REVIEWED BLD2024-0305+Specifications +3.6.2024_8.22.56_AM+4106418REVIEWED BY CITY OF EDMONDS Box Load Calculation RECEIVED Mar 062024 VICTOR TAVERN EDMONDS, WA � CITY OFEDMONDS DEVELOPM SERVICES General Requirements DEVELOPMENT DEPARTMENT BLD2024-0305 Room Temperature: 35 °F Ambient Temperature: 95 °F Design Run-time: 16 Hrs Required Capacity: 11,537 BTUH Area Load Section Material Thickness X - Factor Surface Temp Wall 1 Polyurethane 4 in 0.1 95 °F Dim. 1 Dim. 2 Load 10.1 ft 6.8 ft 3,474.9 BTU Wall 2 Polyurethane 4 in 0.1 95 °F 17.3 ft 6.8 ft 5,946.7 BTU Wall 3 Polyurethane 4 in 0.1 95 °F 10.1 ft 6.8 ft 3,474.9 BTU Wall 4 Polyurethane 4 in 0.1 95 °F 17.3 ft 6.8 ft 5,946.7 BTU Ceiling Polyurethane 4 in 0.1 110 °F 10.1 ft 17.3 ft 10,954.4 BTU Floor Concrete 6 in 1.3 65 °F Product Load - Auto Usage Selected 10.1 ft 17.3 ft 26,082 BTU Total Area Load: 55,879.7 BTU Air Change Load Total Product Load: 22,835.3 BTU Dry Bulb: 80.4 °F Wet Bulb: 65.6 °F Door Type 1: Man Number of Door Type 1: 1 Door Usage: Average Door Type 1: Curtains: None Door Type 1 Curtain Efficiency: 0% Total Door Type 1 Load: 16,800 BTU Total Air Change Load: 53,239.9 BTU Miscellaneous Load People Load: 21,600 BTU Lighting Load: 14,251.2 BTU Motor Load: 0 BTU Other Load: 0 BTU Total Misc. Load: 35,851.2 BTU Load Calculation Summary Total Design Load: 167,806.1 BTU Safety Factor: 10% Total Required Load: 184,586.7 BTU Quotes are valid for 30 Days. Due to ongoing Product development. RapidSpec and its export documentation is subject to change without notice. In no event shall HTPG be liable for special or consequential damages in connection with the use or output of RapidSpec. VICTOR TAVERN I EDMONDS, WA COOLER - System Design Summary General Requirements Room Temperature: 35 °F Ambient Temperature: 95 °F Design Run-time: 16 Hrs Required Capacity: 11537 BTUH Design TD: 10 °F Refrigerant: R-448A Altitude: 0 FT Selected Equipment Line Item Quantity Type Tag Description 1.0 1 System COOLER R-448A - Refrigeration Equipment Match 1 1.1 1 Condensing Unit CDU-1 1.2 1 Unit Cooler UC-1 System Balance RFO150E4SEA RL6A094ADA Balanced Capacity: 11,917.8 BTUH Evap. T.D.: 10.9 °F Line Loss: 2 °F Suction Temp: 22.1 °F Calc. Run -Time: 15.5 Hrs Quotes are valid for 30 Days. Due to ongoing product development. RapidSpec and its export documentation is subject to change without notice. In no event shall HTPG be liable for special or consequential damages in connection with the use or output of RapidSpec. VICTOR TAVERN I EDMONDS, WA COOLER - CDU-1 - Product Information General Data Model Line: NEXT-GEN MINI -CON Model Number: RFO150E4SEA Flooded: Yes Refrigerant: R-448A Voltage: 208-23013160 Compressor Type: SCROLL Performance Data Ambient Temp: 95 °F Suction Temp: 23 °F Capacity: 11,664 BTUH Electrical Data Compressor RLA: 9.3 Compressor LRA: 58 Total Condenser Fan FLA: 1 MCA: 15 MOPD: 20 Physical Data Number of Compressors: 1 Compressor Model: ZS11 KAE Compressor HP: 1.5 Number of Condenser Fans: 2 Approx. Ship Weight: 205 Ibs Sound Data: 71 dBA Liquid Line: 1/2 in. Suction Line: 7/8 in. Pump Down Capacity (%): 90 Pump Down Capacity: 11.6 Ibs Option Data Mounted Option NO STANDARD AIR DEFROST TIMER Mounted Option LIQUID LINE WITH COMPONENTS: SEALED FILTER & SIGHT GLASS Mounted Option STANDARD RECEIVER Mounted Option FIXED HIGH/ADJUSTABLE LOW PRESSURE CONTROL Warranty Option EXTENDED COMPRESSOR WARRANTY (4 YEAR) - SCROLL Compliance Data AWEF: 7.60 Notes Quotes are valid for 30 Days. Due to onaoina product development. RapidSpec and its export documentation is subject to chance without notice. In no event shall HTPG be liable for special or consequential damages in connection with the use or output of RapidSpec. MCA/MOPD and Defrost Kit selection will be confirmed at time of purchase. Submittal data shown represents design conditions. Dimensional Drawing 28-1/4 LIQUII OUT W. T T 24-3/16 ------,j Standard Features • All-weather Galvanized steel painted housing • Generously sized high efficiency condenser, enhanced copper tubes/aluminum fins • Integral Liquid Subcooling Circuit provides subcooled liquid to the expansion device • Crankcase heater • Large electrical panel with hinged/removable door • Color coded point-to-point wiring Certifications 38-1/4 CONTROL PANEL - 7/8" KO (2) FOR ELECTRICAL CONNECTIONS 3/8" MOUNTING HOLES (4) 39-1 /8 39-7/8 • Quick access to shut off valves from exterior • UL/cUL certified for use with multiple refrigerants • UL/cUL listed for outdoor use • Flooded models include flooded head pressure control • Non flooded models include mild ambient fan cycle control VICTOR TAVERN I EDMONDS, WA COOLER - UC-1 - Product Information General Data Model Line: NEXT-GEN ALL -TEMP Model Number: RL6A094ADA Motors: DUAL SPEED EC MOTOR Unit Voltage: 115/1/60 Defrost Type: AIR DEFROST Refrigerant: R-448A Fins Per Inch: 6 Number of Fans: 2 Performance Data Suction Temp: 25 °F T.D: 10.9 °F Capacity: 11,917.8 BTUH CFM: 1570 Electrical Data Motor Voltage: 115/1/60 Total Unit Fan Motor Amps: 1.6 Heater Voltage: 115/1/60 Heater Amps: 0 Heater Watts: 0 MCA: 15 MOPD: 20 Physical Data Liquid Line: 3/8 in. Suction Line: 5/8 in. Approx. Ship Weight: 55 Ibs Option Data Mounted Option EcoNet Control Package Manual Option White Epoxy Cabinet Coating Compliance Data AWEF: 9.00 Notes Quotes are valid for 30 Days. Due to onaoina product development. RapidSpec and its export documentation is subject to chance without notice. In no event shall HTPG be liable for special or consequential damages in connection with the use or output of RapidSpec. Submittal data shown represents design conditions. This quote contains options that were manually added. All manually added options will require review by HTPG prior to orders being accepted. Dimensional Drawing 16 (BACKSIDE) Standard Features • Embossed aluminum housing • Enhanced copper tube and aluminum fin coil construction • Sweat connections • Thermal overload protection • High efficiency fan guard design and deep draw venturi • Heavy-duty fans are balanced for vibration -free operation Certifications ��pSSIFjFo C UL uS 7/8 ELECTRICAL KNOCKOUTS (BACKSIDE) AIR • Fan sections are baffled to prevent short cycling of air • Slide out end panels • Removable drain pan • Mounts flush to the ceiling • Top pan includes 1/2" wide slotted mounting points • UL/cUL certified for use with multiple refrigerants • NSF approved for use in food preparation areas