Trane Precedent Gas/Electric Packaged Rooftop
Application Unit Size Supply FOR (in.) Weight
External
DX cooling, 3 Ton ( 036) Airflow Static Height Width Length Minimum Maximum
gas heat Pressure
1200 cfm 0.500 in H2O 3.41 ft 3.69 ft 5.82 ft 472.0 lb 747.0 lb
Voltage/phase/hertz 208-230/6013
MCA 19.90 A
MOP 30.00 A
Unit Controls Electro mechanical controls 3ph
•• • •
Entering Dry Bulb 80.00 F
Entering Wet Bulb 67.00 F
Ambient Temp 95.00 F
Leaving Coil Dry Bulb 57.21 F
Leaving Coil Wet Bulb 57.21 F
Leaving Unit Dry Bulb 58.99 F
Leaving Unit Wet Bulb 57.90 F
Refrigeration System Options
Leaving Dew Point 57.21 F
Heating Stages 2
Output Heating Capacity 81.00 MBh
Output Heating Capacity with Fan 82.25 MBh
Heating EAT 70.00 F
Heating LAT 132.70 F
Heating Temp Rise 62.70 F
Fan Section
Indoor Fan Data
Type FC Centrifugal
Drive Type Direct
Indoor Fan Performance
Airflow 1200 cfm
Design ESP 0.500 in H2O
Indoor Motor Operating Power 0.40 bhp
Indoor Motor Power 0.30 kW
Indoor RPM 918 rpm
Indoor Fan FLA 0.00 A
Compressor Sect
Power 0.00 kW
Circuit 1 RLA 0.00 A
Capacity
Gross Total 36.97 MBh
Gross Sensible 29.79 MBh
Net Total 35.94 MBh
Net Sensible 28.76 MBh
Fan Motor Heat 1.03 MBh
Refrig Charge -circuit 1 3.2 lb
aa:alaa:��faa:�
12.0 EER
Outdoor Fan Data
Type Propeller
Fan Quantity 1
Drive Type Direct
Outdoor Fan Performance
Condenser Fan FLA 0.00 A
Exhaust Fan Data
Type FC Centrifugal
Drive Type Direct
Exhaust Fan Performance
Exhaust Fan FLA 0.00 A
Page 1 of 9
TRINE®
Job Name:GENSCQ STOCK
STOCK
UnipTag YSC036G3EMB00
Quantity: 1
EVAPORATOR
SECTION ACCESS PANEL
CONDENSATE DRAIN (ALT)
3/4'-14 NPT DIA. HOLE —
4 1 /4"
THROUGH THE BASE
CONDENSATE —
1/2'
"!
i
F - - - -
I I
I I
I
I I RETURN I --
I 18' 1
SUPPLY I I I
=S
L
1s 1r2 91ra" 14' �3 P
PLAN VIEW UNIT
DIMENSION DRAWING
RETURN
SUPPLY 143/4'
PANEL
CONDENSER FAN
SER COIL
UNIT CONTROL WIRE 7/8' DIA. HOLE
SERVICE GAUGE PORTACCESS 1 3/8"DIA.HOLE
UNIT POWER WIRE
CONTROL AND COMPRESSORACCESS PANEL
—1/2" NPTGAS CONNECTION
NOTES:
1. TH RU -THE -BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2.VERIFYWEIGHT, CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
_f 40
23 1/4'
00 00 J3/4"
17 1 /4" 8 7/8' Ll31 /4" 3 3116"
69 7/8"
CONDENSATE
PACKAGED GAS / ELECTRICAL
DIMENSION DRAWING
HORIZONTAL
A1R FLOW
2018-04-25 21:14:40Z Page 2 of 9
Job Name:GENSCQ STOCK
TE® UnipTag: YSared By: GENSCO STOCK
CO 6G3EMBOO
Quantity: 1
3/4_-14 NPT
DRAIN CONNECTION
SUPPLY
RETURN
23 9±15 `4`114
r
ISOMETRIC -PACKAGED COOLING
2018-04-25 21:14:40Z Page 3 of 9
Job Name:GENSCQ STOCK
TRINE® UnipTag YSSTOCK
C036G3EMB00
Quantity: 1
ELECTRICAL / GENERAL DATA
x4x6)
'GENERAL (2
HEATING PERFORMANCE
Model:
YSC036G
Oversized Motor
HEATING - GENERAL DATA
U nit Operating Voltage:
187-253
MCA:
N/A
U nit P rim ary Voltage:
208
MFS: NIA
Heating Model:
Medium
U nit Secondary Volta ge
230
MCB:
N/A
In
Heating Input (BTU):
100,000/70,000
Unit H ertz:
60
Heating Output (BTU):
81,000/56,700
U nit P ha se:
3
N o. Burners:
3
No. Stages
2
E E R/S E E R
12.0/14.0
Standard 1.1 otor
Field Installed Oversized Motor
Gas Inlet Pressure
MCA
19.9
MCA N/A
N atu ra I G as (M in/M ix):
4.5/14.0
MFS:
30.0
MFS: NIA
LP(Min/Max)
11.0/14.0
MCB:
30.0
MCB: N/A
Gas Pipe Connection Size:
1/2'
INDOOR MOTOR
Standard 1,1otor
Oversized Motor
Field Installed Oversized Motor
Number.
1
Number: N/A
Number:
N/A
Horsepower.
0.75
Horsepower. N/A
Horsepower:
N/A
MotorSpeed(RPM):
_
Motor Speed (RPM X N/A
Motor Speed (RPM X
NIA
Phase
1
Phase N/A
Phase
N/A
Full Load Amps:
5.7
Full Load Amps: N/A
Full Load Amps:
N/A
Locked R otorAmps:
_
LockedRotorAmps: N/A
Locked RotorAmps:
NIA
COMPRESSOR
Circuit 1/2
OUTDOOR MOTOR
Number:
1
N um ber: 1
Horsepower:
2.8
H orsepower: 0.25
Phase:
3
LlotorSpeed (RPM): 1100
Rated Load Amps:
12.8
Phase: 3
Locked Rotor Amps:
95.0
Full Load Amps: 1.1
Locked RotorAmps: 3.6
POWER EXHAUST ACCESSORY (3)
FILTERS
REFRIGERANT (2)
(Field Installed Power Exhaust)
Type
Phase:
NIA
Type: Throwaway
Horsepower:
N/A
Furnished: Yes
Factory Charge
Motor Speed (RPM):
N/A
Number 2
Circuit#1 3.2lb
Full Load Amps:
N/A
Recommended 20"x35"YZ
Circuit#2 N/A
Lo cked Rotor Am ps:
N/A
1. M aximum (HACR ) Circuit Breaker sizing is for installations in the Untied States only.
2. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions
3. Value does not include Power Exhaust Accessory.
4. Value includes oversized motor.
S. Value does not include Power Exhaust Accessory.
6. E E R is rated at Ali RI co nditio ns and in a coo rdan ce with D OE test pro cedu res.
2018-04-25 21:14:40Z Page 4 of 9
Job Name:GENSCQ STOCK
TRINE® UnipTag YSSTOCK
CO3 G3EMB00
Quantity: 1
PACKAGED GAS / ELECTRICAL
CORNER WEIGHT
0
R
INSTALLED ACCESSORIES NET WEIGHT DATA
ACCESSORY
WEIGHTS
ECONOMIZER
MOTORIZED OUTSIDE AIR DAMPER
M ANU AL OUTSIDE AIR DAMPER
BAROMETRIC RELIEF
OVERSIZED MOTOR
BELT DRIVE MOTOR
IF
POWER EXHAUST
THROUGHTTHE BASE ELECTRICAUGAS(FIOPS)
UNITMOUNTED CIRCUIT BREAKER (FIOPS)
UNIT MOUNTED DISCONNECT(FIOPS)
POWERED CONVENIENCE OUTLET (FIOPS)
HINGED DOORS (FIOPS)
HAIL GUARD
SMOKE DETECTOR, SUPPLY/RETURN
NOVAR CONTROL
STAINLESS STEEL HEAT EXCHANGER
REHEAT
ROOF CURB
BASIC UNIT WEIGHTS
SHIPPING NET
IF CORNER WEIGHTS
O 193.OIb CO 45.OIb
CENTER OF GRAVITIY
(E)LENGHT (F)WIDTH
577.0lb
472.OIb
178.OIb
DO
SS.OIb
33"
InTF
1. All weights area ppro)dmate.
2. Weights for options that are not list refer to Installation guide.
3. The actual weight are fisted on the unit nameplate.
4. Referto unit nameplate and installation guide for weights before scheduling transportation and installation
ofunit.
5. The weight shown represents the typical unit operating weight forthe configuration selected. Estimated
at+/- 10 % ofthe nameplate weight..
6. Verify weight, connection, and all dimension with installerdocuments before installation.
7. Corner weights are given for information only.
8. N et/Shipping weight of optional accessories should be added to unit weight when ordering factory or field
installed accessories.
PACKAGED GAS/ELECTRICAL
RIGGING AND CENTER OF GRAVITY
2018-04-25 21:14:40Z Page 5 of 9
Job Name:GENSCO STOCK
Prepared By: GENSCO STOCK
Unit Tag:YSC036G3EMB00
Quantity: 1
CLEARANCE 36"
DOWNFLOW CLEARANCE 36"
HORIZONTAL CLEARANCE 18"
ROOF OPENING
UNITOUTLINE—
PACKAGED GAS/ELECTRIC
CLEARA14CE
CLEARANCE48"
CLEARANCE 36"
I
40-
68 3/1G
PACKAGED GAS/ELECTRIC
DO'NNFLO'N TYPICAL ROOF OPENING
CLEARANCE FROM TOP OF UNIT 72'
2018-04-25 21:14:40Z Page 6 of 9
Job Name: GENSCO STOCK
TRINE® UnipTag YSSTOCK
C036G3EMB00
Quantity: 1
General
The units shall be convertible airflow. The operating range shall be between 1150F and 0°F in cooling
as standard from the factory for units with microprocessor controls. Operating range for units with
electromechanical controls shall be between 1150F and 40°F. Cooling performance shall be rated in
accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully
charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation,
and control sequence before leaving the factory. Wiring internal to the unit shall be colored and
numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance
for Central Cooling Air Conditioners.
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall
be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface
shall be tested 672 hours in a salt spray test in compliance with ASTM 13117. Cabinet construction
shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be
removed and reinstalled by removing two fasteners while providing a water and air tight seal. All
exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil -
faced, fire -retardant permanent, odorless glass fiber material. The base of the unit shall be insulated
with 1/8 inch, foil -faced, closed -cell insulation. All insulation edges shall be either captured or sealed.
The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1
1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with
forklift capabilities on three sides of the unit.
Unit Top
The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and
gasket -sealed. The ribbed top adds extra strength and enhances water removal from unit top.
Filters
Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall
also be available.
Compressors
All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps.
Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10
percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors.
Dual compressors are outstanding for humidity control, light load cooling conditions and system back-
up applications. Dual compressors are available on 7'/2-10 ton models and allow for efficient cooling
utilizing 3-stages of compressor operation for all high efficiency models.
Indoor Fan
The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F,
T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward -curved fan wheel along
with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a
variable speed adjustment potentiometer located in the control box.
3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with
adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed,
direct drive motors. All 6 to 8'/2 ton units (standard efficiency) shall have belt drive motors with an
adjustable idler -arm assembly for quick -adjustment to fan belts and motor sheaves. All motors shall be
thermally protected. All 10 tons, 6 ton (074), 7'/2 to 8'/2 (high efficiency) units have variable speed
direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
2018-04-25 21:14:40Z Page 7 of 9
Job Name: GENSCO STOCK
TRINE® UnipTag YSSTOCK
C036G3EMB00
Quantity: 1
Outdoor Fans
The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical
discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal
overload protection.
Evaporator and Condenser Coils
Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be
standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel
condenser coils are standard for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high
efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton
dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube -to -fin
bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can
reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to
better compressor reliability. Compact all -aluminum microchannel coils also help to reduce the unit
weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all
aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition,
flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils
shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser
coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The
condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of
cleaning. A plastic, dual -sloped, removable and reversible condensate drain pan with through -the -base
condensate drain is standard.
Controls
Unit shall be completely factory -wired with necessary controls and contactor pressure lugs or terminal
block for power wiring. Unit shall provide an external location for mounting a fused disconnect device.
A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls
provide for all 24V control functions. The resident control algorithms shall make all heating, cooling,
and/or ventilating decisions in response to electronic signals from sensors measuring indoor and
outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift
from set point, and provides better building comfort. A centralized microprocessor shall provide anti -
short cycle timing and time delay between compressors to provide a higher level of machine
protection. 24-volt electromechanical control circuit shall include control transformer and contactor
High Pressure Control
All units include High Pressure Cutout as standard.
Phase monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by
phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that
provides an ON or FAULT indicator. There are no field adjustments. The module will automatically
reset from a fault condition.
Refrigerant Circuits
Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and
refrigerant line filter driers are factory -installed as standard. An area shall be provided for replacement
suction line driers.
2018-04-25 21:14:40Z Page 8 of 9
Job Name:GENSCQ STOCK
TE® UnipTag: YSared By: GENSCO STOCK
CO 6G3EMBOO
Quantity: 1
Gas Heating Section
The heating section shall have a progressive tubular heat exchanger design using stainless steel
burners
and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the
combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system.
On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before
ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until
manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or
propane (field -installed kit) and also comply with the California requirement for low NOx emissions
(Gas/Electric Only).