FIR2024-0023+Fire_Alarm_Battery_Calculations+3.4.2024_6.44.22_PM+4102411cn 1poLq LLMI= 4 v N C\ W N\ } PROJECT INFORMATION NAME: VICTORY TAVERN T.I. ADDRESS: 550 MAIN STREET, SUITE #100 EDMONDS, WA. 98020 SCOPE OF WORK INSTALLATION OF NEW FIRE ALARM COMPONENTS IN A TENANT IMPROVEMENT SPACE. ALL NEW FIRE ALARM COMPONENT WILL BE CONNECTED TO THE EXISTING FULLY OPERATIONAL ADDRESSABLE FIRE ALARM SYSTEM. EXISTING FIRE ALARM CONTROL PANEL IS POTTER IPA-4000. FIRE ALARM SYSTEM CONTRACTOR NAME: ELECTRO TECH ADDRESS: PO BOX 13889 MILL CREEK WA 98082 PHONE: (425) 405 - 0583 FAX: (866) 798 - 9241 APPLICABLE CODES AND STANDARDS NFPA 72 NATIONAL FIRE ALARM CODE 2019 EDITION INTERNATIONAL CODE 2015 EDITION INTERNATIONAL FIRE CODE 2015 EDITION NFPA 70 NATIONAL ELECTRICAL CODE 2020 EDITION CIRCUIT LABELING LEGEND DEVICE IDENTIFIER SLC1 •### CIRCUIT IDENTIFIER ABBREVIATIONS SLC = SIGNALING LINE CIRCUIT NAC = NOTIFICATION APPLIANCE CIRCUIT A AMPERE AFF ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT AL ALUMINIUM AMP AMPERE AWG AMERICAN WIRE GAUGE BLDG C CONDUIT CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CLG CEILING CO CONDUIT ONLY COMM COMMUNICATION CU COPPER DCV DOUBLE CHECK VALVE DIA DIAMETER DISC DISCONNECT DN DOWN DO DOOR OPERATOR (E) EXISTING EA EACH EF EXHAUSTFAN ELEC ELECTRIC ELEV ELEVATOR EMT ELECTRICAL METALLIC TUBING EOL END OF LINE RESISTOR EOLR END OF LINE RESISTOR EXIST EXISTING F FIXED FA FIRE ALARM FAA FIRE ALARM ANNUNCIATOR FACP FIRE ALARM CONTROL PANEL FAPS FIRE ALARM POWER SUPPLY FARA FIRE ALARM REMOTE ANNUNCIATOR FBO FURNISHED BY OTHERS FDC FIRE DEPARTMENT CONNECTION FEC FIRE EXTINGUISHER CABINET FH FIRE HYDRANT FPL FIRE POWER LIMITED FPLR FIRE POWER LIMITED RISER FPLP FIRE POWER LIMITED PLENUM FS WATER FLOW SWITCH FSD FIRE/SMOKE DAMPER G GROUND GEC GROUNDING ELECTRODE CONDUCTOR GEN GENERATOR HT HEAT TRACE IDC INITIATING DEVICE CIRCUIT J-BOX JUNCTION BOX kV KILOVOLT kVA KILOVOLT AMPERE kW KILOWATT kWh KILOWATT HOUR MFR MANUFACTURER MECH MECHANICAL MIN MINIMUM (A) NEW NAC NOTIFICATION APPLIANCE CIRCUIT NEC NATIONAL ELECTRIC CODE NEUT NEUTRAL NFPA NATIONAL FIRE PROTECTION ASSOCIATION NC NORMALLY CLOSED NIC NOT IN CONTRACT NO NUMBER; NORMALLY OPEN NTS NOT TO SCALE OD OVERHEAD DOOR; OVERALL DIAMETER PIV POST INDICATOR VALVE PNL PANEL PVC POLYVINYL CHLORIDE (PLASTIC) PWR POWER QTY QUANTITY REQD REQUIRED RH RANGE HOOD RMC RIGID METALLIC CONDUIT SF SUPPLY FAN; SQUARE FEET SLC SIGNALING LINE CIRCUIT SPEC SPECIFICATION ST SHUNT TRIP STD STANDARD TEL TELEPHONE TELCOTELEPHONE COMPANY TEMP TEMPORARY TS TAMPER SWITCH TYP TYPICAL UGND UNDERGROUND UL UNDERWRITERS LABORATORIES LION UNLESS OTHERWISE NOTED V VOLT VA VOLT AMPERE VAC VOLTAGE, ALTERNATING CURRENT VDC VOLTAGE, DIRECT CURRENT VR VANDAL RESISTANT W WATT W/ WITH W/0 WITHOUT WP WEATHERPROOF Z IMPEDANCE F 1 F;Z ALARM S Y S TM DEVICE LEGEND SYMBOL EXISTING MANUFACTURER PART NO DESCRIPTION QTY FACE EX X POTTER IPA-4000 EXISTING FIRE ALARM CONTROL PANEL 1 AiM POTTER PAD100-SIM SINGLE INPUT MODULE 1 o WP POTTER HS-24WR-WP OUTDOOR HORN STROBE, FIXED 75 CANDELA, STANDARD ENCLOSURE, RED 1 o' POTTER CHS-24W HORN STROBE, CEILING, WHITE 10 EX X POTTER CS-24W EXISTING STROBE, CEILING, WHITE 2 \ POTTER CS-24W STROBE, CEILING, WHITE 3 FIRE ALARM CABLE AND WIRE LEGEND LABEL WIRE TYPE MFR. PART NO. AWG RESISTANCE p/Mft) DESCRIPTION A SOUTHWIRE 55-46-88-03 16 4.09 2 COND. SOLID COPPER FPLP-MC B ------------------- COMTRAN 38700 14 3.07 2 COND. SOLID COPPER FPLR ANALOG UNSHIELDED C - - - - - - - - - - - - - - COMTRAN 38697 18 6.7000 4 COND. SOLID COPPER FPLR ANALOG UNSHIELDED TYPICAL DEVICE MOUNTING DETAIL ROOF DECK MOUNT TO STRUCTURE XR riff IF HEAD J-BOX ABOVE CEILING DEVICE J-BOX SUPPORT SUPPORT BRACKET BRACKET PLASTER RING CEILING BASE HEAD CEILING MOUNT SMOKE OR HEAT DETECTOR NOTIFICATION APPLIANCE WALL MOUNT NOTIFICATION APPLIANCE FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR OOSWIM MANUAL B B MMM o O eMo� ,ft...bl. R POW PULL STATION FIRE ALARM O 72" 60" 80" 48" DaricI.uarr-rnUr1lu,aut, uu,atuly ..11 For the Arts Grm �f . y 4 B ra 0.ketf s �. Lr�dll� North f Edmonds Ferry Terminal 7jonds •• c9 4 VY D wAon Sri Dayton St � s e l mo-nds StieHeberger A a r h j Creek -- clarl �1 a Sky' St 0,1L 1"Y qt Date} S �ILI ch jr5praguit 5Z 3 b rt 4 Z . Heir $1 550 Mairr St. Z Edmonds, WA980 B Mi3ple S1 > Maple Aldet St Alder E� i Beck Lri Walnut #i�Fly Ds Cedar St �a 1- N VICINITY MAP SHEET INDEX SHEET NO. SHEET DESCRIPTION FAO.1 TITLE SHEET FA1.1 LOWER & GROUND LEVEL - FIRE ALARM SYSTEM FA1.2 UPPER LEVEL, RISER DIAGRAM & BATTERY CALCULATIONS INPUTS GENERAL SYSTEM OPERATION ACTIVATION OF ANY SMOKE DETECTOR, HEAT DETECTOR OR MANUAL PULL STATION SHALL: VISUALLY INDICATE THE APPROPRIATE ZONE ON THE FACP: WHAT TYPE OF DEVICE WAS ACTIVATED. m = FROM WHICH AREA THE ALARM WAS GENERATED. O w = H U') ACTUATE EXTERIOR STROBE. Q w P- _ TRANSMIT THE APPROPRIATE ZONE ALARM SIGNAL TO THE APPROVED CENTRAL z Lu J '-' Ln U STATION FOR COMMUNICATION TO THE FIRE DEPARTMENT. ~ -j Q cm Ln w � THE SYSTEM SHALL BE ELECTRICALLY SUPERVISED SO THAT THE OCCURRENCE OF A Q w 0 OJ w w = w Ln � LA SINGLE OPEN, OR GROUND FAULT ON ANY FIELD WIRING, OR FAILURE OF PRIMARY POWER U Op w Q U, w J a SUPPLY, WILL CAUSE A VISUAL "TROUBLE" AT THE FACP & REMOTE ANNUNCIATOR AND A Q � � � En w a a "TROUBLE" SIGNAL SHALL BE TRANSMITTED TO THE APPROVED CENTRAL STATION FOR O� a O a cn APPROPRIATE ACTION. U >- >- J °C J Q J Q Cn CnLL J Y w (3 Q < < � a � = =)zU-) Q < Q Z � � O2 2 0 u) J ACTUATE ALARM SIGNAL AT FACP TRANSMIT ALARM SIGNAL TO CENTRAL STATION ACTIVATE ALL BUILDING NOTIFICATION APPLIANCES ACTUATE TROUBLE SIGNAL AT FACP TRANSMIT TROUBLE SIGNAL TO CENTRAL STATION O TRANSMIT SUPERVISORY SIGNAL TO CENTRAL STATION TRANSMIT WATERFLOW SIGNAL TO CENTRAL STATION SEQUENCE OF OPERATIONS MATRIX � W 00 LU�� c cn H 0 D 00 ffnn 6 V) 00 00 J . LL + _ Z R I — o vl V Z •~ OLHrn9 0 00 LL N �- m I 0 o O0O 0 0Z�3 " 14 ii 3 EL E C T R T E t H PO Box 13889 Mill Creek, WA 98082 (:425:) 4-05-0583 F=- (:866Do 79E3-9241 W Q 0 Z 0 L W M ADRIAN M. STEIK \ Senior Engineering Technician, Level 4 NI ET Certifcation Number: 093706 Authorizing Signature: 6-w- 0'. j"0 w J F- t= W W H 0 DRAWN BY: " RC CHECKED BY: Adrian M. Steik PLOT DATE: 3 / 2 / 2 4 PROJECT NUMBER: 24-00 DRAWING ONLY TO SCALE IF PLOTTED AT 30" X 42" SHEET NUMBER: �0 IW � � LL01=- v N O\ 00 N�} W� c`n H ^� GENERAL NOTES 2 V Q00 Illu U q< —i 1. ALL SHADED AREA'S ARE NOT PART OF T.I. SCOPE OF j LL - WORK, FIRE ALARM WITHIN THESE AREAS ARE EXISTING x Q I - U AND TO REMAIN UNTOUCHED. EXISTING FIRE ALARM � a 0 N DESIGN IS FOR REFERENCE ONLY. iL H rn LL N t FLAG NOTE u m"I^� o4- CEXISTING KNOX BOX LOCATION WITH KEY. O Z 00 00 CEXISTING DOOR SIGNAGE DENOTING "FACP ENTRANCE". T 3 CINPUT MODULE FOR TYPE I HOOD SUPPRESSION SYSTEM. CEXISTING WALL MOUNT NOTIFICATION APPLIANCE TO BE RELOCATED AND REPLACED WITH NEW CEILING MOUNT T E f- Af NOTIFICATION APPLIANCE. PO Box 13889 Mill Creek, WA 98082 (:425:) 4-05-Ill 583 F8663 798-9241 H O 1 2 3 6 7 8 W C a a A PRIVATE DINING OOM BIN a c X� (il CP•NAC2.OS EOL FRE --� r---------- — 30cd - PIT JL-------------------J BANQUETTE IL)CANOPY, ABOVE 1 B FAA I LSERVII ESTATQN KX 1 o CUSTOMER DINING EX EX WOMEN RESTROOM m H 110CD BANQUETTE CP•NAC2.05 EX 4 115cd I I I I I I I EX I — — — — — — — L — — — — — — — — — — — — — — L T UPPER El < C I I I I I I❑ I I CP•NAC2. 6 75cd L---------- MEN RE STROOM i T R CP•N C •03 75cd \ CP•NAC2.04'\ j ` EX d i BAR — I ADRIAN M. ST EIK ❑ — ------ --------------I P•NA Senior Engineering Technician, Level 4 ❑ D 75cd NICET Certifcation Number: 093706 STAIR I WP _= Authorizing Signature: - I I I ELEVATOR SLC1.004 S EX — — — — � — ❑ I CP•NAC2.03 — — — C — E I 75cd — — — — — CW COUNTER - OPEN KITCHEN/ PREP./ PASS ■ W NOT IN SCOPE S SLC1.005 10CE TJ EX ffhllfhllflll 4 1EX ❑RRI-1 KITCHEN CP•NAC6.01 110CD 4 75cd EX 3 O 0 HR TO EXISTING FACP j o V CP•SLC1.007 < O HR TO EXISTING FACP AIM ❑ SERVI ESTATION N / 15cd jEXIT TA ILLppRR AAC3.01 CP• AC3.02 WALK-IN COOLER SCI ILLERY / 15cd \ O 15cd � W EX RR 00 . I2 LU iiiIiiiiin CP•NAC3.03 110cd W — — — — — — — — — — — — — — ------------ 71 [--�EX _ — — — — — — — — G CP•NAC2.02 75cd PART OF THIS PERMIT LL CP•NAC3.04 Ij KITCHEN STORAGE 75cd W Uj EX FUTURE T.I. � I� W � L V1 W SLC1.002 AIM TAMPER SWITCH 2 FLOW SWITCH O I I I EX 1 CP•NAC3.05 EOL � Q ® SLC1.001 F 3EX NOT IN SCOPE EX z � cP•NAc1•o1 EOL � � NOT PART OF THIS PERMIT FUTURE T.I. �$ Q EX STORAGE 95cd SLC1.003 EX EX " LOADING DOCK O �1Ot� r7 N Ip Ln IN 0 0 UP Uj 04 - - - - -- L- - - - p w W w OW W DRAWN BY: " RC PLAN NORTH PLAN NORTH CHECKED BY: Adrian M. Steik LOWER LEVEL FIRE ALARM SYSTEM GROUND LEVEL FIRE ALARM SYSTEM A SCALE = 118" = 1' 0" 4' $' 12' 16' B SCALE = 118" =1' 0" Q 4' $' 12' 16' Irr3 / 2 / 2 4 iV PLOT DATE: PROJECT NUMBER: 24-00 2 DRAWING ONLY TO SCALE IF PLOTTED AT 30" X 42" SHEET NUMBER: CP•NAC6.08 EOL CP-NAC6.07 CP•NAC6.06 CP•NAC6.05 CP•NAC6.04 15cd 30cd ------------- E--------- 75cd i--------- 75cd i--------- � , 15cd ; /ate i UPPER LEVEL i i CP•NAC6.02 CP•NAC6.03 75cd CP•NAC6.01 75cd WP 75cd CP•NAC2.05 CP•NAC2.04 CP•NAC2.08 EOL CP•NAC2.07 CP•NAC2.06 15cd 15cd CP•NAC2.03 CP•NAC2.02 CP•NAC2.01 30cd ------------- 30cd75cd --------- --------- , EX --------- , EX --------- 75cd ----------i--------- 75cd , 15cd ----i k�( k�C _lam _-� _Ck GROUND LEVEL EXISTING FIRE ALARM -- CONTROL PANEL � CP•SLCl-007 -. ® AIM H - DEDICATED 120V N - 20 AMP CIRCUIT G LOWER LEVEL FIRE ALARM RISER DIAGRAM SCALE = NOT TO SCALE 6 H UPPER LEVEL - FIRE ALARM SYSTEM SCALE = 1/8" = 1' 0" 0 4' 8' 12' 16' GENERAL NOTES 1. ALL SHADED AREA'S ARE NOT PART OF T.I. SCOPE OF WORK, FIRE ALARM WITHIN THESE AREAS ARE EXISTING AND TO REMAIN UNTOUCHED. EXISTING FIRE ALARM DESIGN IS FOR REFERENCE ONLY. 2. BATTERY CALCULATIONS FROM THE FULL EXISTING BUILDING HAVE BEEN ADDED FOR REFERENCE ONLY, ALL CIRCUITS THAT HAVE BEEN ADDED OR ALTERED FOR THIS T.I.'S SCOPE OF WORK HAVE BEEN OUTLINED IN BOLD WITH A "SCOPE OF WORK" TEXT DESIGNATION. FLAG NOTE 1� EXISTING EXTERIOR NOTIFICATION IS MOUNTED BETWEEN 80"-96" AFF. FIELD VERIFY EXACT LOCATION OF EXISTING DEVICE. CEXISTING WALL MOUNT NOTIFICATION APPLIANCE TO BE RELOCATED AND REPLACED WITH NEW CEILING MOUNT NOTIFICATION APPLIANCE. PLAN NORTH ■ all SCOPE OF WORK - SCOPE OF WORK- EXISTING PANEL CP (IPA-4000) BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) PANEL POWER SUPPLY MAX CURRENT =10A TOTAL USED CAPACITY (IN ALARM) = 4.52588A (45.26 %) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL PANEL COMPONENTS 1 IPA-4000 MAIN BOARD Main Board for IPA-4000 0.13 0.13 0.22 0.22 Fire Alarm Control Panel CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) CP•NAC1 0' 1 CHS-24W (EX) Horn Strobe, Ceiling, White 0 0 0.243 0.243 EX 2 CHS 24W Horn Strobe, Ceiling, White 0 0 0.143 0.286 30cd 3 CHS-24W Horn Strobe, Ceiling, White 0 0 0.223 0.669 CP-NAC2 75cd 1 CS-24W Strobe, Ceiling, White 15cd 0 0 0.12 0.12 EX 2 CS-24W (EX) Strobe, Ceiling, White 15cd 0 0 0.12 0.24 N r-1 It -9 N O\ 00 N�} 7 LU�� H 00 6 Vfn) Q N � � W U tL > } Q I - o a�� N aHrn3 LL c I Y O N � U � � mI� o�°O 0Z00 EX 2 CS-24W (EX) Strobe, Ceiling, White 15cd 0 0 0.12 0.24 L E 1 HS-24WW (EX) Horn Strobe, 24 VDC, White 0 0 0.114 0.114 EX 30cd CP•NAC3 1 HS-24WW (EX) Horn Strobe, 24 VDC, White 0 0 0.217 172 0.217 EX 75cd � f 11 1 HS-24WW (EX) Horn Strobe, 24 VDC, White 0 0 0.217 0.217 EX 110cd P O ig O x 1 3 8 8 9 Outdoor Horn Strobe, Fixed CP-NAC4 o WP 1 HS-24WR-WP (EX) 75 Candela, Standard 0 0 0.226 0.226 M i I I C Ir 22 k, WA 9 8 08 2 Enclosure, Red 75cd 4 2 5:) 4 O 5- 0 5 8 3 Outdoor Horn Strobe, Fixed CP•NAC5 �o EX WID 1 HS-24WR-WP (EX) 75 Candela, Standard C'....I....��... D-A 7r-A 0 0 0.226 0.226 F _ 8 6 6� Hom Strobe, Ceiling, White 1 CHS-24W 30cd 0 0 0.143 0.143 4 CHS 24W Hom Strobe, Ceiling, White 0 0 0.223 0.892 75cd CP•NAC6 2 CS-24W Strobe, Ceiling, White 15cd 0 0 0.12 0.24 1 HS-24WR-WP Outdoor Horn Strobe, Fixed 75 Candela, Standard 0 0 0.226 0.226 WP Enclosure, Red 75cd CP•P-LINK LEA-A]EX 1 RA-6500 (EX) IUV 1-11ldld';U11 LI L) 0.02 0.02 0.05 0.05 Annunciator SEX 1 PAD100-DIM (EX) Dual Input Module 0.00024 0.00024 0.00024 0.00024 PAD100-PD Photoelectric Smoke EX 4 w/PAD100-6DB (EX) Detector with 6" Standard 0.0003 0.0012 0.0003 0.0012 CP•SLC1 Base ❑F EX 1 PAD 100-PSSA (EX) Addressable Pull Station S'nole Act on 0.0002 0.0002 0.0002 0.0002 SCOPE OF WORK AiM 1 PAD100-SIM Single Input Module 0.00024 0.00024 0.00024 0.00024 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SCOPE OF WORK SCOPE OF WORK SECONDARY STANDBY LOAD (A) 0.15188 24 3.65 SECONDARY ALARM LOAD (A) 4.52588 0.08 0.38 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 4.02 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 4.83 PROVIDE (2)12V 8AH BATTERIES *BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION. CP NAC1 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.04 in. Operational Voltage: 16 End Of Line Voltage: 20.36 Max. Circuit Current (A): 3 Voltage Drop Percent: 0.20 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.243 Circuit Wiring Properties: 'B' 3870014 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED Total Circuit Length (Ft): 27 Spare Current (A): 2.757 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.168277 Spare Current (A) Percent: 91.90 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) DEVICE TOTALS EX CHS-24W Horn Strobe, Ceiling, White 1 0.243 0.243 Calculation Methods: Total Resistance (0) = Wire Resistance (0/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) CP NAC2 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 2.25 Min. Operational Voltage: 16 End Of Line Voltage: 18.15 Max. Circuit Current (A): 3 Voltage Drop Percent: 11.03 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 1.315 Circuit Wiring Properties: 'B' 3870014 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED Total Circuit Length (Ft): 279 Spare Current (A): 1.685 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.710544 Spare Current (A) Percent: 56.17 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) CS-24W Strobe, Ceiling, White 15cd 3 0.12 0.36 DEVICE TOTALS CHS-24W Horn Strobe, Ceiling, White 2 0.143 0.286 CHS-24W Horn Strobe, Ceiling, White 3 0.223 0.669 Calculation Methods: Total Resistance (0) = Wire Resistance (0/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) CP NAC3 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.56 in. Operational Voltage: 16 End Of Line Voltage: 19.84 Max. Circuit Current (A): 3 Voltage Drop Percent: 2.76 % Wire Resistance (f)/kFt): 3.07 Total Circuit Current (A): 0.743 Circuit Wiring Properties: 'B' 3870014 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED Total Circuit Length (Ft): 123 Spare Current (A): 2.257 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.756602 Spare Current (A) Percent: 75.23 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) In EX HS-24WW Horn Strobe, 0244 VDC, White 1 0.114 0.114 DEVICE TOTALS )C( EX CS-24W Strobe, Ceiling, White 15cd 2 0.12 0.24 I EX HS-24WW Horn Strobe, 24 VDC, White 75cd 1 0.172 0.172 In EX HS-24WW Horn Strobe, 24 VDC, White 110od 1 0.217 0.217 Calculation Methods: Total Resistance (0) = Wire Resistance (f)/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) CP NAC4 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.14 in. Operational Voltage: 16 End Of Line Voltage: 20.26 Max. Circuit Current (A): 3 Voltage Drop Percent: 0.68 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.226 Circuit Wiring Properties: 'B' 3870014 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED Total Circuit Length (Ft): 100 Spare Current (A): 2.774 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.614 Spare Current (A) Percent: 92.47 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) DEVICE TOTALS Ex WP tHS-24WR-WP Outdoor Horn Strobe, Fixed 75 Candela, Standard Enclosure, Red 75cd 1 0.226 0.226 Calculation Methods: Total Resistance (0) = Wire Resistance (0/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) CP NAC5 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.15 in. Operational Voltage: 16 End Of Line Voltage: 20.25 Max. Circuit Current (A): 3 Voltage Drop Percent: 0.75 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.226 Circuit Wiring Properties: 'B' 3870014 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED Total Circuit Length (Ft): 110 Spare Current (A): 2.774 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.6754 Spare Current (A) Percent: 92.47 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) DEVICE TOTALS EX WID HS-24WR-WP Outdoor Horn Strobe, Fixed 75 Candela, Standard Enclosure, Red 75cd 1 0.226 0.226 Calculation Methods: Total Resistance (0) = Wire Resistance (0/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) CP NAC6 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 2.49 Min. Operational Voltage: 16 End Of Line Voltage: 17.91 Max. Circuit Current (A): 3 Voltage Drop Percent: 12.18 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 1.501 Circuit Wiring Properties: 'B' 3870014 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED Total Circuit Length (Ft): 270 Spare Current (A): 1.499 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.655575 Spare Current (A) Percent: 49.97 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) CS-24W Strobe, Ceiling, White 15cd 2 0.12 0.24 CHS-24W Horn Strobe Ceiling, White 1 0.143 0.143 DEVICE TOTALS o CHS 24W Horn Strobe, Ceiling, White 75cd 4 0.223 0.892 �o WP HS-24WR-WP Outdoor Horn Strobe, Fixed 75 Candela, Standard Enclosure, Red 75cd 1 0.226 0.226 Calculation Methods: Total Resistance (0) = Wire Resistance (0/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) FIRE ALARM BATTERY CALCULATIONS SCALE = NOT TO SCALE z 0 W M J O m ADRIAN M. STEIK Senior Engineering Technician, Level 4 NICET Certifcation Number: 093706 Authorizing Signature: 6-- o' F�- Z C14 Uj Fm� 0 V op ON *0 w 00 5Q N W� CN HQ Z 2 Q0 oLri NW L^ Z O V J V W M Q ct V W V'f J W W J J W F- W 'L W H DRAWN BY. " �� CHECKED BY: Adrian M. Steik PLOT DATE: 3/2/24 PROJECT NUMBER: 24-00 DRAWING ONLY TO SCALE IF PLOTTED AT 30" X 42" 1 FA I SHEET NUMBER: