BLD20190869ov EDIV
CITY OF EDMONDS
PHONE: (425) 771-0220 - FAX: (425) 771-0221
121 5TH A VENUE NORTH - EDM ONDS, W A 98020
STATUS: ISSUED 08/14/2019 Pennit#: BLD20190869
BUILDING PERMIT
Expiration Date: 02/14/2020 Project Address: 7320 216TH ST SW #300, EDMONDS
Parcel No: 00580700002901
APPLICANT CONTRACTOR
HEALTHCAREREALTY ALL STAR HEATING& AC INC ALL ST AR HEATING& AC INC
C/O HOSPITAL DISTRICT 2 SNOHO CIO PATRICK CONVERSE C/O PATRICK CONVERSE
PUBLIC PO BOX 70 PO BOX 70
7320 216TH ST SW FALL CITY, WA 98024 FALL CITY, WA 98024
BELLEVUE, W A
(425) 450-9065 (425) 766-1941 (425) 766-1941
LICENSE 9: ALLSTHA044JK EXP:04/12/2021
JOB DESCRIPTION
NEW DUCTWORK AND FAN MIXING BOX FOR NEW OFFICES.
VALUATION: $0
PERMIT TYPE Commercial
PERMIT GROUP: 40 - Mechanical
GRADING: N CYDS: 0
TYPE OF CONSTRUCTION:
RETAINING WALL ROCKERY:
OCCUPANT GROUP�
OCCUPANT LOAD�
FENCE: 0 X 0 FT�)
CODE: 2015
JOTHER - ------- OTHER DESC:
IZONE:
INUMBER OF STORIES: 0
VESTED DATE
INUMBER OF DWELLINGUNITS: 0
LOT 4�
MSTIING AREA
BASEMbN 1, 0 1 ST FLOOR: 0 2ND FLOOR: 0
PROPOSFD AREA
ASEMENT: 0 1 ST FLOOR: 0 2ND FLOOR: 0
3RD FLOOR: 0 GARAGE: 0 DECK: 0 OTHER: 0
FLOOR 0 GARAGE: 0 DECK: 0 OTHER: 0
BEDROOMS- 0 BATHROOMS- 0
IBEDROOMS: 0 BATHROOMS: 0
FRONTSETBACK SIDESETBACK RLARSEFBACK
REQUIRED: PROPOSED: I EQUIRED: PROPOSED: IREQUIREDi PROPOSED
HEIGHT ALLOWED�O PROPOSED�O IREQUIRED: PROPOSED -
SETBACK NOTES
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY, NO
PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION
INSURANCE AND RCW 18:27.
THIS APPLICWON IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HISIIHER DEPUTY AND ALL FEES ARE PAID.
r-a v I C' J)�7
io Alle4ee, 8/14/19
Sign1ure - - Print Name Date
Released By
Date
ATTENTION
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL ORA CERTIFICATE OF
OCCUPANCY HAS BEEN GRANTED. UBCI09/ IBCI 10/ IRCI 10,
= FIRE = APPLICANT = ASSESSOR 7��
C*�
STATUS: ISSUED
BLD20190869
• Final approval on a project or final occupancy approval must be granted by the Building Official prior to use or occupancy of
the building or structure. Check thejob card for all required City inspections including final project approval and final
occupancy inspections.
• Any request for alternate design, modification, variance or other administrative deviation (hereinafter "variance") from
adopted codes, ordinances or policies must be specifically requested in writing and be called out and identified. Processing
fees for such request shall be established by Council and shall be paid upon submittal and are non-refundable.
• Approval of any plat or plan containing provisions which do not comply with city code and for which a variance has not been
specifically identified, requested and considered by the appropriate city official in accordance with the appropriate provision
of city code or state law does not approve any items not to code specification.
• SoundNoise originating from temporary construction sites as a result of construction activity are exempt from the noise limits
of ECC Chapter 5.30 only during the hours of 7:00arn to 6:00pm on weekdays and 10:00arn and 6:00pm on Saturdays, excluding
Sundays and Federal Holidays. At all other times the noise originating from construction sites /activities nmst comply with the
noise limits of Chapter 5.30, unless a variance has been granted pursuant to ECC 5.30.120.
• Applicant, on behalf of his or her spouse, heirs, assigns, and successors in interests, agrees to indemnify defend and hold
harmless the City of Edmonds, Washington, its officials, employees, and agents from any and all claim for damages of
whatever nature, arising directly or indirectly from the issuance for this permit. Issuance of this permit shall not be deemed,to
modify, waive or reduce any requirements of any City ordinance nor limit in any way the City's ability to enforce any ordinance
provision.
I INSPECTIONS
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY
CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS, MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION. PERMIT
TIME LIMIT: SEE ECDC 19.00.005(A) (6)
BUILDING
ENGINEERING (425) 771-0220 EXT. 1326
1. Go to: www.edmondswa.gov
Building Department Inspections
2. Then: Servces
are now scheduled online. If you
FIRE (425) 775-7720
3. Then: Perm its/Development
have difficulties, please call the
4. Then: Online Permit Info
Building Department front desk for
PUBLIC WORKS (426) 771-0235
5: If you don't have one already, create a
assistance during office hours.
login (upper right hand comer)
(425) 771-0220
RECYCLING (426) 275-4801
6: Schedule your inspection
When calling for an inspection please leave the following information: Permit Number, Job Site Address, Type of Inspection
being requested, Contact Name and Phone Number, Date Preferred, and whether you prefer morning or afternoon.
• B-Mechanical Rough In
• B-WSEC Commis ion Report
• B-Mechanical Final
• B-Other
11) C. I g9l
BUILDING PERMIT; Office Use Only
APPLICATION I Permit #:
&zxzo i e;
r% 1 4 C
�V�Wvlllqw" qwlv�.'Wa
Building Division
121 5th Ave N / Edmonds, WA 98020
425.771.0220
For handouts, submittal requirements, permit status and inspection
scheduling information go to: www.edmondswa.go .
PLEASE NOTE: Intake appointments are required for New Single Family
Residences, Large Additions, ADU's, New Commercial, and Major Tenant
Improvement application submittals. If plans are prepared by a profession-
al, electronic files are requested in addition to the hard copies. Please bring
electronic files on a flash drive or coordinate for electronic transfer.
Please call 425-771-0220 to schedule an intake appointment!
JOB SITE INFORMATION/LOCATION: (Where the work is taking place)
Job Site Address: -7 30) 0 P)r,""-5T so
Parcel: STO-7 -00o_ 0�a - 01 - 00
Lot /Unit/Suite #: Subdivision:
PROPERTY OWNER:
Name: 14(!kJhQfAQ-e Re-aLINJ
Mailing Address: I as I- I 14 v-1 rA
City/State/Zip: 190 fictlluc
Phone#:
Email:
OWNER INSTALLATION: *If yes, read and sign*
Will work be performed by the property owner? 11 Yes>d&No
I own, reside in, or will reside in the completed structure. This
installation is being made on property that I own which is not
intended for sale, lease, rent, or exchange according to RCW
18.27.090.
Owner Signature:
APPLICANT/ CONTACT INFORMATION:
Name of Applicant: 81115-141Z
Mailing Address:
City/State/Zip: N
2wo 0
Phone M q,13 0266 041
E-mail: P9-TR irk RJqLL0Ak-HdAr_.Cp
GENERAL CONTRACTOR: (If different from applicant)
General Contractor:
Mailing Address:
City/State/Zip:
Phone M
E-mail:
STATE UIBI #: 703 1� 0
CITY OF EDMONDS BUSI N ESS LICENSE #:
WA STATE CONTRACTOR L & I #: (CCB) & EXPIRATION DATE:
AL_LSThA1)41U' M/01poal— I
TYPE OF PERMIT (Provide
El Accessory Structure/
Detached Garage
Details on Page 2)
0 Addition
El Demolition
JRrMechanical
El New Single Family / Duplex
0 Plumbing
El Fire Sprinkler
0 Remodel
El New Commercial/ Mixed Use
0 Re -Roof
El Signs
0 Tank
El Tenant Improvement
El Other
Remodel Permit fees are based on:
The value of the work performed. Indicate the value (rounded to
the nearest dollar) of all equipment, materials, labor, overhead,
and the profit for the work indicated on this application.
Valuation:
PROPOSED NEW SQUARE FOOTAGE FOR THIS APPLICATION
Basement sq ft: Finished 11 Unfinished El
1st Floor, sq ft:
2nd Floor, sq ft:
Garage/Carport:, sq ft:
Deck/Covered Porch/Patio:
Other sq ft:
PROJECT DESCRIPTION
ADD Milo L)IJ6441,1 fjeW I)Lk& C1110 �'k fo
&eQ PTA KJZZ
/Jeo
4b mco CL5
I certify that the information I have provided on this form/application is true,
correct and complete, and that I am the property owner or duly authorized
agent of the property owner to submit a permit application to the City of
Edmonds.
Print Name:A nt i ck coijaelye
Signature: Date
2____ - - r___ I )*P
L, L_
GENERAL COMMERCIAL DATA
Occupancy Group(s): Occupant Load(s):
Type(s) of Construction:
Fire Sprinklers: Yes El No El
WA STATE ENERGY CODE: If your project affects the building envelope,
mechanical systems, and/or lighting, you must complete the
appropriate WSEC forms.
DEFERRED SUBMITTALS: All commercial building permits that will require
associated plumbing, mechanical, fire sprinkler, and/or fire alarm
permits are applied for separately.
TI / CHANGE OF USE / NEW BLDG: Include TRAFFIC IMPACT worksheet
MECHANICAL EQUIPMENT COUNTS (New and Relocated)
BTUs Gas / Elec Other Qty
A/C Unit /Compressor
Air Handler /VAV
cFti
Boiler
Dryer Duct
Exhaust Fans
Fireplace
Furnace
Heat Pump Unit
Hydronic Heating
Roof Top Unit (Provide eleva-
tions if a Commercial Bldg)
Other:
PLUMBING FIXTURE COUNTS (New, Relocated or re -piped)
QtY Qty
Clothes Washer
Tub/ Showers
Dishwasher
Backflow Device (RPBA, DCDA, AVB)
Drinking Fountain
Pressure Reduction/ Regulator Valve
Floor Drain/Sink
Refrigerator Water Supply
Hose Bibs
Water Heater - Tankless? Y or N
Hydronic Heat
Water Service Line
Sinks
Other:
Toilets
Other:
GAS/FUEL CONNECTION COUNTS (New, Relocated or re -piped 11
BTUs Qty BTUs Qty
A/C Unit
Outdoor BBQ/ Fire pit
Boiler
Stove/Range/Oven
Dryer
Water Heater
Fireplace/ Insert
Other:
Furnace
Other:
MEDICAL GAS, AIR VACUUM COUNTS
(New, Relocated or re -piped)
Qty Qty
Carbon Dioxide
Nitrous Oxide
Helium
Oxygen
Medical Air
Other:
Medical - Surgical Vacuum Other:
DEMOLITION
Type of structure to be demolished:
Square footage of structure to be demolished:
AHERA Survey done? Y / N
7PSCAA Case #:
Critical Areas Determination:
Study Required 13 Conditional Waiver El Waiver El
Fill in Place El Fill Material:,
Removal El
TSi�e of Tank (Gallons)
Critical Areas Determination:
Study Required El Conditional Waiver El Waiver El
GRADE/ FILL/ EXCAVATE
Grading: Cut cubic yards
Fill cubic yards
Cut / Fill in Critical Area: Yes El No EI
GENERAL PROVISIONS
APPLICATIONS: Applications are valid for a maximum of 1 year.
ESLHA Applications, 2 years.
LICENSING: All contractors and subcontractors are required to be licensed
wit Washington State Department of Labor & Industries and have a
current City of Edmonds Business License.
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Mechanilaal Summary MECH-SUM
2012 Washington State Energy Code pliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised May 2015
Project Info
Project Address: 7320 216th ST SW SUITE# 300 EDMONDS 98026
Date 7/10/2019
For Building Dept Use
RECEIVED
JUL 15 2019
Applicant Name: ALLSTAR HEATING
Applicant Address: PO BOX 70 FALL CITY 98024
Applicant Phone: 425-766-1941
Project Description
Briefly describe mechanical systems in
the text box provided
F1 Total Bldg Performance
Total Bldg Performance compliance
includes all mandatory provisions per
C401.2 Option 2. Only MECH-SUM
and MECH-CHK forms required.
E] New Building El Building Addition System Upgrade Liu
INSTALL NEW DUCT WORK TO EXISTING SYSTEM FOR NEW OFFICES 1311-4*2211MG
INSTALL NEW MIX BOX FOR NEW OFFICE
cffy Con
Mechanical Systems Summary
Equip ID
Type of System (Note 1)
Space(s) Served
Compliance
Path
Heating
and Gooling
Fan Flow
Controls
Air
Economizer
(Note 2)
Ventilation
(Note 3)
Energy Recovery
Note I - Provide basic description of system type, for example: unitary rooftop air handier, built-up central air handier single -packaged, split system orpackaged
terminal air conditioner or heat pump; unit heater, warm -air furnace, electric resistance heater, 4-pipe fan coil, VRF system, energy recovery air handier,
make-up air system, ground or water -source heat pump, etc.
Note 2 - If taking an exception to air economizer, select exception taken from drop down menu and complete MECH-ECONO form. Summary definitions of each
exception are listed in MECH-ECONO.
Note 3 - If ventilation "Not applicable' is selected, provide explanation in Project Description box above-
HVAC Hydronic Systems
Hydronic chilled water [] Water -loop heat pump No hydronic systems
Hydronic heating El Geothermal
Service Water Heating
Systems
Equipment Type (s)
El Hot water heating tank(s) El instantaneous El No service water systems
El Dedicated boiler F1 Heat exchange from space heat boiler or
Distribution Type (s) central hot water/steam
Circulation System El On -demand
Mechanical Schedules
Mechanical Paris El MECH EQ For --
Indicate location of equipment compliance inthrmation. If provided on plans then MECH-EQ forms are not required�
however, include on plans all applicable compliance information listed in MECH-EQ tables.
Design�rofa) &a1QciRda'-'ti5ons
El Load calculation summary 0 MECH-LOAD-CALC Form D Equipment, ehofi orrepair
Provide design load calculations for all mechanical systems and equipment serving the building heating, cooling or
ventilating needs, If a load calculation summary is provided with the permit documents that includes all applicable
compliance information then the MECH-LOADLCALC form is not required.
Equipment retrofit and repairprojects where design loads in space(s) sewed have not changed from original design
conditions are not required to perform load calculations.
6LbQ011---0tU1
2012 Washington State Energy Code Compliance Forms for Commercial, Group RI, and > 3 story R2 and R3
Mechanical Summary, pg. 2 MECH-SUM.
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all RI Revised May 2015
0 Air system exceeding 5hp 0 No air system exceeds 5hp
Fan Power
Provide a MECH-FANSYS form for each HVAC system having a total fan system motor nameplate horsepower
exceeding 5 horsepower. Refer to Section C403.2. 10 and MECH-FA NS YS-DO C for requirements and exceptions.
Commissioning Exception
X Commissioning YAll be provided for all applicable systems
Summmy
Commissioning Exceptions:
Describe means of efigibilty for
commissioning exception (capacit3�
F1 Mechanical system(s)
etc) for all systems noted as taking
exception in Mechanical Systems
Summary table. Refer to Section
C408.2 and C408.4 for exceptions.
Service water heating
system(s)
For systems requiring commissioning, Figure C408.1- 2- 1 Commissioning Compliance Checklist shall be submitted to the
code official upon project completion.
Low Energy and Semi -Heated Spaces (Note 6 and 7)
Peak Space
Heating
Cooling
Conditioning
Space
Area Served,
Capacity, Btu/h
Capacity, Btulh
Capacity,
Compliance
Type
Location in Plan(s)
Space(s) Served
square feet
(Note 4)
(Note 5)
Btuth-sf
Check
Notes
Note 4 - Provide total installed heating output capacity of systems serving Low Energy or Semi -Heated space(s) in btuh.
Note 5 - Pfovide total installed cooling capacity of system serving Low Energy space(s) in Blulh. Not allo wed for semPieated spaces. Enter 0 if no cooling.
Note 6 - Refer to Section C 10 1. 5.2 Low Energy Building. Intalled peak space conditioning capacity, heating or cooling, may not exceed 3.4 Btulh-sf
Note 7 - Refer to Section C402.1.4 and Semi -Heated Space definition in Chapter 2. Total heating output capacity may not exceed 8 btuhlsf. Only systems without
electric resistance heating and no cooling are eligible for the wall insulation exception under serni-heated.
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Forms for Commercial Buildings including R2 & R3 over 3 stories and all RI Revised May 2015
Project Address 7320 216th ST SW SUITE # 300 EDMONDS 98026 iDate 7/10/2019
The following information is necessary to check a permit application for compliance with the mechaniciall systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
I
Code Provision
I
Information Required - Must be in permit documents
I
Location in
I
Building Department
(yes,no,na)
Documents
Notes
GENERAL PROVISIONS
Equipment Sizing & Performance
C403.2.1
Load calculations
Load calculations performed per ASHRAE Std 183 or equivalent per Chapter 3
G403.2.2
Equipment and system
Output capacity of heating and cooling equipment and systems do not exceed calculated
sizing
loads, note exceptions taken
C403.2.5
Minimum ventilation
Ventilation (natural or mechanical) provided per IMC; indicate mechanical ventilation is capable
of being reduced to minimum requirement per IMC
C403.2.3 &
C403.2.3.2 &
Equipment minimum
Provide equipment schedules or complete MECH-SUM tables with type, capacity, efficiency,
C403.2.12.1
efficiency
test standard (or other efficiency source) for all mechanical equipment
G403 2.13
Electric motor efficiency
Provide equipment schedule with hp, rpm, and efficiency for all motors; note exceptions taken
C403.2.1 0.1
Fan power limitation
For all applicable systems > 5hp, provide system total narneplate hp in MECH-FANSYS-SUM
form
C403.2 . 10.1
Fan power limitation
For all applicable fan systems > 5hp, verify fan system motor hp or bhp complies with fan
power limits per Table C403.2.10.1 (1), provide MECH-FANSYS form for each system
C403.2.10.2
Motor nameplate hp
Indicate fan motors specified are the smallest available motor hp size greater than fan bnp,
note exceptions taken
C403.2.10.3
Fractional hp fan motors
Indicate fan motors 1/12 to I hp are ECM type or meet minimum efficiency req.
& C403.2.13
C403.2.3
Maximum air cooled chiller
Indicate air-cooled chiller capacity does not exceed air-cooled chiller limit
capacity
C403.2.3.1
Non-standard water-cooled
Full -load and NPLV values for water-cooled oentffugal chiller adjusted for non-standard
chillers
operational conditions
C403.2.12. I.' ,
Centrifugal fan cooling
Large capacity cooling towers with centrifugal fan(s) meet efficiency requirements for axial fan
towers
open circuit cooling towers
C403.2.3
Forced air furnace and unit
Indicate intermittent ignition or IID, flue/draft damper & jacket loss
heaters
C403.2.3.3
Packaged electric
Verify all packaged electric equipment that provides > 20,000 Btu/h cooling capacity and
1heating
heating1cooling equipment
is a heat pump, note in equipment schedule
G403.2.3.4
Humidification Indicate
met1hod of humidification (note requirements for systems with economizer)
k!VAC System Conbrols & Criteria
C403.2.4.1
Them'vostabc controls
Indicate locations of thermostatic control zones on plans, includirtg perimeter systems
C403.2.4.1.1
Heat pump supplementary
Indicate staged heating (compression/supplemental) and outdoor lock -out temperature is set
heat
to 40*F or less
CA03.2.4.2
Setpoint overlap
Indicate 5*F deadband minimum for systems controlling both heating & cooling
(deadband)
G403.2.4.3
Automatic setback and
Indicate zone t-stat controls with required automatic setback & manual override
shutdown
G403.2.4.3.3
Automatic (optimum) start
Indicate system controls #k-d adjust equip start time to match load conditions
C402.4.5.2 &
OSA, exhaust, and relief air
Indicate location of outdoor air supply intake, and exhaust and relief outlet dampers; verify
C403.2.4.4
dampers
Class 1 leakage rating and control type (motorized or gravity); note exceptions taken
G402.4.5.2
Return air dampers
Indicate location of return air dampers; verify motorized control; verffy Class 1 leakage rating
for all return air dampers not integral to packaged equipment
C402.4.5.1
Stairway and shaft vents
Indicate location of stairway and shaft vents, verify Class I leakage rated motorized dampers
and method of activation
G403.2.11
Heating outside a building
Indicate radiant heat system and occupancy controls
C403.2.4.5
Snow mett systems
Indicate shut-off controls based on outdoor conditions
C403.2.4.6
Combustion heating
Indicate modulating or staged control
equipment
C403.2.4.7
Group RI hotellmotel
Indicate method for guest room temperature automatic setback (heating) & set-up (cookig),
systems
confirm adjustment of at least 5*F minimum.
C403.2.4.8 / E
Group R21R3 dwelling and
Indicate 5-2 programmable thermostats in primary spaces with minimum of two setback
sleeping unit systems I
periods; note exceptions taken
C403.2.5.1
Demand controlled
Indicate high -occupancy spaces and systems requiring DCV
+
ventilation
C403.2.5.2
Occupancy sensors
Indicate spaces requiring occupancy4)ased system control and method; or alternate means
provided to automatically reduce OSA when padk* occupied
2012 Washbwdon State Enemy Code Compfiance Forms for Commercial, Group R1, and > 3 story R2 and R3
i
Mechanical Permit Plans Checklist - Page 2 of 4 MECH-CHK'
-1
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised May 2015
Project Address 7320 216th ST SW SUrrE # 300 EDMONDS 98026 iDate 7/10/2019
The following information is necessary to check a permit application for compliance with the mechanicial systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
I
Code Provision
I
Information Required - Must be in permit documents
I
Location in
Documents
Building Department
Notes
(yes,no,n.,l
GENERAL PROVISIONS, CONTINUED
HVAC System Controls & Criteria, Continued
Enclosed loading
Indicate enclosed loading dock and enclosed parking garage ventilation system activation and
C403.2.5.3
dock/parking garage
control method
ventilation
Indicate kitchen hoods requiring make-up air, indicate make-up air source and conditioning
C403.2.5.4.1
Kitchen exhaust hoods
method
Indicate lab exhaust systems requiring heat recovery, method & efficiency; or afternative
C403.2.5.4.2
Laboratory exhaust systems
method taken (VAV, semi -conditioned makeup, or CERM calculation)
C403.2.6.1
Energy recovery (ER) -
Indicate ventilation systems requiring ER, method & efficiency-, note exceptions
ventilation systems
C40326.2
Energy recovery (ER) -
Indicate on -site steam heating systems requiring energy recovery
condensate systems
C403.2.6.3
,ry (ER) -
Energy recove
Indicate remote refrig. condensers requiring EIR and use of captured energy
coolertfreezer condensers
Energy recovery (ER) -
Indicate condenser systems requiring ER to pre -heat service water, indicate ER effectiveness;
C4021.4.6
condenser systems
note exceptions taken
Variable flow control -
Indicate fan and pump motors requiring variable flow control and method (VSD or equivalent
C403. 2.12
fans/pumps
controls)
Variab4e flow control - heat
Indicate heat rejection equipment and cooling tower fans requiring variable flow control and
C403.2. 12.1
. -
rejection equipment
method
Indicate fan systems requiring airflow reduction based on heating and cooling demand; 110te
C403.2.12.2
Large volume fan systems
exceptionstaken
C403.2.12.2
Single zone AC systems
Indicate method of cooling demand -based fan control for sys. > 110,000 Btufh
C403.2.4.10
DDC system capabilities
Identify all DDC system input/output control points arid indicate capability for trending arid
Idemand
response setpoint adjustment
Ducting Systmts
C4103.2.7.1 &
Indicate all ductwork constructed and seated per IMC, C402 leakage requirements and IBC
'&�l
I C403.2.7.3
Duct construction
vapor retarder requirements
C,103.2.7.3.11-'
Duct pressure
ctassifications
Identify location of knN, medium and high pressure ductwork on plans
C40312.7.3.3
High pressure duct leakage
Indicate high pressure duct leakage testing requirements on plans; provide test results to
test
jurisdiction when completed
03.2.7.1/
Duct insulation
Indicate R-value of insulation on ductwork
Piping Systems
lz�
C403.2.8
Piping insulation
Indicate R-value of insulation on piping
C403.2.8.1
Piping insulation exposed to
Indicate method of protection from damageldegredafion
weather
SIMPLE SYSTEMS
Qualifying Systems
Qualifying single zone
Verify unitary or packaged equipment does not exceed capacity limits, does not have active
C403-3
systems
humidifcation or simultaneous heating/cooling
C403.3
Qualifying 2-pipe heating
Verify 2-pipe heating-onty system does not exceed capacity limits
systems
C403.3.2
Hydronic system controls
I Refer to Complex Systems Section C403.4.3
Simple System Economizers
G403.3.1
Air economizer required
Indicate cooling systems requiring economizer controls; note in equipment schedule
C403.3.1
Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with exception(s)
G403.3.1.1.1
Air economizer capacity
Indicate modulating OSA control capability up to 100% OSA; note exceptions taken
C403.3.1.1.2
Integrated air economizer
indicate capability for partial air economizer operation for systems with capacity > 65,000 Btu/h
operation
C403.3.1.1.3
Air economizer high limit
Indicate high limit shut-off control method per Table C403.3.1.1.3(2)
controls
2n12 Wnshinaton State Enerav Code CornDliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Mechanical. Permit Plans Checklist - Page 3 of 4 MECH-CHK
2012 Washington State Energy Code Compliance Forms for Commercist! Buikfings including R2 & R3 over 3 stories and all R1 Revised May 2015
Project Address 7320 216th ST SW SUME # 300 EDMONDS 98026 iDate 7/10/2019
The folkrwing information is necessary to check a permit application for compliance with the mechanicial systems and equipment requirements of the
Washington State Energy Code, Commerciad Provisions.
Applicable
I
Code Section
I
Code Provision
I
Information Required - Must be in permit documents
I
Location in
Documents
Building Department
Notes
(yes,no,na)
COMPLUSYSTEMS
Complex System Economizers
L Uf-'�
C403.4.1
Air economizer required
Indicate cooling systems requiring economizer controls; note in equipment schedule
C403.4.1
Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with exception(s)
For eligible systems where water economizer may be provided in lieu of air economizer,
C403.4. 1.1
Water economizer capacity
indicate system is capable of 100% cooling capacity at 50'F db/45*F wb OSA
Water economizer
Indicate precooling coils and heat exchangers in water economizer system do not exceed
G403.4.1.2
maximum pressure drop
pressure drop limit
C403.4.11.3
Integrated economizer
Indicate capability for partial economizer operation for air or water economizer systems
loperafion
Economizer healing system
Verify control method of HVAC systems with economizers does nort increase building healing
CA03.4.1.4
limped
energy usage during normal operation
Specific System Requirements
C403.4.2 &
VAV fan control
Indicate fans requiring variable flow control and method
C403.2.12
C-403.4.2.11
VAV fan static pressure
I ndk:ate sensor locations on plans; include at least one sensor per major duct branch
No
sensors
C403 ' 4.2.2
VAV fan startic pressure
Indicate fan system static pressure setpoint based on zone requiring most pressure
K I J)
setpoint
I
VAV systems serving
Indicate supply air systems serving multiple zones, method of primary air control, and zones
V
C403.4.5
multiple zones
served; Indicate VAV or note exceptions taken
VAV systems serving
For each air system terminal, indicate the maximum air flaw rate of primary su ppty air during
03
C403.4.5
multiple zones
zone peak cooling and the maximum airflow rates during zone peak healing.
C403.4.5.4
VAV system supply air reset
Indicate controls that automatically reset supply air temp in response to loads
Large capacity cooling
Indicate method of mut&stage or variable control for building cooling system capacity > 300
G403.4
systems
tons
C403.4.7
Hat gas bypass limitation
Indicate cooling equipment unloading or capacity modulation method
C403.4.3
Large capacity boiler
systems
Indicate multi -stage or modulating burner for single boilers > 500,000 Btufh
C403.4.3
Boiler sequencing
Indicate automatic controls that sequence operation of multiple boilers
Chiller / boiler plant pump
Indicate capability to automatically reduce overall plant flow and shut-off flow through chillers &
C403.4.3.5
isolation
boilers when not in use
C403.4 ' 3.6 &
Variable flow control -
Indicate pumps requiring variable flow control & method
C403.2.12
pumps
C403.2.12.1
Variable flow control
Indicate cooling tower fans requiring variable flow control and method
& C403.4.4
cooling towers
Hydronic system part load
Indicate heating & chified water systems have the capability to autornatically reset supply water
C403 4.3.4
-
controls
temp AND reduce flow by � 50% for systems > 300,000 Btu/h
C403.4.3.2
Two -pipe changeover
Indicate deadband, heating/cooling mode scheduling and changeover temperature range
systems
Water loop heat pump -
Indicate capability of central equipment to provide min. 20'F water supply temp deadband
4—
C403.4.3.3.1
deadband
between heat rejection and heat addition modes
C403.4.3.321
Water loop heat pump -
Indicate method used to limit system heat loss when heat rejections is not needed
heat rejection, Zone 4
C403.4.3.3.2.2
Water loop heat pump -
Provide heat exchanger that sepam cooling tower and heat pump loop
heat rejection, Zone 5
Water loop heat pump -
Indicate 2-way isolation valve on each heat pump and variable flow control for systems with
C403.4.3.3.3
isolation
total pump power > 10 hip
C403.5
Walk4n cooler / freezer -
Indicate w/sf & control method for walknin coolier/freezer door anti -sweat heaters
anti -sweat heaters
C403.5 / 6
lCooler / freezer - evaporatorl
Indicate motor type for evaporator and condenser fans < I hp
and condenser fans
2012 Washington State Energy Code Compliance Forms lbr Commercial, Group R1, and > 3 story R2 and R3
Mec,haniqal Permit Plans Checklist - Page 4 of 4 MECH-CHK
20-12 ngton State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised May 2015
Project Address 7320 216th ST SW SU[TE#300 EDMONDS 98026 Pate 7/10/2019
The fbilciwing information is necessary to check a permit application for compliance with the mechanicial systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Sectio
n1
Code Provision
I
Information Required - Must be in permit documents
I
Location in
Documents
Building Department
Notes
(yes,no,na)
SERVICE WATER HEATING
Service Water System
Water -heating equip min.
Provide equipment schedule with type, capacity, efficiency, test standard or other efficiency
C404.2
efficiency
source
C404.3
Temperature controls
Indicate temperature controls have required setpoint capability
C404.4 I
Heat traps
Indicate piping connected to equipment have heat traps on supply & discharge
C404.5
Insulation under water
Indicate R-10 insuleition under electric water heater tanks
heater
G404.6
Service water piping
Indicate R-value of insulation on pip ing; note exceptions taken
insulation
C404.7 18
Circulation systems and
Indicate shut-off capability based on occupancy and periods of limited demand
heat trace shut-aff
Group R-2 service hot water
Indicate method of usage metering for dwelling units served by a central service hot water
G404.9
meters
system
PooK & In -Ground Permanently Installed Spas
Pool heating equip min.
Provide equipment schedule with type, capacity, efficiency, test standard or other efficiency
404'
C 10.1
efficiency
source
Indicate automatic on/off control based on scheduling & accessible ontoff switch on heater that
C404.10.1 / 2
Pool heater on / off controls
operates independent of thermostat setting; note exceptions taken
C404.10.3
Pool covers
Indicate vapor retardant cover and insulation rarting as required
C404.10.3
Pool ssemblyinsulation
Ind" rating of insulation on sides and bottom of pools heated to > WoF
Indicate method, exhaust air temperature reduction and recovered energy use; note
C404.10.4
Heat recovery
exceptions taken
COMMISSIONING
SpwAc System Requirements
Mechanical systems
Indicate all mechanical systems to be commissioned; for those that will not be Comm ss n
C408.2
commissioning
note exception taken
Service water heating
Indicate all service water heating systems to be commissioned; for those that will not be
C408.4
systems commissioning
Commissioned, note exception taken
Provide Commissioning plan for all systems requiring commissioning; include in plan all
C408.1.1
Commissioning plan
required items per this section
C4G8.2.2.1 &
Air system and hydronic
Include in commissioning plan that air and hydronic systems shall be balanced in a manner to
C408.2.2.2
system balancing
first minimize throttling losses, then adjust to meet design flow conditions
Air system balancing
Indicate devices that provide the capability to balance all supply air outlets, zone terminals and
C408.2.2.1
devices
equipment requiring system balancing
Hydronic system balancing
Indicate devices that provide the capability to isolate, balance and measure flow for all
C408.2.2.2
[devices
hydronic, equipment requiring system balancing
Mechanical systems
Provide description offunctional performance testing procedures for all applicable systems
C408.2.3
functional Performance
including: equipment, controls, economizers
testing
Service water heating
Provide description offunctional performance testing procedures for all applicable systems
C-408.4.1
functional performance
including: equipment, controls, pools and spas
testing
C408A.4
I Systems operation training
Indicate required systems operation traii�ing measures to be provided
G408.1 2 &
Indicate required documentation including: record documents, manuals, balancing reports,
C403.1.3
IDocurrientation
commissioning preliminary and final reports
Indicate that Commissioning Compliance Checklist (Figure C408.1.2.1) is required upon
C408.1.2.1
Acceptance report
completion of preliminary commissioning report
14 "
L; i
SUBMITTAL Nailof
Industries Inc.
Project Name: Edmonds Medical - 6.19.19
Project Location:
Engineer:
Contractor:
Contact:
Date: June 19, 2019
Submitted By: AIR REPS, LLC
3290 146TH PL SE BLDG, SUITE# F
BELLEVUE, WA
UNITED STATES, 98007
Telephone:
Fax:
Contact:
(425) 562 - 1150
(425) 562 - 5123
Kendra Porter
RECEVED
JUL 15 2019
BUILDING
Dimensions are in inches (mm) Page 1 of 4
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
rD
(D
=.
Ln
Model
(D
rn
cr
rD
r)
rD
w
0
00
Unit Size
0
(D
x
Outlet Size
00
o
jPrimary Max AF (cfm)
Io
jPrimary Min AF (cfm)
000
ICIg Fan Max (cfm)
Lo
linlet SP (in wg)
i,j
Ln
jOutlet SP (in wg)
1-4
IFan Volt
M
Motor Type
lApplication Watts @Max Fan
pplication Amps @Max Fan
lApplication HP @Max Fan
�Application Watts Per CFM
Ln
-�'t
0
IRated Watts
-
IFLA
IMOP
M CA
-u4-'
R a d N C
Dis NC
:E,Calc
Method
00
Htg AF (cfm)
KW
cn
MBH (mbh)
1-4
�volt
IIPhase
IIStages
w
Htr Amps
'V�Jl
EAT (oF)
-
LAT ('F)
PROJECT SCHEDULE -N- a flo -
Edmonds Medical - 6.19.19 -- - r
Terminal Units tridustries Inc.
Item Qty Model
Unit Max Flan kW
Option Codes Size Primary Airflow
1 1 D35SE 308 800 800 1.75
308- SP- V6- NB- AT- FSC- OR- QP- FG- FN- FR- FS- FN2- 277/1- 1STG- Al- BB- BC- BE
Dimensions are in inches (mm)
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice. Page 2 of 4
D35SE Fan Powered Terminal Unit with Electric Heat e Series Flow IC ] Nahl -0
* Constant Or Variable Volume e Digital Controls Industries Inc.
Item: 1; Tags:
01k z
NOW -
118'(3)
lus"
0000(
— " 00C
(203) 0 0( INDUCED AM
IN
00C INLET FILTER
001,
FILTER L
N M--------- ----
1 1 i *
ELECTRIC (25)
HEATER W
,HINGED FOR 1. —
CLEMENT (25)
REMOVAL
I
15'
(381)
63/4*'171)----j,
(152)
PRIMARY
LINE
H -
ruE
X
(279)
VOLTAGE
1 ' (25)
AIR
ENCLOSURE
2
Right-hand controls location shown
DIMENSIONAL DATA
H
c T us
Intertek
Unit
Inlet
Inducted Air Inlet
Outlet Duct Size
Size
Size
W
H
L
IWxIH
FxG
K
8
18
18
36
12 x 14
10 1/4 x 10 1/2
151/2
21/2
151/4
3
(203)
(457)
(457)
(914)
(305 x 356)
(260 x 267)
(394)
(64)
(387)
Filter
Motor
277V
Size
HP
Motor only FLA
14 x 16
3.1
(356 x 406)
FLA = Full load amperage. All motors are single phase/60 Hz
Refer to Nailorl SelectWorks for application performance data
*The ECM is a variable horsepower motor
FEATURES
* 18 ga. (1.31) galvanized steel channel frame with 20 ga. (1.00) casing components
* 16 ga. (1.61) galvanized steel inclined opposed blade damper, 45* rotation, CW to close
* Multi -point averaging Diamond Flow Sensor. Aluminum construction. Supplied with balancing tees
Project: Edmonds Medical - 6.19.19
Engineer:
Contractor:
Date:
Version No:
6/19/2019
3.74.02 Rev.04
Dimensions are in inches (mm)
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
Page 3 of 4
D35SE Fan Powered Terminal Unit with Electric Heat e Series Flow 0 Nailor
* Constant Or Variable Volume * Digital Controls Industries Inc.
Full size access panels on three sides
Discharge opening designed for flanged duct connection
Ultra -high efficiency ECM fan motor, EPIC fan volume controller
Class A 80/20 Ni/Cr wire
Externally insulated heater element wrapper
Automatic reset high limit cut-outs (one per element)
Damper Actuator: Not Provided
SP - Single point electrical connection
V6 - Fan Motor Voltage: 277V EPIC ECM/1 phase
N13 - Controls: By Others (Field Mounted)
AT - EPIC Fan Card: Auto/Dynamic volume control, 0-10 Vdc
FSC - EPIC Card: Fan status (on/off) contact closure
OR - Right-hand controls location standard (shown)
QP - Fan motor fusing
• FG - Steri-Liner
• FN - Full NEMA 1 type 24V Controls Enclosure
• FR - Induced Air Filter: I" Throwaway
* FS - Hanger brackets
* FN2 - 90' line voltage enclosure with hinged access door opening
* 2771 - Electric Coil: 277 volt/1 phase/2-wire
1STG - Electric Coil: 1 Stage
Al - Positive pressure mechanical air proving switch
BB - Door interlock disconnect switch
BC - Quiet contactors
BE - Main line fusing (electric coil unit)
OR/FN2 - Top View Orientation- Controls Location
AIRFLOW Right Hand Controls Location
40. . r]
OR.
FG - Steri-Liner
* 13/16" (21) thick rigid fiberglass with a fire resistant reinforced aluminum FSK (foil-scrim-kraft) facing
Meets requirements:
- UL 181 & 723
• NFPA 90A & 90B
• ASTM E 84, C 665, C 1071, C 1338, G21 & G22
Project: Edmonds Medical - 6.19.19
Engineer:
Contractor:
Date:
Version No:
6/19/2019
3.74.02 Rev.04
Dimensions are in inches (mm) Page 4 of 4
Noilor Industries Inc, reserves the right to change any information concerning product or pricing without notice.
VAV TERMINAL UNITS
Na'lor'l LINER OPTIONS
Industries Inc. TYPE: STERI-LINER
INSULATION CHARACTERISTICS
Material: Rigid board form fiberglass with a thermosetting resin. Fire resistant reinforced aluminum
foil-scrim-kraft (FSK) facing.
Thickness: 13/16" (21). (37N, 37S, 37SST and 33SZ Size 30 Low Profile Fan Powered Terminal Units use
1/2" (13) material).
Density: 4.1 lb/cu.ft. (66 kg/ml).
Thermal Conductivity: 0.23 BTU -in / hr-ft'-OF @ 750F (0.033 W / m-OK @ 240C).
(K-Factor)
Thermal Resistance: 3.5 hr-W-OF / BTU (0.76 M2_OC / W).
(R-Value)
Flame Spread: 25
Smoke Density: 50
Mold Growth: None
STANDARD AND CODE COMPLIANCE
UL 181 Class I
ASTM E84 and UL 723 Flame/Smoke (25/50)
NFPA 90A and 90B
ASTM C 1071 Air Velocoty (2000 fpm max.)
ASTM C 665
ASTM C 1338, G21 and G22 Fungi and Bacteria Resistance
ACOUSTICAL PERFORMANCE
Correction factors to cataloged sound power level data (standard liner) are shown below.
Single Duct Terminal Units - 3000 Series Basic Unit * All sizes.
Octave Band 2 3 4 5 6 7 NC Impact
Center Frequency (Hz) 125 250 500 1000 2000 4000 (Average)
Discharge Sound 0 0 0 0 0 0 0
Radiated Sound -1 -2 -2 -3 -3 -3 -2
Single Duct Terminal Units with Integral Attenuator * 3000 Series 9 All Sizes
Octave Band
2
3
4
5
6
7
NC Impact
Center Frequency (Hz)
125
250
500
1000
2000
4000
(Average)
Discharge Sound
+2
+2
+3
+5
+7
+8
+3
Radiated Sound
-1
-2
-2
-3
-3
-3
-2
Fan Powered Terminal Units e 33SZ, 35N, 35S, 37N and 37S Series - All sizes
Octave Band
2
3
4
5
6
7
NC Impact
Center Frequency (Hz)
125
250
500
1000
2000
4000
(Average)
Discharge Sound
0
0
0
0
0
0
0
Radiated Sound
+2
+3
+6
+11
+10
+3
+3
Fan Powered Terminal Units * 35SST and 37SST "Stealth" Series * All sizes
Octave Band
2
3
4
5
6
7
NC Impact
Center Frequency (Hz)
125
250
500
1000
2000
4000
(Average)
Discharge Sound
0
0
0
0
0
0
0
Radiated Sound
-5
-4
-4
0
+3
+5
-4
SCHEDULETYPE
PROJECT Edmonds Medical - 6.19.19
ENGINEER DATE B SERIES S�WING NO.
CONTRACTOR 8 - 19 - 16 1 VAV.ACC. 11 - 19 - 12 1 VAV - SL
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNITS MONO&
Recommended Primary Valve Airflow Ranges For All Fan Powered Terminal Units
The recommended airflow ranges below are for fan powered
terminal units with pressure independent controls and are presented
as ranges for total and controller specific minimum and maximum
airflow. Airflow ranges are based upon maintaining reasonable
sound levels and controller limits using Nailor's Diamond Flow
Sensor as the airflow measuring device, For a given unit size, the
minimum, auxiliary and the maximum flow setting must be within the
range limits to ensure pressure independent operation, accuracy
and repeatability.
Minimum airflow limits are based upon .02" w.g. (5 Pa) differential
pressure signal from Diamond Flow Sensor on analog/digital
controls and .03" (7.5) for pneumatic controllers. This is a realistic
low limit for many transducers used in the digital controls industry.
Check your controls supplier for minimum limits. Setting airflow
minimums lower, may cause hunting and failure to meet minimum
ventilation requirements.
Imperial Units, Cubic Feet per Minute
The high end of the tabulated Total Airflow Range on pneumatic
and analog electronic controls represents the Diamond Flow
Sensor's differential pressure reading at 1 " w.g. (249 Pa). The high
end airflow range for digital controls is represented by the indicated
transducer differential pressure.
ASHRAE 130 "Performance Rating of Air Terminals" is the method
of test for the certification program. The "standard rating condition"
(certification rating point) airflow volumes for each terminal unit size
are tabulated below per AHRI Standard 880. These air volumes
equate to an approximate inlet velocity of 2000 fpm (10.2 m/s).
When digital or other controls are mounted by Nailor, but supplied
by others, these values are guidelines only, based upon experience
with the majority of controls currently available. Controls supplied
by others for factory mounting are configured and calibrated in the
field. Airflow settings on pneumatic and analog controls supplied by
Nailor are factory preset when provided.
Range of Minimum and Maximum Settings, cfm
Airflow at
Pneumatic 3000
Analog
Digital
Total
2000 fpm
Inlet
Inlet
Airflow
Controller
Electronic Controls
Controls
Inlet
— Transducer Differential Pressu e (w.g.)
Size
Type
Range ,
Velocity
Min.
Max.
Min.
Max.
Min.
Max.
cfm
(nom.), cfm
.03
1.0
.02
1.0
.02
1.0
1.25
;i- 1.5
4
0-225
150
30
180
25
180
25
180
200
225
5
0-400
250
55
325
45
325
45
325
360
400
6
0-550
400
80
450
65
450
65
450
500
550
7
0-800
550
115
650
95
650
95
650
725
800
8
Round
0- 1100
700
155
900
125
900
125
900
1000
1100
—9
0- 1400
900
200
1150
165
1150
165
1150
1285
1400
10
0-1840
1100
260
1500
215
1500
215
1500
1675
1840
12
0-2500
1600
355
2050
290
2050
290
2050
2290
2500
14
0-3370
2100
475
2750
390
2750
390
2750
3075
3370
16
0-4510
2800
640
3700
520
3700
520
3700
4120
4510
12
0-2500
1600
355
2050
210
2010
210
2050
2300
2500
14
Flat
0-3125
2100
440
2550
360
2550
360
2550
2850
3125
16
Oval
0-3725
2800
525
3040
430
3040
430
3040
3400
3725
18
0-5265
3500
750
4300
610
4300
610
4300
4800
5265
14x 8
R,ct.
0-2450
1560
350
20
290
2000
290
2000
2240
2450
.14 1 (0
0-2950
1900
420
2400
00
340
2400
340
2400
2700
2950
Metric Units, Liters per Second
Range of Minimum and Maximum Settings, Vs
Total
Airflow at
Pneumatic 3000
Analog
Digital
Inlet
Inlet
Airflow
10.2 m/s
Controller
Electronic Controls
Controls
Inlet
Transducer Differential Pressure Pa
Size
Type
Range,
Velocity
Min.
Max.
Min.
Max.
Min.
Max.
vs
(nom.), Vs
7.5
249
5
249
5
249
311
�t 374
1
4
0-106
71
14
85
12
85
12
85
94
106
5
0-189
118
26
153
21
153
21
153
170
189
6
0-260
189
38
212
31
212
31
212
236
260
7
0-378
260
54
307
45
307
45
307
342
378
8
Round
0- 519
330
73
425
59
425
59
425
472
579
9
0- 661
425
94
543
78
543
78
543
606
661
10
0-868
519
123
708
101
708
101
708
790
868
12
0-1180
755
168
967
137
967
137
967
1081
1080
14
0-1590
991
224
1298
184
1298
184
1298
1451
1590
16
0-2128
1321
302
1746
245
1746
245
1746
1944
2128
12
0-1180
755
168
967
137
967
137
967
1085
1180
14
Flat
0-1475
991
208
1203
170
1203
170
1203
1345
1475
16
Oval
0-1758
1321
248
1435
203
1435
203
1435
1604
1758
18
0-2485
1652
354
2029
288
2029
288
2029
2265
2485
14 x 8
Rect.
0-1156
736
165
944
137
944
137
944
1057
1156
14: 1(01
0-1392
897
198
1133
160
1133
160
1133
1274
1392
I
Z
V
0
M
M
M
M
3
Z
Z
=i
(A
C13
FAN POWERED TERMINAL UNITS CONailor"
Performance Data Explanation
Sound Power Levels vs. NC Levels
Discharge Sound
Table El of Appendix E provides typical discharge sound attenuation
values for three sizes of terminal unit.
The Nailor Model Series: 35S, 35SST, 37S, 37SST, 35N and
1. Small box; Less than 300 cf m (142 I/s)
37N fan powered terminal unit performance data is presented in
[Discharge Duct 8" x 8" (203 x 203)].
two forms.
2. Medium box; 300 — 700 cfm (142 - 330 I/s)
The laboratory obtained discharge and radiated sound power
[Discharge Duct 12" x 12" (305 x 305)].
levels in octave bands 2 through 7 (125 through 4000 Hz) center
3. Large box; Greater than 700 cfm (330 I/s)
frequency for each unit size at various flow rates and inlet static
[Discharge Duct 15" x 15" (381 x 381)].
pressures is presented. This data is derived in accordance with
ANSI/ASHRAE Standard 130 and AHRI Standard 880. This data is
These attenuation values have been used to tabulate Discharge NC
raw with no attenuation deductions and includes AHRI Certification
levels applied against the terminal airflow volume and not terminal
standard rating points.
unit size.
Nailor also provides an NC Level" table as an application aid
The following tables provide the calculation method for the discharge
in terminal selection, which include attenuation allowances as
sound total attenuation values based on AHRI Standard 885.
explained below. The suggested attenuation allowances are typical
Small Box Octave Band
and are not representative of specific job site conditions. It is
recommended that the sound power level data be used and a
<300 cfm 2 3 4 5 6
7
detailed NC calculation be performed using the procedures outlined
Environmental Effect 2 1 0 0 0
0
in AHRI Standard 885, Appendix E for accurate space sound levels.
5 ft. (1.5 m) 1" (25) Duct Lining 2 6 12 25 29
18
Branch Power Division (11 outlet) 0 0 0 0 0
0
Explanation of NC Levels
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct 5 10 18 19 21
12
Tabulated NC levels are based on attenuation values as outlined
End Reflection 10 5 2 1 0
0
in AHRI Standard 885 Procedure for Estimating Occupied Space
Space Effect 5 6 7 8 9
10
Sound Levels in the Application of Air Terminals and Air Outlets".
Total Attenuation Deduction 24 28 39 53 59
40
AHRI Standard 885, Appendix E provides typical sound attenuation
values for air terminal discharge sound and air terminal radiated
Medium Box Octave Band
sound.
29
As stated in AHRI Standard 885, Appendix E, These values can
300 — 700 cfm 2 3 4 5 6
7
W
i—
be used as a quick method of estimating space sound levels when
Environmental Effect 2 1 0 0 0
0
0
a detailed evaluation is not available. The attenuation values are
5 ft. (1.5 m) 1" (25) Duct Lining 2 4 10 20 20
14
W
29
required for use by manufacturers to catalog application sound
Branch Power Division (2 outlets) 3 3 3 3 3
3
A
levels. In product catalogs, the end user environments are not
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct 5 10 18 19 21
12
0
known and the following factors are provided as typical attenuation
End Reflection 10 5 2 1 0
0
:116
values. Use of these values will allow better comparison between
Space Effect 5 6 7 8 9
10
Z
manufacturers and give the end user a value which will be expected
Total Attenuation Deduction 27 29 40 51 53
39
19
to be applicable for many types of space.
Y6
Radiated Sound
Large Box Octave Band
Table El of Appendix E provides typical radiated sound attenuation
>700 cfm 2 3 4 5 6
7
values for three types of ceiling: Type 1 — Glass Fiber; Type 2 —
Environmental Effect 2 1 0 0 0
0
Mineral Fiber; Type 3 — Solid Gypsum Board.
5 ft, (1.5 m) 1" (25) Duct Lining 2 3 9 18 17
12
Since Mineral Fiber tile ceilings are the most common construction
Branch Power Division (3 outlets) 5 5 5 5 5
5
used in commercial buildings, these values have been used to
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct 5 10 18 19 21
12
tabulate Radiated NC levels.
End Reflection 10 5 2 1 0
0
The following table provides the calculation method for the radiated
Space Effect 5 6 7 8 9
10
sound total attenuation values based on AHRI Standard 885.
Total Attenuation Deduction 29 30 41 51 52
39
Octave Band
1 . Flexible duct is non-metallic with 1 (25) insulation.
2 3 4 5 6 7
2. Space effect (room size and receiver location) 2500 ft.3
Environmental Effect 2 1 0 0 0 0
(69 M3) and 5 ft. (1.5 m) distance from source.
Ceiling/Space Effect 16 18 20 26 31 36
Total Attenuation Deduction 18 19 20 26 31 36
The ceiling/space effect assumes the following conditions:
1. 5/8" (16) tile, 20 Ib/ft3 (320 kg/M3) density.
2. The plenum is at least 3 feet (914) deep.
3. The plenum space is either wide (over 30 feet (9 m)] or lined with
insulation.
4. The ceiling has no significant penetration directly under the unit.
For a complete explanation of the attenuation factors and the
procedures for calculating room NG levels, please refer to the
acoustical engineering guidelines at the back of this catalog and
AHRI Standard 885.
'FA 32
FAN POWERED TERMINAL UNITS e 35S SERIES CONailor"
Performance Data
ECM Motor Fan Curves - Airflow vs. Downstream Static Pressure
35S Series - Series Flow
Vs CFM Unit Size 1 Vs CFM Unit Size 2
283
600
260
550
236
500
212
450
189
400
165
350
0
_3
LL
142
300
118
250
94
200
71
150
47
100
24
50
425
900
MAX. 1, 2 & 3 ROW
378
800
H. W. COIL
330
700
283
600
0
_j
,
236
500
cc
189
400
142
300
94
200
47
100
MINIMUM
0.0 0.1 0.2 0.3 0.4 0.5 "w.g. 0.0 0.1 0.2 0.3 0.4
0 25 50 75 100 125 Pa 0 25 50 75 100
DISCHARGE STATIC PRESSURE
Vs CFM Unit Size 3
613 1
566 1
519 1
472
425
378
0
_j
LL
R M 330
283
236
189
142
94
0.0
0
Electrical Data
Us
CFM
755
1600
MAX. COOLING
I ROW HW CO:L
2 L
3 ROW HW COIL
661
1400
566
1200
472
1000
0
_j
LL
cc
41
378
800
283
600
189
400
DISCHARGE STATIC PRESSURE
Unit Size 4
MAX. COOLING
I ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
0.5 "w.g.
125 Pa
MAX. COOLING
HW COIL:
1 ROW
2 ROW
3 ROW
94 200 1 1 1 i I I
0.1 0.2 0.3 0.4 0.5 "w.g. 0.0 0.1 0.2 0.3 0.4 0.5 "w.g.
25 50 75 100 125 Pa 0 25 50 75 100 125 Pa
DISCHARGE STATIC PRESSURE DISCHARGE STATIC PRESSURE
NOTES:
Unit
EPIC ECM Motor FLA
Size
Motor HPF120V
208V
240V
277V
1
2.4
1.6
1.5
1.5
2
4.0
2.9
2.8
2.6
3
4.8
3.3
3.2
3.1
F-4
6.9
4.6
4.6
4.4
The ECM is pressure independent and Airflow can be set to operate on
constant volume in operation at factory horizontal performance line at any point
or field set point within the shaded area. within shaded area using the solid state
Airflow does not vary with changing volume controller provided.
static pressure conditions. The motor Fan curves shown are applicable to 120,
compensates for any changes in external 208, 240 and 277 volt, single phase
static pressure or induced air conditions
M 1 A; ECM's. ECM's, although DC in operation,
I
Z
V
0
M
X
M
M
9
Z
Z
The EPIC ECIVI is a variable horsepower motor. suc, as te, oa ng. include a built-in AC/DC converter.
Refer to Selectworks schedule for actual power
consumption.
FLA = Full load amperage.
All motors are single phase/60 Hz.
2-28-19 C43
. FAN POWERED TERMINAL UNITS * 35S SERIES
KONailor"
641
Z
'Z
D
L
Z
Performance Data
ECM Motor Fan Curves — Airflow vs. Downstream Static Pressure
35S Series - Series Flow
Vs CFM Unit Size 5 VS CFM Unit Size 6
991
2100
897
1900
802
1700
708
1500
613
1300
0
_3
LL
519
1100
425
900
330
700
236 500
142 300
47 100
NO HEAT/
1133
2400
ELECTRIC HEAT
1 ROW HW CO:L
2 ROW HW CO L
1038
2200
3 ROW HW COIL
944
2000
849
1800
755
1600
661
1400
566
1200
472
1000
378
800
283
600
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
0.0 0.1 0.2 0.3 0.4 0.5 "w.g. 0.0 0.1 0.2 0.3 0.4 0.5 "w.g.
0 25 50 75 100 125 Pa 0 25 50 75 100 125 Pa
Vs CFMI
1888 4000
1652 3500
1416 3000--
1180 2500
0
LL
cc
R 944 2000
708 1500--
472 1001 t
236 500
0.0
0
Electrical Data
DISCHARGE STATIC PRESSURE
Unit Size 7
NO HEAT/
ELECTRIC HEAT
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
MINIMUM
0"1 0.2 0.3 0.4 0.5 "w.g.
25 50 75 100 125 Pa
DISCHARGE STATIc PRESSURE
NOTES:
Unit
EPIC ECM Motor FLA
Size
Motor HP
120V
208V
240V
277V
5
9.6
6.2
5.9
5.8
6
12.2
7.9
7.7
7.6
7
17.5
11 .1
11.4
11.4
DISCHARGE STATIC PRESSURE
The ECM is pressure independent and Airflow can be set to operate on
constant volume in operation at factory horizontal performance line at any point
or field set point within the shaded area. within shaded area using the solid state
Airflow does not vary with changing volume controller provided.
static pressure conditions. The motor Fan curves shown are applicable to 120,
compensates for any changes in external ;lna 'JAr) 4 1,)77 -If �i� I- h-
The EPIC ECIVI is a variable horsepower motor. static pressure or induced air conditions I I V F
Refer to Selectworks schedule for actual power such as filter loading. ECM's. ECM's, although DC in operation,
consumption. include a built-in AC/DC converter.
FLA = Full load amperage.
All motors are single phase/60 Hz.
C44 2-28-19
FAN POWERED TERMINAL UNITS 9 35S SERIES CONailor�
Performance Data * AHRI Certification and Performance Notes
Model Series 35S - Series Flow - Basic Unit - AHRI Certification Rating Points
Fiberglass Liner
n
Size
S
cfm 1/2
ry
Willow
cfm I/s
Min. wet
APS
"w. g. Pa
APs'vrt .2V W4,(62 ftj
Adleted
P
2 3 4 5 6 7
'2 3 4 5 6 7
2 3 --i—_ 5 6 7
1
5
400 189
105
74 70 66 64 60 57
64 60 55 48 44 40
400 189
0.12 30
67 62 57 54 57 58
2
1 8
1 700 330
155
170 68 64 63 60 57
62 58 53 51 44 40
700 330
0.08 19
68 63 58 56 57 61
3
10
1100 519
270
173 72 71 69 65 63
65 62 59 56 52 48
1100 519
0.03 7
68 65 62 62 61 62
4
12
1550 731
430
80 79 74 74 70 69
68 64 58 57 55 53
1550 731
0.05 12
73 70 66 65 62 63
5
14
2050 967
800
82 79 74 75 72 71
74 69 62 60 57 54
2050 967
0.04 10
73 70 65 62 62 63
6
14
2100 991
790
77 77 75 77 74 73
72 69 62 60 59 57
2100 991
0.06 15
77 72 65 63 63 64
7 1
16 .
2800 1321
760
76 72 70 69...66 64,70
67 61 55 50 49,2800
1321
0.08 19 �
71 69 66 61 58 59
Motor = ECM,
Primary air valve is closed and therefore primary cfm is zero.
Performance Notes for Sound Power Levels:
Discharge (external) static pressure is 0.25" w.g. (63
Pa) in all cases, which is the difference (APS) in static
pressure from terminal discharge to the room.
Discharge Sound Power Levels (SWIL) now include
duct end reflection energy as part of the standard
rating. Including the duct end correction provides sound
power levels that would normally be transmitted into an
acoustically, non -reflective duct. The effect of including
the energy correction to the discharge SWL, is higher
sound power levels when compared to previous AHRI
certified data. For more information on duct end reflection
calculations see AHRI Standard 880.
2. Radiated sound power is the breakout noise transmitted
through the unit casing walls.
Ratings are certified in
accordance with AHRI
Standards.
3. Sound power levels are in decibels, d13 re 10-12 watts.
4. All sound data listed by octave bands is raw data without
any corrections for room absorption or duct attenuation.
Dash (-) in space indicates sound power level is less than
20 d13 or equal to background.
5. Min. inlet APs is the minimum operating pressure of the
primary air valve section.
6. Asterisk (*) in space indicates that the minimum inlet static
pressure requirement is greater than 0.5" w.g. (1125 Pa) at
rated airflow.
7. Data derived from independent tests conducted in
accordance with ANSI / ASHRAE Standard 130 and AHRI
Standard 880.
C48
FAN POWERED TERMINAL UNITS * 35S SERIES CO Nailore
Performance Data * Discharge Sound Power Levels
Model Series 35S 9 Series Flow - Basic Unit
Fiberglass Liner
I
17
n e
r-ThrZoMw
-t W5
W -W
e7lfmr 0s"#:--'-`-'T"--"-
rw.g. 125N)APsl'.
07
PS
Slie
Size
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
Cfm lls
"we. Us
550 260
0.22 54
79 76 71 69 66 63
78 75 69 67 64 62
78 75 69 67 64 61
78 75 70 68 64 62
80 78 71 69 65 63
79 78 71 69 65 63
400 189
0.12 30
70 67 63 60 56 53
70 67 62 60 56 53
71 69 63 60 57 53
72 70 64 60 57 54
72 72 65 60 57 54
HAF1121-STY, MI
67 62 59 55 50 46
6
300 142
0.07 17
65 61 56 53 48 44
67 62 57 54 49 45
69 66 59 55 50 46
71 69 61 56 51 48
71 69 62 57 52 49
200 94
0.04 9
58 52 47 - - -
58 51 45 - - -
58 52 45 41 - -
64 59 50 44 38 33
64 60 55 48 42 38
64 61 55 48 43 39
100 47
0.01 3
57 44 34 - - -
56 44 35 - - -
57 47 37 28 - -
58 49 42 32 25 24
58 50 47 35 29 28
59 50 48 37 31 30
550 260
0.06 15
79 76 71 69 66 63
77 74 68 67 64 62
77 74 68 67 64 61
77 74 69 68 64 62
79 77 70 69 65 63
78 77 70 69 65 63
400 189
0.03 8
74 70 66 64 60 57
69 67 63 59 56 53
69 67 62 59 56 53
70 68 63 59 57 53
71 69 63 59 57 54
71 71 64 60 57 54
8
300 142
0.02 5
67 62 59 55 50 46
63 60 55 52 48 44
65 61 56 53 49 45
67 65 58 54 50 46
69 67 60 55 51 48
69 68 61 56 52 49
200 94
0.01 2
58 52 47 - - -
56 49 44 - - -
56 50 45 40 - -
62 58 49 43 37 33
62 58 54 47 41 38
62 60 54 47 42 39
100 47
10.01 1
57 44 34 - - -
54 43 34 - - -
55 46 36 28 - -
56 48 41 31 25 23
56 49 45 34 29 28
57 49 47 36 31 29
550 260
0.20 50
66 64 61 58 55 52
70 66 62 58 54 51
72 68 62 59 55 52
72 69 62 58 54 50
74 71 63 58 54 51
75 72 63 58 54 52
6
400 189
0.11 27
63 60 57 54 50 45
63 60 56 52 48 42
64 61 56 52 48 42
69 65 57 52 48 43
71 68 58 53 48 44
71 69 59 53 48 45
200 94
0.04 10
57 52 48 44 37 28
58 52 46 42 34 26
62 55 47 42 35 27
63 58 49 43 36 29
63 59 51 44 37 32
63 59 52 45 38 33
2
850 401
0.11 28
74 72 67 68 64 63
76 74 68 67 64 62
78 76 70 68 65 63
76 74 68 66 63 61
77 75 68 66 63 61
78 76 68 66 63 61
91
700 330
0.08 19
73 70 65 63 60 57
76 73 67 65 62 59
73 71 64 62 59 56
75 73 65 62 59 57
76 74 65 62 59 57
66 64 61 58 55 52
8
550 260
0.05 12
68 65 60 58 54 51
70 67 61 59 55 52
70 67 61 57 54 50
72 70 61 58 54 51
73 71 62 58 54 52
400 189
0.02 6
63 60 57 54 50 45
61 58 55 52 47 42
63 60 55 51 47 42
67 63 56 52 47 42
69 66 57 52 48 44
69 67 58 52 48 44
1 200 94
0.01 2
157 52 48 44 37 28
56 50 45 41 34 26
59 53 46 41 34 27
60 57 48 42 36 29
61 58 50 43 36 31
60 57 50 44 37 33
6
550 260
0.20 50
66 64 63 59 55 51
68 66 64 59 54 49
69 66 65 60 54 50
73 68 65 60 54 50
73 70 65 60 54 51
75 71 65 60 54 51
400 189
0.11 27
62 56 55 51 45 36
65 59 57 51 45 36
65 60 57 51 46 36
68 63 57 51 46 37
68 64 58 51 46 39
69 65 58 52 46 40
1100 519
0.12 30
73 72 71 69 65 63
73 72 71 68 64 62
73 72 71 69 64 62
75 73 71 69 64 62
76 75 71 69 64 62
76 76 71 68 64 62
8
900 425
0.08 20
70 68 67 64 60 58
69 69 68 64 59 56
71 69 68 64 60 57
72 71 68 64 60 57
74 73 68 64 60 57
74 74 68 64 60 57
700 330
0.05 12
66 64 63 59 55 51
66 65 63 59 54 50
67 65 64 59 55 50
70 67 64 59 55 50
71 70 64 59 55 51
72 70 64 59 55 51
3
400 189
0.02 5
62 56 55 51 45 36
64 58 56 51 45 36
64 58 57 51 45 36
66 61 57 51 45 37
67 62 57 51 45 39
67 63 58 52 46 40
1215 573
0.03 7
75 74 73 72 68 66
74 74 72 70 67 65
73 74 72 70 67 65
75 75 73 71 67 65
76 76 73 71 67 65
76 76 73 70 67 65
1100 519
U3 7
71 71 70 68 64 62
72 72 70 68 64 62
73 73 70 68 64 62
74 74 70 68 64 62
75 75 71 68 64 62
WARkME, ' - -
70 68 67 64 60 58
10
900 425
0.02 4
67 67 66 63 59 56
69 68 66 63 60 57
70 69 67 63 60 57
72 71 67 63 60 57
72 73 67 63 60 57
700 330
0.01 2
66 64 63 59 55 51
64 63 62 58 54 49
65 64 62 58 54 50
68 65 62 58 54 50
69 68 63 59 54 51
70 68 63 58 54 51
400 189
0.01 1
62 56 55 51 45 36
62 56 55 50 44 35
62 57 55 50 45 36
64 59 55 50 45 37
64 61 56 50 45 38
65 61 56 51 45 39
1550 731
0.10 25
80 79 74 74 70 69
78 77 74 73 70 68
82 79 75 74 70 69
83 81 76 74 71 70
85 82 76 75 72 71
86 83 77 75 72 71
1400 661
0.08 19
77 75 71 71 67 66
76 74 71 69 66 65
79 76 73 71 67 66
81 78 73 71 68 67
83 79 74 72 69 67
84 81 75 73 69 68
10
1200 566
0.05 13
74 72 69 67 64 62
73 70 69 67 63 61
77 73 70 68 64 63
80 75 71 69 65 63
81 77 72 69 66 64
83 78 73 70 66 65
900 425
0.03 7
69 67 64 61 57 54
69 67 64 61 56 53
74 69 66 63 58 55
74 70 65 62 58 54
76 71 66 63 58 55
77 72 67 63 59 56
700 330
0.02 4 165
63 60 57 53 48
66 64 61 57 53 48
71 66 62 59 55 51
69 65 61 57 53 48
71 67 62 58 53 49
72 68 62 58 54 50
4
1550 731
0.0
MR112-11
78 76 73 73 70 68
81 78 74 74 70 69
83 80 75 74 71 70
84 81 76 75 72 71
85 82 76 75 72 71
77 75 71 71 67 66
1400 661
0.03 8
75 73 71 69 66 65
78 75 72 71 67 66
80 77 73 71 68 67
82 78 73 72 69 67
83 80 74 73 69 68
12
1200 566
0.02 5
74 72 69 67 64 62
72 70 68 66 63 61
76 73 69 67 64 63
78 75 70 68 65 63
79 76 71 69 66 64
81 78 72 70 66 65
900 425
0.01 3
69 67 64 61 57 54
67 65 63 61 56 53
72 68 65 62 58 55
72 68 64 61 58 54
73 70 65 62 58 55
75 71 65 63 59 56
700 330
0.01 2
65 63 60 57 53 48
64 63 60 57 52 47
69 64 61 58 54 51
67 64 60 57 52 48
69 65 61 57 53 49
70 66 61 58 53 49
2050 967
0.06 15
82 79 74 75 72 71
82 78 74 73 71 70
82 79 75 74 71 71
84 81 76 75 73 72
86 82 77 76 73 72
86 82 78 76 73 73
1850 873
0.05 12
79 76 72 72 69 68
79 75 72 70 67 66
80 76 73 71 69 68
82 78 74 72 70 69
83 79 75 73 70 69
84 80 75 73 70 70
12
1600 755
0.04 10
77 73 69 68 65 64
76 72 69 68 64 63
79 74 71 69 66 65
80 75 71 70 67 66
82 77 72 71 67 66
82 78 72 71 67 66
1350 637
0,03 7
74 69 66 65 62 60
73 68 65 64 60 59
76 71 67 66 62 61
78 72 68 66 63 62
79 74 69 67 64 62
80 75 69 67 64 63
1100 51910,02
5
70 65 62 61 57 54
71 66 63 60 56 54
74 68 64 62 58 56
76 70 65 63 59 57
77 71 66 63 60 58
77 71 65 62 59 56
5
2050 967
0.04 10
ITAUSLOPITWIl
81 77 73 73 71 70
81 78 74 74 71 71
83 80 75 75 73 72
85 81 76 76 73 72
85 81 77 76 73 73
79 76 72 72 69 68
18�O 873
0.03 8
78 74 71 70 67 66
79 76 72 71 69 68
81 77 73 72 70 69
82 78 74 73 70 69
83 79 74 73 70 70
14
1600 755
0.03 7
77 73 69 68 65 64
75 71 68 67 64 63
77 73 70 68 66 65
79 75 71 69 67 66
80 76 71 70 67 66
80 77 72 70 67 66
1350 637
0.02 5
74 69 66 65 62 60
72 68 65 63 60 59
74 70 67 65 62 61
76 71 68 66 63 62
78 73 68 66 64 62
78 74 69 67 64 63
1
1160 519
0.01 3
70 65 62 61 57 54
69 64 61 60 56 54
71 67 63 61 58 56
73 68 64 62 59 57
75 69 64 63 60 58
74 69 64 62 59 56
2400 1133
0.08 20
81 80 78 80 77 76
80 78 77 78 76 75
80 79 78 79 76 75
82 81 79 80 78 77
83 82 80 80 78 77
84 82 80 81 78 77
6
14
2100 991
0.06 15
11M
76 76 74 76 72 71
77 77 75 76 74 73
79 79 76 78 75 74
80 79 77 78 75 74
81 80 77 78 75 75
1700 802
0.04 10
73 72 71 72 68 67
70 70 70 70 67 66
73 73 72 72 69 68
74 74 73 72 70 69
76 76 74 73 70 69
77 76 74 73 71 70
1400 661
0.03 6
68 67 68 67 63 62
68 66 67 66 62 61
70 68 69 67 65 63
72 70 70 68 65 64
73 71 70 69 66 65
73 71 70 68 65 63
4000 1888
0.15 38
83 80 77 78 75 74
80 78 76 75 73 72
81 79 76 75 73 72
83 81 77 77 74 73
85 82 78 78 75 74
86 83 79 78 76 75
35001652
0.12 29
80 77 74 74 71 70
78 75 73 72 70 69
79 76 73 72 70 69
81 78 75 74 72 70
83 80 76 75 73 72
84 81 76 76 73 72
16
2800 1321
0,08 19
74 71 69 68 65 63
76 73 70 69 66 64
79 75 71 70 68 66
80 77 72 71 69 67
80 75 71 70 67 65
InFREn, M
71 67 65 64 61 57
2100 991
0.04 11
70 66 64 62 59 56
73 68 66 64 61 58
75 70 67 66 62 60
75 70 66 64 61 58
76 71 65 64 61 58
7
1600 755
0.03 6
68 64 62 60 56 51
67 62 61 59 54 49
70 65 62 60 56 51
71 66 62 61 57 53
72 66 62 60 56 52
73 68 63 60 57 53
4000 1888
0 ' 10 25
83 80 77 78 75 74
79 78 75 75 73 72
81 78 75 75 73 72
82 80 76 77 74 73
84 81 78 78 75 74
85 82 78 78 76 75
3500 1652
0.07 18
80 77 74 74 71 70
77 75 72 72 70 69
78 75 73 72 70 69
81 78 74 74 72 70
83 79 75 75 73 72
83 80 76 76 73 72
18
2800 1321
0.05 11
76 72 70 69 66 64
73 70 68 67 65 63
75 72 69 68 66 64
77 74 71 70 68 66
79 76 72 71 69 67
79 75 70 69 67 65
2100 991
0.02 5
71 67 65 64 61 57
68 64 63 62 59 56
71 67 64 64 61 58
73 69 65 65 62 60
73 69 64 64 61 58
74 69 64 63 61 58
1600 755
0.02 4
168 64 62 60 56 51
165 60 60 58 54 49
68 63 60 59 55 50169
64 61 60 56 52170
64 61 59 55 52
71 66 61 60 56 53
For performance table notes, see page C48; highlighted indicate embedded AHRI certification points.
C46
FAN POWERED TERMINAL UNITS 9 35S SERIES CONailor'
Performance Data * NC Level Application Guide
Model Series 35S * Series Flow * Basic Unit
Fiberglass Liner
HOGE P
Size
;sb*
1
0. 5 W�.g'.-
1'(125
i.Ir W-.-g.'
llr V.,
I r w.g.
Fan
uii.�
ew r�,W.g.
lArw.g.
IX W.g.
12.r W.Q.
Pa)
(250 Pa)
(375 Pa)
(500 P8)
081Y
APS
(125 Pa)
(250 Pa)
(375 Pa)
1 (500 Pa)
550 260
0.22 54
37
36
36
36
39
39
36
36
35
36
37
37
400 189
0.12 30
30
26
26
29
30
33
30
30
30
31
33
33
6
300 142
OW 17
20
-
20
25
29
29
25
25
26
28
29
30
200 94
0.04 9
-
20
20
20
-
-
-
22
24
25
1
100 47
0.01 3
1 -
-
-
-
-
-
-
-
-
21
550 260
0.06 15
37
35
35
35
38
38
36
36
35
36
37
37
400 189
0.03 8
30
26
26
28
29
31
30
30
30
31
33
33
8
300 142
0.02 5
20
-
-
24
26
28
25
24
25
28
29
30
200 94
0.01 2
-
21
23
24
100 47
0.01 1
-
I -
20
550 260
0.20 50
23
25
28
29
31
33
24
23
25
29
32
33
5
400 189
0.11 27
-
-
-
24
28
29
-
-
21
24
29
30
200 94
0.04 10
-
I -
-
-
-
I -
-
-
-
22
25
28
2
850 401
0.11 28
31
34
36
34
35
36
35
33
34
35
36
36
700 330
OM 19
28
30
34
31
34
35
28
30
30
33
34
35
8
550 260
0.05 12
23
24
26
26
30
31
24
23
24
28
31
33
400 189
0.02 6
-
-
21
25
26
-
-
20
24
28
30
200 94
0.01 2
-
-
-
-
-
-
-
-
-
21
24
26
6
550 260
0.20 50
23
25
25
28
30
31
26
28
29
32
34
34
400 189
0.11 27
-
-
-
21
23
24
21
22
23
25
29
29
1100 519
0.12 30
31
31
31
33
35
36
34
34
34
36
38
31
8
900 425
0.08 20
26
28
28
30
33
34
30
31
32
34
36
36
700 330
0.05 12
23
24
24
26
30
30
26
28
29
31
34
34
3
400 189
0.02 5
-
-
-
20
21
21
22
23
25
29
29
1215 573
0.03 7
34
34
34
35
36
36
35
34
35
37
38
38
1100 519
0.03 7
31
30
31
33
34
35
34
33
34
36
37
37
10
900 425
0.02 4
26
25
26
28
30
33
30
30
31
33
35
35
700 330
0.01 2
23
21
23
24
28
28
26
26
28
31
33
33
400 189
0.01 1
-
21
21
22
24 1
28
28
1550 731
0.10 25
39
37
39
41
43
44
35
35
37
39
41
43
1400 661
0.08 19
35
34
36
38
39
41
33
33
35
37
40
41
10
1200 566
0.05 13
31
29
33
35
37
38
30
30
33
36
39
40
900 425
0.03 7
25
25
28
29
30
31
25
25
30
32
35
36
4
700 330
0.02 4
21
23
25
24
26
28
22
22
26
30
33 1
34
1550 731
0.05 12
39
36
38
40
41
43
35
35
37
39
41
43
1400 661
0.03 8
35
33
35
37
38
40
33
33
35
37
40
41
12
1200 566
0.02 5
31
29
33
35
36
38
30
30
33
35
38
39
900 425
0.01 3
25
23
26
26
29
30
25
25
29
32
34
36
700 330
0.01 2
21
21
23
23
24
25
22
21
26
29
32
33
2050 967
0.06 15
39
38
39
41
43
43
40
38
39
40
41
43
1850 873
0.05 12
36
35
36
38
39
40
38
36
37
38
39
40
12
1600 755
0.04 10
33
31
34
35
37
38
34
34
35
36
38
38
1350 637
0.03 7
28
26
30
31
34
35
29
30
31
34
36
37
1100 519
O�02 5
23
24
26
29
30
30
26
25
28
30
33
34
5
2050 967
0.04 10
39
37
38
40
41
41
40
38
39
40
41
43
1850 873
0.03 8
36
34
36
37
38
39
38
36
37
38
39
40
14
1600 755
0.03 7
33
30
33
35
36
37
34
34
35
36
38
38
1350 637
0.02 5
28
26
29
30
33
34
29
29
30
34
36
37
1100 519
0.01 3
23
21
25
26
28
28
26
25
28
30
33
34
2400 1133
0.08 20
40
38
39
41
43
43
43
39
41
44
46
46
6
14
2100 991
0.06 15
37
36
37
39
40
40
40
37
38
41
44
44
1700 802
0.04 10
31
29
33
34
36
36
36
33
34
37
40
40
1400 661
0.03 6
26
25
27
29
30
30
33
28
29
34
37
37
4000 1888
0.15 38
40
38
39
41
43
44
46
44
44
45
46
47
3500 1652
0.12 29
37
35
36
38
40
41
43
40
41
43
45
45
16
2800 1321
0.08 19
31
30
33
35
37
35
38
36
37
39
41
43
2100 991
0.04 11
25
24
26
29
29
30
34
33
33
35
38
40
1600 755
0.03 6
21
-
23
24
24
26
30
28
30
33
36
38
7
4000 1888
0.10 25
40
38
38
40
41
43
46
44
44
45
46
47
3500 1652
0.07 18
37
35
35
38
39
40
43
40
41
43
45
45
IS
2800 1321
0.05 11
31
29
31
34
36
35
38
36
37
39
41
41
2100 991
0.02 5
25
21
25
28
28
28
34
33
33
35
38
39
1600 755
0.02 4
21
-
20
21
21
24
30
28
29
32
36
, 37
Performance Notes: 1. NC Levels are calculated based on procedures as outlined on page C132.
2. Dash (-) in space indicates a NC less than 20. C45
FAN POWERED TERMINAL UNITS 9 35S SERIES CONailof
Performance Data * Radiated Sound Power Levels
Model Series 35S - Series Flow - Basic Unit
Fiberglass Liner
T"i t'
Size
Ire t
Size
9 Wi 116101
�%Quf'nmi-
AVWMWJ�Oi
a
-(56
Dfw �t
cfm Us
"wo. Us
2 3 4 ;5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
550 260
0.22 54
68 65 60 54 49 45
67 65 59 54 49 46
68 64 59 53 53 52
69 65 60 56 56 57
69 66 62 58 58 61
70 66 62 59 59 63
400 189
0.12 30
IMKII&MMIJEEM,
64 60 55 48 43 39
65 60 55 50 50 49
66 61 56 52 54 54
67 62 57 55 58 60
61 56 51 44 40 36
6
300 142
ON 17
61 55 51 44 40 36
61 56 52 47 48 47
62 58 53 49 52 51
63 59 54 51 55 54
63 60 54 52 56 55
200 94
0.04 9
51 47 43 35 31 25
51 47 43 34 30 25
54 49 45 41 43 40
55 51 48 44 47 44
56 53 50 47 50 47
56 54 51 48 51 48
100 47
0.01 3
- - -
- - - - - -
- - - 34 34 31
- - - 38 37 35
- - 45 42 39 38
- - 47 44 40 39
1
550 260
0.06 15
68 65 60 54 49 45
67 65 59 53 49 46
68 64 59 52 52 51
69 65 60 55 55 56
69 66 62 57 57 60
70 66 62 58 58 62
400 189
0.03 8
64 60 55 48 44 40
64 60 54 48 43 38
65 60 54 50 50 48
66 61 55 51 53 52
67 62 56 53 56 57
67 62 57 54 58 59
8
300 142
0.02 5
61 56 51 44 40 36
61 55 50 43 39 35
61 56 51 46 47 46
62 58 52 48 50 49
63 59 53 50 54 52
63 60 54 51 55 54
200 94
0.01 2
51 47 43 35 31 25
51 46 43 33 29 24
54 49 45 40 42 39
55 51 47 43 45 42
55 53 49 46 49 46
56 54 50 47 50 47
1
1 100 47
0.01 1
1 - ---- - - -
- - - - - -
- - - 33 33 30
- - - 37 35 33
- - 44 41 38 37
- - 46 42 39 38
550 260
0.20 50
60 55 50 45 39 34
59 54 49 43 38 33
60 54 51 47 49 51
62 58 54 51 54 56
64 61 57 55 58 61
65 62 58 57 60 63
6
400 189
0.11 27
55 49 45 39 32 26
53 48 44 37 31 25
57 51 47 44 48 48
59 55 50 48 53 53
62 59 54 53 58 58
63 60 55 54 60 60
200 94
0.04 10
52 46 41 34 25 18
51 46 41 34 25 -
54 49 44 43 44 42
56 51 48 46 48 46
57 53 51 49 52 50
58 54 53 51 53 52
2
850 401
0.11 28
68 64 58 54 49 45
67 62 57 52 48 44
68 63 57 53 53 53
68 64 59 56 55 57
69 65 60 58 58 61
69 65 61 59 58 63
NA-13FIFTM,
700 330
0.08 19
65 60 54 49 44 39
66 60 54 50 51 51
67 62 56 53 54 56
69 64 59 57 58 62
60 55 50 45 39 34
8
550 260
0.05 12
59 54 49 42 37 32
60 54 50 46 48 49
62 58 53 50 53 54
64 61 56 54 57 60
65 62 57 56 59 62
400 189
0.02 6
55 49 45 39 32 26
53 48 43 36 30 24
56 50 46 43 46 46
59 54 50 47 51 51
61 58 53 52 56 57
62 60 55 53 58 59
1 200 94
0.01 2
152 46 41 34 25 18
51 45 41 33 25 -
54 48 43 41 43 40
55 51 47 45 47 44
57 53 50 48 50 48
57 54 52 49 52 50
6
550 260
0.20 50
59 55 52 48 43 38
57 54 53 49 44 39
59 56 54 53 52 5Y
61 59 57 56 57 58
64 62 59 59 61 64
64 62 59 59 61 64
400 189
0.11 27
55 50 47 42 36 28
57 51 48 43 37 28
57 52 49 47 50 48
59 55 51 51 55 53
61 58 54 54 59 58
61 58 54 54 59 58
1100 519
0.12 30
65 62 59 56 52 48
64 60 59 56 52 48
65 62 59 57 55 55
66 63 61 60 58 59
68 65 63 63 61 63
68 65 63 6T 61 63
8
900 425
0.08 20
62 58 55 52 48 43
60 57 56 53 48 44
62 59 57 55 53 53
64 61 59 58 57 58
65 64 61 61 60 63
65 64 61 61 60 63
700 330
0.05 12
59 55 52 48 43 38
58 54 53 48 43 38
60 56 54 52 51 51
62 60 56 55 56 56
64 63 58 58 61 62
64 63 58 58 61 62
3
-
400 189
.0.02 5
55 50 47 42 36 28
56 50 48 42 36 28
57 52 49 47 49 47
58 55 51 50 53 52
60 57 54 54 56
60 57 54 54 57 56
1215 573
0.03 7
67 63 60 58 54 50
66 62 59 57 53 49
67 63 60 58 56 55
68 65 62 61 59 59
.57
69 66 63 63 61 62
69 66 63 63 61 62
1100 519
0.03 7
64 60 58 56 51 47
65 62 59 57 55 54
66 63 61 59 58 5 8
6 8 65 62 62 61 62
1*19 *X'� I V VM.'
1 * 9 *V *A *J 1 -1 ff-M
62 58 55 52 48 43
65 64 60 59 59 61
10
900 425
0.02 4
60 57 55 52 47 42
62 59 56 54 52 51
64 61 58 57 56 56
65 64 60 59 59 61
700 330
0.01 2
59 55 52 48 43 38
57 54 52 47 42 37
59 56 53 51 50 49
61 59 56 54 54 55
64 62 58 57 59 60
64 62 58 57 59 60
1
1 400 189
0.01 1
55 50 47 42 36 28
56 50 47 41 35 27
56 51 48 46 47 45
58 54 50 49 51 50
59 57 53 52 55 54
59 57 53 52 55 54
1550 731
0.10 25
68 64 58 57 55 53
68 64 58 57 54 53
70 66 61 59 58 56
72 68 64 63 60 60
73 70 66 66 63 63
74 70 67 67 64 65
1400 661
0.08 19
67 62 57 56 53 51
66 62 57 55 52 51
69 64 59 57 56 54
70 66 62 61 59 58
72 68 65 65 62 63
73 69 66 67 64 64
10
1200 566
0.05 13
65 60 55 53 50 48
63 59 55 52 49 48
67 61 57 55 53 53
68 64 61 59 57 57
70 66 64 64 61 62
71 67 65 66 63 64
900 425
0.03 7
61 56 51 49 45 42
60 56 51 48 44 42
63 58 55 53 51 50
64 60 57 57 55 55
65 62 60 61 60 61
65 63 61 62 61 63
700 330
0.02 4
59 53 48 45 41 36
57 52 48 44 39 34
61 55 52 51 49 47
62 57 55 54 54 52
63 59 58 58 58 58
63 60 59 59 60 60
4
1550 731
0.05 12
1-*1:ff--Hb1;1&-TA1k1;%-%j
68 64 58 57 54 52
70 66 61 59 57 56
72 68 64 62 59 59
FRIMIZ-11TW-MM,
74 70 67 67 63 64
67 62 57 56 53 51
72 68 65 65 62 62
1400 661
0.03 8
66 62 57 55 52 50
69 64 59 57 55 54
70 66 62 61 58 58
73 69 66 66 63 64
12
1200 566
0.02 5
65 60 55 53 50 48
63 59 55 52 49 47
67 61 57 54 53 52
68 64 60 59 57 56
70 66 63 63 61 61
71 67 64 65 62 63
900 425
0.01 3
61 56 51 49 45 42
60 56 51 47 43 40
63 58 54 52 50 48
64 60 57 56 54 53
65 62 59 60 59 59
65 63 61 61 60 61
1700 330
0.01 2
59 53 48 45 41 36
56 51 47 43 38 33
61 55 52 50 48 46
61 57 54 53 52 51
62 59 57 56 57 56
62 60 58 58 59 58
2050 967
0.06 15
74 69 62 60 57 54
70 67 62 60 56 54
71 68 62 61 58 56
72 69 64 62 60 60
73 70 65 63 62 64
73 71 65 63 63 65
1850 873
0.05 12
71 67 60 58 55 52
68 65 60 57 53 51
68 66 60 58 56 54
70 67 62 59 59 59
71 68 63 61 61 63
71 69 64 62 62 65
12
1600 755
0.04 10
68 63 57 54 51 47
68 63 58 54 51 48
68 64 59 55 54 53
69 65 61 57 58 58
70 67 62 60 61 63
70 67 63 61 62 65
1350 637
0.03 7
65 59 54 51 47 43
64 59 55 50 46 43
65 60 56 52 52 51
67 63 58 55 56 56
68 65 61 58 60 62
68 66 62 59 62 64
1100 51910.02
5
62 57 50 47 42 38
61 56 51 46 42 38
63 58 52 50 50 49
64 60 55 53 55 55
65 62 58 57 60 61
65 63 59 58 62 63
5
2050 967
0.04 10
70 67 62 59 56 53
71 68 62 60 58 56
72 69 64 61 60 60
"W11K.'141-NMEW
73 71 65 63 63 65
71 67 60 58 55 52
71 68 63 61 61 62
1850 873
0.03 8
68 65 60 56 53 50
68 66 60 57 56 54
70 67 62 59 58 58
71 69 64 61 62 64
14
1600 755
0.03 7
68 63 57 54 51 47
68 63 58 53 50 47
68 64 58 55 54 52
69 65 60 57 57 57
70 67 62 59 60 61
70 67 62 60 61 63
1350 637
0.02 5
65 59 54 51 47 43
64 59 54 49 46 42
65 60 55 52 52 50
67 63 58 55 55 55
68 65 60 58 59 60
68 66 61 59 61 62
11100 519
0.01 3
62 57 50 47 42 38
61 56 50 46 41 37
63 58 52 49 50 48
64 60 55 52 54 53
65 62 58 56 59 59
65 63 59 57 60 61
24001133
0.08 20
74 71 64 63 61 59
72 68 63 62 59 56
74 70 63 63 60 57
76 72 65 64 62 61
78 74 67 65 65 65
78 74 67 65 65 65
6
14
2100 991
0.06 15
69 66 60 59 55 52
72 67 61 61 57 54
74 70 63 62 60 59
77 72 65 63 63 64
IFFIFF23101*1 M
69 65 59 57 55 53
1700 802
0.04 10
66 62 56 55 50 47
68 63 57 57 52 49
71 66 60 59 57 56
73 69 63 61 61 63
73 69 63 61 61 63
1400 661
0.03 6
66 62 55 54 52 50
63 58 53 51 46 42
64 59 54 53 48 43
67 63 57 56 54 52
70 66 60 58 60 61
70 66 60 58 60 61
4000 1888
0.15 38
77 74 68 62 58 58
74 72 66 60 56 56
74 72 67 62 58 57
75 73 69 63 60 60
76 74 70 65 62 63
76 74 71 65 62 64
3500 1652
0.12 29
74 71 65 59 55 55
71 69 64 58 53 52
72 70 65 59 56 55
73 71 67 61 58 58
74 72 69 63 60 61
74 72 69 64 61 62
16
2800 1321
0.08 19
67 65 60 53 48 47
68 66 61 55 52 51
70 68 64 58 55 55
72 70 67 62 59 61
66 63 57 50 45 43
68 67 63 58 56 57
2100 991
0.04 11
63 62 55 48 43 41
64 62 57 51 49 47
66 64 60 55 53 52
69 68 65 59 58 59
7
1600 755
0,03 6
62 60 54 47 41 39
59 58 52 44 38 34
62 60 54 48 47 44
64 62 58 52 51 50
66 64 61 56 55 56
67 65 63 57 57 58
4000 1888
0.10 25
77 74 68 62 58 58
74 72 66 60 56 55
74 72 67 61 57 57
75 73 69 63 59 59
76 74 70 64 61 62
76 74 71 65 62 63
3500 1652
0,07 18
74 71 65 59 55 55
71 69 64 57 53 52
72 70 65 58 55 54
73 71 67 60 57 57
74 72 69 62 59 61
74 72 69 63 60 62
18
2800 1321
0.05 11
70 67 61 55 50 49
67 65 59 52 48 46
68 66 61 54 52 50
70 68 63 57 55 54
71 69 65 60 58 58
72 70 66 61 59 60
2100 991
0.02 5
66 63 57 50 45 43
63 62 55 47 42 40
64 62 56 50 48 45
66 64 59 53 52 50
68 67 63 57 55 55
69 68 64 58 57 57
1600 755
10.02 4
162 60 54 47 41 39159
58 51 43 37 33
61 59 54 47 45 43
63 61 57 51 50 48165
64 61 55 54 54166
65 62 56 55 57
Z
For performance table notes, see page C48; highlighted indicate embedded AHRI certification points.
C47
FAN POWERED TERMINAL UNITS CONailor"
Electric Heating Coils
Features, Selection and Capacities
Nailor Electric Coils are tested with terminal units in
accordance with UL Standard 1995 and meet all requirements
of the NEC (National Electric Code) and CSA (Canadian
Standards Association). Units are listed and labeled by the
ETL Testing Laboratory as a total package. All controls are
enclosed in a NEMA 1 electrical enclosure on the side of the
fan package for easy access.
All wiring for the motor and heater terminates in the enclosure
for single point electrical connection in the field. Each unit is
supplied with a wiring diagram. Note: NEC requires a means
to disconnect the heater power supply within sight or on the
terminal.
Standard Features:
- Automatic reset high limit thermal cut-outs.
. Magnetic contactors per stage on terminals with DDC or
analog electronic controls.
. P.E. switch per stage to carry load or pilot duty with
magnetic contactors as required with pneumatic control.
Positive pressure airflow safety switch.
P.E. switch for fan on parallel terminals (P35NE) with
pneumatic control.
Fan relay for DDC fan terminals.
Control voltage transformer (Class 11) for DDC or analog
electronic terminals.
. Class A 80/20 Ni/Cr wire.
Options:
Toggle disconnect switch.
Door interlocking disconnect switch.
Mercury contactors.
Power circuit fusing.
Dust tight control enclosure.
Manual reset high limits.
SCR Control.
SCR Control Option:
The SCR (Silicon Controlled Rectifier) option provides infinite
solid state heater control using a proportional signal (0 - 10
Vdc or 4 - 20 mA). This option may be specified compatible
with pneumatic, analog electronic or digital (DDC) controls.
Time proportional control of the electric heater provides
superior comfort and energy savings. The SCR controller
modulates the heater to supply the exact amount of heat
based upon the zone requirement. Room set points are
maintained more accurately, undershoot and overshoot
as associated with staged heat are eliminated, reducing
operation costs.
SCR controllers provide silent operation, as mechanical
staged contactors are eliminated. Zero cross switching of the
thyristor prevents electrical noise.
Maximum
KiloWatts - 1 Stage Heat
Models
Unit
Size
�20 Volt
208/240
277 Volt
208 Volt
480 & 600
hase
P7
Volt
1 phase
1 phase
s
3 pha e
Volt
3 phase
30
4,5
to*
11.5
14.5
15
33SZE
40
4.5
10*
11.5
14.5
18
50
4.5
10-
11.5
14.5
25
1
-
8
8
10
8
2
-
8
8
10
8
3
-
8
11.5
10
14
35SE
35SEST
4
-
8
11.5
10
16
5
-
8
11.5
14.5
20.5
6
-
8
11.5
14.5
26
7
-
8
11.5
14.5
30
1
-
5.5
5.5
5.5
5.5
37SE
2
-
10.5**
12
12
12
37SEST
3
-
10-
12
15.5
17
4
-
8
11.5
14.5
27
2
-
8
8
10
8
35NE
3
-
8
11.5
10
14
5
-
8
11.5
14.5
20.5
1 6
1 -
1 8
11.5
14.
26
2
-
8
11.5
11.5
11.5
37NE
3
-
8
11.5
13.5
16
4
-
8
11.5
14.5
27
*208V max is 8.5
**208V max is 9.0
***208V max is 8.5
Recommended Selection:
The table above is a quick reference guide, to illustrate
the relationship between electrical power supply, heater
capacity in kiloWafts and terminal unit size that are available
for fan powered units.
. Digital and pneumatic control terminals are available with
up to 3 stages of heat. Analog electronic
control terminals are available with 1 or
2 stages of heat only. A minimum of 0.5
kW per stage is required.
Voltage and kilowatt ratings are sized C T us
OT
so as not to exceed 48 amps, in order 41STED
to avoid the NEC code requirement for
circuit fusing. Intertek
. A minimum airflow of 70 CfM (33 I/s) Tested and approved to
per kW is required for any given terminal the following Standards:
in order to avoid possible nuisance ANSWIL
tripping of the thermal cutouts. 1995, iSt. ed.
CSA C22.2
Discharge air temperature should not No. 236.
exceed 120OF (490C).
Z
C1 3:
FAN POWERED TERMINAL UNITS ONO&
Electric Heating CONS (continued)
Application Guidelines
Discharge Air Temperature
When considering the capacity and airflow for the heater,
discharge air temperature can be an important factor.
Rooms use different types of diffusers and they are intended
to perform different functions. Slots that blend the air at the
glass and set up air curtains within the room, must be able to
blow the air very low in the room. Hot air will be too buoyant
to be effective in this case. Discharge air temperatures for
this application should be in the 85 — 90'F (29 — 32'C) range.
Diffusers in the center of the room blend their discharge
air as it crosses the ceiling. Discharge air temperatures in
this application can be as high as 1050F (410C) and still
be effective. However, if the return air grilles are in the
discharge air pattern, the warm air will be returned to the
plenum before it heats the room. Again, the air temperature
needs to be blended down to an acceptable temperature
that can be forced down into the occupied space by the
time the air gets to the walls. Discharging warm air into the
room at temperatures above 1050F (41'C) usually will set up
stratification layers and will not keep the occupants warm if
there is a ceiling return because only the top 12" — 24" (300
— 600 mm) of the room will be heated.
The maximum approved discharge air temperature for any
Nailor Fan Powered Terminal Unit with supplemental heat
is 120OF (49'C). No heater should be applied to exceed this
temperature.
Electric Heater Selection
To properly select an electric heater, three things must be
determined: the heat requirement for the room, the entering
air temperature and the desired discharge air temperature.
The heat requirement for the room is the sum of the heat
loss calculation and the amount of heat required to raise the
entering air temperature to the desired room temperature.
Usually, the second item is small compared to the first for fan
powered terminal units in a return air plenum. MBH can be
converted to kW by using the chart or by calculation. There
are 3.413 MBH in 1 kW. If using the chart, find the MBH on
the left scale, then move horizontally to the right and read
kW.
Next, the desired discharge air temperature should be
ascertained. This will depend on the type of diffusers that
are in the room.
The desired heating airflow for the room can then be
calculated using the following equation:
cfm = kW x 3160
At (discharge air temp — inlet air temp.) OF
Assuming 70OF (210C) supply air temperature to the heater,
the room airflow can be selected directly from the chart. Start
at the left at the design kW. Move horizontally to the desired
discharge air temperature. Then, move vertically down to the
cfm at the bottom of the chart.
The kW can be selected directly from the chart. Start at the
bottom with the design cfm into the room. Move vertically
up to the line that represents the desired discharge air
temperature. Then, move left to the kW.
The discharge air temperature can also be selected directly
from the chart. Start at the bottom with the design cfm into
the room. Move to the left side of the chart and find the
design kW. Move horizontally and vertically into the chart
until the lines intersect. The intersection will be the desired
discharge air temperature. Interpolation between the curves
is linear.
170
160
1 50
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Heater Selection Chart
Assuming 70T inlet air temperature at heater.
lirlor
110oF
105T
1 OOoF
957
90oF
85oF
80oF
0 500 1000 1500 2000 2500 3000 3500 4000
AIRFLOW, CFM
Diagonal lines are constant output temperature.
"M 3 4
PROJECT NOTES
PROJECT INFORMATION
SCOPE OF WORK To BE DOME
1) ADD ALL NEW DUCT WORK NEEDED
LEGAL DESCRIPTION
FOR NEW OFFICES
THE WEST 331.60 FEET OF TRACT 29, SOLNERS 5 ACRE TRACTS, ACCORDING
TO THE PLAT THEREOF RECORDED IN VOLUME 7 OF PLATS. PAGE 25, IN
SNOHOMISH COUNTY, WASHINGTON.
SYMBOLS LEGEMB
TAXPMCELNUMBER
2) ADD NEW FAN POWER MIX BOX
5807-000-029-01-00
AUTHORITY HAVING JURISDICTION [AHA
3) MOVE EXISTING FIRE SMOKE DAMPER
CITY OF EDMONDS
MEW SUPPLY AIR DUCT WORK
APPLICABLE CODES
EX ST NG-BUILDING CODE: WA STATE EXISTIN&BUILDING CODE (IEBG With amendments) - 2015
BLIZINGCODE: WA STATE BUILDING CODE (IBC wilh amendments) - 2015
MEW RETURN AIR DUCT WORK
ENERGY CODE: VIA STATE ENERGY CODE (lECC vAth amendments) - 2015
LIFE SAFETY CODE: NFPA 101 - 2012
FIRE CODE: INTERNATIONAL FIRE CODE (IFC) - 2G15
MECHANiCALOODE: INTERNATIONAL MECHANICAL CODE ([MCI -2015
PLUMBING CODE U NIFORM PLUMBING CODE (UPC) - 2015
ALL WORK SUBJECT
MEW EXHAUST AIR DUCT WORK
ELECTR[CALCOIDE NATIONAL ELECTRICAL CODE (NEC) - 2014
ACCESSIBILITY CODE: ANSIA117.11-2009 (BY REFERENCE FROM IBCANDWSBC)
TO FIELD
INSPECTION FOR
EXISTING SUPPLY AIR DUCT WORK OR UNIT
CODE COMPLIANCE
EXISTING PRETURM AIR DUCT WORK
EXISTING EXHAUST AIR DUCT WORK
UNIT RETURN AIR DROPS
g1r, pp,
UNIT SUPPLY AIR DROPS
PLAMS M Ul
RETURN AIR GRILLS
00 H JOB 5011E.
SIDEWALL RETURN AIR GRILLS
SUPPLY AIR GRILLS
SUPPLV AIR GRILLS
PROJECT TEAM
SUPPLY AIR GRILLS
OWNER: OWNER CONTACT.
ERIKA FRYE
S9DEWALL SUPPLY AIR GRILLS
HEALTHCARE REALTY 425.4, 0-9D65
123 IISTHAVENUENE EFRYE@HEALTHGAREREALTY.COM
SUITE 120
VICINITY MAP
BELLEVUE, WA DIM
StSW � p W C)
2116ftStSW
ARCHITECT: PROJECT LEAD: GINA DAIS
TGBARCHITECTS PRINCIPAL IN CHARGE: KENT GREGORY
425
76TH -778-1530
21911 -EVISUITE210
12 GRILL SIZE
300
CFM ALL WORK, ALL EQUIPRflFMT
El Res-rce LibrRy
rossFit IndL
-
2,641 0P.9cISdGmdro
ALL PARTS TO BE IMSTALLED,
GDAIS@TGRARCHITECTS.COM
EDMONDS,WA98M KGREGORY@TGBARCHFrECTS.COM
Ed vids 0
44ter
20X20
GRILL SIZE
WILL BE IM FULL COMPL�MCE
0J.
GENERAL CONTRACTOR:
-4-
HAND DAMPER
WITH ALL CODES BELOW.
TEID
AREA OF WOM
218th St SW
12o
DUCTWORK SIZE
2015 WSEC
Dick's Drive In Q
2015 IMC
CEILING FAN
2017 MEC
W Cc Foods
2191h St SW
IMLIME FAN
2015 IFC
QEIirth&F*m0yCfIrdc
E; G Red Dragon C�imo
2015 IBC
____.Starbuck90
(b
THERMOSTAT
2015 �FGC
220th St SW 220th StSW
220thStSW 226U, S, 1, 1 Sw
Z-15
ZOMEV
ALL EQUIPMEMT WILL BE 7ESTF-0
ZONE DAMPER WITH MOTOR
WITH REPORT PER CODE
ZD-20
N
NEW INSTALL
ALL SUPPLY AIR GRILLS WILL AIR
FLOW TESTED AMD ADJUSTED WIT H
E
E;US71MG INSTALL
REPORT PER CODE
R/D
REDUCT EXISTING GRILLS
MOVE EXISTING
DUCT CONNECTION
N
Q
EDMONDS
MEDICAL PAVILION
SPEC SUITE 300
7320 216TH ST SW
SUITE 300
EDMONDS, WA 98026
GENERAL
INFORMATION
CITY OF EDMONDS
BUILD[BG PEPAPTMJENT
WORK rfleiLhallic-A I
ADDRESS 0 al
OWNER_
APPROVED DATE:
BLDG. OFFICIAL:
NUMBER
1=2ULL- -
RECEIVED
COPY JUL 15 2019
-
-PROJECT NUMBER:
DRAWN BY: PATRICK
SHEET NO
PROVIDE
LIGHT
EXISTING
Snr
&q
"!I �ING PLAN �-LEV�EL3
MIXING BOX
MAKE
NAILOR
MIDDLE #
D35SE
UNIT SIZE
308
CFM MAX
800
MOTOR
ECM / 1/10 HP
HEATER
410 WATTS / 1.75 KW
POWER
277 VOLTS/ 1 PHASE
MOP
15AMPS
LP-11
EDMONDS
MEDICAL PAVILION
SPEC SUITE 300
7320 216TH ST SW
SUITE 300
EDMONDS, WA 98026
CEILING, FF&E &
FINISHES PLAN
RECEIVED
—PROJECT NUMBER:
PROJECTLEAD: JUL 15 2019
DRAWN BY:- PATRICK BUILDING
sHEETNO
N 17_1