FIR2023-0085+Fire_Alarm_Equipment_Specification_Sheets+8.25.2023_10.56.09_AM+3747591
Honeywell QGamewell �� GWF-7075 Analog and Networking Systems ntelligent Fire Alarm Control Panel General RECEIVED Aug 28 2023 FIR2023-085 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT The Gamewell-FCI°, GWF-7075 is an Addressable Fire Alarm Control Panel (FACP). The GWF-7075 has a signaling line circuit (SLC) loop that is used to connect the addressable detectors. The SLC loop is capable of supporting up to 75 detectors and 75 modules using the System Sensor°Velociti° Protocol, and it also offers the built-in support for the SWIFT'' wireless fire alarm devices. The GWF-7075 is equipped with two configurable Notification Appliance Circuits (NACs) that support a maximum output of 2.5A. This panel communicates with the built-in, dual -line digital and IP communicator including an optional cellular communication module. The GWF-7075 fire alarm control panel offers the following powerful features: • detector sensitivity • pre -trouble maintenance alert • day/night thresholds • calibration trouble alert • drift compensation The GWF-7075 panel supports a variety of devices, including the following accessories: • RA-1000Remote Annunciator • 5880 - LED 1/0 Module • GFPS-6S Intelligent Remote Power Supply • 5824 Serial/Parallel Printer Interface Module (for printing system reports) FEATURES & BENEFITS • Built-in support for up to 75 detectors and 75 modules operating in Velociti° or CLIP mode • Offers a four line LCD display with 40 characters per line • Available in a red or a black cabinet • GWF-7075 can be surface or flush mounted • Contains a built-in USB interface used for programming • Includes the programmable date setting for Daylight Saving Time • Uses a JumpStart Auto Programming° feature for easy programming • System programmable from the front panel • Provides a built-in dual phone line, digital alarm communicator/ transmitter(DACT), IP or optional cellular technologies GWF-7075 • Firmware can be upgraded in the field • Supports up to four SWIFT'" wireless gateways. Each gateway may include up to 49 wireless devices • Supports Class B (Style 4) and Class A (Style 6 or Style 7 configuration for SLC, and SBUS • Offers a built-in synchronization for appliances from AMSECO'", Gentex", System Sensor', and Wheelock- - Reports events to the Central Station by point or by zone Optional Accessories RA-1000: Remote Annunciator The RA-1000 is a remote annunciator used to operate the GWF-7075 Fire Alarm Control Panel (FACP). It connects to the control panel via the RS-485 system bus. The RA-1000 is equipped with five status LEDs which indicate: • Alarm • AC Power Loss • System Silenced • Trouble • Supervisory GFPS-6S: Intelligent Remote Power Supply The GFPS-6S intelligent power supply delivers 6A of notification appliance circuit (NAC) power and offers built-in synchronization from appliances developed by the following manufacturers: • System Sensor' • FaradayT" • Gentex° • AMSECOT' • WheelockT" The GFPS-6S provides its own AC power connection, battery charging circuit, and backup battery for use with the GWF-7075 FACP. The output circuits can be programmed as NACs or as auxiliary power (configurable for constant, resettable, or door holder power). 5824: Serial/ Parallel Module The 5824 is equipped with one parallel and one RS- 232 serial portthat allows the GWF-7075 to connectto virtually any standard PC -compatible printer to generate reports on site. 5880: LED 1/0 Module The 5880 provides 40 programmable LED outputs and eight supervised dry contact inputs. These devices offer an effective way to customize remote annunciation. The GWF-7075 supports up to eight 5880 modules to offer maximum flexibility. 5220: Direct Connect Module The 5220 is a direct connect module used to connect a fire alarm control panel (FACP) to a city box or polarity reversal communicator. CELL -MOD: Cellular Fire Alarm Communicator (Plastic Enclosure) The CELL -MOD houses the GSM communicator inside a plastic enclosure that may or may not require an external antenna depending on the installation environment. COMPATIBLE DEVICES For a list of compatible devices, refer to the following documents: • Compatibility Addendum for Gamewell-FCI Manuals. P/N: 9000-0427-L8 • SWIFTT" Intelligent Wireless Detectors, P/N: 9021-60818 • SWIFTT" Intelligent Wireless Modules, P/N: 9021-60819 • SWIFTT" Wireless Gateway, P/N: 9021-60824 ORDERING INFORMATION GWF-7075: Intelligent Fire Alarm Control Panel. Red GWF-7075B: Intelligent Fire Alarm Control Panel, Black SBUS Accessories RA-1000: Remote Annunciator (Black) Dimensions: 7.4"H x 9.1"W x 1.5" (18.8 x 23.1 x 3.8) cm RA-1000R: Remote Annunciator (Red) GFPS-6S: Intelligent Remote Power Supply Dimensions:16"H x 12.25"W 3"D (40.6 x 30.9 x 7.6) cm 5824: Serial/ Parallel Module Dimensions: 6"H x 7.75"W x 1.44"D (15.0 x 19.4 x 3.6) cm 5880: LED 1/0 Module Dimensions: 7.75"H x 6"W x 1.94"D (19.4 x 15.0 x 4.8) cm 5220: Direct Connect Module Dimensions: 1.31"H x 6.5"W x 2.13"D (3.33 x 16.51 x 5.40)cm Miscellaneous Accessories HFSS: Software Suite. Provides programming, upload/ download and event reporting BB-17F: Remote Battery Box Cabinet. Holds up to two 18 Amp Hour batteries. Dimensions: 16" W x 10" H x 6" D (40.64 W x 25.40 H x 15.24 D) cm CELL -MOD: Cellular Communicator in Plastic Enclosure GWF-7075 Technical Specifications SYSTEMS PHYSICAL: Overall Dimensions: 15.12" H x 12.71" W x 3.33" D 38.40 H x 32.28 W x 8.46 D cm Weight: 25 lbs. Color: Red or Black Environmental Operating Temperature: 32°F to 120OF (0°C to 49°C) Humidity: 0 to 93% relative humidity (non -condensing) ELECTRICAL: GWF-7075 Primary AC: 120 VAC C 60 Hz, 900mA Tota l Accessory Load: 2.5A @ 27.4 VDC Class A Power -Limited NAC Power: lA per NAC, 2.5A Total Aux Power: 27.4 VDC Form C Trouble & Alarm Relay: 2.5A @ 27.4 VDC, Resistive Standby Current: 165 mA Alarm Current: 310 mA Battery Charging Capacity: 7 to 35 AH Battery Size: 7 A/H maximum allowed in the control panelcabinet. Largercapacity batteries can be housed in the BB-17F accessory cabinet. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 — 49°C/32 —120°F and at a relative humidity 93%± 2% RH (noncondensing) at 32°C ± 20C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended thatthis system and its peripherals be installed in an environment with a normal room temperature of 15 — 271C/60 — 80°F. For more information Learn more about Gamewell-FCI's GWF-7075 and other products available by visiting www.Gamewell-FCI.com Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com STANDARDS The GWF-7075 is designed to comply with the following standard: UL Standard: UL 864 9th Edition NFPA STANDARDS NFPA 13 Sprinkler N FPA 15 Water Spray NFPA 16 Foam Water N FPA 70 N FPA 72 Central Station Remote Signaling Local Protective Signaling Systems Auxiliary Protected Premises Unit & Water Deluge Releasing Service For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewe[L- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI°, System Sensor' and Velociti° are registered trademarks and SWIFT'" is a trademark of Honeywell International, Inc. AMSECO- is a registered trademark of Kobishi America Inc. Asco® is a registered trademark of Asco Power Technologies Inc. AGENCY LISTINGS AND APPROVALS FarradayTM is a trademark of Faraday LLC. These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL:S1869 CSFM: 7165-1703:0500 MEA COA: 6255 OSHPD (CA): Approved Releasing Solenoids: Asco° T821OA107 24 VDC 3 A max. 0 Hz Asco° 821OG207 24 VDC 3 A max. 0 Hz ISO 9001 Certification 9021-60966 1 A 1 12/17 ©2017 Honeywell International Inc. Gentex° is a registered trademark of Gentex Corporation Inc. Microsoft, Windows®, and the Windows Logo' are registered trademarks or trademarks of Microsoft Corporation. UL® is a registered trademark of Underwriter's Laboratories Inc. Wheelock- is a trademark of Cooper -Wheelock Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subjectto change without notice. Honeywell !q,of AESO SECURITY CORPORATION INNOVATION 7707 Fire Subscribers r,, IntelfiNet till 4 Introducing a Newer, Smarter Alarm Communications Platform New Feature Highlights ael X • Leverages state of the art technology --,NNW • Applies advanced security protection • Offers flexible power and configuration options • Engineered for backward compatibility with legacy systems • Enables future ready capabilities • Provides instant subscriber status through front panel with Power and Trouble LEDs, a backlit LCD display, and Menu/Silence button • Improves functionality with an adaptive Graphic User Interface (GUI) for programming via smartphones, tablet and PCs • Plus many more... m I r4m] @ NFPA LISTED Key Benefits that Make 2.0 the Best Alarm Monitoring Solution Ever • Built upon the solid foundation of AES-IntelliNet patented mesh radio technology for use in private licensed wireless networks • Protects subscriber units against unauthorized access and rogue activity with a password protected Dealer Code • Makes programming and streamlined troubleshooting easy with user friendly interface • Adds integrated supervision of AES-IntelliPro full data module • Provides versatile power options: (1) Direct from the Fire Alarm Control Panel (FACP) without requiring an electrician onsite and without Subscriber backup battery (2) Directly from the FACP with Subscriber backup battery; or (3) Traditional installation with plug in Class 2 low power transformer • Allows for enhancement upgrades and an expanded number of new features to be added easily with highly flexible and scalable alarm communications infrastructure • Rigorously tested to the highest industry standards and future ready to meet emerging NFPA code and UL standards Enhanced Wireless Fire Alarm Monitoring Powered by AES enhanced mesh radio technology, IntelliNet 2.0 7707 Fire Subscribers are next generation universal wireless communicators that provide advanced security protection for any new or existing alarm monitoring network. The AES Model 7707 is ideal for commercial fire applications. With the AES-IntelliPro full data module option, they are the ideal drop -in replacement for Plain Old Telephone Service (POTS) lines. The red metal enclosure comes with a key lock and front panel LCD backlit display with intuitive view that provides an instant visual of the subscriber status. The user friendly GUI makes it easy to program AES subscriber units via a smartphone, laptop, tablet, or integrated Universal Serial Bus (USB)—without the need for special cables or having to use a handheld programmer. Additional knockouts make it easier to mount for faster installation. IntelliNet 2.0 Private Wireless Mesh Radio Network D) Burglary D Subscriber ---------------- r � 1 E C � I 1 N B) Fire � r I \ / Subscriber 1 I AFSNet kManaS—t System C§ B — — — — — — — — — — — — — — — — Prlmery AES-MulrfNer Receiver I 1 1 I A) Alarm E 1 Panel I SecondaryAES-MulriNer Recelrer � 1 � I 1 � l B i� I B Alarm Automation -- L p `{---- ---- - - C ---_ C)IPLinks Customer Location Mesh Radio Technology Central Monitoring Station Alarm Panel & AES Subscriber Multi -path AES-IntelliNet® Network Primary & Secondary AES-MultiNet System sends critical event signal delivers alarm signals via smart routing, receives transmission in 1-3 seconds The IntelliNet 2.0 Fire Subscriber has an 8 Zone modular design for expansion with normal and reverse polarity, POTS and DACT interfaces with an option for the 7794A AES-IntelliPro full data module add -on accessory board. AES subscribers' intelligent software automatically detects new hardware and devices to reduce installation time. An AES certified WiFi accessory allows seamless wireless connectivity for configuration and programming. A laptop, Ethernet cable, or a Wi-Fi USB dongle is required for IntelliNet 2.0 programming, handheld programmers will not work with 2.0 units. The forward compatible design allows for feature add-ons, engineered to adapt seamlessly with future software upgrades as technology advances. IntelliNet 2.0 allows configuration cloning for faster installation time. The AES 7707 was designed with quick configuration and installation in mind to make it easier for field technicians to get in, out, and on to the next install. Visit our Fire Marshal Resources web page for official NFPA and UL Listings: http://aes-corp.com/products/fire/fire-marshal-resources/ How to Order 7707 Fire InteffiNet 2.0 Fire Subscribers 2.0 PREMIUM (UL & ULC Listed, Available Now!) IntelliNet 2.0 Fire Subscriber, 8 Zone, 8 Supervised Zones, with integrated onboard 7707P-88 Local Annunciator, Red Enclosure IntelliNet 2.0 Fire Subscriber, 8 Zone, 8 Supervised Zones with 7794A AES-IntelliPro 7707P-88-ULP and integrated onboard Local Annunciator, Red Enclosure IntelliNet 2.0 Fire Subscriber, 4 Zone, 4 Supervised Zones, with integrated onboard 7707P-44 Local Annunciator, Red Enclosure IntelliNet 2.0 Fire Subscriber, 4 Zone, 4 Supervised Zones with 7794A AES-IntelliPro 7707P-44-ULP and integrated onboard Local Annunciator, Red Enclosure 2.0 FEATURE ADD (Pending UL Review) IntelliNet 2.0 Fire Subscriber, 8 Zone with Multiple Communication Technologies 7707P-88-M (MCT), Red Enclosure IntelliNet 2.0 Fire Subscriber, 8 Zone with 7794A AES-IntelliPro, and integrated 7707P-88-ULP-M onboard Local Annunciator plus MCT, Red Enclosure IntelliNet 2.0 Fire Subscriber, 4 Zone with Multiple Communication Technologies 7707P-44-M (MCT), Red Enclosure IntelliNet 2.0 Fire Subscriber, 4 Zone with 7794A AES-IntelliPro, and integrated 7707P-44-ULP-M onboard Local Annunciator plus MCT, Red Enclosure 7707M-UPG IntelliNet 2.0 Fire MCT Software Upgrade 2.0 ACCESSORIES Standalone AES-IntelliPro Fire full data module add -on accessory board with 7794A firmware for new IntelliNet 2.0 units only, cannot be used in legacy units 77-WiFi AES certified WiFi adapter Legacy• .- 7706-ULF Integrated Fire Monitoring System, Red Enclosure Legacy Fire Subscriber, 8 Zone with 7795 AES-IntelliPro (7794 full data module, 7788F-ULP-P 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones with 7794 AES-IntelliPro, 7788F-ULP Red Enclosure 7788F Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones, Red Enclosure Legacy Fire Subscriber, 4 Zone with 7795 AES-IntelliPro (7794 full data module, 7744F-ULP-P 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure Legacy Fire Subscriber, 4x4 Zone, 4 Supervised Zones with 7794 AES-IntelliPro, 7744F-ULP Red Enclosure Legacy Fire Subscriber, 4x4 Zone, 4 Reversing Polarity, 4 Supervised Zones, 7744F Red Enclosure LEGACY ACCESSORIES Standalone AES-IntelliPro Fire full data module add -on accessory board for legacy 7794 units only, please see 7794A above for IntelliNet 2.0 version Technical Specifications 7707 Fire DIMENSIONS 13"H x 8.5"W x 4.5"D (33cmH x 21.5cmW x 11.4cmD) WEIGHT 5.8 Ibs (2.6 kilograms) excluding battery 13 Ibs (5.9 kilograms) with 10 Ah battery RADIO FREQUENCY Standard Frequency Range 450-470 MHz Contact AES for other UHF and VHF frequencies ANTENNA 2.5 dB tamper resistant antenna included, mounts on enclosure Optional remote mounting antenna available POWER INPUT AC SOURCES Class 2 transformer 40VA, 120V AC primary ELK ELK-TRG1640, MG Electronic Sales MGT1640, and AES 1640 are UL Listed for use (not included) 1.75A, maximum input current value 16.5V AC, nominal output value DC SOURCES External regulated power supply, 24V DC, rechargeable backup battery in Subscriber 1.3A, input current Regulated power supply from FACP AUX power, 24V DC, UL Listed FACP with backup battery in FACP 1.3A, input current Contact Us BACKUP BATTERY 10-12 Ah, UL recognized lead acid gel cell, size based on subscriber configuration ALARM SIGNAL INPUTS/ZONES 8 individually programmable E.O.L. type zone inputs 4+4: 4 reverse polarity input and 4 individually programmable E.O.L. type zone inputs Optional 7794A AES-IntelliPro for full data via Contact ID, Pulse, Modem Ile and Modem IIla2 UL LISTINGS UL 864 loth Edition Standard for Control Units and Accessories for Fire Alarm Systems ULC S559-04 1st Edition Equipment for Fire Signal Receiving Centres and Systems TROUBLE OUTPUT—ACK DELAY/ANTENNA CUT Form C relay, fail secure, rated 24V DC 1A resistive RESET BUTTON Located on main circuit board OPERATING TEMPERATURE 32 to 120°F (0 to 49°C) STORAGE TEMPERATURE 14 to 140°F (-10 to 60°C) RELATIVE HUMIDITY 0 to 93%, non -condensing RECHARGE CAPABILITY Will charge 12V battery size from 10-12 Ah PORTS Ethernet for configuration and communication USB access for software upgrade REMOTE ANNUNCIATOR AES Model 7740 Remote Annunciator, supervised COMPATIBLE RECEIVERS 7705i AES-MultiNet Receiver CONFIGURATION INTERFACE Web browser capable device accessible via smartphone, tablet, laptop, or PC CURRENT CONSUMPTION Standby with charged backup battery: 175 mA Standby + charging backup battery: 200 mA Transmitting: 1.2 A (typical transmission is 1/3 second length) POWER OUTPUT 2 or 5 Watts Factory set ENCLOSURE MATERIAL Steel with paint finish FINISH COLOR Red VISUAL INDICATORS Front panel LCD (2 x 20 alphanumeric character backlit display) Power and Trouble LEDs (ALM Trouble Tx, Rx, WA) For pricing and availability or to learn more about IntelliNet 2.0, please call your local AES Sales Representative at (800) 237-6387 or email sales@aes-corp.com. Honeywell QGamewell 29 MS-7 Series Addressable Devices Manual Fire Alarm Pull Stations General The Gamewell-FCI, MS-7 Series manualfire alarm pullstations are available in a wide variety of configurations. The pull stations comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All pull stations include a key lock/reset which is keyed alike with the Gamewell-FCI fire alarm control panels and other man ualfire alarm pull stations. MS-7AF Velociti Addressable Station The MS-7AF VelociC Series addressable station is a double action pull station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the pull station causes its assigned address to register at the fire alarm control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The station features screw terminals. MS-7ASF Velociti Addressable Station MS-7 Series The MS-7ASF Velociti' Series addressable pull station is a single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is activated* The station features screw terminals. The Velociti� Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and focuses on the single device. The net effect offers a response speed up to five times greater than earlier designs. MS-7 Double Action Station The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. FEATURES & BENEFITS • Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls • The pull stations (MS- 7LOB) are Listed for outdoor applications • Complies with ADA pull force requirements • Offers surface or semi - flush mounting • Shock and vibration resistant • Conventional stations Both single and double suitable for use with action pull stations any UL® Listed control available panel • Includes a tumbler lock for test and reset keyed alike with analog addressable fire alarm controls *Only the red LED is operative in panels that do not operate in Velociti mode MS-7S Single Action Station The MS-7S single action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating circuit. MS-7SP Double Action Station The MS-7SP is a double action pull station similar to the MS-7 station, with the additional feature of including both English and Spanish instructions molded into the unit. MS-7LR Dual -action Agent Release Station The MS-7LR is designed for usewith the Gamewell-FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems. It features a set of single pole contacts and screw terminals used to connect to an initiating circuit. MS-7LRA Agent Release Station with Abort The MS-7LRA is designed for use with the Gamewell- FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabilities are required. It consists of the following: • An MS-7LR mounted on a plate with an abort switch • LED indicators that signal system normal and system activated status MS-7LOB Double Action Station (Listed for Outdoor Applications) The MS-71_O13 station must be mounted on a Model SB-1/0 backbox. In retrofit applications, the pull station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals. Mounting The MS-7 interior pull stations may be surface mounted or semi -flush mounted on a standard double -gang, or4-inch (10.2 cm) square electrical box. An optional trim ring (BG12TR) may also be used for semi -flush mounting. NYC -Plate The NYC -Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC -Plate Ordering Information MS-7: Double action station MS-7AF**: Velociti addressable double action station MS-7ASF**: Velociti addressable single action station MS-7S: Single action station, wire leads MS-7SP: Double action station, English and Spanish instructions MS-7LR: Agent release station, dual -action MS-7LRA: Agent release station with abort switch, LED indicators, dual- action MS-7LOB: Double action station, outdoor use (Includes SB-1/0 - Indoor/outdoor use backbox) SB-I/O: Indoor/outdoor use backbackbox SB-10: Surface backbox BG12TR: Trim ring for semi -flush mount, plastic NY -PLATE: NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. MS-7 Series Technical Specifications SYSTEMS STANDARDS For a complete listing of all Material: Lexan" The MS-7 Series is designed to com l wth the following ii g p y g compliance approvals and certifications, please visit: Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) standard: http://www.gamewell- Dimensions: 5 5/8" H x 41/4" W x 1 1/4" D UL Standard: UL 864 9th Edition fci.com/en-US/ (14 x 10.1 x 3.2 cm) AGENCY LISTINGS AND APPROVALS documentation/Pages/ Listings.aspx Operating Temperature: These listings and approvals apply to the modules LEXAN Is a registered (MS-7AF, MS-7ASR 320 to 1200 F (00 to 490 C) specified in this document. In some cases, certain trademark of GE Plastics, a (MS-71-013): -30'to 150' F (-350 to 660 C) modules or applications may not be listed by certain subsidiary of General Electric Relative Humidity: approval agencies, or listing may be in process. Company. (MS-7AF, MS-7ASF): 10 to 93% (non -condensing) Consult factory for latest listing status. Velociti° and Gamewell-FCI (MS-7LOB): 85%± 5% @ 861 ± 3.61(301± 2° C) UL: S2465 are registered trademarks of Alarm Current:.0030 amp. 0.007 for LED FM: 3023594 Honeywell International Inc. Supervisory Current: MEA FDNY: 67-02-E Vol. VI I UL® is a registered trademark (MS-7AF, MS-7ASR .00030 amps. CSFM: of Underwriter's Laboratories TEMPERATURE AND HUMIDITY RANGES 7160-1703:0119 Inc. 7160-1703:0170 This system meets NFPA requirements for operation at 0 This document is not intended - 490C/32 -120OF and at a relative humidity 93%± 2% 7160-1703:0109 to be used for installation RH (noncondensing) at 32°C ± 21C (90oF± 3oF) ISO 9001 Certification purposes. We try to keep our However, the useful life of the system's standby batteries product information up -to - and the electronic components may be adversely affected date and accurate. We cannot cover all specific applications by extreme temperature ranges and humidity. Therefore, or anticipate all requirements. it is recommended that this system and its peripherals be All specifications aresubjectto installed in an environment with a normal room change without notice. temperature of 15 - 271C/60 - 80°F. For more information Learn more about Gamewell-FCI's MS-7 Series and other products available byvisiting www.Gamewell-FCI.com Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 9020-0616 1 F 1 11/17 Honeywell www.honeywell.com ©2017 Honeywell International Inc. Honeywell I Addressable Devices QGamewell �^ Velociti° Series 3 Detectors Photoelectric Detectors Description The Gamewell-FCI, Velociti° Series 3 intelligent photoelectric detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 smoke detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The photoelectric detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. The Gamewell-FCI, ASD-PL3 photoelectric detector's re -designed optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The sensitivity of Velociti series detectors can be programmed using the control panel software to suit the environment. The ASD-PL3R photoelectric detector is also remote test capable that may be used with a DNR (DN RW) duct smoke detector housing. The ASD-PTL3 multi - sensor detector offers either photoelectric detection or thermal detection through dual electronic thermistors at 135°F fixed temperature thermal sensing. For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number after the detector model. Note: Although the E3 Series° and S3 Series panels support both the Velociti° and CLIP" protocols, the GWF-7075 panel does not support the CLIP protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL° • Contains a built-in Standard 268 7th functional test switch Edition activated by external • Designed with a new magnet profile to offer modern • Supports a lowstandby and improved current aesthetics Photoelectric Detector • Provides rotary address • Includes dual LEDs for Offers expanded color switches (01-159) 360'visibility options • Supplies optional relay, isolator, or sounder bases (standard or low frequency) Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL' suffix indicates Black color model. NOTE: "WH" suffix indicates Bright White color model. ASD-PL3: Photoelectric smoke detector, bright white, Velociti ASD-PL3R: Photoelectric smoke detector, remote test capable, for use with DN R(W) duct smoke detectors, bright white, Velociti ASD-PTL3: Photoelectric smoke detector with thermal sensing, bright white, Velociti ASD-PL3-IV : Photoelectric smoke detector, ivory, Velociti/ CLIP ASD-PL3R-IV: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, ivory, Velociti/CLIP ASD-PTL3-IV: Photoelectric smoke detector with thermal sensing, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. Note: "IV" suffix indicates Flashscan and CLIP devices. "WH" suffix indicates brightwhite B501-WHITE: 4" Flangeless mounting base, brightwhite B501-WHITE-BP: 4" Flangeless mounting base bulk pack, brightwhite B501-IV: 4" Flangeless mounting base, ivory B300-6: 6" Flanged mounting base, brightwhite B300-6-IV: 6" Flanged mounting base, ivory B300-6-BP: 6" Flanged mounting base bulk (Pack of 10) B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B20OS-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, brightwhite B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory DNR: Intelligent duct detector housing, non -relay DNRW: Intelligent duct detector housing, non -relay, watertight Ordering Information Accessories SMB600:Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6° Base, bright white TR300-IV: Accessory Flange Ring for B300 6" Base, ivory RA10OZ: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single -gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCSCOF Series detectors. (Pack of 10) CK300-BL: Black detector kit. (Pack of 10) CK300-IR-BI: Black, detector color kit for use with MCSCOF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR213: Detector removal tool. Allows the installation and/ or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR213. Shipped with three, 5-foot (1.524,m) sections. 4 Velociti° Series 3 Detectors Technical Specifications SYSTEMS STANDARDS Photoelectric Intelligent Detector: The Velociti° Series 3 Photoelectric Detectors are Physical Specifications designed to comply with the following standard: Height: 2.0 inches (51 mm) installed in B300-6 base UL Standard: UL 268 Diameter: 6.1 inches (15.49 cm) installed in B300-6 base 4 inches (10.16 cm) installed in B501 base Shipping Weight: 3.4 oz (96.4 g) Operating Temperature Range: Photo: 321 F to 1221 F (01 C to 501 C) Photo in Duct Applications: -41 F to 1580 F (-20° C to 701 C) Photo with Thermal: 321 F to 1001 F (01 C to 381 C) Operating Humidity Range: 10% to 93% non -condensing Rate -of -Rise Detection: Responds to greater than 150F/minute or 135°F (8.3° C/minute or 57°C Air Velocity Range: 0 to 4,000 ft/min (0 to 1219.2 m/min) Electrical Specifications Voltage Range: 15 to 32 VDC Standby Current (C 24 VDC): 200 UA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): 2 mA C 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): 4.5 mA C 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: 0.0063 For more information Learn more about Gamewell-FCI's Velociti° Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL:S2332 FM:3023594 MEA FDNY: COA-219-02-EVol. VI CSFM:7272-1703:0501 ISO 9001 Certification 9020-0617 1 K 1 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL` is a registered trademark of Underwriter's Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications aresubjectto change without notice. Honeywell INSTALLATION AND MAINTENANCE INSTRUCTIONS B300-6 and B300-6-IV 6" Plug-in Detector Bases SYSTEM171 SEIV-SOR° 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com SPECIFICATIONS Base Diameter: 6.1 inches (155 mm) Base Height: 0.76 inches (19 mm) Operating Temperature: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com. Electrical Ratings: Operating Voltage: 15 to 32 VDC Standby Current: 170 pA Listings: UL268 BEFORE INSTALLING Please read the System Smoke Detectors Application Guide, which provides detailed information on detector spacing, placement, zoning, wiring, and spe- cial applications. Copies of this application guide are available from System Sensor. NFPA 72 guidelines should be observed. NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once a year. GENERAL DESCRIPTION The B300-6 and B300-6-IV are plug-in detector bases intended for use in an intelligent system, with screw terminals provided for power (+ and -), and remote annunciator connections. Communication takes place over the power lines (+ and -). BASE TERMINALS NO. FUNCTION 1 Power (-), Remote Annunciator (-) 2 Power (+ ) 3 Remote Annunciator (+) FIGURE 1. TERMINAL LAYOUT TERMINAL TERM INAL 1 C0127-07 MOUNTING This detector base mounts directly to 4-inch square (with and without plaster rings), 4-inch octagon, 31/2-inch octagon, and single gang junction boxes. To mount, remove the decorative ring by turning it in either direction to unhook the snaps, then separate the ring from the base. Install the base on the box using the screws supplied with the junction box and the appropriate mounting slots in the base. Place the decorative trim ring on the base and rotate it in either direction until it snaps into place. (See Figure 2.) FIGURE 2. MOUNTING DETECTOR TO BOX SNAP ON DECORATIVE RING ~(ry S SUPPLIED) DETECTOR BASE I I I I T 69 o(IVDSUPPIED) � C2036-01 INSTALLATION AND WIRING GUIDELINES (SEE FIGURE 3) All wiring must be installed in compliance with all applicable local codes and any special requirements of the authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color -coded to reduce the like- lihood of wiring errors. Improper connections can prevent a system from re- sponding properly in the event of a fire. For signal wiring (the wiring between interconnected detectors), it is recom- mended that the wire be no smaller than 18 AWG (0.823 mmz). Wire sizes up to 12 AWG (3.31 mmz) may be used with the base. Make electrical connections by stripping about 3/8 inch (10 mm) of insulation from the end of the wire (use strip gauge molded in base). Then slide the wire under the clamping plate and tighten the clamping plate screw. Do not loop the wire under the clamping plate. (See Figure 4.) Check the zone wiring of all bases in the system before installing the detec- tors. This includes checking the wiring for continuity, correct polarity, ground fault testing and performing a dielectric test. The base includes an area for recording the zone, address, and type of detec- tor being installed. This information is useful for setting the detector head address and for verification of the detector type required for that location. Once all detector bases have been wired and mounted, and the loop wiring has been checked, the detector heads may be installed in the bases. I56-6566-001 11/17/2017 TAMPER -RESIST FEATURE NOTE: Do not use the tamper -resist feature if a removal tool will be used. The detector base includes a tamper -resist feature that prevents removal of the detector without using a small screwdriver or similar tool. To activate this feature, use needle -nose pliers to break the tab on the detector base as shown in Figure 5A. Then, install the detector. To remove the detector from the base once the tamper -resist feature has been activated, remove the decorative ring by rotating it in either direction and pulling it away from the base. Then, insert a small screwdriver into the notch, as indicated in Figure 513, and press the plastic lever toward the mounting surface before rotating the detector counterclockwise for removal. The tamper -resist feature can be defeated by breaking and removing the plas- tic lever from the base. However, this prevents the feature from being used again. REMOTE ANNUNCIATOR (RA1002) Connect the remote annunciator between terminals 1 and 3 using the spade lug terminal included. The spade lug terminal is connected to the base termi- nal as shown in Figure 6. It is not acceptable to have three stripped wires under the same wiring ter- minal unless they are separated by a washer or equivalent means. The spade lug supplied with the model RAl00Z is considered an equivalent means. See Figure 3 for proper installation. FIGURE 3. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP _EWTAINALTAII• "• FIGURE 5A. ACTIVATE TAMPER -RESIST FEATURE PLASTIC LEVER BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE C0130-00 FIGURE 513. DETECTOR REMOVAL USE SMALL -BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN nN DIRECTION OF ARROW r A C0130-00 FIGURE 6. CONNECTION TO REMOTE ANNUNCIATOR TERMINAL STRIPPED WIRE WIRE WITH SPADE LUG C0116-00 C0129-02 FIGURE 4. TERMINAL WIRE INSTALLATION THIS NOT THIS 0 An C0473-00 Please refer to insert for the Limitations of Fire Alarm Systems THREE-YEAR LIMITED WARRANTY System Sensor warrants its enclosed smoke detector base to be free from defects in ma- 12220 Rojas Drive, Suite 700, El Paso TX 79936 USA. Please include a note describing the terials and workmanship under normal use and service for a period of three years from malfunction and suspected cause of failure. The Company shall not be obligated to repair date of manufacture. System Sensor makes no other express warranty for this smoke or replace units which are found to be defective because of damage, unreasonable use, detector base. No agent, representative, dealer, or employee of the Company has the au- modifications, or alterations occurring after the date of manufacture. In no case shall the thority to increase or alter the obligations or limitations of this Warranty. The Company's Company be liable for any consequential or incidental damages for breach of this or any obligation of this Warranty shall be limited to the repair or replacement of any part of other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the smoke detector base which is found to be defective in materials or workmanship the Company's negligence or fault. Some states do not allow the exclusion or limitation of under normal use and service during the three year period commencing with the date of incidental or consequential damages, so the above limitation or exclusion may not apply manufacture. After phoning System Sensor's toll free number 800-SENSOR2 (736-7672) to you. This Warranty gives you specific legal rights, and you may also have other rights for a Return Authorization number, send defective units postage prepaid to: Honeywell, which vary from state to state. System Sensor® is a registered trademark of Honeywell International, Inc. 2 I56-6566-001 ©2017 System Sensor. I l/17/2017 M Altronix° AL802ULADA NAC Power Extender Rev. 07202022 Altronix AL802ULADA is an extremely cost effective voltage regulated remote NAC Power Extender. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and providing auxiliary power to support system accessories. C,.... :i: ..L: V r.JVV II IVU�IVIIJ Input Voltage 120VAC, 60Hz, 4A Two (2) Class A or two (2) Class B inputs Two (2) NC dry contact trigger inputs Input Ratings (INP1 and INP2): 8-30VDC 6.5mA max from FACP 12V 6.5mA, 24V 6.5mA from FACP Output Voltage 24VDC power -limited outputs Current 8A max. total alarm current 2.5A max. current per output Auxiliary 1 A. Other Thermal and short circuit protection with auto reset Filtered and regulated outputs Programmable Supervised Indicating Circuit Outputs: Four (4) Class B, or Two (2) Class A, or One (1) Class A and Two (2) Class B Back-up Battery (notincluded) Type Sealed lead acid or gel type Failover Upon AC loss, instantaneous Supervision AC Failure Battery Indicators (LED) AC Power (Green) DC Output (Red) Logic Board (Red and Green) Form "C" contacts Form "C" contacts Input voltage is present Powered Output status Agency Listings UL UL864 (Control Units and Accessories for Fire Systems) MEA NYC Department of Buildings Approved FM Factory Mutual Approved CSFM California State Fire Marshal Approved Special Features 2-wire horn/strobe Sync mode allows audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/deactivated at the same time Sync protocols include Potter/Amseco, Gentex@, System Sensors, and CooperWheelock(D - Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit) - Compatible with 12VDC or 24VDC fire panels - Output loop supervision steered to Input 1 or Input 2 - Signal circuit trouble memory (helps identify intermittent loop problems) - Common trouble input and output for external trouble signals tie-in - Ground fault detection Physical and Environmental Dimensions (H x W x D) Enclosure: 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm) Shipping: 16.5" x 13.5" x 6" (419.1 mm x 342.9mm x 152.5mm) Enclosure accommodates up to two (2) 1 2VDC/1 2AH batteries. Weight (approx.) Product: 9.6 lb. (4.35 kg) Shipping: 12.3 lb. (5.58 kg) Temperature Operating: 0°C to 490C (320F to 1200F) Storage: — 200C to 700C (— 40F to 15800 Relative Humidity 85% +/— 5% BTU/Hr. (approx.) 41.3 BTU/Hr. Lifetime Warranty Altronix Corporation 1 140 58th St I Brooklyn, NY 11220 USA phone: +1 718.567.8181 1 fax: +1 718.567.9056 1 email: info@altronix.com I www.altronix.com O,�� SYSTEM � SENSOR - Indoor Selectable - Output Strobes and Horn Strobes for Ceiling Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features • Plug-in design with minimal intrusion into the back box • Tamper -resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field -selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Listed for ceiling mounting only Agency Listings SIGNALING z F M LISTED APPROVED S5512 FM approved except 7125-1653:0504 S4011 for ALERT models 7135-1653:0503 3057383 The System Sensor L-Series offers the most versatile and easy -to -use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, wall and ceiling mounting options, System Sensor L-Series can meet virtually any application requirement. The entire L-Series product line of ceiling -mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time- consuming ground faults. To further simplify installation, the L-Series utilizes a universal mounting plate so installers can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field -selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. L-Series Specifications General L-Series ceiling -mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double - gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuif" Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field -selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non -coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non -condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling -Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high) Ceiling -Mount Surface Mount Back Box Skirt Dimensions 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS86800 UL Current Draw Data IL ,. .. .. -, 8-17.5 Volts Candela DC 15 87 30 153 75 N/A 95 N/A 115 N/A 150 N/A 177 N/A Max. Current Draw (rnA RMS), 2-Wire Horn 16-33 Volts DC 41 63 111 134 158 189 226 StrobeUL FWR 60 86 142 164 191 228 264 8-17.5 Volts DC Input 15cd 30cd 16-33 Volts 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non -Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1 K Temporal High 111 164 69 94 147 163 184 229 257 3.1 K Temporal Low 103 163 54 88 143 155 185 212 252 3.1 K Non -Temporal High 111 172 69 94 144 164 202 229 271 3.1 K Non -Temporal Low 103 169 54 88 131 155 187 217 259 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non -Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1 K Temporal High 108 135 179 200 225 255 289 3.1 K Temporal Low 79 101 150 171 196 229 260 3.1 K Non -Temporal High 108 135 179 200 225 255 289 3.1 K Non -Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones and Sound Output Data Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8-17.5 Volts DC 16-33 Volts DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non -Temporal High 85 90 90 4 Non -Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non -Temporal High 84 89 89 8 3.1 KHz Non -Temporal Low 77 83 83 AVDS86800 L-Series Dimensions YJux 2.47 1.37 y' 6.92 Ceiling -Mount Horn Strobes Ceiling Surface Mount Back Box Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box L-Series Ordering Information Ceiling Horn Strobes Ceiling Strobes PC2RL 2-Wire, Horn Strobe, Red SCRL Strobe, Red PC2WL 2-Wire, Horn Strobe, White SCWL Strobe, White SCWL-CLR-ALERT Strobe, White, ALERT Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCWL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White SYSTEM System Sensor. ©t SENSORS 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensoccom to c or current productinformation,-the his data sheet. Phone: 800-SENSOR2 • Fax: 630-377-6495 03/17stversionof AVDS86801 • 03/17 O,�� SYSTEM � SENSOR - Indoor Selectable - Output Low Frequency Sounders and Low Frequency Sounder Strobes System Sensor L-Series audible visible notification products are rich with features guaranteed to maximize profits with lower current draw and modern aesthetics. Features The L-Series offers the most versatile and easy -to -use line of low • 520 Hz ± 10% square wave tone, NFPA compliance frequency sounder and low frequency sounder strobes in the industry. With white and red plastic housings, listed for wall and • Full candela range plus High/Low tone options to optimize current ceiling mounting, L-Series Low Frequency can meet virtually any draw for a wide variety of applications application requirement. • Compact, standard, and round ceiling options • Field -selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Rotary switch for High and Low, Temp3 and Temp4 settings • Plug-in design with minimal intrusion into the back box • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices (Direct replacement for HW/R-LF and P2R/WH-LF) • Compatible with MDL3 sync module • Sounders listed for ceiling and wall mounting • Sounder Strobe listed for wall mounting • Updated modern aesthetics Agency Listings SIGNALING U� FM z LISTED 54011 PR452768 Horns only: 7135-1653:0516 Horn/Strobes: 7125-1653:0517 The low frequency sounder and low frequency sounder strobes were designed to address the NFPA 72 sleeping space requirements that require a low frequency notification appliance that operates within frequency range of 520 Hz ± 10% and is of a square wave tone. Like the entire L-Series product line they include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, L-Series uses a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field -selectable candela settings, 24- volt operation, and a rotary switch for 520 Hz low frequency sounder tones. AVDS910-01 • 10/1/2019 • Page 1 L-Series Specifications General L-Series low frequency sounder and low frequency sounder strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double -gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 17/s-inch back box. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuif'° Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit (0°C to 49°C) from a regulated DC or full -wave rectified unfiltered power supply. Low Frequency Sounder strobes shall have field -selectable candela settings including 15, 30, 75, 95, 110, 135, 185. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone and have a permanent marking on the housing that reads "low frequency sounder". Low Frequency Sounder The low frequency sounder shall be a System Sensor L-Series Model listed to UL 464 and shall be approved for fire protective service. The low frequency sounder and the Sync•CircuitTM MDL3 Module accessory, if used, shall be powered from a notification appliance circuit output and shall operate on a nominal 24 volts (includes fire alarm panels with built-in sync). When used with the Sync•Circuit Module MDL3, 24-volt rated notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on a circuit. The low frequency sounder has an option to switch between temporal three or temporal four pattern, non - temporal (continuous) pattern and coded supply within the frequency range of 520Hz t 10% square wave tone. The low frequency sounder shall operate on a coded or non -coded power supply with high and low volume settings. Low Frequency Sounder Strobe Combination The low frequency sounder strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The low frequency sounder strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The sounder shall have an option to switch between a temporal three or temporal four pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. The low frequency sounder on low frequency sounder strobe models shall operate on a non -coded power supply with high and low volume settings. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/e-inch back box. The module shall also control two Class B circuits or one Class A circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non -condensing Frequency Range 520 Hz t 10% Strobe Flash Rate 1 flash per second Nominal Voltage Low Frequency Sounder Regulated 24 DC/FWR1 Nominal Voltage Range Low Frequency Sounder Strobe Regulated 24 VDC/FWR1 Operating Voltage Range 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Dimensions Wall Sounder Strobe (including lens) 5.6" L x 4.7" W x 1.9" D (142 mm L x 119 mm W x 49 mm D) Standard Wall Sounder 5.6" L x 4.7" W x 1.5" D (142 mm L x 119 mm W x 38 mm D) Compact Wall Sounder 5.25" L x 3.46" W x 1.5" D (133mm L x 88mm W x 38mm D) Ceiling Sounder 6.8" diameter x 1.4" high (173mm diameter x 36mm high) Standard Wall Sounder with SBBRUSBBWL Surface Mount Back Box 5.7" L x 4.8" W x 3.3" D (145 mm L x 120 mm W x 87 mm D) Compact Wall Sounder with SBBGRUSBBGWL Surface Mount Back Box 5.4" L x 3.6" W x 3.0" D (137 mmL x 91mm W x 76 mm D) Low Frequency Ceiling Sounder with SBBCRUSBBCWL Surface Mount Back Box 6.9" diameter x 3.9" high (175mm diameter x 99mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs. AVDS910-01 • 10/1/2019 • Page 2 UL Current Draw and Sound Output Data Current Draw (mA) Sound Output Volume I 16-33 VDC I 16-33 FWR I 16-33 V Pos Tone Setting I 15cd 30cd 75cd 95cd 110cd 135cd 185cd I 15cd 30cd 75cd 95cd 110cd 135cd 185cd I DC FWR 1 Temporal High 98 115 158 173 182 212 266 136 153 188 206 228 258 304 80 1 80 2 Temporal 3 Low 98 102 141 162 173 202 255 150 150 176 194 216 242 280 76 76 3 Temporal High 98 108 137 151 178 202 252 200 198 169 188 212 242 290 80 80 4 Temporal 4 Low 102 104 122 136 163 187 237 176 174 154 173 197 227 275 76 76 5 Continuous High 141 158 198 216 234 264 305 190 207 249 268 289 321 368 80 80 6 Continuous Low 120 128 179 196 215 244 285 165 182 226 244 266 297 342 76 76 UL Max. Pos Low Frequency Tone Sounder Volume Setting Current Draw Current Draw (mA) (mA RMS) Sound Output (dBA) Reverberant 16-33 Volts 16-33 Volts DC FWR DC FWR 1 Temporal High 108 150 80 80 2 Temporal Low 78 76 76 76 3 Temporal High 111 151 80 80 4 Temporal Low 80 76 76 76 5 Continuous High 111 151 80 80 6 Continuous Low 80 76 76 76 7 Coded High 111 151 80 80 8 Coded Low 80 76 76 76 'NU I t: ror coded tones, temporal coding must be provided iDy the NAC. If the NAC voltage is held constant, the sounder output will remain constantly on. Coded ratings provided are for continuous voltage. AVDS910-01 • 10/1/2019 • Page 3 L-Series Dimensions Wall LF Sounder Strobe Ceiling LF Sounder Red White Low Frequency Sounder Strobes Wall LF Sounder 1�1.438 3.455 1.453 °O000 °°000000000 0°0°0°0°°00 0°0°0°0°0°0 ®°0°°°®°0°° o°o°o°o®o0 5.265 goo ®0°°®0°0 e°o°o°o°o°e oao°®°e°ono 00000000000 Compact Wall LF Sounder P2RL-LF P2WL-LF LF Sounder Strobe, Wall Low Frequency Sounders HRL-LF HWL-LF LF Sounder, Wall HGRL-LF HGWL-LF Compact LF Sounder, Wall HCRL-LF HCWL-LF LF Sounder, Ceiling Accessories MDL3R MDL3W Sync•CircuitTM Module, UL-listed SBBWL SBBWL Surface Mount Back Box, Wall SBBCRL SBBCWL Surface Mount Back Box, Ceiling SBBGRL SBBGWL Surface Mount Back Box, Wall, Compact System Sensor® is a registered trademark and Sync•Circuil is a trademark of Honeywell International, Inc. SYSTEM ©t to c System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensoccom SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 or current product information,including 0-01.10/1/latest version of his data sheet. AVDS910-01 • 10/1 /2019 O,�� .SYSTEM � SENSOR - Outdoor Selectable - Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field -selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from —40°F to 151 °F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper -resistant construction • Listed for ceiling or wall mounting Agency Listings SIGNALING L FM MEA 7300-1653:187 (outdoor strobes) LISTED approved 7125-1653:188 (horn strobes, S4011 (chimes, horn strobes, horns) APPROVED pp chime strobes) S3593 (outdoor and alert strobes) 3023572 MEA452-05-E 7135-1653:189 (horns, chimes) f o m S y s t e rn S e n s o r SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE -printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from —40oF to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field -selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in -and - out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock -outs located on the back eliminate the need to drill holes for screw -in mounting. Plastic and metal weatherproof back boxes come with 3/4-inch top and bottom conduit entries and 3/4-inch knock -outs at the back. A screw -in NPT plug with an O-ring gasket for a watertight seal is included with each back box. SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuif' Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between —40 and 151 degrees Fahrenheit from a regulated DC or full -wave rectified unfiltered power supply. Strobes and horn strobes shall have field -selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non -temporal (continuous) pattern. These options shall be set by a multiple position switch. On four -wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non -coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Operating Temperature —40oF to 151°F (-40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall -Mount Dimensions (including lens) 5.6-L x 4.7-W x 2.5-D (142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6-L x 4.7-W x 1.3-D (142 mm L x 119 mm W x 33 mm D) Wall -Mount Weatherproof Back Box Dimensions (SA-WBB) 5.7-L x 5.1-W x 2.0-D (145 mm L x 130 mm W x 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 UL Current Draw Data 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non -Temporal High 57 56 69 75 95 NA NA 181 176 Non -Temporal Medium 42 50 60 69 110 NA NA 202 195 Non -Temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 Max. Current Draw (mA RMS), 2-Wire Horn Strobe,UL .. . 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non -Temporal High 141 152 91 100 116 176 201 221 229 Non -Temporal Medium 133 145 75 85 102 163 187 207 216 Non -Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non -Temporal High 142 161 103 112 126 181 203 221 229 Non -Temporal Medium 134 155 85 95 110 166 189 208 216 Non -Temporal Low 132 154 80 90 105 161 184 202 211 Max. Current Draw (mA RMS), 2-Wire Horn Strobe,UL 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non -Temporal High 255 270 303 it 309 Non -Temporal High 233 248 275 281 Non -Temporal Medium 242 259 293 299 Non -Temporal Medium 219 232 262 267 Non -Temporal Low 238 254 291 295 Non -Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures, listed Horn and Horn Strobe Output candela ratings must be reduced in accordance with 8-175 16--33 24-Volt Nominal this table. S ' h S d Volts Volts Reverberant Anechoic StrobeOutput Listed Candela Candela rating at —40°F 15 Do not use below 32°F 15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 1185 wc Position oun Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 tSettings 7, 8, and 9 are not available on 2-wire horn strobe. AVDS01201 SpectrAlert Advance Diaqrams 2.5" 3- Wall-Mount Horn Strobes 'a erproof Back Box Wall -Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Wall Horn Strobes P2RK*t 2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P2RHK*t 2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) P2WK*t 2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2WHK*t 2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) P4RKt 4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK*t Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) SRHK*t Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) SWK*t Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) SWHK*t Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) Horns HRKt Horn, Red, Outdoor (includes plastic weatherproof back box) Accessories SA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box Notes: * Add "-P" to model number for plain housing (no "FIRE" marking on cover), e.g., P2RK-P. t Add "-R" to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW. "Standard cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. "High cd" refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. SYSTEM ©o12 System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensoccom SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 or current product information,AVDS01 Di201 heiatestversionof his data sheet. S0101 • 3/12 O,�� .SYSTEM � SENSOR- SSM/SSV Series Alarm Bells System Sensor's SSM and SSV series alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features • Approved for indoor and outdoor use • Low current draw • High dB output • Available in six-inch, eight -inch, and ten -inch sizes • AC and DC models • DC models polarized for use with supervision circuitry • Mount directly to standard four -inch square electrical box indoors • SSM and SSV series come pre -wired Agency Listings & ' Fm gAPPROVED s MEA R approved S4011 C5549 3005255 7135-1653:0217 331-01-E Reliable Performance. The SSM and SSV series provide loud resonant tones. The SSM series operates on 24VDC and are motor driven, while the SSV series operates on 120VAC utilizing a vibrating mechanism. Simplified Installation. For indoor use, the SSM and SSV series mount to a standard four -inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used. The SSM and SSV series come pre -wired, to reduce installation time. The SSM series incorporates a polarized electrical design for use with supervision circuitry. SSM/SSV Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 678710-(specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi -flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4-square electrical box having a maximum projection of 21/2-. Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA. Physical/Operating Operating Temperature Range —31°Fto1407 Operating Voltage SSM series: 24 VDC SSV series:120 VAC Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years Electrical Specifications Model Gong Diameter (inches) Nominal Voltage Operating Voltage Maximum Current Sound Output (dBA) Limit SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 82 SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 81 SSV120-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96 to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 * Sound output measured at Underwriter Laboratories, as specified in UL464 Ordering Information r SSM24-6 SSM24-6A I- Bell, 6-,24VDC, Polarized, 82dBA SSM24-8 SSM24-8A Bell, 8-,24VDC, Polarized, 80dBA SSM24-10 SSM24-10A Bell, 10-, 24VDC, Polarized, 81 dBA SSV120-6 SSV120-6A Bell, 6-,120VAC, 85dBA SSV120-8 SSV120-8A Bell, 8-,120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10-, 120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors SYSTEM SENSOR' ®20ha System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Productspecficationssubjecrtochange without notice. Mist systemsensorcom for Phone:800-SENSOR2 • Fax:630-377-6495 current information,A050260-01 -08/11 test -#28e ionofthisdaasheet A05-0260-010.08/11 .82870 Honeywell QGamewel29=l Accessories Fire Alarm Documents (FAD) Cabinet Fire Alarm Storage Cabinet Description The Gamewell-FCI Fire Alarm Documents Cabinet (FAD) is the perfect solution to meet the demanding code standards required today. Gamewell-FCI's primary goal is to manufacture code compliant solutions and this product allows you to do just that. This cabinet is the answer to comply with the NFPA 72 2007, Section 6.2.2.1 requirements which states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit. The Fire Alarm Documents cabinet may be used as a storage box for both printed and digital documentation, enabling you to store the system's test and certified inspection documents, service records, manuals and AS built drawings. This cabinet is constructed of durable 16 gauge steelwith a solid piano hinge and key lock. The cabinet includes a 4GB USB memory flash drive interface. Using a standard USB B connector, the USB flash drive interface allows you to use any standard USB printer cable to upload or download information. This feature allows you to store the fire alarm software in one secure place, so that the Technician can easily access the software and service the system. Fire Alarm Documents Cabinet The Fire Document Box (FDB) interior is designed to contain critical manuals and documents. It is constructed with a durable steel retainer. The FDB has two key ring hooks to hold system keys, and a frame to insert Authorized personnel business cards. In the inner door, you can add the Legend Sheet to record property, system, service, code and AHJ certification information, as well as required documentation. (See Figure 2). Ordering Information: GW-FAD: Fire Alarm Storage Cabinet, Red FEATURES & BENEFITS • Installed with a 4 gigabyte digital flash drive interface with USB B connector • Overall Dimensions 12"Width x 13" Height x 21/4" Depth (30.48 W x 33.02 H x 5.71 D cm) • Offers two, key ring hooks to hold the system keys • Contains a frame plate to insert Authorized Personnel business cards • Constructed with 16 gauge steel box and cover for added security with a solid stainless steel hinge • Coated with a durable, baked -on finish (other colors available) • Builtwith a stainless steel piano hinge with standard 3/4"cat 30 key Lock (other lock assemblies available) • Includes a Legend Sheet to record passwords and system information • Imprinted with white indelible ink, 1" high Lettering labeled, "FIRE ALARM DOCUMENTS" Figure 1 shows the interior enclosure of the Fire Alarm Documents cabinet. Interface requires i"R B-B Connector Hooks Card Holder Legend sheet used to store system information including the following: - Contacts Sign -off Maintenance Test information Alternate locations of additional records Figure 1 Fire Alarm Documents Cabinet Figure 2 shows the Legend Sheet attached to the inner door of the Fire Alarm Document Cabinet (See Figure 2). Property Information Minimum Required Documentation Name of Property: 1 Written narrative providing intent and system description. Address: FN/A FEnclosed or Alt. Location: 2 Riser diagram Description of Property: Occupancy Type: FN/A F Enclosed or Alt. Location: Certification and Approvals 3 Floor plan layout showing location of all devices and control equipment. 16.1 System Installation Contractor: F-]N/A Enclosed or Alt. Location: This system, as specified herein, has been installed and 4 Sequence of operation in either an input/ output matrix or narrative form. tested according to all NFPA Standards cited therein. F1N/A F1 Enclosed or Alt. Location: Signed: 5 Equipment technical data sheets. FIN/A FlEnclosed or Alt. Location: Printed Name: Date: / / 6 Manufacturers published instructions, including operation and maintenance instruction. Organization: FIN/A FlEnclosed or Alt. Location: Title: 7 Battery calculations (where batteries are provided). FIN/A FlEnclosed or Alt. Location: 8 Voltage drop calculations for notification appliance circuits. Phone: 16.5 Authority Having Jurisdiction: I havewitnessed a satisfactory acceptance testof this with F-1N/A FlEnclosed orAlt. Location: system and find it to be installed and operating properly in 9 Completed record of inspection and testing in accordance with 7.6.6 and 7.8.2. accordance with its approved plans and specifications, F-1N/A Enclosed or Alt. Location: its approved sequence of operations, and with all NFPA 10 Completed record of completion in accordance with 7.5.6 and 7.8.2. standards cited herein. F1N/A FlEnclosed or Alt. Location: Signed: 11 Copy of site specific software, where applicable. FIN/A FlEnclosed or Alt. Location: Printed Name: Date: / I 12 Record (as -built) drawings. Organization: FIN/A FlEnclosed or Alt. Location: Title: 13 Periodic inspection, testing, and maintenance documentation in accordance with Section 7.6. FIN/A FlEnclosed or Alt. Location: Phone: Equipment Information: ID No. 1: 14 Records, record retention, and record maintenance in accordance with 7.7. FIN/A FlEnclosed or Alt. Location: Serial: Access Code: ID No. 2: Signed: Date: / / Serial: Access Code: Figure 2 Legend Sheet Fire Alarm Documents (FAD) Cabinet Technical Specifications SYSTEMS FAD: Fire Alarm Documents Cabinet Dimensions: 12° W x 13" H x 21/4" D (30.48 W x 33.02 H x 5.71 D cm) Door Keylock: Barrel lock and piano hinge Dimensions: 3/4" barrel lock and 12" (30.48 cm) piano hinge FAD Cabinet: UL° Listed, constructed of 18 gauge cold rolled steel Cabinet Finish: Red powder coat epoxy finish Cabinet Cover Label: Silkscreen imprinted with white indelible ink, 1" high lettering labeled, "FIRE ALARM DOCUMENTS" Cabinet Keylock: Keylocked with 3/4" barrel lock and 12" (30.48 cm) width stainless steel piano hinge Cabinet Backbox: The backbox includes a 4-hole knockout mounting pattern. Cabinet Frame Plate: insert frame plate accommodates and protects standard 81/2 x 11 manuals and document records. Cabinet Inner Door Label: Legend Sheet attached to the inner door frame for system required documentation, key contacts and code information. Cabinet Flash Drive Interface: 4 Gigabyte (minimum) digital flash memory drive with a standard USB B connector (used to upload and download information) is securely assembled to the interior cabinet. The drive is restricted to Authorized personnel with permission to use secure hardware devices to access the records. Cabinet Key Holder: Two key ring holders and a pre - assembled frame plate to insert Authorized Personnel business cards. For more information Learn more about Gamewell-FCI's Fire Alarm Documents (FAD) Cabinet and other products available by visiting www.Gamewell- FCl.com Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com STANDARDS For a complete listing of all compliance approvals and The Fire Alarm Documents (FAD) Cabinet is designed to certifications, please visit: comply with the following standard: http://www.gamewell- UL Standard: S2580 fci.com/en-US/ documentation/Pages/ AGENCY LISTINGS AND APPROVALS Listings.aspx These listings and approvals apply to the modules Gamewell-FCI° is a registered specified in this document. In some cases, certain trademark of Honeywell modules or applications may not be listed by certain International Inc. approval agencies, or listing may be in process. Consult factory for latest listing status. Space Age Electronics, Inc. is a ©copyright. UL: S2580, Vol. 3 CSFM: 7300-0553-0110 UL° is a registered trademark NFPA: 72 2007 of Underwriter's Laboratories Inc. NEMA ISO 9001 Certification This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subjectto change without notice. 1OS/18 @2Honeywell ©2018Hone Honeywee ll International Inc.