BLD201903860 � ED A,
CITY OF EDMONDS
Expiration Date: 04/23/2020
Parcel No: 00434400700800
121 5TH AVENUE NORTH - EDMONDS, WA 98020
HONE: (425) 771-0220 - FAX: (425) 771-0221
A
/ 1. " ! I , e)
Pertnit #: BLD20190386
ject Address: 201 MAIN ST, EDMONDSi
011��k
APPLICANT
CONTRACTOR
2020 LLC EDMONDS
WASHINGTON ALARM INC
WASHINGTON ALARM INC
307 BELL ST
C/O TREYVEN CHIN
C/O TREYVEN CHIN
EDMONDS, WA 98020
2030 AIRPORT WAY S
2030 AIRPORT WAY S
SEATTLE, WA 98134
SEATTLE, WA 98134
(2 06) 3 28-32 8 8
(206) 328-3288
LICENSE #: WASHIA12820 EXPA2/05/2019
JOB DES RIP'nON
FIREALARM SYSTEM
VALUATION: $22,000
PERMIT TYPE Commercial
PERMIT GROUP: 79 - Fire Alarm
GRADING: N CYDS: 0
OF CONSTRUCTION
_TYPE
RETAINING WALL ROCKERY:
OCCUPANT GROUP:
OCCUPANT LOAD -
FENCE: OXO FT-)
CODE
IOTHER: ------- OTHER DESC
lZONE:
INUMBER OF STORIES: 0
[VESTED DATE:
'ELLINGUNITS 0
ILOT #-
EXIS'llNG ARM
BASEMENT 0 1 ST FLOOR 0 2ND FLOOR: 0
PROPOSII) AREA
fEASEMENT 0 1 ST FLOOR. 0 2ND FLOOR 0
3RD FLOOR: 0 GARAGE: 0 DECK 0 OTHER: 0 13RD
FLOOR: 0 GARAGE: 0 DECK 0 OTHER: 0
BEDROOMS: 0 BATHROOMS: 0 IBEDROOMS:
0 BATHROOMS: 0
FRONTSETBACK SIDEWFBACK REAR SEIFBACK
=1RED. PROPOSED: ��7QUIRED: PROPOSED: [REQUIRED: PROPOSED
HEIGHT ALLOWED:O PROPOSE5.1-0 IREQUIRED: PROPOSED:
SETBACK NOTES:
I AGREE TO COMPLY WITH CITY AND STAIE4,AWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY, NO
PERSON WILL BE EMPLOY ED IN VIOLATION OF THE LABOR CO F THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION
T
C
PERMrFV/ INL NC AND RCW 18:27.
TIL
THIS APPL E B
JQ,ATION IS NOT A SIGNEDBYTHEB ILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID.
Christina Wayland 4/23/19
SignatAq.�,� Print Narne Dal�- Released By Date
I ATTENTION
USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF
OCCUPANCY HAS BEEN GRANTED. UBC 1091 IBCI 10/ IRCI 10.
= FIRE = APPLICANT = ASSESSOR = CITY
STATUS: ISSUED BLD20190386
• Final approval on a project or final occupancy approval must be granted by the Building Official prior to use or occupancy of
the building or structure. Cbeck thejob card for all required City inspections including final project approval and final
occupancy inspections.
• Any request foralternate design, modification, variance orother administrative deviation (hereinafter "variance") from
adopted codes, ordinances or policies must be specifically requested in writing and be called out and identified. Processing
fees for such request shall be established by Council and shall be paid upon submittal and are non-refundable.
• Approval of any plat or plan containing provisions which do not comply with city code and for which a variance has not been
specifically identified, requested and considered by the appropriate city official in accordance with the appropriate provision
of city code or state law does not approve any items not to code specification.
• SoundNoise originating from temporary construction sites as a result of construction activity are exempt from the noise limits
of ECC Chapter 5.30 only during the hours of 7:00arn to 6:00pm on weekdays and 10:00arn and 6:00pm on Saturdays, excluding
Sundays and Federal Holidays. At all othertimes the noise originating from construction sites /activities must comply with the
noise limits of Chapter 5.30, unless a variance has been granted pursuant to ECC 5.30.120.
• Applicant, on behalf of his or her spouse, heirs, assigns, and successors in interests, agrees to indemnify defend and hold
hannless the City of Edmonds, Washington, its officials, employees, and agents from any and all claims for damages of
whatever nature, arising directly or indirectly from the issuance for this pen -nit. Issuance of this pen -nit shall not be deemed to
modify, waive or reduce any requirements of any City ordinance nor limit in any way the City's ability to enforce any ordinance
provision.
THIS PERMFTAUTHORVES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY
CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS, MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION. PERMIT
TIME LIMIT: SEE ECDC 19.00.005(A)(6)
BUILDING
ENGINEEIRING (425) 771-0220 EXT. 1326
1. Go to: www.edmondswa.gov
Building Department Inspections
2. Then: SenAces
are now scheduled online. If you
FIRE (425) 775-7720
3. Then: Perm its/Dewlopment
have difficulties, please call the
4. Then: Online Permit Info
Building Department front desk for
PUBLIC WORKS (425) 771-0235
5: If you don't ha\e one already, create a
assistance during office hours.
login (upper right hand corner)
(425) 771-0220
RECYCLING (425) 275-4801
6: Schedule your inspection
When calling for an inspection please leave the following information: Permit Number, Job Site Address, Type of Inspection
being requested, Contact Name and Phone Number, Date Preferred, and whether you prefer morning or afternoon.
• F-Fire Alarm System Acceptance
• F-Fire Compliance
• F-Fire Final
- IL
I — 61_39eoe?
'131P C?Olq
/Y 3 1-3 — /
cP DEVELOPMENT SERVICES
COMMERCIAL & MULTI -FAMILY BUILDING
PERMIT APPLICATION
121 5h Avenue N, Edmonds, WA 98020
t,
City of Edmonds Phone 425.771.0220 9 Fax 425.771.0221
PLEASE REFER TO THE COMMERCIAL & MULTI -FAMILY BUILDING CHECKLIST FOR SUBMITTAL REQUIREMENTS
PROJECT ADDRESS (Street, Suite City State, Zip):
201 Main St, Edmonds WA, 98020
Parcel #:
00434400700700
Subdivision/Lot #:
Project Valuation: $
22,000
APPLICANT:
Treyven Chin
Phone:
206-436-5300
Fax:
206-322-7214
Address (Street, City, State, Zip):
2030 Airport Way S Seattle, WA 98134
E-Mail Address:
Permits0washingtonalarm.com
PROPERTY OWNER:
Phone:
Fax:
Address (Street, City, State, Zip):
E-Mail Address:
LENDING AGENCY:
Phone:
Fax:
Address (Street, City, State, Zip):
E-Mail Address:
CONTRACTOR:*
Washington Alarm Inc
Phone:
206-328-1800
Fax:
206-322-7214
Address (Street, City, State, Zip):
2030 Airport Way S Seattle, WA 98134
E-Mail Address
Install(-Wwashingtonalarm.com
*Contractor must have a valid City of Edmonds business license prior to
doing work in the City. Contact the City Clerk's Office at 425.775.2525
WA State License #/Exp. Date:
WASHIAI282C3 12/5/2019
City Business License #/Exp. Date:
NR-014536
DETAIL THE SCOPE OF WORK: Parts/Smartsi field trim installation of fire alarm system in anew fully sprinkled multi-farnily, mixed use building.
Installation to include sprinkler monitoring, elevator recall, and full non -voice occupant notification.
PROPOSED NEW SQUARE FOOTAGE FOR THIS PROJECT:
1 st Floor: -Sq. ft.
2 nd Floor:
sq. ft.
3d Floor: sq. ft.
Basement: sq. ft.
Garage:
sq. ft.
Deck/Cvrd Porch: -sq. ft.
Other: -sq. ft.
Retaining Wall: Yesl I
No
I 1_
Fire Sprinklers: YesF_1 No Li
Occupancy Group(s):
Occupant Load(s):
Type(s) of Construction:
Grading: Cut -cu.yds. Fill cu.yds.
Fut/Fill in Critical'Area: Yes
L] No L_]
Ideclare underpenalty ofpeijury laws thatthe information Ihaveprovidedon this formlapplication is true, correctand
complete, and that I am the property owner or duly authorized agent of the property owner to submit a permit application to
the City of Edmonds.
Print Name: T,eyven Chin Owner []Agent/OtherF7)J (specify): Permit Coordinator
Signature- Date:
FORM E LABuilding New Folder 201000NE & x-ferred to LBuilding-New driveTorm E 2014.docx Updated: 1/17/2014
Equipment Type
MECHANICAL
Appliance/Equipment Information (new and relocated)
Total #
Furnace
Gas #—Elec
#—Other:—
#_ BTUs: <100k— >100k— Location(s)
Air Handier / VAV
(circle selected)
Gas #—Elec
#—Other:—
#—CFM: <10k_ >10k Location(s)
AC / Compressor
Boiler / Heat Pump
Roof Top Unit
(circle selected)
Gas #—Elec
HP:
#—Other:—
<3, _3-15,
#_ BTUs:—<100k, 100k-500k, 5OOk-lMil
_15-30 Location(s)
Hydronic Heating
Gas #—Elec
#—In-Floor ___�Wall
Radiant— Boiler BTUs:_ Location
Exhaust Fans (single
duct)
Bath #
Kitchen # Laundry # —Other: #
Fireplace
Gas #—Elec
#—Other:—
#_ Location(s)
Dryer Duct
Appliance Type
Appliance/Equipment Information (new and relocated)
Total #
AC Unit
BTUs:
Location(s):
Furnace
BTUs:
Location(s):
Water Heater
BTUs:
Location(s):_
Boiler
BTUs:
Location(s):
Other:
BTUs:
Location(s):
Fireplace/Insert
BTUs:
Location(s):
Stove/Range/Oven
Dryer
Outdoor BBQ
TOTAL OUTLETS
PLUMBING FIXTURE COUNT
Fixture Type (new and relocated) Total # Fixture Type (new and relocated)
Total #
Water Closet (Toilet)
Pressure Reduction Valve/Pressure Regulator
Sink (kitchen, laundry, lavatory, bar, eye wash, etc.)
Water Service Line
Tub/Shower
Drinking Fountain
Dishwasher
Clothes Washer
Hose Bib
Backflow Prevention Device (e.g. RBPA, DCDA, AVB)
Water Heater Tankless? YesEj
NoEj
Hydronic Heat in: Floor EJ wall El
Floor Drain/Floor Sink
Other:
Refrigerator water supply (for water/ice dispenser)
Other:
FORM E LABuilding New Folder 2010\DONE & x-ferred to L-Building-New driveTorra E 2014.docx Updated: 1/17/2014
Arl )"%
1P
DEVELOPMENT SERVICES
COMMERCIAL & MULTI -FAMILY BUILDING CHECKLIST
4 1215'h Avenue N, Edmonds, WA 98020
est, I sl)�� Phone 425.771.0220 9 Fax 425.771.0221
City of Edmonds
PROJECTADDRESS: 201 /'10�,V� r_()M0"3SJWA9�0?_0
PRE -APPLICATION MEETING? YES NO [7 If YES, Pre -application Number:
Plans shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed, and conform to the provisions of
the adopted International Codes and City Ordinances.
n >
tr 10
n
W
CW
SUBMITTAL REQUIREMENTS
The number indicates the number of copies for
submittal (if applicable). Check marks indicate
additional submittal requirements that may
apply to your project.
Ro �e
eD
7 n
M 0
C1
5
eD
z
M
4
a
F .3
M
-i —
M
a
M
eD
a
"ft
4
Z "I --I
—
>
0 11 5'
0
CD
V
Application Form E
Site Plan
3
3
3
3
3
3 F/C
Reduced Site Plan (11 X 14 or 8 1/2 x 11)
1
1
1
1
1
1 F/C
3 V/
Construction Drawings
3
3
3
3
3
3
Structural Drawing and Calculations
3
3
3
3
WA State Energy Code NREC Calcs & Lighting
V/
V/
V/
Site Classification Worksheet
3
3
Site Development Plans/Civils
4
4
Engineering Report/Drainage Calculations
3
3
Landscape Plan
3
3
Right —of-Way Permit Application
I
I
Critical Areas Determination or Checklist
I
I
Geotechnical Report
3
3
Health District Approval Letter
V/
Manufacturer's Specifications/Cut Sheets
V/
V/
3
Contractor's City of Edmonds Business License
V/
V/
V/
V/
V/
Washington State Contractors License
V/
V/
V/
V/
Plan Check Fee (due upon submittal)
V/
V/
V/
V/
V/
Traffic Impact Analysis
3
3
3
3
Survey
3
3
Special Inspection and Testing Agreement
V/
V/
V11
Envelope Plans and Documents/Condos
2
2
Bonds
I
I
V/
Architectural Design Approval
I
I
Peer Review Fees
V
V/
Deferred Submittals
I/
V/
Shop Drawings
V/
V/
Street Use
V/
• Handouts and Standard Details may be found on the City's website www.edmondswa.�zov or can be obtained at City Hall
during normal business hours.
• Plans/calculation/reports prepared by state licensed architects or professional engineers must be stamped and signed by the
design professional.
FORME LABuilding New Folder 201MONE & x-ferred to L-Building-New driveTorm E 2014.docx Updated: 1/17/2014
WASF
November 13, 2018
To whom it may concern,
This letter is to ensure that the Fire Alarm Plans for 201 Main St, Edmonds WA, 98020 have been
reviewed & approved for review by Phong Nguyen NICET Level 3. Certificate No. 139398 Exp.
01/01/2021.
•
FAO. 0 1
•
FAO.02
•
FAO.03
•
FA4.00
APR 0 8 2019
•
FA4.01
•
FA4.02
DEVELOPMM I otnv luct, G1 h-
CRY OF EDMONDS
•
FA4.03
•
FA9.01
For any questions regarding this project please refer to the contact person listed on the application.
Thank you,
L
NICET M A,
CWT. No, 139338 Exp 01/01/2021
Phong Nguyen
Washington Alarm Inc.
pnizuyen@washingtonalartn.com
206.391.2029
2030 Airport Way S UL LISTED CENTRAL STATION
Seattle WA 98134-1603 LICENSED & BONDED ELECTRICAL CONTRACTOR
WASHIAI2820
P: 206-328-3288
F: 206-322-7214
www.washingtonalarm.com
it �
WASHIN
Prepared By:
Eric Hamerski
Washington Alarm, Inc.
1420 King St
Bellingham, WA, 98229
360.733.1330
WASHIA12820
CITY COPY
EDMONDS MIXED USE
201 MAIN ST
EDMONDS, WA, 98020
Job:18313-1
Date: October 10,2018
SeCrr.jVF-0
8 20
SejRVjr'LS O'K.
0MLOr"4T,E0,
5 LL)-z- C)� q -
6820
Addressab[e Fire Alarm Control Panel
The 6820 is an add ressablefire alarm control pa net (FACIP) that can
be configured to achieve an overall point capacity of up to 1,110
points and connect up to 17 panels in a single communications Link.
It has one built-in signaling Line Circuit (SI-Q, which can support 159
(SK) Systern Sensor"'sensors and 159 SK modules or 127 (SID) Hochiki"'
devices per Loop. To increase point capabilities, additional SLC loops
can be added using the 6815 SLC expander for SK devices or the
5815XL expander for SID devices, increasing the point capacity to a
maximum of 1,110 points for SK devices and 635 points for SID devices.
Three additional SLCs are needed to reach 1,110 points (SK devices).
6820
Four additional SLCs are needed to reach 635 points (SD devices).
The 6820 also has Form C trouble relay, and
A common communications and annunciation link allows up to 17
two programmable Form C relays, along with
panels to be connected via copper or fiber optic cable. A designated
powerfLll features such as drift compensation,
panel is configured asthe communicatorfor all panels in the tinkfor
pre -trouble maintenance alert, a built-in sensor
convenient singte-point communications. It also has a built-in, dual-
Lest to complywith NFPA 72 calibration testing
Line POTs and IP communicator and optional cellular side -cars.
requirements, and calibration trouble alert.
The 6820 system can be enhanced by adding modules such as the It supports a variety of devices, including the
6860 remote annunciator which also has "our programmable lunction 6860, 5860, and 6855 remote annunciators,
buttons to help automate tasks and reduce time spentatthe panel. 5824 serial parallel printer interlace module (for
printing system reports), the 5496 NAC expander,
SWIFT'wireLess compatibility provides options lorwireLess detection 5895XL power module, and SK or SID devices.
through a Class A mesh network. It is idea[ for hard -to -wire locations,
buildings where new wiring is not allowed, or to provide an easy
install fire system for new construction projects. SWIFTdevices can
be combined with other hard -wired 6820 compatible devices.
FEATURES & BENEFITS
- Capable of providing
up to 1,110 points for
enhanced design
flexibility. Additional
Signal Line Circuits
can be added until
maximum point levels
arereached.
- Built-in USB interface
for convenient and
quick programming
- Connect up to 17
panels on one site with
convenient single -
point access using the
SK-NIC Network
Interface Card.
Connected panels can
have mixed compatible
FACP modeLs.
- Convenient
fieLd-upgradealote
firmware.
* Integrated dual path
I P and POTs
communications and
optional cellular
side -cars for reliable
backup
* 6860 annunciator with
a 4 x 40 large display,
and 4 programmable
function buttons.
Free -up time spent at
the panel. Prograrn
them for simple or
compLextasks.
• Programmable date
setting for automatic
and convenient
Daylight Saving Time
changes
• Built-in dual phone
line and digital alarm
communicator/
transmitter (DACT) for
additional
COMMUnication
options
- Flexput- circuits can
be individually
programmed to
function as
notification circuits,
auxiliary power
outputs, or initiating
circuits that support
both 2- and 4-wire
smoke detectors
6820 Product Information
SIGNAL LINE CIRCUIT (SLC)
I
The 6815 signal tine circuit (SLC)
supports multiple device types or SK
protocol, white the 5815XL signal tine
circuit (SLC) supports muLtipte device
types of SID protocol. You cannot mix
SID and SK SLC devices on a FACP_
The 6820 has one built-in signaling
tine circuit (SLC) which supports
multiple devices. Additional points
can be added using the 6815 SLC
expanders to increase overall capacity
to 1,110 maximum points (SK devices)
or by adding up tofour 5815XL SLC
expanders to reach 635 maxil-1-ILIM
points (SD devices). The number of
SLCs which can be used within one
system is Limited by point count. (See
the Manual for additional inion-nation.)
alarm, supervisory, system trouble,
system silenced and system power.
System operations include silencing
alarms and troubles, resetting alarms
and the display of alarm troubles and
memory. The systern's non-voLatile
event history buf4er stores 1,000
events ,or viewing From the built-
in or remote annunciator. System
operations can be initiated with a
mechanical firefighter's keyor a
valid 4- to 7-digit operator's code.
recommended. The 6820 also has
13 preset notification cadence
patterns (including ANSI 3,41),
AGENCY LISTINGS AND APPROVALS
NFPA 13, NFPA 15, NFPA 16, NFPA
70, NFPA 72: Centratstation; remote
Signaling: LocaL Protective Signaling
Systerns: Auxiliary Protected Premises
Unit; Water Deluge releasing service.
Suitable forautornaLic, manLiat,
waterftow, sprinklet supervisory (DACT
non -coded) signaling services.
• UL Listed:
• CSFIVI 7165-0559:0500�
• FDNYCOA#6249;
• FIVI approved-,
• Seismic (CA) (pending)
The 6820 SLC loops support multiple 6820 KEYPAD ORDERING INFORMATION
device types, maintenance alerts, and a
built-in sensor test to comply with NFPA
72 calibration testing requirements.
INDICATOR LIGHTS
• General Alarm (Red): Flashes if in
ala rn-i; solid when alarm is silenced
• Supervisory (Yettow): Flashes if a
Supervisory condition exists; solid
when supervisory is silenced
• System Troubtes (Yettow): Flashes
if a trouble condition exists;
solid when trouble is silenced
System Silenced (Yellow):
On when an alarm, trouble or
supervisory condition has been
sitenced but not yet cleared
System Power (Green): Flashes
for AC failure; solid when
power systems are normal
USERINTERFACE
The 6820 built-in 4 x 20 annunciator
with 80 character LCD display
and Large easy -to -use tactile
touchpad can be used for system
operation, programming and
maintenance. It has five LEDs for
PROGRAMMING
The 6820system offers several options
to simplify and speed-up programming.
JumpStart"'AutoProgran-ii-ning
minimizes prograrnming required to
start a new system. The built-in keypad,
or the 6860, 5860 or 6855 rernote
annUnciators give you on -site access
to Current systen-) programming. You
can also program the system using
the Honeywell Fire Software Suite
(HFSS), which is Windows' based.
SOFTWARE TOOLS
SKST. Silent Knight Selection Tool.
provides the installer ordesign architect
with a Windows' software system
configuration tool. to create a detailed
BitLof Material (BOM) and battery
calculations.
HFSS: Honeywell Fire Software Suite
provides communication and panel
programming, detector status, event
history and additional data. Requiresa
Windows -based computer.
ADDITIONAL INFORMATION
Twisted -u nshielded pair wire is
6820: Addressable Fire A[arm
Control Panel. (Red cabinet) -
COMPATIBLE ANNUNCIATORS
6860:4x4O LCD remote fire
annunciator(4 lines and up to
160characters) per system; four
programmable buttons
5860:4x2O LCD remote fire
annunciator. 5860 is gray; 586OR is red
6855:4x2O LCD remote fire
annunciator
5865-3 or 5865-4: LED annunciators
can display up to 30 LEDs (15 red and
15 yellow). The 5865-4 has key switches
for silence and reset, and a system
trouble LED.
5880:The 5880 LED / 10 module
has 40 programmabLe LED outputs
and eight supervised dry contact
inputs which are useful for CLIStOrn
applications. You can Use LIP to eight
5880 modules on one control panel for
maximum flexibility. Its compact size
allows mounting inside the annunciator,
or in an accessory cabinet.
6820 COMPATIBLE DEVICES AND
ACCESSORIES
See t lie data sheets listed below for a
complete listing of theSK. SD or S'�,'IFT
devices.
53623: SK Devices Data Sheet
53624: SID Devices Data Sheet
350614,350616) & 350618: SWIFT
wireless devices
For a complete and current listing of
compatible devices and accessories go to
www.sitentknight.com
Important: You cannot mix SK and SID
devices in th.,�p same fire alarm system.
SK COMPATIBLE ADDRESSABLE
DEVICES
SK-ACCLIMATE: Multi criteria
photoelectric smoke detectorwith thermal
13511F fixed temperture
SK-BEAM: Reflected beam smoke detector
without test feature
SK-BEAM-T- Reflected beam smoke
detector with test feature
SK-CONTROL: Supervised control module
SK-CONTROL-6: Six circuit supervised
control module
SK-DUCT: Photoelectric duct smoke
detector with extended air speed range
SK-FIRE-CO: Four criteria fire and carbon
monoxide detector
SK-HEAT. Fixed thermal detector (1350F)
SK-HEAT-ROR: Fixed rate of rise detector
(1350F)
SK-HEAT-HT. Fixed high temperature
thermal detector (1901F)
SK-ISO: Fault isolator module
SK-MINIMON: Mini monitor module
SK-MONITOR: Monitor module
SK-MONITOR-2: Dual inpUt monitor
module
SK-MON-10: 10 input monitor module
SK-PHOTO: Photoelectric smoke detector
SK-PHOTO-T. Photoelectric smoke
detector with thermal (135OF fixed
temperture)
SK-PHOTOR- Photoelectric detector with
remote test capability
SK-PULL-SA: Addressabte single action
put( station
SK-PULL-DA: Addressable dual action putt
station
SK-RELAY: Addressable relay module
SK-RELAY-6: Addressable Six relav control
module
SK-RELAYMON-2: Addressable Dual relay/
monitor module
SK-ZONE: Addressable zone interface
module
SK-ZONE-6: Six zone interface module
B210 LP: 6" mounting base
8501: 4" Flangeless mounting base
B20OS: Intelligent sounder base
B20OS-LF: Low-f requency intelligent
sounderbase
B224RB: Relay base
B224BI: Isolator base
SO COMPATIBLE ADDRESSABLE
DEVICES
SD505-6AB: Addressable 6" base
SD505-61B: Addressable 6'short circuit
isolator base
SD505-6RB: Addressable 6"retay base
SID505-16SB:Addressable 6'sounder base
SD500-AIM: Addressabte, input module
(switch input)
SD500-ANM: Addressabte notification
module
SD500-ARM: Addressable relay module
SD505-DTS-K: Remote test switch and
LED indicator for the SD505-DUCTR
SD505-DUCT: Addressable Duct Smoke
Detector.
SD505-DUCTR: Addressable Duct
Detector housing with relay base.
SD505-HEAT: Absolute temperature
heat detector. Trip point range from
135OF-150OF(OOC-370C).
SD500-LIM: Addressabte Line isolator
module
SD500-MIM: Addressable Mini input
monitor mod ule (switch input)
SD505-PHOTO: Photoelectric smoke
detector
SD500-PS/-PSDA: Addressable Single or
dual action pull station
SD500-SDM: Addressable smoke detector
module
AUDIBLE/VISIBLE DEVICES
These AV devices are all 2-wire. Cotor:"R'
indicates red; "W' denotes white. For a
complete listing of Silent Knight AV devices
go to www.sitentknight.com.
C H S R L/C H SW L: Wa It chime/strobe
CHSCRL/CHSCWL: Ceiling chime/strobe
C H R L/C HW L: Wa It chime
H RL/HWL: Watt horn
P2RL/P2WL: Watt horn/strobe
PC2RL/PC2WL: Ceiling horn/strobe
SRL/SWL: Wall strobe
SCRL/SCWL: Ceiling strobe
SPSCRL/SPSCWL: Ceiling speaker/strobe
SPSRL/SPSWL: Watt speaker/strobe
SPRL/SPWL:Wall speaker
SPCRL/SPCWL: Ceiling speaker
SWIFT WIRELESS DEVICES
SWIFT is only compatible with
Systern Sensor (SK) devices. It is not
compatible with Hochiki (SD) devices.
WSK-WGI: Wireless Gateway
WSK-PHOTO: Wireless Photoelectric
smoke detector
WSK-PHOTO-T. Wireless M Utti - cri ter ia
photoelectric smoke detectorwith thermal
detection (1350Ffixed temperture) and
B51OW 4" base
WSK-HEAT.- Wireless Heat, (135OF fixed
temperture) and B51OW 4" base
WSK-HEAT-ROR:Wit-eless heat. ROR
(135OF fixed temperture) and B51OW 4'
base
WSK-MONITOR: Wireless monitor module
WSK-RELAY:Wiretess relay mod ule
W-USB: SWIFTToots USB transceiver used
for Communication with SWIFT devices
SIBUISACCESSORIES
6815: Each Single Line Circuit allows for
an additional 159 SK modules and 159 SK
sensors to be added to the system -up to
1,i10 total points. Supports System Sensor
SK devices only.
5815XL: Each Single Line Circuit provides
an additional 127 SD devices to be added to
the system Jor a maximum of 635 points.
Supports SD devices only.
5496: A 6 amp notification power expander
with four power -limited notification
appliance circuit Outputs.
5883: Relay Interface. Provides 10 Form C
relays.
5824: Serial/ParaItet Printer Interface
Module for printer connection.
5895XL: Power Supply with six F(expu t7'1
circuits, and two Form C relay-,. Max. 16 per
system.
5815RMK: Remote mounting kit.
Dimensions 10 3/8"W x 10-3/16"H x 3"D
COMMUNICATION OPTIONS
CELL-CAB-SK: Cellular communicator,
metal enclosure with tock/key*
CELL -MOD: Cellular communicator, plastic
enclosure*
*Sote path. powered by panel.
IPGSM-4G: Dual path fire alarm
communicator. cellular and/or I P (primary
or backup. selectable)
SKAP-2: Remote reporting via the Internet.
Requires a VisorAtarm"' receiverat the
central station
MISC. ACCESSORIES
SK-NIC: Network Interface Card. Provides a
common communications link for the 6820.
SK-NIC-KIT. Installation Accessory Kit
SKFML: Fiber -Optic Multi Mode,
transmitter and receiver
SK-FSL: Fiber -Optic Single Mode
RBB: Remote battery box accessory cabinet
for batteries that are too large to fit in the
FACP cabinet. Dimensions: 16'W x 10-'H x
6'D (406mm W x 254mm H x 152rnm D).
SK-SCK: Seismic Compliance Kit used to
seCLirelyfasten batteries to the fire panel.
6820 Technical Specifications
PHYSICAL
FLEXPUTCIRCUITS
For a complete listing of all
Overall Dimensions: 16.36'W x 26.37' H x 3.9i"D
Six programmable circuits which can be
compliance approvalsand
Shipping Weight: �')2 lh-�
programmed individually as:
certifications, pteasevisit
www.siLentknight.com,
Color: Pell
Notification Appliance Circuits: 3A C. 27.4VDC
per circuit. power-Umited (with a panel maximum
Microsoft, Windows, and
ENVIRONMENTAL
current of 6A)
the Windows Logo are
Operating Temperature: 321F to 120OF (OIC to
Auxiliary power circuits: 3A @ 27.4VDC per circuit,
registered trademarks
ortrademarks of
490C)
power-Unnited
Microsoft Corporation,
Humidity: 0 to 93��oreiative humidity (non-
Initiating Circuits (Circuits 5 and 6 Only): iOOmA
condensing)
t_z 27,4VDC per circuit. power limited
Silent Knight'�, Honeywell"
and SWIFT" are
ELECTRICAL
Supports Class B (Style 4) and Class A (Style 6)
registered trademarks
and ReXpUt"' is 8
6820 Primary AC: 120AC @ 60Hz, 3.3A Total
configuration for SLC, SBUS, and Flexput circuits
trademarkof Honeywell
Accessory Load: 6A Ia, 27.4VDC power-timited
International, Inc
Standby Current: 190mA
WIRING: See the product manual forwiring details
This document is not
Alarm Current: 250mA
intended to be used for
Battery Charging Capacity: 17 to 35AH
installation purposes. We
Battery Size: 18AH max- allowed in control panel
try to keep ou r prodUCt
information up -to
cabinet. Larger capacity batteries can he housed in
date and accurate. We
RBB accessory cabinet.
oarinat cover a U spoci fic
applications or anticipate
all reoUirements. All
specifications are. subject
to change witho'A notice.
ForTechnicat Support,
call 800-Li46-641414.
For more infDrmation
Learn more about Honeywell Sitent Knight
and other products byvisiting
wwwsitentknightcorn
Honeywell Silent Knight
12 Clintonville Road
Northford. CT 06472 351610 1 A 111/17 Honeywell
800-328-0103 M 2017 Honeywell International Inc.
SILENT ModeI5895XL
KNIGHT Intelligent Power Module
(D The intelligent way to distribute power
by Honeywell throughout your installation.
With 6.0 amps of output power, six programmable Flexp UtTM 1/0 circuits, and two Form C relay contacts, the
Model 5895XL Intelligent Power Module allows you to greatly enhance the capabilities of an IntelliKnight system,
distributing power where needed throughout a facility.
5895XL modules connect via the RS-485 system bus. Up to eight 5895XL modules can be used per IntelliKnight
system. Each 5895XL has its own optically isolated RS-485 bus to which other modules, such as 5860 remote
annunciators and 5824 printer interface modules, can be connected. You can also connect 5815XL SLC
expansion modules, adding flexibility and wiring distance. Each 5895XL supports its own backup batteries and
monitors the AC power.
Description
5895XL adds 6.0 amps of power, six Flexput 1/0 circuits, and
two Form C relay circuits to an IntellilKnight installation.
The 5895XL is optically isolated providing ground loop
isolation and transient protection. The 5895XL conditions the
RS-485 system bus allowing up to an additional 6,000 feet of
wiring.
Operation
The green LED on the 5895XL board indicates communication
with the IntellilKnight FACP.
The Flexput circuits can be notification appliance circuits,
continuous power, resettable power, door holder power or
initiation circuits that can support both 2- and 4-wire smoke
detectors.
All Flexput circuits and relay outputs are individually mappable
from the IntellilKnight 5820XL FACP.
Features
• 6.OA output power
• Flexput 1/0 circuits, 3A each, programmable as notification
circuits, auxiliary power circuits, or initiation circuits
• Supports Class A configuration for SBUS & Flexput circuits
- Ground loop isolation
• 2 Form C programmable relays rated at 2.5A at 24 VDC
• Transient protection
• SBUS repeater conditions the RS-485 signal
• Up to 6,000 feet wiring distance from 5895XL (same
distance as main FACP)
• Battery charging capacity 35 Ah
• Large cabinet can house two 18 Ah batteries or RBB
accessory cabinet can house battery sizes larger than 18 Ah
• Room in FACP cabinet to mount two 5815XL SLC
expander's
• Built-in synchronization for appliances from AMSECOO,
Gentex@, Faraday, System Sensor@, and Wheelock@
LZ3
Model 5895XL
Approvals
- NFPA 13, NFPA 15, NFPA 16, NFPA 70,
NFPA 72 and NFPA 101
• UL 864; CSFM
• MEA429-92-E, Vol. IX
• FM approved
• OSHPD (CA) OSP-0065-1 0
ModeI5895XL
Intelligent Power Module
Engineering Specifications
The contractor shall supply a power module compatible with the IntelliKnight Model 5820XL FACP. The power
module must have 6.0 amps of output power, Flexput 1/0 circuits rated 3.0 amps each, and two Form C relay
contacts rated at 2.5 amps at 24 VDC. The power module shall connect to the main FACP via an RS-485
system bus (SBUS). The power module shall contain an additional RS-485 bus that is completely compatible
with all IntellilKnight add -on modules, including 5815XL SLC expander's, 5860 remote annunciators, 5824
serial/parallel printer interface modules.
The power module RS-485 bus shall be optically isolated providing ground loop isolation and transient
protection. The unit shall be an SBUS repeater that conditions the signal driving up to 6,000 feet of additional
wiring.
SLC
z
m
ca
C
0
'LC
I ;IN SIXISINIOUT
23 22 21 20 19 18 17 16 32 31 30
A 11 4, A B + A �'B
NACs, Auxilary
Power.
611241 L!!n used in
Class A
configurations Up to 6,000 Feet, Non -shielded
NACs, Auxilary Power, etc
5895XL-1 SBUS
58601 158601 15824
Electrical Specifications
Primary AC:
120 VRMS @ 60 Hz, 2.5A
240 VRMS @ 60 Hz, 1.4A
Total Accessory Load:
6A @ 24 VDIC
Current:
Standby: 40 mA
Alarm: 160 ITIA
Mechanical Specifications
Flush or surface mount
Dimensions:
14-1/2"W x 24-3/4"H x 3-7/8"D
(36.8 W x 62.9 H x 9.8 D cm )
5896XL Connection to FACP
5895XL Installation Example
23 22 21 20 19 IS 17 16
- + A B " .+ A 11
0313 '? 0 121 (2) (2)
Used in To Next
Class A SBUS Device
Configurations
NACs, Auxiliary Power, etc.
5896XL-2 SBUS
To Next 5895XL
Overall Dimensions:
16-1/8"W x 26-3/8"H x 4-1/8"D
(40.6 W x 67 H x 11.8 D cm)
Color: Red
Environmental
Operating Temperature:
32-F — 120OF (0- — 49-C
Humidity: 10% — 93%
non -condensing
Ordering Information
5895XL Intelligent Power Module
Accessories
SK-SCK Seismic Compliance Kit
SILIEW This document is not intended to be used for installation purposes. We try to Assembled in America
keep our product information up-to-date and accurate. We cannot cover all
KNIGHT specific applications or anticipate all requirements. All specificabons are subject to PN 350212 Rev F
change without notice. For more information, contact Silent Knight 12 Clintonville 0 2014 Honeywell International Inc.
by Honeywell Road, Northford, CT 06472 Phone: (203) 484-7161, Fax: (203) 484-7118. For
Technical Support, Please call 800-446-6444. www.silentknight.com.
Holxmz-
SMENT,
XINIGHT
46011811
Remote Annunciator
The S860 remote annunciator, can be used to operate and program
Honeywell Silent Knight fire alarm control pa nets (FACPs) from anywhere
within the system.
The 5860 features inctude an 80-character backlit LCD providing easy -to
understand system messages. The annunciator is ergonornicalty designed
with over -sized buttons lor the most frequently used features, like Reset
and Silence.
In addition to status messages displayed on the LCD, there are five LEDs
for alarm, supervisory, trouble, silence, and AC power status.
The 5860 annunciator is available in gray to match virtually any decor and
red "or applications where the annunciator must standout, The
annunciator enclosure can be surface or ftush mounted. A trim ring kit is
available for surface mounting.
COMPATIBILITY
The 5860 is compatible with the following Honeywell Silent Knight FACPs:
6820:,�ddressabte fire alarm controtpanet with up to 1,110 add ressable points
6820EVS: Ad dressable fire alarm control panel with an ern erg ency
communication systems and up to 1.110 add ressaWe points
6808: Add ressable fire alarm control panel. with up to 198 add ressable points
6700:AddressabLe fire alarm control pa net with up to 100 add ressablepoints
5820XL:Addressable fire alarm control pane I
5820XL-EVS:Addressabte fire alarm control panel with an emergency
communication systems
5808: Addressabte fire alarm control panel.
5700: Addressable fire alarm control panel
FEATURES & BENEFITS
- 80-characterbacklit
LCD display (4 lines
with 20 characters per
Line)
Tactile/audibte
feedback when a key is
pressed on the
annunciator
- Uses the RS-485
SBUS to interface with
the panel
• Support for
simultaneous use of
multiple 5860s
• Easily view current
status by alarms,
SUpervisories, or
troubles
- Five Status LEDs
- Available in red or tight
gray color
5860 / 58GOR
- Accommodates wiring
lengths up to 6000 ft.
from the control panel
for added design and
install flexibility
• Accepts user codes or
fire fighter's key
• Larger keypad buttons
makes it easier to
maneuver for system
reset and silencing
5860 Technical Specifications
111ISO111111111I
xi&EWzi&a
Wire Runs Up to 6000 Feet From FACIP
0
:7,
SIBUS
qq ro.!, M
- Up to Eight 5860s Per 5700 or 6700 System
- Up to 12 5860s Per 5808, 6808, 5820XL, or 5820XL-EVS System
- Up to 16 5860s per 6820 or 6820EVS System
Compatible Silent Knight FACP
5860 Features
PHYSICAL
ORDERING INFORMATION
Dimensions: 9.1'Wx 7.4'H x 1.5"D (23.1Wx
18.8H x S860: Remote Annunciator. four line (4x20) LCD
3.81D cm)
annunciator with 20 characters per tine. Gray
Shipping Weight: 2.8 lbs (1.3 kg)
586OR: Remote Annunciator. four line Nx20) LCD
Color: 586OR: Red: 5860: Gray
annunciator with 20 characters per tine. Red
ENVIRONMENTAL
ACCESSORIES
Operating Temperature: 321F to 120'F (O'C to 5860TR: Red Trim Ring for surface mounting
490C)
586OTG: Gray Trim Ring for surface mounting
Humidity: 10% - 93% non -condensing)
AGENCY LISTINGS AND APPROVALS
ELECTRICAL
UL listed
Operating Voltage: 24VDC
CSFM approved
Standby Current: 20mA
Meets N FPA 72 requirements
Alarm Current: 25mA
FM approved
MEAapproved
For more information
Learn more about Honeywell Silent Knight and other
products by visiting
www.sitentknight.corn
Honeywell Sitent Knight
12 Clintonville Road
Northford, CT 06472
800-328-0103
Dnc 35022/4 1 �ZevJ 112/17
Cc' 2017 Honeywetl International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit
www.sitentknight.com,
Microsoft, Windows, and
theWindows Logo are
registered trademarks
ort(ademarks of
Microsoft Corporation.
Silent Knightl� and
Honeywell" are registered
t rademarks of Honeywell
international, Inc.
This document is not
intended to be used for
installation purposes. We
try to keep our product
information up -to
date and accurate. We
cannot cover a[[sipeclfic
applications or anticipate
all requirements, A[[
specifications are subje.ct
to changewithout notice.
ForTechnical Support,
call 800-446-644/1.
Har�L)Jq'V'V'V3E
rSILENT
r7l� EN[GHT
Honeywell
SILENT'
WGffr
6815
Signaling Line Circuit Expander
The 6815 is a signaling line circuit (SLO expanderfor use with Honeywell
Silent Knight 6820 or 68210EVS fire alarm control panels (FACPs)using
System Sensor' (SK) protocol. The 6815 signaling circuit has the same
functionality as the SLC that is built into the 6820 and 6820EVS panels
and support the same addressabLe devices as the one in each panel. The
number of 6815 SLCs that can be used within one systern is Largely
dependent on maximum available points. They provide a powerful way to
customize configurations in large or complex installs.
The 6820 and 6820EVS panels support up to 1, 110 maximum points and
come with one integrated SLC. Each added 6815 can support an
additional 159 SK devices, and 159 SK modules.
The 6815 can also be used for SWI FT1 wireless detection, SWIFT wireless
devices communicate with the FACID throug h a gateway (WSK-WGI) that
connects to the SLC using SK protocol. The integrated SLC, or a 6815 SLC,
can be used for this purpose, SWIFT devices can also be combined with
hard -wired devices on the same SLC for additional versatility. The result is
more flexibility and design options when hard -wire solutions are
problematic.
The 6815communicates with the FACIP via an RS485 system bus. A green
LED on the 6815 board blinks to indicate good communication. 1, an
add ressabte device on a 6815 1 a its, the Loop communicates the failure to
the 6820 and 6820EVS and continues to operate normaLty
FEATURES & BENEFITS
- The number of 6815
SLCs that can be used
in one system is
largely determined by
maximum point
counts. With 1,110
available points on the
6820 and 6820EVS
and6815SLC
flexibility, new design
and installation
opportunities are now
possible.
Use the 5815RMK
mounting kit to
securely house more
SLCswithin one
system.
Pair with the separate
6860 remote
annunciator for
additional installation
and operating options.
The 6860 has four
programmable
buttons that are useful
for executing routine
or complex tasks.
6815
- Up to two additional
6815 SLCs can be
securely housed in one
FACP, thus limiting the
need for separate
housing
Useful for installations
where buildings are
connected for
muffi-site benefits
using fiber optic or
copper wiring. The
ability to use multiple
6815 SLCs in these
situations provides
additional fire system
design options.
6815 Technical Specifications
Here is an example ofthe 6820 FACP with
one integrated SLC and two additional 6815 SLCs
installed in the panel. Two additional 6815 SILC
are also installed inside a 5895XL Intelligent
power module.
In this case the design has a total ol`5 SLC
loops, with 6815 SLC expander flexibility, many
more could be added as long as additional power
supplies are added and any related installation
needs are considered-
6820 FACP
5896XL Power Module
S� L-1 3 0
Film
M co 17;
U
a US to SBUS wy n,
4�
BattL
ryi i Battery
SLC L-4 SLC L— 5
DESIGN VERSATILITY. THE 6815SLC EXPANDER
PHYSICAL ACCESSORIES
Dimensions: 4.2'H x4.8"W(10.7 x 12.2 cm) 5895XL: Intelligent Power Module. Cabinet holds
Shipping Weight: 5.6oz (159g) two 6815s.
5815RM K: Remote Mounting Kit Cabinet holds two
ELECTRICAL 6815s. Red.
Standby & Alarm Current: 78mA max
ENVIRONMENTAL
Operating Temperature: 320F to 120OF (OOC to
490C)
Humidity: 0 to 93% non -condensing
SYSTEM CAPACITY
6815 Capacity: 159 SK sensors and 159 SK
modules per loop
The maximum 1.110 point count forthe 6820 and
6820EVS, and related support requirements, limit
the number of 6815 SLCs that can be added to a
fire system installation.
ORDERING INFORMATION
6815: Signaling Line Circuit Expander.
For more information
Learn more about Honeywell Silent Knight and other
products by visiting
www.silentknight.corn
Honeywell Silent Knight
12 Clintonville Road
Northford. CT 06472
800-328-0103
AGENCY LISTINGS AND APPROVALS
UL listed
CSFM approved 7165-0559:0500
Meets NFPA 72 requirements
FM approved
FDNY COA (pending)
COMPATIBILITY
* 6820: AddressabLe fire alarm control paneL
with up to 1,110 addressable points
* 6820EVS: AddressabLe fire alarm control panel
with an emergency voice system, up to 1,110
addressabLe points
*Hochikil (SM devices utilize the 5815XL
signaling tine circuit(SLU
351628 1 A 111/17
@ 2017 Honevwett International Inc.
Fora complete listing ofatt
compliance approvals and
certifications, please visit
www.sitentknight.com.
Microsoft, Windows, and
theWincows Logo are
registered trademarks
or trademarks of
Microsoft Corporation.
SieInt Knight", Systern
Sensor'9@nd HoneywelP
are registered
fadernarks of Honevwell
International Inc
This document is not
intended to he used for
installation purposes. We
try to keep our product
information up -to
date and accorate. We
cannot coverallspociffic
applications or anticipate
all requirements. All
specificitions are subject
to change without notice.
ForTechnical
Support, Please call
800-W16-6/014.
FiR==,�7unM
FSELENT'
MGHT
0 SILENT Die Cast Metal
KNIGHT Manual Pull Stations
by Honeywell Silent Knight die cast metal manual pull
stations put quality and peace of mind
in easy reach
A manual pull station doesn't have to be fancy —just tough, reliable and extremely easy to operate. Silent
Knight's die cast metal pull stations are all three. they're the high -quality choice for fast, sure initiation of a fire
alarm signal.
Our manual pull stations feature rugged, die cast metal construction that lasts and lasts. they're available in sin-
gle or dual action models. And the Silent Knight PS-SATK and PS-DATK pull stations are UL-Listed, CSFM
Approved, and MEA (BSA) Approved. For outdoor use, a weatherproof model is also available.
On your next job, make the high -quality choice —Silent Knight manual pull stations. For more information, or
additional information on our complete fire products line, call Silent Knight at 1-800-328-0103.
Description
The PS-DATK and PS-SATK manu-
al pull stations feature high -quality,
die cast metal construction. They
are available in either single or dual
action configurations with SPST
switch, and terminal strip connec-
tions. The normally open contact,
which closes when the pull station
is activated, is rated for 1 amp, at
125 VAC or 30 VDC. The contacts
are gold-plated to avoid risk of cor-
rosion. All models in the series
have been tested by UL for compli-
ance to the latest requirements of
the Americans with Disabilities Act
(ADA).
Features
. UL listed
• CSFM approved
• MEA (BSA) approved
• ADA compliant
• Weatherproof model approved
for outdoor use
• Single or dual action
• Terminal connections
• Reset using the same keys as
Silent Knight enclosures
• Surface mount backboxes avail-
able
• High -gloss red enamel finish on
die cast metal
• Corrosion -resistant gold-plated
contacts
Operation
The single action pull stations are
operated by simply pulling the han-
dle on the front of the Station as far
down as it will go, at which point
the handle locks into place and is
easily visible from up to 50 feet. A
scored acrylic break rod is also
supplied with each unit for applica-
tions where it is necessary. the
handle is reset by opening the sta-
tion with a key, placing the handle
in the normal upright position and
relocking the station.
On the dual action models, pushing
the PUSH bar causes it to rotate
inward, allowing the PULL handle
to be grasped in a one -handed
motion. The dual action models are
also supplied with break rods. Dual
action models are reset in the
same way as a single action
model.
The weatherproof version of the
pull stations is provided with a gas-
ket and die cast metal backbox
tapped on one end for 1/2" conduit,
for surface mounting.
M*w%l �ssa�
PS-SATK
Single Action Pull Station
PUSH
PULL
Q
PS-DATK
Dual Action Pull Station
PS-DATK and PS-SATK
Die Cast Metal Manual Pull Stations
Engineering Specification
The PS-SATK and PS-DATK manual pull stations are die cast metal construction painted with red enamel. The pull stations
contain the word FIRE in two locations on the front of the units as well as the Silent Knight company logo. Operating instruc-
tion are clearly visible on the front of the units. These manual stations contain a key operated reset lock, using a lock plate
actuator. The reset key and lock shall be the same as used on the FACP.
These manual stations shall contain two terminals for connection to the conventional fire detection loops.
Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the American
Disabilities Act .
Specifications
Ordering Information
Switch Rating:
1 amp at 125 VAC, or 30 VDC.
Model
Description
Pull Station
PS-SATK
Pull Station, Single Action, Terminal
Dimensions:
4-3/4" H x 3-1/4" W x 1-1/8" D
Connection, Key Reset
Surface Mount
PS-DATK
Pull Station, Dual Action, Terminal
Backbox
ConnectJon, Key Reset
Dimensions:
4-3/4" H x 3-1/4" W x 2-1/4" D
PS-SATK-WP
Pull Station, Single Action, Terminal
(cast and sheet metal).
Connecfion, Key Reset, Weatherproof Box
Color:
Red with raised white letters, white
PS-WP13
Weatherproof Box
PULL bar with raised red letters.
Accessories:
All models are supplied with one
PS -BB
Back Box
scored acrylic break -rod and a key.
PS-GR-12
Box of 12 Scored Acrylic Break Rods
To Fire
Alarm
Control
Panel
Wring Diagram - Termina
Screw
Terminals
To Next
Device
or ELR
This document is not intended to be used for installation purposes. We try to MADE IN AMERICA
0SILENT keep our product information up-to-date and accurate. We cannot cover all
KNIGHT specific applications or anticipate all requirements. All specifications are sub- P/N 350792 Rev. C
. ject to change without notice. For more information, contact Silent Knight @ 2014 Honeywell International Inc.
by Honeywell 12 Clintonville Road Northford, CT 06472-1610 Phone: (800) 328-0103,
Fax: (203) 484-7118. For Technical Support, please call 800-446-6444.
www.silentknight.com
SK-PHOTO-W Series
Intelligent P[ug-In Photoelectric Smoke
Detector
Honeyweit Silent Knight SK-PHOTO-W Series ptug-in smoke detectors are
designed for both performance and aesthetics. A new modern, sleek,
contemporary design and enhanced optical sensing charriber is
engineered to sense smoke produced by a wide range o� combustion
sources in accordance with more stringent code standards.
The SK-PHOTO-W Series detector sensitivity can be prograrnmed in the
control panel software. Sensitivity is continuously monitored and reported
to the panel. Point ID capability allows each detector's address to be set
with rotary, decirnaL address switches, providing exact detector location for
selective maintenance when chamber contamination reaches an
unacceptable level.
Dual electronic thermistors add 1351F (5710 fixed temperature thermal
sensing on the SK-PHOTO-T-W. The SK-PHOTO-R-W is a remote test
capable detector for use with DNR Series duct detector housings.
FEATURES & BENEFITS
• New modern profile for
improved aesthetics
• Stable communication
technique with noise
immunity
• Low standby current
• Two-wireSLC
connection
- Optional remote,
single- gang LED
accessory
• Dual LED design
provides 3600 viewing
angle
• Remote test feature
from the panel
• Built-in functionattest
switch activated by
external magnet
• Built-in tamper -
resistant feature
- Seated against back
pressure
• Expanded color
options
• S EMS screws for
wiring of the separate
base
SK-PHOTO-W
- Optional relay.
isolator, and sounder
bases
- Plugs into separate
base for ease of
installation and
maintenance
DETECTOR SPACING AND INTELLIGENT BASES ACCESSORIES
APPLICATIONS
Honeywell. recommends spacing
detectors in compliance with NFPA 72.
In low airflow applications with smooth
ceiling, space detectors 30 feet (9m),
For specific information regarding
detector spacing, placement, and
special applications refer to NFPA 72,
System Smoke Detector Application
Guide, document A05-1003. is available
at systemsensor.com
INSTALLATION
The SK-PHOTO-W Series ptug-iin
detectors use a separate base to
simplify installation, service, and
maintenance. Installation instructions
are shipped with each detector.
Mount base (all base types) on an
electrical backbox which is at Least 1.5"
(3.81 crn) deep.
NOTE:
- Because of the inherent supervision
provided by the SLC loop, end-ol-tine
resistors are not required. Wiring
"T-taps'or branches are permitted for
Style 4 (Class "B") wiring.
- When using relay or sounder bases,
consult the installation sheet for device
Limitations between isolator modules
and isolator bases.
ORDERING INFORMATION
SK-PHOTO-W: Photoelectric smoke
detector, white.
SK-PHOTO-R-W: Photoelectric smoke
detector, remote test capable, for use
with DNR(W) duct smoke detectors,
white.
SK-PHOTO-T-W: Photoelectric smoke
detector with thermal sensing, white.
B300-6: White, standard flanged
tow -profile mounting base.
B300-6-BP: Bulk pack of B300-6,
package contains 10.
B300-6-IV: Ivory, standard flanged
tow-profi le mounting base.
B501-WHITE: White, standard
CK300: Color Kit (includes cover and
trim ring), white, 10-Pack.
CK300-IV: Color Kit (includes cover
and trim ring), ivory, 10-Pack.
CK300-BL: Color Kit (includes cover
and trim ring), black, 10-Pack.
M02-04-01: Detector test magnet.
European flangeless mounting base. UL
M02-09-00:Tetescoping test magnet.
listed.
RA10OZ: Remote LED annunciator
B501-BL: Black, standard European
SMB600: Surface Mounting Kit
ftangetess mounting base. UL listed.
J la nged).
B501-IV: Ivory, sLandard European
TR300: Replacement trim ring for
ftange[ess mounting base. UL listed.
B300-6, white.
B20OS-WH: White, I nteLLigent,
TR300-IV: Replacement trirnring for
programmable Sounder base.
8300-6-IV, ivory.
B20OS-IV: Ivory, Intelligent,
programmable sounder base.
B200SR-WH: White, I nteLLigent sounder
base for retrofit applications.
B200SR-IV: Ivory, I nteLLigent sounder
base for retrofit applications.
B20OS-LF-WH: WhiLe, Low Frequency
IntelLigent, programmable sounder
base.
B20OS-LF-IV: Ivory, Low Frequency
Intelligent, programmable sounder
base.
B200SR-LF-WH: White, Low
Frequency Intelligent sounder base lor
retrofit applications.
B200SR-LF-IV: Ivory, Low Frequency
Intelligent sou nder base for retrofit
applications.
B224RB-WH: White, ptug-in System
Sensor relay base.
B224RB-IV: Ivory, plug-in System
Sensor relay base.
B224BI-WH: White, plug-in System
Sensor isolator detector base.
B224BI-IV: Ivory, plug-in System
Sensor isolator detector base.
SK-PHOTO-W Series Detector Technical Specifications
PHYSICAL
Height: 2.0"(51mm) installed in B300-6 base
Diameter: 6.2" (156mm) installed in B300-6
base 4.1" (104 mm) installed in B501 base
Weight: 3.4 oz (95 g)
ENVIRONMENTAL
Operating Temperature range:
Photo: 321F to 122'F (01C to 501C)
Photo with Thermal: 321F to 1001F (01C to
380C)
UL listed Velocity range: Photo/Photo with
Thermal: 0 to 4,000 f prn (0 to 20 rn/sec)
�suitabl.e lor installation in ducts)
Humidity: 10% to 93% non -condensing
Thermal Ratings: Fixed Temperature Set point:
1350F(57"C)
ELECTRICAL RATINGS
Voltage Range: 15 to 32VDC peak
Operating Current @ 24VDC: 20O.uA (one
communication every 5 seconds with green LED
blink on communication)
Maximum Current: 4.5mA @ 24VDC (one
communication every 5 seconds with arnber LED
solid on).
For more information
Learn more about Honeywell Silent Knight and other
products by visiting www.silentknight-corn
Honeywell Silent Knight
12 Clintonville Road
Northford. CT06472
800-328-0103
COMPATIBILITY
The SK-PHOTO-W series detectors are
compatible with the following Honeywell Silent
Knight fire alarm control panels:
6820: Addressabte fire alarm control panel
6820EVS: Addressabte fire alarm control panel
with an emergencyvoice system.
6808:Addressabte fire alarm control panel
6700: Addressable fire alarm control panel
5700: Addressabte fire alarm control panel
5808:Addressabte fire alarm control panel
5820XL: Addressable fire alarm control panel
5820XL-EVS: Addressable fire alarm control
panel with an emergency voice system
AGENCY LISTINGS AND APPROVALS
For exact certification listings for each model.
please reference the respective agencyWeb site.
UL listed: S6173
FM approved
CSFM: 7272-0559:0523
Doc 3516314 1 RevA 104/13
C) 2018 Hon�ywelt Intanational Inc -
For a complete listing of all
compliance approvals and
certifications, pieasevisit
www.sitentknight.com.
Microsoft, Windows, and
theWindows Logoare
registered trademarks
ortrademarksof
Microsoft Corporation.
Silent Knight', System
Sensor" and Honeywell"
are registered
trademarks of 1-loneywell
International, Inc.
This document is no[
intended to be used fcr
installation purposes. We
try to keep ou r product
information Lp-to
date and accurate.We
cannot cover altspecific
applications or anticipate
all requirements. All'
specifk-,ations are subject
to change without notice.
ForTechnical Support,
call 800-14465-6444.
Honeywell
CSELENT'
3XMGlfr
Honeywell
SICLENT'
MGHT
SK-ACCLIMATE
Intelligent Multi -Criteria Smoke Detector
The SK-ACCL I MATE Multi criteria Photoelectric Smoke Detector
incorporates both thermal and photoelectric technologies that interact to
maximize detection. An on -board microprocessor with advanced software
focuses on rejecting nuisance alarms. The SK-ACCLIMATE is for use with
the Honeywell Silent Knight series fire alarm control panels (FACPs).
Using advanced software. SK-ACCLI MATE continuously samples the air in
the environment and adjusts its detection parameters and alarm threshold
accordingly. And it does this automatically. without user intervention. A
dual stage dri"t compensation feature reduces maintenance frequency.
SK-ACCLIMATE offsets the effects of g raduat dust buitd-up a nd will notify
the control panel Wore its compensation level is reached, allowing time
I or maintenance. Once the compensation limit is reached, a second signal
is sent to the control. panel indicating an urgent need for maintenance.
BASE COMPATIBILITY
SK-ACCLIMATE is compatible with the following detector bases:
B21OLP: 6'base (included)
B501:2 wire base
B224RB: Relay base
B224BI: Isolator base
B200SR: Sounder base
FEATURES & BENEFITS
• Reliableanalog
- Microprocessor- based
- Variety of mounting
communications for
design to provide
options to meet any
trouble -free operation
maximumfeatures
application
• Dual electronic
- Simple field cleaning
- Dual LED indicators
thermistor design
for code compliance
for 3600 visibility
6" mounting base 0.025- mesh bug
included screen to keep
Superior EMI unwanted insects out
resistance for
reliability
0
SK-ACCLIMATE (BASE INCLUDED)
• Detector transmits
signal to indicate
maintenance is
required
• Detector sensitivity
increases in hot fires
- Transient smoke
conditions are ignored
- Rotaryaddress
switches forfast
installations
SK-ACCLIMATE Technical Specifications
PHYSICAL
Height: 2.0"(5.Ocm)
Diameter: 6.1'(155mm) installed in B201LP base
Shipping Weight: 5.2oz U47g)
ELECTRICAL
Operating Voltage: 15-32VDC
SLC Standby and Alarm Current: 300ltA @ 24VDC
(one communication every 5 sec with LED enabled)
LED Current: 6.5mA @ 24 VDC max (when on)
ENVIRONMENTAL
Operating Temperature: 321 -1001F (OOC - 380C)
Humidity: 10% - 93'�/o non -condensing
THERMAL RATINGS
Thermal: Fixed Temperature Set point: 135oF
(570C)
Velocity: 0 - 4000 fpm (0 - 6.1 m/sec)
Insect Screen Hole Size: 0.025'(0.64 mm) nominal
For more information
Learn more about Honeywell Silent Knight
and other products by visiting
www.silentknightcorn
Honeywell Silent Knight
12 Clintonville Road
Northford. CT 06472
800-328-0103
For a complete tisting of all
ORDERING INFORMATION
compliance approvals and
SK-ACCLIMATE: Mutti-criteria photoelectric
certifications, ploase visit
smoke detector
www.sitentknight.com.
Microsoft, Windows, and
ACCESSORIES
theWindows Logo are
RA10OZ: Rernote LED annunciator
registereo trademarks
RMK400: Recesses mounting kit. Provides tow
ortrademarks of
profile for use with 8501
Microsoft Corporation,
XR2B: Detector removal too[. A removal and
Silent KnightL, System
replacement too[ for SK series plug-in detectors.
Sensor, and Honeywell'
Includes the TSS-127-000
are registered
M02-04-01: Detector test magnet.
trademarks of Honeywell
International, Inc.
M02-09-00:Test magnetwith telescoping handle
XP-4: Extension Pole for XR213. Extends from 5 -
This doc�,ment is not
15 ft.
intended to be used For
installation purposes. We
T55-127-000: Detector removal head
try to keep our product
information Up-tO
COMPATIBILITY
oateand aCCUrate.We
The SK-ACCLI MATE is compatible with the
cannoteover allspecific
following Honeywell Silent Knight fire alarm
applications or anticipate
all requirements. All
control panels:
specifk-.atlons are Subject
6820: Addressabte fire alarm control panel
to change without notice.
6820EVS: Addressabte fire alarm control panel
For Technical Suppor t,
with an emergency mass notification system.
cat[800-446-6444.
6808: Addressable fire alarm control panel
6700: Addressable fire alarm control panel
5700: Addressabte fire alarm control panel
5808: Addressabte fire alarm control panel
5820XL: Addressabte fire alarm control panel
5820XL-EVS: Addressabte fire alarm control panel
with an emergency mass notification system.
Doc 3501211 Rev E 111/17
@ 2017 Honeywell International Inc.
Honeywell
SI]LINT*
Honeywell I nte RI gent/ Address able Devices
SILENT' I
RX[G1-rF
Intelligent Bases
Standard, Re[ay, Isolator, Sounder, and Low Frequency Sounder Bases
Generall
To meet local code and application requirements, Silent Knight' offers standard 4'
and 6' bases. as well as, specialty base designs including relay. isolator, sounder and L
towfrequency sounderoptions forthe new SK-W Series of addressabte detectors as
Z,4
well as previous generations. -A
The standard 4' and 6" bases offer a plug-in detector base intended for use in
intelligent systems, with screw terminals provided for power (+ and -). and remote
annunciator connections. Communication takes place over the power (+ and -) tines.
The 4'base offers a compact design while the 6" base provides compatibility with a
wider range of junction boxes.
The specialty bases support application driver requirements. These bases employ a
separate mounting plate that installs on various junction box sizes to eliolinate
unsightly surface -mount boxes. The mounting plate enables pre -wiring of all
connections to speed and simplify installation.
Relay bases (B224RB-WH/I3224RB-IV) provide one form-C contact relayfor control
of auxiliary functions. such as door closure and elevator recall. The relay can operate
in two different modes (shortand tong delay). The activation time for the short delay
is 60-100 milliseconds, white the activation time for the long delay is 6-iO seconds. A
shuntwith pin headers, located on the base PC board, is used to set the delay timing.
Isolator bases (8224BI-WH/B224BI-IV) allow the Signaling Line Circuit (SLC) loop to
operate underfault conditions created from a short circuit preventing an entire
communication loop from being disabled. The base isolates the section of the loop
containing the short circuit from the remainder of the circuit and automatically
restores when the fault is corrected.
Sounder and low frequency (-LF) sounder bases are designed for new and existing
dwelling unit applications. They offer maximum flexibility in installation,
configuration, and operation to meetor exceed UL 268 and UL 464 requirements. The
low frequency sounder bases are designed to rneet the NFPA 72 steeping space
requirementto produce a fundamental frequency of 520 Hz +/- 10% with a square
wave or its equivalent. Studies show that a lower frequency, centered around 520 Hz,
is the most ideal to wake sleeping occupants, even those with rni[d to severe hearing
loss.
FEATURES & BENEFITS
- Bases enable quick and - Support for 12-24 AWG - Standard white color
secure detector plug-in
provides installation
with ivory and black
• SEMS Screws provide
flexibility
options
easy wiring connection
- Multiple base formats
Mechanical locking
• UL268comptiant
meet application
feature restricts removal
requirements
of attached sensor head
8300-6 Standard 8300-6-IVStatidard 6"
6 " Ba s e (Wh ite) Base (Ivory)
B20OS-WH Sounder
B20OS-LF-WH Low
Base(White)
Frequency Sounder Base
(Wh ite)
B501 -WHITE Flangeless
B501-BLFlangeless4"
4" Base (White)
Base (Black)
Specialty Base Features:
- Pre -wired mounting
platesimplifies
installation
- Application driven
feature sets
- Sounder bases both
UL268 and UL464
compliant
The 8200S sounder and LFsounder bases (B200S-WH/B200S-IV/
8200S-LF-WH/B20OS-LF-IV) adopt the same address as the
detector. but use a unique device type on the loop. The Fire Atarm
Control Panet(FACP) can use that address to command an individual
sounder — or a group of sounders — to activate. The command set
from the FACP can be tailored to multiple event -driven tone outputs
allowing selection of volume (75 or 85 dBA), tone (ANSI Temporal 3,
ANSI Tempora[4. or March Time) and group. In addition, sorne FACPs
will enable custom tone patterns. The 8200S series sounder bases
recognize the System Sensor synchronization protocol. This enables
B20OS-IV: Ivory, Intelligent addressable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3,
ANSI Temporal 4, continuous tone. marching tone, and custom tone.
Uses SK protocol.
B20OS-LF-WH: White. Low Frequency Intelligent, programmable
sounder base. Produces a fundamental frequency of 520 Hz +/- 10%
with a square wave or its equivalent: designed to rneet the NFPA 72
sleeping space requirement.
B20OS-LF-IV: ivory, Low Frequency Intelligent, programmable
them to be used as a component of the general evacuation signal — sounder base. Produces a fundamental frequency of 520 Hz +/- iO%
ith a square wave or its equivalent: designed to rneetthe N"PA 72
along with otherSystern Sensor AV appliances — when connected to a w
power supply or FACP output capable of generating the System steeping space requirement.
Sensor synchronization pulses. B200SR-WH: White, Intelligent sounder base capable of producing
The B200SR sounder and LF sounder bases (B200SR-WH/B200SR-
IV/B200SR-LF-WH/B200SR-LF-IV) are fully compatible with existing
B501BH Series sounder base installations. The device enables users
to select one of two B501-supported tones (ANSI Temporal 3 or
Continuous) through a jumper.
Product Line Information
INTELLIGENT BASES
"-IV'suffix indicates Ivory color model.
'-BL7 suffix indicates Black color model.
'-WH" and '-WHITE" suffix indicates White color model.
6300-6: White, 6' base, standard flanged low -prof ile mounting base;
replacement base for the 821OLP.
6300-6-BP: Bulk pack of B300-6, package contains 10: replacement
forthe 821OLPBR
B300-6-IV: Ivory.6' base, standard ftanged tow -profile mounting
base.
B501-WHITE: White, 4'standard European ftangeless mounting
base. UL/ULC listed.
B501-WHITE-BP: Bulk pack of B501-WHITE contains 10.
B501-BL: Black, 4"standard European flangetess mounting base.
B501-IV: Ivory coLor.4'standard European flangeless mounting base.
B224RB-WH: White, relay base.
B224RB-IV: Ivory, relay base.
8224BI-WH: White. isolator detector base.
8224BI-IV: Ivory isolator detector base.
B20OS-WH: White. Intelligent addressable sounder base capable of
producing sound output in high or low volume with ANSi Temporal 3,
ANSI Temporal 4, continuous tone, marching tone, a nd custom tone.
Uses SK protocol.
Page 2 of 4 — SK-61045:A - 7/18/2018
sound output with ANSI Temporal 3 or continuous tone. intended for
retrofit applications.
B200SR-IV: Ivory. Intelligent sounder base capable of producing
sound outputwith ANSI Temporal 3 orcontinuous tone. Intended for
retrofit applications.
B200SR-LF-WH: White, Low Frequency Intelligent, programmable
sounder base. Produces a fundamental frequency of 520 Hz +/- 10%
with a square wave or its equivalent: designed to meet the NFPA 72
steeping space requirement. Intended for retrofit applications.
B200SR-LF-IV: ivory, Low Frequency Intelligent, programmable
sounder base. Produces a fundamental frequency of 520 Hz +/- 10%
with a square wave or its equivalent: designed to meet the NFPA 72
steeping space requirement. Intended for retrofit applications.
MOUNTING KITS AND ACCESSORIES
TR300: White, replacement flange for B300-6 base.
TR300-IV: Ivory, replacement flange for B300-6-IV base.
RA10OZ: Remote LED annunciator. 3 — 32 VDC. Mounts to a U.S.
single -gang electrical box. For use with B501 and B300-6.
M02-04-00: Test magnet.
M02-09-00: Test magnet with telescoping handle.
CK300: White, detector color kit. Pack of 10.
CK300-IV: Ivory, detector color kit Pack of 10.
CK300-BL: Black, detector color kit. Pack of 10.
Junction Box Selection Guide
Base Models
Single Gang
Double Gang
3.5" Ocz.
4.0" Oct.
4.0" Square
4.0" Square with 3.0" mud ring
50 mm
60 mm
7
.OMM
T5MM
B200S.B200SR
"'es
Yes
Yes
Yes
Yes
Yes
No
IN a
N o
No
B501
No
No
Yes
N o
No
Yes
Yes
Yes
Yes
No
B300-6
Yes
No
Yes
Yes
Yes
Yes
No
No
N o
No
B22481,B224RB
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Box d epth contingent on base and wire size,
Refer to National Electric Code or applicable loca I cod es for a ppropria te recom mend a tions.
Applies to all model variants W, '-LF",'-IV'. '-W.H, and "-WH I TE'. See Prod Uct Li ne I nforma tion for d eta iled model description.
Page 3 of 4 — SK-61045A - 7/18/2018
Intelligent BaseS Technical Specifications
ELECTRICAL
For B300-6 Series bases:
Operating voltage: 15 to 32 VDC
Standby current: 170 pA maximum
For B501 Series bases:
Operating voltage: 15 to 32 VDC
Standby current: 150 pA maximum
For B200 Series bases:
External supply voltage: 16 to 33 VDC (FWR)
Standby current: 500 pA maximurn
Alarm current for B20OS(-IV)(-WH):
35 mA maxi i-nuni at high -volume setting
15 mA maxinnurn at low -volume setting
Alarm currentfor B20OS-LF(-IV)(-WH) High -volume
setting:
70 rn.A maxi mum @ 33.0 VDC
90 rnA maximu m @ 24.0 VDC
140 mA maximum Ca,16.0 VDC
Alarm current for B20OS-LF(-IV)(-WH) Low -volume
setting:
15 mA maximu m @ 33.0 VDC
20mAmaximum@24.OVDC
25 mA maximum @ 16.OVDC
Alarm current for B200SR(-IV)(-WH):
35mAmaximum
Alarm current for B200SR-LF(-1VX-WH):
65 mA maximum @ 33.OVDC
90 mA maximum @ 24.OVDC
125 mA maximum Ca 16.0 VDC
SLC operating voltage: 15 to 32 VDC
SLIC standby current: See applicable sensor
specification
Sound output: Greater than 85 dBA minimum;
measured in a LIL reverberant room at 10 feet, 24 Volts
(continuous tone)
For B2241311, B224RB (-IV) (-WH) bases:
Operating voltage15 to 32 VDC (powered by SLC)
Standby ratings: <450 pA maximum @ 24 VDC
Set time: (B224RB(-IV)(-WH) only): short delay 60- 100
milliseconds; long delay 6-10 seconds
Reset time: (B224RB(-IV)(-WH) only): 20 milliseconds
maximum
Relay characteristics: (B224RB(-IV)(-WH) only): two -
coil latching relay: one Form-C contact; ratings M L/
CSA): 0.9 A @ 125 VAC. 0.9 A @ 110 VDC, and 3.0 A @ 30
VDC
HoneywettSitent Knight
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.sitentknight.com
PHYSICAL
Note: Specificationsappties to all model variants'-BI:,"-LF","-iV'. 41-1, -
WHITE. See product Line Information for detailed model description.
Diameter
B501-WH ITE: 4"(10.16 cm)
B300-6,: 6.1"(15.49 crn)
B224BI, B224RB: 6.2'(15.748 crn)
B200S, B200SR: 6.875"(17.46 cm)
Wire gauge
B224BI, B224RB: 14 to 24 AWG
B300-6, B501, B200S, B200SR: 12 to 24 AWG
Temperature range
B224BI, B224RB, B200S, B200SR: 32'Fto 120OF(OI)C
Lo 491)Q.
B300-6, B501: -4'F to 150OF (-200C to 6600.
Humidity range: i00/b to 93% RH, non -condensing.
System temperature and humidity ranges- This system
meets NFPA requirements for operation atOIC to 49'C
(321F to 1200R, and at a relative hurnidity (non -
condensing) of 850/c at 301C (861F) per '4FPA, and 93%
2% at 321C ± 20C (89.61F ± 1.119 per U LC. However, the
useful life of the system's standby batteries and the
electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is
recornmended that this system and aR peripherals be
irstatted in an environment with a nominal room
temperature of 150C to 27'C (60OF to 800F).
AGENCY LISTINGS AND APPROVALS
The listingsand approvatsbetowapplyto intelligent bases
as noted. In some cases, certain modules orapplications
may not be listed bycertain approval agencies, or listing
may be in process. Consult factory for latest listing status.
UL/ULC Listed: S911
FM Approved
CSFM: 7300-1653:0109.7300-1653:0126,
7300-1653:0213,7300-1653:0238
SK-61045 I A 1 07/18
0-2018 Idoneywett International Inc.
Silent KnightO and System
Sensor" are registered
tradernarks of Honeywe[l Inc,
t-52018 by Honeywe[l.
International Inc. A[1. rights
reserved. Unauthorized use of
this docurrent is strictly
prohibited,
This document is not intended
to be used for instattation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific appkcatioos
or anticipate a[[ requirenlents,
All specifications aresubjectto
change without n0tiM
Honeywell
SILENT'
Honeywell
SELENT'
IC14IGHT
SK-HEAT-W Series
Intelligent Thermal (Heat) Detector
Honeywet[Sitent Knight SK-HEAT-W Series intettigent thermal detectors
are designed [or both per flormance and aesthetics. Anew modern, sleek,
contemporary design and advanced thermaLtechnotogies rn a ke the
SK-HEAT-W Series idea[ for both system operation and bui[di rig design.
The point I D address. set using rotarydecirn at switches, provide specific
detector locations. The series includes a 135'F/57'C fixed temperature,
rate -of -rise and a 1901F/881C fixed high -temperature detectors. These
thermal detectors provide el fective, intelligent property protection in a
variety of applications.
FEATURES & BENEFITS
• Sleek and stylish
contemporary design
• Advanced thermal
technology for fast
response
• Fixed temperature
inodet(SK-HEAT-W)
factory preset to
1350F(570C)
• Rate -of -rise model
(SK-HEAT-W-ROR),
151F (8.31M per
minute
- High temperature
tnodet(SK-HEAT-
W-HT) factory preset
to 1901F (881C)
• Addressable by device
• Two-wireSLC
connection
- VisibteLEDs'bLink"
every time the unit is
addressed
- Built-in tamper -
resistant feature
• 3601-field viewing
angle of the visual
alarm indicators (two
bi-color LEDs). LEDs
btink green in Normal
condition and turn on
steady red in Alarm.
• Integral
communications and
buift-in device -type
identification
- Remote test feature
from the panel
S K- H EAT-W
• Built-in functional test
switch activated by
external magnet
• Walk test with address
display (an address of
121wiliblinkthe
detector LED 12-
(pause)-I)
• Low standby current
• Designed for
directsurface or
electrical box
mounting
- Sealed against back
pressure
- Plugs into separate
base for ease of
installation and
maintenance
- SEMS screws for
wiring of the separate
base
- Optional remote,
single- gang LED
accessory
APPLICATIONS
Use thermal detectors for protection of
property. For further information, refer
to manual 156-6541, Applications
Manual for System Smoke Detectors,
which provides detailed information on
detector spacing, placement, zoning,
wiring, and special applications
INSTALLATION
The SK-HEAT-W Series plug-in
i nteLLigent thermal, detectors use a
separate base to simplify installation,
service, and maintenance. Installation
instructions are shipped with each
detector
Mount base (aLL base types) on an
electrical backbox which is at Least 1.5"
(3.81 cm) deep.
NOTE:
0 Because of the inherent supervision
provided by the SLC Loop, end -of -Line
resistors are not required. Wiring
"T-taps" or branches are permitted for
Style 4 (Class "B") wiring.
- When using relay or sounder bases,
consult the installation sheet for device
Limitations between isolator modules
and isolator bases.
NOTE: Detectors must be mounted to one
of the Intelligent Bases listed below.
ORDERING INFORMATION
SK-HEAT-W: TherrriaL heat detector,
1351F fixed, white.
SK-HEAT-ROR-W: Thermal. heat
detector, 1351F rate of rise, white.
SK-HEAT-HT-W: Thermal heat detector,
1901F high temp, white.
INTELLIGENT BASES
B300-6: White. standard flanged
low-profite mounting base.
B300-6-BP: Bulk pack of 6300-6.
package contains 10.
B300-6-IV: Ivory, standard flanged
tow-profite mounting base.
B30OA-6-IV: Ivory, standard flanged
low-profi(e Mounting base. ULtisted.
8501-WHITE: White, standard
European flangetess mounting base. UL
listed.
B501-BL: Black, standard European
f(ange(ess mounting base. UL listed.
B501-IV: Ivory, standard European
flangeless mounting base. UL listed.
B20OS-WH: White, Intelligent,
programmable sounder base.
B20OS-IV: Ivory, Intelligent,
programmable sounder base.
B200SR-WH: White, Intelligent sounder
base for retrofit applications.
B200SR-IV: Ivory, I nteltigent sounder
base for retrofit applications.
B20OS-LF-WH: White, Low Frequency
Intelligent, programmable sounder
base.
B20OS-LF-IV: Ivory, Low Frequency
Intelligent, programmable sounder
base.
B200SR-LF-WH: White, Low
Frequency Inteltigent sounder base 1 or
retrofit applications.
B200SR-LF-IV: Ivory, Low Frequency
Intelligent sounder base for retrofit
applications.
B224RB-WH: White, plug-in System
Sensor relay base.
B224RB-IV: Ivory, plug-in System
Sensor relay base.
B224BI-WH: White, plug-in System
Sensor isolator detector base.
B224BI-IV: Ivory, plug-in System
Sensor isolator detector base.
ACCESSORIES
CK300: Color Kit OnCtUdes cover and
tri m ring), white, 10-Pack.
CK300-IV: Color Kit (includes cover
and trim ring). ivory, 10-Pack.
CK300-BL: Color Kit (includes cover
and trim ring), black, 10-Pack.
M02-04-01: Detector test mag net.
M02-09-00:TeLpscoping test magnet.
RA10OZ: Remote LED annunciator
SMB600: Surlace Mounting Kit
Cf[anged).
TR300: Replacement trim ring �or
B300-6, white,
TR300-IV: Replacement trimring for
B300-6-IV, ivory..
SK-HEAT-W Series Detector Technical Specifications
PHYSICAL
Height: 2.0" (51mm) installed in B300-6 base
Diameter: 6.2"(156mm) installed in B300-6
base 4.1" (104 mn-)) installed in B501 base
Weight: 3.4 oz (95 g)
ENVIRONMENTAL
Operating Temperature range:
Heat -Fixed temperature: -40Fto 100OF (-200C
to 3810
Heat -Rate of Rise (ROR): -40F to 1001F (-201C
to 3800
Heat -High Temperature: -40F to 150OF (-20oC
to 66'C)
H umidity: 10% to 93% non -condensing
Thermal Ratings: Fixed Temperature Set point:
1350F(570C)
Rate -of -Rise Detection: 150F/min. (8.31C/min
High Temperature Heat: 1901F (8810E[ectrical
Ratings
ELECTRICAL RATINGS
Voltage Range: 15 to 32VDC peak
Standby current (max. avg.): 200uACa, 24 VDC
(one communication every 5 seconds with LED
enabled).
LED current (max.): 4.5mA i� 24 VDC ("ON").
For more information
Learn more about Honeywell Silent Knight and other
products by visiting www.silentknight.com
Honeywell Silent Knight
12 ClintonviLte Road
Northford. CT06472
800-328-0103
COMPATIBILITY
The SK-H EAT-W series detectors are
compatible with the following Honeywell Silent
Knight fire alarm control panels:
6820: Add ressabte fire alarm control panel
6820EVS: Addressabie fire alarm control panel
with an emergency voice system.
6808: Addressabte fire alarm control panel
6700: Addressable fire alarm control panel
5700: Addressable fire alarm control panel
5808: Addressabte fire alarm control panel
5820XL: Addressabie fire alarm control panel
5820XL-EVS: Addressable fire alarm control
panel with an emergency voice system
AGENCY LISTINGS AND APPROVALS
For exact certification listings for each model.
please reference the respective agency Web site.
UL listed: S2101
FM Approved
CSFM: 7270-0559:0511
Doc 3516371 RevA 104/18
@ 2018 Honeywell International Inc.
For a. complete tisting of aft
compliance approvals and
certifications, pl��asevisit
www.siLentknight.com.
Microsol t, Windows, ano
theWindows Logo are
registered trademarks
or trademarks of
MicrosoftCorporation.
Silent Knight". System
Sensor' and Honeywell'
are registered
trademarks of Honeywell
International. Inc.
I his document is not
intended to he used for
installation purposes. We
try to keep our product
information up -to
date and accu(ate.We
cannot,7.over all specific,,
applications or anticipate
all requirements. All
specifications are subject
to change -withou It notice.
ForTechnica.t Support,
call 800-1446-6/444.
Honeywell
SI]LENT*
NMGlfr
(2,)POTTER
The Symbol of Protection
Features
• Dual Action (Rate of RiseNixed'remperature) or Fixed
Temperature only.
y
• Available with protective light hazard guard (specify "MPG"
when ordering).
• Up to 70* inter detector spacing.
• Secure fusible link mechanism locks contacts in alarm state
when releasing temperature is reached.
• Operating temperature range -40"Fi+250'F (40'C11120'C).
• Fly leads are factory installed and sealed in corrosion resistant
mounting plate.
Description
The MP Series is a standard THERMOFLEX' single circuit, Normally
Open contacts detectors. in which the connectivity is modified with
pigtail leads that extend through a seal plate.This provides for enhanced
protection against corrosive or raoisture-laden environ inents.
This detector is suitable for use in areas where condensation or
corrosion can have harmful effects on circuit wiring connected to
standard terminals. Its seal plate (with extended pigtail leads) will
mount onto a typical cast exterior back box.The detector is connected
to a fire alarm system's input circuit as an initiating device.The
internal contacts are normally open, and will close when the detector
operat,zseither on a rate of temperature increase, or if the releasing
temperature is reached. It is often installed with an addressing
module if it is to be annunciated as a specific room or space, e.g.
electrical room. garbage compactor. etc. With its non-metallic
diaphragm, the detector can operate normally at low temperatures,
making it suitable for non -heated or chilled environments including
garages and carports.
THERMOFLEX@
MP Series
Heat Detector
- - pa &
LISTED
7270-1110:0100 S2406
Technical Specifications
Dimensions
4.375" (11. 11 cm) x 2.0" (5.08 ern)
Device Weight
.4 1 lbs (. 19 gram s)
3 Amps at 125VAC
I Amp at 28VDC
Contact Ratings
0.3 Amps at 125VDC
0. 1 Amps at 250 VDC
Environmental
-20-F (-30-C) - 250`17 (120-C)
Limitations
Exclusive of Operating Temperature
Mounting
14" Round Standard WP Electrical Box
Potter Electric Signal Conipan�� LLC - St. Louis,. MO - Tech Support: 866-956-1211 / Customer Service: 866-572-3005 - ),"vwpottersignal.coni
883oO77-REVA - 8!15 PAGE I OF 3
(E)POTTER
The Symbol of Protection
Models CR-135MP, CR-165MP, CR-165MP, and CR-20OMP
THERMOFLEV
MP Series
Heat Detector
These models are dual -action types that will respond to a rate of temperature increase at the ceiling of 15' Fahrenheit de rees per minute (8.40 Celsius
9
degrees per minute). These detectors will also respond when the fixed temperature (non -restorable) threshold is exceeded. Dual -action detectors are
installed in areas where rapid fluctuations in ceiling temperatures are not expected -
Models CF-135MP, CF-165MP, CF-20OMP, and CF-285MP
These models are fixed temperature only detectors and should be installed in areas where rapid fluctuations in ceiling temperatures are expected.
Installation
On conventional, initiating circuits, or when using an addressing module. contacts are installed across the circuit such that operation ofthe detector will
create a short circuit condition. required in order to activate the fire alarni control panel (FACP). or addressing module.
Fig I
Initi
.... I
Circuit
3.5 inch
End of Line
Device
The detector is installed using rain -tight conduit and a standard. approved weatherproof
electrical enclosure as shown above. A neoprene (or similar gasket supplied with the back
box), is installed between the detector's seal plate and the back box. The wire leads are
connected to the initiating circuit inside the enclosure. Unused threaded openings are sealed
with threaded plugs. A decorative anodized aluminum cover ring snaps over the detector to
complete the installation.
Potter Electric Signal Company, LLC - St. Louis, MO - Tech Support: 866-956-1211 / Customer Service: 966-572-3005 - xNqv"vpottersignal.com
ISO 9001-20081DESIGNING, MANUFACTURING.
& DIST RIBUTING QUALITY SYSTEMS 8830077-REVA - 8115 PAGE 2 OF 3
(E)POTTER
The Symbol of Protection
Testing
Testing th e " CR " seriey detector
THERMOFLEV
MP Series
Heat Detector
Testingthe Rate-of-Riseportion. is acconipli shed by applying heat from a controlled heat source, such as a hair blo-vdi-ver. hold 8-12 in ches away
and aimed at the detector. The detector will respond within 6- 10 seconds. Providing that the fusible link has not released. tile detector will restore
as it cools.
NOTE. A heat ouli should not be used as the heat Output can easily fuse the detector.
C
• Portable test units designed specifically for this purpose are acceptable, and must be UL listed.
• Care must be taken to not allow the heat source to reach the device's fusing temperature. If the detector's fitsing temperature is reached and the
plunger is released. the detector will be in permanent alarni and must be replaced.
• Devices using open flame are prohibited front testing heat detectors. (ULC S536, ULC S537).
Testing the " CF" series detector
The Fixed Temperature Only detector, cannot be tested by warming the unit as permanent contact closure may result.. requiring replacement ofthe
detector. Shorting across the wire leads connected to the fire alann input circuit will confirm the circuit function and Zone identification.
Engineering Specifications
Fire Detection Devices Ltd. heat detectors for fire alarm systems comply with UL 521 Heat Detectors for Fire Protective Signaling Systems and ULC
S531 Standard for Heat Actuated Fire Detectors for Fire Alarm Systems. The UL/ULC control number is 411-19. file number S2466. CSFM listing
#7270-1110:0 100. Detectors featuring wire (pigtail) leads are included in these documents.
The detector is installed using rain -tight conduit and a standard. approved weatherproof electrical enclosure. A neoprene (or similar gasket supplied
with the back box), is installed between the detector's sea] plate and the back box. The wire leads are connected to the initiating circuit inside the
enclosure. Unused threaded openings are sealed with threaded plugs. A decorative anodized aluminum cover ring snaps over the detector to complete
the installation.
Ordering Information
Model
Description
Stock
Number
Operating
Ternpurature
MaxAmurnInstallation
Tempurature
Spacing Betweeen
Detectors
Spacing Betiveeen
Detectors Widi Guards
CR- 135MP
DualAction
1000137
135-F (57-C)
82-F (28-C)
707 (2 1 m)
40'(12m)
CR-165MP
Dual.Action
1000162
1657 (71-C)
I I 7-F (47-C)
7W (21m)
407 (12m)
CR-20OMP
DualAction
1000139
200-F (9YC)
156-F (69-C)
70" (21m)
40'(12m)
CF-135MP
Fixed Temp. Only
1000136
135-F (57-C)
82-F (28-C)
40'(12m)
25'(7.5ni)
CF-165MP
Fixed Temp. Only
1000163
165-F (71-C)
I I 7-F (47-C)
25'(7.5m)
20'(6m)
CF-20OMP
Fixed Temp. Only
1000138
200-F (93-C)
156-F (69-C)
25"(7.5m)
20'(6m)
CF-285MP
Fixed Temp. Only
1 1000164
1 285'F(140'Q
225'F (107.2'C)
25'(7.5m)
20 � (6m)
Potter Electric Signal Company. LLC - St. Louis. MO - Tech Support: 866-956-1211 / Customer Set -vice: 866-572-3005 - ww-tv.pottersignal.com
8830077-REVA - V15 PAGE 3 OF 3
Honeywell
SMENT'
KMGW
SK-MONITOR
Intelligent Monitor Module
The SK-MONITOR is an addressabte monitor mod utef or use with
Honeywell Silent Knight Series fire alarm control panels (FACPs). The
SK-MONITOR is intended for use in intelligent. two -wire systems. where
individual address of each module is selected using the bUift-in rotary
switches.
The SK-MONITOR supports Class A supervised or C[ass B supervised
wiring to the load device. Conventional.4-wire smoke detectors can be
monitored for alarm and trouble conditions.
INSTALLATION
The SK-MONITOR mounts directly into a 4' square electrical box. The box
must have a minimum depth of 2-1/8". A surface mount electrical box
(System Sensor' PN SM13500) is available 1 rom Silent Knight. SK-MONITOR
FEATURES & BENEFITS
• Single contact monitor
- Pane[controLLed
- U L Listed
• Support for Class A
status LED that
- Rotaryaddress
and Class B wiring
flashes green in
switches for fast
normal state and is
instattation
• Fully supervised
solid red in atarrn
- SEMS screws for easy
wiring
SK-MONITOR Technical Specifications
For a complete listing af, a[[
compliance approvals and
certifications, please visir
PHYSICAL
ORDERING INFORMATION
www.sitentknight.com,
Height: 4.S'H x4"Wx 1.2S'D (11.4 X 10.2 X 3cm)
SK-MONITOR: Monitor Module
Shipping Weight: 6.3 oz (196 g)
Microsoft, Windows, ano
the Windows Logo are
ACCESSORIES.
registered trademarks
ELECTRICAL
SMB500: 4"Square surface mountelectrical box
or trademarks of
Operating Voltage: 15 - 32VDC
Microsoft Corporation,
Current Draw (LED on): 5.OmA max
COMPATIBILITY
Silent Knight", System
Operating Current (LED flashing): 375uA
The SK-MONITOR is compatible with the
SensorL and Honeywell"
Standby Current: 400 uA max @ 24 VDC (one
following Honeywell Silent Kin ight fire alarm
are registered
communication every 5 sec with 47K EOU 550 pA
control panels:
trademarks of l-loneywell
max @ 24VDC (one communication every 5 sec
6820: Addressabte fire atarm control panel
Inteinationa[, Inc.
with EOL <1K)
6820EVS: Addressable fire alarm control panel
This docurnent is not
5.5 mA (with LED latched on)
with an emergency mass notification system.
intended to be used for
LED Current: 5.5 mA (with LED latched on)
6808: Addressable fire alarm control panel
installation purposes, We
End -of -Line Resistance: 47K Q
6700: Addressabte fire alarm control panel
try to keep our product
information up -to
Initiating Device Circuit Wiring Resistance: 1,500
5700: Add ressable fire alarm control panel
date and accurate. We
Qmax
5808: Addressabtefire alarm control panel
cannotcover atispecific
SLC Loop Resistance: 40 �2 rnax.
5820XL: Addressabie fire atarn) control panel
applications or anticipate
5820XL-EVS: Addressable fire atarm control panel
all requirements, Al I
speci fications are $Libje,-t
ENVIRONMENTAL
with an emergency mass notification system
to change without notice.
Operating Temperature: 320F - 1201F (01C -
491�(j
ForTechnical Support.
Humidity: 10% - 93% non -condensing
call 800-446-6444,
For more information
Learn more about Honeywell Silent Knightand other
products by visiting
www.si[entknightcorn.
Honeywell Silent Knight
12 CAintonvitte Road Honeywell
Northford. CT 06472 Doc 3501311 Rev G 111/17 SELENT
800-328-0103 0 2017 Honeywell International Mo. 13 XMGHT
Honeywell
i SmWr,
3 WGffr
SK-MONITOR-2
AddressabLe DuaL Monitor ModuLe
The SK-MONITOR-2 module is capable of monitoring two separate Class B
circuits simultaneously, making it ideal forwaterf[ow tamper switch and
f tow switch monitoring.
The SK-MONITOR-2 is an addressabte monitor modutewith two initiating
circuitsfor usewith Honeywell Silent Knight series fire alarm control panels
(FACPs). The SK-MONITOR-2 acts as an interface to contact devices, such
as waterftow switches and putt stations.
The SK-MONITOR-2sup ports Class Bsupervised wiring to the [oad device.
ConventionaL4-wire smoke detectors can be monitored ior a [arm and
trouble conditions..
INSTALLATION
SK-MONITOR-2 mounts directly into a 4" square etectricat box. The box
must have a minimum depth of 2-1/8". A surface mount etectrical box
kSystem Sensor' part number SMB500) is avai[abLe from Silent Knight.
FEATURES & BENEFITS
• Monitor two circuits
with unique
addresses,
simultaneously
• Support for Class B
wiring
• Fully supervised
- Panel controlled
status LED that
flashes green in
normal state and is
solid red in alarm
- Attractive ivory cover
plate
- Rotaryaddress
switches for fast
installation
- SEMS screws for easy
wiring
0, M18, W,
SK-MONITOR-2
SK-MOMTOP-2 Technica[ Specifications
Two initiat
St(ye B Po,
12VDC rn�
Wiring SK-Monitor-2 Modules
PHYSICAL
Height: 4 5' H x4"Wxl.25"D
Shipping Weight: 6.3 oz(196 g)
ELECTRICAL
Operating Voltage: 15 - 32 VDC
Standby and Alarm Current: 750VA max @ 24VDC
(one communication every 5 sec with 47K EOL)
End -of -Line Resistance: 47KO
ENVIRONMENTAL
Operating Temperature: 321F - 1201F (OIC -
490C)
Humidity: 10' /c) - 93c/, non -condensing
ORDERING INFORMATION
SK-Monitor-2: Duat Monitoring Module
ACCESSORIES.
SMB500:4" Square Surface Mount Electrical Box
For more information
Learn more about Honeywell Silent Knight and other
products by visiting
www.sitentknightcoi,n
HoneyweR Silent Knight
12 Clintonville Road
Northford. CT 06472
800-328-0103
AGENCY LISTINGS AND APPROVALS
UL LisLed
CSFM Approved
City of NewYork Approved
COMPATIBILITY
The SK-MON ITOR-2 is compatible with the
following Honeywell Silent Knight fire alarm
control panels:
6820: Addressable fire alarm control panel
6820EVS: Addressabte fire alarm control panel
with an emergency mass notification system.
6808: Addressable fire alarm control panel
6700: Addressable fire alarm control panel
5700: Addressabte fire alarm control panel
5808: Addressable fire alarm control panel
5820XL: Addressabte fire alarm control panel
5820XL-EVS: Addressabte fire alarm control panel
with an emergency mass notification system.
Doc 3501241 Rv E 111/17
@ 2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, pteasevisit
www.sitentknight.com.
Microsoft, Windows, and
theWindows Logo are
registered trademarks
or trademarks of
Microsoft Corporation.
Silent Knight', System
Sensor" and Honeywell"
are registered
trademarks ol Honeywell
International, Inc.
This document is not
intended to be,,sed -or
installation purposes. We
trvtc keep Our product
invormation up -to
date and accurate. We
cannot cover all specific
applications or anticipate
all requirements. All
specifications aresubject
to change without notice.
For Technical Su pport,
call 800-4146-6/4 414,
Honeywell
SELENT'
XMG]Frr
Honeywell
SmoqT'
KMGfff
SK-MINIMON
Intelligent Mini Monitor Module
The SK-M IN I MON is an add ressable monitor mod utes for use with the
Honeywell Silent Knight fire alarm control pa nets (FACIDs). The SK-
MINI MON acts as an interface to contact devices, such as waterf low
switches and put[ stations. The SK-MINIMON supports Class Bsupervised
wiring to the toad device. Conventional.4-wire smoke detectors can be
monitored �or alarm and trouble conditions
The SK-M IN I MON can be mounted in a single gang junction box directly
behind the monitored device. Its small size and tight weight a Ilow it to be
installed without rigid mounting requirements.
SK-MINIMON
INSTALLATION
The SK-MINIMON can be mounted in a single gang junction box directly
behind the monitored device. Its small size and Lightweight allow it to be
installed without rigid mounting requirements.
FEATURES & BENEFITS
• Single contact monitor
- Rotary address
• SK-Minimon support
switches for fast
for Class 8 (Style 13)
installation
contact monitor wiring
- UL Listed
• Smail and lightweight
- CSFM Listed
size allows for flexible
- FM Approved
mounting options
SK-MINIMON Technical Specifications
For a complete listing of a I I
compliance approvals and
certifications, pti�,ase visit
PHYSICAL
ORDERING INFORMATION
www.sitentkn1ght.com.
Dimensions: 2.75�Wx 1.3" Hx0.5"D
SK-MINIMON: Mini nnonitor�ng r-nodule
Weight: 1.2 oz (37 g)
Microsoft, Windows, and
COMPATIBILITY
the Windows Logo are
registered trademarks
ELECTRICAL
The SK-MINIMON is compatible with the
ortrademarks of
Operating Voltage: 15 - 32VDC
following Honeywell Silent Knight fire alarm
Microsoft Corporaticn.
SLC Standby and Alarm Current: 350 �tA
control panels:
Silent Knight'. System
End -of -Line Resistance: 47KQ
6820: Add ressabte fire alarm control panel
Sensor" and Honeywell"
Initiating device circuit wiring resistance: 1.5000
6820EVS: Addressalote fire alarm control panel
areregistered
max
wi th an emergency voice system.
trademarks of Honeywell
SLC loop resistance: 400 max
6808: Addressablefire alarm control panel
International, Inc.
Wire Length: 6"min.
6700: Addressabte fire alarm control panel
This c1ccument is not
5700: Addressable fire alarm control panel
intended to be used for
ENVIRONMENTAL
5808: Addressable fire alarm control panel
installation purposes. We
try to keep our product
Operating Temperature: 321F - 120OF (OIC -
5820XL: Addressabiefire alarm control pane[
information up -to
490C)
5820XL-EVS: Addressabte fire alarm control panel
date and accurate. We
Humidity: 10% - 93% non -condensing
with an emergency voice system
cannot cover all specific
applications or anticipate
all reClUirements. All
specifications are subject
to change without notice.
ForTechnical Support,
call 800-446-64Ll4.
For more infDrmation
Learn more about Honeywell Silent Knight and other
products by visiting www-silentknight.corn
Honeywell Silent Knight
12 '-tintonvi[te Road
Honeywell
Northford. CT 06472
Doc 3501331 R9vG 111/17 SME*4T*
13
800-328-0103
0 2017 Honeywel[International Inc. XMIGHT
Honeywell
S11'Wr,
SK-RELAY
Intel�igent Relay Module
The SK-RELAY is an add ressableretay mod LAeforusewith Honeywell Silent
Knight Series fire alarm control panels (FACPs). The SK-RE LAY allows a
Silent Knight FACP to switch discrete contacts by code command. The
relay contains two isolated sets of Form C contacts, which operate as a
DPDTswitch. No supervision is provided for the notification appliance
circuit.
The SK-RELAY contacts can be used for virtually any normattyo pen or
normally closed application. Each SK-RELAY is programmed with a unique
signaling Line circuit(SLC) loop address. When an event occurs that
controls the SK-RELAY. the relay is triggered by the FACP.
INSTALLATION
The SK-RELAY mounts directly into a 4` square electrical box. The box must
have a minimum depth of 2-1/8". A surface mount electrical box (System
Sensor" PN SME1500) is available from Silent Knight.
FEATURES & BENEFITS
- Two sets of Form C
contacts
- Rotary address
switches for fast
installation
- Contacts are rated for
a variety of amps (see
Specifications)
- Panel controlled
status LED that
flashes green in
normal state and is
solid red in alarm
- Relay programming is
comptetelyflexibte-
can be mapped to
zone conditions
• Polling LED visible
through the cover
plate
• S EMS screws for easy
wiring
• UL Listed
0+
HoneyvveN
os"Lqr
MGM
0+
Ch.tilloR
L-101 1'WJ1Z!V
SK-RELAY
SK-RELAY Technical Specifications
PHYSICAL ORDERING INFORMATION
4.675"H x4.275"Wx 1.4"D SK-RE[AY: Relay Module
Shipping Weight: 6.3 oz U96 g)
ELECTRICAL
Operating Voltage: iS - 32 VDC
End -of -Line Resistance: Not used
SLC Standby&A[arm Current:.255mA max @
24VDC (one cornmunication every 5 sec with LED
enabled)
ENVIRONMENTAL
Operating Temperature: 321F - 1201F (O'C -
490C)
Humidity: 10L'/6 - 93% non -condensing
RELAY CONTACT RATINGS
3.OA 30VDC resistive
0.9A liOVDC resistive
0.9A 125VAC resistive
0.5A 125VAC inductive (PF -.35)
07A 75VAC inductive (PF =.35)
For more information
Learn more about Honeywell Silent Knight and other
products by visiting
www.sitentknightcorn
Honeywell Silent Knight
12 Clintonville Road
Northford. CT 06472
800-328-0103
ACCESSORIES.
SM B500:4"Square Surface Mount Electrical Box
CB500:Modute Barrier
COMPATIBILITY
The SK-RELAY is compatible with the following
Honeywell Silent Knight fire alarm control panels:
6820: Addressable fire alarm control pane�
6820EVS: Addressabtefire alarm control panel
with an emergency mass notification system.
6808: Addressable fire alarm control panel
6700: Addressable fire alarm control panel
5700: Addressable fire alarm control panel
5808: Addressabte fire alarm control panel
5820XL: AddressabLe fire alarm control panel
5820XL-EVS: Addressabte fire alarm control panel
with an emergency mass notification system.
Doc 3501271 Rev G1 11/17
0 2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, pteasevisit
www.sitentknight.com,
Microsoft, Windows, and
theWindows Logoare
registered trademarks
ortrademarks of
Microsoft Corporation.
Silent Knight', System
Sensor" and Honeywe[111
are registered
trademarks of Honeywell
International, Inc.
his document is not
intended to be -sea for
installation purposes, We
try to keep cu r product
inyormation up-Lo
date and aCCUrate. We
cannotcovcr attspecific
applications or anticipate
all requirements. All
specifioitic.)ns are subject
to change without notice,
ForTechnica[ Support,
call 800-446-6444.
Honeywell
SILENT'
XMGFfr
Indoor Selectable -
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
System Sensor L -Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Features
• Updated Modern Aesthetics
• Small profile devices for Horns and Horn Strobes
• Plug-in design with minimal intrusion into the oack oox
• Tamper- resistant construction
• Automatic selection of 12- or 24-volt ooeration at 15 and 30
candela
• Field -selectable candela settings on wall units:
15, 30, 75, 95, 110, 135, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and two volume selections
• Mounting plate for all standard and all compact wall units
• Mounting plate shorting spring checks wiring continuity before
device installation
Electrically compatible with legacy SpectrAlert and SpectrAlert
Advance devices
• Compatible with MDL3 sync module
• Strobes and Horn Strobes listed for wall mounting only
• Horns listed for wall or ceiling use
Aaencv Ustinas
SIGNALING
LISTED
S55�2
FM appoved ex�pt
7�25- V0504
S40 1
fm ALERT mdels
7 351653 MM
3057383, 3057072
The System Sensor L-Series offers the most versatile and
easy -to -use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
plastic housings, standard and comoact devices, and.plain, FIRE,
and FUEGO- ' orinted devices, System Sensor L-Series can
meet virtually any application requirement.
The L-Series line of wall -mount horns, strobes, and horn strobes
include a variety of features that increase their apolication versatility
while simplifying installation. All devices feature olug-in designs
with minimal intrusion into the oack oox, making installations fast
and foolproof while virtually eliminating costly and time-consuming
ground faults.
To further simplify installation and protect devices from construction
damage, the L-Series utilizes a universal mounting plate for all
models with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range
of application requirements using field -selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
FA
L-Series Specifications
General
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/%3-inch back box, 4 x 4 x 11/2-inch back box, 4-inch
octagon back box, or double -gang back box. L-Series compact products shall mount to a single -gang 2 x 4 x 17/8-inch back box. A universal
mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall De
used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate, Also, L-Series
products, when used with the Sync*Circult" Module accessory shall be powered from a non -coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync*Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Sehes products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -wave rectified unfiltered power supply
Strobes and horn strobes shall have field -selectable candela settings including 15, 30, 75, 95, 110, 135, and 185.
Strobe
The strobe shall be a System Sensor L-Series Model, listed to U L 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances. flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/ref lector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non -coded power supply.
Synchronization Module
The module shall be a System Sensor Sync*Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair oil wires. The module shall mount to a 411/16 x 41'/16 x 21/6-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32-F to 120-F (0-C to 49-C)
Humidity Range 10 to 93% non -condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDU Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall -Mount Dimensions (including lens) 5.6 - L x 4.7 -W x 1.91 - D (143 mm L x 119 mm W x 49 mm D)
Compact Wall- -Mount Dimensions (including lens) 5.262' L x 3.46" W x 1.9 1" D (133 mm L x 88 mm W x 49 mm D)
Horn Dimensions 5.6-L x 4.7-W x 1.25-D (143 mm L x 119 mm W x 32 mm D)
Compact Nam Dimensions 5.25" L x 3.45" W x 1.25"D (133 mm L x 88 mmW x 32 mm D)
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs.
2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.
AVDS965-05 -2/22120118 -Page 2
UL Current Draw Data
B-1 Z5 Volts 16-33 Volts
8-lZ5Volts
16-33Volts
Candela
DC
DC
FWIR
Sound Pattem
dB
DC
DC
FWR
Candela 15
88
43
60
Temporal
High
39
44
54
Range 30
143
63
83
Temporal
LOW
28
32
54
75
N/A
107
136
Non -Temporal
High
43
47
54
95
N/A
121
155
Non -Temporal
LOW
29
32
54
110
N/A
148
179
3.1 KHz Temporal
High
39
41
54
135
N/A
172
209
3.1 KHz Temporal
LOW
29
32
54
185
N/A
222
257
3.1 KHz Non -Temporal High
42
43
54
3.1 KHz Non -Temporal Low
28
29
54
Coded
High
43
47
54
3.1 KHz Coded
High
42
43
54
UL Max. Current Draw (mA
R MS), Wall Horn
Strobe,
Candela Range
(15-185
cd)
8175 Volts
16-33 Volts
DC Input
15cd
30cd
15od
30ed 75cd
95cd
110cd
135ed
185ed
Temporal High
98
158
54
74
121
142
162
196
245
Temporal Low
93
154
44
65
ill
133
157
184
235
Non-TernPoral High
106
166
73
94
139
160
182
211
262
Non-lemportal Low
93
156
51
71
119
139
162
190
239
3. 1 K Temporal High
93
156
53
73
119
140
164
190
242
3. 1 K Temporal Low
91
154
45
66
112
133
160
185
235
3. 1 K Non -Temporal High
99
162
69
90
135
157
175
208
261
3. 1 K Non -Temporal Low
93
156
52
72
119
138
162
192
242
16-33 Volts
FWR Input
15cd
30cd
75cd
95cd
110cd
135cd
185cd
Temporal High
83
107
156
177
198
234
287
Temporal Low
68
91
145
165
185
223
271
Non -Temporal High
ill
135
185
207
230
264
316
Non-Temportal Low
79
104
157
175
197
235
283
3.1 K Temporal High
81
105
155
177
196
234
284
3.1 K Temporal Low
68
90
145
166
186
222
276
3.1 K Non -Temporal High
104
131
177
204
230
264
326
3.1 K Non -Temporal Low
77
102
156
177
199
234
291
Horn Tones and Sound Output Data
Morn and
Switch
Position
horn Strobe Alutput (dI3A)
Sound Pattern
dB
8-175
Volts
DC
16-33
Volts
DC
FWR
I
Temporal
High
84
89
89
2
Temporal
Low
75
83
83_
3
Non -Temporal
High
85
90
90
4
Non -Temporal
Low
76
84
84
5
3.1 KHz Temporal
High
83
88
88
6
3.1 KHz Temporal
Low
76
82
82
7
3.1 KHz Non -Temporal
High
84
89
89
8
3.1 KHz Non -Temporal
Low
77
83
83
9�
Coded
High
85
90
90
10*
3.1 KHz Coded
High
84
89
89
* Settings 9 and 10 are not available on 2-wire horn strobes, Temporal coding must
be provided by the NAC. If the NAC voltage is held constant, the horn output rernains
constantly on.
AVDSE65-05 - 2/2,/2018 - Page 3
L-Series Dimensions
Compact Strobe, Horn Strobe
4.70'
(11.94 cm) 1.91"
(4.85 cri
1.25"
(3.18mm)
5.67'
(14.4 =)
Lf.- I
Compact mom
Strobe, Horn Strobe 00 Horn
L-Series Ordering Information
11V — 357-
32 mm (9.1
tp— "=
(117 CM) 0
L
A0547-00 An557 00
Compact Wall Surface Mount Back Box
SBBGRL, SBBGWL
t25'
32m
1.55rl
(3.9 Cirri)
C
0
(12.24—)
(439cm)
C
a 0 C) 0
_ �M',
N11,51 01
Wall Surface Mount Back Box
SBBRL/SBBW`L
Wall Horn Strobes
Homs*
P2RL
2-Wire, Horn Strobe, Red
HRL*
Horn, Red
P2WL
2-Wire, Horn Strobe, White
HWL*
Horn, White
P2GRL
2-Wire, Compact Horn Strobe, Red
HGRL*
Compact Horn, Red
P2GWL
2-Wire, Comp 2 fils act Horn Strobe, White
HGWL*
Compact Horn, White
P2RL-P
2-Wire, Horn Strobe, Red, Plain
Accessories
P2WL-P
2-Wire, Horn Strobe. White, Plain
TR_2
Universal Wall Trim Ring Red
P2RL-SP
2-Wire, Horn Strobe, Red, FUEGO
TR-2W
Universal Wall Trim Ring White
P2WL-SP
2-Wire, Horn Strobe, White, FUEGO
SBBRL
Wall Surface Mount Back Box, Red
P4RL
4-Wire, Horn Strobe, Red
SBBWL
Wall Surface Mount Back Box, White
P4WL
4-Wire, Horn Strobe, White
SBBGRL
Compact Wall Surface Mount Back Box, Red
Wall Strobes
SBBGWL
Compact Wall Surface Mount Back Box, White
SRL
Strobe, Red
SWL
Strobe, White
SGRL
Compact Strobe, Red
SGWL
Compact Strobe, White
SRL-P
Strobe, Red, Plain
SWL-P
Strobe, White, Plain
SRL-SP
Strobe, Red, FUEGO
SWL-CLR-ALERT Strobe, White, ALERT
Notes:
All -P models have a plain housing (no "FIRE' marking on cover).
All -SP models have "FUEGO" marking an cover.
All -ALERT models
have "ALERT" marking on cover
'Horn -only models are listed for wall or ceiling use-
3825 Ohio Avenue - St. Charles, IL 60174 �2018 Sys�em Sensor.
SYSTEM Prodiuct specificallom �.Wcl to change without notice. visit systemsensw.corn
Phone: 800-SENSOR2 * Fax: 630-377-6495 for current Predict infOrinalon. including the latest version of this data sheet.
SONSOR' www.systemsensor.com AVDS865-05 - 2/22/2018
f, -
5 V5
5EM5 am
Selectable -Output
Low Frequency
Sounder and Low
Frequency Sounder
Strobes for Wall
Applications
SpectrkerP Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.
Features
* 520 Hz ± 10% square wave tone
* Plug-in design with minimal intrusion into the back box
* Tamper -resistant construction
* Field -selectable candela settings on wall units:
135, 150, 177, and 185
* Rotary switch for low frequency sounder tone
• Universal mounting plate for wall units
• Mounting plate shorting spring checks wiring continuity before
device installation
• Electrically compatible with legacy SpectrAlert devices
• Compatible with MDL3 sync module
• Listed for ceiling or wall mounting
T
a A , — 4
The SpectrAllert Advance series offers the most versatile
and easy -to -use line of low frequency sounder and low frequency
sounder strobes in the industry. With white and red plastic housings,
dual listed for wall and ceiling mounting, SpectrAlert Advance can
meet virtually any application requirement.
The wall -mount low frequency sounder, and low frequency sounder
strobes were designed to address the NFPA 72 sleeping space
requirements that require a low frequency notification appliance that
operates within frequency range of 520 Hz t 10% and is of a square
wave tone, Like the entire SpectrAlert Advance product fine they
include a variety of features that increase their application versatility
while simplifying installation. All devices feature plug-in designs
with minimal intrusion into the back box, making installations fast
and foolproof while virtually eliminating costly and time-consuming
ground faults.
To further simplify installation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field -selectable candela settings,
Agency Listings
automatic selection of 12- or 24-volt operation. and a rotary switch
for 520 Hz low frequency sounder tones.
SIGNAUNG
&
<�> MEA
00
USTED
APPROVED approved
S4011 (sounder)
S5512 (strobes)
3047563 MEA452-05-E
7135-1653 02-13
7 1 25- 1 653 02�4
SpectrAlert Advance Specifications
General
SpectrAlert Advance low frequency sounder and low frequency sounder strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch
octagon back box. or double -gang back box, Two -wire products shall also mount to a single -gang 2 x 4 x 17/8-inch back box, A universal
mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate,
Also, SpectrAlert Advance products, when used with the Sync*Circu it" Module accessory, shall be powered from a non -coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the SyncoCircuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17,5 volts: 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -
wave rectified unfiltered power supply. Low Frequency Sounder strobes shall have field -selectable candela. settings including 135, 150, 177.
and 185. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone and have a permanent marking
on the housing that reads "low frequency sounder"
Low Frequency Sounder
The low frequency sounder shall be a System Sensor SpectrAlert Advance Model listed to UL 464 and shall be approved for fire
protective service. The low frequency sounder and the SyncoCircuitTM MDU Module accessory, if used, shall be powered from a notification
appliance circuit output and shall operate on a nominal 12 or 24 volts (includes fire alarm panels with built in sync). When used with the
SynceCircult Module MDL3, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated
notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with
the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on
a circuit. The low frequency sounder has an option to switch between temporal three pattern, non -temporal (continuous) pattern and coded
supply within the frequency range of 520Hz ± 10% square wave tone. The low frequency sounder shall operate on a coded or non -coded
powersupply.
Low Frequency Sounder Strobe Combination
The low frequency sounder strobe shall be a System Sensor SpectrAlert Advance Model - listed to UL 1971 and UL 464 and shall be
approved for fire protective service. The low frequency sounder strobe shall be wired as a primary -signaling notification appliance and comply
with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating
voltage range. The strobe light shall consist of a xenon flash tube and associated lens/ref lector system. The sounder shall have an option to
switch between a temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. The low
frequency sounder on low frequency sounder strobe models shall operate on a non -coded power supply. The field selectable tones will sound
within the frequency range of 520 Hz ±10% square wave tone.
Synchronization Module
The module shall be a System Sensor Sync*Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module
shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The module shall mount to a
411/le x 41'/16 x 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall
synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The
module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32'F to 12OoF (O'C to 49'C)
Humidity Range 10 to 93% non -condensing
Frpaupncv Rance 520 Hz j- 10%
Strobe Flash Rate 1 flash per second
Nominal Voltage Low Frequency Sounder Regulated 12 DC/FWR or regulated 24 DC/FWR'
Nominal Voltage Range Low Frequency Sounder Strobe Regulated 24 VDC/FWR1
Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDU Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
InputTerminal Wire Gauge 12 to 18 AWG
Wall -Mount Dimensions (including lens) 6.4 inches L x 4.7 inches W x 2.5 inches D
(162 mm L x 119 mm W x 64 mm D)
Sounder Dimensions 5.6 inches L x 4.7 inches W x 1.3 inches D
(142 mm L x 119 mm W x 33 mm D)
Low Frequency Sounder/Strobe with Surface Mount Back Box 6.4 inches L x 4.7 inches W x 4.3 inches D
Dimensions (SBBR, SBBW) (162 mm L x 120 mm W x 108 mm D)
Low Frequency Sounder with Surface Mount Back Box Dimensions 5-7 inches L x 4.8 inches W x 3 inches D
(SBBR, SBBW) (145 mm L x 120 mm W x 76 mm D)
Notes;
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs.
UL Current Draw Data
UL Max. Low Frequency Sounder Current Draw (mA RMS)
8—lz5volts 16-33 Volts
Sound Pattern dB DC FWR DC FWR
Temporal 3 High 191 262 138 166
Continuous High 292 384 138 208
Coded High 292 388 153 205
UL Max. Current Draw
(mA RMS), 2-Wire
Low Frequency Sounder
Strobe, High Candela
Range
16-33 Volts
16-33 Volts
DC Input
135 150
177 185
FWR Input
135
150 177 185
Temporal 3
277 292
325 344
Temporal 3
296
309 343 351
Continuous
337 362
387 417
Continuous
393
395 432 433
Low Frequency Sounder Tones and Sound Output Data
Low Frequency Sounder
and Low Frequency
Sounder Strobe
Output (dBA)
8-1Z5
16-33
24-Volt Nominal
Volts
Volts
Reverberant
Anechoic
Switch Position
Sound Pattern
DC FWIR
DC FWR
DC FWR
DC FWIR
1 Temporal 3 76 76 76 76 76 76 - 86 86
2 Continuous 80 80 80 80 80 80 90 90
3t Coded 80 80 80 80 80 80 90 90
t Sounder ratings provided are for continuous voltage as provided by the NAC
SpectrAlert Advance Dimensions
Wall -mount low frequency sounder strobes
SpectrAlert Advance Ordering Information
Wall -mount low frequency sounder
I'llodel
Wall Low Frequency Sounder Strobes
zescription
P2RH-LF
2AN-ire Low Frequency Sounder Strobe, High cd. Red
P2WH-LF
2-Wire Low Frequency Sounder Strobe, High cd, White
Low Frequency Sounders
HR-LF
Low Frequency Sounder, Red
HW-LF
Low Frequency Sounder, White
Accessories
SBBR Surface Mount Back Box, Wall, Red
SBBW Surface Mount Back Box, Wall, White
TR-HS Trim Rinq, Wall, Red
Notes:
"High cd" refers to strobes that include 135.150, 117, and 185 candea settings.
3825 Ohio Avenue - St. Charles, IL 60174 02015 Syseri Sansoc
SySTEM Prodrictapeoilicai �bject to change without notice VsitsySiontsensorcorn
Phone: 800-SENSOR2 * Fax: 630-377-6495 for wrinerit pri information. mlod ing the latest vefslon of this data sheet.
SENSOR' www.systemsensor.com AVDS16404 - 1/15
SYSTEM
SENSOR
Outdoor Selectablellill!
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
Speci Advance outdoor audible visible products
are rich with features that cut installation times and
maximize profits.
Features
• Weatherproof per NEIVIA 4X, IP56
• Listed to UL 1638 (strobe) and UL 464 (horn)
• Compatible with System Sensor synchronization protocol and
legacy SpectrAlert products
• Field -selectable candela. settings: 15, 15/75, 30, 75, 95, 110, 115,
135, 150, 177, and 185
• Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
• Rotary switch for horn tone and three volume selections
• Horn rated at 88+ dBA at 16 volts
• Rated from —40'F to 151'F
• Universal mounting plate with an onboard shorting spring that
tests wiring continuity before devices are installed
Plug-in design with minimal intrusion into the back box
Tamper -resistant construction
Listed for ceiling or wall mounting
Agency Listings
S IGNAUN
& G
FM MEA
USTED 7125-1653:188(ho[n st, 'a"
S4011 (chimes, horn strobes, horns) APPROVED approved c h i m a s O,,Lb,,)
S3593 (outdoor and alert strobes) 3C73�--2 MEA4805-E 7135-1653:189 (horns, chimes)
SPECTPAlert
,ft q %fft M Q &
SpectrAllert Advance offers the broadest line of outdoor horns,
strobes, and horn strobes in the industry. With white or red plastic
housings, wall or ceiling mounting options, and plain or FIRE -printed
devices, SpectrAlert Advance can meet virtually any application
requirement, including indoor, outdoor, wet, and dry applications in
temperatures from —40'F to 151'F.
Like the entire SpectrAlert Advance line, outdoor horns. strobes,
and horn strobes for wall applications include a variety of features
that increase application flexibility and simplify installation. First
field -selectable settings, including candela, automatic selection of
12- or 24-volt operation, horn tones, and three volume options enable
installers to easily adapt devices to meet requirements.
Next, SpectrAlert Advance devices use a universal mounting plate
for both wall and ceiling applications. This mounting plate includes
an onboard shorting spring that ensures wiring continuity before
devices are installed. so installers can verify proper wiring without
mounting the devices and exposing them to potential construction
damage. Once the plates are mounted, all SpectrAlert Advance
devices utilize a plug-in design with a single captured screw to
speed installation and virtually eliminate costly ground faults.
Outdoor devices ship with weatherproof plastic back boxes (metal
back boxes are available separately) that accommodate in -and -
out wiring for daisy chaining devices- Plastic back boxes feature
removable side flanges and improved resistance to saltwater
corrosion. Knock -outs located on the back eliminate the need to drill
holes for screw -in mounting. Plastic and metal weatherproof back
boxes come with 3/4-inch top and bottom conduit entries and 3/4-inch
knock -outs at the back. A screw -in NPT plug with an 0-ring gasket
for a watertight seal is included with each back box.
SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications
General
SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall
be used for mounting ceiling and wall products, The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products. when used with the Sync*Circult" Module accessory, shall be powered from a non -coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync*Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 9 and 17.5 volts: 24-volt-rated notification appliance circuit outputs shall operate between 17
and 33 volts. Outdoor SpectrAlert Advance products shall operate between -40 and 151 degrees Fahrenheit from a regulated DC or full -wave
rectified unfiltered power supply. Strobes and horn strobes shall have field -selectable candela settings including 15, 15/75� 30, 75, 95, 110,
115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service
The strobe shall be wired as a primary-signa ling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved
per UL. The strobe shall be suitable for use in wet environments.
Horn Strobe Combiruition
The horn strobe shall be a System Sensor SpectrAlert Advance Model - listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe
light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to
switch between a temporal three pattern and a non -temporal (continuous) pattern. These options shall be set by a multiple position switch,
On four -wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or
non -coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The
horn strobe shall be suitable for use in wet environments.
Operating Temperature -40-F to 151 'F (-40-C to 66-C)
Strobe Flash Rate 1 flash per second
NominalVoltage Regulated 12 DCIFWR or regulated 24 DCIIFWRI
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 ANG
Wall -Mount Dimensions (including lens) 5.6- L x 4.7-W x 2.5-D (142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6-L x 4.7-W x 1.3-D (142 mm L x 119 mm W x 33 mm D)
Wall -Mount Weatherproof Back Box Dimensions (SA-WBB) 5.7- L x 5.1 -W x 2.0-D (145 mm L x 130 mm W x 51 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15[75 cd.
AVOSOU01
UL Current Draw Data
I
2111111���
it A :
III!
8-11Z5 volts
16-33 Volts
8-1Z5VOlts
16-33 Volts
Candela
DC
FWR
DC
FWR
Sound Pattern
dB
DC
FWR
DC
FWR
Standard 15
123
128
66
71
Temporal
High
57
55
69
75
Candela 15/75
142
148
77
81
Temporal
Medium
44
49
58
69
Range 30
NA
NA
94
96
Temporal
Low
38
44
44
48
75
NA
NA
158
153
Non -Temporal
High
57
56
69
75
95
NA
NA
181
176
Non -Temporal
Medium
42
50
60
69
110
NA
NA
202
195
Non -Temporal
Low
41
44
50
50
115
NA
NA
210
205
Coded
High
57
55
69
75
High 135
NA
NA
228
207
Coded
Medium
44
51
56
69
Candela 150
NA
NA
246
220
Coded
Low
40
46
52
50
Range 177
NA
NA
281
251
185
NA
NA
286
258
UL Max. Current Draw (mA
RMS), 2-Wire
Horn
Strobe,
Standard
Candela
Range (15-115
cd)
8-175 volts
16-33 Volts
DC Input
15
15/75
15
15/75 30
75
95
110
115
Temporal High
137
147
79
90
107
176
194
212
218
Temporal Medium
132
144
69
80
97
157
182
201
210
Temporal Low
132
143
66
77
93
154
179
198
207
Non -Temporal High
141
152
91
100
116
176
201
221
229
Non -Temporal Medium
133
145
75
85
102
163
187
207
216
Non -Temporal Low
131 144
68
79 96 156
182
201
210
FWIR lnptft
Temporal High
136 155
88
97 112 168
190
210
218
Temporal Medium
129 152
78
88 103 160
184
202
206
Temporal Low
129 151
76
86 101 160
184
194
201
Non -Temporal High
142 161
103
112 126 181
203
221
229
Non -Temporal Medium
134 155
85
95 110 166
189
208
216
Non -Temporal Low
132 154
80
90 105 161
184
202
211
UL Max. Current Draw (mA
DC Input
RMS), 2-Wre Horn
16-33 Volts
135 150
Strobe, High Candela
177 185
Range (135-185 cd)
FWR Input
16-33 Volts
135 150
177
185
Temporal High
245 259
290
297
Temporal High
215 231
258
265
Temporal Medium
235 253
288
297
Temporal Medium
209 224
250
258
Temporal Low
232 251
282
292
Temporal Low
207 221
248
256
Non -Temporal High
255 270
303
309
Non -Temporal High
233 248
275
281
Non -Temporal Medium
242 259
293
299
Non -Temporal Medium
219 232
262
267
Non -Temporal Low
238 254
291
295
Non-TeMpDral Low
214 229
256
262
Candela Derating
For K series products used at low temperatures, listed
candela ratings must be reduced in accordance with
this table.
Strobe Output (cd)
Horn Tones and Sound Output Data
Horn and Horn Strobe Output (dBA)
8-175 16-33
Switch Sound volts volts
Position Pattern dB DC FWR DC FWR
24-Volt Nominal
Reverberant Anechoic
DC FWR DC FWR
Usted Candela
Candela rating at --40IF
15
Do not use below 32-F
15/75
30
75
44
95
70
110
110
115
115
135
135
150
150
177
177
185
185
1
Temporal
High
78
78
84
84
88
88
99
98
2
Temporal
Medium-
74
74
80
80
86
86
96
96
3
Temporal
Low
71
73
76
76
83
80
94
89
4
Non-
Temporal
High
82
82
88
88
93
92
100
100
5
Non-
Medium
78
78
85
85
90
90
98
98
Temporal
6
Non-
Low
75
75
81
81
88
84
96
92
Temporal
7t
Coded
High
82
82
88
88
93
92
101
101
8t
Coded
Medium
78
78
85
85
90
90
97
98
9t Coded LOW 75 75 81 81 88 85 96 92
tSettings 7, 8, and 9 are not available on 2-wire horn strobe. AVDS01201
SpectrAlert Advance Diagrams
Wall -Mount Horn Strobes
711010
erproof Back Box
Wall -Mount Horn Strobe with Plastic Weatherproof Back Box
SpectrAlert Advance Ordering Information
Wall Horn Strobes
P2RK*t
2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
P2RHK*t
2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
P2WK�
2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
P2WHK*t
2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
P4RKt
4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
P4WK
4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
P2RHK-120
2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box)
Wall Strobes
SRK*t Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
SRHK*' Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
SWK*t Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
SWHK*`h Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
Horns
HRKt Horn, Red, Outdoor (includes plastic weatherproof back box)
Accessories
SA-WBB Red, Metal Weatherproof Back Box
SA-WBBW White, Metal Weatherproof Back Box
Notes:
* Add "-P" to model number for plain housing (no "FIRE" marking on cover), e.g., P2RK-P.
t Add "-R"to model number for weatherproof replacement device (no back box included), only for use Wth weatherproof outdoor flush momfing plate, WTP and WTPW.
"Standard cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. "High cd" refers to strobes that include 135, 150, 177, and 185
candela settings. When replacing standard outdoor units both the device and back box must be replaced.
02012SYste sensor.
EM 3825 Ohio Avenue * St, Charles, IL 60174 Product specifications subject to change wM ithout notice. Visit systernsensor com
ST
for current product Information, including the latest version of this data sheet
SENSOR' Phone: 800-SENSOR2 * Fax: 630-377-6495 AVDSOI-101 - 3/12
-7
Outdoor Selectable -
Output Strobes and
Horn Strobes for
Ceiling Applications
SpectrA lert@ Advance outdoor audible visible products
are rich with features that cut installation times and
maximize profits.
Features
• Weatherproof NEMA 4X, IP56 rated
• Listed to UL 1638 (strobe) and UL464 (horn)
• Compatible with System Sensor s�ynchronization protocol and
legacy SpectrAlert products
• Field -selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115,
135, 150, 177, and 185
• Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
• Rotary switch for horn tone and three volume selections
• Horn rated at 88+ dBA at 16 volts
• Rated from -40*F to 151 OF
• Universal mounting plate with an onboard shorting spring that
tests wiring continuity before devices are installed
• Plug-in design With minimal intrusion into the back box
• Tamper -resistant construction
• Listed for ceiling or wall mounting
Agency Listings
S IGNAUN
& G
FM MEA
USTED 7125-1653:188 (horn
S4011 (oh—S, -in strobes, horns) APPROVED approved �h,,e Strobes)
S3593 (outdoor and alert stiat—) .3.32 2 � 7:,' MEA452-05-E 7135-1653:189 (horns, chimes)
e—'�
. �78
0
-awl
SPECTRA-Mert
L, r-17 7 M M 7 a5% i � �3 �1
SpectrAllert Advance offers the broadest line of outdoor horns,
strobes, and horn strobes in the industry. With white or red plastic
housings, wall or ceiling mounting options, and plain or FIRE -printed
devices, SpectrAlert Advance can meet virtually any application
requirement, including indoor, outdoor, wet, and dry applications in
temperatures from —40'F to 151'F.
Like the entire SpectrAlert Advance line, outdoor strobes and horn
strobes for ceiling applications include a variety of features that
increase application flexibility and simplify installation. First, field -
selectable settings, including candela, automatic selection of 12- or
24-volt operation, horn tones, and three volume options enable
installers to easily adapt devices to meet requirements.
Next, SpectrAlert Advance devices use a universal mounting plate
for both wall and ceiling applications. This mounting plate includes
an onboard shorting spring that ensures wiring continuity before
devices are installed, so installers can verity proper wiring without
mounting the devices and exposing them to potential construction
damage. Once the plates are mounted, all SpectrAlert Advance
devices utilize a plug-in design with a single captured screw to
speed installation and virtually eliminate costly ground faults.
Outdoor devices ship with weatherproof plastic back boxes (metal
back boxes are available separately) that accommodate in -and -
out wiring for daisy chaining devices. Plastic back boxes feature
removable side flanges and improved resistance to saltwater
corrosion. Plastic and metal weatherproof back boxes come with
3/4-inch top and bottom conduit entries and 3/4-inch knock -outs at the
back. Three screw -in NPT plugs with O-ring gaskets for a watertight
seal "is included with each back box.
SpectrAlert Advance Outdoor Strobe, and Horn Strobe Specifications
General
SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate,
Also, SpectrAlert Advance products, when used with the SyncoCircuit'" Module accessory, shall be powered from a non -coded notification
appliance circuit output and shall operate on a norninal 12 or 24 volts. When used with the Sync*Circuft Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between -40 and 151 degrees Fahrenheit from a regulated DC or full -
wave rectified unfiltered power supply. Strobes and horn strobes shall have field -selectable candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1638 and shall be approved for fire protective service
The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/ref lector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved
per UL. The strobe shall be suitable for use in wet environments.
Horn Strobe Combination
The horn strobe shall oe a System Sensor SpectrAlert Advance Model - listed to UL 1638 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non -temporal (continuous) pattern. These options shall be set by a multiple position switch. On four -
wire products, the strobe shall be powered independently of the sounder. The horn strobe on a 2-wire model shall work on a non -coded power
supply. The horn on 4-wire horn strobe models shall operate on a coded or non -coded power supply. The horn strobe must be installed with
its weatherproof back box in order to remain outdoor listed per UL. The horn strobe shall be suitable for use in wet environments.
Operating Temperature -40OF to 15 1 OF (-400C to 660C)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR'
Operating Vottage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range with MDU Sync Module 8.5 to 17.5V (12 V nominal) or 16.5 to 33V (24 V nominal)
InputTerminal Wire Gauge 12 to 18 ANG
Ceiling -Mount Dimensions (including lens) 6.8-diameter x 2.5-high (173 mm diameter x 64 mm high)
Strobe I Ham Strobe Dimensions 5.6-L x 4.7-W x 1.3-D (142 mm L x 119 mm W x 33 mm D)
Strobe I Horn Strobe Dimensions with Back Box 5.6-L x 4.7-W x 1.3-D (142 mm L x 119 mm W x 33 mm D)
Ceiling -Mount Weatherproof Back Box Dimensions 7.1 -diameter x 2.0-high (180 mm diameter x 51 mm high)
Notes:
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs
2. Products Vill operate at 12 V nominal only for 15 and 15/75 cd.
AVDS11401
UL Current Draw Data
8-175 volts
16-33 Volts
8--1Z5VOIts
16-33 Volts
Candela
DC
FWR
DC
FWR
Sound Pattern
dB
DC
FVVR
DC
FWR
Standard 15
123
128
66
71
Temporal
High
�)7
55
69
75
Candela 15/75
142
148
77
81
Temporal
Medium
44
49
58
69
Range 30
NA
NA
94
96
Temporal
LOW
38
44
44
48
75
NA
NA
158
153
Non -Temporal
High
57
56
69
75
95
NA
NA
181
176
Non -Temporal
Medium
42
50
60
69
110
NA
NA
202
195
Non -Temporal
Low
41
44
50
so
115
NA
NA
210
205
Coded
High
57
55
69
75
High 135
NA
NA
228
207
Coded
Medium
44
51
56
69
Candela 150
NA
NA
246
220
Coded
Low
40
46
52
50
Range 177
NA
NA
281
251
185
NA
NA
286
258
UL Max. Current Draw (mA
RMS), 2-Wire
Horn
Strobe,
Standard
Candela
Range (15-115
cd)
8-175valts
16-33 Volts
DC Input
15
15/75
15
15f75 30
75
95
110
115
TemPoral High
137
147
79
90
107
176
194
212
218
Temporal Medium
132
144
69
80
97
157
182
201
210
Temporal Low
132
143
66
77
93
154
179
198
207
Non-Jemporal High
141
152
91
100
116
176
201
221
229
Non -Temporal Medium
133
145
75
85
102
163
187
207
216
Non -Temporal Low
131
144
68
79
96
156
182
201
210
FWR Input
Temporal High
136 155
88
97 112 168
190
210
218
Temporal Medium
129 152
78
88 103 160
184
202
206
Temporal Low
129 151
76
86 101 160
184
194
201
Non -Temporal High
142 161
103
112 126 181
203
221
229
Non -Temporal Medium
134 155
85
95 110 166
189
208
216
Non -Temporal Low
132 154
80
90 105 161
184
202
211
UL Max. Current Draw (mA
DC Input
RMS), 2-Wire Horn
16-33 Volts
135 150
Strobe,
177
High Candela
185
Range (135-185 cd)
FWR Input
16-33 Volts
135 150
177
185
Temporal High
245 259
290
297
Temporal High
215 231
258
265
Temporal Medium
235 253
288
297
Temporal Medium
209 224
250
258
Temporal Low
232 251
282
292
Temporal Low
207 221
248
256
Non -Temporal High
255 270
303
309
Non -Temporal High
233 248
275
281
Non -Temporal Medium
242 259
293
299
Non -Temporal Medium
219 232
262
267
Non -Temporal Low
238 254
291
295
Non -Temporal I ow
214 229
256
262
Candela Derating
For K series products used at low temperatures, listed
candela ratings must be reduced in accordance with
this table.
Strobe Output (cd)
Horn Tones and Sound Output Data
Horn Strobe Output (dBA)
8-175 16-33
Switch Sound Volts volts
Position Pattern dB DC FWR DC FWR
24-Volt Nominal
Reverberant Anechoic
DC FWR DC FWR
Listed Candela
Candela rating at -40'F
15
Do not use below 32'F
15/75
30
75
44
95
70
110
110
115
115
135
135
150
150
177
177
185
185
1
Temporal
High
78
78
84
84
88
88
99
98
2
Temporal
Medium
74
74
80
80
86
86
96
96
3
Temporal
Low
71
73
76
76
83
80
94
89
4
Non-
Temporal
High
82
82
88
88
93
92
100
100
5
Non-
Temporal
Medium
78
78
85
85
90
90
98
98
6
Non-
Temporal
LOW
75
75
81
81
88
84
96
92
7t
Coded
High
82
82
88
88
93
92
101
101
8t
Coded
Medium
78
78
85
85
90
90
97
98
9t
Coded
LOW
75
75
81
81
88
85
96
92
tSettings 7, 8, and 9 are not available on 2-wire horn strobe.
AVOS 11401
SpectrAlert Advance Diagrams
Dia.
2 5-
4z
Ceiling -Mount Horn Strobes
1261
a""
Ceiling Plastic Weatherproof Back Box
Ceiling -Mount Horn Strobe with Plastic Weatherproof Back Box
SpectrAlert Advance Ordering Information
Model Description
Ceiling Horn Strobes
PC2RK 2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
PC2RHK 2-Wire Horn Strobe. High cd, Red, Outdoor (includes plastic weatherproof back box)
PC2WK 2-Wire, Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
PC2WHK 2-Wire, Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
Ceiling Strobes
SCRK Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
SCRHK Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
SCWK Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
SCWHK Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
Accessimies
SA-WBBC Red, Metal Weatherproof Back Box
SA-WBBCW White, Metal Weatherproof Back Box
MP120K
Notes:
"Standard cd" refers to strobes that include 15,15/75, 30, 75, 95, 110, and 115 candela settings "High cd" refers to strobes that include 135, 150, 177, and 185
candela settings. When replacing outdoor units, both the device and back box must be replaced.
02015 S stem Sensor.
Sy TEM 3825 Ohio Avenue - St. Charles, IL 60174 Pioductspei subject to chaynge without notice, Wsitsystemsensor.corn
for current product informaton, W101 ing the tatesiversionofthiSdatasheet.
-.S-ENSOR' Phone: 800-SENSOR2 a Fax: 630-377-6495 AVDS1'1d402-02h5
(E,)POTTER
The Symbol of Protection
Features
Easily installed
Completely scaled sensor, moisture and vapor resistant
Hivilly resistant to vibration and corrosion
Highly sensitive to temperature changes
No sensitivity- loss due to aging
Repetitive operation without the need to replace sensing elements
Small compact design
Precision and quality at low cost
RTS-O/RTS-C
Room Temperature Switch
SIGNALING
C @ us
LISTED
Important: This document contains important inforniation on the installalion and operation of room temperature switches, Please read all instructions
carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Description
Each unit consists of a bi-metal operating mechanism, featuring
herinctically scaled precious metal contacts. N.O. or N.C., which
automatically reset for repetitive operation, eliminating the need for
sensing element replacement.
Small compact design, highly resistant to vibration and corrosion.
Easily installed using the enclosed hardware or adhesive mounting
pad.
Screw terminals permit easy installation in single or multiple
detector circuits.
Application
The RTS Series complies vkrith the requirements of NFPA 13 and 72
for a room temperature switch to operate at 40'F to protect a drY pipe
valve from freezing. The RTS can also be used for other temperature
detection applications.
Operation
The normally open detector, RTS-0. will close the contact when the
temperature drops below 40'F (4�5'C). The normally closed detector,
RTS-C. will open the contact when the temperature �rops below 40'F
(4�5'C). The detector will automatically reset to the nonnal state when
the temperature rises above 401F (4,5'C).
The RTS Series Room Temperature Sensors are precision engineered,
designed and manufactured for commercial or residential use.
Technical Specifications
Enclosure
WhiteABS
Dimensions
2 1/16"W x 3 7/16"l. x 1 1/4'14
(5.2cin W x 8.7cm L x 3,2cm H)
Sensor
Epoxy sealed stainless steel case. bi-metallic
operating mechanism.
Contacts
Silver clad. available normally open oi- normally
closed
Electrical
Rating
I Anip at 24V[)C
Temperature
Setting
401 ±5*F (4,5' ±3'Q
Terminals
Screw Tenninals
Mounting
Wall Mount. Surface
Potter Electric Signal Company. LLC - St. Louis, N10 * Phone: 866-956-0988 / Canada 888-882-1833 - www.pottersignal.com
5401019 - REV H - 09/15 PAGE 1 OF2
(E)POTTER
The Symbol of Protection
Inspection, Testing, & Maintenance
RTS-O/RTS-C
Room Temperature Switch
The frequency of inspection and testing of the RTS and its associated monitoring system shall be in accordance with applicable local and NFPAcodes
and standards. Manufacturer recommends quarterly or more frequently.
Functional test can be accomplished by spraying the RTS with circuit cooler or equivalent.
More accurate test requires exposing the RTS to 407 ± 50F.
The RTS requires no maintenance other than ensuring the vent holes are not obstructed.
Fig I
RTS-0 RTS-0
0- C"—
Control Unit
Supervisory Device EOLR
Circuit
0—
RTS-C RTS-C
0— ID
Control Unit
Supervisory Device EOLR
Circuit
DWG# 1019-1
NOTE. This RTS does not have duplicate terminals. Do not use looped wire under terminals. Break wire run to provide supervision of connections.
RTS Mounting Template
Fig 2
Ordering Information
Model
Description
Stock No.
RTS-0
Normally Open Room Temperature
1010108
Switch
RTS-C
Normally Closed Room Temperature
1010109
Switch
Supervisory switches have a normal service life of 10-15 years.
However. the service life may be significantly reduced by local
environmental conditions.
Potter Electric Signal Company, LLC - St. Louis, MO - Phone: 866-956-0988 / Canada 888-882-1833 - www-poliersi�,,nal.coin
5401019 - REV H * 09/15 PAGE 2 OF 2
Isi
k,
Standard Features:
• Relays may be energized from a voltage
source of 18 to 35VDC or VAC, 120VAC
or230VAC
• Each relay position contains a red
LED, which illuminates when the coil is
energized.
• Single, dual or triple relay modules
may be "snapped apart" from standard
4-position master
DC input is polarized
Continuous duty use
Available in dust resistant enclosures with
LED viewing port
/C versions mounted in enclosures
/C/R versions with red covers for NYC
and other uses
/T versions come complete with track
mounting hardware which facilitates
installation in standard cabinets
U L recognized relays rated at 10,000,000
mechanical operations
UL listed as Control Unit Accessory
PEWal WAM
NFPA Made I
Uses UL Recognized Components
Space Age Electronics, Inc. 2008
ED0313 LT1 0278 Rev.B 1/2
MR1
MR2
MR-100 & MR-200 Series Relays
The MR Series Multi -voltage Control Relays offer SPDT
or DPDT 10 Amp resistive contacts which may be
operated by one of four input control voltages. A single
relay may be energized from a voltage source of 24VDC,
24VAC, 120VAC or 230VAC by wiring to appropriate input
terminals.
Each relay position contains a red LED which indicates
the relay coil is energized. Relays may be "snapped
apart" from a standard 4 module assembly and used
independently. These devices are ideal for applications
where local contacts are required for system status,
remote contacts for control of electrical loads and
general purpose switching. They are suitable for use with
HVAC, temperature control, fire alarm, security, energy
management and lighting control systems.
SPDT CONTACTS
DPDT CONTACTS
10A RESISTIVE@
10A RESISTIVE@
120VAC
120VAC
IONC C NO NC C N0*1
I I
MAY
RELAY I
ENFERGLZED
ENERGIZ 0 _�U
LED
LED
I
Fu Ei z 2
INPUT
CONTROL I*
INPUT
CONTROL 16 11' �"o
VOLTAGE __ I — I
VOLTAGE --I— _��
24(18-35)VDC�
24(18-35)VDC--+
24(1W2)VAC---0-lAllXXI
24VAC�I&ej—Xx
120VAC--*
120VACI�
230VAC --- 6-1 H XD< H
230VAC�l H D<D< H
TI!RMNAL STRIP �ECTIMS
TERMINAL STRIP CONECTIONS
MR-101 M R-201
(MR-104) (M R-204)
@u
kBUILDIMGS
__ _f
IS09061
REGIS,fEkED
IltOA' OANY
Space Age Electronics, inc.
www.ISAE.com
800.486.1723 Toll Free
508.485.0966 Local
508.485.4740 Fax
No Excuses, Just Solutions!
.PSPACEAGE
L
ELECTRONICS, INC.
SSU-
SSU-
SSU-
SSU-
SSU-
SSU-
SSU-
SSU-
SSU-
SSU-
SSU-
ssu-
PRODUCT SPECIFICATIONS
('nf11TAe'T r:Klr'! nQHDr: III- hAPA r1(zMA
MODEL
MODULE
CONFIGURATION
MOUNTED
MOUNTED
COVER
FILE
FILE
17300-1004
FILE
NUMBER:
POSITIONS�
PER POSITION
HXVVXD
HXVVXD
MATERIAL
S3403
73-92-E
3.25" (82mm)
MR-1011T
1
SPDT
2.125" (54mm)
UOXX2
I
:106
1.50" (38mm)
Grey
MR-101/C
1
SPDT
5.125" (130mm)
ABS-94VO
�ed
UOXIX
Vol. 14
3.125" (79mm)
2.50" (63mm)
Plastic
UOXX2
UOXX7
:101
Red
MR-101/CfR
1
SPDT
ABS-94V
Vol. 22
Plastic
3.25" (82mm)
MR-104/T
4
SPIDT
8.50" (215mm)
UOXX2
:106
I
1.50" (38mm)
I
Plated
MR-104/C
4
SPDT
5.125" (130mm)
18ga
UOXX
9.50" (241 mm)
2.50" (63mm)
UOXX2
UOXX7
Vol. 14
:101
MR-104/C/R
4
SPDT
3.25" (82mm)
MR-201/T
I
DPDT
2.126'(54mm)
UOXX2
:106
1.50" (38mm)
Grey
MR-201/C
1
DPDT
5.125" (1 30m rn)
ABS-94VO
UOXX
Vol. 16
3.125" (79mm)
2.50" (63mm)
UOXX2
UOXX7
:101
MR-201/CIR
1
DPDT
3.25" (82mm)
MR-204/T
4
DPDT
8.5" (215mm)
UOXX2
:106
1.50" (38mm)
Plated
MR-204/C
4
DPDT
5.125" (130mm)
18ga
UOXX
1 9.50" (241 mm)
2.50" (63mm)
C S
UOXX2
UOXX7
Vol. 16
:101
Red
�R
1
MR-204/C/R
4
DPDT
I
I
1 a
I
CIRS
I
I
COIL VOLTAGE: M R-1 00: 24(18-35)VDC, 24(18-35)VAC, 120VAC, 230VAC
MR-200:24(18-35)VDC, 24VAC, 120VAC, 230VAC
(Pull in voltage: 75% of nominal max. @ 25*C; Drop out voltage: 25% of nominal min. @ 25'C)
POLARIZED:
DC input only
ENERGIZED LED INDICATOR:
One per module position
CURRENT REQUIREMENT.
Per module position: MR-100 Series = 18mA / MR-200 Series = 40mA
CONTACT RATINGS:
7A @ 28VDC / 10A (NO:1/6HP, NC:1/8HP) @ 120VAC I 7A @ 230VAC
CONTACT CONSTRUCTION:
Dry Form "C"
ENVIRONMENTAL:
32'F to 120'F (O'C to 49'C) @ 85% RH (@ 32*17), Non -condensing, Non-freezing
WIRING:
Solid or stranded; #12 to #22 AWG terminals
/T VERSIONS:
3.5" wide, low profile plastic snap track provided with mounting screws
/C VERSIONS:
Backbox: 18ga CRS, plated with 1/2" conduit knockouts top and bottom
Space Age Electronics, inc.
www.lSAE.com
800.486.1723 Toll Free
508.485.0966 Local
508.485.4740 Fax
No Excuses, Just Solutions!
*UOXX=Control Unit Accessories, System; 2=Component; 7=Certified for Canada
This document is subject to change vAthout notice, see doc # ED0479 for legal disclaimer
ED0313 LT1 0278 Rev.B 2/2
5 V5 ya W
5600 Series
Mechanical Heat
Detectors
System Sensor� 5600 series mechanical heat detectors
offer a lo w-cost means for property protection against fire,
and for non-life-salety installations where smoke detectors
are inappropriate.
Features
• Multiple configurations for installations:
- Single- and dual -circuit models
- Fixed temp and combination fixed- temp/rate-of-rise
135'F or 194*F ratings.
• Plain housing for residential installations (Model 5601P)
• Easy -to -use terminal screws
• Abroad range of back box mounting options:
- Single gang
- 3.5-and 4-Octagonal
- 4"square with square to round plaster ring
• Reversible mounting bracket
Agency Listings
S2101 30MM CS&30 7270-16530167
LISTED
APPROVED
5601 P
F151
r_
5621
Multiple conflquirations. The 5600 series offers a full -line of
configurations to accommodate a broad range of applications. Both
single- and dual -circuit models are available for low- and high -
temperature ratings with either fixed temperature or combination
fixed temperature/rate-of-rise (ROR) activation. The ROR element of
the fixed/ROR models is restorable to accommodate field-testing.
Installation flexibility. To satisfy a variety of installation needs,
the 5600 series easily mounts to single -gang and octagonal back
boxes. And these models accommodate four -square back boxes,
when used with a square to round plaster ring. The reversible
mounting bracket permits both flush- and surface -mount back box
installations.
Visual Identification. The 5600 series provides clear markings
on the exterior of the unit to ensure that the proper detector is being
used. Alphanumeric characters identify the activation method, as
well as the temperature rating, in Fahrenheit and Celsius degrees.
Fixed temperature models are identified FX, while combination fixed/
rate -of -rise units are marked FX/ROR. The 5600 series also provides
a post -activation indicator in the form of a collector. When the
detector is activated. the collector drops from the unit, making it easy
to identify the unit in alarm.
Specifications
Mechanical heat detector shall be a System Sensor 5600 series model number , listed to Underwriters Laboratories UL 521 for
Heat Detectors for Fire Protective Signaling Systems. The detector shall be either a single -circuit or a dual -circuit type, normally open. The
detector shall be rated for activation at either 1351F (571C) or 194*F (901C), and shall activate by means of a fixed temperature thermal sensor,
or a combination fixed temperature/rate-of-rise thermal sensor. The rate -of -rise element shall be activated by a rapid rise in temperature,
approximately 151F (8.3'C) per minute. The detector shall include a reversible mounting bracket for mounting to 31/2-inch and 4-inch
octagonal, single gang, and 4-inch square back boxes with a square to round plaster ring. Wiring connections shall be made by means of
SEMS screws that shall accommodate 14-22AWG wire. The detector shall contain alphanumeric markings on the exterior of the housing to
identify its temperature rating and activation method. The rate -of -rise element of combination fixed temperature/rate-of-rise models shall be
restorable, to allow for field-testing. The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm,
4
Maximum Installation Temperature 5601P, 5603,5621, and 5623: 100,F(38oC)
5602, 5604, 5622, and 5624: 150'F (65.6*C)
Operating Humidity Range 5 to 95% RH non -condensing
Dimensions wfth mounting bracket Diameter: 4.57 inches (1 1.6cm)
Height: 1.69 inches (4.3cm)
Alarm Temperature 5601 P. 5603, 562 1, and 5623: 135'F (57'C)
5602, 5604, 5622, and 5624: 194'F (90*C)
Weight 6 oz. (170 grams)
Rate -of -Rise Threshold 151F (8.3'C) rise per minute (models 5601 P, 5602, 5621, and 5622 only)
Mounting 31/2-inch octagonal back box
4-inch octagonal back box
Single gang back box
4-inch square back box with a square to round plaster ring
LIN
Operating Voltage Contact 6-125VAC / 3A
Ratings 6-28VDC / 1 A
125VDC O.3A
25OVDC 0. 1A
InputTerminals 14-22 AWG
Y FO-
0
ly
5601 P 5602,S622 5603,S623 S604,S624 S621
Ordering Information
5601 P
Single
None
135-F(57-C)
Fixed Temperature / Rate-cf-Rise
50 feet x 50 feet (1 5.24m x 15.2m)
5602
Single
Lettering
194'F(90-C)
Fixed Temperature / Rate -of -Rise
50 feet x 50 feet (1 5.24m x 15.2m)
5603
Single
Lettering
135--F(57-C)
Fixed Temperature
25 feet x 25 feet (7.62m x 7.62m)
5604
Single
Lettering
194-F(90-C)
Fixed Temperature
25 feet x 25 feet (7.62m x 7,62m)
5621
Dual
Lettering
135-F(57-C)
Fixed Temperature / Rate -of -Rise
50 feet x 50 feet (15.24m x 15.2m)
5622
Dual
Lettering
194-F(90-C)
Fixed Temperature / Rate -of -Rise
50 feet x 50 feet (15.24m x 15.2m)
5623
Dual
Lettering
135-F(57-C)
Fixed Temperature
25 feet x 25 feet (7.62m x 7.62m)
5624 Dual Lettering
*NOTE: Refer to NFPA72 guidelines for
194-F(90-C) Fixed Temperature
spacing reductions when ceiling heights exceed 10 feet.
25 feet x 25 feet (7.62m x 7.62m)
4 02013 System Sensor
3825 Ohio Avenue - St. Charles, L 60174
_SY M
STE Phone: 800-SENSOR2 o Fax: 630-377-6495 Product specifications sutWtlo change without notice Visit systemsensoroorn
for current product intormation, including the latest version of this data sheat
�A www.systemsensor.com SPDS,;,)06 - 7113
4- + +
4- 4-
LRG�
0 Absorbent Glass Mat (AGM) technology for superior
performance
0 Valve regulated, spill proof construction allows safe
operation in any position
p.10L)FL 0 Power/volume ratio yielding unrivaled energy density
i J 0
Rugged impact resistant ABS case and cover (UL94-HB)
0 Approved for transport by air. D.O.T., I.A.T.A., F.A.A.
and C.A.B. certified
0 I.I.L. recognized under file number MH. 20845
I V-79adzElE UZ&
• F I -Quick disconnect tabs, Nominal Voltage ....................................................... 12 volts (6 cells)
0. 187" x 0.032"- Mate with
AMP. INC. FASTON "187" F1 F2 Nominal Capacity
series- OR - l12A 14.75 3.4 -1 6.35 20-hr. (4OOmA to 10.50 volts) .......................................... 8.00 AH
• F2 - Quick disconnect tabs, EA =91 I 0-hr. (720mA to 10.50 volts) .......................................... 7.20 AH
0.250" x 0.032" - Mate 1-- 6.35 -1 0.8 . F- 7.95 - .. A 0.8 5-h r. (1.33A to 10.20 volts) ........................................... 6.65 AH
with AMP. INC FASTON
"250" series I -hr. (4.90A to 9.00 volts) ............................................. 4.90 AH
15-min. (15.1 A to 9.00 volts) ............................................... 3.78 AH
Approximate Weight ........................................ 5.60 lbs. (2.54 kg)
Energy Density (20-hr. rate) ............. 1.69 W-h/in3 (103.39 W-h/l)
DID T Specific Energy (20-hr. rate) ............ 17.42 W-h/lb (38.41 W-h/kg)
W internal Resistance (approx.) ..................................... 18 milliohms
Max Discharge Current (7 Min.) ............................... 24.0 amperes
E>, -11
77 Max Short -Duration Discharge Current (10 Sec.) .... 80.0 amperes
Shelf Life (% of nominal capacity at 68*F (20*C)
1 Month ................................................................................. 97%
MODEL PS-128OF1 HT 3 Months ................................................................................ 91%
_1 '. 6 Months ............................................................................... 83%
Operating Temperature Range
L Charge ................................................. 4'F (-200C) to 1220F (500C)
Discharge ............................................. 40'F (-40'C) to 140OF (600C)
L 5.95 (15 1) W: 2.56 (65) H: 3.72 (94.5) HT. 3.90 (99) Case .................................................................................. ABS Plastic
Tolerances are +/- 0.04 in. I+/- I mm) and +/- 0.08 in. (+/- 2mm) for Power -Sonic Chargers ................................. PSC-12800A, 1280OA-C
height dimensions. All data subject to change without notice.
Discharge Characteristics
6.5- 130 Temperature: 25*
6.0 - 120 Z: ZZ , -4 1
-4- N
5.5- 11.0 -
�.66A 7T414A.
5.0- 10.0 - 2k
4.5. 9.0 - BA - SA
4.0- 8.0 ---L I I
1jA I I I
1 2 4 6 810 20 40 60 2 4 6 8 10 20
1 1- In
Discharge Time
Cycle Life in Relation to Depth of Discharge
Testing condition
Discharging: current 0. 1 7C (FV 1. 7V/cell)�
Chargingl 2.45V/cell,max. 0.25CA;
Charging volurl discharged capacity.
12C
10C
,.R 80
2�
Z 60
M 40
Q
20
0
Ambient Temperat re:
25'C(77-F)
0 200 400 600 800 1000 1200
Number of Cycles
Cycle Applications: Limit initial current to 2.4A. Charge until battery voltage (under
charge) reaches 14.4 to 14-7 volts at 68oF (20'C). Hold at 14.4 to 14.7 volts until
current drops to under 8OmA. Battery is fully charged under these conditions, and
charger should be disconnected or switched to "float" voltage.
"Float" or "Stand -By" Service: Hold battery across constant voltage source of 13.5
to 13.8 volts continual When held at this voltage, the battery will seek its own
current level and maintain itself in a fully charged condition.
Note: Due to the self discharge characteristics of this type of battery, it is imperative
that they be charged within 6 months of storage, otherwise permanent loss of
capacity might occur as a result of suffation.
Power -Sonic offers a wide range of chargers suitable for batteries up to I OOAH.
Please refer to the Charger Selection Guide in our specification sheets for "C-Series
Switch Mode Chargers" and "Transformer Type A and F Series". Please contact our
Technical department for advice if you have difficulty in locating suitable models.
Charging Characteristics (Cycle Use)
ChaW "U9119
Ch.Vd
Wum "ur"I
(A)
W"
(VIC01) -
0. 10CA
- 2.25 V/Cell Temperature:
25*C
0. 25
20 '
100 - OM-
14
80- 0.15-
13 ENV%===
E
60- 011-
12VENAMEMENE
41]
20 005_
1
Mon.
10�
8 12
16
20
24 28 32 36 40
0 4
Charging
Time (Hours)
Temperature Effects in Relation to Battery Capacity
120
100
0 80
M
60
.3 40
M
20
0
0
0.05CA
0 10 CA
0,20CA
ICA
2CA
3CA
-20 -10 0 10 20 30 40 50
Temperatul
100
80
60
art 40
E 20
0
12�
0
Self Discharge Characteristics
too.
0 2 4 6 8 10 12
Storage Time (Months)
EA-�jNo supplementary charge required
(Carry out supoementary charge before use if 100% capacit� is required.)
Supoementary charge required before use.0ptional charging vial as bdow
MEI.Charged for above 3 days at limted current 0.25CA and constant vdatge 2.25V/cell.
2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cdl.
3.Charged for 8-10hours at Ill current 0.05CA.
Ec-�]Supoementary charge may often fail to recover the capacft�.
The battery should never be left standing till this is reached
Please refer to our website www.power-sonic.com for a complete range of useful
downloads, such as product catalogs, material safety data sheets (MSDS), ISO
certification, etc..
9 2013. R-r-Sonil All ngh� reserved All:,ademarks are the property ol their respeOve o�nem.
0 I'll I I +
166,61'' ��, , 4- 4- 4-
��MgD 02� �ttp VEM 61X3 4-
"owns 0 Absorbent Glass Mat (AGM) technology for superior
performance
Valve regulated, spill proof construction allows safe
4, operation in any position
P,
P"
Power/volume ratio yielding unrivaled energy density
Rugged impact resistant ABS case and cover (UL94-HB)
0 Approved for transport by air. D.O.T., I.A.T.A., F.A.A.
and C.A.B. certified
0 U.L. recognized under file number MH 208,45
• F2 - Quick disconnect F2 f- 3,4 NB
tabs, 0.250" x 0.032" Us 14 H2 Nominal Voltage ....................................................... 12 volts (6 cells)
-Mate with AMP. INC EAT -41 i [q 61�112
FASTON "250" series F-- 7,95 --J Nominal Capacity
• NB2: Tin plated brass O�8 20-hr. (900mA to 10.50 volts) .......................................... 18.0 AH
post with nut & bolt
connectors T12 1 0-hr. (1 7A to 10. 50 volts) ............................................. 17.0 AH
• Tl 2 -Threaded insert 5-hr. (12A to 10.20 volts) ............................................. 16.0 AH
with 5mm stud T6- 1 -hr. (11. 1 A to 9. 00 volts) ............................................. 11.1 AH
15-min. (34.3A to 9.00 volts) ............................................... 8.58 AH
Approximate Weight ....................................... 12.60 lbs. (5.72 kg)
Energy Density (20-hr. rate) .... .......... 1.53 W-h/in3 (93.51 W-h/1)
W Specific Energy (20-hr. rate) ............ 17.14 W-h/lb (37.79 W-h/kg)
Do] Fo 01 internal Resistance (approx.) ..................................... 14 milliohms
Max Discharge Current (7 Min.) ............................... 54.0 amperes
l=:7= 0 T Max Short -Duration Discharge Current (110 Sec.).. 180.0 amperes
Shelf Life (% of nominal capacity at 681 (20*C)
IMonth ................................................................................. 97%
zee� HT H 3 Months .... ........................................................................... 91%
6 Months ............................................................................... 83%
Operating Temperature Range
- L Charge ................................................. 4'F (-20'C) to 122'F (50'C)
Discharge ............................................. 40'F (-400C) to 140'F (601C)
L: 7.13 (18 1) W: 3.00 (76) H: 6.59 (167) W: 6.59 (167) Case .................................................................................. ABS Plastic
Tolerances are +/- 0.04 in. (+/- 1 mm) and +/- 0.08 in. (+/- 2mm) for
height dimensions. All data subject to change without notice. Power -Sonic Chargers ............................... PSC-1 22000A, 124000A,
................................................................. 12200OA-C, 12400OA-C
efe 0 t e �t- iho-nrbf0WRh-nFc-a% M7`9Fr'T1=.P eM
1 0 OU WiFE-2son
WQM� . 6- ic. 0M
100
. 1 2
80
0
60
40
M
CL
Shelf Life & Storage
ANEREENEEN
� I- Cha*gisnot
e,e,sgyunles
1 0% of capacit
164,
LN7
N
0
N
0
0
E.
-0
is required.
MEN
001INNEEN
Chargingbefore
useisnecessar,
to help recover
EWEN,
WOMEN
full capacity.
Chargenrayfal
torectorefull
capacity. Do not
letbafteriesfoor!
ONE:
thisstate,
0 2 4 6 8 10 12 14 16 18 20
Standing Period (Months)
Discharge Time vs. Discharge Current
20
is
10
5
2
30
E
10
5
Final
Voltage
10.5V
110.2V
__T
9.6V
lov,
9 .0v
40*�
20%
0%
8.1 v I
0.90 1.8 3.6 9.0 18 36
Discharge Current (A)
14.0
13.0
12.0
M
0 11.0
.S 10.0
E
9.0
8.0
Discharge Characteristics
01
lei
1.2 2.4 6 12 24 36481 2 4 6 810 20 40
I- min -1� h �l
Discharge Time
100
ov
M 60
40
20
Life Characteristics in Stand -By Use
Ambient Temperature 20*C (68'F)
Ae
Float Charging
2.25 - 2.30
Voltage
V/Cell
0 1 2 3 4
(1104"F)
(68-F) Years
(32-F)
Life Characteristics in Cyclic Use
Cycle Applications: Limit initial current to 5.4A. Charge until battery voltage
(under charge) reaches 14.4 to 14.7 volts at 68'F (20'C). Hold at 14.4 to 14.7
volts until current drops to under 1 8OmA. Battery is fully charged under these
conditions, and charger should be disconnected or switched to "float" voltage.
"Float- or "Stand -By" Service: Hold battery across constant voltage source of
13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its
own current level and maintain itself in a fully charged condition.
Note: Due to the self -discharge characteristics of this type of battery, it is imperative
that they be charged within 6 months of storage, otherwise permanent loss of
capacity might occur as a result of sulfation.
120
100
80
U
60
.2 40
1�
20
0
0
Discl�arge
Depth 100%
Discharge
Depth501
Discharge
Depth 30%
1. Discharge Current 0.2C (Final Voltage 1.7V/Cell)
?-Charge Current: 0.11C I 1 1
3. Ambient Temperature: 20 , C to 26 oC (68oF to 77oF)
200 400 600 800 1000 1200
Number of Cycles
Power -Sonic offers a wide range of chargers suitable for batteries up to I OOAH.
Please refer to the Charger selection Guide in our specification sheets for "C-Series Please refer to our website www.power-sonic.com for a complete range of useful
Switch Mode Chargers" and "Transformer Type A and F Series". Please contact our downloads, such as product catalogs, material safety data sheets (MSDS), ISO
Technical department For advice if you have difficulty in locating suitable models. certification, etc..
02016. Po -Sonic Corporation, Al I nghts reserved, All kadernarks are the property of their respectNeomem.
PRODUCTS, INC
BW-DocBox
OW-DoclRox (15"Wx 13 " H x 4 " D)
• UUc-UL Listed
• THREE labels:
"Fire Alarm Documents"
"As Built Permits"
"Test and Maintenance Documents"
An adjUstable bungee allows you to
fit variOLIS sizes of binders,
documents, smoke -cans, etc.
• A door bracket holds two CDs, three
sels of keys and more documents
• A cam lock with two keys
BW-DocBox2 (11"Wx 15'Wx 4"D)
Smaller model without the door bracket.
DocROXES
r)I'FR -�' V
The door can
be left blank, or
one of the three
labels may be
used.
i
BW-DocBox2
Other colors, graphic screening,
and custornization are available
for quantities of 25 or more.
F'OFT
Indoor & Outdoor Electrical Enclosures I Drive -Alert Vehicle Detection & Asset Protection Systems I Custom Fabrication
800-473-0213 - info@mierproducts.com - www.mierproducts.com
,fSECURITY
CORPORATION I N N (I VA Y 10 N
7707 Fire Subscribers
IntelfiNet
A Newer, Smarter Alarm
Communications Platform
Feature Highlights
* Leverages state of the art technology
Applies advanced security protection
Offers flexible power and configuration options
Engineered for backward compatibility with legacy systems
Enables future ready capabilities
Provides instant subscriber status through front panel with Power and Trouble LEDs,
a backlit LCD display, and Menu/Silence button
Includes robust Multiple Communication Technologies (MCT) feature
Emulates virtual keypad
Improves functionality with an adaptive Graphic User Interface (GUI) for programming
via smartphones, tablets and PCs
0 Plus many more...
Key Benefits
aes-corp.com
NFPW LISTED
• Built upon the solid foundation of AES-IntelliNet patented mesh radio technology for use in private
licensed wireless networks
• Protects subscriber units against unauthorized access and rogue activity with a password -protected
Dealer Code
Makes programming and streamlined troubleshooting easy with user friendly interface
Adds integrated supervision of AES-IntelliPro full data module
Provides versatile power options:
(1) Direct from the Fire Alarm Control Panel (FACP) without requiring an electrician onsite and
without Subscriber backup battery;
(2) Directly from the FACP with Subscriber backup battery; or
(3) Traditional installation with plug in Class 2 low power transformer
Allows for enhancement upgrades and an expanded number of new features to be added easily
with highly flexible and scalable alarm communications infrastructure
Rigorously tested to the highest industry standards and future ready to meet emerging N FPA code
and UL standards
Enhanced Wireless Fire Alarm Monitoring
Powered by AES enhanced mesh radio technology, IntelliNet 2.0 7707 Fire Subscribers are next generation
universal wireless communicators that provide advanced security protection for any new or existing alarm
monitoring network. The AES Model 7707 is ideal for commercial fire applications. With the AES-InteffiPro full data
module option, they are the ideal drop -in replacement for Plain Old Telephone Service (POTS) lines.
The red metal enclosure comes with a key lock and front panel LCD backlit display with intuitive view that provides
an instant visual of the subscriber status. The user friendly GU I makes it easy to program AES subscriber units
via a smartphone, laptop, tablet, or integrated Universal Serial Bus (USB)—without the need for special cables or
having to use a handheld programmer. Additional knockouts make it easier to mount for faster installation.
IntelliNet 2.0 Private Wireless Mesh Radio Network
0) Burglary D
Subscriber - - - - - - - - - -
C
3) Fire
Subscriber
- - - - - - - - - - - - - - - - - - Pt..ry AES-M.10NO R
A)Alarm
Panel
6 113 C Alarm Automation
*A A Q IP Links
g Station
rm Panel & AES Subscriber W-'alh AES-Mtellift* NeWo- k Primary & Secondary AES-MultiMet Syste m
W"J� L,ititdl ewnt �ipdl dpll--rs alarm signals va smart routing receNes transmission In 1-3 seconds
Customer Location Me h Radio Technology Central Monitcrin
Ala
777 rdu
The IntelliNet 2.0 Fire Subscriber has an 8 Zone modular design for expansion with normal and reverse polarity,
POTS and DACT interfaces with an option for the 7794A AES-IntelliPro full data module add -on accessory board.
AES subscribers' intelligent software automatically detects new hardware and devices to reduce installation time.
An AES certified WiFi accessory allows seamless wireless connectivity for configuration and programming. A
laptop, Ethernet cable, or a Wi-Fi USB clongle is required for lntelliNet2.0 programming, handheld programmers
will not work with 2.0 units. A FACP Power Supply Adapter is required for certain configurations when using flexible
power options. The forward compatible design allows for feature add-ons, engineered to adapt seamlessly with
future software upgrades as technology advances. IntelliNet 2.0 allows configuration cloning for faster
installation time.
The AES 7707 was designed with quick configuration and installation in mind to make it easier for field technicians
to get in, out, and on to the next install.
Visit our Fire Marshal Resources web page for official NFPA and UL Listings:
aes-corp.com/products/fire/fire-marshal-resources
How to Order
7707 Fire
IntelliNet 2.0 Fire Subscribers
2.OPREMIUM (UL&ULCListed)
7707P-88-M
IntelliNet 2.0 Fire Subscriber, 8 Zone with Multiple Communication Technologies
(MCT), Red Enclosure
7707P-88-ULP-M
IntelliNet 2.0 Fire Subscriber, 8 Zone with 7794A AES-IntelfiPro, and integrated
onboard Local Annunciator plus MCT, Red Enclosure
7707P-44-M
IntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with
Multiple Communication Technologies (MCT), Red Enclosure
IntelliNet 2.0 Fire Subscriber, 44 Zone (4 Reversing Polarity, 4 Supervised)
7707P-44-ULP-M
with 7794A AES-IntelliPro, and integrated onboard Local Annunciator plus
MCT, Red Enclosure
2.0 ACCESSORIES
7794A
Standalone AES-IntelliPro Fire full data module add -on accessory board with
firmware for new IntelliNet 2.0 units only, cannot be used in legacy units
77-WiFi
AES certified WiFi adapter
77-FACPA
FACP Power Supply Adapter for internal mount
77-FACPA-KIT
External installation hardware for 2-wayjunction Box
Legacy Fire Subscribers
7706-ULF
Integrated Fire Monitoring System, Red Enclosure
7788F-ULP-P
Legacy Fire Subscriber, 8 Zone with 7795 AES-IntelliPro (7794 full data module,
7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure
7788F-ULP
Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones with 7794 AES-IntelliPro,
Red Enclosure
7788F
Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones, Red Enclosure
7744F-ULP-P
Legacy Fire Subscriber, 4 Zone with 7795 AES-IntelliPro (7794 full data module,
7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure
7744F-ULP
Legacy Fire Subscriber, 4x4 Zone, 4 Supervised Zones with 7794 AES-IntelliPro,
Red Enclosure
7744F
Legacy Fire Subscriber, 4x4 Zone, 4 Reversing Polarity, 4 Supervised Zones,
Red Enclosure
LEGACY ACCESSORIES
7794
Standalone AES-IntelliPro Fire full data module add -on accessory board for legacy
units only, please see 7794A above for IntelliNet 2.0 version
Technical Specifications
DIMENSIONS
13"H x 8.5"W x 4.5"D
(33cmH x 21.5cmW x 11.4cmD)
WEIGHT
5.8 lbs (2.6 kilograms)
excluding battery
13 lbs (5.9 kilograms) with
10 Ah battery
RADIO FREQUENCY
Standard Frequency Range
450-470 MHz
Contact AES for other UHF
and VH F frequencies
ANTENNA
2.5 dB tamper resistant antenna
included, mounts on enclosure
Optional remote mounting
antenna available
POWER INPUT
AC SOURCES
Transformer: Class 2
16.SV AC nominal output
1.9 A max current (40 VA MIN)
ELK ELK-TRG1640,
MG ELECTRONIC SALES MGT1640,
or AES 1640 (not included)
DC SOURCES (includes FACP)
24V DC Regulated Power Supply
with Subscriber
Rechargeable Battery
1.9 A max current
BACKUP BATTERY
10-12 Ah, UL recognized lead acid
gel cell, size based on subscriber
configuration
Contact Us
ALARM SIGNAL INPUTS/ZONES
8 individually programmable
E.O.L. type zone inputs
4+4: 4 reverse polarity input and
4 individually programmable
E.O.L. type zone inputs
Optional 7794A AES-IntelliPro for
full data via Contact ID, Pulse,
Modem Ile and Modem Illa2
UL LISTINGS
UL 864 loth Edition
Standard for Control Units and
Accessories for Fire Alarm Systems
ULC S559-04 lst Edition
Equipment for Fire Signal
Receiving Centres and Systems
TROUBLE OUTPUT—ACK
DELAY/ANTENNA CUT
Form C relay, fail secure, rated 24V
DC 1A resistive, unsupervised
RESET BUTTON
Located on main circuit board
OPERATING TEMPERATURE
32 to 120OF (0 to 490C)
STORAGE TEMPERATURE
14 to 1400 F (-1 0 to 600C)
RELATIVE HUMIDITY
0 to 93%, non -condensing
RECHARGE CAPABILITY
Will charge 12V battery size
from 10-12 Ah
7707 Fire
PORTS
Ethernet for configuration
and message communication
USB access for software upgrade
REMOTE ANNUNCIATOR
AES Model 7740
Remote Annunciator, supervised
COMPATIBLE RECEIVERS
7705i AES-MultiNet Receiver
CONFIGURATION INTERFACE
Web browser capable device
accessible via smartphone, tablet,
laptop, or PC
CURRENT CONSUMPTION
Standby w/ charged backup battery:
200 mA (1.2 A Transmitting)
Standby + charging backup battery:
900 mA (1.9 A Transmitting - MAX)
POWER OUTPUT
2 or 5 Watts
Factory set
ENCLOSURE MATERIAL
Steel with paint finish
FINISH COLOR
Red
VISUAL INDICATORS
Front panel LCD
(2 x 20 alphanumeric character
backlit display)
Power and Trouble LEDs
(ALM, Trouble, Tx, Rx, WA)
For pricing and availability or to learn more about IntelliNet 2.0, please call your local
AES Sales Representative at (800) 237-6387 or email sales@aes-corp.com.
aes-corp.com
'Et URITY
CORPORATION
Full DOW Module
A E— S —ire LISTED
TECHNI[CAL
SPECIFICATIONS
-Transmits full data to AES
receiver using Contact ID
or Pulse formats
- Formats Supported: Contact
ID, Pulse 3+1, Pulse 4+11, Pulse
4+2, Modem Ile*, and
Modem IIIa2*
1/0 CONNECTIONS
• AES subscriber with power
• Handheld/PC programming
port
• POTS incoming phone line
-Phone output from alarm panel
-Trouble output (form C relay)
SIZE
2.8 x 5.0 inches (7.1cm x 12.7cm)
POWER REQUIREMENTS
12 VDC nominal, primary and
backup power provided by the
AES RF Transceiver Unit
HOW TO ORDER
Model Description
7794 AES-IntelliPro Fire
7744F-P UL Fire Subscriber
w/7794 (4 reversing
polarity & 4 EOL
inputs)
7788F-P UL Fire Subscriber
w/7794 (8 EOL inputs)'
4oW
P 0-V
13
6c,
006
0
Features
-Commercial fire alarm applications -
with or without phone lines
-Transmits full alarm data from any
Contact ID or Pulse format fire
alarm panel
-Supports expanded event reporting
from Bosch Modem 11 and Modem
III alarm panels
-Primary or back-up communications
-Universal wireless alarm transmitter
supports most manufacturers'
panels
Easy to install in AES subscriber
Easily programs using an AES
Handheld Programmer or laptop
-Option to remotely configure via a
web browser
-Option to monitor telephone lines
-Transmits full data to AES receiver
using Contact ID or Pulse formats
-Formats Supported: Contact I D,
Pulse 3+1, Pulse 4+1, Pulse 4+2,
Modem Ile*, and Modem IIIa2*
The 77'14 AES-InteffiPro F!re is an add -of-, r-r-odLile for A -IS
subscribers that enables trarsr—won of full a1c,Irm zone data
from an alarm parel to a centi-al sLation over an
established AES-IntelliNet relw,/ork.
AES subscribers with AES-IntelliPro Fire can operate in applications with or without
a phone line providing full emulation of the phone line for the alarm panel
communicator. AES-IntelliPro Fire supports most popular alarm communication
protocols including Contact ID and Pulse as well as Modem 11 and Modem III
converted to CID.
About AES Corporation
Established in 1974, AES
Corporation empowers
companies to grow profitable
alarm monitoring businesses,
and government agencies to
enhance security anywhere
in the world. By providing
the industry's only patented
operator -owned and controlled
private wireless mesh networks,
AES ensures superior reliability,
low TCO and optimal RMR while
reducing dependence on service
provider infrastructures.
The company's flagship
AES-IntelliNet systems are
deployed in over a half million
locations worldwide.
Easy Installation
AES-IntelliPro Fire easily installs in the subscriber housing and is powered from the
transceiver module, requiring no additional power connections. AES subscribers can
be ordered with AES-IntelliPi'o Fire installed. AES-IntelfiPro Fire is easy to program
using the AES Handheld Programmer.
Alarm Panel
,41VAESj1ntej1jNet
��.110.
AES-IntelliNet' Private Wireless Mesh Network
Custorner's Premise
IP Link
Central Statio
n
ev) Alarm Automation
EDMONDS
FIRE ALARM SYSTEM
MIXED USE -- PHASE 2
SHEET INDEX
GENERAL INSTALLATION NOTES
FAO 01 GENERAL NOTES, CODE INFORMATION, SYMBOL LIST
1. NOT ALL GENERAL NOTES MAY BE IN EFFECT FOR THIS INSTALLATION AND SCOPE OF WORK.
FAO:02 FIRE ALARM: SYSTEM RESPONSE MATRIX, SYSTEM MATRIX
2. FOR THE PURPOSE OF THIS INSTALLATION, SPRINKLER MONITORING AND FIRE ALARM ARE INTERCHANGEABLE
FAO . 03 FIRE ALARM: SYSTEM CALCULATIONS
AND EQUAL. SEE SCOPERROJECT NARRATIVE.
3. PER IFC (2015ed/2018ed) 907.1.3, ALL WIRE AND DEVICES CONNECTED TO THE FIRE ALARM SYSTEM SHALL BE
LISTED BY AN APPROVED LISTING AGENCY (TYPICALLY UL OR FMJ COMPATIBLE, AND INSTALLED PER
MANUFACTURER'S SPECIFICATIONS AND INSTRUCTIONS. INSTALLATION SHALL BE IN ACCORDANCE WITH ALL
FA4 00 FIRE ALARM & ARA: LEVEL 0 PLAN
AUTHORITIES HAVING JURISDICTION (AHJ), NFPA, IFC, NEC, WAC, MUNICIPAL CODE, AND CONTRACT
'
FA4.01 FIRE ALARM & ARA: LEVEL 1 PLAN
DOCUMENTS.
4. INSTALLING CONTRACTOR(S) SHALL PROVIDE WASHINGTON ALARM WITH A LEGIBLE, CLEAN, AND ACCURATELY
FA4.02 FIRE ALARM & ARA: LEVEL 2 PLAN
NOTED DRAWING FOR "AS BUILT" PURPOSES. THE DRAWINGS SHALL INCLUDE PERTINENT WIRE RUNS, CONDUIT
FA4.03 FIRE ALARM & ARA: LEVEL 3 PLAN
SIZES/LOCATIONS, JUNCTION BOXES, SIGNIFICANT DEVICE LOCATION CHANGES, MOUNTING HEIGHTS THAT
FA9.01 FIRE ALARM &ARA: RISER DIAGRAM
DIFFER FROM LISTED HEIGHTS, AND 120VAC POWER CIRCUIT PANEL LOCATIONS/CIRCUIT NUMBERS.
S. FIRE ALARM DOCUMENTATION SHALL NOT BE STORED IN THE FIRE ALARM CONTROL UNIT PER NFPA72 (2019ed)
7 1 7.2.3. AN APPROPRIATE RECORDS ENCLOSURE SHALL BE SUPPLIED.
6. PROTECTED PREMISES FIRE ALARM (NFPA72, 2016ed: 3.3.103A.2) SYSTEMS SHALL BE MONITORED BY A LISTED
SUPERVISING STATION (NFPA72, 2016ed: 3.3.280/3.3.281) IN ACCORDANCE WITH IFC (2015ed/201 Bed) 907.6.6.
COMMUNICATION METHODS SHALL BE IN ACCORDANCE WITH NFPA72 (2013ed/2016ed) 26.6. COMMUNICATION
VIA DACT (2 "POTS" LINES) ALONE IS NOT ACCEPTABLE WITHOUT APPROVAL BY ALL AHJ 'S PER NFPA72 (2013ed)
26.6.3.2.1A OR NFPA72 (2016ed) 26.6.4.1 A. MONITORING MAY BE SUBJECT TO DEFERRED CONTRACT, AND MAY
BE PERFORMED BY OTHERS BEYOND THE CONTROL OF WASHINGTON ALARM.
7. ALL 120VAC WIRING TO CONTROL UNITS AS DEFINED BY NFPA72 (2013ed) 3.3.59,3.3.10Z 3.3.199 OR NFPA72
(2016ed) 3.3.60, 3.3.100, 3.3.196 SHALL BE PERMITTED (SEPARATELY IF REQUIRED BY AHJ AND INSTALLED BY AN
ELECTRICAL CONTRACTOR LICENSED TO PERFORM SUCH WORK. ALL 120VAC WIRING TO CONTROL UNITS AND
POWER SUPPLIES SHALL BE DEDICATED, LABELED, AND INSTALLED WITH A BREAKER LOCK. ALL CONTROL UNITS
AND POWER SUPPLIES SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF WASHINGTON ALARM STAFF. ALL
120VAC WIRING ENTERING FIRE ALARM CABINETS SHALL BE THROUGH DEDICATED KNOCKOUTS, AND SHALL
CODEPROJECT INFORMATION
MAINTAIN A MINIMUM OF 0.25" SEPARATION FROM POWER UMrrED/LOW VOLTAGE WIRING.
8. THIS PROJECT MAY EMPLOY A SEPARATE ELECTRICAL CONTRACTOR AND FIRE ALARM CONTRACTOR IN A JOINT
VENTURE. UNLESS OTHERWISE NOTED BY ANY CONTRACT DOCUMENTS, THE ELECTRICAL CONTRACTOR SHALL
PERMIT (SEPARATELY, IF REQUIRED BY THE AHJ), FURNISH AND INSTALL ALL BACKBOXES, RACEWAY, AND WIRE
17 Z
PER WASHINGTON ALARM SPECIFICATIONS. ELECTRICAL CONTRACTOR SHALL INSTALL ALL SPECIALTY
&g N
BACKBOXES, ENCLOSURES, FIRE ALARM TERMINAL CABINETS PROVIDED BY WASHINGTON ALARM. PLEASE
ALLOW FOR A MINIMUM TWO WEEK LEAD TIME ON ALL WASHINGTON ALARM SUPPLIED EQUIPMENT.
9. WIRING SHALL BE PER DESIGN WITH RESPECT TO CONDUCTOR SIZE AND/Olk CABLE TRAY. TYPE, QUANTITY,
COLOR CODE AND CONDUCTORS SHALL BE PERMANENTLY AND UNIQUELY MARKED FOR FUTURE
IDENTIFICATION. ELECTRICAL CONTRACTOR SHALL MAINTAIN THE CLEANLINESS OF ALL INSTALLED
9
BOXES/ENCLOSURES. DIRT/DEBRIS SHALL BE CLEANED PRIOR TO TRIM.
10.WIRING SHALL CUT FOR IN/OUT. WIRING SHALL NEVER BE LOOPEDTHROUGH DEVICES, ALLSPLICEDWIRE
POSSESSING SHIELD SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS.
Q
1.�l 11-1 E-1
11. WIRING SHALL RUN CON11NUOUS FROM SOURCE TO FIRST DEVICE ON CIRCUIT THEN FROM DEVICE TO DEVICE
WITHOUT SPLICING IN PULL BOXES OR OTHER BACKBOXES OF DIFFERENCT CIRCUITS. "T-TAPPING" OF
CONVENTIONAL IN117ATION aDC-S) OR NOTIFICATION APPLIANCE CIRCUITS (NAC-S) WILL RESULT IN A NON
R-Y
FUNCTIONAL SYSTEM, AND IS STRICTLY PROHIBITED.
12. WIRING SHALL BE METERED AND VERIFIED TO BE CONTINUOUS, FREE FROM GROUND, SHORTS, OR ANY OTHER
e
T"
C,di.A1tMQ F.,y 1�
FAULTS.
13. WIRING SHALL BE IN CONDUIT, OR CONCEAUED/HIDDEN. SURFACE MOUNT WIRING INSTALLATION ALLOWABLE
&1
WH E N AP P ROVE D BY OWN ER, OWN ER REP., 0 R P ROJ ECT TEAM AN D CO M P LIANT WITH ADO PTE D CO D ES.
> Q Rld �q
14. NUMBERS ADJACENT TO NOTIFICATION SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS AND NOTIFICATION
Ny-S,
SETTING. EXAMPLE DEVICE SCII-9 WOULD BE NINTH DEVICE ON SIGNAL CIRCUIT 1. 30CD DENOTED CANDELA
RATING SETTING. NOTIFICATION CIRCUIT WIRING IS SUPERVISED. PARALLEL BRANCHING IS NOT PERMISSIBLE.
15. WALL MOUNT SIGNALLING APPLIANCES SHALL BE INSTALLED PER THE HEIGHTS LISTED BY THE SYSTEM
DESIGNER/WASHINGTON ALARM IN ORDER TO ACHIEVE CURRENT COMPLIANCE AS WELL AS POTENTIAL
MANUFACTURING DESIGN CHANGES IN THE FUTURE. COMPLIANCE WITH NFPA72 (2013ed/2016ed)l 8.5.5 WHERE
THE ENTIRE LENS OF STROBE IS NOT LESS THAN 80" AND NOT GREATER THAN 96" ABOVE FINISHED FLOOR. SEE
PROJECT SITE
ALSO NFPA72 CHAPTER 18 FOR LOW WALL HEIGHTS, OR CEILING MOUNTING INSTALLATIONS.
OWNER:
16. DO NOT DEVIATE FROM CIRCUIT RUNS SHOWN ON PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM
EDMONDS 2020 LLC, EDMONDS, WA
DESIGNER/WASHINGTON ALARM. SYSTEM SHALL BE INSTALLED NTH MINIMUM 20% SPARE CAPACITY (SUBJECT
TAX ID/PARCEL
TO ADDITIONAL CONTRACT REQUIREMENTS) PER IFC (2015ed/2018ed) 907.5.2.3.1. FACTORS SUCH AS EXCESSIVE
00434400700800
VOLTAGE DROP, ENGINEERING, ADDITIONAL COMPONENTS, ETC SHALL BE THE RESPONSIBILITY OF THE
FIRE ALARM AUTHORITY:
CONTRACTOR DICTATING AS BUILT ROUTING.
17. NOTIFICATION APPLIANCES SHALL PRODUCE AN AUDIBILITY OF NOT LESS THAN 1 SdB ABOVE THE AMBIENT
CITY OF EDMONDS
NOISE LEVELS AND REMAIN IN COMPLIANCE WITH WASHINGTON STATE ADMINISTRATIVE CODE (WAC)
OCCUPANCY:
51-54A-0907. NON VOICE SYSTEMS SHALL SOUND IN THE STANDARD TEMPORAL THREE PATTERN AT THE
CLASS: B, S, R2
LOWEST DECIBEL SETTING (90dB) UNLESS OTHERWISE NOTED ON PLANS. ALL VISUAL DEVICE CANDELA RATINGS
CONSTRUCTION:
ARE DETERMINED IN ACCORDANCE WITH NFPA72 (2013ed/2016ed) 18.5.5.4.
TYPE: V-13
18. RISER ROOMS CONTAINING FIRE ALARM CONTROL UNITS SHALL BE SIZED APPROPRIATELY IN ACCORDANCE
SPRINKLED: YES, FULLY
WITH IFC 901.4.6. ALL DEVICES SHALL BE ACCESSIBLE OR MADE ACCESSIBLE (BY WAY OF HATCH, CATWALK ABOVE
CODES:
CEILING GRID, REMOVABLE PANELS) FOR ALL CURRENT AND FUTURE INSTALLATION, TESTING OR MAINTENANCE
CITY OF EDMONDS MUNICIPAL CODE: 19.25.000
REQUIREMENTS. ACCESSIBILITY SHALL BE IN ACCORDANCE WITH NFPA72 (2016ed) 3.3.1 - 33A.
IFC (2015ed) NFPA72 (2016ed)
19. ALL DEVICES SHALL BE ACCESSIBLE OR MADE ACCESSIBLE (BY WAY OF HATCH, CATWALK ABOVE CEILING GRID,
WAC 51-54A-0907
REMOVABLE PANELS) FOR ALL CURRENT AND FUTURE INSTALLATION, TESTING OR MAINTENANCE
SCOPE RESPONSIBILITIES:
REQUIREMENTS. ACCESSIBILITY SHALL BE IN ACCORDANCE WITH NFPA72 (2016ed) 3.3.1 - 33A.
WASHINGTON ALARM TO FURNISH/INSTALL ALL EQUIPMENT SHOWN (UNLESS NOTED),
20.ANY POST CONTRACT ISSUANCE CHANGES TO CONSTRUCTION, INCLUDING THE LOCATION AND TYPE OF WALLS,
INCLUDING DETECTION, NOTIFICATION, CONTROL PANELS. 120VAC POWER FURNISHED
CEILINGS, PERMANENT FIXTURES MAY AFFECT DESIGN, AND SHALL BE IMMEDIATELY BROUGHT TO THE
BY EXPRESS ELECTRIC.
ATTENTION OF THE SYSTEM DESIGN ER/WASHINGTON ALARM, AS A RE -REVIEW BY ALL AHTS MAY BE REQUIRED.
PROJECT DESCRIPTION:
21.SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 36.. FROM AN AIR
NEW FIRE ALARM SYSTEM TO COVER BOTH PHASES: SPRINKLER MONITORING, SELECTIVE
SUPP DIFFUSER.
AUTOMATIC INITIATION, AND FULL OCCUPANT NOTIFICATION. EXTERIOR NOTIFICATION
22.DO NOT INSTALL SMOKE DETECTOR HEADS UNTIL FINAL CLEANING, OR IF UNPRACTICAL DUE TO CONSTRUCTION
TO FACE FIRE DEPARTMENT RESPONSE.
SCHEDULES, SMOKE DETECTORS SHALL BE PROTECTED FROM CONSTRUCTION DUST AND OTHER
FIRE ALARM PATHWAY CLASS DESIGNATIONS:
ENVIRONMENTAL CONCERNS.
23.ALL DETECTORS SHALL BE RATED FOR THE TEMPERATURE AND ENVIRONMENT FOR THE LOCATION IN WHICH
NOTIFICATION APPLIANCE CIRCUMS): B
THEY ARE INSTALLED.
SIGNALING LINE CIRCUMS): 8
24. IN ACCORDANCE WITH IFC (2015ed/2018ed) 907.2 AND NFPA72 (2016ed) 23.8.5.1.2, MANUAL PULL STATIONS
INITIATION DEVICE C3RCUFr(S): SPRINKLER WATERFLOWS=A, ALL OTHERS=B
INSTALLED IN A SPRINKLER RISER ROOM SHALL BE ACTIVE AT ALL TIMES INCLUDING DURING SPRINKLER OR
SURVIVABILITY: 0 (NONE REQUIRED)
AUTOMATIC DETECTION IMPAIRMENT, OR WHEN SYSTEM IS IN "TEST". APPROPRIATE WARNING SIGNAGE SHALL
COMMUNICATION METHOD:
BE PLACED ADJACENT.
SUBJECT TO OWNER APPROVAL AND SEPARATE CONTRACT
25.RESCUE ASSISTANCE SYSTEMS SHALL BE MONITORED PER IFC1009.8.1. PROVIDE INSTRUCTIONAL SIGNAGE AT
FIRE ALARM: NEW ONE WAY PRIVATE RADIO IN ACCORDANCE WITH NFPA72 (2016ed)
EACH STATION PER ICC All 17.1, IFC 1009.8.2. PROVIDE 1 TELEPHONE LINE AT MASTER STATION.
26.6.3.3.2, MONITORED BY WASHINGTON ALARM, 206.328.3288. UL: 110698-001
26.RESCUE ASSISTANCE SYSTEMS SHALL BE MONITORED FOR INTEGRITY PER NFPA 72 (2016ed) 24.10.4. TO BE
ACHIEVED BY FIRE ALARM SYSTEM.
27.SEE MANUFACTURER SPECIFICATION SHEETS FOR SIGN MOUNTING HEIGHTS AND LOCATIONS.
EDMONDS, WASHIN
SYMBOL LIST -FIRE ALARM
QTY: EX QTY: NEW SYMBOL DESCRIPTION MANUFACTURER MODEL BACKBOX MOUNTING HEIGHT
REPLACE 1 F RE ALARM
I SILENT KNIGHT 6820XL PROVIDED BY 66" A.F.F
CONTROL PANEL SILENT KNIGHT TO TOP
0
2
REPLACE
0
5
1
2
0
1
10
3
I
0
VERIFY
vtKII-Y
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
1
14
3
4
4
2
1
VERIFY
VERIFY
2
7
9
11
9
57
5
1
1
E
F-F-C-p-1-1
FIRE ALARM
NODE
SILENT KNIGHT
5895XL
PROVIDED BY
SILENT KNIGHT
FIELD DETERMINE
FS--E-p-X I
SIGNAL EXTENDER
PANEL
POTTER
PSN106
PROVIDED BY
FIELD DETERMINE
POTTER
FIRE ALARM
COMMUNICATOR
AES
7707
PROVIDED BY
ADJACENT
-ARM
AES
TO FACP
- - AL
�UMENT
MIER PRODUCTS
BWDOCBOX2
N/A
ADJACENT
LOSURF
TO FACP
FIRE ALARM
ANNUNCIATOR
SILENT KNIGHT
5860R
SEE FAO.3
qFF FAO.3
DETAIL 3
DETAIL 3
PHOTOELECTRIC
SMOKE DETECTOR
SILENT KNIGHT
PHOTO-W
4S DEEP
W/1G RING
CEILING
Q,
MULTI CRITERIA
SMOKE DETECTOR
SILENT KNIGHT
ACCLIMATE
TOP OF SHAFT
(NORTH BUILDING)
EXISTING CONDITION
TO REMAIN
F
HEAT DETECTOR
SILENT KNIGHT
HEAT-W
EXISTING CONDITIONS TO REMAIN
/L-J\
WEATHERPROOF
POTTER
CR 35MP W/
4S DEEP
\D/F
HEAT DETECTOR
SILENT KNIGHT
MONITOR
W/1G RING
CEILING
,U\
\2/E
ELEVATOR SHUNT
SYSTEM SENSOR
5623 WV
4S DEEP
HEAT DETECTOR
SILENT KNIGHT
MONITO 2
W/1G RING
CEILING
ADDRESSABLE SINGLE SILENT KNIGHT
MINIMON
INPUT MODULE
SILENT KNIGHT
MONITOR
4S DEEP
FIELD DETERMINE
ADDRESSABLE DUAL
INPUT MODULE
SILENT KNIGHT
MONITOR2
4S DEEP
FIELD DETERMINE
ADDRESSABLE SINGLE
OUTPUT MODULE SILENT KNIGHT
RELAY
4S DEEP
FIELD DETERMINE
LINE ISOLATION
MODULE
SILENT KNIGHT
ISO
4S DEEP
FIELD DETERMINE
FIRE ALARM
SILENT KNIGHT
PS-SATK W/
4S DEEP
48" A.F.F.
MANUAL PULL
SILENT KNIGHT
MINIMON
W/1G RING
TO TOP
SPRINKLER
WATERFLOW
PROVIDED BY OTHERS - MONITORED BY SK-MONITOR
-..VALVE
SPRINKLER
TAMPER
PROVIDED BY OTHERS - MONITORED BY SKmMONITOR
SPRINKLER
LOW AIR
PROVIDED BY OTHERS - MONITORED�ETY
SK-MONITOR
SPRINKLER LOW
POTTER
RTSO Wv
FIELD DETERMINE
TEMPERATURE
SILENT KNIGHT
MONIT
FIELD DETERMINE
NOTIFj.,ATION
HOR STROBE
SYSTEM SENSOR
PG2xL
4S DEEP
W/1G RING
84" A.F.F.
TO CENTER
MOUNT
NOTIFICATION E
451UPP
SYSTEM SENSOR
SYSTEM SENSOR
PC2xL
PC2wHK
VARIES
CEILING
HENHHOOF
NOTIFI�,ATION
SYSTEM SENSOR
P2RK
PROVIDED BY
84" A.F.F.
SYSTEM SENSOR
TO CENTER
FREtMEtCY
N ION
HORN qTRR
SYSTEM SENSOR
P2WH-LF
4S DEEP
CEILING
LOW FREQuph CY
NOTIFICATION
SYSTEM SENSOR
HxLF
4S DEEP
W/1G RING
84" A.F.F.
TO
HORN ONLY
CENTER
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHIAI282C3
P: 360.416.8227
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.com
WA Lic: RHEMAEL940DH
Project Title
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Project Numbers
18313-1
Issue & Revision Dates
10 OCL 2018 RO-INMAL DESIGN
SUBMFITALS
OWNER _e�b_y\qtI LC;2 7
,L-Zja_ 16LL;
APPROVED DATE:
BLDG. OFFICIAL:
PERMIT NUM -Elt
NU11FICA110IN
STROBE ONLY
SYSTEM SENSOR SGxL
4S DEEP
W/1G RING
84" A.F.F.
TO CENTER
Th�eetljtle
9CM
CEILING MOUNT
NOTIFICATION
STRC 3E ONLY
SYSTEM SENSOR SCxL
4S DEEP
W/1G RING
CEILING
FIRE ALARM &
CONTROL RELAY FUNCTIONAL
4k NON -ADDRESSABLE DEVICES RIBU1C-RD N/A
FIELD DETERMINE
ARA SYSTEM
INFORMATION
PERTINENT
JUNCTION BOX LOCATE AS REQUIRED -- NOT ALL J-BOXES APPEAR ON PLANS
END OF LINE
RESISTOR
AREA OF RESCUE ASSISTANCE SYMBOL LIST
QUANTITY
SYMBOL
DESCRIPTION MANUFACTURER
MODEL
BACKBOX
MOUNTING A�GHT
AREA OF RESCUE
RATH
2500-205
PROVIDED BY
66" A.F.F
MASTER STATION
RATH
To TOP
AREA OF RESCUE RATH
POWER SUPPLY
2500-PWR
PROVIDED BY
RATH
FIELD DETERMINE
2
DACS
AREA OF RESCUE RATH
CALL STATION
2100-958SSRC2
PROVIDED BY
44" A.F.F
-
RATH
TO CENTER
SECONDARY POWER SUPPLY FACTORY
INSTALLED ALLOWS FOR MINIMUM 4 HOURS
TALK TIME
RECrEIVIED
APR 0 8 2019
DEVELOPMENI S�HVl GTR.
CITY OF EDMONDS
Q� in L6v-&� o/;
MOUNT INSTRUCTION
SIGN ADJACENT
rrePared By Nicet Revie�
E , Hamerski P. Nguyen
118193 139398
F,P 12/1/21 Expires 1/] /21
Sheet Number
FAO.O 1
0---m
FIRE ALARM SYSTEM DEVICE MATRIX
Wilkinson - North Building
Address
Dev Type
Response
Desc(iption/Type
001 -009
Unused
n/a
Not Used
1T.Solo
Addr1nitDetPhato
Fire
LO Ele� Landing Smk (was 33:001)
1 7.
Addr.InitDetPhoto
Fire
LO Elev Machine Rm SmIc (was 33:002)
17.:001121
AddrinitDet:Photo
Fire
Ll E e Landing S k (was 33.,008)
17.'s013
t ec
Add r1ni D Photo
Fire
L2 E:ev Landing Smk (was 33 009)
v m
17:s014
AddrjniLDetHeat
Fire
L3 Elev Landing Heat (was 31010)
17:s015
Addr.InitDet:Heat
Fire
L4 Elev Landing Heat (was 33:01 1)
17:s016
Add,lnitDet:Acclimate
Fire
Elev Shaft SmIc (was 31012)
17:017
Add'Init:Det:Photo
Fire
Ll Elec Rm S.k (was 33:014)
016-159
Unused
n/a
Not Used
Wilkinson -
North Building
dress
Dev Type
Response
Description/Type
001-010
Unused
n/a
Not Used
17:m011
Addr.InitSwitch:Manual Pull
Fire
LO Sprinkler Rm Pull (RELOCATED)
1 PmO12
Addr.InitSwitch:Supervisory
Suprvsy
Sprinkler Rm Low Temp (NEW)
17:m0l 3
Addr.InitSwitch,.Waterflow
Fire
Main Wet Waterflow (was 33:016)
lPmO14
AddrinitSwitch:Supe"isory
Suprvsy
Main Wet Tampers (was 33:017)
1T.m015
Addr.InitSwitch,.Waterflow
Fire
Main Dry Waterflow (was 33:018)
17.'m016
Addr. InitSwitch:Supervisory
Suprvsy
Main Dry Tampers (.as 33:019)
1T.m017
dr. InitSwitch:Supervisory
Suprvsy
Low Air (was 33:020)
17.'m018
Addr.InitSwitch:SupeNiory
Suprvsy
Backilow Tampers (was 33:021)
1 T.M0119
Addr1nitSwitch:Supervisory
Suprvsy
N Stair Standpipe (was 33:022)
1 TM020
AddrInitSwitchrSupervisory
Suprvsy
S Stai r Stand pipe (was 33:023)
17:MO21
Unused
n/a
Not Used
17:mO22
Addr.Init:Switch:Detector Input
Suprvsy
DAS System Point (was 33:013)
17.,mO23
Addr.InitSwitch:Detector Input
Suprvsy
SEPI Trouble (NEW)
1T.mO24
AddrJnitSwitch:Detector Input
Suprvsy
SEP2 Trouble (NEW)
024-030
Unused
n/a
Not Used
17.'m031
Addr.Sys:Relay-Aux-Resettable
n/a
Relay: Elev Phase 1 (was 33.iD04)
17:mO32
Addr.Sys:Relay.Aux-Resettable
n/a
Relay: Elery Phase 2 (was 33:005)
17:mO33
Addr.Sys:Relay.Aux-Resettable
n/a
Relay: Elev Flashing Hat (was 33.,007)
17:mO34
Addr.InitSwitch:Detector Input
Suprvsy
Elevator Shunt Heat (was 33:003)
1 7:m03S
Unused
n/a
Not Used
17:mO36
Addr.Sys:Relay:Aux-Resettable
n/a
Relay: N Gate Rollup Door (was 31024)
17"037
Addr.Sys:Relay:Aux-Resettable
n/a
Relay. S Gate Rollup Door (was 33:026)
17:MO38
Addr.Sys:Relay:Aux-Resettable
n/a
Relay. Damper Relay (was 33:025)
039-050
Unused
n/a
Not Used
17=051
Addr.Init:Switch:Manual Pull
Fire
Ll Main Entry Pull (was 31027)
052-159
Unused
n/a
Not Used
WIRE DESIGNATIONS
=South Buildineg,,
Type
Response
DescriptiorVType
001-009
Unused
n/a
Not U��d
97:010
AddrinitDet:Photo
Fire
LO Elev Landing Smk
97:sOl 1
Addr.Init:Det: Photo
Fire
LO Eiev Machine Rm Sm1k
97:012
Add,lnit:Det:Photo
Fire
LI El- Landing Smk
97:013
Addr.jnit:Det:Ph�b,
Fire
LI FACP Smk
Addr.Init:Det.Photo
Fire
LI Trash (Post Ofc) Smk
:7::0114
7: 0 5
AddrinitDetPhoto
Fire
Ll Trash (Residents) Smk
016-159
Unused
n/a
Not Used
Main - South Building
Address
Dev Type
Response
Descriptionfrype
001-010
Unused
n/a
Not Used
97:mOl 1
AddrinitSwitch:Manual Pull
Fire
LO Sprinkler Rm Pull
97:m012
Addr.InitSwitch:Supewisory
Suprvsy
Sprinkler Rm Low Temp
97:m013
Addr.InitSwitch:Waterflow
Fire
Main Wet Waterflow
97:m014
AddrInitSwitch:Supervisory
Suprvsy
Main Wet Tampers
97.,mOI5
Unused
rVa
Reserved for Sprinkler Point
97.*m016
Unused
rVe
Reserved lor5prinkler Point
SITM017
Unused
rVa
Reserved for Sprinkler Point
97.'m0l8
Un—d
rVa
Reserved for Sprinkler Point
9Tm0l9
Un—d
ala
Reserved for Sprinkler Point
97=020
Addr.Init:Switch:Detector Input
S.P'sy
DAS System Point
97:m021
Addr.Init:Switch:Detector Input
Suprvsy
DAS System Point
97:mO22
AddrinitSwitch:Detector Input
Suprvsy
SEP3 Trouble
97:mC23
AddrinitSwitch:Detector Input
Suprvsy
SEP47rrouble
024-049
Unused
n/a
Not Used
97:m051
AddrinitSwitch:Detector Input
Fire
L2 Elev Landing Heat
97:mOS2
AddrinitSwitch:Detector Input
Fire
L3 Elev Landing Heat
053-059
Unused
n/a
Not Used
97:m06O
Addr.Sys:Relay:Aux-Resettable
n/a
Relay. Dampers
97:m061
Addr.Sys:Relay-Aux-Resettable
n/a
Relay. Elev Phase I
97:m062
Addr.Sys:RelayAux-Resettable
n/a
Relay: Elev Phase 2
97:m063
AddrSys:RelayAux-Resettable
n/a
Relay: Elev Flashing Hat
97:mO64
Addr.1nitSwitch:Detector Input
Suprvsy
Elevator Shunt Heat
97:m065
Addr.InitSwitch:Detector Input
Suprvsy
Elevator Shunt Heat Power
97:m066
Addr.Init:Switch:Manual Pull
Fire
Ll FACP Pull
067-070
Unused
n/a
Not Used
97:m071
Addr.Init:Switch:Detector Input
Suprvsy
L2 Elev Landing ARA Trouble
97:mO72
Add r.InitSwitch:Detector Input
Suprvsy
L3 Elev Landing ARA Trouble
073-159
Unused
h/a
Not Used
WIRE DESIGNAI'ION
SYM DESCRIPTION NUMBER OF CONDUCTORS SIZE
TYPE
COLOR CODE
A FA SBUS LOOP FOUR #16
FPL/FPLP
RED JACKETT—
Dx FA SLC CIRCUIT TWO 6
FPL/FPLP
RED (JACKET)
DI FA INITIATION DEVICE CIRCUIT TWO 116
FPL/FPLP
RED (JACKET)
H FA DOOR HOLDER POWER TWO #16
FPL/FPLP
RED (JACKET)
S FA SIGNAL CIRCUIT TWO #14
FPL/FPLP
RED (JACKET)
Dx NUMBER AFTER CIRCUIT SIGNIFIES CIRCUIT NUMBER
Sx NUMBER AFTER CIRCUIT SIGNIFIES CIRCUIT NUMBER
e IN FRONT OF LE17ER SIGNIFIES CIRCUIT CABLE EXISTING, TO REMAIN
= HASH MARK QUANTITY SIGNIFIES QUANTITY OF DESCRIBED WIRE
ALL WIRE PERMITTED, FURNISHED, AND INSTALLED BY RHEMA ELECTRIC
TYPE OF CIRCUITRY SHALL BE UNIQUELY AND LOGICALLY LABELED. FIRE ALARM WIRING SHALL
MAINTAIN SEPARATION FROM EACH OTHER, AND FROM AC CIRCUITRY.
WIRE DESIGNATION
SYM DESCRIPTION GA/QTY & TYPE
RATH PART#
GENESIS PART #
CA CALL STATION — COMMUNICATION 18GA 1 PAIR SOLID/SHIELDED
RP7500094P
2214
CP CALL STATION — POWER 22GA 2 PAIR SOLID/SHIELDED (PAIR)
RP7500094
1263
e IN FRONT OF LETTER SIGNIFIES CIRCUIT CABLE IS EXISTING IN NATURE — VERIFY
= HASH MARK QUANTITY SIGNIFIES QUANTITY OF DESCRIBED WIRE
ALL WIRE PERMITTED, FURNISHED, AND INSTALLED BY ELECTRICAL CONTRACTOR AS LISTED
ON THIS
PAGE. EACH
TYPE OF CIRCUITRY SHALL BE UNIQUELY AND LOGICALLY LABELED. ANY CHANGES SHALL BE SUBJECT TO APPROVAL
BY BOTH WASHINGTON ALARM, AND ELECTRICAL ENGINEER LISTED ON THIS PAGE.
FIRE ALARM SYSTEM OPERATIONS MATRIX
OUTPUT---0
INPUT
z
<
D
mr'o
<
0
H
Z
E,
zooz�
M
0
H
0z'.'
r-O
z-
t--
0
H
< �!
z
0
z
<
H
d
0
Ew�"
1�p
c<d
ML9
5
< -
n
<
42
�En
I
<
,
z
E=
ftf?
!R a
I
E
E
f.: 0
!R�
<Z
I
<
E
j'5.
oE
f�
05
<Z
!�
Pu-
'0
z
n
n
H
E�S
a: (9
z
6
0
<�
20�.-O
E�
L9
z
< z
1
E
64
61
0
E 'm
0
wz
z
0
U
zaj
'N' o'
z
0
.0
��
U
2 tj
z
,
z
0
6
U
2
ZLU
R ,
z
6
U
tz;
zcj
R" P
0
z
r.
I
P
wt�
�'
z
0
Z.
9 U1
97:m01 1 SOUTH BUILDING SPRINKLER MANUAL PULL STATION ACTIVATION
X
X
X
x
x
x
x
x
97:mO66 SOUTH BUILDING FACP MANUAL PULL STATION ACTIVATION
X
X
X
x
x
x
x
x
x
17:m011 NORTH BUILDING SPRINKLER MANUAL PULL STATION ACTIVATION
X
X
x
x
x
x
x
17:m051 NORTH BUILDING Ll MAIN ENTRY MANUAL PULL STATION ACTIVATION
X
X
X
x
x
x
x
x
x
ALARM: 9T.s0l0 SOUTH BUILDING LO ELEV LANDING
X
X
X
x
x
x
x
x
x
ALARM: 97:011 SOUTH BUILDING LO ELEV MACHINE RM
X
X
X
x
x
x
x
x
x
x
ALARM: 97:012 SOUTH BUILDING Ll ELEV LANDING
X
X
X
x
x
x
x
x
x
ALARM: 97:s01 3 SOUTH BUILDING FACP
X
X
X
x
x
x
x
x
ALARM: 97:014 SOUTH BUILDING LI TRASH
X
X
X
x
x
x
x
x
ALARM: 97:015 SOUTH BUILDING Ll TRASH
X
X
X
x
x
x
x
x
ALARM: 97'.m051 SOUTH BUILDING L2 ELEV LANDING
x
x
x
x
x
x
ALARM: 97.'m052 SOUTH BUILDING L3 ELEV LANDING
X
X
x
x
x
x
ALARM: 97:mO64 SOUTH BUILDING LO ELEV SHUNT HEAT
—x
x
ALARM: 97:m06S SOUTH BUILDING LO ELEV SHUNT HEAT POWER
x
x
ALARM: 17:010 NORTH BUILDING LO ELEV LANDING
X
X
X
x
x
x
x
x
x
ALARM: 17:011 NORTH BUILDING LO ELEV MACHINE RM
X
X
X
x
—!:—:E
x
x
x
x
ALARM: 17:012 NORTH BUILDING Ll ELEV LANDING
X
X
X
x
x
x
x
x
x
ALARM: 17:s013 NORTH BUILDING L2 ELEV LANDING
X
X
x
x
x
x
x
ALARM: 17:014 NORTH BUILDING L3 ELEV LANDING
X
X
x
x
x
x
x
ALARM: 17:015 NORTH BUILDING L4 ELEV LANDING
X
X
x
x
x
x
x
ALARM: 17:016 NORTH BUILDING ELEVSHAFT
X
X
x
x
x
x
x
ALARM: 17:017 NORTH BUILDING Ll ELEC ROOM
X
X
X
x
x
x
x
ALARM: 17.,mO34 NORTH BUILDING U) ELEV SHUNT HEAT
x
DAS SYSTEM TROUBLE
x
x
ANY AREA OF RESCUE ASSISTANCE POINT TROUBLE
x
x
ALARM: ANY WATERFLOW
x
x
x
-------------
x
x
x
x
x
ANY TAMPER, PrV, LOW PRESSURE, LOW TEMP
----------
x
x
ALARM STATE: SILENCE BUTTON PRESSED
x
x
x
—
—
—
—
—
—
—
—
—
—
x
x
x
ALARM STATE: RESET BUTTON PRESSED
X
x
x
x
x
x
SHORT ON SLC CIRCUIT (NOTE 3)
x
x
COMPONENTIDEVICE TROUBLE, OPEN—El—R—CUrr
SHORT ON NAC CIRCUIT WIRING
T—
x
COMMUNICATION FAIL/TROUBLE
x
AC FAILURE
1 T-
T-x
UFtKAILUNb MAI KLA NUILb
NOTE 1: AC FAIL DELAY 3-6 HOURS
NOTE 2: SYSTEM WILL TRANSMIT IF ABLE
NOTE 3: SLC SHORT WILL INCAPACITATE CIRCUIT
BETWEEN ZONES, PROVIDE ISOLATION
PROTECTION AS REQUIRED BY NFPA72
2016ed 23.6.1
NOTE 4: INCLUDES MULTI CRITERIA
DETECTORS, EXCUJDES SHUNT HEAT
NOTE 5: COORDINATE WITH HVAC CONTRACTOR
GLOBAL/INDIVIDUAL SHUTDOWNS
NOTE 6: SYSTEM MUST REPORT FULL POINT ANNUNCIATION
FOR THIS SECTION TO BE IN COMPLIANCE.
6 +1
WASHINGTON AL RM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHIA1282C3
W1- I FE-VE00,
P: 360.416.8227
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.com
WA Lic: RHEMAEL940DH
Project Title
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Froject —Numbem
18313-1
Issue & Revision Dates
10 OCT, 2018 RO-INITIAL DESIGN
SUBMIITALS
Sheet nne
FIRE ALARM
INFORMATION
RFr,
. EIVIE-D
APR 0 B 21319
OLVE SENCES CTR'
twr 112
Prepared By Nicet Rev—
E. H.merski E. Hornerski
11.113
"'Ires '2/1/21
Sheet Number
FAO.02
SECONDARY POWER
SUPPLY CALCULATION
)K
JOB NAME, EDMONDS MIXED USE
PANEL: FACP=FIRE ALARM
CONTROL PANEL
LOCATION- Ll ELEC ROOM
DATE
PERFORMED- 2018-10-10
QTY.
DEVICE INFO
QUICENT(A)
----------------------------------
ALARM(A)
--------------------------------
1
FACP- SK6820
0.1900
0,2500
3
SBUS- SK5860
0.0200
0,0250
1
SBUS, SK5895
0.0200
0.0250
6
SMK- SKPHOTOW
0.0035
0.0035
4
MOD- SKRELAY
0.0020
0.0020
14
MOD- SKMONITOR/MINIMON
0.0015
0.0015
7
MOD, SKMONITOR2
0,0049
0.0049
4
MOD, SKISO
0.0024
0,0024
1
NAC- SC1
0.0000
0.1400
1
NAC- SC2
0.0000
016990
1
NAC, SC3
0.0000
0.5790
1
NAC- SC4
0.0000
0.0000
1
1/13- SC5
010000
0.0000
1
1/0- SC6
0.0000
0.0000
TOTALS = 0.22135 1.7460
QUICENT LOAD = 0,229 AMPS ALARM LOAD = 1.746 AMPS
QUICENT TIME = 24 HRS. ALARM TIME = 0.25 HRS.
------------------------------- -----------------------------
QUICENT = 5,496 AMPxHRS ALARM = 0,437 AMP*HRS
TOTAL = QUICENT + ALARM
= 5.496 + 0.437
= 5,933 AMPwHRS
DE -RATING FACT13R OF 25% --- > 5.933 w 1.25 = 7.417
w
MINIMUM BATTERY SIZE = 7.42 AMPEREwHOURS W
INSTALL 2 12V ISAH BATTERIES (PART NUMBER- ASLAII16)
SECONDARY POWER
SUPPLY CALCULATION
JOB NAME, EDMONDS MIXED USE
PANEL- FACP=FIRE ALARM
CONTROL PANEL
LOCATIONi Ll ELEC ROOM
DATE
PERFORMED- 2018-10-10
QTY.
DEVICE INFO
QUICENT(A>
ALARM(A)
-------------------------------------------------------------------
I
FCP1- SK5895
0.1900
0.2500
1
SBUS- SK6815
0.0200
0.0250
1
SMK. SKACCLIMATE
0,0012
0.0012
5
SMK- SKPHQTOW
0.0015
0.0360
6
MOD, SKRELAY
0.0020
0.0020
15
MOD, SKMONITOR/MINIMON
0.0015
0,0015
1
1/0- SC7
0.0000
0.8180
1
1/0, SCS
0.0000
0.9290
1
1/0- SC9
0.0000
0.4450
1
1/0- SCIO
0.0000
1.5000
1
1/0- SC11
0.0000
1.5000
1
1/0- SC12
0.0000
1.5000
TOTALS = 0.2285 1.7460
QUICENT LOAD = 0.229 AMPS ALARM LOAD = 1.746 AMPS
QUICENT TIME = 24 HRS. ALARM TIME = 0.25 HRS.
------------------------------- -----------------------------
QUICENT = 5.496 AMP*HRS ALARM = 0.437 AMPwHRS
TOTAL = QUICENT + ALARM
= 5.496 + 0.437
= 5.933 AMPwHRS
DE -RATING FACTOR OF 25% --- > 5.933 1.25 = 7.417
)K w
w MINIMUM BATTERY SIZE 7.42 AMPEREwHOURS w
INSTALL 2 12V IBAH BATTERIES (PART NUMBER, ASLAII16)
SECONDARY POWER SUPPLY
CALCULATION
SECONDARY POWER SUPPLY
CALCULATION
?K
JOB NAME, EDMONDS MIXED USE
JOB NAME- EDMONDS MIXED USE
PANEL: SEP1=SIGNAL EXTENDER
PANEL 3
PANEL, SEP4=SIGNAL EXTENDER
PANEL 4
LOCATION: Ll ELEC ROOM
LOCATION, LI ELEC ROOM
DATE
PERFORMED- 2018-10-10
DATE
PERFORMED, 2018-10-10
QTY,
DEVICE INFO
QUICENT(A)
ALARM(A)
QTY.
-------------------------------------------------------------------
DEVICE INFO
QUICENT(A)
ALARM(A)
-------------------------------------------------------------------
1
SEP3, PSN106
0. 0750
0. 0750
1
SEP4, PSN106
0. 0750
0. 0750
1
NAC1, SC25
0. 0000
0. 9850
1
NACI- SC31
0. 0000
0. 9850
1
NAC2, SC26
0.0000
1. 1230
1
NACR, SC32
0. 0000
1. 1230
1
NAC31 SC27
0.0000
1. 3990
1
NAC3- SC33
0. 0000
1. 3990
1
NAC41 SC28
0. 0000
1. 2610
1
NAC4, SC34
0. 0000
0. 5220
1
NAC5 SC29
0. 0000
0. 0000
1
NAC5- SC35
0. 0000
0. 9540
1
NAC6, SC30
0. 0000
0. 0000
1
NAC6- SC36
0. 0000
0. 7930
TOTALS = 0.0400 4,8430
QUICENT LOAD 0.075 AMPS ALARM LOAD 4.843 AMPS
QUICENT TIME 24 HRS. ALARM TIME 0.25 HRS.
------------------------------- -----------------------------
QUICENT = 1.800 AMP*HRS ALARM = 1,211 AMP?mHRS
TOTAL = QUICENT + ALARM
= 1,800 + 0.901
= 2,701 AMP*HRS
DE -RATING FACTOR OF 25Y --- > 2.701 IN 1.25 = 3.377
W MINIMUM BATTERY SIZE 3.38 AMPEREwHOURS w
CALCULATED UNDER FUTURE POTENTIAL FULL LOAD
INSTALL 2 12V 7AH BATTERIES (PART NUMBER, SLA1075)
TOTALS = 0.04CO 5,8510
QUICENT LOAD 0.075 AMPS ALARM LOAD 5.851 AMPS
QUICENT TIME 24 HRS. ALARM TIME 0.25 HRS.
------------------------------- -----------------------------
QUICENT = 1.800 AMP)NHRS ALARM = 1.463 AMP3KHRS
TOTAL = QUICENT + ALARM
= 1,800 + 1.463
= 3.263 AMP*HRS
DE -RATING FACTOR OF 25% --- > 3,263 1.25 = 4,079
MINIMUM BATTERY SIZE 4.08 AMPERE�HOURS
INSTALL 2 12V 7AH BATTERIES (PART NUMBER: SLA1075)
u
95
u
0
z
o
z
o
15
u
z
<
o
z
a
0
wo
z
Cs 6
2 (a,
0
r
1z
z
o
z
o 6
ej
�u
0
9
1z
z
o
z
o 6
ul
I
C)
1
-t�
z
o
1-
z ';
o
mo
C)
r
1z
z
c'
z
-
o '5
2 u
-
C)
z
= 9
C) 6
2 @'
t;
-
.
o
0 1
.
z
0
-
.
o
01
o
z
ru-
0
!z
-
.
C) z
o I
z
ru-
0
!Z
-
.
o
o
o N
o
w
.
z 0
5
cs
z
C,
b
6
0
1z
z
lo
o
@j
c,
z w
c)
a
- q
� z
ox
b
z
-0
z
�o
o
8
>
-t ,
z
d
>
SC 1
FACP
S ELEC
S BLDGENTRY/ELEV
4.7K
320
14
2.823
1
0
1
0
0
0
0
0
0
0
0
3
0
0
0.626
1.8117
1.131
19.27
SC 2
FACP
S ELEC
S BUDGW RETAIL
4.7K
40
14
2.823
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0.235
0.226
0.053
20.35
SC 3
FACP
S ELEC
S BLDG SE RETAIL
4.7K
100
14
2.823
0
0
0
a
1
0
0
0
0
0
0
0
0
0
0.235
0.565
0.133
20.27
SC 4
FACP
S ELEC
S BLDG EUEC/TRASH
4.7K
100
14
2.823
0
0
0
0
0
0
1
1
0
0
1
0
0
0
0.254
0.565
0.143
20.26
SC 5
FACP
S ELEC
SEP 3/4TRIGGER
4.7K
10
14
2.823
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.056
0.000
20.40
SC 6
FACP
S ELEC
UNUSED
N/A
0
N/A
2.823
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
0.000
20.40
Sc 7
FCP1
IN ELEC
5 BLDG LO WEST
4.7K
365
14
2.823
1
0
0
1
0
1
0
0
0
2
0
0
0
0
0.818
2.061
1.686
18.71
SC 8
FCP1
N ELEC
S BLDG LO EAST
4.7K
280
14
2.823
0
1
0
0
0
0
0
0
0
3
0
0
0
0
0.929
1.581
1.469
18.93
SC 9
FCP1
N ELEC
S BLDG Ll PARKING
4.7K
160
14
2.823
0
0
0
0
0
0
0
0
1
1
0
0
0
0
0.445
0.903
0.402
20.00
SC 10
FCP1
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
MOOD
0.000
20.40
SIC 11
FCP1
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
MOOD
0.000
20.40
SIC 12
FCP1
IN ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
MOOD
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
0.000
20.40
SC 13
SEPI
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
MODO
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
0.000
20.40
SIC 14
SEPI
N ELEC
RECONFIGURE EXISTING
4,7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0,000
0.000
20.40
SC 15
SEPI
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
MODD
0.000
0.000
20.40
SC 16
SEPI
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
MOOD
0.000
20.40
SC 17
SEPI
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
MOOD
0.000
20.40
SC 18
SEPI
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
MOOD
0.000
20.40
SC 19
SEP2
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
0.000
20.40
SC 20
SEP2
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
MOOD
0.000
20.40
SC 21
SEP2
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
0.000
20.40
SC 22
SEP2
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
MOOD
20.40
SC 23
SEP2
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
a
0
0
MOOD
0.000
0.000
20.40
SIC 24
SEP2
N ELEC
RECONFIGURE EXISTING
4.7K
0
N/A
0.000
0
0
0
0
0
0
0
0
0
0
0
0
0
MOOD
0.000
0.000
20.40
SIC 25
SEP3
S ELEC
L2NW
4.7K
270
14
2.823
0
0
0
0
0
0
0
0
0
0
0
1
0
6
0.995
L524
1.502
18.90
SC 26
SEP3
S ELEC
L2 SW
4.7K
310
14
2.823
0
0
0
0
0
0
0
0
0
0
0
1
0
7
1.123
1.750
1.966
18.43
SC 27
SEP3
S ELEC
L2 SE
4.7K
340
14
2.823
0
0
0
0
0
0
0
0
0
0
0
1
0
9
L399
1.920
2.686
17.71
SIC 28
SEP3
S ELEC
L2 NE
4.7K
350
14
2.823
0
0
0
0
0
0
0
0
0
0
0
1
0
8
1.261
1.976
2.492
17.91
SC 29
SEP3
S ELEC
UNUSED
N/A
0
N/A
2.823
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.000
0.000
0.000
20.40
SC 30
SEP3
5 ELEC
UNUSED
N/A
0
N/A
2.823
0
0
0
0
0
0
0
0
0
0
0
0
0
0
MOOD
0.000
0.000
20.40
SC 31
SEP4
S ELEC
L3 NW
4.7K
300
14
2.823
0
0
0
0
0
0
0
0
0
0
0
,
0
6
0.985
1.694
1.668
18,73
SC 32
SEP4
S ELEC
L3SW
4.7K
340
14
2.823
0
0
0
0
0
0
0
0
0
0
0
1
0
7
1.123
1.920
2.156
18.24
SC 33
SEP4
S ELEC
L3 SE
4.7K
370
14
2.823
0
0
0
0
0
0
0
0
0
0
0
1
0
9
1.399
2.089
2.923
17.48
SC 34
SEP4
S ELEC
L3 308 & 309
4.7K
275
14
2.823
0
0
0
0
0
0
0
0
0
0
0
0
0
4
0.552
L553
0.857
19.54
SC 35
SEP4
S ELEC
L3 311
4.7K
295
14
2.823
0
0
0
0
0
3
0
0
0
0
0
0
3
0
0.954
1-666
--
18-11,
SC 36
SEP4
S ELEC
L3 310
4.7K
260
14
2.823
0
0
0
.0
0
2
0
.0
.0
.0
0
1
2
.0
.0.793,
1.468131.164
19.24
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHIA1282C3
WE 'Ek"AW-5w5i
P: 360.416.8227
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.com
WA Lic: RHEMAEL940DH
Project Title
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, P8020
Project Numbers
18313-1
Issue & Re�islon Dates
10 OCT. 2018 RO-INMAL DESIGN
SUBMITrALS
Sheet Title
FIRE ALARM &
ARA SYSTEM
INFORMATION
nECEWFED
APR 0 8 2019
DEVELOPMENI SERVIGES CTR
CITY OF EDMONDS
Prepared By Nicet Revii-
e . H.m-ki P. Nguye
1 18193 139398
Exp 12/l/21_ Expires 1/ 1 /21
Sheet Number
FAO.03
FIRE ALARM - SYSTEM NOTES
O-WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL
AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE
RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM
INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS.
1 -CONNECT TO ALL SPRINKLER ROOM POINTS. LOCATE
APPROPRIATE FIRE WATCH & PULL STATION SIGNAGE ADJACENT.
SEE ALSO FA9.01
2-FIELD LOCATE A DUAL INPUT MONITOR MODULE ADJACENT TO
DAS (BY OTHERS) TO MONITOR INACCORDANCE WITH IFC
3-AVOID INSTALLATION OF COM BUILDING SYSTEM EIN
16'-2"
FUTURE RETAIL SPACES. 7"
44
�A/
18, 1 F
D, E 16-7 17-6f
'G�
17-2�'
H
23' 1.
PHASE
AREAOFWORK' '4-
PHASE I
-b-DaSTING TO REMAIN
UNLESS NOTED
�SPRINKLIER
RISER ROOM
--,BD
0,3
F ie�
::�N: :.011
A A
—SBus0I
IV— — — — —
—
PARKING
_�106
S7
S
S -4
62
D2
D2
177C
I
SBUS,DATA-q.
HOMERUN TO
SEE -.0,
P
LOBE)
PARKING
B104
B106
THIS AREA
UNEXCAVATED
NT
I
POWER H
7:1011 s
SHUNTH
S
P. 97-064
:97.
LASH H
PHASE2.
T. 97.-nr063
97:.062
41
PHASE 1:
97=061
97:,010(;
L
S7
4
D2
I
UP
47,
I Ch,
,SC
S_
C7
2
STAIR
S7
D2
.1 5CD
L,L_._j
Lj
—1i
z.
12
STORAGE
TRANS,
ABOVE
X
;.T i T.
�Q
=z;zm��a�z:
SB S7
SC7, SC8
HOMIRUI
SO S7
E)GONG CIRCUIT TO REMAIN AS IS
Eg--,--4REARRANGE SOURCES AS REQUIRED TO
SC
-2
�TO
S, FCP1 SEE
MAINTAIN STROBE SYNC WITH NEW CIRCUITS
_40 -
�8, �C, �D, �E, �F, �G,
1111�911111111111
PROJECT
NORTH
0 LOWER PARKING PLAN L:1'�
_1\ +1,A,
I A
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHIA1282C3
P: 360.416.8227
628 S Spruce St
Burling on, 3
www.rhemaelectric.com
WA Lic: RHEMAEL940DH
Project ritle
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Project Numbers
18313-1
Issue & ReAsion Dates
10 OCL 2018 R04NITIAL DESIGN
SUBMI]TALS
Shi TO _.
FIRE ALARM &
ARA SYSTEM
DRAWING
RECE5VED
APR 0 8 2919
DEVELOPMENT SERVICES OTH.
CRY OF EDMONDS
Prepared By Nicet Re�ii:�
I ... P. Nguye
118193 139398
E:xp 12/1/21 Expires 1/1/21
Sheet Number
FA4.00
FIRE ALARM & ARA:
SCALE: 1/8" = 1'
FIRE ALARM — SYSTEM NOTES
O-WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL
AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE
RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM
INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS.
1 -CONNECT TO ALL SPRINKLER ROOM POINTS. LOCATE
APPROPRIATE FIRE WATCH & PULL STATION SIGNAGE ADJACENT.
SEE ALSO FA9.01
2-FIELD LOCATE A DUAL INPUT MONITOR MODULE ADJACENT TO
L�:— DAS (BY OTHERS) TO MONITOR IWACCORDANCE WITH IFC C
I I
6N SYSTEM IN
I I. ' F
D 1 E
3-AVOID INSTALLATION OF COM BUILDING
FUTURE RETAIL SPACES. a 16-7 1 l'-7"
21 18, 16-7
-of �511 2
4-PROVIDE ISOLATION MODULES A
R�-
JACENT TO FACP AS
REQUIRED TO PROTECT SLC CIRCU
PER NFPA 72 23.6.1
5-LOCATE MONITOR MODULES: HPIANREEACPHTNEW,AND
EXISTING SIGNAL EXTENDER PANEL! 11
11 111 11 11 111 U III
7-4
- - - - - - -- -
IF - - - - - - -
11 L _11 11 11 111
- - - - - -
-7
n n
a
24 lull= 4
-
- — - — -
W RETAIL
F-106-1
ANtf FUTURE WORK IN THIS
S CE BE C MPLETIED
NTOR
F fl
SEPOA.TE
CONTRACTIPERMIT
C cl
' ' i- I- -
# �'i FAA I H=L=f
flity
A -�SBUS HOtIERUN
,�O FACP
It U0
It It LOB RE
kk 03
�1' I I in I H
ANI FUTURE -.RK N TH.
SPACE To E Co., EYED
13 UNDER SEPARA E
CONTRACTIPE IT
U5 — 4
03 -01
/6,—
L
S HOM RUN
C11
TO FACP
I
DATA-97 JOMERUN
TO FACP
G
— - W -
17'- H IT-11 'E�A'
04i, 23-k�--
AR , 2 PHASE 1
EA.=R E)aMNG TO REMAIN
UNLESS NOTED
S -3
75CD
ICI DATA-97
...ERUN To
ACP
SC4-
15 �CD2
PROJECT
FIRE ALARM: LEVEL 1 PLAN NORTH
SCALE: 1/8" = 1' (9
i +1
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHIAI282C3
P: 360.416.8227
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.com
WA Lic: RHEMAEL940DH
Project Me
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Project Numbers
T8313-1
Issue & Revisim Dates
10 OCT. 2018 RO-IN11RAL DESIGN
SUBMITTALS
Rheef �Tifle
FIRE ALARM &
ARA SYSTEM
DRAWING
RECEIVEm
APR 08 2gig
DEVELOPMENT SERVICES CTR
CITY OF EDMONDS
Prepared By ITIC-01115--ew
E P. Nguye
118193 139398
Exp 1 1/21 E�pires 111/21
Sheet Number
FA4.01
a-,--
FIRE ALARM - SYSTEM NOTES
O-WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL
AND/Olk FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE
RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM
INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS.
1 -CONNECT TO ALL SPRINKLER ROOM POINTS. LOCATE
APPROPRIATE FIRE WATCH & PULL STATION SIGNAGE ADJACENT.
SEE ALSO FA9.01
2-FIELD LOCATE A DUAL INPUT MONITOR MODULE ADJACENT TO
DAS (BY OTHERS) TO MONITOR INAqCORDANCE WITH IFC C"�
I j�FIN
3-AVOID INSTALLATION OF COM� N �BUILDING SYSTEM ' a -
FUTURE RETAIL SPACES. 16'-2" 1 V-7'
/ � 4-�l
2 - -
30
4
L5O
I
F,
'E� 17- IT-21 'H, 1 1
21'- 1 JT-1021'
2' If 23-8�'
PROJECT
FIRE ALARM: LEVEL 2 PLAN NORTH
SCALE: 1/8" = 1'
PHASE -PHASE 1
FVVORK� � EMSTING TO REMAIN
UNLESS NOTED
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lie: WASHIA1282C3
P: 360.416.8227
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.com
WA Lie: RHEMAEL94ODH
Project Title
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Project Numbers
18313-1
Issue & Revision Dates
10 OCT, 2018 RO-INMAL DESIGN
SUBMITTALS
Sheet —Title
FIRE ALARM &
ARA SYSTEM
DRAWING
RECEIVED,
APR 08 2019
DEVELOPMENT SERVICES CTFL
C47Y OF EDMONDS
Prepared By —N,—..7 —Revl�
F Hamorsid P. Nguyen
118193 139398
Exp 12/1/21 &pIres 1/1/21
Sheet Number
FA4.02
FIRE ALARM - SYSTEM NOTES
O-WIRING IS SHOWN POINT TO POINT ONLY. ELECTRICAL
AND/OR FIRE ALARM CONTRACTOR SHALL ANNOTATE ALL WIRE
RUNS, CONDUIT SIZES, RISER LOCATIONS, AND OTHER SYSTEM
INFORMATION TO FACILITATE ACCURATE AS BUILT DRAWINGS.
1-CONNECT TO ALL SPRINKLER ROOM POINTS. LOCATE
APPROPRIATE FIRE WATCH & PULL STATION SIGNAGE ADJACENT.
SEE ALSO FA9.01
2-FIELD LOCATE A DUAL INPUT MONITOR MODULE ADJACENT TO
DAS (BY OTHERS) TO MONITOR IN.A CORDANCE WITH IFC.-
3-AVOID INSTALLATION OF BUILDIN YSTEM ja_� IN
FUTURE RETAIL SPACES. 1F25
�,44
5
66
I I
C 21'- D')J 18' 1
17- G) 17' 1 H)
7-
PROJECT
FIRE ALARM: LEVEL 3 PLAN NORTH
SCALE: 1/8" = 11' 0�
/ E A�
N
i +1
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHlA1282C3
P: 360.416.822�
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.com
WA Lic: RHEMAEL940DH
Project 71tle
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Project Numbers
18313-1
Issue & ReAston Dates
10 OCr, 2DIS RO-INITIAL DESIGN
SUBMITTALS
Theet -rifle
FIRE ALARM &
ARA SYSTEM
DRAWING
RECEIVEO
APR 0 8 2019
DEVELOPMENr SERIAGES CTR.
CIIY OF EDMONDS
Nepare.�y Nicet ReView
P.Nguyen
118193 139398
Exp 12 1/21 Expires 1/1/21
Sheet Number
FA4.03
LEVEL
LEVEL
DM
LEVEL
LEVEL 3
LEVEL 2
LEVEL 1
WASHINGTON ALARM
P: 360.733.1330
1420 King St, Ste E
Bellingham, WA, 98229
www.washingtonalarm.com
WA Lic: WASHIA1282C3
P: 360.416.8227
628 S Spruce St
Burlington, WA, 98223
www.rhemaelectric.corn
WA Lic: RHEMAEL940DH
Project Title
EDMONDS MIXED USE
PHASE 11
201 MAIN ST
EDMONDS, WA, 98020
Project Numbers
18313-1
Issue & Revision Dates
10 OCT, 2018 - ROANITAL DESIGN
SUBMITTALS
�m SYSTW
Sheet Title
FIRE ALARM &
AW.
ARA SYSTEM
INFORMATION
RECEIVED
APR 0 8 2013
DL)fEUOFMENTSEhv,GESCTR
CITY OF EDMONDS
Prepared By N[Cet Revlev�
LEVEL 1 E. H.merski P. Nguyen
118193 139398
Exp 12/1/21 Expires 1/1/21
Sheet Number
FA9.01