Series TY-FRB, 5.6 K-factor
ECEIVED
Feb 27 2024
Worldwide
Contacts www.tyco-fire.com oE,gRNTEENr Es
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb -type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY313...... Upright 5.61K, 1/2-NPT
TY323...... Pendent 5.61K, 1/2-NPT
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)`
`The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi'/2 (80,6 LPM/bar'/2)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button......................Brass/Copper
Sealing Assembly ... Stainless Steel w/TEFLON
Bulb...............................Glass
Compression Screw.................Bronze
Deflector..........................Bronze
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
Page 1 of 4
FEBRUARY 2018
TFP172
TFP172
Page 2of4
Components: * Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE -IN ESCUTCHEON
6* I
5 7/16"
(11,1 mm)
4 NO 2" U U
MAKE -IN (50,8 mm)
2 2" 1-3/8"
3 (50,8 mm) (34,9 mm)
W
Fl
1
1/2" NPT** DEFLECTOR* 2-7/8" (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT, QUICK RESPONSE
^WRENCH RECESS
(USE ONLY
END "A")
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb -type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) and 3/32
inch (2,4 mm) for the 286°F (141°C) tem-
perature ratings.
A leak -tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum to maximum torque of 7 to 14
ft.-Ibs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over -tightening
the sprinkler. Re -adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe -thread sealant
applied to the pipe threads, hand -
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 ft.-Ibs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe -thread
sealant applied to the pipe threads,
hand -tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft.-Ibs. (9,5 to 19,0
N m).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP172
Page 3 of 4
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non -
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
2-7/8" DIA. _
(73,0 mm)
2-1/4" DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING 5/8" (15,9 mm)
FLUSH
3/8±5/16"
(9,5±7,9 mm)
MOUNTING 1/8" +
(3,2 mm)
SURFACE
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 518 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA. _
(73,0 mm)
FACE OF
SPRINKLER 2-1/4" DIA.
FITTING (57,2 mm)
5/16±1/4" 1/2" (12,7 mm)
(7,9±6,4 mm)
FLUSH
MOUNTING
SURFACE aL(312/8mm)l
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify') finish, P/N (specify')
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
TFP172
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR
TYPE
TEMPERATURE
BULB LIQUID
COLOR
NATURAL
BRASS
CHROME
PLATED
POLYESTERC
135°F(57°C)
Orange
UPRIGHT
(TY313)
155°F (68°C)
Red
175°F (79°C)
Yellow
and
1, 2, 3, 4, 5, 6
PENDENT
(TY323)
° °
200F 93C
( )
Green
286°F (141°C)
Blue
5.6
1/2" NPT
135°F(57°C)
Orange
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
1, 2, 3, 4
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
Notes:
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved (For details, contact TYCO Fire Protective Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are ILL and C-UL Listed as Corrosion -Resistant Sprinklers.
a. Installed with Style 15 (1/2" NPT) 5/8" Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/ Na 77 — XXX — X — XXX
SIN
370 1 5.6K UPRIGHT (1/2-'NPT) I TY313
371 15.6K PENDENT (1/2-NPT) I TY323
Notes:
a. Use suffix "I" for ISO 7-1 connection; for example,
77-370-4-175-1
SPRINKLER
FINISH
1
NATURAL BRASS
3
PURE WHITE (RAL9010)a
POLYESTER
4
SIGNAL WHITE (RAL9003)
POLYESTER
5
JET BLACK (RAL9005)
POLYESTER
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F(93°C)
9 CHROME PLATED 286 I 286°F (141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Otto
62018Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revisiondateand are subject to change without notice. Jot 1nson
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls
TEFLON is a registered trademark of DuPont
tqC00
Series EC-11 and
11.2 K and 14.0 K
Extended Covera
General
Description
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers are decorative
glass -bulb sprinklers designed for use
in light or ordinary hazard occupancies.
They are intended for use in automatic
sprinkler systems designed in accor-
dance with standard installation rules,
such as NFPA 13, for a maximum cov-
erage area of 400 ft2 (37,2 m2) as com-
pared to the maximum coverage area
of 130 ft2 (12,1 m2) for standard cover-
age sprinklers used in ordinary hazard
occupancies, Series EC-11 and EC-14
Extended Coverage Sprinklers feature
a UL and C-UL Listing that permits their
use with unobstructed or non-combus-
tible obstructed ceiling construction as
defined and permitted by NFPA 13, as
well as a specific application listing for
use under concrete tees.
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers have been fire tested
to compare their performance to that
of standard coverage spray sprinklers.
These tests have shown that the pro-
tection provided is equal to or more
effective than standard coverage spray
sprinklers.
Corrosion -resistant coatings, where
applicable, help extend the life of
copper alloy sprinklers beyond that
which occurs when exposed to
corrosive atmospheres. Although
corrosion -resistant coated sprinklers
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide I Contacts I www tyco-fire.com
EC-14 Sprinklers,
Upright and
ge Light and Ordinary Hazard
Pendent
passed standard corrosion tests of
the applicable approval agencies, this
testing is not representative of all pos-
sible corrosive atmospheres. Conse-
quently, it is recommended that the end
user be consulted with respect to the
suitability of these corrosion -resistant
coatings for any given corrosive envi-
ronment. The effects of ambient tem-
perature, concentration of chemicals,
and gas/chemical velocity should be
considered, along with the corrosive
nature of the chemical to which the
sprinklers will be exposed.
NOTICE
Series EC-11 and EC-14 Extended
Coverage Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, (NFPA), in addition to
the standards of any other authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers
TY5137 ............ Upright, 11.2K
TY5237............ Pendent, 11.2K
TY6137 ............ Upright, 14.OK
TY6237........... Pendent, 14.OK
TY5137 is a re -designation for C5137, G1894, and S2510
TY5237 is a re -designation for C5237, G1893, and S2511
TY6137 is a re -designation for C6137, G1896, and S2610
TY6237 is a re -designation for C6237, G1895, and S2611
Technical
Data
Approvals
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers are UL and C-UL
Listed. See Table A for complete sprin-
kler approval information including cor-
rosion -resistant status. The approvals
apply to the service conditions indi-
cated in the Design Criteria section.
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers are FM Approved. See
Table A for complete sprinkler approval
information including corrosion -resis-
tant status. The approvals apply to
the service conditions indicated in the
Design Criteria section.
Page 1 of 8
JUNE 2019
TFP22O
TFP220
Page 2of8
WRENCH
FLAT
3/4"
N PT **
2-7/16"
(61,9 mm)
UPRIGHT &
PENDENT
1/2" (12,7 mm)
NOMINAL MAKE -IN
UPRIGHT
ESCUTCHEON PLATE
.,FATINr,' sl IRFACE
1
2
3
16"
_-4
nm)
5
6*
CROSS
PENDENT SECTION
Components:
1 Frame
2 - Button
3 Sealing Assembly
4 Bulb
5 Compression Screw
6 Deflector
* Temperature rating is
indicated on Deflector.
** Pipe thread connections per
ISO 7-1 can be provided on
special request.
FIGURE 1
SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237)
14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237)
ASSEMBLY
The Style 60 Two -Piece Flush Escutch-
eon shown in Figure 4 is UL Listed for
use with the Series EC-11 and EC-14
Pendent Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 in. NPT
Discharge Coefficients
K = 11.2 GPM/psis (161,3 LPM/bars)
K = 14.0 GPM/psi/2 (201,6 LPM/bar')
Temperature Ratings
See Table A
Finish
Sprinkler: See Table A
Recessed or
Flush Escutcheon:
White -Coated,
Chrome -Plated, and
Brass -Plated
Physical Characteristics
Frame ............................
Bronze
Button ............................
Bronze
Sealing Assembly .
Beryllium Nickel w/TEFLON
Bulb ........................
Glass (3 mm)
Compression Screw
................ Bronze
Deflector ...........................
Brass
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, which then allows the sprin-
kler to activate and flow water.
Design
Criteria
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must only be
installed in accordance with the
applicable UL and C-UL Listing or
FM Approval requirements as indi-
cated below. Only Style 30 or 40
Recessed Escutcheons are to be used
for recessed installation, as applica-
ble. See Tables A, B, and C, for more
information.
UL and C-UL
Listing Requirements
1. Series EC-11 and EC-14 Extended
Coverage Sprinklers may be used
for the coverage areas shown in
Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all sprinklers in the
design area.
2. Series EC-11 and EC-14 Extended
Coverage Sprinklers are permitted
to be used with unobstructed or
non-combustible obstructed ceil-
ing construction as defined and
permitted by NFPA 13; for example:
• Unobstructed, combustible or
noncombustible, ceiling con-
struction with a deflector to
ceiling/roof deck distance of
1 to 12 in. (25 to 300 mm).
• Obstructed, non-combusti-
ble, ceiling construction with a
deflector location below struc-
tural members of 1 to 6 in.
(25 to 150 mm) and a maximum
deflector to ceiling/roof deck dis-
tance of 22 in. (550 mm).
3. Series EC-11 and EC-14 Extended
Coverage Sprinklers, specifically
tested and listed for non-combus-
tible obstructed construction, are
permitted to be used within truss-
es or bar joists having non-com-
bustible web members greater
than 1 in. (25,4 mm) when apply-
ing the 4 times obstruction crite-
ria rule defined under "Obstruc-
tions to Sprinkler Discharge Pattern
Development".
4. To prevent cold soldering, the
minimum allowable spacing be-
tween Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers is 8 ft
(2,4 m) for upright sprinklers and
9 ft (2,7 m) for pendent sprinklers.
5. Series EC-11 and EC-14 Extended
Coverage Sprinklers are to be in-
stalled in accordance with all oth-
er requirements of NFPA 13 for
extended coverage upright and
pendent sprinklers; For exam-
ple, obstructions to sprinkler dis-
charge, obstructions to sprinkler
pattern development, obstructions
to prevent sprinkler discharge from
reaching hazard and clearance to
storage.
TFP220
Page 3 of 8
Hazard
Type
Temperature
Bulb
Liquid
Sprinkler Finish (See Note 5)
Natural
Brass
Chrome
Plated
polyester*
Lead
Coated
135°F(57°C)
Orange
Upright
K=11.2 (TY5137)
1, 2, 3--, 4
° ° 155F 68C
( )
Red
175°F (79°C)
Yellow
Light
Pendent
Table B describes
UL and C-UL
K=11.2 (TY5237)
K=14.0 (TY6237)
200°F (93°C)
Green
1, 2, 4
1, 2, 4
286°F (141°C)
Blue
Sensitivity Rating
Table C describes
FM
Sensitivity Rating
Recessed Pendent
K=11.2 (TY5237)
K=14.0 (TY6237)
135°F (57°C)
Orange
1, 2, 3, 4
N/A
155°F (68°C)
Red
175°F (79°C)
Yellow
With Style
Escutcheonn
1, 2, 4
200°F (93°C)
Green
286°F (141°C)
Blue
Ordinary
Table B describes
Upright
K=11.2 (TY5137)
K=14.0 (TY6137)
Pendent
K=11.2 (TY5237)
135°F (57°C)
Orange
1, 2, 3, 4
1, 2, 3, 4
155°F (68°C)
Red
175°F (79°C)
Yellow
1, 2, 4
200°F (93°C)
Green
UL and C-UL
Sensitivity Rating
K=14.0 (TY6237)
286°F (141°C)
Blue
Table C describes
Recessed Pendent
135°F(57°C)
Orange
155°F (68°C)
Red
FM
Sensitivity Rating
K=11.2 (TY5237)
K=14.0 (TY6237)
With Style 30 or 40
1, 2, 4
N/A
175°F (79°C)
Yellow
Escutcheon
200°F(93°C)
Green
NOTES
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL)
3. Approved by Factory Mutual Research Corporation (FM)
4. Approved by the City of New York under MEA 177-03-E
5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers
N/A = Not Available
* Frame and Deflector only
** Pendent only
TABLE A
LABORATORY LISTINGS AND APPROVALS
Light Hazard
Ordinary Hazard
Area
Style
ftxft
135°F
155°F
175°F
200°F
286°F
135°F
155°F
175°F
200°F
286°F
(57°C)
(68°C)
(79°C)
(93°C)
(141°C)
(57°C)
(68°C)
(79°C)
(93°C)
(141°C)
Upright or Pendent
-
-
-
-
OR
OR
OR
OR
OR
14 x 14
Style 30 Recessed
-
-
-
-
OR
OR
OR
OR
OR
Style 40 Recessed
-
-
-
-
OR
OR
OR
OR
OR
Upright or Pendent
OR'
QW
QR'
OR`
OR'
SR
SR
SR
SR
SR
16 x 16
Style 30 Recessed
QW
QW
QR'
OR'
OR'
SR
SR
SR
SR
SR
Style 40 Recessed
N/A
N/A
N/A
N/A
N/A
SR
SR
SR
SR
SR
Upright or Pendent
QW
QW
QR"
QR"
QR"
SR
SR
SR
SR
SR
18 x 18
Style 30 Recessed
QW
QR"
QR"
QW
QR'
SR
SR
SR
SR
SR
Style 40 Recessed
N/A
N/A
N/A
N/A
N/A
SR
SR
SR
SR
SR
Upright or Pendent
QR"
QR'
QW
SR`
SR*
SR
SR
SR
SR
SR
20 x 20
Style 30 Recessed
OR'
QR'
QR'
SR*
SR`
SR
SR
SR
SR
SR
Style 40 Recessed
N/A
N/A
N/A
N/A
N/A
SR
SR
SR
SR
SR
NOTES
• QR = Quick Response
• SR = Standard Response
• N/A = Not Applicable
' Does not apply to Upright K=14.0
TABLE B
SENSITIVITY RATING
FOR UL AND C-UL LISTING OF
SERIES
EC-11 OR
EC-14
SPRINKLERS
(SEE TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
TFP220
Page 4 of 8
HC-1
Linear Spacing
Area Spacing
ft
ft
Ceiling Height
ft
Ceiling Type
K-factor
Style
Response
Min
Max
Min
Max
Noncombustible Unobstructed,
11.2 EC
Pendent or
10
20
100
400
Up to 30
Noncombustible Obstructed, or
14.0 EC
Upright
Combustible Unobstructed
Noncombustible Unobstructed,
11.2 EC
Pendent
10
20
100
400
Up to 30
Noncombustible Obstructed, or
14.0 EC
Recessed
Combustible Unobstructed
Style 30
10
20
100
400
Up to 30
Combustible Obstructed
11.2 EC
14.0 EC
Pendent or
Upright
Quick
11.2 EC
Pendent
10
20
100
400
Up to 30
Combustible Obstructed
14.0 EC
Recessed
Style 30
10
20
100
400
Over 30 and
up to 45
Noncombustible Unobstructed
11.2 EC
14.0 EC
Upright
HC-2
Linear Spacing
Area Spacing
ft
ft
Ceiling Height
ft
Ceiling Type
K-factor
Style
Response
Min
Max
Min
Max
10
20
100
400
Up to 30
Noncombustible Unobstructed,
11.2 EC
Pendent or
Upright
Quick
10
20
100
400
Up to 30
14.0 EC
Pendent or
Upright
Combustible Unobstructed
10
16
100
256
Over 30 and
11.2 EC 14.0
Upright
up to 45
EC
HC-3
Linear Spacing
Area Spacing
ft
ft
Ceiling Height
ft
Ceiling Type
K-Factor
Style
Response
Min
Max
Min
Max
10
16
100
256
Up to 30
11.2 EC
Upright
10
20
100
400
Up to 30
14.0 EC
Pendent or
Upright
Noncombustible Unobstructed,
Combustible Unobstructed
Quick
10
16
100
256
Over 30 and
11.2 EC,
Upright
up to 45
14.0 EC
NOTES
• The design for K 11.2 EC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less
than 12 psi (0,8 bar);
similarly the design for K 14.0
EC (K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi (1,2 bar).
• For flow criteria, refer to FM Loss Prevention Data Sheet 3-26.
• Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations.
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR
EC-14 SPRINKLERS
UL and C-UL Specific Application
depth of the concrete tees must not
3. When the sprinkler deflectors are
Listing Requirements for
exceed 30 in. (762 mm). The maxi-
located higher than a horizontal
Installation under Concrete Tees
mum permitted concrete tee length
plane 1 in. (25,4 mm) beneath the
Series EC-11 and EC-14 Extended Cov-
is 32 ft (9,8 m). However, where the
bottom of the concrete tee stems,
erage Upright and Pendent Sprinklers
concrete tee length exceeds 32 ft
the obstruction to sprinkler dis-
(TY5137, TY5237, TY6137 and TY6237)
(9,8 m), non-combustible baffles,
charge criteria requirements of
have a UL and C-UL Specific Applica-
equal in height to the depth of the
NFPA 13 for extended coverage
tion Listing for use under concrete tees
tees, can be installed so that the
upright and pendent sprinklers
when installed as follows:
space between the tees does not
applies.
1. Stems of the concrete tee con-
exceed 32 ft (9,8 m) in length.
struction must be spaced at less
2. The sprinkler deflectors are to be
than 7.5 ft (2,3 m) on center but
located in a horizontal plane at or
more than 3 ft (0,9 m) on center. The
above 1 in. (25,4 mm) below the
bottom of the concrete tee stems.
TFP220
Page 5 of 8
Description
Area
ft x ft
Light Hazard
0.10 GPM/ft2
Group I
Ordinary Hazard
0.15 GPM/ft2
Group II
Ordinary Hazard
0.20 GPM/ft2
GPM
PSI
GPM
PSI
GPM
PSI
14 x 14
30
7.2
30
7.2
39
12.1
16 x 16
30
7.2
39
12.1
51
20.7
TY5137
18 x 18
33
8.7
49
19.1
65
33.7
(K=11.2) Upright
20 x 20
40
12.8
60
28.7
80
51.0
14 x 14
30
7.2
30
7.2
39
12.1
16 x 16
30
7.2
39
12.1
51
20.7
TY5237
18 x 18
33
8.7
49
19.1
65
33.7
(K=11.2) Pendent
20 x 20
40
12.8
60
28.7
80
51.0
14 x 14
N/A
N/A
39
7.8
51
13.3
16 x 16
N/A
N/A
39
7.8
51
13.3
TY6137
18 x 18
N/A
N/A
49
12.3
65
21.6
(K=14.0) Upright
20 x 20
N/A
N/A
60
18.4
80
32.7
14 x 14
37
7.0
39
7.8
51
13.3
TY6237
16 x 16
37
7.0
39
7.8
51
13.3
18 x 18
37
7.0
49
12.3
65
21.6
(K=14.0) Pendent
20 x 20
40
8.2
60
18.4
80
32.7
NOTES
• 1 ft = 0,3048 m
• 1 1t2 = 0,093 m2
• 1 GPM = 3,785 LPM
• 1 psi = 0,06895 bar
• 1 GPM/ft2= 40,74 mm/min
TABLE D
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS
FM Approval Requirements
Series EC-11 and EC-14 Extended
Coverage Upright and Pendent Sprin-
klers are to be installed in accor-
dance with the applicable FM Loss
Prevention Data Sheet for limited use
in buildings of specific roof construc-
tion and for the protection of certain
specific ordinary hazard (non -storage
and/or non-flammable or combustible
liquid) occupancies. Information pro-
vided in the FM Loss Prevention Data
Sheets relates to, but is not limited to,
hydraulic design, ceiling slope, and
obstructions, minimum and maximum
allowable spacing, and deflector -to -
ceiling distance.
These criteria may differ from UL
and/or NFPA criteria. Therefore, the
designer should review and become
familiar with FM requirements before
proceeding with design.
Installation
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must be installed
in accordance with this section.
General Instructions
Do not install any bulb -type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to 3/32 in.
(2,4 mm) for the 286°F (141 °C) tempera-
ture ratings.
A leak -tight 3/4 in. NPT sprinkler joint
should be obtained by applying a min-
imum -to -maximum torque of 10 to
20 lb-ft (13,4 to 26,8 N•m). Higher levels
of torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under or over -tightening
the Sprinkler. Re -adjust the position of
the sprinkler fitting to suit.
Step 1. Install the sprinkler with the
deflector parallel to the mounting
surface. Install pendent sprinklers in
the pendent position. Install upright
sprinklers in the upright position.
Step 2. After installing the Style 30, 40,
or 60 mounting plate, or other applica-
ble escutcheon, over the sprinkler pipe
threads and with pipe -thread sealant
applied to the pipe threads, hand -
tighten the sprinkler into the sprinkler
fitting.
Step 3. For upright or pendent sprin-
klers, wrench -tighten using only the
W-Type 3 (End A) Sprinkler Wrench.
For the pendent sprinkler installed
with Style 30, 40, or 60 Escutcheon,
wrench -tighten the sprinkler using only
the W-Type 22 Sprinkler Wrench.
Apply the wrench recess of the appli-
cable sprinkler wrench, Figure 5 and 6,
to the sprinkler wrench flats, Figure 1.
TFP220
Page 6 of 8
2-7/8" DIA. _
(73,0 mm) 1/2" 12,7 mm
(12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
SPRINKLER MOUNTING
FITTING � PLATE
MOUNTING
SURFACE 1/8"
(3,2 mm)
CLOSURE TY5237 or 1-3/8" (34,9 mm)
TY6237 1-1/8" (28,6 mm)
FIGURE 2
SERIES EC-11 AND EC-14 RECESSED
PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 112IN. TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
SPRINKLER MOUNTING
FITTING PLATE
�wd
V77 7/
MOUNTING
SURFACE 1/8"
(3,2 mm)
CLOSURE TY5237 or 1-3/8" (34,9 mm)
TY6237 7/8" (22,2 mm)
FIGURE 3
SERIES EC-11 AND EC-14 RECESSED
PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 314 IN. TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
2-7/8" DIA. _
(73,0 mm)
INTERNAL
2-1/4" DIA. DIMENSIONS OF
(57,2 mm) STYLE 60 ESCUTCHEON
ACCOMMODATE
CLASS 150 MALLEABLE
FACE OF
IRON REDUCING
SPRINKLER FITTING:
SPRINKLER FITTING
3/8" (9,5 mm) ABOVE
TO 1/8" (3,2 mm) BELOW
MOUNTING
MOUNTING SURFACE
1/8" SURFACE
V
(3,2 mm)
ESCUTCHEON PLATE
SEATING SURFACE:
1/4" (6,4 mm) ABOVE
CLOSURE
TO 1/2" (12,7 mm) BELOW
2-5/16" (58,7 mm)
3/4" NPT
MOUNTING SURFACE;
MOUNTING 1-13/16" (46,0 mm)
3/4" (19,1 mm) TOTAL
PLATE
ADJUSTMENT
FIGURE 4
SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY
WITH 314 IN. TOTAL ADJUSTMENT
STYLE 60 TWO-PIECE FLUSH ESCUTCHEON
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
/ WRENCH
RECESS
(END "A")
FIGURE 5
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS
p �0111111O
WRENCH
HEX
FIGURE 6
W-TYPE 22 RECESSED
SPRINKLER WRENCH
TFP220
Page 7 of 8
P/N 51 -
XXX -X -XXX
SIN
SPRINKLER
TEMPERATURE
FINISHI
RATING
893
11.2K Pendent TY5237
1 NATURAL BRASS
135
135°F (57°C)
894
11.2K Upright TY5137
SIGNAL WHITE
155
155°F (68°C)
4 (RAL9003)
POLYESTER
895
14.OK Pendent TY6237
JET BLACK (RAL9005)
175
175°F (79°C)
5 POLYESTER
896
14.OK Upright TY6137
200
200°F (93°C)
7 LEAD COATED
286
286°F (141°C)
9 CHROME -PLATED
000
OPEN2
NOTES:
1. Escutcheon ordered separately.
2. OPEN
indicates the sprinkler assembly without
glass bulb, button, and sealing assembly.
TABLE E
SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Care and
Maintenance
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section, for more information.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this doc-
ument, as well as with the applicable
standards recognized by the Approval
agency, such as NFPA 25, in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series EC-11 or EC-14
(specify) Sprinkler, SIN (specify),
(specify) K-factor, Pendent or Upright
(specify) Extended Coverage, (specify)
temperature rating, (specify) finish, P/N
(from Table E)
Recessed Escutcheon, Two -Piece
Specify: Style (30 or 40) Two -Piece
Recessed Escutcheon with (specify)
finish, P/N (specify*)
*Refer to Technical Data Sheet TFP770
Flush Escutcheon, Two -Piece
Specify: Style 60 Two -Piece Flush
Escutcheon with (specify) finish, P/N
(specify*")
**Refer to Technical Data Sheet TFP778
Sprinkler Wrenches
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprinkler
Wrench, P/N 56-665-7-001
TFP220
Page 8of8