Loading...
FIR2021-0039+Seismic_Bracing+4.23.2021_11.50.22_AM+2161141TOLBraceTM Seismic Bracing Calculations Contractor: NORTHWEST FIRE SYSTEM; Project Address: MAIN STREET COMMONS Address: 22645 83RD AVE S F KENT, WA 98032 AR 550 MAIN ST Phone: 206-772-7502 PG"MWewsgessw0fi&+de EDMONDS, WA Licence: NORTHFS928CR Job # 05043C Calculations based on 2016 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 1001 Clamp 1600 Ibs (726 kg) 1131 Ibs (513 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE ATTACHMENT Fastener Information STEEL PIPE Orientation to Connecting Surface NFPAType E Fastener r� Type Through -Bolt+ Diameter 1/2in. Length 1-1 /2in. TOLCO FIG. 1001 Maximum Load 230 Ibs (104 kg) FAST CLAMP Brace Identification on Plans SB1 Prying Factor N/A Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.598 Diameter Type Length Total Length Weight Per Unit Length Total Weight 2.5" (65 mm) I Eddy -Flow 118.25 ft (5.6 m) 118.25 ft (5.6 m) 15.3 lb/ft (7.89 kg/m) 197 Ibs (44 kg) 1.25" (32 mm) I Eddy -Flow 182 ft (25 m) 182 ft (25 m) 2.02 lb/ft (3.01 kg/m) 1166 Ibs (75 kg) Subtotal Weight 263 Ibs (119 kg) Wp (incl. 15%) 302 Ibs (137 kg) Main Size 2.5" Type/Sch. Eddy -Flow Spacing (ft) 18.25 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 181 Ibs (82 kg) 549 lb (249 kg) fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations MAIN STREET COMMONS 550 MAIN ST Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 05043C SB1 NFPA Type E 2.5" EddyFlow Pipe 18' 2.4" (5.56 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45* 1/2in. x 1-1/2in. Through -Bolt 1-1/2in. Summary of Pipe within Zone of Influence 2.5" EddyFlow Pipe (63.5 mm) 18.25 ft (5.6 m) 1.25" EddyFlow, Pipe (31.75 mm) 182 ft (25 m) G-Factor Used 0.598 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 180 Ibs (82 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 230 Ibs (104 kg) Fig. 1001 Clamp 1131 Ibs (513 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member TJI Calculations prepared by IAN * The description of the Structural Member is for informational purposes only. TOLBraceT" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBraceT' 8 Visit us at www.tolco.com FMT* N ----------------------------+ WASHINGTON STATE ■ CERTIFICATE OF COMPETENCY ■ FIRE PROTECTION SPRINKLER SYSTEMS Byron Richard Moye N 9419-0815-C Level ■ Northwest Fire Systems, LLC �2 .� ■ NOFff HFS928CR o A■ ■ o■ 77 Sign 1 t�71ffl r............................A TOLBraceTM Seismic Bracing Calculations Contractor: NORTHWEST FIRE SYSTEM; Project Address: MAIN STREET COMMONS Address: 22645 83RD AVE S KENT, WA 98032 MIk 550 MAIN ST Phone: 206-772-7502 I:b"P g8nsrnessiNw&W6 EDMONDS, WA Licence: NORTHFS928CR Job # 05043C Calculations based on 2016 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length 7' 0" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1" Fig. 1001 Clamp 1600 Ibs (726 kg) 1131 Ibs (513 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) FlG. 980 UNIVERSAL SWAY CONCRETE BRACEATTACHMENT ANCHOR Fastener Information Orientation to Connecting Surface NFPAType B Fastener STEEL APE Type Through -Bolt O Diameter 1/2in. Length 2-1 /2in. RG. 1001 PIPE CLMP Maximum Load 200 Ibs (91 kg) Brace Identification on Plans SB2 Prying Factor N/A Brace Type Lateral [ ] Longitudinal [ ] 4-Way [X] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.598 Diameter Type Length Total Length Weight Per Unit Length Total Weight 4" (100 mm) Eddy -Flow 10 ft (3 m) 10 ft (3 m) 11.29 Ib/ft (16.8 kg/m) 113 Ibs (51 kg) 2.5" (65 mm) Eddy -Flow 5 ft (1.5 m) 5 ft (1.5 m) 5.3 lb/ft (7.89 kg/m) 26 Ibs (12 kg) 1" (25 mm) Sch. 10 4 ft (1.2 m) 4 ft (1.2 m) 1.81 lb/ft (2.69 kg/m) 7 Ibs (3 kg) Subtotal Weight 146 Ibs (66 kg) Wp (incl. 15%O) 168 Ibs (76 kg) Main Size 4" Type/Sch. Eddy -Flow Spacing (ft) 10 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 100 Ibs (46 kg) N/A fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations MAIN STREET COMMONS 550 MAIN ST Job # 05043C FMT* N PoweMw 6r6"S5 M MM& Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener SB2 NFPA Type B 4" EddyFlow Pipe 10' 0" (3.05 m) Riser 1" Sch.40 7' 0" (2.13 m) 200 45* 1/2in. X 2-1/2in. Through -Bolt 2-1/2in. Summary of Pipe within Zone of Influence 4" EddyFlow Pipe (101.6 mm) 110 ft (3 m) 2.5" EddyFlow Pipe (63.5 mm) 15 ft (1.5 m) 1" Sch.10 Steel Pipe (25.4 mm) 14 ft (1.2 m) G-Factor Used 0.598 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 101 Ibs (46 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 200 Ibs (91 kg) Fig. 1001 Clamp 1131 Ibs (513 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member TJI Calculations prepared by IAN * The description of the Structural Member is for informational purposes only. TOLBraceT" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBraceT' 8 Visit us at www.tolco.com ----------------------------+ WASHINGTON STATE ■ CERTIFICATE OF COMPETENCY ■ FIRE PROTECTION SPRINKLER SYSTEMS Byron Richard Moye N 9419-0815-C Level ■ Northwest Fire Systems, LLC �2 o� ■ NQRTHFS928CR o a■ 1 0■ ExplrwJ � Slgn 1213V21 TOLBraceTM Seismic Bracing Calculations Contractor: NORTHWEST FIRE SYSTEM; Project Address: MAIN STREET COMMONS Address: 22645 83RD AVE S f KENT, WA 98032 550 MAIN ST Phone: 206-772-7502 ftmwweiw+nasewiwdwde EDMONDS, WA Licence: NORTHFS928CR Job # 05043C Calculations based on 2016 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1.. Fig. 1001 Clamp 1000 Ibs (454 kg) 707 Ibs (321 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG, 980 UNIVERSAL SWAY BRACE ATTACHMENT O+ Fastener Information STEEL PIPE Orientation to Connecting Surface NFPAType E Fastener Type Through -Bolt+ Diameter 1/2in. Length 2-1 /2in. q TOLCO FIG. 1001 Maximum Load 280 Ibs (127 kg) FAST CLAMP Brace Identification on Plans SB3 Prying Factor N/A Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.598 Diameter Type Length Total Length Weight Per Unit Length Total Weight 2" (50 mm) I Mega -Flow 110.5 ft (3.2 m) 110.5 ft (3.2 m) 13.63 lb/ft (5.4 kg/m) 138 Ibs (17 kg) 2" (50 mm) I Eddy -Flow 17 ft (2.1 m) 7 ft (2.1 m) 13.98 lb/ft (5.92 kg/m) 128 Ibs (13 kg) Subtotal Weight 66 Ibs (30 kg) Wp (incl. 15%) 76 Ibs (34 kg) Main Size 2" Type/Sch. Mega -Flow Spacing (ft) 10.5 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 45 Ibs (21 kg) 298 Ib (135 kg) fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations MAIN STREET COMMONS 550 MAIN ST Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 05043C SB3 NFPA Type E 2" MegaFlow Pipe 10'6"(3.2m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45* 1/2in. X 2-1/2in. Through -Bolt 2-1/2in. Summary of Pipe within Zone of Influence 2" MegaFlow Pipe (50.8 mm) 77577 (3.2 m) 2" EddyFlow Pipe (50.8 mm) 17 ft (2.1 m) G-Factor Used 0.598 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 45 Ibs (20 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 280 Ibs (127 kg) Fig. 1001 Clamp 707 Ibs (321 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member TJI Calculations prepared by IAN * The description of the Structural Member is for informational purposes only. TOLBrace'" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBraceT"' 8 Visit us at www.tolco.com E:�T*N ftmVing 9fsinassV1OMMde P----------------------------+ WASHINGTON STATE ■ CERTIFICATE OF COMPETENCY ■ FIRE PROTECTION SPRINKLER SYSTEMS Byron Richard Moye N 9419-0815-C Level ■ i Northwest Fire Systems, LLC �2 o� ■ NQPTHFS928CR o a■ ■ o■ tom. E 'Plros � Slgn 12l31121 � i............................ TOLBraceTM Seismic Bracing Calculations Contractor: NORTHWEST FIRE SYSTEM; Project Address: MAIN STREET COMMONS Address: 22645 83RD AVE S f KENT, WA 98032 550 MAIN ST Phone: 206-772-7502 ftmwweiw+nasewiwdwde EDMONDS, WA Licence: NORTHFS928CR Job # 05043C Calculations based on 2016 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1.. Fig. 1001 Clamp 1000 Ibs (454 kg) 500 Ibs (227 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1007 Ibs (457 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 30° Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 926 Ibs (420 kg) TOLCO FIG, 980 UNIVERSAL SWAY BRACE ATTACHMENT Fastener Information STEEL PIPE+ Orientation to Connecting Surface NFPAType D Fastener Type Through -Bolt+ Diameter 1/2in. Length 2-1 /2in. q TOLCO FIG. 1001 Maximum Load 160 Ibs (73 kg) FAST CLAMP Brace Identification on Plans SB4 Prying Factor N/A Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.598 Diameter Type Length Total Length Weight Per Unit Length Total Weight 2" (50 mm) I Mega -Flow 118.9 ft (5.8 m) 118.9 ft (5.8 m) 13.63 lb/ft (5.4 kg/m) 169 Ibs (31 kg) 1.25" (32 mm) I Eddy -Flow 138.1 ft (11.6 m) 138.1 ft (11.6 m) 12.02 lb/ft (3.01 kg/m) 77 Ibs (35 kg) Subtotal Weight 146 Ibs (66 kg) Wp (incl. 15%) 168 Ibs (76 kg) Main Size 2" Type/Sch. Mega -Flow Spacing (ft) 18.9 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 100 Ibs (46 kg) 298 Ib (135 kg) fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations MAIN STREET COMMONS 550 MAIN ST Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 05043C SB4 NFPA Type D 2" MegaFlow Pipe 18' 10.8" (5.76 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 30* 1/2in. X 2-1/2in. Through -Bolt 2-1/2in. Summary of Pipe within Zone of Influence 2" MegaFlow Pipe (50.8 mm) 77977 (5.8 m) 1.25" EddyFlow, Pipe (31.75 mm) 138.1 ft (11.6 m) G-Factor Used 0.598 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 100 Ibs (45 kg) Material Capacity 926 Ibs (420 kg) Fastener Capacity 160 Ibs (73 kg) Fig. 1001 Clamp 500 Ibs (227 kg) Fig.980 Universal Swivel 1007 Ibs (457 kg) Structural Member TJI Calculations prepared by IAN * The description of the Structural Member is for informational purposes only. TOLBrace'" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBraceT"' 8 Visit us at www.tolco.com E:�T*N ftmVing 9fsinassV1OMMde WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Byron Richard Moye N 9419-0815-C Level N • Northwest Fire Systems, LLC 77 e� NO HFS928CR CD e1 tom. ExP1. Slgnad� 12131121 �............................a