FIR2023-0010+Fire_Alarm_Battery_Calculations+2.13.2023_10.29.36_AM+3365969
BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL PANEL COMPONENTS 1 GWF-7075 Main Board Intelligent Fire Alarm Control Panel Main Board 0 0 0 0 CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) AIM 2 4 AMM-21F Addressable Dual Monitor Module 0.0007 0.0028 0.0007 0.0028 AOM 5 AOM-2RF Addressable Relay Module 0.0003 0.0015 0.0003 0.0015 L1 0 P 4 ASD-PI3 / B300-6 BASE Addressable, Photo, Det. 0.0003 0.0012 0.0003 0.0012 4 ATD-1-3 / B300-6 BASE Intelligent Addressable 1357 (57°C) Thermal Detector W/ 6" Detector Base 0.0003 0.0012 0.0003 0.0012 ❑F 1 MS-7ASF Addressable Pull Station 0.0003 0.0003 0.007 0.007 Ell WP 2 P2RK Horn/Strobe,WP,Wall , Red 110cd 0 0 0.221 0.442 N1H 1 PC2WL Horn/Strobe, Ceiling, White 15cd 0 0 0.071 0.071 ;C11 1 SCWL Strobe, Ceiling, White 15cd 0 0 0.041 0.041 N2 Ell 14 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0 0 0.111 1.554 TOTAL STANDBY (A) 0.007 TOTAL ALARM (A) 2.1217 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SECONDARY STANDBY LOAD (A) 0.007 24 1 0.17 SECONDARY ALARM LOAD (A) 2.1217 0.08 1 0.18 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 0.34 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 0.41 PROVIDE (2) 12V 7AH BATTERIES *BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION. BATTERY CALCULATIONS RPS•N2.008 RPS•N2.009 RPS-12-010 RPS•N2.011 RPS•N2.012 RPSN2-013 RPSN2-014 EOL N1 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.37 Min. Operational Voltage: 16 End Of Line Voltage: 20.03 Max. Circuit Current (A): 2.5 Voltage Drop Percent: 1.81 % Wire Resistance (4/kFt): 3.07 Total Circuit Current (A): 0.554 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 188 Spare Current (A): 1.946 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.155506 Spare Current (A) Percent: 77.84 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent Nl-001 P2RK Horn/Strobe,WP,Wall , Red 110cd 0.221 0.554 32 0.194385 0.11 20.29 0.11 0.53 % Nl-002 SCWL Strobe, Ceiling, White 15cd 0.041 0.333 50 0.307 0.1 20.19 0.21 1.03 % N1.003 PC2WL Horn/Strobe, Ceiling, White 15cd 0.071 0.292 32 0.193621 0.06 20.13 0.27 1.31 % N1.004 EOL P2RK Horn/Strobe,WP,Wall , Red 110cd 0.221 0.221 75 0.4605 0.1 20.03 0.37 1.81 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (0/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) N2 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 2.21 Min. Operational Voltage: 16 End Of Line Voltage: 18.19 Max. Circuit Current (A): 2.5 Voltage Drop Percent: 10.82 % Wire Resistance (4/kFt): 3.07 Total Circuit Current (A): 1.554 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 363 Spare Current (A): 0.946 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 2.227758 Spare Current (A) Percent: 37.84 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent N2.001 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 1.554 100 0.614 0.95 19.45 0.95 4.68 % N2.002 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 1.443 16 0.098313 0.14 19.3 1.1 5.37 % N2.003 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 1.332 2 0.011292 0.02 19.29 1.11 5.45 % N2.004 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 1.221 17 0.102415 0.13 19.16 1.24 6.06 % N2.005 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 1.11 28 0.174209 0.19 18.97 1.43 7.01 % N2.006 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.999 22 0.137515 0.14 18.83 1.57 7.68 % N2.007 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.888 21 0.129635 0.12 18.72 1.68 8.24 % N2.008 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.777 50 0.307 0.24 18.48 1.92 9.41 % N2.009 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.666 21 0.129635 0.09 18.39 2.01 9.84 % N2.010 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.555 22 0.137515 0.08 18.32 2.08 10.21 % N2.011 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.444 28 0.174209 0.08 18.24 2.16 10.59 % N2.012 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.333 17 0.102415 0.03 18.21 2.19 10.76 % N2.013 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.222 2 0.011292 0 18.2 2.2 10.77 % N2.014 EOL HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.111 16 0.098313 0.01 18.19 2.21 10.82 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (0/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) POINT TO POINT VOLTAGE DROP CALCULATIONS L1 -D006 L1 •DO07 135* 135* FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM ROY L CATS LU #0 rn r NFRA CFPS #14T3 T 00 CD CD k N _ LL: w_ ❑ U H Lu Z LU U > W �W0 CO U J 11 H ❑ U = IX VH U J IL LU Q U p ❑ o z>.wRU- cow, O O m❑LLc� V 2 Z3: J W �w�*ka ❑ �wwCaR Q ❑ofCnJa ❑ REVISION RECORD DATE / DESCRIPTION RECEIVED Feb 13 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FI R2023-0010 DATE: 02/09/2023 PROJECT NAME THIRD FLOOR ----------- A --------------------------------------------------- THIRD FLOOR z o - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4M W w Q LF LF LF LF A LF LF LF U =zU) c FACP•N1 •004 EOL RPS•N2.007 RPS•N2.006 RPS�N2.005 RPS•N2.004 RPS•N2.003 RPS412.002 RPS�N2.001 y y LV 11 IO A L1 -DO04 L1 •D005 WP Q 135* 135* 0 = Z SECOND FLOOR -__------------------------------------------------- SECOND FLOOR Q m a O - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - NEW FACP AES Qin FIRE ALARM a LOLV CONTROL PANEL 3Z Z02 Z02 Z02 Z02 � 7PS ®uZ01 DFZ01 01 Z01 Q r, rA a r, FACP +11 •003 >� FACP •N 1 -002 15cd 15cd v FACP •N 1 -001 110Cd N-ID2DEDICATED 120V „ u u I� Z Z Z Z Z u u SHEET TITLE WP c -B 20 AMP CIRCUIT F S AIM 2 AIM 2 AIM 2 AIM 2 S AOM S AOM AOM AOM AOM FACP PULL FACP SMOKE L1 0002 L1 •M004 L1 •M006 L1 •M008 LVL 1 ELEV L1 •M010 LVL 1 ELEV L1 •M011 L1-M012 L1 •M013 L1 •M014 FIRE ALARM L1 0001 L1 •DO01 WET WF DRY WF LOW AIR L1 •M009 LOBBY SMOKE ELEV DH MACH RM SMOKE PRIMARY ALTERNATE HAT DAMPER BATTERY CALCULATIONS L1 -M003 L1 •M005 L1 •M007 BACKFLOW L1 •DO02 L1 -D003 & WET TMPR DRY TMPR PIV SINGLE LINE RISER WET SYS DRY SYS DIAGRAM FIRST FLOOR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - FIRST FLOOR SINGLE LINE RISER DIAGRAM SHEET NUMBER I FA 10