Loading...
REVIEWED BLD2024-0778+Manufacturer_Specifications_and_Installation_Instructions+6.12.2024_2.30.42_PM+4317991TRAIVE® Job Name: Stock heat pumps Prepared For: Gensco B LD2024-0778 RECEIVED Unit Tag: WSC036H3ROA01 Quantity: 1 Jun 14 2024 Trane Precedent Heat Pump Packaged Rooftop DE EiLO OF MEN SEDMONDSERVICES Application Unit Size = Supply F7R"R External Airflow Static DX cooling 3 Ton Pressure 1200 cfm 0.500 in H2O Dimensions Operating Weight Height Width Length Minimum Maximum 3.41 ft 3.69 ft 5.82 ft 507.0 lb 785.0 lb Unit Electrical Voltage/phase/hertz 208-230/60/3 - MCA 26.00 A MOP 40.00 A MCA (230 w/ Elec Heat) 0.00 A MOP (230 w/ Elec Heat) 0.00 A *See page 4 for electrical for unit + heater Unit is single point entry only ntering Dry Bulb 80.00 F Entering Wet Bulb 67.00 F Ambient Temp 95.00 F Leaving Coil Dry Bulb 55.64 F Leaving Coil Wet Bulb 55.55 F Leaving Unit Dry Bulb 57.92 F Leaving Unit Wet Bulb 56.71 F Heat Pump Mode Output Heating Capacity 35.50 MBh Output Heating Capacity with Fan 35.79 MBh Heating Delta T 27.39 F Heating EAT 70.00 F Heating Ambient Temp 47.00 F Heating Ambient WB 42.60 F Heating Ambient Relative 70.00 % Humidity EER IEER/SEER Elevation 12.1 EER 14.30 Capacity Gross Total 39.43 MBh Gross Sensible 29.42 MBh Net Total 38.68 MBh Net Sensible 28.67 MBh Fan Motor Heat 0.29 MBh Refrig Charge -circuit 1 7.7 lb 0.00 ft • Indoor Fan Data Outdoor Fan Data Type FC Centrifugal Type Propeller Drive Type Direct Fan Quantity 1 Evap Fan FLA 5.70 A Drive Type Direct Indoor Fan Performance Outdoor Fan Performance Airflow 1200 cfm Condenser Fan FLA 1.10 A Design ESP 0.500 in H2O Component SP 0.000 in H2O Total SP 0.500 in H2O Supply Motor Horsepower 0.750 hp Indoor Motor Operating Power 0.29 bhp Indoor RPM 795 rpm Compressor Power 2.93 kW EMctric heaters 6 kW Electric heat 3 ph Circuit 1 RLA 15.00 A Circuit 2 RLA 0.00 A ' 2022/06/15 16:15:14 Page 1 of 9 TRAIVE® 0 Job Name: Stock heat pumps Prepared For: Gensco Unit Tag: WSC036H3ROA01 Quantity: 1 Acoustics Sound Path 63 Hz 125 Hz 250 Hz Ducted Discharge 82 dB 73 dB 67 dB Ducted Inlet 81 dB 72 dB 61 dB Outdoor Noise 84 dB 85 dB 80 dB 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz 63 dB 57 dB 53 dB 53 dB 44 dB 56 dB 51 dB 45 dB 42 dB 35 dB 80 dB 77 dB 74 dB 70 dB 64 dB 2022/06/15 16:15:14 Page 2 of 9 TRAIVE® 0 Job Name: Stock heat pumps Prepared For: Gensco Unit Tag: WSC036H3ROA01 Quantity: 1 EVAPORATOR SECTION ACCESS PANEL CONDENSATE DRAIN (ALT) 3/4"-14 NPT DIA. HOLE — 4 1/4' THROUGH THE BASE CONDENSATE PANEL CONDENSER FAN DENSER COIL ® 23 9/16"IT CONTROL WIRE 7/8" DW HOLE eONTROLAND 421/4" AUGE PORT ACCESS 1 3/8" DIA. HOLE WIRE PRESSOR ACCESS PANEL SEE NOTE 3 23 12-1 4 3/16" F----� I I F, I I I I I I I I I I RETURN SUPPLY 1 18" 1 1 I I I I I I I ----I 4" 1512" 91/4" 14" c35/8" PLAN VIEW UNIT DIMENSION DRAWING RETURN SUPPLY 143/4" 7 23 1 4" 40 00 00 4 3/4" 171/4" 87/8" 131/4" 33/16" 89 7/8" CONDENSATE PACKAGED HEATPI DIMENSION DRAWING HORIZONTAL AIR FLOW 2022/06/15 16:15:14 Page 3 of 9 Job Name: Stock heat pumps TRANE® Unit WSC036H3ROA01 Quantity: 1 ELECTRICAL / GENERAL DATA (2)(4X6) GENERAL WITH HEATER Model: WSC036H Oversized Motor Heater kW Rating : 4,5/&0 U nd Operating Voltage: 187-256 MCA: N/A Stage: 1 U nit Primary Voltage: 208 MFS: N/A MCA: 42.0/44.0 Urut Secondary Voltage: 230 MCB: N/A MFS 50.0/50.0 Unit Hertz: 60 MCB %0/%0 Unit Phase: 3 SEER 12.1/14.3 Standard Motor Field Installed Oversized Motor Oversized Motor Field Installed Oversized Motor Minimum CircuitAmpacily: 260 MCA: N/A MCA: N/A MCA Maximum Fuse Size: 40.0 MFS: N/A MFS: N/A MFS: Maximum (HACR) Circuit Breaker. 40.0 MCB: N/A MCB: N/A MCB: INDOOR MOTOR Standard Motor Outsized Motor Field Installed Oversized Motor Number: 1 Number. N/A Number: N/A Horsepower: 0.75 Horsepower: N/A Horsepower: N/A Motor Speed (RPM): — Motor Speed (RPM): N/A Motor Speed (RPM): N/A Phase. 3 Phase: N/A Phase: N/A Full Load Amps: 5.7. Full Load Amps: N/A Full Load Amps: N/A Locked RotorAmps - Locked RotorAmps. N/A Locked RotorAmps N/A COMPRESSOR Circuit 1/2 OUTDOOR MOTOR Number 1 Number. 1 Horsepower: 3.2 Horsepower: 025 Phase. 3 Motor Speed (RPM): 1100 Rated Load Amps: 15.0 Phase: 3 Locked RotorAmps: - Full Load Amps: 1.1 MCC: Locked RotorAmps: - POWER EXHAUST ACCESSORY (37) FILTERS REFRIGERANT (2) (Field Installed Power Exhaust) Type R410 Phase: N/A Type: Throwaway Horsepower: N/A Furnished: Yes Factory Charge Motor Speed (RPM): N/A Number 2 Circuit#1 7.7lb Full Load Amps: N/A Recommended 20"05"x2" Circuit#2 N/A Locked RotorAmps: N/A NOTES: 1. Maximum (HACR) Circuit Breaker sizing is for installations in the United States only. 2. Refrigerant charge is an approximate value. Fora more precise value, see unit nameplate and service instructions. 3. Value does not include Power Exhaust Accessory. 4. Value includes oversized motor. 5. Value does not include Power Exhaust Accessory. 6. EER is rated at AHRI conditions and in accordance with DOE test procedures. 7. Installation ofths powerexhaust kit will affect unit level MCA and could affect MOP sizing having a direct impact on existing field wiring and unit protection devices. The change in MCA4AOP is the sole responsibility of the field installing party Trane will not issue new nameplates as a result of this power exhaust accessory installation. FLA of the power exhaust kit option must be added to the MCA of the unit for building supply conductor sizing determination. 2022/06/15 16:15:14 Page 4 of 9 TRAIVE® Job Name: Stock heat pumps 0 Prepared For: Gensco Unit Tag: WSC036H3ROA01 Quantity: 1 PACKAGED HEAT PUMP CORNER WEIGHT INSTALLED ACCESSORIES NET WEIGHT DATA ACCESSORY WEIGHTS ECONOMIZER MOTORIZED OUTSIDE AIR DAMPER MAN UAL O UTSIDE AIR DAMPER BAROMETRIC RELIEF OVERSIZED MOTOR BELT DRIVE MOTOR POWER EXHAUST HEATER 15.0 Ib THROUGHT THE BASE ELECTRICAL (FIOPS) UNIT MOUNTED CIRCUIT BREAKER (FIOPS) UNIT MOUNTED DISCONNECT (FIOPS) POWERED CONVENIENCE OUTLET (FIOPS) HINGED DOORS (FIOPS) HAIL GUARD SMOKE DETECTOR, SUPPLY/RETURN ROOFCURB BASIC UNIT WEIGHTS SHIPPING NE7 CORNER WEIGHTS OA 144.OIb O 110.OIb CENTER OF GRAVITIY (E) LENGHT (F) WIDTH 812.0 b 507.0 Ib BO 122.0 Ib pO 130.0 Ib 32' 21" NOTE: 1. CORNER WEIGHTSARE GIVEN FOR INFORMATION ONLY. 2. TO ESTIMATE SHIPPING WEIGHTADD 5 LBS TO NET WEIGHT. 3. BASIC UNIT WEIGHT DOES NOT INCLUDE ACCESSORY WEIGHT. TO OBTAIN TOTAL WEIGHT, ADD ACCESSORY NET WEIGHT TO BASIC UNIT WEIGHT. 4. WEIGHTS FOR OPTIONS NOT LISTED ARE >5 LBS. 0' \' 0 PACKAGED HEAT PUMP RIGGING AND CENTER OF GRAVITY 2022/06/15 16:15:14 Page 5 of 9 0 rRavF Job Name: Stock heat pumps Prepared For: Gensco Unit Tag: WSC036H3ROA01 Quantity: 1 CLEARANCE 36" DOWNFLOW CLEARANCE 36" HORIZONTAL CLEARANCE 18" ROOF OPEN IN UNff OUTLINE — PACKAGED HEAT PUMP CLEARANCE CLEARANCE FROM TOP OF UNIT 72" CLEARANCE 48" CLEARANCE 36" I I 37" 44 1 ^_" I I 40" 8 3/16" PACKAGED HEAT PUMP DOWNFLOWTYPICAL ROOF OPENING 2022/06/15 16:15:14 Page 6 of 9 Job Name: Stock heat pumps TRAIV6® Unit Tag: WSC036H3ROA01 Quantity: 1 General The units shall be convertible airflow. The operating range shall be between 11 YF and 0°F in cooling as standard from the factory for units with microprocessor controls. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for Central Cooling Air Conditioners. Case Unit casing shall be constructed of zinc coated, heavy gauge, and galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM 13117. Cabinet construction shall allow for all maintenance on one side of the unit. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil -faced, fire -retardant permanent, odorless glass fiber material. All insulation edges shall be either captured or sealed. The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8" high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit. Unit Top The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and gasket -sealed. The ribbed top adds extra strength and enhances water removal from unit top. Filters Throwaway filters shall be standard on all units. Optional 2" MERV 8 and MERV 13 filters shall also be available. Compressors All units shall have direct -drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Refrigerant Circuits Service pressure ports, and refrigerant line filter driers are factory -installed as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Internally finned, 5/16"copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 650 psig and pressure tested to 450 psig. The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A removable, reversible, double -sloped condensate drain pan with through the base condensate drain is standard. Outdoor Fans The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Standard efficiency 6 to 8.5 ton units come standard with belt drive motors with an adjustable idlerarm assembly for quick -adjustment to fan belts and motor sheaves. All high efficiency and 10 ton standard efficiency shall have variable speed direct drive motors. All motors shall be thermally protected. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). 2022/06/15 16:15:14 Page 7 of 9 Job : Stock heat eFor: Gen co pumps Prepared TINE® Unit Tag: WSC036H3ROA01 Quantity: 1 Controls Unit shall be completely factory -wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls provide for volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized Microprocessor shall provide anti -short cycle timing and time delay between compressors to provide a higher level of machine protection. Phase monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments. The module will automatically reset from a fault condition. Frostat This option is to be utilized as a safety device. The Frostat opens when temperatures on the evaporator coil fall below 10°F. The temperature will need to rise to 50°F before closing. This option should be utilized in low airflow or high outside air applications. (Cooling with Electric Heat Only.) Accessory - Electric Heaters Electric heat modules shall be available for installation within basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide single point connection. Electric heat modules shall be UL listed or CSA certified. Sequence of Operation (if applied in a SINGLE -ZONE CONSTANT -VOLUME SYSTEM or a CHANGEOVER BYPASS SYSTEM) B. SINGLE -ZONE CONSTANT -VOLUME SYSTEM 1. OCCUPIED HEAT/COOL: The RTU shall operate the supply fan continuously and modulate (or cycle) compressors, modulate (or stage) heat, and/or enable airside economizing to maintain zone temperature at setpoint. The OA damper shall open to bring in the required amount of ventilation. 2. MORNING WARM-UP/PRE-COOL: The RTU shall operate the supply fan and modulate (or cycle) compressors or modulate (or stage) heat to raise/lower zone temperature to its occupied setpoint. The OA damper shall remain closed, unless economizing. D. CHANGEOVER BYPASS SYSTEM 1. OCCUPIED HEAT/COOL: Each VAV terminal shall use pressure -independent control, with airflow measurement, to vary primary airflow to maintain zone temperature at its occupied setpoint. The RTU shall modulate the bypass damper to maintain duct static pressure at setpoint and modulate (or cycle) compressors, modulate (or stage) heat, and/or enable airside economizing based on current zone cooling/heating demands. The OA damper shall open to bring in the required amount of ventilation. 2. MORNING WARM-UP/PRE-COOL: Each VAV terminal unit shall vary primary airflow to raise/lower zone temperature to its occupied setpoint. The RTU shall modulate the bypass damper to maintain duct static pressure at setpoint and modulate (or cycle) compressors or modulate (or stage) heat based on current zone cooling/heating demands. The OA damper shall remain closed, unless economizing. 2022/06/15 16:15:14 Page 8 of 9 MAKE® Job Name: Stock heat pumps Prepared For: Gensco Unit Tag: WSC036H3ROA01 Quantity: 1 3. COOLING/HEATING CHANGEOVER LOGIC: The System Controller shall determine the overall system cooling/heating mode based on "voting" from each zone. When the majority of zones require cooling, the RTU shall operate in cooling mode and any zone that requires heating shall reduce primary airflow to minimum. When the majority of zones require heating, the RTU shall operate in heating mode and any zone that requires cooling shall reduce primary airflow to minimum. 2022/06/15 16:15:14 Page 9 of 9