APPROVED FIR2023-0085+Fire_Alarm_Plan+8.25.2023_10.56.16_AM+3747592
VICINITY MAP rPAf ABBREVIATIONS USED IN THE DRAWING AIM ADDRESSABLE INPUT MODULE cd CANDELA D DETECTOR EOL END OF LINE FACP FIRE ALARM CONTROL PANEL IBC INTERNATIONAL BUILDING CODE IFC INTERNATIONAL FIRE CODE L1 SLC LOOP 1 M MODULE N1 NAC #1 N2 NAC #2 Approved DFM Chris Burt South County Fire Date: 09/05/2023 09-05-2023 PLAN REVIEW APPROVED WITH CONDITIONS: INSTALL AN ANNUNCIATOR NEAR ON THE INTERIOR AT MAIN ENTRANCE. 2. KNOX BOX REQUIRED AT MAIN ENTRANCE. DFM BURT SYSTEM INPUTS NAC NOTIFICATION APPLIANCE CIRCUIT NEC NATIONAL ELECTRICAL CODE NFPA NATIONAL FIRE PROTECTION ASSOCIATION ntc NOT TO SCALE RPS REMOTE POWER SUPPLY SLC SIGNAL LINE CIRCUIT WP WEATHERPROOF ZN ZONE BF BARRIER FREE (ADA) SYSTEM OUTPUTS Required Fire Safety Control System Actions y Central Station FACP Annunciation c O� c �m r w epr co y y z u CO wo Q .y O .Q JQ or co C ZrO 05 -qj io y , F��fc � Jvii m�3 .v Q m Q FF y y� p . Q �� VO L �O , �` 0 z O o 6 0 r x6o z 3 c Q Q Q w w w W 4 v 10 10 a`° a`° c Q u u u aim aim aim aim u u :� �QQ QQo A B C D E F G H I I J 1 Manual Fire Alarm 1 W2 Smoke Detector 2 Q3 Wet Waterflow 3 4 Unused 4 5 Tamper 5 a6 Backflow 6 y 7 Unused 7 8 Unused 8 9 Fire Alarm AC Power Failure 9 LU 10 Fire Alarm System Low Battery 10 11 Open Circuit 11 O o: 12 Ground Fault 12 ~ 13 NAC / AUDIO / SLC Circuit Short 13 14 Transmitter Trouble 14 Puget Sound Aon �0000' ©QQ©QO TYPICAL WIRING DETAIL Fa n n(i 22811 100th Ave W, Edmonds. WA 98020 Bothell 7*_ c_ Kirkland_ r% Ap�10��C� D A A D D FL-JRE A. An- L-M LK A M -9-1 PROWE _j -M SYMBOL QTY MANUFACTURER PART NO DESCRIPTION NEW HEAD -END EQUIPMENT FACP 1 GAMEWELL GWF-7075 ANALOG ADDRESSSABLE FIRE ALARM CONTROL PANEL AEs 1 AES 7707-88-ULP WIRELESS COMMERCIAL FIRE ALARM COMMUNICATOR DOC 1 GAMEWELL GW-FAD FIRE ALARM STORAGE CABINET, RED NEW INITIATION DEVICES S 0 1 GAMEWELL ASD PL3 ADDRESSABLE, PHOTO, DET. P 1 GAMEWELL B300-6 BASE ADDRESSABLE, DETECTOR BASE 1 GAMEWELL MS-7ASF ADDRESSABLE PULL STATION AIM 2 2 GAMEWELL AMM-21F ADDRESSABLE DUAL MONITOR MODULE NEW OCCUPANT NOTIFICATION DEVICES NAc 1 ALTRONIX AL802ULADA 8-AMP, 24-VOLT POWER SUPPLY nH 7 SYSTEM SENSOR PC2WL HORN/STROBE, CEILING, WHITE �� i0� 9 SYSTEM SENSOR SCWL STROBE, CEILING, WHITE LF 2 SYSTEM SENSOR HWL-LF L-SERIES , LOW FREQU. HORN, WALL, WHITE 1 SYSTEM SENSOR HWL HORN, WHITE WP 1 SYSTEM SENSOR P2RK HORN/STROBE,WP,WALL , RED ADDITIONAL FIRE ALARM EQUIPMENT 2 DURACELL 12VDC, 8AH BATTERY BATTERIES FOR FIRE ALARM CONTROL PANEL 2 DURACELL 12VDC, 8AH BATTERY BATTERIES FOR FIRE ALARM RPS PANEL 1 DURACELL 12VDC, 12AH BATTERY BATTERY FOR WIRELESS COMMUNICATOR ��.,, L� 1 BY OTHERS BY OTHERS ALARM BELL, 24VDC, RED g1 BY OTHERS BY OTHERS CONTACT DEVICE 3 BY OTHERS BY OTHERS TAMPER SWITCH SITE PLAN - nts 227th PLACE SW > 0 0 FACP in SPRINKLER DOGHOUSE OUTDOOR HORN/STROBE I DEVICE INSTALLATION REQUIREMENTS I 4" MIN 12" MAX A/C SUPPLY OR RETURN DIFFUSER PENDANT MOUNTED - CEILING -MOUNTED ^rlll^In AUDIBLE/VISUAL 4" MINI HEAT DETECTOR APPLIANCES 0 6" MIN. � 3 6 " MIN. I-� AUDIBLE/VISUAL AUDIBLE -ONLY REMOTE ALARM CEILING MOUNTEDJ/CEILING MOUNTED NEVER AND/OR VISUAL APPLIANCES INDICATOR SMOKE/HEAT AUDIBLE/VISUAL HERE ONLY APPLIANCE O❑ ❑� DETECTOR APPLIANCES WALL -MOUNTED HEAT DETECTOR DOOR WIDTH LESS 3'�-j MAGNETIC 30' MAX FSA o DOOR Al FACP SYSTEM HOLDER RECORDSo 82°-96" 82-96" MIN. 10' MAX DOCUMENTS TO LOWEST WHERE CEILING AFF PART OF LENS HEIGHT ALLOWS E= 5' MAX. 66" TO 66" TO 66" TO FROM EXIT TOP OF TOP OF TOP OF FSA FACP CABINET MANUAL PULL 42"-48" STATION 30' MAX AFF NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST POINT OF DETECTOR 12" MAX WALL -MOUNTED SMOKE DETECTOR SIDE WALL NFINISHED WALL SHEET # SHEET DESCRIPTION FA 0.0 FIRE ALARM INSTALLATION DETAILS FA 1.0 FIRE ALARM PLAN - FIRST AND SECOND FLOORS, ENLARGED SPRINKLER ROOM FA 2.0 SINGLE LINE RISER DIAGRAM, BATTERY AND POINT TO POINT CALCULATIONS PROJECT DETAILS SCOPE OF WORK: A FIRE ALARM TENANT IMPROVEMENT ON AN EXISTING 2-STORY BUILDING THAT HAS A SPRINKLER SYSTEM. SCOPE OF WORK INCLUDES: THE INSTALLATION OF (1) ADDRESSABLE FIRE CONTROL PANEL, (1) AES WIRELESS COMMUNICATOR, (1) REMOTE POWER SUPPLY, (1) BATCH OF SPRINKLER MONITORING, (1) DOCUMENT ENCLOSURE, (1) ADDRESSABLE SMOKE DETECTORS, (1) ADDRESSABLE MANUAL PULL STATION, AND (20) OCCUPANT NOTIFICATION DEVICES. NO ADDITIONAL WORK IS INCLUDED IN THIS SCOPE. OWNER EDWAY TAPHOUSE 22811 100TH AVE W EDMONDS, WA 98020 CONTACT : JILL LIKES PHONE : 206.251.3274 EMAIL JILLLIKES@HOTMAIL.COM )NTACT INFO FIRE ALARM CONTRACTOR FIRE PROTECTION, INC 17410 ASH WAY, SUITE 8 LYNNWOOD, WA 98037 CONTACT : DAVID MOW PHONE : 425.290.9600 EMAIL DAVID@FPISEATTLE.COM CODE INFO AUTHORITY HAVING JURISDICTION : CITY OF EDMONDS BUILDING CODE : INTERNATIONAL BUILDING CODE, 2018 EDITION FIRE CODE : INTERNATIONAL FIRE CODE, 2018 EDITION MUNICIPAL CODE : CITY OF EDMONDS BUILDING USE AND OCCUPANCY : A-2, FULLY SPRINKLED STANDARDS: NFPA-70 (NEC), NFPA-72, IBC, IFC, & WAC 51-50 CLASSIFICATION OF SUPERVISING STATION : REMOTE SUPERVISING STATION NAME OF SUPERVISING STATION : STANLEY SECURITY, INC TAX PARCEL NUMBER : 27033600107900 1 • THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS. 2. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. 3. CABLE ROUTING SHOWN ON DRAWINGS IS FOR INTENT. EXACT ROUTING TO BE COORDINATED WITH OTHER TRADES IN THE FIELD. SEE SPECIFICATIONS AND DRAWING NOTES FOR ACCEPTABLE INSTALLATION METHODS. SEE WIRING LEGEND FOR CABLE TYPES AND SIZES. 4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. 5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE -RATED CONSTRUCTION. 6. POWER -LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED IN THE CABINET. ALL POWER -LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NON -POWER LIMITED CIRCUIT WIRING. FURTHERMORE, ALL POWER -LIMITED AND NON -POWER LIMITED CIRCUIT WIRING MUST ENTER AND EXIT THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. 7. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT MANUFACTURER FOR THE INTENDED PURPOSE. CABLES USED IN VERTICAL RUNS SHALL BE TYPE FPLR. CABLE SPLICES OR TERMINATIONS SHALL BE MADE IN LISTED FITTINGS, BOXES, ENCLOSURES, FIRE ALARM DEVICES, OR UTILIZATION EQUIPMENT. WHERE INSTALLED EXPOSED, CABLES SHALL BE ADEQUATELY SUPPORTED AND INSTALLED IN SUCH A WAY THAT PROTECTION AGAINST PHYSICAL DAMAGE IS AFFORDED BY BUILDING CONSTRUCTION. WHERE EXPOSED CABLE IS LOCATED WITHIN 7 FT OF THE FLOOR, IT SHALL BE RUN IN RACEWAY. 8' ALL CEILINGS IN BUSINESS SPACES WILL BE OPEN TO STRUCTURE AND DEVICES WILL BE MOUNTED ON THE BEAMS. 9' ALL CEILINGS IN TENANT SPACES WILL BE HARD -LID AND DEVICES WILL BE MOUNTED PER A NORMAL INSTALL. 10. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION CLEAN-UP IS COMPLETED 100%. 11. WHEN MORE THAN TWO NOTIFICATION APPLIANCES ARE VISIBLE AT THE SAME TIME WHETHER THEY ARE IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW, THE FLASH OF THOSE STROBES SHALL BE SYNCHRONIZED (NFPA-72, SECTION 18.5.4.3.2(3) & (4). 12. THE MEANS OF SIGNAL TRANSMISSION TO THE REMOTE SUPERVISING STATION SHALL BE VIA THE FACP'S ONBOARD DACT AND A UL LISTED AES WIRELESS RADIO COMMUNICATOR. 13. ALL SYSTEMS AND DEVICES SHALL BE INSTALLED AND TESTED PER THE MANUFACTURES LISTING AND THE AUTHORITY HAVING JURISDICTION (NFPA72 10.14.2.1). ALL INITIATING DEVICES AND DEVICES CONTAINING EOL'S SHALL HAVE A PHYSICAL LABEL IDENTIFYING THE DEVICE'S ADDRESS / END OF LINE RESISTOR. 14. INSTRUCTIONS FOR THE OPERATING, TESTING AND MAINTENANCE OF THE SYSTEM, ALONG WITH RECORD DRAWINGS OTHERWISE REFERRED TO AS ("AS -BUILT") AND EQUIPMENT SPECIFICATIONS SHALL BE KEPT IN THE FIRE ALARM DOCUMENT CABINET NEXT TO THE FACP (NFPA-72 10.18.2.3). 15. PRIOR TO CALLING FOR INSPECTION, THE INSTALLER SHALL PROVIDE DOCUMENTATION TO THE LOCAL AHJ STATING THAT THE SYSTEM HAS BEEN INSTALLED, TESTED, EVALUATED AND CONFIRMED TO BE IN ACCORDANCE WITH ALL GOVERNING CODES AND THE APPROVED PLANS. THE FIRE ALARM SYSTEM INSTALLER SHALL COMPLETE AN NFPA-72 RECORD OF COMPLETION (NFPA-72 10.18.2.1.1). THE COMPLETED RECORD OF COMPLETION ALONG WITH THE AES RADIO TABLE REPORT SHALL BE PROVIDED TO THE AHJ INSPECTOR PRIOR TO REQUESTING A FIRE FINAL INSPECTION (NFPA-72 10.18.2.1.2.4). FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM ROY L CATS `Q�QROTECT��2. o rn W I r) Gb NFPA' �^ �J Y CFPS #1473 bo cn — r� � d LL 0 u 2LU z LU > U Q�o`n, w Y w rn U �en Z. � U = z U) j H V J a J 0 a 0 o Z>.W_j �mu_U)� O nwwQ J W H * d 0 Ywwo6 W Q 3Wc)_ja 0 REVISION RECORD DATE / DESCRIPTION RECEIVED Aug 28 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT I�ICY��Y.Ii��1:�7 DATE: 08/18/2023 PROJECT NAME LU 3:CD N CD =) W 00 =aQ ~ CD � ��� a_z r 00 0 W N W SHEET TITLE I FIRE ALARM PROJECT DETAILS 1 SHEET NUMBER I FINISHED FLOOR FA OmO rAAF FIRE ALARM DEVICE IDENTIFICATION (SLC) ADDRESSABLE DEVICES NOTIFICATION DEVICES SLC LOOP # PANEL DEVICE ADDRESS CIRCUIT # SLC1:D001 O DEVICE # RH) FACP:NAC1:002 15cd CANDELA CONDUIT, CABLE AND WIRE LEGEND Mr LINE TYPE LABEL CABLE TYPE AWG RESIST. ( ()/M ft) DESCRIPTION A 14/2 FPLR 14 3.07 NAC NOTIFICATION APPLIANCE CIRCUIT FOR BUSINESS SPACE AA 14/4 FPLR 14 3.07 NAC NOTIFICATION APPLIANCE CIRCUIT FOR TENANT SPACE U 18/4 FPLR 18 7.77 SLC SIGNALING LINE CIRCUIT — Z 18/2 FPLR 18 7.77 IDC ANALOG INITIATING DEVICE CIRCUIT All CONDUCTORS SHALL BE INSTALLED IN RACEWAYS SUITABLE FOR THE INSTALLATION CONDITIONS, PER THE REQUIREMENTS OF IBC, IFC, NPFA-72 & NFPA-70 (NEC) # INSTALLATION KEY NOTES 10 A DEDICATED 120VAC POWER CIRCUIT IS REQUIRED FOR THE EXISTING FIRE ALARM PANEL. MAKE SURE OF LOCATION OF PANEL. ® A DEDICATED 120VAC POWER CIRCUIT IS REQUIRED FOR THE NEW REMOTE POWER SUPPLY, CAN SHARE FACP CIRCUIT. MAKE SURE OF LOCATION OF PANEL. ® A DEDICATED 120VAC POWER OUTLET IS REQUIRED FOR THE EXISTING AES RADIO, CAN SHARE FACP CIRCUIT. MAKE SURE OF LOCATION OF PANEL. ® A NEW DOCUMENT CAN. ® INSTALL OUTDOOR DEVICE AT ACCEPTABLE HEIGHT TO BE SEEN BY APPROACHING EMERGENCY VEHICLES. © SPRINKLER BELL REQUIRED FOR SPRINKLER SYSTEM, AND TO RING ON WATERFLOW ALARM. 0 FIELD VERIFY SPRINKLER DEVICE LOCATIONS. o- 0 T O O G \ L_ I -IVI U U `T T ENLARGED FIRE SPRINKLER ROOM O O N FIRE ALARM FLOOR PLAN -FIRST FLOOR � SCALE : 1 /8" = 1' 5' 1020' nc nD nE nF N FIRE ALARM FLOOR PLAN -SECOND FLOOR � SCALE : 1/8" = 1' 5' 10 20' FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM ROY L CATS `Q�QROTECT��2. o rm Gb NFPA �^ CFPS #1473 r � DO O cn #k nl .0 o J w z U W Q� con) w Y w rn � U a z U = amp j H U J a J p o a z>- Lu LL - mw* o �oL`(n>- o nwwQ-1 2 �wL)a m Ywwo6 W Q 3WcnJa o REVISION RECORD DATE / DESCRIPTION RECEIVED Aug 28 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FIR2023-085 DATE: 08/18/2023 PROJECT NAME LU �CD N CD W =aQ �ocn a Z � 00 004 W N W SHEET TITLE FIRE ALARM FLOOR PLAN BASEMENT/ FIRST & SECOND FLOORS SHEET NUMBER FA 1.0 r IF FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM MAIN LEVEL N2-005 EOL N2.004 N2.003 75cd 15cd 15cd N2.002 N2-001 15cd 30cd N3-004 EOL N3.003 N3.002 N3-001 30cd N1 -011 EOL N1 -010 N1 -009 N1 -008 N1 -007 N1 -006 N1 -005 N1 -004 N1 -003 N1 -002 N1 -001 110cd 75cd 15cd 15cd 15cd 15cd 75cd 15cd 15cd 15cd 15cd WP NAC EXPANDER POWER SUPPLY H DEDICATED 120V G 20 AMP CIRCUIT FIRE ALARM CONTROL PANEL 0 H DEDICATED 120V H G 20 AMP CIRCUIT AES Z02 Z02 Z01 Z01 2Z P L1 -M001 L1 -DO01 L1 -M002 L1 -M004 L1 -M 003 L1 -M 005 WATERFLOW BACKFLOW TAMPER BACKFLOW MAIN LEVEL uv N1 -001 EOL LOWERLOWER LEVEL LEVEL SINGLE LINE RISER DIAGRAM BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) PANEL COMPONENTS CITY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL 1 GWF-7075 Main Board Intelligent Fire Alarm Control Panel 0 0 0 0 CIRCUIT SYMBOL CITY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) AIM 2 2 AMM-21F Addressable Dual Monitor Module 0.0007 0.0014 0.0007 0.0014 L1 OP 1 ASD-PL3 / B300-6 BASE Addressable, Photo, Det. 0.0003 0.0003 0.0003 0.0003 ❑F 1 MS-7ASF Addressable Pull Station 0.0003 0.0003 0.0003 0.0003 N1 1 SSM24-8 Alarm Bell 8" 24VDC, red 0 0 0.0535 0.0535 N2 FN A C1 1 AL802ULADA 8-Amp, 24-Volt Power Supply 0 0 1.682 1.682 TOTAL STANDBY (A) 0.002 TOTAL ALARM (A) 1.7375 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SECONDARY STANDBY LOAD (A) 0.002 24 1 0.05 SECONDARY ALARM LOAD (A) 1.7375 0.08 1 0.14 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 0.19 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 0.23 PROVIDE (2) 12V 7AH BATTERIES BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) PANEL COMPONENTS QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL 1 AL802ULADA Main Board Fire Alarm Power Supply Board 0 0 0.069 0.069 CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) KI WP 1 P2RK Horn/Strobe,WP,Wall , Red 110cd 0 0 0.221 0.221 HC 2 PC2WL Horn/Strobe, Ceiling, White 15cd 0 0 0.071 0.142 N1 nH 2 PC2WL Horn/Strobe, Ceiling, White 75cd 0 0 0.143 0.286 A, 6 SCWL Strobe, Ceiling, White 15cd 0 0 0.041 0.246 H( 1 PC2WL Horn/Strobe, Ceiling, White 15cd 0 0 0.071 0.071 N2 HC 1 PC2WL Horn/Strobe, Ceiling, White 75cd 0 0 0.143 0.143 A 2 SCWL Strobe, Ceiling, White 15cd 0 0 0.041 0.082 '10" 1 SCWL Strobe, Ceiling, White 30cd 0 0 0.063 0.063 1 HWL Horn, White 0 0 0.047 0.047 N3 LF 2 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0 0 0.111 0.222 rH) 1 PC2WL Horn/Strobe, Ceiling, White 30cd 0 0 0.09 0.09 TOTAL STANDBY (A) 0 TOTAL ALARM (A) 1.682 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SECONDARY STANDBY LOAD (A) 0 24 1 0 SECONDARY ALARM LOAD (A) 1.682 0.08 1 0.14 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 0.14 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 0.17 PROVIDE (2) 12V 7AH BATTERIES BATTERY CALCULATIONS N1 POINT-TO-POINT REPORT -NUIL .& CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0 Min. Operational Voltage: 16 End Of Line Voltage: 20.4 Max. Circuit Current (A): 2.5 Voltage Drop Percent: 0.02 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.0535 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 14 Spare Current (A): 2.4465 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.086444 Spare Current (A) Percent: 97.86 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From m Previous () Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent Nl-001 EOL SSM24-8 Alarm Bell 8" 24VDC, red 0.0535 0.0535 14 0.086444 0 20.4 0 0.02 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (0/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) N2 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.01 Min. Operational Voltage: 16 End Of Line Voltage: 20.39 Max. Circuit Current (A): 2.5 Voltage Drop Percent: 0.06 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 1.682 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 1 Spare Current (A): 0.818 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.006843 Spare Current (A) Percent: 32.72 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent N2.001 EOL AL802ULADA 8-Amp, 24-Volt Power Supply 1.682 1.682 1 0.006843 1 0.01 20.39 1 0.01 0.06 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (0/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) AV r N1 POINT-TO-POINT REPORT ji CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.39 Max. Voltage Drop: 1.34 Min. Operational Voltage: 16 End Of Line Voltage: 19.05 Max. Circuit Current (A): 3 Voltage Drop Percent: 6.55 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.895 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 311 Spare Current (A): 2.105 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.912049 Spare Current (A) Percent: 70.17 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (a) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent Nl-001 SCWL Strobe, Ceiling, White 15cd 0.041 0.895 114 0.698287 0.62 19.76 0.62 3.07 % N1.002 SCWL Strobe, Ceiling, White 15cd 0.041 0.854 18 0.11231 0.1 19.67 0.72 3.54 % N1.003 PC2WL Horn/Strobe, Ceiling, White 15cd 0.071 0.813 14 0.083186 0.07 19.6 0.79 3.87 % N1.004 SCWL Strobe, Ceiling, White 15cd 0.041 0.742 26 0.162161 0.12 19.48 0.91 4.46 % N1.005 PC2WL Horn/Strobe, Ceiling, White 75cd 0.143 0.701 41 0.25134 0.18 19.3 1.09 5.32 % N1.006 PC2WL Horn/Strobe, Ceiling, White 15cd 0.071 0.558 23 0.141281 0.08 19.22 1.16 5.71 % N1.007 SCWL Strobe, Ceiling, White 15cd 0.041 0.487 14 0.086818 0.04 19.18 1.21 5.92 % N1.008 SCWL Strobe, Ceiling, White 15cd 0.041 0.446 13 0.077844 0.03 19.15 1.24 6.09 % N1.009 SCWL Strobe, Ceiling, White 15cd 0.041 0.405 5 0.02879 0.01 19.14 1.25 6.14 % N1.010 PC2WL Horn/Strobe, Ceiling, White 75cd 0.143 0.364 27 0.163798 0.06 19.08 1.31 6.44 % N1.011 EOL P2RK Horn/Strobe,WP,Wall , Red 110cd 0.221 0.221 17 0.106234 0.02 19.05 1.34 6.55 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) N2 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.39 Max. Voltage Drop: 0.74 Min. Operational Voltage: 16 End Of Line Voltage: 19.65 Max. Circuit Current (A): 3 Voltage Drop Percent: 3.62 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.359 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 370 Spare Current (A): 2.641 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 2.270707 Spare Current (A) Percent: 88.03 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent N2.001 SCWL Strobe, Ceiling, White 30cd 0.063 0.359 277 1.702005 0.61 19.78 0.61 3.00 % N2.002 SCWL Strobe, Ceiling, White 15cd 0.041 0.296 24 0.147549 0.04 19.73 0.65 3.21 % N2.003 PC2WL Horn/Strobe, Ceiling, White 15cd 0.071 0.255 28 0.172869 0.04 19.69 0.7 3.43 % N2.004 SCWL Strobe, Ceiling, White 15cd 0.041 0.184 16 0.09525 0.02 19.67 0.72 3.51 % N2.005 EOL PC2WL Horn/Strobe, Ceiling, White 75cd 0.143 0.143 25 0.153034 0.02 19.65 0.74 3.62 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) N3 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.39 Max. Voltage Drop: 0.7 Min. Operational Voltage: 16 End Of Line Voltage: 19.69 Max. Circuit Current (A): 3 Voltage Drop Percent: 3.42 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.359 Circuit Wiring Properties: 'A' 994 14 AWG, 4 Cond. Solid Copper FPLR Analog Unshielded Total Circuit Length (Ft): 391 Spare Current (A): 2.641 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 2.40193 Spare Current (A) Percent: 88.03 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent N3.001 PC2WL Horn/Strobe, Ceiling, White 30cd 0.09 0.359 150 0.919112 0.33 20.06 0.33 1.62 % N3.002 HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.269 202 1.241523 0.33 19.72 0.66 3.26 % N3.003 HWL Horn, White 0.047 0.158 26 0.158176 0.02 19.7 0.69 3.38 % N3.004 EOL HWL-LF L-Series , Low Frequ. Horn, Wall, White 0.111 0.111 14 0.083119 0.01 19.69 0.7 3.42 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) ROY L CATS `Q�QROTECTZ�2. o rm W n Gb NFPA' �^ CFPS #1473 r � DO rn N .0 o Jw Z U W Q�o`n, w Y w Cn � U a z U = j H V J d LU a J p 0 CD z>- W-U- M W* U- o nwLU J LU H L) d 0 Yw06W LU Q 3WcnJa 0 REVISION RECORD DATE / DESCRIPTION RECEIVED Aug 28 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FIR2023-085 DATE: 08/18/2023 PROJECT NAME LU �CD N CD LU 00 =aQ ~ O cn a_z r C OD04 c LU N LU SHEET TITLE SINGLE LINE RISER DIAGRAM / BATTERY & POINT TO POINT CALCULATIONS SHEET NUMBER FA 2mO_