REVIEWED BLD2024-0736+Manufacturer_Specifications_and_Installation_Instructions+6.3.2024_8.28.21_AM+4295408TRAIVE® Job Name: STOCK RECEIVED Prepared By:: GENS GENSCO STOCK Unit Tag: YSC036G3EMB00 Quantity: 1 B L D 2024-0736 Jun 03 2024 CITY OF EDMONDS Trane Precedent Gas/Electric Packaged Rooftop DEVELD PARTMENRVICES Application Unit Size pp y an xternai Dimensions m. Weigh EER IEER/SEER = External � DX cooling, 3 Ton 036 Airflow Static Height Width Length Minimum Maximum gas heat ) Pressure 12.0 EER 1200 cfm 0.500 in H2O 3.41 ft 3.69 ft 5.82 ft 472.0 lb 747.0 lb Unit Electrical ;0 \/nl4�nn/nh�cc/hnh� �nu_�zn/an/� Entering Dry Bulb 80.00 F Capacity Entering Wet Bulb 67.00 F Gross Total 36.97 MBh Ambient Temp 95.00 F Gross Sensible 29.79 MBh Leaving Coil Dry Bulb 57.21 F Net Total 35.94 MBh Leaving Coil Wet Bulb 57.21 F Net Sensible 28.76 MBh Leaving Unit Dry Bulb 58.99 F Fan Motor Heat 1.03 MBh Leaving Unit Wet Bulb 57.90 F Refrig Charge -circuit 1 3.2 lb Refrigeration System Options Leaving Dew Point 57.21 F Heating Section Heating Stages 2 Output Heating Capacity 81.00 MBh Output Heating Capacity with Fan 82.25 MBh Heating EAT 70.00 F Heating LAT 132.70 F Heating Temp Rise 62.70 F • Indoor Fan Data Outdoor Fan Data Type FC Centrifugal Type Propeller Drive Type Direct Fan Quantity 1 Indoor Fan Performance Drive Type Direct Airflow 1200 cfm Outdoor Fan Performance Design ESP 0.500 in H2O Condenser Fan FLA 0.00 A Indoor Motor Operating Power 0.40 bhp Exhaust Fan Data Indoor Motor Power 0.30 kW Type FC Centrifugal Indoor RPM 918 rpm Drive Type Direct Indoor Fan FLA 0.00 A Exhaust Fan Performance Exhaust Fan FLA 0.00 A Power 0.00 kW Circuit 1 RLA 0.00 A 2018-04-25 21:14:40Z * Circuit 2 RLA 1.10 A M Page 1 of 9 TRANS® Job Name:GENSCO STOCK PreparedSTOCK Unit YSCO 6G3 MBOO Quantity: 1 EVAPORATOR SECTION ACCESS PARED CONDENSATE DRAIN (ALT) 3/4'-14 NPT DIA. HOLE — THROUGH THE BASE CONDENSATE — L', 1Q" i RETURN lIr 4`' 1 91/4" 14' 1 L3518- DIMENSION DRAWING RETURN SUPPLY E143/4- PANEL CONDENSER FAN SER COIL 'NIT CONTROL WIRE 7/8' DIA. HOLE SERVICE GAUGE PORTACCESS 1 3/8'DIA. HOLE NRPOWER WIRE ONTROL AND COM PRESSOR ACCESS PANEL —1R' NPT GAS CONNECTION NOTE S: 1. TM RU -TM E -BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS. 2. VERIFY WEIGHT,CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 40 231/4" 4 3/4' 17 1 /4' 8 7/8' Ll3 1 /4' 3 3/18' 69 7B' CONDENSATE 7/8" 201/4" 9 5/8' 4 1/4' 5 9/ 16 7 5/8 44 1/4' PACKAGED GAS / ELECTRICAL DIMENSION DRAWING HORIZONTAL AIR FLOW 2018-04-25 21:14:40Z Page 2 of 9 Job Name:GENSCO STOCK TRANS® Unit Prepared YSSTOCK CO 6G3 MBOO Quantity: 1 3/4'-14 NPT DRAIN CONNECTION SUPPLY RETURN 23 9/16' \4\v4 r ISOMETRIC -PACKAGED COOLING 2015-04-25 21:14:40Z Page 3 of 9 Job Name: GENSCO STOCK TRAIV6® Unit Prepared YSSTOCK CO 6G3 MBOO Quantity: 1 ELECTRICAL / GENERAL DATA 12X4)(a) GENERAL HEATING PERFORMANCE Model YSC036G Oversized Motor HEATING -GENERALDATA Unit Operating Voltage. 187-253 61 CA: N/A Unit Prim aryVoltage 208 1.1FS: N/A Heat ng 6lodel Medium Unit Secondary Voltage 230 Ia CB: NIA Heating Input (BTU) 100.000/70.000 Unit H ertz. 60 Heating Output (BTU ). 81.000/56,700 Unit Phase. 3 No Burners. 3 No Stages 2 EE R/SE ER 12.0/14.0 Standard Motor Field Installed Oversized 61 otor Gas Inlet Pressure 1.1CA- 19.9 1.1CA- N/A NaturalGas (Min/Mix) '. 4.5/14.0 MFS. 30.0 1.1FS N/A LP(M nlM ax) 11.0/14,0 1.1CB 30.0 1.1C8 N/A Gas Pipe Connection Size: 1/2, INDOOR MOTOR Standard 1.1 otor Oversized Motor Field Installed Oversized Motor Number 1 Number N/A Number NIA Horsepower 0.75 Horsepower N/A Horsepower NIA Motor Speed ( RPLIV — Motor Speed (RPM N/A Motor Speed(RPM) NIA Phase 1 Phase N/A Phase NIA Full Load Amps: 5 7 Full Load Amps N/A Full Load Amps N/A Locked RotorAmps. _ Locked Rotor Amps N/A Locked Rotor Amps: NIA COMPRESSOR Circut 12 OUTDOOR MOTOR Number 1 Number 1 Horsepower 2.8 Horsepower: 0.25 Phase 3 1.1 oto r Speed (RPM): 11DO Rated Load Amps. 12.8 Phase. 3 Locked Rotor amps. 950 Full Load Amps-. 1.1 Locked RotorAmps. 3.6 POWER EXHAUST ACCESSORY FILTERS REFRIGERANT i2' iField Installed Power E#rausti Type Phase. N/A Type, Throwaway Horsepower N/A Furnished. Yes Factory Charge Motor Speed(R PM): N/A Number 2 Crcwt $l 32It, Full Load Amps N/A Recommended 20'x3"x2' Circuit s2 N/A Lo cked Rotor Am ps. N/A 110uK 1 61 aximum (HACR ) Circuit Breaker sang is br installations in the United States only 2 Refrigerant charge is an approxm ate value For a more pre ase value, see unit nameplate and sery ice instructions. 3 Value does not ncludePower Exhaust Accessory 4 Value includes oversized motor 5 Value does not include Power E xhaust Accessory 6. E E R is rated at AH RI conditions and in accordance with DOE test procedures 2018-04-25 21:14:40Z Page 4 of 9 Job Name: GENSCO STOCK 0 TR E® Unit Prepared YSCO 6G3EMBOOCK Quantity: 1 PACKAGED GAS / ELECTRICAL CORNER WEIGHT \O A INSTALLED ACCESSORIES NET WEIGHT DATA ACCE SSORY E IGH—S ECONOMIZER 1.1OTORIZED OUTSIDE AIR DAMPER 1.1ANUAL OUTSIDE AIR DAMPER BAROMETRIC RELIEF OVERSIZED MOTOR BELT DRIVE MOTOR POWER EXHAUST THROUGHTTHE BASE ELECTRICAL/GAS.FIOPS UNIT MOUNTED CIRCUIT BREAKER (FIOPS) UNIT MOUNTED DISCONNECT (FIOPS) POWERED CONVENIENCE OUTLET (FIOPS) HINGED DOORS iFIOPSI HAIL GUARD SMOKE DETECTOR, SUPPLY/ RETURN NOVAR CONTROL STAINLESS STEEL HEAT EXCHANGER REHEAT ROOFCURB BASIC UNIT WEIGHTS SHIPPING NET 577.0 Ib 172.0 Ib CORNER WEIGHTS [Ell 193 0lb CO sE C It 178 0 lb DO 5° C IC CENTER OF GRAVITIY (E) LENGHT (F) WIDTH 33' OTE: All weights are a ppro w m a to Weights for options that are not list refer to Installation guide The actual walght are listed on the unit nameplate Ion guide for weights before scheduling transportation and Installation olcal unit operating veight for the configuration sekrted Estimated nenslon with installer documents before Installation Ition only �ssones should be added to unit velght Men ordering factory or field PACKAGED GAS/ELECTRICAL RIGGING AND CENTER OF GRAVITY 2018-04-25 21:14:40Z Page 5 of 9 0 TRIIIYE Job Name:GENSCO STOCK Prepared By: GENSCO STOCK Unit Tag: YSC036G3EMB00 Quantity: 1 CLEARANCE 36" 1 DOWNFLOW CLEARANCE 36" HORIZONTAL CLEARANCE 18' ROOF OPENING UNIT OUTLINE- PACKAGED GAS/ELECTRIC CLEARANCE CLEARANCE FROM TOP OF UNIT 72' CLEARANCE48" CLEARANCE 36" 37" I 44 VT 40" 68 3118' PACKAGED GAS/ELECTRIC DOWN FLOW TYPICAL ROOF OPENING 2018-04-25 21:14:40Z Page 6 of 9 Job Name: GENSCO STOCK TRANS® Unit Tag: YSCO 6G3 MBOOCK Quantity: 1 General The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be between 1150F and 40°F. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for Central Cooling Air Conditioners. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM 13117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil - faced, fire -retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with 1/8 inch, foil -faced, closed -cell insulation. All insulation edges shall be either captured or sealed. The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit. Unit Top The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and gasket -sealed. The ribbed top adds extra strength and enhances water removal from unit top. Filters Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall also be available. Compressors All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Dual compressors are outstanding for humidity control, light load cooling conditions and system back- up applications. Dual compressors are available on 7'/2-10 ton models and allow for efficient cooling utilizing 3-stages of compressor operation for all high efficiency models. Indoor Fan The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F, T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward -curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control box. 3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed, direct drive motors. All 6 to 8'/2 ton units (standard efficiency) shall have belt drive motors with an adjustable idler -arm assembly for quick -adjustment to fan belts and motor sheaves. All motors shall be thermally protected. All 10 tons, 6 ton (074), 71/2 to 8'/2 (high efficiency) units have variable speed direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). 2018-04-25 21:14:40Z Page 7 of 9 Aft Job Name: GENSCO STOCK TJMME® Unit Prepared YSCO 6G3 MBOOCK V Quantity: 1 Outdoor Fans The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. Evaporator and Condenser Coils Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel condenser coils are standard for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube -to -fin bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better compressor reliability. Compact all -aluminum microchannel coils also help to reduce the unit weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A plastic, dual -sloped, removable and reversible condensate drain pan with through -the -base condensate drain is standard. Controls Unit shall be completely factory -wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls provide for all 24V control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized microprocessor shall provide anti - short cycle timing and time delay between compressors to provide a higher level of machine protection. 24-volt electromechanical control circuit shall include control transformer and contactor High Pressure Control All units include High Pressure Cutout as standard. Phase monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments. The module will automatically reset from a fault condition. Refrigerant Circuits Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter driers are factory -installed as standard. An area shall be provided for replacement suction line driers. 2018-04-25 21:14:40Z Page 8 of 9 Job Name:GENSCO STOCK 0 TR E® Unit Prepared YSCO 6G3EMBOOCK Quantity: 1 Gas Heating Section The heating section shall have a progressive tubular heat exchanger design using stainless steel burners and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or propane (field -installed kit) and also comply with the California requirement for low NOx emissions (Gas/Electric Only). 2018-04-25 21:14:40Z Page 9 of 9