Loading...
FIR2023-0102+Fire_Sprinkler_Equipment_Specification_Sheets+10.11.2023_8.20.26_AM+3833858Company name: A-PEX Design Services, Inc. Created by: Noah Eakman G R U N T FO S N Phone: 425-493-9680 Email: sales@a-pexdesignservices.com Position Count Description 1 CMBE 5-62 1-U-C-E-D-F 14 Product No.: 98548116 The Grundfos CME Booster is a compact booster system for water supply in domestic applications. The integrated speed controller enables the CME Booster to keep constant pressure in the pipe system. A pressure sensor monitoring changes in the water consumption will signal to the speed controller to change the motor speed to adapt performance to the new state. The CME Booster is very easy to install. When the pipework has been installed, it is all a matter of plugging the unit into a socket, and the system is operational. The CME Booster consists of: • CME pump with integrated frequency converter • 5-way valve • expansion tank • pressure gauge • manometer Features • Constant pressure, integrated speed control • compact • robust, stainless steel • easy installation • dry run protection Thermal protection CME Booster pumps require no external motor protection. The MGE motor incorporates thermal protection against slow overloading and blocking (IEC 34.11: TP 211). Liquid: Pumped liquid: Water Liquid temperature range: 32 .. 140 °F Liquid temperature during operation: 68 °F Density: 62.29 Ib/ft3 Technical: Actual calculated flow: 26 US gpm Resulting head of the pump: 69.48 psi Primary shaft seal: AQQE Approvals and markings: CE,CULUS Curve tolerance: IS09906:2012 3B Start pressure: Integrated Frequency converter Materials: Printed from Grundfos Product Center [2018.05.020] 1 /4 Company name: A-PEX Design Services, Inc. Created by: Noah Eakman G R U N T FO S N Phone: 425-493-9680 Email: sales@a-pexdesignservices.com Position Count Description Pump housing: Stainless steel DIN W.-Nr. 1.4301 AISI 304 Impeller: Stainless steel DIN W.-Nr. 1.4301 AISI 304 Rubber: EPDM Installation: Maximum ambient temperature: 122 °F Flange standard: INTERNAL NPT THREAD Pump inlet: NPT 1 1/4 Pump outlet: NPT 1 Electrical data: Rated power - P2: 2 HP Main frequency: 50 / 60 Hz Rated voltage: 1 x 200-240 V Maximum current consumption: 9.10-7.60 A Rated speed: 360-4000 rpm Enclosure class (IEC 34-5): IP55 Insulation class (IEC 85): F Type of cable plug: NONE Mains cable: NO CABLE m Tank: Tank volume: 21 Others: Net weight: 42.1 lb Gross weight: 63.6 lb Country of origin: us Custom tariff no.: 8413.70.2040 Printed from Grundfos Product Center [2018.05.020] 2/4 Company name: A-PEX Design Services, Inc. Created by: Noah Eakman G R N T FO S N Phone: 425-493-9680 U Email: sales@a-pexdesignservices.com 98548116 CMBE 5-62 1-U-C-E-D-F H CMBE 5-62, 1*230 V [psi] Q = 26 US gpm H = 69.48 psi n = 95 % / 3660 rpm Pumped liquid = Water Liquid temperature during operation = 68 T 100 Density = 62.29 Ib/ft3 00 24 28 32 36 90 95 % 40 44 80 70 46 60 44 50 40 30 40 20 10 _ Eff pump = 52.6 % 0 Eff pump + motor + freq. conv = 46.1 % 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Q [US gpm] P NPSH [HP] [psi] 2.5 25 1 m for+fr q.con Ferte ) 2.0 20 1.5 15 1.0 10 0.5 5 P1 (motor+freq.converter) = 1.708 kW P2 = 2.01 HP 0.0 NPSH = 8.72 psi 0 Printed from Grundfos Product Center [2018.05.020] 3/4 Company name: A-PEX Design Services, Inc. Created by: Noah Eakman G R U N T FO S N Phone: 425-493-9680 Email: sales@a-pexdesignservices.com Description Value General information: Product name: CMBE 5-62 I-U-C-E-D-F Product No.: 98548116 EAN: 5711496977534 Technical: Actual calculated flow: 26 US gpm Resulting head of the pump: 69.48 psi Impellers: 4 Primary shaft seal: AQQE Approvals and markings: CE,CULUS Curve tolerance: IS09906:2012 3B Model: A Start pressure: Integrated Frequency converter Materials: Pump housing: Stainless steel DIN W.-Nr. 1.4301 AISI 304 Impeller: Stainless steel DIN W.-Nr. 1.4301 AISI 304 Rubber: EPDM Installation: Maximum ambient temperature: 122 °F Flange standard: INTERNAL NPT THREAD Pump inlet: NPT 1 1/4 Pump outlet: NPT 1 Liquid: Pumped liquid: Water Liquid temperature range: 32 .. 140 OF Liquid temperature during operation: 68 OF Density: 62.29 Ib/ft3 Electrical data: Rated power - P2: 2 HP Main frequency: 50 / 60 Hz Rated voltage: 1 x 200-240 V Maximum current consumption: 9.10-7.60 A p max system: 145.04 psi Rated speed: 360-4000 rpm Enclosure class (IEC 34-5): IP55 Insulation class (IEC 85): F Type of cable plug: NONE Mains cable: NO CABLE m Tank: Tank volume: 21 Others: Net weight: 42.1 lb Gross weight: 63.6 lb Config. file no: 98499013 Country of origin: US Custom tariff no.: 8413.70.2040 H [psi] 100 90 80 70 60 50 40 30 20 10 n CMBE 5-62, 1`230 V Q = 26 US gpm H = 69.48 psi n = 95 % / 3660 rpm 100 % Pumped liquid = Water 28 :Liquid temperature during operation = 68 T 95 % Density = 62.29 Ib/ft3 \ 44 40 1 v Eff pump = 52.6 Eff pump + motor + freq. conv = 46.1 l 5 1n 15 A 95 O rt 1S nnmt P NPSH [HP] [psi] 2.5 1 motor+freq.co SS venter) 2.0 P2 20 1.5 — 15 1.0 10 0.5 P1 (motor+freq.converter) = 1.708 kW 5 P2 = 2.01 HP 0.0 NPSH = 8.72 psi 0 0 o a 8.54" Printed from Grundfos Product Center [2018.05.020] 4/4 SENJU V SPRINKLER Model RC-RES K-Factor: 4.9 SIN: SS8464 Residential Lead Free Flat Concealed Sprinkler, Pendent C &US LISTED I NSF/ANSI/CAN 61 & 312 EU c us GENERAL DESCRIPTION The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push -on and/or thread -on, thread -off design of the concealed cover plate assembly allows for easy installation of the cover plate. Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes, hotels and other living quarters. The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. The Model RC-RES has a 4.9 (70.6 LPM/bar'/2) K-factor that meets the required residential flow rates with minimal residual pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. "Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, plumbing fittings and fixtures. 41114 www.senjusprinkler.com Page 1 of 8 Document No.U085168 • 02-08-2021 WARNINGS The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction. In the event of this condition, consult the authorities having jurisdiction for guidance and approval. Failure to do so may impair the integrity of these devices. It is the responsibility of the installing contractor to provide a copy of this document to the owner or their representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any related questions. TECHNICAL DATA • Approvals: 0 cULus Listed • UL-EU Listed (162°F (72°C) only) • NSF/ANSI/CAN 61, NSF/ANSI 372 • Sprinkler Identification Number (SIN): SS8464 • Maximum Working Pressure: 175psi (12.1bar) • Discharge Coefficient (Nominal K-Factor): 0 K = 4.9 GPM/psi1/2 (70.6 LPM/bar1/2) • Temperature Rating: • 162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate • 205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate • Color Code (Sprinkler) • 162°F (72°C): Uncolored • 205°F (96°C): White • Color Code (Cover Plate) • 140°F (60°C): No Mark • 1620F (720C): White -Colored Mark • Vertical Adjustment: 1/2 inch (12.8 mm) • Cover Plate Finishes: 0 Standard Finishes: White, Ivory, Beige, Brown, Black, Nickel, Wood Grain 0 Custom Finishes: Custom color and custom pattern cover plates are available on special order. Contact a Senju Sprinkler representative with any custom orders. Please see chart on Page 8 for more detail. • Physical Characteristics: Ref. Figures 1 and 1.1 2-1/16" (052mm) Lot No. s Year of Manufacture SIN: SS8464 E 1 K-Factor: K4.9 4 Temperature Rating: 162°F/72 °C 5 or 205 Z UL Mark v 6 Control No: 6P37 ALS Mark: NSF 61/372 RES SPKR t) Body (Copper Alloy) �z Deflector (Phosphorus Bronze) 0 Gasket (PTFE) 2-5/8" (068mm) ® Fusible Metal (Solder) or 3-1/4" (083mm) �s Heat Collector (Copper) or 2-5/8" square (o68mm) © Cover Plate Assembly Figure 1: Model RC-RES K = 4.9 Cover Plate (Top View) Marking (Deflector) SIN: SS8464 Color Code K-Factor: 14.9 \ - Temperature Temperature Rating: 162°F/72 °C / [ or 205 °F/96 °C UL Mark Sprinkler (Bottom View) Figure 1.1: Marking (Color Code) 4,16 www.senjusprinkler.com Page 2 of 8 Document No.U085168 • 02-08-2021 OPERATION In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be distributed on the affected fire area. (Ref. Figure 2) Normal Condition Cover Plate Operation Sprinkler Operation Water Discharge Figure 2: Operation Process (For illustrative purposes only) DESIGN CRITERIA The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly implemented for safe and full results. Notes Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic sprinkler system design, installation procedures, and techniques. Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the sprinkler system. Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, should be submitted to your contracted company. Include sketches and technical details, as appropriate. In some instances, the requirements of this document may concern specifications which are more stringent, and which take precedence over those specified in NFPA 13, 13D, 13R, or by the authority having jurisdiction. The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below. Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the cup are open and free from any air flow impediment. The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs or other parts of the dwelling structure. The number of sprinklers within each compartment (as defined by NFPA 13D, 13R, or 13) must be kept as few as possible while observing all guidelines relating to obstructions and spacing. Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern. ofj www.senjusprinkler.com Page 3 of 8 Document No.U085168 • 02-08-2021 Obstruction to Water Distribution Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers. General Service Conditions The Model RC-RES must only be utilized in WET PIPE sprinkler systems. Heat Source Criteria Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-RES, due to the exposure of a heat source other than an actual fire. Precautionary Warnings for Corrosive Environments Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the following: 1. Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non -Fire conditions or Not Operating when exposed to an actual fire. 2. Sprinkler system piping with Copper Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association) — Solder Joint) All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system. Hydraulic Design Criteria The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in Table A as a function of temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sprinkler from each of the total number of "design sprinklers" as specified in NFPA 13D or 13R. For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area. • A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the "design area" comprised of the four most hydraulically demanding sprinklers for the actual coverage area being protected by the four sprinklers. 41, www.senjusprinkler.com Page 4 of 8 Document No.U085168 • 02-08-2021 Table A. NFPA 13D & 13P Wet Pipe Hydraulic Design Criteria for Model SS8464 For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as applicable. Maximum Maximum Ordinary Temperature Intermediate Temperature Coverage Spacing Rating 162°F (72°C) Rating 20TF (96°C) Deflector to Installation Minimum Area(,) Ft. x Ft. Ft. Ceiling Type Spacing Ft. (m) FlowN GPM PressureN Flow(b)GPM PressureN (m x m) (m) (LPM) PSI (bar) (LPM) PSI (bar) 12 x 12 12 13 7.0 13 7.0 Smooth (3.7 x 3.7) (3.7) (49.2) (0.48) (49.2) (0.48) Ceilings 3/8 to 7/8 Inches. 14 x 14 14 13 7.0 13 7.0 (4.3 x 4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Beamed Ceilings per 16 x 16 16 13 7.0 13 7.0 NFPA 13D, Concealed 8 (4.9 x 4.9) (4.9) (49.2) (0.48) (49.2) (0.48) 13R or 13. Installed in (2.4) 18 x 18 18 17 12.0 17 12.0 (5.5 x 5.5) (5.5) (64.4) (0.83) (64.4) (0.83) beam 3/8 to 7/8 inches below bottom 20 x 20 20 21 18.4 21 18.4 (6.1 x 6.1) (6.1) (79.5) (1.27) (79.5) (1.27) of beam. a. For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the Next Higher Coverage Area listed. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. Sprinkler Spacing Criteria The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the coverage area calculated by using the specific hydraulic factors. (Ref. Table A) INSTALLATION The Model RC-RES must be installed in accordance with the following instructions: NOTES Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which show deformation or cracking in either the Sprinkler or the Protective Cap. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to the sprinklers that could cause improper operation or non -operation. The Protective Cap must remain on the sprinkler during installation. After the installation is completed, the Protective Cap must be removed to place the sprinkler in service. Use a torque of 7 to 14 ft•lbs (9.5 to 19.0 N•m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler. Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is prohibited and may cause damage to the sprinkler. In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit. Do not rotate the Cap Removal Tool for RC to the left with force when placing the two hook arms into place. The installed sprinkler may become loosened, which may cause water leakage. Ofi www.senjusprinkler.com Page 5 of 8 Document No.U085168 • 02-08-2021 Installation Steps Step 1: The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 2 inches (50.8mm) as shown in Figure 3. Step 2: With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the Socket NR-H or Ratchet (3/8" drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly with the grooves on the Sprinkler for proper installation (Ref. Figure 4). Step 3: If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Vertical Adjustment" indicator on the Protective Cap to check for proper installation height (Ref. Figure 3). Make a Space Here Ave. 1/4" (6.4mm) Min. 1/8" 3.2mm Vertical Do Not Over -Tighten ��x Mounting Surface Correct Incorrect Figure 3: Installation Groove on the Socket NR-H ■ Ratchet Figure 4: Ratchet & Socket Step 4: Use the Cap Removal Tool for RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening the Cover Plate Assembly once the flange has contact with the ceiling. If the ceiling has been lifted from its normal position in the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6. Hook Up Sprinkler Head LTI mrv, Protective Cap S Cap Removal Tool l Pull down Step 1 Step 2 Step 3 Figure 5: Protective Cap Removal 4 www.senjusprinkler.com Page 6 of 8 Document No.U085168.02-08-2021 r Mounting E Surface E Deflectorjr +� M 2-5/8" (068mm) or 3-1/4" (083mm) or 2-5/8" souare (o68mm) Figure 6: Installation (Cover Plate Assembly) E E E E r a Incorrect Correct Incorrect Figure 7: Installation (Correct and Incorrect) CARE & MAINTENANCE The following instructions must be implemented for the maintenance and service of the Model RC-RES. Notes Wet pipe sprinkler systems must be maintained at a minimum temperature of 40oF / 4°C to prevent freezing and bursting of the pipe and/or sprinklers. Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result. Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of a fire. Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may cause improper operation or non -operation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover plates. Non - factory applied paint may adversely delay or prevent sprinkler operation in case of a fire. Do not pull the Cover Plate. Separation may result. In preparation for maintenance of the fire protection system, permission to close the main control valve must be obtained from the proper authorities, and all affected parties by this action, and must be informed before the maintenance session can commence. Do NOT enclose any sprinklers within drapes, curtains, or valances. Do NOT hang anything from the sprinklers. Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning fluids, or other chemicals. Remove dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle (i.e., dusting) brush attachment. Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire development and spread of these materials can reduce the ability of the sprinkler system to aid in the control of a fire involving such hazards. www.senjusprinkler.com Page 7 of 8 Document No.U085168 • 02-08-2021 Leaking or corroded sprinklers must be replaced. Automatic Sprinklers must be kept in a cool and dry place. Automatic sprinklers must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the sprinklers have been in any way modified, they must be replaced. Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged units because of dropping, hitting, over -tightening, or wrench slippage, must be replaced. The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated under Table A "Hydraulic Design Criteria"). When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verify that the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations. The owner is responsible for the maintenance of the sprinkler system, including inspection and testing of its compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with NFPA 25. LIMITED WARRANTY For details of warranty, refer to Sales Contract. ORDER PROCEDURE When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and Finish). Sprinkler • Model: RC-RES SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 1620F (72°C) or 205°F (96°C) Cover Plate Assembly • 2-5/8 inch (�68mm) or 3-1/4 inch (�83mm) or 2-5/8 inch square (❑68mm), Order separately from Sprinkler Please refer to the chart below for available sizes, temperature, and finishes. White Ivory Beige Standard Brown Finishes Black Nickel Copper Wood Grain Custom I Finishes Custom Custom Color Pattern 2-5/8" Round, 140°F O O - - - - - - O O 3-1/4" Round, 140°F O O O O O O O O O O 2-5/8" Square, 140°F O - - 2-5/8" Round, 162°F O - - 3-1/4" Round, 162°F O O O O O 2-5/8" Square, 162°F O - - - - Tools & Accessories • Socket NR-H for use with a 3/8" drive ratchet (not included) • Socket NR-H Plastic for use with a 1/2" drive ratchet (not included) • Cap Removal Tool for RC • Cover Plate Installation Tool Iwww.senjusprinkler.com Page 8 of 8 Document No.U085168 • 02-08-2021 UponorAquaPEX®White, coils Submittal information Revision M: Sept. 18, 2018 Project information Job name: Location: Part no. ordered: Uponof Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved by: Technical data Material: Crosslinked polyethylene PEX-a Engel Method; PEX 5106 Standard grade hydrostatic ratings (PPI): 200°F (93°C) at 80 psi (551 kPa) 180°F (82°C) at 100 psi (689 kPa) 73.4°F (23°C) at 160 psi (1,103 kPa) '/2", %", 1", 1'/4", 1'/2" and 2" UponorAquaPEX® White only: --- 120°F (49°C) at 130 psi (896 kPa) Linear expansion rate: 1.1'/10°F/100' (27.94mm/5.56°C/30.48m) Product information and application use Uponor AquaPEX White is used for hot and cold domestic potable water distribution and residential fire safety as well _ as radiant heating/cooling and hydronic piping systems containing no ferrous corrodible components or where ferrous components are isolated from the piping. ✓ Description Part number I.D. O.D. Weight '/4' Uponor AquaPEX White, 100-ft. coil F1040250 0.241" 0.375" 4.0 lbs. Uponor AquaPEX White, 400-ft. coil F1090375 0.350" 0.500" 20.0 lbs. Uponor AquaPEX White, 1,000-ft. coil F1120375 0.350" 0.500" 44.0 lbs. ''/2" Uponor AquaPEX White, 100-ft. coil F1040500 0.475" 0.625" 6.0 lbs. %" Uponor AquaPEX White, 300-ft. coil F1060500 0.475" 0.625" 18.0 lbs. ''/z" Uponor AquaPEX White, 500-ft. coil F1100500 0.475" 0.625" 27.6 lbs. ''/z" Uponor AquaPEX White, 1,000-ft. coil F1120500 0.475" 0.625" 54.0 lbs. Uponor AquaPEX White, 300-ft. coil F1060625 0.574" 0.750" 28.0 lbs. Uponor AquaPEX White, 1000-ft. coil F1120625 0.574" 0.750" 86.0 lbs. Uponor AquaPEX White, 100-ft. coil F1040750 0.671" 0.875" 10.0 lbs. Y44" Uponor AquaPEX White, 300-ft. coil F1060750 0.671" 0.875" 34.0 lbs. %" Uponor AquaPEX White, 500-ft. coil F1100750 0.671" 0.875" 54.0 lbs. 1" Uponor AquaPEX White, 100-ft. coil F1041000 0.862" 1.125" 20.0 lbs. 1" Uponor AquaPEX White, 300-ft. coil F1061000 0.862" 1.125" 56.0 lbs. 1" Uponor AquaPEX White, 500-ft. coil F1101000 0.862" 1.125" 93.0 lbs. 1'/4' Uponor AquaPEX White, 100-ft. coil F1061250 1.054" 1.375" 34.0 lbs. 1'/4" Uponor AquaPEX White, 300-ft. coil F1021250 1.054" 1.375" 106.0 lbs. 1'/z" Uponor AquaPEX White, 100-ft. coil F1061500 1.244" 1.625" 44.0 lbs. 1'/z" Uponor AquaPEX White, 300-ft. coil F1021500 1.244" 1.625" 133.0 lbs. 2" Uponor AquaPEX White, 100-ft. coil F1062000 1.629" 2.125" 68.2 lbs. 2" Uponor AquaPEX White, 200-ft. coil F1052000 1.629" 2.125" 136.4 lbs. 2" Uponor AquaPEX White, 300-fit. coil F1022000 1.629" 2.125" 204.6 lbs. 2'/i' Uponor AquaPEX White, 100-ft. coil F1062500 2.011" 2.625" 88.0 lbs. 2'/i' Uponor AquaPEX White, 300-ft. coil F1022500 2.011" 2.625" 264.0 lbs. 3" Uponor AquaPEX White, 100-ft. coil F1063000 2.400" 3.125" 128.0 lbs. 3" Uponor AquaPEX White, 300-ft. coil F1023000 2.400" 3.125" 384.0 lbs. Installation Use ProPEX® fittings for %" through 3" pipe.' Refer to the ProPEX Connections Instructional Guide, Uponor Piping Pocket Guide, Plumbing Design Assistance Manual (PDAM), Complete Design Assistance Manual (CDAM), Hydronic Piping Design Assistance Manual (HPDAM) or AquaSAFET1A Residential Fire Sprinkler Installation Guide for more information. Listings2 Codes Standards cNSFus-fs3; cNSFus-pw; cQAlus P321; UL; IAPMO; ICC; IPC; IMC; IRC; ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM CSA; PPI TR-4; ICC-ES; BMEC; CCMC UPC; UMC; NSPC; HUD; F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; UFGS; NPC of Canada; ASTM E814/ULC S115; CSA B137.5; CSA B214; NBC of Canada UL 18213; ULC/ORD-C199P3; AWWA C9044 Related applications Contact information PEX-a plumbing systems Uponor, Inc. Uponor Ltd. AquaSAFETM fire safety systems 5925 148"' Street West 6510 Kennedy Road Radiant heating and cooling systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Hydronic piping systems Phone: 800.321.4739 Phone: 888.994.7726 Fax: 952.891.2008 Fax: 800.638.9517 uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor, Inc. ProPEX- is a trademark of Uponor Ltd. 2Visit listing agency's website for complete information. 3For 3/4", 1" and 1'W pipe only. 4For %" to 3" pipe. ProPEX° Ring Submittal information Revision I: Nov. 1, 2018 Project information Job name: Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved by: Technical data Material: Engel -method crosslinked polyethylene (PEX-a) Density: 926 to 940 kg/m3 Degree of crosslinking: 70% to 89% Product information and application use Uponor ProPEX® rings are required to make a proper ProPEX connection.' The ProPEX ring with stop includes a leading edge chamfer and stop edge. ✓ Description Part number ProPEX Ring, %" ProPEX Ring with Stop, '/2" ProPEX Ring with Stop, %" ProPEX Ring with Stop, 3/4" ProPEX Ring with Stop, 1" ProPEX Ring with Stop, 1'/4" ProPEX Ring with Stop, 1'/2" ProPEX Ring with Stop, 2" ProPEX Ring with Stop, 2'/2" ProPEX Ring with Stop, 3" Installation Q4690302 Q4690512 Q4690625 Q4690756 Q4691000 Q4691250 Q4691500 Q4692000 Q4692500 Q4693000 uponof Length I.D. O.D. Weight 0.54" 0.49" 0.74" 0.005lbs. 0.63" 0.63" 0.87" 0.006lbs. 0.79" 0.75" 1.00" 0.008lbs. 0.87" 0.88" 1.13" 0.012lbs. 1.10" 1.13" 1.42" 0.020lbs. 1.35" 1.38" 1.66" 0.030lbs. 1.61" 1.63" 1.91" 0.040 lbs. 1.97" 2.14" 2.61" 0.133lbs. 2.61" 2.66" 3.25" 0.230lbs. 3.12" 3.16" 3.87" 0.400lbs. Square cut the Uponor PEX tubing. Remove excess material. Slide the ProPEX ring over the end of the tubing (maximum 'lid' over -hang for rings without stop). When using the ProPEX ring with stop, slide the ring on the tubing with the chamfered edge first until the end of the tubing contacts the stop edge. Expand the tubing and ring. If using the ProPEX Manual Expander Tool, rotate the tool a quarter turn after each expansion to prevent the formation of grooves. Remove the expansion tool and fully seat the tubing and ring against the shoulder of the fitting. Make ProPEX connections at temperatures above 5°F/-15°C. For more information, refer to the Uponor ProPEX Connections Instructional Guide. Listings' cNSFus-fs3; cNSFus-pw; cNSFus-rfh; cQAlus; UL; CSA; PPI TR-4; ICC-ES; IAPMO; BMEC; CCMC; cQAlus P321 Codes ICC; IPC; IMC; IRC; UPC; UMC; NSPC; HUD; UFGS; NPC of Canada; NBC of Canada Standards ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; ASTM E814/ULC S115; CSA 13137.5; CSA B214; UL 18213; ULC/ORD-C199P3 Related applications Contact information PEX-a plumbing systems Uponor Inc. Uponor Ltd. AquaSAFE fire safety systems 5925 148"' Street West 6510 Kennedy Road Hydronic radiant heating and cooling systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Snow melting systems Phone: 800.321.4739 Phone: 888.994.7726 Turf conditioning systems Fax: 952.891.2008 Fax: 800.638.9517 Permafrost prevention systems uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd. 2Visit listing agency's website for complete information; 3For '/2",'/", 1", 11/", 1'/2" and 2" tubing only ProPEXO Engineered Submittal information Revision H: May 23, 2019 Project information Job name: Polymer (EP) Tee Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved bv: Technical data Material: Engineered polymer (EP) Maximum temperature (no pressure): 320°F (160°C) Maximum working temperature/pressure: 210*F (99*C) at 150 psi (1,034 kPa) Product information and application use ProPEX® engineered polymer (EP) tees make diverting connections for Uponor crosslinked polyethylene (PEX-a)tubing for use in hot and cold domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX® or Wirsbo hePEXTM tubing.' Note: Branch size is listed last in the part descriptions. Uponof Part ✓ Equivalent Equivalent cv cv Description number A B Weight length (ft.) length (ft.) through branch through branch ProPEX EP Tee, ''M." PEX x'/z' PEX x'/" PEX Q4755060 2.50" 1.53" 0.02 lbs. 1.0 6.3 7.7 3.4 ProPEX EP Tee, %" PEX x'/:' PEX x'/:' PEX* Q4757575 3.30" 1.94" 0.05 lbs. 1.5 15.6 15.7 5.4 ProPEX EP Tee, 1" PEX x 1" PEX x 1" PEX* Q4751010 4.10" 2.47" 0.07 lbs. 1.3 12.7 30.5 11.3 ProPEX EP Tee, 1'/4" PEX x 1'/4" PEX x 1'/4" PEX* Q4751313 4.80" 3.22" 0.15 lbs. 3.8 8.6 34.0 23.9 ProPEX EP Tee, 1 Yz' PEX x 1'/." PEX x 1'M." PEX Q4751515 5.80" 3.82" 0.25 lbs. 1.8 10.6 63.7 31.0 ProPEX EP Tee, 2" PEX x 2" PEX x 2" PEX Q4752000 7.45" 4.79" 0.38 lbs. 0.8 15.5 150.7 52.5 ProPEX EP Tee, 21/' PEX x 21/z' PEX x 21/z' PEX Q4752500 10.56" 5.45" 1.14 lbs. 2.7 22.3 197.2 81.5 ProPEX EP Tee, 3" PEX x 3" PEX x 3" PEX Q4753000 12.26" 6.37" 1.86 lbs. 2.8 23.9 286.6 122.8 Installation Use the appropriate ProPEX Ring for PEX-a tubing. Refer to the Uponor Professional Plumbing Installation Guide, AquaSAFET"^ Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional information. Standards ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61 Codes IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC Listings cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code Related applications Contact information PEX-a plumbing systems Uponor, Inc. Uponor Ltd. Hydronic radiant heating and cooling systems 5925 148t' Street West 6510 Kennedy Road Snow and ice melting systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Turf conditioning systems Phone: 800.321.4739 Phone: 888.994.7726 Permafrost prevention systems Fax: 952.891.2008 Fax: 800.638.9517 AquaSAFETm fire safety systems uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd. ProPEX° Engineered Polymer (EP) Reducing Tee (up to 11/2") uponof Submittal information Revision I: Sept. 16, 2019 Project information Job name: Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved by: Technical data Material: Engineered polymer (EP) n� Maximum temperature (no pressure): 320°F (160°C) Max. working temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa) Product information and application use ProPEX® engineered polymer (EP) reducing tees make diverting connections for Uponor PEX-a pipe for use in hot and cold B domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX11 or Wirsbo hePEXTM pipe.' Note: Branch size is listed last in the part descriptions. ✓ Description Part A B Weight Equiv, length (ft.) Equiv. length Cv Cv number through (ft.) branch through branch ProPEX EP Reducing Tee,''/2" PEX x'/i' PEX x %" PEX Q4755575 2.86" 1.76" 0.03 lbs. 1.0 15.6 7.7 5.4 ProPEX EP Reducing Tee, '/<" PEX x'/i' PEX x'/i' PEX Q4757555 3.10" 1.70" 0.04 lbs. 3.5 6.4 4.6 3.4 ProPEX EP Reducing Tee, '/<" PEX x'/z' PEX x'/;' PEX* Q4757557 3.10" 1.94" 0.04 lbs. 2.3 16.1 5.4 5.4 ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x PEX Q4757563 3.30" 1.85" 0.05 lbs. N/A N/A N/A N/A ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x'/z' PEX* Q4757550 3.30" 1.70" 0.04 lbs. 2.0 7.6 14.2 3.1 ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x 1" PEX* Q4757710 3.64" 2.32" 0.08 lbs. 1.5 5.7 15.7 8.7 ProPEX EP Reducing Tee, 1" PEX x'/i' PEX x 1" PEX Q4751501 3.71" 2.43" 0.09 lbs. 1.98 9.7 12.3 5.7 ProPEX EP Reducing Tee, 1" PEX x'/d' PEX x'/ PEX Q4751750 3.65" 1.96" 0.07 lbs. 2.27 6.69 3.1 13.2 ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x'/4" PEX* Q4751775 3.90" 2.24" 0.08 lbs. 2.4 16.7 12.8 5.3 ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x 1" PEX* Q4751751 3.90" 2.47" 0.08 lbs. 2.4 15.1 12.9 10.5 ProPEX EP Reducing Tee, 1" PEX x'/;' PEX x 1%" PEX Q4751753 4.15" 2.95" 0.12 lbs. 2.74 19.48 14.7 12.0 ProPEX EP Reducing Tee, 1" PEX x 1" PEX x'/;' PEX* Q4751150 4.10" 2.00" 0.08 lbs. 1.2 6.5 32.2 3.4 ProPEX EP Reducing Tee, 1" PEX x 1" PEX x %" PEX* Q4751175 4.10" 2.24" 0.09 lbs. 1.7 6.4 27.8 8.2 ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 1 '/;' PEX* Q4751113 4.38" 2.95" 0.13 lbs. 6.52 5.37 15.0 28.0 ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x'/<" PEX* Q4751377 4.11" 2.38" 0.09 lbs. 2.74 7.41 7.3 12.0 ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x 1" PEX* Q4751371 4.37" 2.62" 0.11 lbs. 2.70 7.59 13.9 12.1 ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x 1Y<" PEX* Q4751373 4.61" 2.88" 0.13 lbs. 2.74 11.91 18.8 12.0 ProPEX EP Reducing Tee, 1'/<" PEX x 1" PEX x %" PEX* Q4751317 4.50" 2.73" 0.11 lbs. 3.4 5.2 21.0 9.3 ProPEX EP Reducing Tee, 11/;' PEX x 1" PEX x 1" PEX* Q4751311 4.70" 2.97" 0.12 lbs. 11.0 23.0 11.7 8.4 ProPEX EP Reducing Tee, 11/;' PEX x 11/4" PEX x'/;' PEX* Q4751350 4.40" 2.15" 0.10 lbs. 1.9 3.9 45.2 4.1 ProPEX EP Reducing Tee, 11/4" PEX x 11/4" PEX x %" PEX* Q4751337 4.70" 2.73" 0.13 lbs. 2.3 5.7 43.4 8.9 ProPEX EP Reducing Tee, 11/4" PEX x 11/4" PEX x 1" PEX* Q4751331 5.00" 2.97" 0.14 lbs. 4.2 6.3 33.0 15.8 ProPEX EP Reducing Tee, 1'/z" PEX x'/<" PEX x %" PEX Q4751577 4.37" 2.64" 0.13 lbs. 2.88 7.41 7.3 11.7 ProPEX EP Reducing Tee, 1'/z" PEX x'/<" PEX x 1'/z" PEX Q4751575 4.97" 3.39" 0.19 lbs. 2.74 19.10 22.9 12.0 ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x %" PEX Q4751517 5.25" 3.06" 0.17 lbs. 4.0 5.1 19.5 9.3 ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x 1" PEX Q4751511 5.25" 3.30" 0.18 lbs. 4.3 6.5 18.9 15.6 ProPEX EP Reducing Tee, 11/2" PEX x 1" PEX x 11/2" PEX Q4751505 5.40" 3.45" 0.20 lbs. 4.2 14.9 19.0 26.5 ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x %" PEX Q4751537 5.50" 2.65" 0.18 lbs. 4.2 11.3 33.1 6.3 ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x 1" PEX Q4751531 5.50" 2.85" 0.19 lbs. 3.1 13.1 36.4 11.2 ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x 11/4" PEX Q4751533 5.50" 3.15" 0.21 lbs. 2.0 17.7 45.4 17.0 ProPEX EP Reducing Tee, 1'/z" PEX x 1'/2" PEX x'/i' PEX Q4751550 4.95" 2.30" 0.14 lbs. 2.4 6.3 60.5 3.4 ProPEX EP Reducing Tee, 1'/z" PEX x 1'/2" PEX x %" PEX Q4751557 5.30" 3.06" 0.20 lbs. 2.9 5.4 56.0 9.0 ProPEX EP Reducing Tee, 1'/2" PEX x 1'/2" PEX x 1" PEX Q4751551 5.75" 3.30" 0.21 lbs. 3.1 6.9 53.8 15.3 ProPEX EP Reducing Tee, 1'/2" PEX x 1'/2" PEX x 11/4" PEX Q4751553 5.80" 3.56" 0.22 lbs. 3.2 4.1 54.3 33.7 Installation Use the appropriate ProPEX ring for PEX-a pipe. Refer to the Uponor Piping Systems Installation Guide, the AquaSAFETm Residential Fire Sprinkler Installation Guide or the Uponor Radiant Installation Handbook for additional information. Standards Codes Listings ASTM E84; ASTM E119; ASTM E814; IBC; IMC; IPC; IRC; NPC of Canada; cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ASTM F877; ASTM F1960; NSPC; UMC; UPC ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code CAN/CSA B137.5; NSF 14; NSF 61 Related applications Contact information PEX-a plumbing systems Uponor Inc. Uponor Ltd. Hydronic radiant heating and cooling systems 5925 1481h Street West 6510 Kennedy Road Snow and ice melting systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Turf conditioning systems Phone: 800.321.4739 Phone: 888.994.7726 Permafrost prevention systems Fax: 952.891.2008 Fax: 800.638.9517 AquaSAFETM fire safety systems uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor Inc. ProPEX" is a trademark of Uponor Ltd. ProPEX® Engineered Polymer (EP) Elbow Submittal information Revision J: June 21, 2019 Project information Job name: Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: ADDroved bv: Technical data Material: Engineered polymer (EP) Maximum temperature (no pressure): 320°F (160°C) Maximum working temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa) Product information and application use ProPEX® engineered polymer (EP) elbows make 90-degree connections for Uponor crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic potable water systems, residential fire safety and hydronic radiant heating and cooling systems. Each end of the elbow is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX® or Wirsbo hePEXTm tubing.' Uponof ✓ Description Part number A B Weight Equivalent Cv length (ft.) ProPEX EP Elbow, '/z" PEX x'/z" PEX Q4760500 1.30" 1.30" 0.02 lbs. 10.4 2.6 ProPEX EP Elbow, 3/4° PEX x 3/4" PEX* Q4760750 1.60" 1.60" 0.03 lbs. 10.8 6.7 ProPEX EP Elbow, 1" PEX x 1" PEX* Q4761000 2.10" 2.10" 0.07 lbs. 11.5 11.9 ProPEX EP Elbow, 1'/4" PEX x 1'/4" PEX* Q4761250 2.45" 2.45" 0.11 lbs. 10.0 22.2 ProPEX EP Elbow, 1'/z" PEX x 1'/z" PEX Q4761500 2.77" 2.77" 0.18 lbs. 11.5 29.7 ProPEX EP Elbow, 2" PEX x 2" PEX Q4762000 3.76" 3.76" 0.30 lbs. 17.1 50.2 ProPEX EP Elbow, 2'/z" PEX x 2'/z" PEX Q4762500 4.93" 4.93" 0.85 lbs. 20.0 86.0 ProPEX EP Elbow, 3" PEX x 3" PEX Q4763000 5.88" 5.88" 1.44 lbs. 23.2 125.0 ProPEX EP 45 Elbow, 1'/2' PEX x 1'/2" PEX Q4761515 2.32" 2.32" 0.13 lbs. 9.3 33.1 ProPEX EP 45 Elbow, 2" PEX x 2" PEX Q4762020 2.91" 2.91" 0.32 lbs. 8.8 68.9 ProPEX EP 45 Elbow, 2'/2' PEX x 2'/2" PEX Q4762525 3.83" 3.83" 0.65 lbs. 7.0 136.8 ProPEX EP 45 Elbow, 3" PEX x 3" PEX Q4763030 4.48" 4.48" 1.07 lbs. 8.3 195.5 Installation Use the appropriate ProPEX ring for PEX-a tubing. Refer to the Uponor Piping Pocket Guide, AquaSAFETm Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional information. Standards ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61 Codes IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC Listings cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code Related applications Contact information PEX-a plumbing systems Uponor Inc. Uponor Ltd. Hydronic radiant heating and cooling systems 5925 148t' Street West 6510 Kennedy Road Snow and ice melting systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Turf conditioning systems Phone: 800.321.4739 Phone: 888.994.7726 Permafrost prevention systems Fax: 952.891.2008 Fax: 800.638.9517 AquaSAFE fire safety systems uponorpro.com uponorpro.com 1 ProPEX® is a registered trademark of Uponor, Inc. ProPEX- is a trademark of Uponor Ltd. Bulletin 905 ® Fire Sprinkler Adapters Residential Fire Safety System inblim Multipurpose Piping System 3/4" (19 mm),1" (25.4 mm) Features: 1. 300 series stainless construction 1. Integral Mounting Bracket 2. Connection Type — PEX (cross -linked Polyethylene) per ASTM F1960 3. 112" Sprinkler Connection 4. Rating — 130 psig 5. Provides sufficient stand-off from structural members for in- stallation of recessed and concealed sprinklers. Approvals and Listings 1. Underwriters Laboratories Inc. UL Listed in accordance with UL 1821 and Certified for Canada (cULus) in accordance with ULC/ORD C199P 2. NSF International Standard 61 3. Uniform Plumbing Code (UPC) — IAPMO 4. International Plumbing Code (IPC) Product Description The Reliable Fire Sprinkler Adapters are specifically designed to be hanger attachments by integrating a mounting bracket as a part of the fitting. There are three (3) basic fitting configurations (Straight, Tee, and Elbow) that allow to facilitate its use in "NFPA 13D Multipurpose Piping Systems (Figure A.6.3 b)". The fitting can be mounted directly to a stud or beam without the use of a separate hanger. W CD D 0 0 Cn Installation 1. Install the fitting by attaching the mounting bracket, using two (2) #10 x 1-1/4" coarse threaded screws (or similar fasteners) and washer, to the structure 2. Connect one end of the PEX Tubing (using the proper in- stallation tool and procedure) to the appropriate "barbed" end desired. 3. Install the properly design sprinkler head into the threaded end using potable water - safe thread sealants only (Teflon tape is recommended). Technical Data: Allowance for friction loss in fittings Ordering Information: Note: This table shows the allowance for friction loss for fitting, expressed as equivalent length of pipe. T ... T ...-- Filing Type Slim Equhrdllerd _ Straight Adat�tc �4 x 12' FN r ... ..... _ 1 Straight Actapter 1"x 12 FNPT i 1 _ .......... Tee ............ 3/4' x 3/4' x 1/2' FNPT ! 2 Tee 1" x 1" x 1/2' FNPT 2 RH Elbow (90°) 3/4' x 12' FNPT 6 RH Elbow (90') 1 ° x 12' FNmr j 7 LH Elbow (90') �14 x 12' FNPT 6. LH Elbow (90°) 1" x 1/2' FNPT i7 Part No. 6888100134 Type SUaicj rt SMjl�t Tee_____.. Tee Sim 3/4' PEXx 1/2' FNPT 68BB100100 68000234 6BMlCO20D VPDCx12TNPT _' PEX x �4 PD( x 12' FNPr 1" PEX x 1" PEX x 12' FNPT 68000334 BbDN (RH) �W PEX x 12' FNPT 68881003DD RboN (RH) 1" PEX x 12' FNPT 6900D434 Bbm (LJ-i) �W PD( x 12' W 6888100400 EbaN (LH) 1" PE)(x 12' FNm The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York , 10523 Dimension Data: --- .. F i .a. �. �• (( •p• ._..... ...... : •A• Elbow Adapter (Only Right Hand Shown, Left Hand is similar) Connection Sae i A B C D E F 3/4" (19 mm) 2.25 (57) 1.88 (48) 1.87 (48) 1.41(36) .19 (4.8) .95(24) j 1" (25.4 mm) 2,63(67) 1.88 (48) 2.17(54) 1.54 (39) .19 (4.8) .._._.._ 1.18(6. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and propertyfor over 80 years, and are installed and serviced byte most highly qualified and reputa- be sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. Recycled (800) 431-1588 Sales Offices Paper (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address E.G. Printed in U.S.A. 02/08 P/N 9999970361