REVIEWED BLD2023-0961+Manufacturer_Specifications_and_Installation_Instructions+7.31.2023_8.37.07_AM+3696972REVIEWED BLD2023-0961 RECEIVED
Aug 01 2023
BY CI OFEDMONDS
DEVEeTPM TSERVICES
q"9 I CITY OF EDMONDS Box Load Results
Y'S Project Location: EDMONDS
Worldwide Refrigeration Quote ID: Item #:
Submitted For: HHS CONSTRUCTION Submitted On: 0712812023
Submitted By STEVE Submitted From: STEVE W/HHS
Identity #: CONSTRUCTION
Tag:
Room Type
General Cooler
Total Loadt
Wall Load
3,201 31.0%
Room Location
Indoor
Infiltration Load
3,196 31.0 %
Room Temperature (deg. F)
35.0
Product Load
1,350 13.0%
Ambient Temperature (deg. F)
75.0
Miscellaneous Load
1,561 15.0%
Room Shape
Rectangle
Safety Load" (10%)
931 9.0%
Total Room Volume (cu.fi)
1,600
Run-time (Hrs)
16.0
11 Room Dimensions
Detail
75.0
Polyurethane
4.0
0.14
28.57
160.0
Wall #1
Wall #2
75.0
Polyurethane
4.0
0.14
28.57
80.0
Wall #3
75.0
Polyurethane
4.0
0.14
28.57
160.0
Wall #4
75.0
Polyurethane
4.0
0.14
28.57
80.0
Ceiling
95.0
Polyurethane
4.0
0.14
28.57
200.0
Floor
60.0
Concrete
1 6.0
1.25
1 4.8
1 200.0
128
BTU/H
Lighting
1.00
Personnel
1.00
85
BTU/H
Motors
1.00
450
BTU/H
Calculated load is based on pulldown data as provided by user, it is the responsibility of the user to ensure appropriate product packaging and air flow conditions prevail to allow product pulldown
temperature within this time period.
' The TOTAL LOAD includes a contingency safety factor to cover the possibility of unforeseen high load conditions, excessive ambient temperatures, unexpected increases of business, or product
packaging changes.