REVIEWED BLD2024-0305+Specifications +3.6.2024_8.22.56_AM+4106418REVIEWED
BY
CITY OF EDMONDS Box Load Calculation RECEIVED
Mar 062024
VICTOR TAVERN EDMONDS, WA
�
CITY OFEDMONDS
DEVELOPM SERVICES
General Requirements DEVELOPMENT
DEPARTMENT
BLD2024-0305
Room Temperature: 35 °F Ambient Temperature: 95 °F Design Run-time: 16 Hrs Required Capacity: 11,537 BTUH
Area Load
Section Material Thickness X - Factor Surface Temp
Wall 1 Polyurethane 4 in 0.1 95 °F
Dim. 1 Dim. 2 Load
10.1 ft 6.8 ft 3,474.9 BTU
Wall 2 Polyurethane 4 in 0.1 95 °F
17.3 ft 6.8 ft 5,946.7 BTU
Wall 3 Polyurethane 4 in 0.1 95 °F
10.1 ft 6.8 ft 3,474.9 BTU
Wall 4 Polyurethane 4 in 0.1 95 °F
17.3 ft 6.8 ft 5,946.7 BTU
Ceiling Polyurethane 4 in 0.1 110 °F
10.1 ft 17.3 ft 10,954.4 BTU
Floor Concrete 6 in 1.3 65 °F
Product Load - Auto Usage Selected
10.1 ft 17.3 ft 26,082 BTU
Total Area Load: 55,879.7 BTU
Air Change Load
Total Product Load: 22,835.3 BTU
Dry Bulb: 80.4 °F Wet Bulb: 65.6 °F
Door Type 1: Man Number of Door Type 1: 1 Door Usage: Average
Door Type 1: Curtains: None Door Type 1 Curtain Efficiency: 0% Total Door Type 1 Load: 16,800 BTU
Total Air Change
Load: 53,239.9 BTU
Miscellaneous Load
People Load: 21,600 BTU Lighting Load: 14,251.2 BTU
Motor Load: 0 BTU
Other Load: 0 BTU
Total Misc. Load: 35,851.2 BTU
Load Calculation Summary
Total Design Load: 167,806.1 BTU Safety Factor: 10%
Total Required Load: 184,586.7 BTU
Quotes are valid for 30 Days. Due to ongoing Product development. RapidSpec and its export documentation is subject to change without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec.
VICTOR TAVERN I EDMONDS, WA
COOLER - System Design Summary
General Requirements
Room Temperature: 35 °F Ambient Temperature: 95 °F
Design Run-time: 16 Hrs Required Capacity: 11537 BTUH
Design TD: 10 °F Refrigerant: R-448A
Altitude: 0 FT
Selected Equipment
Line Item Quantity Type Tag
Description
1.0 1 System COOLER
R-448A - Refrigeration Equipment Match 1
1.1 1 Condensing Unit CDU-1
1.2 1 Unit Cooler UC-1
System Balance
RFO150E4SEA
RL6A094ADA
Balanced Capacity: 11,917.8 BTUH Evap. T.D.: 10.9 °F
Line Loss: 2 °F Suction Temp: 22.1 °F Calc. Run -Time: 15.5 Hrs
Quotes are valid for 30 Days. Due to ongoing product development. RapidSpec and its export documentation is subject to change without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec.
VICTOR TAVERN I EDMONDS, WA
COOLER - CDU-1 - Product Information
General Data
Model Line: NEXT-GEN MINI -CON Model Number: RFO150E4SEA
Flooded: Yes
Refrigerant: R-448A Voltage: 208-23013160
Compressor Type: SCROLL
Performance Data
Ambient Temp: 95 °F Suction Temp: 23 °F
Capacity: 11,664 BTUH
Electrical Data
Compressor RLA: 9.3 Compressor LRA: 58
Total Condenser Fan FLA: 1
MCA: 15 MOPD: 20
Physical Data
Number of Compressors: 1 Compressor Model: ZS11 KAE
Compressor HP: 1.5
Number of Condenser Fans: 2 Approx. Ship Weight: 205 Ibs
Sound Data: 71 dBA
Liquid Line: 1/2 in. Suction Line: 7/8 in.
Pump Down Capacity (%): 90 Pump Down Capacity: 11.6 Ibs
Option Data
Mounted Option NO STANDARD AIR DEFROST TIMER
Mounted Option LIQUID LINE WITH COMPONENTS: SEALED FILTER & SIGHT GLASS
Mounted Option STANDARD RECEIVER
Mounted Option FIXED HIGH/ADJUSTABLE LOW PRESSURE CONTROL
Warranty Option EXTENDED COMPRESSOR WARRANTY (4 YEAR) - SCROLL
Compliance Data
AWEF: 7.60
Notes
Quotes are valid for 30 Days. Due to onaoina product development. RapidSpec and its export documentation is subject to chance without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec. MCA/MOPD and Defrost Kit selection will be confirmed at time of
purchase. Submittal data shown represents design conditions.
Dimensional Drawing
28-1/4
LIQUII
OUT
W.
T T
24-3/16 ------,j
Standard Features
• All-weather Galvanized steel painted housing
• Generously sized high efficiency condenser,
enhanced copper tubes/aluminum fins
• Integral Liquid Subcooling Circuit provides subcooled
liquid to the expansion device
• Crankcase heater
• Large electrical panel with hinged/removable door
• Color coded point-to-point wiring
Certifications
38-1/4
CONTROL
PANEL
- 7/8" KO (2)
FOR
ELECTRICAL
CONNECTIONS
3/8" MOUNTING HOLES (4)
39-1 /8
39-7/8
• Quick access to shut off valves from exterior
• UL/cUL certified for use with multiple refrigerants
• UL/cUL listed for outdoor use
• Flooded models include flooded head pressure
control
• Non flooded models include mild ambient fan cycle
control
VICTOR TAVERN I EDMONDS, WA
COOLER - UC-1 - Product Information
General Data
Model Line: NEXT-GEN ALL -TEMP Model Number: RL6A094ADA Motors: DUAL SPEED EC MOTOR
Unit Voltage: 115/1/60 Defrost Type: AIR DEFROST Refrigerant: R-448A
Fins Per Inch: 6 Number of Fans: 2
Performance Data
Suction Temp: 25 °F T.D: 10.9 °F Capacity: 11,917.8 BTUH CFM: 1570
Electrical Data
Motor Voltage: 115/1/60 Total Unit Fan Motor Amps: 1.6
Heater Voltage: 115/1/60 Heater Amps: 0 Heater Watts: 0
MCA: 15 MOPD: 20
Physical Data
Liquid Line: 3/8 in. Suction Line: 5/8 in. Approx. Ship Weight: 55 Ibs
Option Data
Mounted Option EcoNet Control Package
Manual Option White Epoxy Cabinet Coating
Compliance Data
AWEF: 9.00
Notes
Quotes are valid for 30 Days. Due to onaoina product development. RapidSpec and its export documentation is subject to chance without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec. Submittal data shown represents design conditions. This quote contains
options that were manually added. All manually added options will require review by HTPG prior to orders being accepted.
Dimensional Drawing
16
(BACKSIDE)
Standard Features
• Embossed aluminum housing
• Enhanced copper tube and aluminum fin coil
construction
• Sweat connections
• Thermal overload protection
• High efficiency fan guard design and deep draw
venturi
• Heavy-duty fans are balanced for vibration -free
operation
Certifications
��pSSIFjFo
C UL uS
7/8 ELECTRICAL
KNOCKOUTS
(BACKSIDE)
AIR
• Fan sections are baffled to prevent short cycling of air
• Slide out end panels
• Removable drain pan
• Mounts flush to the ceiling
• Top pan includes 1/2" wide slotted mounting points
• UL/cUL certified for use with multiple refrigerants
• NSF approved for use in food preparation areas