves Cover Gasket ................... 975-218-01 Clapper Facing ..................975-006-01 8" (DN200) Valves Cover Gasket ...................975-479-01 Clapper Facing ..................975-463-01 10" (DN250) Valves Cover Gasket ...................976-000-01 Clapper Facing .................. 975-977-01 12" (DN300) Valves Cover Gasket ................... 976-472-01 Clapper Facing .................. 976-474-01 © 2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 SECTION 4 ALARMS AND SUPERVISORY DEVICES c POTTER The Symbol of Protection AWARNING • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. General Information The Model VSR is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering Information chart. The VSR may also be used as a sectional waterflow detector on large systems. The VSR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Installation: See Fig. 1 These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD UL, CUL and CSFM Listed, FM Approved, LPCBApproved, For CE Marked (EN12259-5) / VdS Approved model use VSR-EU Service Pressure: 450 PSI (31 BAR) - UL Flow Sensitivity Range for Signal: 4-10 GPM (15-3 8 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F-120°F, (4.5°C - 49°C) - UL • Non -corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090148 Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill. (see Fig. 1) Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to required torque. (see Fig. 1). The vane must not rub the inside of the pipe or bind in any way. Specifications subject to change without notice. Ordering Information Nominal Pipe Size Model Part Number 2" DN50 VSR-2 1144402 21/2" DN65 VSR-2 1/2 1144425 3" DN80 VSR-3 1144403 3 1/2" VSR-3 1/2 1144435 4" I DN100 VSR-4 1144404 5" I VSR-5 1144405 6" DN150 VSR-6 1144406 8" I DN200 VSR-8 1144408 Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG. 95401146 - REV H PAGE 1 OF 3 12/07 CP� POTTER The Symbol of Protection Fig.1 roYERTAMPEBS—H REE UT— AADITT: LASTED BY ROTATMG THE RETARD ADNSTMENT KNOB FROMOTO THE MAX SETFMG (_0 SECONDS), THE TA1E DELAY SHOULD BE SET AT TID? MMH.IGM EEO —TO PREVENT FALSE ALARMS. VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD DO NOT LEAVE COV ER OFF FOR EXTENDED PERIOD OF TIME SOmm ADAPTER ADAPTER TIGHTEN NUTS ALTERNATELY ® � � 20mma2mm MAX. DNSIO ONLY USE (2) 5180162 ADAPTERS AS SHOWN ABOVE MOUNT ON -E SO ARROW ON SADDLE 0 S— ONION ROLL PADDLE M OPPOSFFE DIRECITON OF -BELOW (Flowing water activates device in one direction only) Installation Requirements Model Nominal Pipe Size Nominal Pipe O.D. Hole Size U-Bolt Nuts Torque inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 1.25+.125/-.062 33.0+2.0 20 27 VSR-21/2 21/2 2.875 73.0 VSR-21/2 21/2 DN65 3.000 76.1 VSR-3 3 1 DN80 3.500 j 88.9 2.00+.125 50.8+2.0 VSR-31/2 31/2 4.000 101.6 VSR-4 4 DN100 4.500 114.3 VSR-5 5 5.563 141.3 VSR-6 6 DN150 6.625 168.3 VSR-8 8 DN200 8.625 219A Fig. 3 Typical Electrical Connections NEGATIVE DC OR NEUTRAL AC OSITIVE DC R HOT AC FLOW ZONE 3 PANEL Notes: 1. TheModelVSRhastwo switches, one canbeused to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. A condition of LPC Approval of this product is that the electrical entry must be sealed to exclude moisture. 3. For supervised circuits see "Switch Terminal Connections" drawing and caution note (Fig. 2). Fig. 2 Switch Terminal Connections Clamping Plate Terminal �yG v� GJ,S�,O DwGp Pn-3 WERAWARNING& An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. A CAUTION Waterflow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. Fig. 4 Fig. 5 Break out thin section of cover when wiring both To remove knockouts: Place screwdriver at switches from one conduit entrance. I inside edge of knockouts, not in the center. PRINTED IN USA MFG. #5401146 - REV H 12/07 PAGE 2 OF 3 CP� POTTER The Symbol of Protection VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Compatible Pipe Model Nominal Pipe Size Nominal Pipe O.D. Pipe Wall Thickness Schedule 10 (UL) Schedule 40 (UL) BS-1387 (LPQ DN (VDS) inch mm inch mm inch mm inch mm inch mm inch mm VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 VSR-2 1/2 21/2 2.875 73.0 0.120 3.05 0.203 5.16 VSR-2 1/2 DN65 3.000 76.1 0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 98.9 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 31/2 4.000 101.6 0.120 3.05 0.226 5.74 VSR-4 4 DN100 1 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 VSR-5 5 5.563 141.3 0.134 3.40 0.258 6.55 VSR-6 6 DN150 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 1 219.1 0.148 3.76 1 0.322 8.18 0.248 6.3 0.177 4.5 Note: For copper or plastic pipe use Model VSR-CF. Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). Ifprovided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR is not recommended or advisable. A minimum flow of 10 GPM (38 LPM) is required to activate this device. Maintenance Inspect detectors monthly for leaks. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble -free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029055. There is no maintenance required, only periodic testing and inspection. Removal • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. Important Notice Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Mounting Dimensions EWS U-BOLT NUT U-BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U-BOLT NOMINAL PIPE DIA. +44,5 mm (+ 1-3/4) FOR DN50 - DN65 (2 - 2-1/ NOMINAL PIPE DIA. +54,0 mm (+ 2-1/8") FOR DN80 - DN200 (3 - 8/ ,IA. mm 4") DWG# 1146-6 PRINTED IN USA MFG. 95401146 - REV H PAGE 3 OF 3 12/07 SECTION 5 FIRE SPRINKLERS tqCo Fire &Building Products Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series DS-1 — 5.6 K-factor Dry Type Sprinklers Standard & Quick Response, Extended Coverage General Description The Tyco° Series DS-1, 5.6 K-factor, Quick Response (3 mm Bulb) and Stan- dard Response (5 mm Bulb), Extend- ed Coverage Horizontal Sidewall, Dry Type Sprinklers are decorative glass bulb automatic sprinklers. They are in- tended for use in applications where the sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures (e.g., horizontal piping extensions through a wall to protect an unheated area of a build- ing). The Series DS-1 Extended Cov- erage Horizontal Sidewall Sprinklers are designed for extended cover- age use in light hazard occupancies (ECLH). WARNINGS The Series DS-1 Dry Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addi- tion to the standards of any other au- thorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. manufacturer should be contacted with any questions. The Series DS-1 Dry Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Model/Sprinkler Identification Numbers TY3338 - (3 mm Bulb Type) TY3358 - (5 mm Bulb Type) Technical Data Approvals UL and C-UL Listed. NYC Approved (Refer to Table A) Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connection 1 inch NPT Discharge Coefficient K=5.6 GPM/psi'/2 (80,6 LPM/bar'/2) Temperature Ratings Refer to Table A Finishes Sprinkler: Natural Brass, Chrome Plated, White Polyester Escutcheon: White Coated or Chrome Plated, Brass Plated Physical Characteristics Inlet ..................... Copper Plug .....................Copper Yoke ...............Stainless Steel Casing .... Galvanized Carbon Steel Insert ....................Bronze Bulb Seat ...........Stainless Steel Bulb ...................... Glass Compression Screw ........ Bronze Deflector ................ Bronze Frame .................... Bronze Guide Tube .......... Stainless Steel Water Tube ......... Stainless Steel Spring ............. Stainless Steel Sealing Assembly ................ ......... Beryllium Nickel w/Teflon" Escutcheon .......... Carbon Steel `Registered Trademark of DuPont Patents U.S.A. Patent No. 5,188,185 Operation When the Series DS-1 is in service, water is prevented from entering the assembly by the Plug & Belleville Seal- ing Assembly (Ref. Figure 1) in the Inlet of the Sprinkler. The glass Bulb contains a fluid that expands when exposed to heat. When the rated tem- perature is reached, the fluid expands sufficiently to shatter the glass Bulb, and the Bulb Seat is released. The compressed Spring is then able to ex- pand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug & Belleville Seal from the Inlet allowing the sprin- kler to activate and flow water. Page 1 of 6 MAY, 2008 TFP520 Page 2 of 6 TFP520 SPRINKLER FINISH TY3338 HSW (3 mm Bulb Type) w/ Standard Escutcheon (Ref. Fig. 2) TY3358 HSW (5 mm Bulb Type) w/ Standard Escutcheon (Ref. Fig. 2) Temperature Bulb Color Natural Chrome White Rating Code Brass Plated Polyester 135°F/57°C Orange 1, 2, 3 155°F/68°C Red 1, 2, 3 Notes: 1. Listed by Underwriters Laboratories, Inc. (Maximum order length of 48 inches). 2. Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches). 3. Approved by the City of New York under MEA 352-01-E. TABLE A SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVAL Coverage (') Min Min Temperature Top Of Deflector To APPLICATION W x L Flow Pressure Rating OF (C°) Ceiling Distance Ft. x Ft. (m x m) GPM (LPM) PSI (bar) Inches (mm) 16 x 16 (4,9 x 4,9) 26 (98) 21.6 (1,49) TY3338 HSW 16 x 18 (4,9 x 5,5) 29 (110) 26.8 (1,85) (3 mm Bulb Type) For Quick Response 135 & 155 4 to 12 16 x 20 4,9 x 6,1 ( ) 32 (121 ) 2,25 32.7 ( ) Light Hazard Extended Coverage (57 & 68) (100 to 300) Per NFPA 13 18 x 16 (5,5 x 4,9) 29 (110) 26.8 (1,85) APPLICATION Coverage (1) W x L Min Flow Min Pressure Temperature OF Top Of Deflector To Ceiling Distance (2) Ft. x Ft. (m x m) GPM (LPM) PSI (bar) Rating (CO) Inches (mm) 16 x 16 (4,9 x 4,9) 26 (98) 21.6 (1,49) TY3358 HSW 16 x 18 (4,9 x 5,5) 29 (110) 26.8 (1,85) (5 mm Bulb Type) For Standard Response 135 & 155 4 to 12 16 x 20 (4,9 x 6,1) 32 (121) 32.7 (2,25) Light Hazard Extended Coverage (57 & 68) (100 to 300) Per NFPA 13 18 x 16 (5,5 x 4,9) 29 (110) 26.8 (1,85) Notes: 1. The minimum allowable spacing between sprinklers to prevent cold soldering is 14 feet (4,3 m). 2. To meet the deflector -to -ceiling distance of 4 to 12 inches (100 to 300 mm), the centerline of the sprinkler waterway must be 4-7/16 to 12-7/16 inches below the ceiling. TABLE B SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS UL AND C-UL INSTALLATION CRITERIA TFP520 Page 3 of 6 PLUG WITH YOKE CASING INSERT FRAME 3 or 5 mm GASKETED SPRING BULB DEFLECTOR PLATE SEAL COMPRESSION WATER GUIDE BULB VENT SCREW INLET 1"NPT Sp ING TUBE TUBE SEAT HOLE FIGURE 1 TY3338 (3 mm BULB) TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY Design Criteria The Tyco° SeriesDS-1 Sprinklers are in- tended for use in fire sprinkler systems designed in accordance with the ex- tended coverage installation guide- lines provided by NFPA 13 and the in- stallation criteria provide by Table B. The 1 inch NPT Series DS-1 Sprin- klers are to be installed in the 1 inch NPT outlet or run of malleable or duc- tile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3 (Class 150) or cast iron threaded tee fittings that meet the dimension- al requirements of ANSI B16.4 (Class 125). The Series DS-1 Sprinklers may also be installed in the 1 inch NPT out- let of a Grinnell Figure 730 Mechani- cal Tee. Typically, the end sprinkler fitting on a branch line is plugged as shown in Figure 2. The DS-1 Sprinklers cannot be installed into an elbow fitting. For wet pipe systems, the DS-1 Sprin- klers may also be installed in the fol- lowing Tyco° CPVC fittings: (P/N 80145) 1" x 1" NPT Female Adapter or (P/N 80249) 1" x 1" x 1" NPT Sprinkler Head Adapter Tee. NOTE Do not install the Series DS-1 into any other type fitting without first con- sulting the Technical Services De- partment. Failure to use the appro- priate fitting may result in: failure of the sprinkler to properly operate due to formation of ice over the inlet Plug or binding of the inlet Plug; or, insuf- ficient engagement of the inlet pipe threads with consequent leakage. Branch, cross, and feedmain piping connected to Dry Sprinklers and sub- ject to freezing temperatures must be pitched for drainage in accordance with the minimum requirements of the ORDER LENGTHS: 2-1/2" to 48" (63,5 to 1219,2 mm) 4" t 1 IN 1/4" (6,4 mm) (101,6 ± 3,2 mm) INCREMENTS FACE OF ----------- FACE OF MOUNTING 1-3/4" DIA. SURFACE SPRINKLER (44,5 mm) FITTING SPRINKLER FITTING -- --� (REFER TO DESIGN CRITERIA SECTION) 1 3" DIA. (76,2 mm) CENTERLINE 7/16" OF WATERWAY (11,1 mm) FIGURE 2 TY3338 (3 mm BULB) TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL w/ STANDARD ESCUTCHEON WRENCH FLAT WRENCH RFC;FRS t PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCH FLATS FIGURE 3 W-TYPE SPRINKLER WRENCH Page 4 of 6 TFPS20 National Fire Protection Association for dry pipe sprinkler systems. When Dry Sprinklers are to be used in wet pipe sprinkler systems protecting areas subject to freezing temperatures (e.g., sprinkler drops into freezers), consideration must be given to the appropriate length of the sprinkler that will prevent freezing of the water in the connecting pipes due to conduction. When the temperature surrounding the wet pipe sprinkler system is main- tained at a minimum temperature of 40°F/4°C, the following are the mini- mum recommended lengths between the face of the sprinkler fitting and the outside surface of the protected area (i.e., length exposed to minimum am- bient of 40°F/4°C — Ref. Figure 4): • 12 inches (300 mm) when the tem- perature within the protected area is-20°F/-29°C • 18 inches (450 mm) when the tem- perature within the protected area is-40°F/-40°C • 24 inches (600 mm) when the tem- perature within the protected area is-60°F/-51°C For protected area temperatures be- tween those given above, the minimum recommended length from the face of the fitting to the outside of the protect- ed area may be determined by interpo- lating between the indicated values. The 2007 edition of NFPA 13, Sec- tion 8.4.10.2 requires that dry sprin- klers connected to wet pipe sprinkler systems protecting insulated freezer structures have the clearance space around the sprinkler barrel be sealed. The use of the Model DSB-2 Dry Sprin- kler Boot described in Technical Data SheetTFP591, and illustrated in Figure 5, will meet the intent of NFPA 13. EXPOSURE LENGTH (SEE DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING i DSB-2 / INTENDED FOR FREEZER STRUCTURES HEATED AREA FIGURE 4, EXPOSURE LENGTH 1-3/4" DIA. (44,5 mm) CLEARANCE INSULATED HOLE FREEZER ADHESIVE STRUCTURE DSB-2 BOOT STRAP TIES DS-1 (ENDS ON SHOWN WITH OPPOSING STANDARD SIDES OF ESCUTCHEON BOOT) FIGURE 5 MODEL DSB-2 SPRINKLER BOOT WITH SIDEWALL SERIES DS-1 DRY SPRINKLER Installation The Tyco° Series DS-1 Dry Type Sprin- klers must be installed in accordance with the following instructions: NOTES The Series DS-1 must only be installed in fittings that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important requirements regard- ing piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter of the air bubble is approximately 1116 inch (1,6 mm). A 1 inch NPT sprinkler joint should be obtained with a minimum to maximum torque of 20 to 30 ft. lbs. (26,8 to 40,2 Nm). Higher levels of torque may dis- tort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for in- sufficient adjustment in an Escutcheon Plate by under -or over -tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water- way perpendicular to the back wall and parallel to the ceiling. The word "TOP" on the Deflector is to face to- wards the ceiling. Step 2. With pipe thread sealant ap- plied to the inlet threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Wrench tighten the sprinkler by wrenching on the Casing with a pipe wrench whenever the casing is readily accessible. Otherwise, use a W-Type 7 Sprinkler Wrench (Ref. Figure 3). The wrench recess of the W-Type 7 is to be applied to the sprinkler wrench flats (Ref. Figure 3). Step 4. After the wall has been in- stalled/finished, slide on the outer piece of the Escutcheon until it comes in contact with the ceiling/wall. TFP52O Page 5 of 6 Care and Maintenance The Series DS-1 Dry Type Sprin- klers must be maintained and ser- viced in accordance with the following instructions: NOTES Absence of the outer piece of an es- cutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper au- thorities and all personnel who may be affected by this action must be notified. A Vent Hole is provided in the Bulb Seat (Ref. Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evi- dence of leakage from the Vent Hole is an indication that there may be weepage past the Inlet seal and that the sprinkler needs to be removed for determining the cause of leakage (e.g. an improper installation or an ice plug). The fire protection system control valve must be closed and the system drained before removing the sprinkler. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be com- pletely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age -before, during, and after instal- lation. Sprinklers damaged by drop- ping, striking, wrench twist/slippage, or the like, must be replaced. Also, re- place any sprinkler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installation Section). The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any oth- er authorities having jurisdiction. The installing contractor or sprinkler manu- facturer should be contacted relative to any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national code. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warran- ty is given for products or components manufactured by companies not affili- ated by ownership with TFBP or for products and components which have been subject to misuse, improper in- stallation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with applicable Standards of the Nation- al Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFBP shall not be respon- sible for sprinkler system design er- rors or inaccurate or incomplete infor- mation supplied by Buyer or Buyer's representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warran- ties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Page 6 of 6 TFPS20 P/N 60 - XXX - X - XXX MODEL/SIN EC Sidewall 3 mm Bulb 350 (V NPT), 135°F/57°C TY3338 351 EC Sidewall 3 mm Bulb TY3338 (1" NPT), 155°F/68°C EC Sidewall 5 mm Bulb 950 (V NPT), 135°F/57°C TY3358 951 EC Sidewall 5 mm Bulb TY3358 (1" NPT), 155°F/68°C NOTES (1). Dry Type Sprinklers are furnished based upon "Order Length" as measured per Figure 2 After the measurement is taken, round it to the nearest 1/4 inch increment. Eastern Hemisphere sales only SPRINKLER FINISH ESCUTCHEON FINISH 1 NATURAL BRASS WHITE 4 WHITE POLYESTER WHITE 9 CHROME PLATED CHROME PLATED 0 CHROME PLATED WHITE 3 WHITE (RAL9010)' WHITE (RAL9010)' 2 NATURAL BRASS BRASS PLATED ORDER LENGTH (1) (EXAMPLES) 055 5.501, 082 8.25" 180 18.00" 187 18.75" 372 37.25" 480 48.00" TABLE C PART NUMBER SELECTION SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS (Use Prefix "I" for ISO 7-R1 Connection, e.g., 1-60-361-1-180) Ordering Procedure Dry Sprinklers: Contact your local distributor for availability, and please specify the following: 1. Sprinkler. • Model/SIN. • Bulb Size (3 or 5 mm) • Extended Coverage Horizontal Sidewall Dry Type Sprinkler. • 5.6 K-factor. • Order Length. Dry Type Sprinklers are furnished based upon Order Length as mea- sured from the face of the wall to the face of the sprinkler fitting (Ref. Figure 2). After the measurement is taken, round it to the nearest 114 inch increment. • 1 Inch NPT Inlet Connection. • Temperature Rating. • Sprinkler Finish. • Standard Escutcheon and Finish. • Part Number from Table C. 2. W-Type 7 Sprinkler Wrench. Refer to the Price List for complete listing of Part Numbers. Model DSB-2: Specify: Model DSB-2 Dry Sprinkler Boot', P/N 63-000-0-002. Includes one Boot, two Strap Ties, and 1/3 oz. of Adhesive (quantity of adhesive is sufficient for installing one Boot) © 2007-2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446 tqC00 Worldwide I www.tyco-fire.com Contacts Series TY-FRB - 2.85 4.25 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRB 2.8, 4.215.61 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers described in herein are quick response, standard coverage, decorative 3 mm glass bulb -type spray sprinklers. They are designed for use in light or ordinary hazard, commercial occupancies such as banks, hotels, and shopping malls. The TY-FRB Recessed Pendent Sprin- kler, where applicable, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following Recessed Escutcheons: • A two-piece Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) Recessed Escutcheon with 1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total adjustment from the flush pendent position. • A two-piece Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) Recessed Escutcheon with 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion -resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond what would be obtained when exposed IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. to corrosive atmospheres. Although corrosion -resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agen- cies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, con- centration of chemicals, and gas/ chemical velocity, should be consid- ered, as a minimum, along with the cor- rosive nature of the chemical to which the sprinklers will be exposed. An intermediate level version of the Series TY-FRB Pendent Sprinklers is detailed in Technical Data Sheet TFP356. Sprinkler Guards are detailed in Technical Data Sheet TFP780. MUM The Series TY-FRB 2.8, 4.21 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protec- tion Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. NFPA 13 prohibits installation of 1/2 in. NPT sprinklers with K-factors greater than 5.6 in new construction. They are intended for retrofit in existing sprinkler systems only. Sprinkler Identification Number (SIN) TY1131 ... Upright 2.8K, 1/2 in. NPT TY1231 .. Pendent 2.8K, 1/2 in. NPT TY2131 ... Upright 4.2K, 1/2 in. NPT TY2231 .. Pendent 4.2K, 1/2 in. NPT TY3131 ... Upright 5.6K, 1/2 in. NPT TY3231 .. Pendent 5.6K, 1/2 in. NPT TY4131 ... Upright 8.OK, 3/4 in. NPT TY4231 .. Pendent 8.OK, 3/4 in. NPT TY4831 ... Upright 8.OK, 1/2 in. NPT TY4931 .. Pendent 8.OK, 1/2 in. NPT Technical Data Approvals UL and C-UL Listed FM, LPCB, and NYC Approved Refer to Table A and B for complete approval information including corrosion -resistant status. Maximum Working Pressure Refer to Table C Page 1 of 10 JULY 2018 TFP171 TFP171 Page 2 of 10 * Temperature rating ** Pipe thread connections per 1 - Frame is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Deflector. special request. PLATE SEATING SURFACE 7/16" (11,1 mm) NOMINAL 2-1/4" MAKE -IN (57,2 mm) 1 2-3/16"/T (55,6 mm) 1-9/16" �\ 1 1/2' NPT** WRENCH STYLE 10 or 20 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON 2-7/8" (73,0 mm) DIA. RECESSED PENDENT 3 - Sealing 5 Compression Assembly Screw 4 - Bulb 6 Deflector* 7 Bushing CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K-FACTOR, 112 IN. NPT * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on ESCUTCHEON Deflector. special request. PLATE SEATING SURFACE 7/16" (11,1 mm) NOMINAL 2-3/16" MAKE -IN (55,6 mm) 2-3/16" 1-1/2" (55,6 mm) (38,1 mm) 1/2" NPT** WRENCH STYLE 10 or 20 FLATS RECESSED 1 - Frame 3 - Sealing 5 - Compression 2 - Button Assembly Screw 4 - Bulb 6 - Deflector* 2-7/8" (73,0 mm) DIA. - 3 2 4 - 5 6* UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K-FACTOR, 112 IN. NPT Discharge Coefficient K=2.8 GPM/psi'/= (40,3 LPM/bars) K=4.2 GPM/psi'/2 (60,5 LPM/bari) K=5.6 GPM/psis (80,6 LPM/bar'/2) K=8.0 GPM/psii (115,2 LPM/bar'/2) Temperature Rating Refer to Table A and B Finishes Sprinkler: Refer to Table D Recessed Escutcheon: Signal or Pure White, Grey Aluminum, Jet Black, Chrome Plated, or Natural Brass Physical Characteristics Frame ............................Bronze Button......................Brass/Copper Sealing Assembly. Beryllium Nickel w/TEFLON Bulb...............................Glass Compression Screw ................. Bronze Deflector ................... Copper/Bronze Bushing (K=2.8) ....................Bronze Poly -Stainless Physical Characteristics Frame ............................Bronze Button ................ L316 Stainless Steel' Bulb...............................Glass Compression Screw ..... L316 Stainless Steel* Deflector ................... Copper/Bronze Sealing Assembly. Gold Plated Beryllium Nickel w/TEFLON 'Type L316 stainless steel (UNS 31603) per ASTM A479/479M or BS EN 1008 WN1.4404. Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers are intended for fire protection systems designed in accordance with the stan- dard installation rules recognized by the applicable Listing or Approval agency, such as UL Listing based on the requirements of NFPA 13 and FM Approval based on the requirements of the FM Global Loss Prevention Data Sheets. Use only the style 10, 20, 30, or 40 Recessed Escutcheon, as applica- ble, for recessed pendent installations. TFP171 Page 3 of 10 * Temperature rating is indicated on Deflector. ** Pipe thread connections per ISO 7-1 can be provided on special request. ESCUTCHEON PLATE SEATING SURFACE 7/16" (11,1 mm) NOMINAL 2-3/16" MAKE -IN (55,6 mm) 2-3/16" 1-1/2" (55,6 mm) (38,1 mm) 1/2" NPT** WRENCH STYLE 10 or 20 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON UPRIGHT 1 - Frame 3 - Sealing 5 - Compression 2 - Button Assembly Screw 4 - Bulb 6 - Deflector* 2-7/8" (73,0 mm) DIA. -I RECESSED PENDENT ALL FINISHES EXCEPT POLY -STAINLESS WRENCH 1/2" ESCUTCHEON FLATS NPT PLATE SEATING SURFACE 7/16" 1,1 mm) OM I NAL 2-3/16" RAKE -IN (55,6 mm) 2-3/16" 1-1/2" (55,61 mm) (38,11 mm) 1 1 PENDENT STYLE 1( RECESSEu ESCUTCHEON 3 4 - 5 6* CROSS SECTION 1 - Frame 3 - Sealing 5 - Compression *Temperature 2 - Button Assembly Screw rating indicated 4 - Bulb 6 - Deflector* on Deflector. RECESSED PENDENT POLY -STAINLESS FINISH ONLY 1 3 - 2 4 - 5 6* CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K-FACTOR, 112 IN. NPT Installation The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) and 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings. A leak -tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum -to -maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N•m). A leak tight 3/4 in. NPT sprinkler joint should be obtained with a torque of 10 to 20 lb-ft (13,4 to 26,8 N•m). Higher levels of torque can distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to com- pensate for insufficient adjustment in the escutcheon plate by under- or over - tightening the sprinkler. Re -adjust the position of the sprinkler fitting to suit. Series TY-FRB Upright and Pendent Sprinklers The Series TY-FRB Upright and Pendent Sprinklers must be installed in accordance with the following instructions: Step 1. Install pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 14). With reference to Figure 1 to Figure 5, apply the W-Type 6 Sprinkler Wrench to the sprinkler wrench flats. Series TY-FRB Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- dance with the following instructions: Step 1. After installing the Style 10, 20, 30, or 40 Mounting Plate, as applica- ble, over the sprinkler threads and with pipe -thread sealant applied to the pipe threads, hand -tighten the sprinkler into the sprinkler fitting. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 15). With reference to Figure 1 to 4, apply the W-Type 7 Recessed Sprin- kler Wrench to the sprinkler wrench flats. Step 3. After the ceiling is installed or the finish coat is applied, slide on the Style 10, 20, 30, or 40 Closure over the Series TY-FRB Recessed Pendent Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 4 of 10 * Temperature rating ** Pipe thread connections per 1 Frame 3 Sealing 5 Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 Button Assembly Screw Deflector. special request. PLATE SEATING 4 Bulb 6 Deflector* SURFACE 1/2" (12,7 mm) NOMINAL T(58,7 5/16" MAKE -IN mm) 2-1/4" 1-9/16" (57,2 mm) (39,7 mm) \ 3/4" NPT** WRENCH STYLE 30 or 40 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON 2-7/8" (73,0 mm) DIA. RECESSED PENDENT ALL FINISHES EXCEPT POLY -STAINLESS WRENCH 3/4" ESCUTCHEON FLATS NPT PLATE SEATING SURFACE 1/2" (12,7 mm) NOMINAL MAKE -IN 2-5/16" (58,7 mm) 2-1/4" 1-9/16" (57,2 mm) !R4 7 mm1 CROSS SECTION 1 - Frame 3 - Sealing 5 - Compression *Temperature 2 - Button Assembly Screw rating indicated 4 - Bulb 6 - Deflector* on Deflector. STYLE 40 RECESSED UPRIGHT PENDENT ESCUTCHEON 2-7/8" (73,0 mm) DIA. — RECESSED PENDENT POLY -STAINLESS FINISH ONLY CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K-FACTOR, 314 IN. NPT CEILING PLATE 1 - Frame 5 Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 Deflector Assembly 3 4 - Bulb (111,11 7/16 2-1/4" NOMINAL mm) (57,2 mm) 2 NO MAKE-IN * Temperature rating is 2-3/16" 1-9/16" 4 indicated on Deflector. (55,6 mm) i (39,7 mm) 5 ** Pipe thread connections \ per ISO 7-1 can be 6 * provided on special 1/2" NPT** WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K-FACTOR, 112 IN. NPT TFP171 Page 5 of 10 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (17FACE 6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) OF (57,2 mm) -,i MOUNTING SPRINKLER PLATE FITTING MOUNTING SURFACE CLOSURE SERIES TY-FRB (3,22 mm) 1-5/16" (33,3 mm) 13/16" (20,6 mm) FIGURE 6 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 IN. NPT 5/8±1 /4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING MOUNTING SURFACE 2-7/8" DIA. (73,0 mm) 3/4" (19,1 mm) mm 1/41/4" (6,4 mm) 2-1/4" DIA. (57,2 mm) MOUNTING PLATE CLOSURE SERIES TY-FRB Y/ 8" (3,21/mm) 1-1/4" (31,8 mm) 3/4" (19,1 mm) FIGURE 8 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 4.2 K-FACTOR, 112 IN. NPT 2-7/8" DIA. (73,0 mm) 1/2" 12,7 mm (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" ► (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 1-1/16" (27,0 mm) FIGURE 7 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 IN. NPT 2-7/8" DIA. 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (17±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" ► (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 1" (25,4 mm) FIGURE 9 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 112 IN. NPT TFP171 Page 6 of 10 5/8±1/4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING MOUNTING SURFACE 2-7/8" DIA. (73,0 mm) 3/4" (19,1 mm) 2-1/4" DIA. 1/4" (6,4 mm) (57,2 mm) MOUNTING r, PLATE CLOSURE SERIES TY-FRB C/ r (3,22 mm) 1-1/4" (31,8 mm) 3/4" (19,1 mm) FIGURE 10 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 112 IN. NPT 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (57,2 mm) FACE OF MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) 1 MOUNTING SURFACE CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) FIGURE 12 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 314 IN. NPT WRENCH RECESS (END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS (END "B" USED FOR 3/4" NPT MODELS) FIGURE 14 W-TYPE 6 SPRINKLER WRENCH 2-7/8" DIA. (73,0 mm) 1/2" 12,7 mm (13,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) 7FACE OF (57,2 mm) MOUNTING SPRINKLER,_4L PLATE FITTING /8" mm) /77 1 1 MOUNTING SURFACE CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 1 " (25,4 mm) FIGURE 11 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 112 IN. NPT 2-7/8" DIA. 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 1-1/16" (27,0 mm) FIGURE 13 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 314 IN. NPT WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 15 W-TYPE 7 RECESSED SPRINKLER WRENCH TFP171 Page 7 of 10 Sprinkler Firl K- Factor Type Temperature Bulb Liquid Color Natural Brass Chrome Plated Polyester 135°F(57°C) Orange Pendent (TY1231) 155°F(68°C) Red 175°F (79°C) Yellow and 1, 2, 3, 4 Upright (TY1131) 200°F (93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 1/2 in. NPT Recessed Pendent 68 155°F°C ( ) Red 175°F (79°C) Yellow (TY1231)a Figure 6 200°F (93°C) Green 1,2,4 135°F(57°C) Orange Recessed Pendent 155°F (68°C) Red (TY1231)b Figure 7 175°F (79°C) Yellow 200°F (93°C) Green 135°F(57°C) Orange Pendent (TY2231) 155°F(68°C) Red 175°F (79°C) Yellow and Upright (TY2131) 200°F (93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 4.2 1/2 in. NPT Recessed Pendent 1,2 68 155°F°C ( ) Red 175°F (79°C) Yellow (TY2231)a Figure 8 200°F (93°C) Green 135°F(57°C) Orange Recessed Pendent 155°F(68°C) Red (TY2231)b Figure 9 1750F (79°C) Yellow 200°F (93°C) Green NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion - resistant sprinklers. TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 8 of 10 Sprinkler Finish$ K- Factor Type Temperature Bulb Li uid Color Natural Brass Chrome Plated Polyesters Poly -Stainless Lead Coated Pendent (TY3231) 135°F (57°C) Orange 155°F(68°C) Red 175°F (79°C) Yellow and 1, 2, 3, 4, 5, 6, 7 1,2 1, 2, 3, 5 (Uprigh) 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red 5.6 1/2 in. NPT Recessed Pendent (TY3231)a Figure 10 1, 2, 4, 5 1,2 N/Ad 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red Recessed Pendent (TY3231)6 1, 2, 3, 4, 5 N/A N/A 0 0 175 F 79 C Yellow 200°F (93°C) Green Figure 11 286°F (141°C) Blue Pendent (TY4231) 135°F (57°C) Orange 155°F(68°C) Red 175°F (79°C) Yellow and 1, 2, 3, 4, 5, 6, 7 1,2 1, 2, 5 Upri 31) 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red 80 3/4 in. NPT Recessed Pendent (TY4231)a Figure 12 1, 2, 5 1,2 N/A 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red Recessed Pendent (TY4231)6 1, 2, 3, 5 N/A N/A 0 0 175 F 79 C Yellow 200°F (93°C) Green Figure 13 286°F (141°C) Blue 8.0 Pendent (TY4931) 135°F (57°C) Orange 155°F(68°C) Red 175°F (79°C) Yellow 1/2 in. and 1, 2, 4, 5, 6 N/A 1, 2, 5 NPT Upright (TY4831) 200°F (93°C) Green 286°F (141°C) Blue NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. d. Not Available (N/A) 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead -Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers. Where Lead -Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion -Resistant Sprinklers. TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 9 of 10 Sprinkler Finish K- Factor Type Natural Brass Chrome Plated polyester Lead Coated Pendent (TY1231) and 2.8 Upright (TY1131) 1/2 in. 175 psi (12,1 bar) N/A2 NPT Recessed Pendent (TY1231) Pendent (TY2231) and 4.2 Upright (TY2131) 1/2 in. 175 psi (12,1 bar) N/A Recessed NPT Pendent (TY2231) Pendent (TY3231) and 5.6 Upright (TY3131) 250 psi (17,2 bar) 1/2 in. or 175 psi (12,1 bar)' Recessed NPT Pendent (TY3231) Pendent (TY4231) 175 psi 8.0 and Upright (TY4131) (12,1 bar) 3/4 in. 175 psi (12,1 bar) Recessed N/A NPT Pendent(TY4231) 8.0 Pendent (TY4931) 175 psi 1/2 in. and 175 psi (12,1 bar) (12,1 bar) NPT Upright (TY4831) NOTES 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Under- writers Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. 2. Not applicable (N/A). TABLE C MAXIMUM WORKING PRESSURE Care and Maintenance The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire pro- tection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be taken to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or sprinkler manufac- turer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- tion Section). Initial and frequent visual inspections of random samples are recommended for corrosion -resistant sprinklers to verify the integrity of the corrosion -resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice.lnspections of corrosion -resis- tant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprinkler condition and the long-term integrity of the corrosion -resistant material, which can be affected by the corrosive conditions present. TFP171 Page 10 of 10 P/N 57 — XXX — X — XXX SIN 330 2.8K UPRIGHT (112 in. NPT) TY1131 331 2.8K PENDENT (112 in. NPT) TY1231 340 4.2K UPRIGHT (1/2 in. NPT) TY2131 341 4.2K PENDENT (1/2 in. NPT) TY2231 370 5.6K UPRIGHT (1/2 in. NPT) TY3131 371 5.6K PENDENT (112 in. NPT) TY3231 390 8.OK UPRIGHT (3/4 in. NPT) TY4131 391 8.OK PENDENT (3/4 in. NPT) TY4231 360 8.OK UPRIGHT (1/2 in. NPT) TY4831 361 8.OK PENDENT (1/2 in. NPT) TY4931 SPRINKLER FINISH 1 NATURAL BRASS POLY -STAINLESS GREY 2 ALUMINUM (RAL9007)1 POLYESTER 3 PURE WHITE POLYESTER (RAL9010)2 4 SIGNAL WHITE POLYESTER (RAL9003) 5 JET BLACK POLYESTER (RAL9005)3 7 LEAD COATED 9 1 CHROME PLATED TEMPERATURE RATINGS 135 135°F (57°C) 155 155°F(68°C) 175 175°F(79°C) 200 200°F (93°C) 286 286°F (141°C) NOTES 1. Available only on TY3131, TY3231, TY4131, and TY4231 2. Eastern Hemisphere sales only. 3. Available in only 2.8K, 4.21K, and 8.01K, 155°F (68°C) and 200°F (93°C); requires longer lead time to manufacture. TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright) Sprinkler (specify) temperature rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify") finish, P/N (specify`) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 m 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson 1 nson ORO NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registeretl trail —arks of National Flre Protection Association; Controls TEFLON Is a reglsteretl trademark of DuPont