APPROVED ENG STM RESUB1 BLD2021-0092+Structural Plans+3.1.2021_8.29.44_AM+2067939DESIGN CRITERIA VERTICAL LOADS ON VAULT LID; *UNIFORM LIVE LOAD ; = 150PSF *HS20 TRUCK WHEEL LOADS 13'-6" 14' to 30' TRACTOR FRONT AXLE = 81000 lb, 0 0 o SINGLE REAR AXLE = 321000 lb. FRONT REAR REAR TRAILER 0 0 o SINGLE REAR AXLE = 321000 lb, TRACTOR TRAILER *DESIGN LIVE LOAD & TRUCK WHEEL LOAD TO BE APPLIED INDEPENDENTLY AND IN COMBINATION WITH THE SOIL COVER DEAD LOAD, IMPACT & FATIGUE: DUE TO THE LOW SPEEDS OF SERVICE VEHICLES OVER THE LID, AND THE SOIL COVER OVER THE LID, INCREASES IN VEHICLE LOADS TO ACCOUNT FOR IMPACT & FATIGUE ARE NOT REQUIRED, SOIL COVER FOR LID DESIGN: PLANK MANUFACTURER SHALL BE RESPONSIBLE FOR DETERMINING THE SOIL COVER DEPTHS USED IN THE LID DESIGN BASED ON THE VAULT AND FINISHED GRADE ELEVATIONS AS SHOWN ON THE PERMITTED CIVIL DWGS, SOIL COVER FOR SUBSTRUCTURE DESIGN; THE SUBSTRUCTURE WAS DESIGNED FOR A SOIL COVER OF 1,2FT MIN TO 1,5FT MAX. FOUNDATION DESIGN: FOUNDATION DESIGN IS BASED ON THE FOLLOWING VALUES PROVIDED BY PAN GEO IN THEIR REPORT DATED 11-14-2018, ALLOWABLE BEARING PRESSURE; 4,00E PSF LATERAL EARTH PRESSURES ON DETENTION VAULT; DRAINED LEVEL BACKFILL AT REST CONDITION; 45 PCF EFW ACTIVE CONDITION; 35 PCF EFW SEISMIC PRESSURE COMPONENT; E=7H PSF UNIFORM SATURATED SOIL DENSITY; 125PCF SPECIAL INSPECTION PLAN GENERAL: SPECIAL INSPECTION BY A QUALIFIED INSPECTOR IS REQUIRED IN ACCORDANCE WITH THE 2015 IBC. QUALIFICATION: THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL, REQUIRED VERIFICATION & INSPECTION: THE SPECIAL INSPECTOR SHALL PERFORM THE VERIFICATIONS & INSPECTIONS NOTED IN THE SCHEDULE BELOW INSPECTION & TESTING SCHEDULE TYPES OF WORK FREQ. SECS IBC SECTION CAST IN PLACE CONC REINFORCING STEEL, PLACEMENT. P 1705.3 INSTALLATION & FASTENING OF PRECAST PANELS P 1705.3 PLACEMENT OF CONCRETE C 1705.3 VERIFYING USE OF REQUIRED DESIGN MIX P 1705.3 TESTING OF THE CONCRETE FOR SPECIFIED STRENGTH, AIR CONTENT AND SLUMP C 1705,3 SOILS VERIFICATION OF SOIL -BEARING CAPACITY: INSTALLATION OF DRAINAGE SYSTEM: C 1705.6 PLACEMENT & COMPACTION OF WALL BACKFILL: P 1705.6 FREQUENCY LEGEND C = CONTINUOUS P = PERIODIC SEE REFERENCES AND STANDARDS LISTED WITHIN THE VERIFICATION & INSPECTION SCHEDULE FOR MEANING OF PERIODIC AND CONTINUOUS INSPECTIONS, SUBMITTAL OF REPORTS: ALL SPECIAL INSPECTION REPORTS AND TESTING REPORTS SHALL BE SUBMITTED TO THE OWNER, SITE STRUCTURES AND THE BUILDING OFFICIAL BY THE AGENCY PERFORMING THE INSPECTION OR TESTING, HOLLOW CORE PLANK SCOPE OF WORK: THE WORK INCLUDED IS THE DESIGN, MANUFACTURE AND DELIVERY OF PRECAST PRESTRESSED CONCRETE UNITS, DESIGN PLANK FOR THE MOST CRITICAL OF THE LOADING CONDITIONS AS SHOWN WITHIN THE DESIGN CRITERIA NOTE, THE MANUFACTURER SHALL SUBMIT STRUCTURAL CALCULATIONS AND PLACEMENT DRAWINGS SIGNED BY A WASHINGTON STATE REGISTERED CIVIL ENGINEER FOR REVIEW PRIOR TO FABRICATION, THE MANUFACTURER SHALL INSTALL ALL BLOCK OUTS REQUIRED FOR STRUCTURAL CONNECTIONS AS INDICATED ON THESE DRAWINGS, NO OTHER PENETRATIONS ARE ALLOWED WITHOUT THE PRIOR APPROVAL OF THE PLANK MANUFACTURER. ALL HOLLOW CORE JOINTS SHALL BE GROUTED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, GENERAL CONSTRUCTION NOTES CODE: VAULT DESIGN AND CONSTRUCTION SHALL CONFORM TO THE PROVISIONS OF THE 2015 IBC AS ADOPTED BY THE CITY OF EDMONDS, WASHINGTON, GENERAL DETAILS: CONSTRUCTION DETAILS NOT FULLY SHOWN OR NOTED SHALL BE SIMILAR TO DETAILS SHOWN FOR SIMILAR CONDITIONS, DISCREPANCIES: THE CONTRACTOR SHALL NOTIFY ENGINEER UPON FINDING ANY DISCREPANCY OR OMISSION IN THE DRAWINGS OR SPECIFICATIONS, SHORING & EXCAVATION: THE CONTRACTOR SHALL BE SOLEY RESPONSIBLE FOR ALL EXCAVATION PROCEDURES, INCLUDING LAGGING, SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES, WALL BACKFILL: PRIOR TO BACKFILLING VAULT WALLS THE CONTRACTOR SHALL HAVE PLACED THE LID PLANKS AND PROVIDED A MINIMUM OF 5 DAYS OF CURE ON THE PLANK VOID FILL, BACKFILL SOIL: SEE THE GEOTECHNICAL REPORT FOR WALL BACKFILL MATERIAL REQUIREMENTS AND PLACEMENT AND COMPACTION REQUIREMENTS. ALL COMPACTION OCCURING WITHIN 5' OF THE WALL SHALL BE COMPLETED USING HAND OPERATED MACHINERY, CONCRETE CONCRETE REQUIREMENTS: LOCATION STRENGTH MAX W/C RATIO VAULT WALLS 4000PSI @ 28 DAYS 0.50 VAULT FTGS & GRADE SLAB 4000PSI @ 56 DAYS 0.53 PLANK VOID FILL TO MEET PLANK MFGR'S REQUIREMENTS* PLANK JOINT GROUT TO MEET PLANK MFGR'S REQUIREMENTS* MINIMUM STRENGTH SHALL BE 3000PSI @ 28 DAYS. AIR CONTENT; CONCRETE EXPOSED TO WEATHER SHALL CONTAIN 5% +/-1% ENTRAINED AIR. MIX DESIGN; SHALL BE BASED ON FIELD EXPERIENCE OR TRIAL MIXTURES IN CONFORMANCE WITH THE SPECIFICATIONS, SUBMIT MIX DESIGNS TO THE ENGINEER FOR REVIEW PRIOR TO PLACEMENT, MATERIAL REQUIREMENTS: CEMENT; ASTM C150, ADMIXTURES; ACI 301. AGGREGATES; ASTM C33, WATER; ASTM C94, EXPOSURE CATEGORIES: FREEZING THAWING FO SULFATE SO IN CONTACT w/ WATER W1 CORROSION PROTECTION Cl PLACING REQUIREMENTS: PLACING: PLACE CONCRETE AS NEARLY AS PRACTICABLE TO ITS FINAL POSITION TO AVOID SEGREGATION, DEBRIS; REMOVE ALL DEBRIS FROM FORMS PRIOR TO PLACING CONCRETE, CONSOLIDATION; CONSOLIDATE CONCRETE BY SUITABLE MEANS. THOROUGHLY WORK CONCRETE AROUND EMBEDDED ITEMS AND INTO CORNERS OF FORMS, CURING REQUIREMENTS; CURING; CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A SUITABLE PERIOD OF TIME AFTER PLACEMENT, WEATHER CONDITIONS; ADEQUATE PRECAUTIONS SHALL BE TAKEN DURING HOT AND COLD WEATHER IN ACCORDANCE WITH THE SPECIFICATIONS, LID PLANK PLACEMENT: IN NO CASE SHALL THE LID PLANKS BE PLACED BEFORE THE WALLS HAVE BEEN ALLOWED A MINIMUM OF 3 DAYS OF CURE, WHEN AVERAGE AMBIENT TEMPERATURES ARE LESS THAN 50 DEGREES FAHRENHEIT, THE CONTRACTOR MUST ALLOW A MINIMUM CURE TIME OF 7 DAYS OR PROVIDE AN ADDITIONAL SET OF CYLINDERS TO BE BROKEN AT THE TIME OF LID PLACEMENT DEMONSTRATING A MINIMUM CONCRETE STRENGTH OF 11000 PSI HAS BEEN REACHED, REINFORCING EAR MATERIAL REQUIREMENT: REINFORCING BARS: USE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60, EXCEPT AS NOTED ON THE DRAWINGS, FABRICATION AND PLACING REQUIREMENTS: BENDING: BARS SHALL BE BENT COLD, BARS PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT UNLESS NOTED OR SHOWN OTHERWISE OR AUTHORIZED BY THE ENGINEER, PLACING: REINFORCEMENT SHALL BE SUPPORTED AND TIED TO PREVENT DISPLACEMENT BY CONSTRUCTION LOADS OR BY PLACING OF CONCRETE, MAXIMUM SPACING OF SUPPORTS SHALL BE 3'-611 CONCRETE COVER: MINIMUM CONCRETE COVER FOR REINF, SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE; CONCRETE CAST AGAINST EARTH 311 CONCRETE CAST AGAINST FORMS AND EXPOSED TO EARTH 211 WET SETTINGS: REINFORCEMENT ANCHOR BOLTS, OR ANY EMBEDDED ITEM WITHIN THE CONCRETE, MAY NOT BE SET INTO THE CONCRETE AFTER IT HAS BEEN POURED WITHIN THE FORMS, LAP SPLICES: LAP ALL BARS 2411 MIN UNLESS SHOWN OTHERWISE ON THESE DRAWINGS. DEFERRED SUBMITTALS THE FOLLOWING AREAS OF WORK SHALL BE CONSIDERED AS "DEFERRED SUBMITTALS" AS DEFINED IN THE 2015 IBC PRECAST PRESTRESSED HOLLOW CORE PLANK ALL DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF A CIVIL ENGINEER LICENSED TO PRACTICE IN THE STATE OF WASHINGTON WHO HAS CURRENT DESIGN EXPERIENCE IN THE TYPE OF WORK REVIEWED. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED BY THE ENGINEER OF RECORD, COPIES OF THE APPROVED DEFERRED SUBMITTAL DOCUMENTS SHALL BE MAINTAINED ON SITE BY THE GENERAL CONTRACTOR AND MADE AVAILABLE FOR REVIEW AS REQUESTED, 48110 PRECAST CATCH BASIN BASE SPECIFICATIONS: PRECAST CATCH BASIN BASE SHALL MEET ASTM C478 AND THE APWA/WSDOT STANDARD SPECIFICATION FOR PRECAST CONCRETE MANHOLE SECTIONS, MATERIALS: a, REINFORCING STEEL Fy=60KSI MINIMUM b, CONCRETE f'c=4,000PSI MIN @ 28 DAYS MINIMUM REQUIREMENTS:: CIRCUMFERENTIAL WALL THICKNESS SHALL BE NO LESS THAN 511 THICK AND SHALL HAVEA MINIMUM OF 0.12 SQ. IN/FT OF REINFORCING STEEL HORZ AND VERT PLACED AT THE CENTER OF THE WALL, BASE THICKNESS SHALL BE NO LESS THAN 611 THICK AND SHALL HAVE A MINIMUM OF 0.15 SQ, IN/FT OF REINFORCING STEEL IN EACH ORTHOGONAL DIRECTION PLACED AT THE CENTER OF THE SLAB, MAX DOWEL & VERT REINF TO BE PLACED IN LINE DOWN THE LENGTH OF THE WALL DOWEL w/off FTG TO VERT WALL VERT BAR WALL DOWEL REINF SPLICE TYP DOWEL PLACEMENT S1 SCALE 1114-011 FILL WITH GROUT AS DIRECTED BY PRECAST PLANK MFGR, DO ocSIN N =IC4 cV CONT. BACKER ROD IF REQ'D, TYP PLANK JOINT DETAIL S1 SCALE 11'=11-0'1 V-0" MAX TYP WALL REINF SEE CIVIL DWGS PIPE LOCATION AND INVERT ELEVATION i ADD #5x4811 I ` ' I♦ DIAG EA FACE AS SHOWN ADD ONE VERT FULL HEIGHT REINF BAR EACH SIDE OF BLOCKOUT FOR EA PAIR OF VERT BARS CUT AT THE BLOCKOUT, WALL REINF @ PIPE PENETRATION SCALE N/A INSIDE FACE OF PERIMETER VAULT WALL RISER SEE CIVIL MMfIr GnM Al I SINGLE PIECE OF MOLDED FIBERGLASS GRATING DESIGNATION MS-200, 2" HEIGHT WITH 2" MESH, PROVIDE LEAST POSSIBLE NOTCH AT T-PIPE, GRATING TO BEAR 1-3/811 MIN ONTO SUPPORT ANGLE "YPE 2 CATCH BASE w/ I111-1/4"mx1-3/411LONG HEX HEAD STAINLESS STEEL SIMPSON TITEN CONCRETE SCREWS SPACED AS SHOWN, PROVIDE CRL BITUMINOUS COATING TO ALL ANGLE SURFACES IN CONTACT WITH THE CONCRETE, GRATING @ SUMP VAULT PERIMETER WALL I21 #4 CIRCULAR TIES CAST FTG & GRADE SLAB id AGAINST PRECAST BASE. i it ---------------------�-- ® J FIBERGLASS GRATING COVER & SUPPORT ANGLE VOLCLAY RX-102 WATERSTOP AT THE PERIMETER OF THE SUMP TO SLAB INTERFACE 48110 4811 CATCH - BASIN BASE. SECTION @ SUMP SUMP DETAIL SCALE 3/411=1'-011 #4@1811o/c OR CHAIR TYP GRADE SLAB SECTION SCALE 1-1/21'4-011 ADD ONE VERT. EA SIDE OF BLOCKOUT ADD I21-#5x4'-011@311o/c ��.� - NEAR INSIDE FACE OF .��. WALL ABOVE BLOCKOUT 40 op MAX . �,•'�'•��'' _ 12110 INLET OR OUTLET PIPE ------------- --- z�----------= . -------------- NON SHRINK a .'�• '��. GROUT VOID FILL TOP OF GRADE SLAB - FOOTING 3'-011 I1I#5x21-311C WITHOUT KNEEWALL LID REINF @ MANHOLE #3x811x2411 @ NTS 1211o/c ALONG EDGE OF SUMP IN RADIAL PATTERN 4'-011 WALL REINFORCING ON INSIDE, FACE — � cn #5@12"o/c HORZ & VERT ON BACK FACE OF WALL, DOWELS TO FOOTINGS w ARE NOT REQUIRED AT THESE VERT BARS w Q #5@1211o/c WALL REINF @ CENTER OF WALL 1TYP WALL CORNER REINF, I I I I I I I I I I I I I I I I I I I I I I I I I r-- #5 IN EACH VOID M TOTAL 11_0II� o p cc z a c4 u, m J J W a Z cs H = as c Lu � z z 0 � cn a � 0 c� Z c y W C LL O p G W = Lu ~ a C3 cn � Lri N 0 N N 0 N H N N N , G -rL 0 N 0 U a i 9 m ® v c .0) E W cm � 050 Y 15 0 co Q 0 T j cr Q as -o 01 - W G 20744 �• crvAAL EEO` may` ss�o N a� E�C� rLl Z 0 o 0 �J z J ca M a a 3 ca Z W O Z W Z ~ O W O W V ~ a W W y z � O W c ~ y LL O Z � a SHEET: S10F 2 S-21-004 1 TYP WALL SECTION S2 SCALE 1/211=11-011 J - -1 �p co Q 2 TYP WALL SECTION S2 SCALE 1/211=11-011 4'-0" WIDE PLANK I I I I I I I I I I L I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ❑ I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I Ll I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I IL I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ______;;__ __ _____ __ ;_____;;____ �r- PLAN VIEW 3611 #5x 1411 C 3611 CLOSURE TO WALL #5 x 2411 C LID DOWELS @ 2811o/c, TO CLOSURE DOWELS @ EA PLANK. VAULT WALL ELEVATION VIEW LID d WALL TO CLOSURE DOWELS AT PLANK VOID FILL WALL GENERAL KEYNOTES 101. PLANK TO BEAR 3" MINIMUM ONTO THE TOP OF THE CONCRETE WALL. SEE PLANK MANUFACTURER'S DRAWINGS FOR FINAL BEARING LENGTH, INSTALL BEARING PAD AS DETAILED ON THE PRECAST PLANK PLACEMENT DRAWINGS, 102. 12-1/2" THICK PRECAST HOLLOW CORE PLANK. 103. FINISHED GRADE, ELEVATION VARIES, SEE DESIGN CRITERIA ON SHEET S1 FOR APPROXIMATE SOIL DEPTHS OVER THE VAULT LID IN ADDITION TO THE CIVIL DWGS FOR FINAL GRADE ELEVATIONS, 104. 4110 PERFORATED PVC FOOTING DRAIN MIN IE=78,15, WRAPPED IN 16"x16" MINIMUM DRAIN ROCK BEDDING & FILTER FABRIC, ROUTE DRAIN TO DISCHARGE POINT AS SHOWN ON THE CIVIL DWGS. 105. PREENGINEERED DRAINAGE MATT TO EXTEND OVER THE HEIGHT OF THE WALL AS SHOWN, SEE GEOTECHNICAL REPORT FOR SPECIFICATIONS, 106. 4" PVC RIBBED WATERSTOP w/ CENTER BULB AT ALL PERIMETER WALLS OF THE VAULT, INSTALL AT THE CENTER OF THE WALL, IN ACCORDANCE WITH THE MANUFACTURERS REQUIREMENTS, 107. SEE FOUNDATION PLAN FOR GRADE SLAB REINFORCING, 108. CIP CONCRETE LID SECTION, SEE A/52 FOR REINFORCING, WALL REINFORCING KEYNOTES 201, 811 THICK CONCRETE WALL REINF w/ #5@1211o/c HORZ & #5@1511o/c VERT, PLACE VERT REINF NEAR THE INSIDE FACE OF THE WALL, PROVIDE (2)-#5 CONT HORZ BARS @ THE TOP OF THE WALL, EXTEND BARS 1111 INTO LID CLOSURE POUR WHERE POSSIBLE, 202, #5 FOOTING TO WALL DOWELS TO MATCH WALL VERTICAL REINFORCING SPACING. PROVIDE STD HOOK @ END OF BAR CAST INTO FOOTING, DOWELS SHALL BE EMBEDDED A MINIMUM OF 911 INTO 1211 THICK FTG. & SHALL EXTEND INTO THE WALL 2411 MIN. SEE 6/51 FOR PLACEMENT REQUIREMENTS. 203, (3146 CONT IN CLOSURE POUR, LAP 3611 @ ALL SPLICE LOCATIONS, 204, REINF FTG w/ (21-#5 LONG & #5@1511o/c TRANS BOT, 205, LID & WALL TO CLOSURE POUR REINF @ VOID BLOCK OUT, SEE 4/S2, 206, LID & WALL TO CLOSURE POUR REINF @ END VOID FILL. SEE 3/52. 1211 #4 x11411 SET @ CENTER OF VOID HOLLOW CORE 11-011 1'-0" PLANK lool ---------- ----------- ---�_/ #5 @CENTER OF ---------- ------------------ —i VOID -----------------------t -------CELL BLOCKOUT 0 0 O PLAN VIEW 3611 #5x 151, C — CLOSURE TO WALL DOWELS @ 3011o/c, PERIMETER WALL WALL VERT REINF EXTENDING INTO CLOSURE 1211 #4 x::---] 1411 SET @ ENTER OF VOID ----- -------- ---------- -- --; -- ■ ■ ■ ■ ----,----- -■- --- --- -------------- VAULT WALL ELEVATION VIEW LID & WALL TO CLOSURE DOWELS AT VOID BLOCKOUTS 13 PLANKS @ 4'-0" = 521-011 4 S2 S1 5 ❑ b --- I it I`--- g n n --- A ❑ 10 — 6 ❑ ❑ ------- El ❑ ❑ ------- El 1 S1 ❑ ❑ ------- [I El 8 — 4 ❑ ❑ ------- [I El --- --- El El 1 ------- ❑ ❑ ------- ------------ ❑ ❑ ❑ ❑ ❑ ❑ ITOV=84,65 TYP THROUGH OUT VAULT, g ❑ ❑ ❑ ❑ ❑ ------- ❑ ❑ 6 10 ❑ ❑ ------- ❑ n g 12-1/211 THICK HOLLOW CORE PLANK LID, TOP OF LID EL= 85.69 1 ❑ ❑ ❑ ❑ ❑ ❑ ---- ❑ ❑ 1 co - S2 3'-611 5 5 VAULT LID PLAN 21 81 SCALE 3/1611 = 11-011 0' 4' 41-011 53'-411 521-01' 1 F24x12 S2 8" ——,-------------------------------------------- 1 3 5" THICK CONCRETE _ SLAB ON GRADE IBOV=77,30 � IBOV=77,30 I ---� 7'-0" TYP IBOV=77,65 7 3 TYP @ VAULT Ii PERIM WALL jL----------- --------1--- ------------— — — — — — — — — VAULT FOUND SCALE 3/16" = 11-011 PLANKEYNOTES ATION PLAN F24x12 1 S2 1, 511 THICK CONCRETE SLAB ON GRADE REINF WITH #4@1811o/c EA WAY, PLACE ALL REINF AT MID -DEPTH OF THE SLAB, CAST GRADE SLAB IN A SINGLE POUR, SEE 2/S1 FOR REINF PLACEMENT. 2, C,I,P, CONCRETE WALLS AT THE PERIMETER & INTERIOR OF THE VAULT. SEE WALL SECTIONS FOR THICKNESS & REINFORCING UNO, SEE 5/S1 FOR WALL CORNER REINF, 3, THICKENED SLAB FTGS TO BE CAST WITH THE GRADE SLAB, SEE WALL SECTIONS FOR SIZE & REINF. 4, 12-1/2" THICK PRECAST HOLLOW CORE PLANK, SEE S1 FOR DESIGN CRITERIA, 5, PIPE INLET OR OUTLET TO VAULT. SEE CIVIL DWGS FOR PIPE DIAMETER, LOCATION & INVERT ELEVATION, SEE 3/S1 FOR WALL REINF @ PENETRATION, ADDITIONAL REINF IS NOT REQUIRED FOR PIPES LESS THAN 8`0 PROVIDED THEY ARE PLACED BETWEEN THE TYPICAL WALL REINFORCING, 6, 6110 VENT PIPE THROUGH HOLLOW CORE PLANK VOID SET AT THE CENTER OF THE VOID, SEE PLANK MANUFACTURE LID PLACEMENT DWGS FOR ADDITIONAL INFORMATION, 7, 48'10 CATCH BASIN BASE TO ACT AS SUMP. SEE 7/S1 FOR DETAILS 8, POUR SLOTS IN TOP OF PLANK, MANUFACTURER TO PROVIDE A MINIMUM OF 2 SLOTS @ EACH END OF EACH PLANK AS SHOWN, PLANK MANUFACTURER MAY REQUIRE GROUTING OF ADDITIONAL CELLS BEYOND THE MINIMUM, THE GENERAL CONTRACTOR SHALL INCLUDE GROUTING OF THESE ADDITIONAL CELLS IN HIS BID. SEE WALL SECTIONS FOR TYP WALL AND LID TO CLOSURE REINF AT THE POUR SLOTS, 9, PROVIDE BLOCKOUTS IN THE EDGE CELL OF THE PLANK PARALLEL TO THE VAULT WALL. LOCATE BLOCKOUTS APPROXIMATELY AS SHOWN ON THIS PLAN, SEE 4/S2 FOR TYP REINF @ BLOCKOUT, 10. 24" DIAM, OPENING THRU LID TO ACCEPT RISERS, LADDER, RING AND LOCKING MANHOLE COVER PER CIVIL DRAWINGS, SEE 4/S1 FOR LID REINF AT MANHOLE, 21 8' O1 41 LEGEND IBOV BOTTOM OF VAULT ITOV INSIDE TOP OF VAULT LID ( TOP OF CONC WALL 1 CIP CONCRETE WALL ------ ------ CONCRETE SPREAD FOOTING DIRECTION OF DOWNWARD SLOPE F24x12 2411 WIDE x 1211 THICK FTG, SEE 1 & 2/S2 CONSTRUCTION LOADS THE VAULT LID HAS BEEN DESIGNED TO CARRY THE "DESIGN LOADS" ONLY AFTER VAULT CONSTRUCTION IS COMPLETE, ALL DESIGN CONCRETE AND GROUT STRENGTHS HAVE BEEN ACHIEVED, AND ALL COVER HAS BEEN PLACED OVER THE VAULT WITHIN THE LIMITS SPECIFIED ON THIS DRAWING, "BOBCAT" OR OTHER LIGHT EQUIPMENT SHALL BE USED FOR PLACEMENT OF MATERIALS OVER THE VAULT LID. ALTERNATIVELY, ALLOWABLE UNIFORM LOADS ON THE BARE SLAB CAN BE OBTAINED FROM THE PLANK MFGR, DIMENSIONS & ELEVATIONS THE CONTRACTOR AND HIS SUBCONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL DIMENSIONS AND ELEVATIONS SHOWN ON THESE DRAWINGS WITH THE CURRENT PERMITTED SET OF CIVIL DRAWINGS, AND SHALL NOTIFY BOTH THE CIVIL & STRUCTURAL ENGINEERS IN WRITING OF ALL DISCREPANCIES BETWEEN THE CIVIL DWGS AND THESE DWGS PRIOR TO CONSTRUCTION, O H z Q W J J W a Z cs H arc N c Lu � z z G ca z a c� � o c� z c y W C Li O G W = W I— a c a N 0 N N 0 N H � 0 N N cc N , 0 0 0 a i C. •m E w A mS i oho Y z ow=� 9 W� 3 c`. •� Lyy rV7 L N Q w V r 11, EL J. K M G 20744 L ss"OM Z zo 0 � z ZD a m a 3 Z W O Z W Z ~ O W O W V ~ a 300 W Lu 2 y z oc o 0 W � U. O� Z a Z J cl) O u.l C] 0 � � Z LLL O 1- W 0 CO2 J J J J 7 MCC SHEET: SCALE 3/41611-011 SCALE 3/4"=1'-0"