FIR2024-0019+Fire_Sprinkler_Equipment_Specification_Sheets+2.27.2024_11.54.36_AM+4085711F I R2024-0019 tqK:00 Series TY-FRB, 5.6 K-factor ECEIVED Feb 27 2024 Worldwide Contacts www.tyco-fire.com oE,gRNTEENr Es Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers described in this data sheet are quick response, standard coverage, decorative 3 mm glass bulb -type spray sprinklers designed for use in light or ordinary hazard, commercial occupan- cies such as banks, hotels, and shop- ping malls. The recessed version of the Series TY-FRB Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following: • A two-piece Style 15 Recessed Escutcheon with recessed adjust- ment up to 5/8 inch (15,9 mm) from the flush pendent position. • A two-piece Style 20 Recessed Escutcheon with recessed adjust- ment up to 1/2 inch (12,7 mm) from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Intermediate level versions of Series TY-FRB Sprinklers are described in Technical Data Sheet TFP357. Sprin- kler guards and shields are described in Technical Data Sheet TFP780. IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. NOTICE The TYCO Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY313...... Upright 5.61K, 1/2-NPT TY323...... Pendent 5.61K, 1/2-NPT Technical Data Approvals Refer to Table A Maximum Working Pressure 175 psi (12.1 bar) 250 psi (17.2 bar)` `The maximum working pressure of 250 psi (17.2 bar) only applies to the listing by Underwriters Laborato- ries, Inc. (UL). Discharge Coefficient K=5.6 GPM/psi'/2 (80,6 LPM/bar'/2) Temperature Rating Refer to Table A Finishes Sprinkler: Refer to Table B Recessed Escutcheon: White Coated, Black Coated, Chrome Plated, or Brass Plated Physical Characteristics Frame ............................Bronze Button......................Brass/Copper Sealing Assembly ... Stainless Steel w/TEFLON Bulb...............................Glass Compression Screw.................Bronze Deflector..........................Bronze Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers are intended for fire protec- tion systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (such as, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM's Loss Prevention Data Sheets). Only the Style 15 or Style 20 Recessed Escutcheon is to be used for recessed pendent installations. Page 1 of 4 FEBRUARY 2018 TFP172 TFP172 Page 2of4 Components: * Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE -IN ESCUTCHEON 6* I 5 7/16" (11,1 mm) 4 NO 2" U U MAKE -IN (50,8 mm) 2 2" 1-3/8" 3 (50,8 mm) (34,9 mm) W Fl 1 1/2" NPT** DEFLECTOR* 2-7/8" (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS 5.6 K-FACTOR, 112 INCH NPT, QUICK RESPONSE ^WRENCH RECESS (USE ONLY END "A") FIGURE 2 W-TYPE 6 SPRINKLER WRENCH WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 W-TYPE 7 RECESSED SPRINKLER WRENCH Installation The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be installed in accor- dance with this section. General Instructions Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) and 3/32 inch (2,4 mm) for the 286°F (141°C) tem- perature ratings. A leak -tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum to maximum torque of 7 to 14 ft.-Ibs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutch- eon Plate by under- or over -tightening the sprinkler. Re -adjust the position of the sprinkler fitting to suit. Upright and Pendent Sprinklers The Series TY-FRB Upright and Pendent Sprinklers must be installed in accordance with the following instructions. Step 1. Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe -thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 2). With ref- erence to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats. Torque sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0 Nm). Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- dance with the following instructions. Step A. After installing the Style 15 or Style 20 Mounting Plate over the sprinkler threads, and with pipe -thread sealant applied to the pipe threads, hand -tighten the sprinkler into the sprinkler fitting. Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0 N m). Step C. After ceiling installation and finishing, slide on the Style 15 or Style 20 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP172 Page 3 of 4 Care and Maintenance The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be maintained and ser- viced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non - operation in the event of a fire or inad- vertent operation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- tion Section.) The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. 2-7/8" DIA. _ (73,0 mm) 2-1/4" DIA. FACE OF (57,2 mm) SPRINKLER FITTING 5/8" (15,9 mm) FLUSH 3/8±5/16" (9,5±7,9 mm) MOUNTING 1/8" + (3,2 mm) SURFACE CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm) TY-FRB PLATE 3/4" (19,1 mm) FIGURE 4 SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) WITH TWO PIECE 518 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON 2-7/8" DIA. _ (73,0 mm) FACE OF SPRINKLER 2-1/4" DIA. FITTING (57,2 mm) 5/16±1/4" 1/2" (12,7 mm) (7,9±6,4 mm) FLUSH MOUNTING SURFACE aL(312/8mm)l CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm) TY-FRB PLATE 7/8" (22,2 mm) FIGURE 5 SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB Upright or Pendent (specify) Sprinkler, SIN (specify), K=5.6, Quick Response, (specify) temperature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify: Style 15 Recessed Escutch- eon with (specify') finish, P/N (specify') Specify: Style 20 Recessed Escutch- eon with (specify*) finish, P/N (specify*) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 TFP172 Page 4 of 4 SPRINKLER FINISH (See Note 7) K FACTOR TYPE TEMPERATURE BULB LIQUID COLOR NATURAL BRASS CHROME PLATED POLYESTERC 135°F(57°C) Orange UPRIGHT (TY313) 155°F (68°C) Red 175°F (79°C) Yellow and 1, 2, 3, 4, 5, 6 PENDENT (TY323) ° ° 200F 93C ( ) Green 286°F (141°C) Blue 5.6 1/2" NPT 135°F(57°C) Orange RECESSED PENDENT (TY323) Figures 4a and 5b 1, 2, 3, 4 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green Notes: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved (For details, contact TYCO Fire Protective Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are ILL and C-UL Listed as Corrosion -Resistant Sprinklers. a. Installed with Style 15 (1/2" NPT) 5/8" Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. Listings and approvals apply to color (Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/ Na 77 — XXX — X — XXX SIN 370 1 5.6K UPRIGHT (1/2-'NPT) I TY313 371 15.6K PENDENT (1/2-NPT) I TY323 Notes: a. Use suffix "I" for ISO 7-1 connection; for example, 77-370-4-175-1 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE (RAL9010)a POLYESTER 4 SIGNAL WHITE (RAL9003) POLYESTER 5 JET BLACK (RAL9005) POLYESTER TEMPERATURE RATINGS 135 135°F (57°C) 155 155°F (68°C) 175 175°F (79°C) 200 200°F(93°C) 9 CHROME PLATED 286 I 286°F (141°C) Notes: a. Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Otto 62018Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revisiondateand are subject to change without notice. Jot 1nson NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls TEFLON is a registered trademark of DuPont tqC00 Series EC-11 and 11.2 K and 14.0 K Extended Covera General Description TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers are decorative glass -bulb sprinklers designed for use in light or ordinary hazard occupancies. They are intended for use in automatic sprinkler systems designed in accor- dance with standard installation rules, such as NFPA 13, for a maximum cov- erage area of 400 ft2 (37,2 m2) as com- pared to the maximum coverage area of 130 ft2 (12,1 m2) for standard cover- age sprinklers used in ordinary hazard occupancies, Series EC-11 and EC-14 Extended Coverage Sprinklers feature a UL and C-UL Listing that permits their use with unobstructed or non-combus- tible obstructed ceiling construction as defined and permitted by NFPA 13, as well as a specific application listing for use under concrete tees. Series EC-11 and EC-14 Extended Cov- erage Sprinklers have been fire tested to compare their performance to that of standard coverage spray sprinklers. These tests have shown that the pro- tection provided is equal to or more effective than standard coverage spray sprinklers. Corrosion -resistant coatings, where applicable, help extend the life of copper alloy sprinklers beyond that which occurs when exposed to corrosive atmospheres. Although corrosion -resistant coated sprinklers IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide I Contacts I www tyco-fire.com EC-14 Sprinklers, Upright and ge Light and Ordinary Hazard Pendent passed standard corrosion tests of the applicable approval agencies, this testing is not representative of all pos- sible corrosive atmospheres. Conse- quently, it is recommended that the end user be consulted with respect to the suitability of these corrosion -resistant coatings for any given corrosive envi- ronment. The effects of ambient tem- perature, concentration of chemicals, and gas/chemical velocity should be considered, along with the corrosive nature of the chemical to which the sprinklers will be exposed. NOTICE Series EC-11 and EC-14 Extended Coverage Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Numbers TY5137 ............ Upright, 11.2K TY5237............ Pendent, 11.2K TY6137 ............ Upright, 14.OK TY6237........... Pendent, 14.OK TY5137 is a re -designation for C5137, G1894, and S2510 TY5237 is a re -designation for C5237, G1893, and S2511 TY6137 is a re -designation for C6137, G1896, and S2610 TY6237 is a re -designation for C6237, G1895, and S2611 Technical Data Approvals TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers are UL and C-UL Listed. See Table A for complete sprin- kler approval information including cor- rosion -resistant status. The approvals apply to the service conditions indi- cated in the Design Criteria section. Series EC-11 and EC-14 Extended Cov- erage Sprinklers are FM Approved. See Table A for complete sprinkler approval information including corrosion -resis- tant status. The approvals apply to the service conditions indicated in the Design Criteria section. Page 1 of 8 JUNE 2019 TFP22O TFP220 Page 2of8 WRENCH FLAT 3/4" N PT ** 2-7/16" (61,9 mm) UPRIGHT & PENDENT 1/2" (12,7 mm) NOMINAL MAKE -IN UPRIGHT ESCUTCHEON PLATE .,FATINr,' sl IRFACE 1 2 3 16" _-4 nm) 5 6* CROSS PENDENT SECTION Components: 1 Frame 2 - Button 3 Sealing Assembly 4 Bulb 5 Compression Screw 6 Deflector * Temperature rating is indicated on Deflector. ** Pipe thread connections per ISO 7-1 can be provided on special request. FIGURE 1 SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS 11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237) 14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237) ASSEMBLY The Style 60 Two -Piece Flush Escutch- eon shown in Figure 4 is UL Listed for use with the Series EC-11 and EC-14 Pendent Sprinklers. Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection 3/4 in. NPT Discharge Coefficients K = 11.2 GPM/psis (161,3 LPM/bars) K = 14.0 GPM/psi/2 (201,6 LPM/bar') Temperature Ratings See Table A Finish Sprinkler: See Table A Recessed or Flush Escutcheon: White -Coated, Chrome -Plated, and Brass -Plated Physical Characteristics Frame ............................ Bronze Button ............................ Bronze Sealing Assembly . Beryllium Nickel w/TEFLON Bulb ........................ Glass (3 mm) Compression Screw ................ Bronze Deflector ........................... Brass Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, which then allows the sprin- kler to activate and flow water. Design Criteria TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers must only be installed in accordance with the applicable UL and C-UL Listing or FM Approval requirements as indi- cated below. Only Style 30 or 40 Recessed Escutcheons are to be used for recessed installation, as applica- ble. See Tables A, B, and C, for more information. UL and C-UL Listing Requirements 1. Series EC-11 and EC-14 Extended Coverage Sprinklers may be used for the coverage areas shown in Table D, based on maintaining the minimum specified flow rate as a function of coverage area and haz- ard group for all sprinklers in the design area. 2. Series EC-11 and EC-14 Extended Coverage Sprinklers are permitted to be used with unobstructed or non-combustible obstructed ceil- ing construction as defined and permitted by NFPA 13; for example: • Unobstructed, combustible or noncombustible, ceiling con- struction with a deflector to ceiling/roof deck distance of 1 to 12 in. (25 to 300 mm). • Obstructed, non-combusti- ble, ceiling construction with a deflector location below struc- tural members of 1 to 6 in. (25 to 150 mm) and a maximum deflector to ceiling/roof deck dis- tance of 22 in. (550 mm). 3. Series EC-11 and EC-14 Extended Coverage Sprinklers, specifically tested and listed for non-combus- tible obstructed construction, are permitted to be used within truss- es or bar joists having non-com- bustible web members greater than 1 in. (25,4 mm) when apply- ing the 4 times obstruction crite- ria rule defined under "Obstruc- tions to Sprinkler Discharge Pattern Development". 4. To prevent cold soldering, the minimum allowable spacing be- tween Series EC-11 and EC-14 Ex- tended Coverage Sprinklers is 8 ft (2,4 m) for upright sprinklers and 9 ft (2,7 m) for pendent sprinklers. 5. Series EC-11 and EC-14 Extended Coverage Sprinklers are to be in- stalled in accordance with all oth- er requirements of NFPA 13 for extended coverage upright and pendent sprinklers; For exam- ple, obstructions to sprinkler dis- charge, obstructions to sprinkler pattern development, obstructions to prevent sprinkler discharge from reaching hazard and clearance to storage. TFP220 Page 3 of 8 Hazard Type Temperature Bulb Liquid Sprinkler Finish (See Note 5) Natural Brass Chrome Plated polyester* Lead Coated 135°F(57°C) Orange Upright K=11.2 (TY5137) 1, 2, 3--, 4 ° ° 155F 68C ( ) Red 175°F (79°C) Yellow Light Pendent Table B describes UL and C-UL K=11.2 (TY5237) K=14.0 (TY6237) 200°F (93°C) Green 1, 2, 4 1, 2, 4 286°F (141°C) Blue Sensitivity Rating Table C describes FM Sensitivity Rating Recessed Pendent K=11.2 (TY5237) K=14.0 (TY6237) 135°F (57°C) Orange 1, 2, 3, 4 N/A 155°F (68°C) Red 175°F (79°C) Yellow With Style Escutcheonn 1, 2, 4 200°F (93°C) Green 286°F (141°C) Blue Ordinary Table B describes Upright K=11.2 (TY5137) K=14.0 (TY6137) Pendent K=11.2 (TY5237) 135°F (57°C) Orange 1, 2, 3, 4 1, 2, 3, 4 155°F (68°C) Red 175°F (79°C) Yellow 1, 2, 4 200°F (93°C) Green UL and C-UL Sensitivity Rating K=14.0 (TY6237) 286°F (141°C) Blue Table C describes Recessed Pendent 135°F(57°C) Orange 155°F (68°C) Red FM Sensitivity Rating K=11.2 (TY5237) K=14.0 (TY6237) With Style 30 or 40 1, 2, 4 N/A 175°F (79°C) Yellow Escutcheon 200°F(93°C) Green NOTES 1. Listed by Underwriters Laboratories, Inc. (UL) 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) 3. Approved by Factory Mutual Research Corporation (FM) 4. Approved by the City of New York under MEA 177-03-E 5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers N/A = Not Available * Frame and Deflector only ** Pendent only TABLE A LABORATORY LISTINGS AND APPROVALS Light Hazard Ordinary Hazard Area Style ftxft 135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F (57°C) (68°C) (79°C) (93°C) (141°C) (57°C) (68°C) (79°C) (93°C) (141°C) Upright or Pendent - - - - OR OR OR OR OR 14 x 14 Style 30 Recessed - - - - OR OR OR OR OR Style 40 Recessed - - - - OR OR OR OR OR Upright or Pendent OR' QW QR' OR` OR' SR SR SR SR SR 16 x 16 Style 30 Recessed QW QW QR' OR' OR' SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR Upright or Pendent QW QW QR" QR" QR" SR SR SR SR SR 18 x 18 Style 30 Recessed QW QR" QR" QW QR' SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR Upright or Pendent QR" QR' QW SR` SR* SR SR SR SR SR 20 x 20 Style 30 Recessed OR' QR' QR' SR* SR` SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR NOTES • QR = Quick Response • SR = Standard Response • N/A = Not Applicable ' Does not apply to Upright K=14.0 TABLE B SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS (SEE TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS) TFP220 Page 4 of 8 HC-1 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-factor Style Response Min Max Min Max Noncombustible Unobstructed, 11.2 EC Pendent or 10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Upright Combustible Unobstructed Noncombustible Unobstructed, 11.2 EC Pendent 10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Recessed Combustible Unobstructed Style 30 10 20 100 400 Up to 30 Combustible Obstructed 11.2 EC 14.0 EC Pendent or Upright Quick 11.2 EC Pendent 10 20 100 400 Up to 30 Combustible Obstructed 14.0 EC Recessed Style 30 10 20 100 400 Over 30 and up to 45 Noncombustible Unobstructed 11.2 EC 14.0 EC Upright HC-2 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-factor Style Response Min Max Min Max 10 20 100 400 Up to 30 Noncombustible Unobstructed, 11.2 EC Pendent or Upright Quick 10 20 100 400 Up to 30 14.0 EC Pendent or Upright Combustible Unobstructed 10 16 100 256 Over 30 and 11.2 EC 14.0 Upright up to 45 EC HC-3 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-Factor Style Response Min Max Min Max 10 16 100 256 Up to 30 11.2 EC Upright 10 20 100 400 Up to 30 14.0 EC Pendent or Upright Noncombustible Unobstructed, Combustible Unobstructed Quick 10 16 100 256 Over 30 and 11.2 EC, Upright up to 45 14.0 EC NOTES • The design for K 11.2 EC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi (0,8 bar); similarly the design for K 14.0 EC (K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi (1,2 bar). • For flow criteria, refer to FM Loss Prevention Data Sheet 3-26. • Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations. TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS UL and C-UL Specific Application depth of the concrete tees must not 3. When the sprinkler deflectors are Listing Requirements for exceed 30 in. (762 mm). The maxi- located higher than a horizontal Installation under Concrete Tees mum permitted concrete tee length plane 1 in. (25,4 mm) beneath the Series EC-11 and EC-14 Extended Cov- is 32 ft (9,8 m). However, where the bottom of the concrete tee stems, erage Upright and Pendent Sprinklers concrete tee length exceeds 32 ft the obstruction to sprinkler dis- (TY5137, TY5237, TY6137 and TY6237) (9,8 m), non-combustible baffles, charge criteria requirements of have a UL and C-UL Specific Applica- equal in height to the depth of the NFPA 13 for extended coverage tion Listing for use under concrete tees tees, can be installed so that the upright and pendent sprinklers when installed as follows: space between the tees does not applies. 1. Stems of the concrete tee con- exceed 32 ft (9,8 m) in length. struction must be spaced at less 2. The sprinkler deflectors are to be than 7.5 ft (2,3 m) on center but located in a horizontal plane at or more than 3 ft (0,9 m) on center. The above 1 in. (25,4 mm) below the bottom of the concrete tee stems. TFP220 Page 5 of 8 Description Area ft x ft Light Hazard 0.10 GPM/ft2 Group I Ordinary Hazard 0.15 GPM/ft2 Group II Ordinary Hazard 0.20 GPM/ft2 GPM PSI GPM PSI GPM PSI 14 x 14 30 7.2 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 TY5137 18 x 18 33 8.7 49 19.1 65 33.7 (K=11.2) Upright 20 x 20 40 12.8 60 28.7 80 51.0 14 x 14 30 7.2 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 TY5237 18 x 18 33 8.7 49 19.1 65 33.7 (K=11.2) Pendent 20 x 20 40 12.8 60 28.7 80 51.0 14 x 14 N/A N/A 39 7.8 51 13.3 16 x 16 N/A N/A 39 7.8 51 13.3 TY6137 18 x 18 N/A N/A 49 12.3 65 21.6 (K=14.0) Upright 20 x 20 N/A N/A 60 18.4 80 32.7 14 x 14 37 7.0 39 7.8 51 13.3 TY6237 16 x 16 37 7.0 39 7.8 51 13.3 18 x 18 37 7.0 49 12.3 65 21.6 (K=14.0) Pendent 20 x 20 40 8.2 60 18.4 80 32.7 NOTES • 1 ft = 0,3048 m • 1 1t2 = 0,093 m2 • 1 GPM = 3,785 LPM • 1 psi = 0,06895 bar • 1 GPM/ft2= 40,74 mm/min TABLE D FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS FM Approval Requirements Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprin- klers are to be installed in accor- dance with the applicable FM Loss Prevention Data Sheet for limited use in buildings of specific roof construc- tion and for the protection of certain specific ordinary hazard (non -storage and/or non-flammable or combustible liquid) occupancies. Information pro- vided in the FM Loss Prevention Data Sheets relates to, but is not limited to, hydraulic design, ceiling slope, and obstructions, minimum and maximum allowable spacing, and deflector -to - ceiling distance. These criteria may differ from UL and/or NFPA criteria. Therefore, the designer should review and become familiar with FM requirements before proceeding with design. Installation TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 286°F (141 °C) tempera- ture ratings. A leak -tight 3/4 in. NPT sprinkler joint should be obtained by applying a min- imum -to -maximum torque of 10 to 20 lb-ft (13,4 to 26,8 N•m). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutch- eon Plate by under or over -tightening the Sprinkler. Re -adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler with the deflector parallel to the mounting surface. Install pendent sprinklers in the pendent position. Install upright sprinklers in the upright position. Step 2. After installing the Style 30, 40, or 60 mounting plate, or other applica- ble escutcheon, over the sprinkler pipe threads and with pipe -thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 3. For upright or pendent sprin- klers, wrench -tighten using only the W-Type 3 (End A) Sprinkler Wrench. For the pendent sprinkler installed with Style 30, 40, or 60 Escutcheon, wrench -tighten the sprinkler using only the W-Type 22 Sprinkler Wrench. Apply the wrench recess of the appli- cable sprinkler wrench, Figure 5 and 6, to the sprinkler wrench flats, Figure 1. TFP220 Page 6 of 8 2-7/8" DIA. _ (73,0 mm) 1/2" 12,7 mm (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) SPRINKLER MOUNTING FITTING � PLATE MOUNTING SURFACE 1/8" (3,2 mm) CLOSURE TY5237 or 1-3/8" (34,9 mm) TY6237 1-1/8" (28,6 mm) FIGURE 2 SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 112IN. TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) SPRINKLER MOUNTING FITTING PLATE �wd V77 7/ MOUNTING SURFACE 1/8" (3,2 mm) CLOSURE TY5237 or 1-3/8" (34,9 mm) TY6237 7/8" (22,2 mm) FIGURE 3 SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 314 IN. TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 2-7/8" DIA. _ (73,0 mm) INTERNAL 2-1/4" DIA. DIMENSIONS OF (57,2 mm) STYLE 60 ESCUTCHEON ACCOMMODATE CLASS 150 MALLEABLE FACE OF IRON REDUCING SPRINKLER FITTING: SPRINKLER FITTING 3/8" (9,5 mm) ABOVE TO 1/8" (3,2 mm) BELOW MOUNTING MOUNTING SURFACE 1/8" SURFACE V (3,2 mm) ESCUTCHEON PLATE SEATING SURFACE: 1/4" (6,4 mm) ABOVE CLOSURE TO 1/2" (12,7 mm) BELOW 2-5/16" (58,7 mm) 3/4" NPT MOUNTING SURFACE; MOUNTING 1-13/16" (46,0 mm) 3/4" (19,1 mm) TOTAL PLATE ADJUSTMENT FIGURE 4 SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY WITH 314 IN. TOTAL ADJUSTMENT STYLE 60 TWO-PIECE FLUSH ESCUTCHEON "FITTING SIDE" TOWARDS SPRINKLER FITTING / WRENCH RECESS (END "A") FIGURE 5 W-TYPE 3 SPRINKLER WRENCH WRENCH RECESS p �0111111O WRENCH HEX FIGURE 6 W-TYPE 22 RECESSED SPRINKLER WRENCH TFP220 Page 7 of 8 P/N 51 - XXX -X -XXX SIN SPRINKLER TEMPERATURE FINISHI RATING 893 11.2K Pendent TY5237 1 NATURAL BRASS 135 135°F (57°C) 894 11.2K Upright TY5137 SIGNAL WHITE 155 155°F (68°C) 4 (RAL9003) POLYESTER 895 14.OK Pendent TY6237 JET BLACK (RAL9005) 175 175°F (79°C) 5 POLYESTER 896 14.OK Upright TY6137 200 200°F (93°C) 7 LEAD COATED 286 286°F (141°C) 9 CHROME -PLATED 000 OPEN2 NOTES: 1. Escutcheon ordered separately. 2. OPEN indicates the sprinkler assembly without glass bulb, button, and sealing assembly. TABLE E SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Care and Maintenance TYCO Series EC-11 and EC-14 Extended Coverage Upright and Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. Refer to the Instal- lation section, for more information. Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprin- klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this doc- ument, as well as with the applicable standards recognized by the Approval agency, such as NFPA 25, in addition to the standards of any authorities having jurisdiction. Contact the installing con- tractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series EC-11 or EC-14 (specify) Sprinkler, SIN (specify), (specify) K-factor, Pendent or Upright (specify) Extended Coverage, (specify) temperature rating, (specify) finish, P/N (from Table E) Recessed Escutcheon, Two -Piece Specify: Style (30 or 40) Two -Piece Recessed Escutcheon with (specify) finish, P/N (specify*) *Refer to Technical Data Sheet TFP770 Flush Escutcheon, Two -Piece Specify: Style 60 Two -Piece Flush Escutcheon with (specify) finish, P/N (specify*") **Refer to Technical Data Sheet TFP778 Sprinkler Wrenches Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001 Specify: W-Type 22 Recessed Sprinkler Wrench, P/N 56-665-7-001 TFP220 Page 8of8 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Otto 6 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls TEFLON is a registered trademark of DuPont