REVIEWED BLD2024-0736+Manufacturer_Specifications_and_Installation_Instructions+6.3.2024_8.28.21_AM+4295408TRAIVE® Job Name: STOCK RECEIVED
Prepared By:: GENS GENSCO STOCK
Unit Tag: YSC036G3EMB00 Quantity: 1 B L D 2024-0736
Jun 03 2024
CITY OF EDMONDS
Trane Precedent Gas/Electric Packaged Rooftop DEVELD PARTMENRVICES
Application Unit Size pp y an xternai Dimensions m. Weigh EER IEER/SEER
= External �
DX cooling, 3 Ton 036 Airflow Static Height Width Length Minimum Maximum
gas heat ) Pressure 12.0 EER
1200 cfm 0.500 in H2O 3.41 ft 3.69 ft 5.82 ft 472.0 lb 747.0 lb
Unit Electrical ;0
\/nl4�nn/nh�cc/hnh� �nu_�zn/an/�
Entering Dry Bulb 80.00 F
Capacity
Entering Wet Bulb 67.00 F
Gross Total 36.97 MBh
Ambient Temp 95.00 F
Gross Sensible 29.79 MBh
Leaving Coil Dry Bulb 57.21 F
Net Total 35.94 MBh
Leaving Coil Wet Bulb 57.21 F
Net Sensible 28.76 MBh
Leaving Unit Dry Bulb 58.99 F
Fan Motor Heat 1.03 MBh
Leaving Unit Wet Bulb 57.90 F
Refrig Charge -circuit 1 3.2 lb
Refrigeration System Options
Leaving Dew Point 57.21 F
Heating Section
Heating Stages 2
Output Heating Capacity 81.00 MBh
Output Heating Capacity with Fan 82.25 MBh
Heating EAT 70.00 F
Heating LAT 132.70 F
Heating Temp Rise 62.70 F
• Indoor Fan Data
Outdoor Fan Data
Type FC Centrifugal
Type Propeller
Drive Type Direct
Fan Quantity 1
Indoor Fan Performance
Drive Type Direct
Airflow 1200 cfm
Outdoor Fan Performance
Design ESP 0.500 in H2O
Condenser Fan FLA 0.00 A
Indoor Motor Operating Power 0.40 bhp
Exhaust Fan Data
Indoor Motor Power 0.30 kW
Type FC Centrifugal
Indoor RPM 918 rpm
Drive Type Direct
Indoor Fan FLA 0.00 A
Exhaust Fan Performance
Exhaust Fan FLA 0.00 A
Power 0.00 kW
Circuit 1 RLA 0.00 A
2018-04-25 21:14:40Z * Circuit 2 RLA 1.10 A
M
Page 1 of 9
TRANS®
Job Name:GENSCO STOCK
PreparedSTOCK
Unit YSCO 6G3 MBOO
Quantity: 1
EVAPORATOR
SECTION ACCESS PARED
CONDENSATE DRAIN (ALT)
3/4'-14 NPT DIA. HOLE —
THROUGH THE BASE
CONDENSATE —
L',
1Q"
i
RETURN
lIr
4`'
1
91/4" 14' 1 L3518-
DIMENSION DRAWING
RETURN
SUPPLY
E143/4-
PANEL
CONDENSER FAN
SER COIL
'NIT CONTROL WIRE 7/8' DIA. HOLE
SERVICE GAUGE PORTACCESS 1 3/8'DIA. HOLE
NRPOWER WIRE
ONTROL AND COM PRESSOR ACCESS PANEL
—1R' NPT GAS CONNECTION
NOTE S:
1. TM RU -TM E -BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2. VERIFY WEIGHT,CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
40
231/4"
4 3/4'
17 1 /4' 8 7/8' Ll3 1 /4' 3 3/18'
69 7B'
CONDENSATE
7/8"
201/4"
9 5/8'
4 1/4'
5 9/ 16
7 5/8
44 1/4'
PACKAGED GAS / ELECTRICAL
DIMENSION DRAWING
HORIZONTAL
AIR FLOW
2018-04-25 21:14:40Z Page 2 of 9
Job Name:GENSCO STOCK
TRANS® Unit Prepared
YSSTOCK
CO 6G3 MBOO
Quantity: 1
3/4'-14 NPT
DRAIN CONNECTION
SUPPLY
RETURN
23 9/16' \4\v4
r
ISOMETRIC -PACKAGED COOLING
2015-04-25 21:14:40Z Page 3 of 9
Job Name: GENSCO STOCK
TRAIV6® Unit Prepared
YSSTOCK
CO 6G3 MBOO
Quantity: 1
ELECTRICAL / GENERAL DATA
12X4)(a)
GENERAL
HEATING PERFORMANCE
Model
YSC036G
Oversized Motor
HEATING -GENERALDATA
Unit Operating Voltage.
187-253
61 CA:
N/A
Unit Prim aryVoltage
208
1.1FS:
N/A
Heat ng 6lodel
Medium
Unit Secondary Voltage
230
Ia CB:
NIA
Heating Input (BTU)
100.000/70.000
Unit H ertz.
60
Heating Output (BTU ).
81.000/56,700
Unit Phase.
3
No Burners.
3
No Stages
2
EE R/SE ER
12.0/14.0
Standard Motor
Field Installed Oversized 61 otor
Gas Inlet Pressure
1.1CA-
19.9
1.1CA- N/A
NaturalGas (Min/Mix) '.
4.5/14.0
MFS.
30.0
1.1FS
N/A
LP(M nlM ax)
11.0/14,0
1.1CB
30.0
1.1C8 N/A
Gas Pipe Connection Size:
1/2,
INDOOR MOTOR
Standard 1.1 otor
Oversized Motor
Field Installed Oversized Motor
Number
1
Number N/A
Number
NIA
Horsepower
0.75
Horsepower N/A
Horsepower
NIA
Motor Speed ( RPLIV
—
Motor Speed (RPM N/A
Motor Speed(RPM)
NIA
Phase
1
Phase N/A
Phase
NIA
Full Load Amps:
5 7
Full Load Amps N/A
Full Load Amps
N/A
Locked RotorAmps.
_
Locked Rotor Amps N/A
Locked Rotor Amps:
NIA
COMPRESSOR
Circut 12
OUTDOOR MOTOR
Number
1
Number 1
Horsepower
2.8
Horsepower: 0.25
Phase
3
1.1 oto r Speed (RPM): 11DO
Rated Load Amps.
12.8
Phase. 3
Locked Rotor amps.
950
Full Load Amps-. 1.1
Locked RotorAmps. 3.6
POWER EXHAUST ACCESSORY
FILTERS
REFRIGERANT i2'
iField Installed Power E#rausti
Type
Phase.
N/A
Type, Throwaway
Horsepower
N/A
Furnished. Yes
Factory Charge
Motor Speed(R PM):
N/A
Number 2
Crcwt $l 32It,
Full Load Amps
N/A
Recommended 20'x3"x2'
Circuit s2 N/A
Lo cked Rotor Am ps.
N/A
110uK
1 61 aximum (HACR ) Circuit Breaker sang is br installations in the United States only
2 Refrigerant charge is an approxm ate value For a more pre ase value, see unit nameplate and sery ice instructions.
3 Value does not ncludePower Exhaust Accessory
4 Value includes oversized motor
5 Value does not include Power E xhaust Accessory
6. E E R is rated at AH RI conditions and in accordance with DOE test procedures
2018-04-25 21:14:40Z Page 4 of 9
Job Name: GENSCO STOCK
0 TR E® Unit Prepared
YSCO 6G3EMBOOCK
Quantity: 1
PACKAGED GAS / ELECTRICAL
CORNER WEIGHT
\O
A
INSTALLED ACCESSORIES NET WEIGHT DATA
ACCE SSORY
E IGH—S
ECONOMIZER
1.1OTORIZED OUTSIDE AIR DAMPER
1.1ANUAL OUTSIDE AIR DAMPER
BAROMETRIC RELIEF
OVERSIZED MOTOR
BELT DRIVE MOTOR
POWER EXHAUST
THROUGHTTHE BASE ELECTRICAL/GAS.FIOPS
UNIT MOUNTED CIRCUIT BREAKER (FIOPS)
UNIT MOUNTED DISCONNECT (FIOPS)
POWERED CONVENIENCE OUTLET (FIOPS)
HINGED DOORS iFIOPSI
HAIL GUARD
SMOKE DETECTOR, SUPPLY/ RETURN
NOVAR CONTROL
STAINLESS STEEL HEAT EXCHANGER
REHEAT
ROOFCURB
BASIC UNIT WEIGHTS
SHIPPING NET
577.0 Ib 172.0 Ib
CORNER WEIGHTS
[Ell 193 0lb CO sE C It
178 0 lb DO 5° C IC
CENTER OF GRAVITIY
(E) LENGHT (F) WIDTH
33'
OTE:
All weights are a ppro w m a to
Weights for options that are not list refer to Installation guide
The actual walght are listed on the unit nameplate
Ion guide for weights before scheduling transportation and Installation
olcal unit operating veight for the configuration sekrted Estimated
nenslon with installer documents before Installation
Ition only
�ssones should be added to unit velght Men ordering factory or field
PACKAGED GAS/ELECTRICAL
RIGGING AND CENTER OF GRAVITY
2018-04-25 21:14:40Z Page 5 of 9
0 TRIIIYE
Job Name:GENSCO STOCK
Prepared By: GENSCO STOCK
Unit Tag: YSC036G3EMB00
Quantity: 1
CLEARANCE 36"
1
DOWNFLOW CLEARANCE 36"
HORIZONTAL CLEARANCE 18'
ROOF OPENING
UNIT OUTLINE-
PACKAGED GAS/ELECTRIC
CLEARANCE
CLEARANCE FROM TOP OF UNIT 72'
CLEARANCE48"
CLEARANCE 36"
37" I 44 VT
40"
68 3118'
PACKAGED GAS/ELECTRIC
DOWN FLOW TYPICAL ROOF OPENING
2018-04-25 21:14:40Z Page 6 of 9
Job Name: GENSCO STOCK
TRANS® Unit Tag: YSCO 6G3 MBOOCK
Quantity: 1
General
The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling
as standard from the factory for units with microprocessor controls. Operating range for units with
electromechanical controls shall be between 1150F and 40°F. Cooling performance shall be rated in
accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully
charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation,
and control sequence before leaving the factory. Wiring internal to the unit shall be colored and
numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance
for Central Cooling Air Conditioners.
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall
be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface
shall be tested 672 hours in a salt spray test in compliance with ASTM 13117. Cabinet construction
shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be
removed and reinstalled by removing two fasteners while providing a water and air tight seal. All
exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil -
faced, fire -retardant permanent, odorless glass fiber material. The base of the unit shall be insulated
with 1/8 inch, foil -faced, closed -cell insulation. All insulation edges shall be either captured or sealed.
The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1
1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with
forklift capabilities on three sides of the unit.
Unit Top
The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and
gasket -sealed. The ribbed top adds extra strength and enhances water removal from unit top.
Filters
Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall
also be available.
Compressors
All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps.
Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10
percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors.
Dual compressors are outstanding for humidity control, light load cooling conditions and system back-
up applications. Dual compressors are available on 7'/2-10 ton models and allow for efficient cooling
utilizing 3-stages of compressor operation for all high efficiency models.
Indoor Fan
The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F,
T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward -curved fan wheel along
with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a
variable speed adjustment potentiometer located in the control box.
3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with
adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed,
direct drive motors. All 6 to 8'/2 ton units (standard efficiency) shall have belt drive motors with an
adjustable idler -arm assembly for quick -adjustment to fan belts and motor sheaves. All motors shall be
thermally protected. All 10 tons, 6 ton (074), 71/2 to 8'/2 (high efficiency) units have variable speed
direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
2018-04-25 21:14:40Z Page 7 of 9
Aft
Job Name: GENSCO STOCK
TJMME® Unit Prepared
YSCO 6G3 MBOOCK
V Quantity: 1
Outdoor Fans
The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical
discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal
overload protection.
Evaporator and Condenser Coils
Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be
standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel
condenser coils are standard for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high
efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton
dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube -to -fin
bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can
reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to
better compressor reliability. Compact all -aluminum microchannel coils also help to reduce the unit
weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all
aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition,
flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils
shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser
coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The
condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of
cleaning. A plastic, dual -sloped, removable and reversible condensate drain pan with through -the -base
condensate drain is standard.
Controls
Unit shall be completely factory -wired with necessary controls and contactor pressure lugs or terminal
block for power wiring. Unit shall provide an external location for mounting a fused disconnect device.
A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls
provide for all 24V control functions. The resident control algorithms shall make all heating, cooling,
and/or ventilating decisions in response to electronic signals from sensors measuring indoor and
outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift
from set point, and provides better building comfort. A centralized microprocessor shall provide anti -
short cycle timing and time delay between compressors to provide a higher level of machine
protection. 24-volt electromechanical control circuit shall include control transformer and contactor
High Pressure Control
All units include High Pressure Cutout as standard.
Phase monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by
phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that
provides an ON or FAULT indicator. There are no field adjustments. The module will automatically
reset from a fault condition.
Refrigerant Circuits
Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and
refrigerant line filter driers are factory -installed as standard. An area shall be provided for replacement
suction line driers.
2018-04-25 21:14:40Z Page 8 of 9
Job Name:GENSCO STOCK
0 TR E® Unit Prepared
YSCO 6G3EMBOOCK
Quantity: 1
Gas Heating Section
The heating section shall have a progressive tubular heat exchanger design using stainless steel
burners
and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the
combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system.
On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before
ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until
manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or
propane (field -installed kit) and also comply with the California requirement for low NOx emissions
(Gas/Electric Only).
2018-04-25 21:14:40Z Page 9 of 9