Loading...
REVIEWED RE Copperstone 2-Hour Floor Ceiling AssemblyFrom: Jesse Binford <jbinford@bcie.net> Sent: Wednesday, May 8, 2024 10:46 AM To: Carter, Eric Cc: Nils Moerkeseth Subject: RE: Copperstone 2-Hour Floor/Ceiling Assembly Attachments: 05-08-24 Intumescent Paint ESL-1191.pdf Eric, See the attached PDF of the ICC approved ESL that indicates 43mils dry film thickness yields a 2-hour rating for an exterior wall that only has 1-hour protection from dryrwall. The ESL shows a 2-hour rated exterior wall assembly, but as we are looking for an applied thickness to achieve the needed 1-hour it is sufficient. There are no ESLs for a floor/ceiling assembly but that's likely due to the fact they are testing the fire -resistance of the paint and not the assembly. At least (3) coats will be required per the manufacturer's specification previously provided as they indicate 13.5 to 16.2 mils per coat dry. Thanks, Jesse Binford, PE, Principal BCINVESTIGATIVE ENGINEERS, LLC RESPONSIVE • ACCURATE • THOROUGH 3605 C Street NE, Auburn, WA. 98002 253-670-9513 (c) 253-833-5557 (o) From: Carter, Eric <Eric.Carter@edmondswa.gov> Sent: Tuesday, May 7, 2024 12:54 PM To: Jesse Binford <jbinford@bcie.net> Subject: RE: Copperstone 2-Hour Floor/Ceiling Assembly Hi Jesse, I am reviewing the submittal and had a question and figured it was best to go straight to the source, I hope you don't mind. The paint specs provide a mil thickness per coat, but I don't how many mils or coats it will take to provide the one hour necessary. Any info you can provide? Did I miss something? To help expedite their permit I can add your response to the permit. Thanks for your help. tip`` T'Ti.,T Eric Carter I Senior Building Inspector Building 1 121 5' AVE N. I Edmonds WA 98020 425.771.0220 (office) Eric.Carter@edmondswa.gov NOTICE: All emails, and attachments, sent to and from the City of Edmonds are public records and may be subject to disclosure pursuant to the Public Records Act (RCW 42.56) From: Jesse Binford <ibinford@bcie.net> Sent: Wednesday, May 1, 2024 7:54 AM To: Nils Moerkeseth <nilsmoerkeseth@yahoo.com> Cc: Carter, Eric <Eric.Carter@edmondswa.gov> Subject: Copperstone 2-Hour Floor/Ceiling Assembly Nils/Eric, Attached is the specification PDF from the intumescent paint that you can get at Home Depot. There are other paints available so if they meet ASTM 2768/ASTM E-84 and ASTM E-119, UL 263, or NFPA 251 they are acceptable. The rating is 1-hour for floor/ceiling assemblies, which when applied over the (3) layers of 5/8" type 'X' (base direct and then (2) over REC) which provides at leat a 1 hour rating, the total assembly provides a minimum 2-hour fire -rated assembly. Thanks, Jesse Binford, PE, Principal BCINVESTIGATIVE ENGINEERS, LLC RESPONSIVE • ACCURATE • THOROUGH 3605 C Street NE, Auburn, WA. 98002 253-670-9513 (c) 253-833-5557 (o)