BLD20180821 (2)of ED 4f
I TY OF EDMONDS
121 5TH AVENUE NORTH - EDMONDS, WA 98020
PHONE: (425) 771-0220 - FAX: (425) 771-0221
STATUS: ISSUED 07/02/2018 Pennit#: BLD20180821
BUILDING PERMIT
Expiration Date: 0 1 /02/2 0 19 1 _P ect Address: 71 EST MAINST., EDMONDS
L roi
Parcel No: 00454800201901
FERRY TERMINAL HERMANSON COMPANY HERMANSON COMPANY
C/O ON THE DOCK SERVER ROOM C/O KIMBERLY LANGE C/O KIMBERLY LANGE
PO BOX 330310 1221 2ND AVE N 1221 2ND AVE N
SEATTLE, WA 98133 KENT, WA 98032 KENT, WA 98032
(206) 575-9700 (206) 575-9700
LICENSE 4� HERMACLO05BJ EXP:08/25/2018
JOB DESCRIPTION
REPLACEEXISTING SPLIT AC WITHNEW
VALUATION: $0
PERMIT TYPE: Commercial
PERMIT GROUP: 40 - Mechanical
GRADING: N CYDS: 0
TYPE OF CONSTRUCTION -
RETAINING WALL ROCKERY:
OCCUPANT GROUP:
OCCUPANT LOAD.
FENCE: 0 X 0 FT-)
CODE: 2015
IOTHER: ------- OTHER DESC:
ZONE:
INUMBER OF STORIES: 0
1 VESTED DATE:
INUMBER OF DWELLING UNIT & 0
ILOT R�
EXISTING AREA
BASEMENT: 0 1 ST FLOOR: 0 2ND FLOOR: 0
PROPOSEDARFA
S
ASEMENT: 0 1 ST FLOOR: 0 2ND FLOOR: 0
3RD FLOOR: 0 GARAGE- 0 DECK: 0 OTHER: 0
E3RD FLOOR: 0 GARAGE: 0 DECK� 0 OTHER: 0
BEDROOMS: 0 BATHROOMS: 0
IBEDROOMS: 0 BATHROOMS: 0
FRONTSEIFBACK SIDESEIFBACK REARSETBACK
IREQUIRED: PROPOSED: JITQUIRED: PROPOSED: IREQUIRED: PROPOSED:
1HEIGHT ALLOWED:O PROPOSED:O IREQUIRED: PROPOSED
ISETBACK NOTES
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY, NO
PERSON VALL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION
INSURANCE AND RCW 18:27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR, IS/H_�K DEPUTY AND ALL FEES ARE PAID.
Siqnatde v Pri Date- RP1PhqPr1 N f\ n.t.
L_�� �'yyl / -
ATTENTION
ITIS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUC71JRE UNTIL A FINAL TNSPEC"nON HAS BEEN MADE AND APPROVAL OR A CFR'HFICATE OF
OCCUPANCY HAS BEEN GRANTED. UBC] 09/ IBCI 10/ IRCI 10.
0
= FIRE = APPLICANT = ASSESSOR �6 CITY
STATUS: ISSUED
BLD20180821
• Final approval on a project or final occupancy approval must be granted by the Building Official prior to use or occupancy of
the building or structure. Check the job card for all required City inspections including final project approval and final
occupancy inspections.
• Any request for alternate design, modification, variance or other administrative deviation (hereinafter "variance") from
adopted codes, ordinances or policies must be specifically requested in writing and be called out and identified. Processing
fees for such request shall be established by Council and shall be paid upon submittal and are non-refundable.
• Approval of any plat or plan containing provisions which do not comply with city code and for which a variance has not been
specifically identified, requested and considered by the appropriate city official in accordance with the appropriate provision
of city code or state law does not approve any items not to code specification.
• Sound/Noise originating from temporary construction sites as a result of construction activity are exempt from the noise limits
of ECC Chapter 5.30 only during the hours of 7:00arn to 6:00pm on weekdays and 10:00am and 6:00pm on Saturdays, excluding
Sundays and Federal Holidays. At all other times the noise originating from construction sites/activities must comply with the
noise limits ofChapter 5.30, unless a variance has been granted pursuant to ECC 5.30.120.
• Applicant, on behalf ofhis or her spouse, heirs, assigns, and successors in interests, agrees to indemnify defend and hold
harmless the City of Edmonds, Washington, its officials, employees, and agents from any and all claims for damages of
whatevernature, arising directly or indirectly fromthe issuance for this permit. Issuance ofthis permit shall not be deemed to
modify, waive orreduce any requirements of any City ordinance nor limit in any way the City's ability to enforce any ordinance
provision.
THIS PERMFAUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY
CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDB/VALKS, DRIVBIVAYS, MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION. PERMIT
TIME LIMIT: SEE ECDC 19.00.005(A) (6)
BUILDING
ENGINEERING (425) 771-0220 EXT. 1326
1. Go to: vmw.edmondswa.gov
Building Department Inspections
2. Then: Services
are now scheduled online. If you
FIRE (425) 775-7720
3. Then: Perm its/Development
have difficulties, please call the
4. Then: Online Permit Info
Building Department front desk for
PUBLIC WORKS (425) 771-0235
5: If you don't have one already, create a
assistance during office hours.
login (upper right hand comer)
(425) 771-0220
RECYCLING (425) 275-UOI
6: Schedule your inspection
I I
When calling for an inspection please leave the following information: Permit Number, Job Site Address, Type of Inspection
being requested, Contact Name and Phone Number, Date Preferred, and whether you prefer morning or afternoon.
• B- Refer line Pressure test
• B-M echan ical Rough In
• B-Mechanical Final
,PC. 1 ?,9-
BUILDING PERMIT
APPLICATION
Development Services
Building Division
121 Sth Ave N / Edmonds, WA 98020
425.771.0220
For handouts, submittal requirements, permit status and inspection
scheduling information go to: http://www.edmondswa.gov
JOB SITE INFORMATION/LOCATION: (Where the work is taking place)
JobSiteAddress: 199 Sunset Ave S Edmonds, WA 98020
Parcel: -11�p mo'kv%
Lot /Unit/Suite #: Subdivision:
PROPERTY OWNER:
Name: Washington State Ferries
MailingAddress: 2901 3rd Ave Suite 500
City/State/Zip: Seattle, WA 98121
Phone#: 206-389-8513
Email: colest@wsdot.wa,gov
OWNER INSTALLATION: *If yes, read and sign*
Will work be performed by the property owner? 0 Yes 0 No
I own, reside in, or will reside in the completed structure.
This installation is being made on property that I own which is
not intended for sale, lease, rent, or exchange according to
RCW 18.27.090,
Owner Signature:
APPLICANT / CONTACT INFORMATION:
Name of Applicant: Kimberly Lange
Mailing Address: 1221 2nd Ave N
City/State/Zip: Kent, WA 98032
Phone#: 206-573-2023
E-mail: klange@hermanson.com
GENERAL CONTRACTOR: (if different from applicant)
General Contractor: - Hermanson Company
MailingAddress: 1221 2nd Ave N
City/State/Zip: Kent, WA 98032
Phone#: 206-575-9700
E-mail: k1anae@herrnanscn,com
WA STATE CONTRACTOR L & I # (CCB) & EXPIRATION DATE:
HERMACLOOSBJ
CITY OF EDMONDS BUSINESS LICENSE#: NR-025058
Office Use Only
TYPE OF PERMIT (Provide
El Accessory Structure/
Detached Garage
Details on Page 2)
0 Addition
0 Demolition
E3 Mechanical
El New Single Family/ Duplex
0 Plumbing
• Fire Sprinkler
0 Remodel
• New Commercial/ Mixed Use
0 Re -Roof
El Signs
0 Tank
0 Tenant Improvement
0 Other
Remodel Permit fees are based on:
The value of the work performed. Indicate the value (rounded to
the nearest dollar) of all equipment, materials, labor, overhead,
and the profit for the work indicated on this application.
Valuation:
PROPOSED NEW SQUARE FOOTAGE FOR THIS APPLICATION
Basement sq ft: Finished 0 Unfinished D
1st Floor, sq ft:
2nd Floor, sq ft:
Garage/Carport:, sq ft:
Deck/Covered Porch/Patio:
Other sq ft:
PROJECT DES CRIPTION
Replace Existing Split AC with New
I certify that the information I have provided on this form/application is true,
correct and complete, and that I am the property owner or duly authorized
agent of the property owner to submit a permit application to the City of
Edmonds.
Print Name: _rAAA�
Signature: 11� Zoom-C 0 Date
IKN�
Hermanson
Building Today, DGfining Tomo"ow Hermanson Company LLP tel 206-575-9700
1221 2nd Avenue North fax 206-575-9800
Kent, WA 98032
C) 7-
Project: WSF EDMONDS — SERVER RM
199 SUNSET AVE. S.
EDMONDS, WA. 98020
Date: JUNE-12-2018
copy
RECEOVED
JUN 14 2018
DEVELOPMENT SERVICES
COUNTER
HVAC SYSTEM COOLING/HEATING CALCS
CARRIER HAP VERSION: 5.10
PRMIT SUBMITTAL PACKAGE
Mechanical Construction,
Engineering and Service
www.hermanson.com
Hermanson
Building Today, Defining Tomorrow Hermanson Company LLP tel 206-575-9700
1221 2nd Avenue North fax 206-575-9800
Kent, WA 98032
Project: WSF EDMONDS — SERVER RM
199 SUNSET AVE. S.
EDMONDS, WA. 98020
Date: JUNE-12-2018
Hermanson
Building Today, Defining Tomorrow
HVAC SYSTEM COOLING/HEATING CALCS
CARRIER HAP VERSION: 5.10
ENVELOPE INPUTS
Mechanical Construction,
Engineering and Service
www.hermanson.com
Edmond� WSF SERVER Rm v5 10 Window Constructions 06/12/2018
Hermans&n Company LLP — — 03:08PM
Existing Windows
Window Details:
Detailed Input ................................................... ......... ... .. No
Height. .................................................................................. 4.00 ft
Width- .......... ....... .. ...... - . .................................................. 1.00 ft
Overall U-Value ....... ......................... .............................. 0.450 BTU/(hr-ftl-'F)
Overall Shade Coefficient ............................................. 0.810
Hourly Analysis Program v5.1 0 Page 1 of I
Edrnond� WSF SERVER Rm v5 10 Roof Constructions 06/12/2018
Hermans&n Company LLP — — 03:08PM
Existing roof
Roof Details
Outside Surface Color_ Medium
Absorptivity 0.675
Overall U-Value ... ............. 0.062 BTU/(hr-ft2. 'F)
Roof Lavers Details (inside to Outside)
Layers
Thickness
in
Density
lb/ft3
Specific Ht.
R-Value
hr-ftl-*F /BTU
Weight
lb/ft2
Inside surface resistance
0.000
0.0
0.00
0.68500
0.0
1/2-in gypsum board
0.500
50.0
0.26
0.44803
2.1
R-1 3 batt insulat on
4.000
0.5
0.20
12.82051
0.2
1/2-in plywood
0.500
34.0
0.29
0.62189
1.4
Asphalt sheathing
0.500
70.0
0.35
1.43678
2.9
Outside surface resistance
0.000
0.0
0.00
0.17000
0.0
Totals
5.500
16.18221
6.6
Hourly Analysis Program v5. 10 Page 1 of 1
Edmond� WSF SERVER Rm v5 10 Wall Constructions 06/12/2018
Hermans(3n Company LLP 03:08PM
Existing walls
Wall Details
Outside Surface Color --- - ----- ------ --- - -- - Medium
Absorptivity .................. ............ -- - -- ------------- -- 0.675
Overall U-Value .... - -- ................... .............. 0.104 BTU/(hr-ftl-'F)
Wall Lavers Details finside to Outside)
Layers
Thickness
in
Density
lb/ft'
Specific Ht.
BTU / lb-*F
R-Value
U
Weight
I b1ft2
Inside surface resistance
0.000
0.0
0.00
0.68500
0.0
Gypsum board
0.625
50.0
0.26
0.56022
2.6
R-I 1 batt insulation
2.5001
0.5
0.20
8.01282
0.1
Outside surface resistance
0.000
0.01
0.001
0.333001
0 0
Totals
3.1251
1 9.591041
2..d7
0
Hourly Analysis Program v5.10 Page 1 of 1
Hermanson
Building Today, Defining Tomorrow Hermanson Company LLP te/ 206-575-9700
1221 2nd Avenue North fax 206-575-9800
Kent, WA 98032
Project: WSF EDMONDS — SERVER RM
199 SUNSET AVE. S.
EDMONDS, WA. 98020
Date: JUNE-12-2018
Hermanson
Building Today, Defining Tomorrow
HVAC SYSTEM COOLING/HEATING CALCS
CARRIER HAP VERSION: 5.10
SPACEINPUTS
Mechanical Construction,
Engineering and Service
www.hermanson.com
I Space Input Data
Edmonds WSF SERVER Rm v5 10 06/12/201 E
Hermans&n Company LLP — — 03:05PIV
1- WSF Edmonds SERVER Rm
1. General Details:
Floor Area ................... . .
. ....... -- - ----- --- -- ..... 1".0
ft2
Avg. Ceiling Height. ......................
......... .......... .......... -8.0
ft
Building Weight - .
_ � .................. 70.0
Ib/ft2
1.1. OA Ventilation Requirements:
Space Usage -------------
GENERAL: Break room
CA Requirement I, � ....
........ ................... ............. ........ 5.0
CFM/person
CA Requirement 2 .....
- __ .......................... ...... ...... 0.06
CFM/ft2
Space Usage Defaults
ASHRAE Standard 62.1-2010
2.lnternals:
2.1. Overhead Lighting:
Fixture Type .................. ........... Recessed (Unvented)
Wattage __ .. .... ............................................. 0.96 VV/11-
Ballast Multiplier._ . ----------------_------- ------------- ...... 1.08
Schedule . ...... __ __ ... _ 90.1 Retail Lights/Elec
2.2. Task Lighting:
Wattage 0.00 W/ft2
Schedule... ...... .... None
2.3. Electrical Equipment:
Wattage ., ..... ............ Watts
Schedule ........ . ... ...... _ 90.1 Retail Lights/Elec
3. Walls, Windows, Doors:
2.4. People:
Occupancy_ .......................
- - __- ---- ......... . 1.0
Person
Activity Level ........................
... Seated at Rest
Sensible . __ ..................
_ ---- ----- .......... ...... ....... 230.0
BTU/hr/person
Latent-. . ..... .................
.... . ... _ .,, ...... ...... 120.0
BTU/hr/person
Schedule ........ .. _ ..
............... � 90.1 Retail Occupants
2.5. Miscellaneous Loads:
Sensible._ ................ . .......... . . 0 BTU/hr
Schedule _.. . .......... -- - ----- ...... .. ...... . ........... ... None
Latent. ............. ....... . . ... ..... ............... ...... .. --- 0 BTU/hr
Schedule........................................ .. ..... ....... .... ._ None
Exp.
Wall Gross Area (ft2)
Window I Qty.
Window 2 Qty.
Door 1 Qty.
N
120.0
0
0
0
S
120.0
0
0
0
W
120.0
0
0
0
E
1 120.0
1 0
1 0
1 0 1
3.1. Construction Types for Exposure N
Wall Type .. I '. . 11 . ................ Existing walls
3.2. Construction Types for Exposure S
Wall Type. Existing walls
3.3. Construction Types for Exposure W
Wall Type . ... ..... ..... .. ........ ....... ........... Existing walls
3.4. Construction Types for Exposure E
Wall Type ...... . .......... ... Existing walls
4. Roofs, Skyfights:
Exp.
Roof Gross Area (ft-)
Roof Slope (deg.)
Skylight City.
H
144.0
0
o I
4.1. Construction Types for Exposure H
Roof Type ............. Existing roof
5. Infiltration:
Design Cooling ........... . .. .... 0.00 CFM
Design Heating .... ... ... ... ... ....... 0.50 ACH
Energy Analysis ....... ....... . 0.00 CFM
Infiltration occurs at all hours.
Hourly Analysis Program v5. 10 Page 1 of 2
I Space Input Data
Edmonds WSF SERVER Rm v5 10 06/12/2018
Hermans&n Company LLP 03:05PM
6. Floors:
Type ... .. ...... ..... Floor Above Unconditioned
Space
Floor Area
144.0
ft2
Total Floor U-Value,
0.062
BTU/(hr-ftl-*F)
Unconditioned Space Max Temp.
82.0
OF
Ambient at Space Max Temp . ........
82.0
OF
Unconditioned Space Min Temp . .. . ... ... ..........
........ 24.0
OF
Ambient at Space Min Temp . ...................................
... 24.0
OF
7. Partitions:
(No partition data).
Hourly Analysis Program v5. 10 Page 2 of 2
71\1k
2JP Hermanson
Building Today, Defining Tomorrow Hermanson Company LLP tel 206-575-9700
1221 2nd Avenue North fax 206-575-9800
Kent, WA 98032
Project: WSF EDMONDS — SERVER RM
199 SUNSET AVE. S.
EDMONDS, WA. 98020
Date: JUNE-12-2018
7/31
Hermanson
Building Today, Defining Tomorrow
HVAC SYSTEM COOLING/HEATING CALCS
CARRIER HAP VERSION: 5.10
SYSTEMINPUTS
Mechanical Construction,
Engineering and Service
www.hermanson.com
WSF EDMONDS SERVER RM Input Data
Project Name: Edmonds WSF SERVER Rm_v5_1 0 06/12/2016
Prepared by: Hermanso�_Company LLP 03:06PfV
1. General Details:
Air System Name. - ------- -- - - - -- --- WSF EDMONDS SERVER RM
Equipment Type ---------- ... ....... .. . . .. ......... . Terminal Units
Air System Type .. .......... ------------------ ------------- - . ...... Packaged DX Fan Coil
Numberof zones -------------------------- - - ----------- - - --- ......................... - .............. I
Ventilation .. ... . .. . . .................. ................. ....... Direct Ventilation
2. Dedicated Outdoor Air System Components:
(Dedicated Outdoor Air System not used: no inputs)
3. Zone Components:
Space Assignments:
lZone 1: Zone I
11 - WSF Edmonds SERVER Rm xi
Thermostats and Zone Data:
T-Stat
Cooling T-Stat
Cooling T-Stat
Heating T-Stat
Heating T-Stat
Throttling
Zone
Occ.
Unocc.
Occ.
Unocc.
Range
(*F)
ff)
(*F)
(*F)
(*F)
1
72.0
75.0
70.0
65.0
1.50
Thermostat Schedule ......,.........24/7HVAC Schedule
Unoccupied Cooling is.. Available
Common Terminal Unit Data:
Cooling Coil:
DesignSupply Temp . ..........................................................
... ...... ...... .. — 58.0 'F
CoilBypass Factor ..................................................................
......... ............ 0.100
Cooling Source ...................................................
.... ....... — - __ . Air -Cooled DX
Schedule .............. ...........................................................................
JFMAMJJASOND
Heating Coil:
Design Supply Temp. ...........................................
........... .. . .. ... ...... ____ 95.0 'F
Heating Source .................. ........ . . .......... .....................
__ ....... ..... Electric Resistance'
Schedule.................................... ........................................
.................... JFMAMJJASOND
Fan Control ............ ... - _...
Ventilation Sizing Method
Terminal Units Data:
.............................................. . Fan On
........ . ..... Sum of Space OA Airflows
Air
Distribution
Air
Design
Aii r
Effectiveness
Distribution
Fan
Supply
Zone
Terminal Type
Distribution
Specification
Effectiveness
Minimum Airflow
Fan Performance
Efficiency
Temp.
I
Fan coil
Ceiling supply /
Not Used
-
0.00 CFM/person
0.00 in wg
50%
ceiling return
4. Sizing Data (Computer -Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature ........................................................................................ 58.0 *F
Heating Supply Temperature .............................. ... .... ............................................... 95.0 oF
Hydronic Sizing Specifications:
Chilled Water Delta-T .......................
Hot Water Delta-T ...... ..... ... ..... .......
Safety Factors:
Cooling Sensible ..... ..... .......................................
Cooling Latent .......................................................
Heating.. ....................................... ..... . ...................
..... .................................. I ......... 10.0 *F
.................................. — 20.0 'F
.... . ................... I .................. 1— 0 %
.................................... .......... _0 %
I ............................ - ........... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method .. ... .. "r ........................ - Sum of space airflow rates
Hourly Analysis Program 5.10 Page 1 of 2
WSF EDMONDS SERVER RM Input Data
Project �ame: Edmonds WSF SERVER Rm_v5_10 06/12/2018
Prepared by: Hermansoii-Company LLP 03:06PM
Space Airflow Sizing Method . ... .... 1.11.1 ..... Individual peak space loads
Zone
SupplyAirflow
(CFM)
Zone Htg Unit
(MBH)
Reheat Coil
(MBH)
Ventilation
(CFM)
1227.7
13.6
5. Equipment Data
Terminal Cooling Units - Air -Cooled DX
Estimated
Gross
Capacity
Compressor
Maximum
Design
Cooling
Oversizing
+ OD Fan
ARI
Conventional
Load
OAT
Equipment
Capacity
Factor
Power
Performance
Cutoff OAT
Zone
Sizing
(MBH)
(kW)
Rating
Units.
F)
1
18.9
95.0
Auto -Sized
0
11.000
EER
0.0
Hourly Analysis Program 5.10 Page 2 of 2
Hermanson
Building Today, Defining Tomorrow Hermanson Company LLP tel 206-575-9700
1221 2nd Avenue North fax 206-575-9800
Kent, WA 98032
Project: WSF EDMONDS — SERVER RM
199 SUNSET AVE. S.
EDMONDS, WA. 98020
Date: JUNE-12-2018
Hermanson
Building Today, Defining Tomorrow
HVAC SYSTEM COOLING/HEATING CALCS
CARRIER HAP VERSION: 5.10
SYSTEM OUTPUTS
Mechanical Construction,
Engineering and Service
www-hermanson-com
Dedicated Outdoor Air System (DOAS) Sizing Summary for WSF EDMONDS SERVER RM
Project Name: Edmonds - WSF SERVER Rm—v5-10 06/12/2018
Prepared by: Hermanso� Company LLP 03:06PM
Air System Information
Air System Name . - WSF EDMONDS SERVER RM
Equipment Class ...... . -- ---------- -------------------- - - . TERM
Air System Type ........ -------------------- ---- PKG-FC
Sizing Calculation Information
Calculation Months .... ........ Jan to Dec
Sizing Data ---------- - — Calculated
Number of zones ... ..... — - , A
Floor Area ............ . .............. . ...... -- 144.0 ft2
Location.. .. ... . ...... ....... .. EDMONDS, Washington
Zone CFM Sizing .......... Sum of space airflow rates
Space CFM Sizing ..... .... Individual peak space loads
NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).
Hourly Analysis Program 5.10 Page 1 of 6
Zone Sizing Summary for WSF EDMONDS SERVER RM
Project Name: Edmonds WSF SERVER Rm v5 10 06/12/2018
Prepared by: Hermanso�-Company LLP - - 03:06PM
Air System Information
Air System Name . - WSF EDMONDS SERVER RM
Equipment Class .................................................. TERM
Air System Type -- . .. . ... .. .................. .............. PKG-FC
Sizing Calculation Information
Calculation Months ....... ....... .. - ............. Jan to Dec
Sizing Data .. ........... ................................... . Calculated
Terminal Unit Sizing Data - Cooling
Number of zones - ....................... .... ...... ....... ..... . 1
FloorArea . ....... ................................... __ . , . 144.0 ft2
Location ................ ....................... EDMONDS, Washington
Zone CFM Sizing .................... Sum of space airflow rates
Space CFM Sizing ........... Individual peak space loads
Total
Sens
Coil
Coil
Water
Time
Coil
Coil
Entering
Leaving
Flow
of
Load
Load
DB/WB
DB/WB
@ 10.0 'F
Peak Coil
Zone
Zone Name
(MBH)
(MBH)
(*F)
('F)
(gpm)
Load
CFM/ft2
Zone 1
18.9
18.8
73.0/63.0
58.8/57.8
Aug 1600
8.53
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Heating
Htg Coil
Heating
Coil
Water
Fan
OA Vent
Coil
Ent/Lvg
Flow
Design
Fan
Fan
Design
Load
DB
@20.0 -F
Airflow
Motor
Motor
Airflow
Zone Name
(MBH)
(*F)
(gpm)
(CFM)
(BHP)
(kW)
(CFM)
Zone 1
- 4.2
69.3/72.41
12281
0.0001
0.0001
141
Zone Peak Sensible Loads
Zone
Zone
Zone
Cooling
Time of
Heating
Floor
Sensible
Peak Sensible
Load
Area
Zone Name
(MBH)
Cooling Load
(MBH)
(ft2)
Zone 1
18.6
Jul 1600
3.6
144.0
Space Loads and Airflows
Time of
Cooling
Peak
Air
Heating
Floor
Zone Name
Sensible
Sensible
Flow
Load
Area
Space
— Space Name
Mult.
(MBH)
Load
(CFM)
(MBH)
(ft2)
CFM/ft2
Zone 1
I
— 1- WSF Edmonds SERVER Rm
1
18.6.
Jul 1600,
1228,
3.6
144.0,
8.53
Hourly Analysis Program 5. 10 Page 2 of 6
Ventilation Sizing Summary for WSF EDMONDS SERVER RM
Project Name: Edmonds WSF SERVER Rm v5 10 06/12/2018
Prepared by: HermansorTCompany LLP — — 03:06PM
1. Summary
Ventilation Sizing Method --------------------------- -- ---------------- Sum of Space OA Airflows
2. Space Ventilation Analysis
2.1 Zone: Zone 1
Zone Name / Space Name
Mult.
Floor
Area
(ft2)
Maximum
Occupants
Maximum
Supply Air
(CFM)
Required
Outdoor Air
(CFM/person)
Required
Outdoor Air
(CFM/W)
Required
Outdoor Air
(CFM)
Required
Outdoor Air
(% of supply)
Uncorrected
Outdoor Air
(CFM)
Zone 1
1- WSF Edmonds SERVER Rm
1
144.0
1.0
1227.7
5.00
0.06
00
0.0
13.6
Totals (incl. Space Multipliers)
1227.7.
13.6
Hourly Analysis Program 5.10 Page 3 of 6
Air System Design Load Summary for WSF EDMONDS SERVER RM
Project Name: Edmonds WSF SERVER Rm — v5 — 10 06/12/2018
Prepared by: Hermanso�-Company LLP 03:06PM
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1600
COOLING OA DB WB 85.5 *F 66.8 *F
HEATING DATA AT DES HTG
HEATINGOADB/WB 24.0*F/19.2*F
ZONE LOADS
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Details
Sensible
(BTU/hr)
Latent
(BTU/hr)
Window & Skylight Solar Loads
0 ft2
0
0 ft,
-
-
Wall Transmission
480 ft2
1543
480 ft2
2302
-
Roof Transmission
144 ft2
244
144 ft2
409
-
Window Transmission
0 ft2
0
0 ft2
0
-
Skyliqht Transmission
0 ft2
0
0 ft2
0
-
Doorl-oads
0 ft2
0
0 ft2
0
-
Floor Transmission
144 ft2
71
144 ft2
411
-
Partitions
0 ft2
0
0 ft2
0
Ceiling
0 ft2
0
0 ft2
0
Overhead Lighting
149 W
442
0
0
Task Lighting
0 w
0
0
0
Electric Equipment
5000 W
16056
-
0
0
-
People
1
187
120
0
0
0
Infiltration
-
0
0
-
477
1
Miscellaneous
0
0
-
0
0
Safety Factor
0%/0%
0
0
0%
0
0
>> Total Zone Loads
18543
120
3599
1
Zone Conditioning
-
18586
120
-
3528
1
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
0
0
Plenum Lighting Load
0%
0
0
0
Exhaust Fan Load
0 CFM
0
-
0 CFM
0
-
Ventilation Load
14 CFM
186
-14
14 CFM
674
1
Ventilation Fan Load
0 CFM
0
-
0 CFM
0
-
Space Fan Coil Fans
-
0
-
0
Duct Heat Gain / Loss
0%
0
-
0%
0
-
>> Total System Loads
-
18772
106
4203
2
Terminal Unit Cooling
18772
130
0
0
Terminal Unit Heating
0
-
4203
-
>> Total Conditioning
18772
130
42031
0
Key:
Positive values are cig loads
Negative values are htg loads
Positive values are htg loads
Negative values are cig loads
Hourly Analysis Program 5.10 Page 4 of 6
Space Design Load Summary for WSF EDMONDS SERVER RM
Project Name: Edmonds WSF SERVER Rm v5 10 06/12/2018
Prepared by: Hermansor�Company LLP — — 03:06PM
TABLE 1.1.A. Component
Loads For Space "11- WSF Edmonds SERVER Rim" In Zone "Zone I"
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1600
COOLINGOADB/WB 85.5*F/66.8'F
OCCUPIED T-STAT 72.0 *F
HEATING DATA AT DES HTG
HEATING OA DB / WB 24.0 *F 19.2 *F
OCCUPIED T-STAT 70.0 *F
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
Window & Skylight Solar Loads
0 ft2
0
0 ft2
-
Wall Transmission
480 ft2
1536
480 ft2
230'2
Roof Transmission
144 ft2
270
144 ft2
409
Window Transmission
0 ft2
0
0 ft2
0
Skylight Transmission
0 ft2
0
0 ft2
0
Doorl-oads
0 ft2
0
0 ft,
0
Floor Transmission
144 ft2
71
144 ft2
411
Partitions
0 ft2
0
0 ft2
0
Ceiling
0 ft2
0
0 ft 2
0
Overhead Lighting
149 W
442
0
0
Task Lighting
0 w
0
0
Electric Equipment
5000 W
16056
-
0
0
People
187
120
0
0
0
Infiltration
01
01
-
477
1
Miscellaneous
01
01
-1
01
0
Safety Factor
0%/0%
0
01
0%1
01
0
>> Total Zone Loads
18562
1201
.1
35991
1
TABLE 1.1.13. Envelop Loads For S ace "I- WSF Edmonds SERVER Rm" In Zone "Zone I"
COOLING
COOLING
HEATING
Area
U-Value
Shade
TRANS
SOLAR
TRANS
(W)
(BTU/(hr-ft2. *F))
Coeff.
(BTU/hr)
(BTU/hr)
(BTU/hr)
N EXPOSURE
WALL
120
0.104
230
576
S EXPOSURE
— WALL
120
0.104
364
576
W EXPOSURE
WALL
120
0.104
668
576
E EXPOSURE
— WALL
1201
0.104
275
576
H EXPOSURE
I
=:=
ROOF
1441
0.0621
-i
2701
-1
409
Hourly Analysis Program 5. 10 Page 5 of 6
6 System Psychrometrics for WSF EDMONDS SERVER RM
Project Name: Edmonds WSF SERVER Rm—v5-1 0 06/12/2018
Prepared by: Hermansoii-Company LLP 03:06PM
I July DESIGN COOLING DAY, 1500 7--71
TABLE 1: SYSTEM DATA
Component
Location
Dry -Bulb
Temp
(*F)
Specific
Humidity
(lb/lb)
Airflow
(CFM)
CO2 Level
(ppm)
Sensible
Heat
(BTU/hr)
Latent
Heat
(BTU/hr)
Ventilation Air
Inlet
86.0
0.00978
14
400
187
-30
Vent - Return Mixing
Outlet
0.0
0.00000
0
0
-
-
Ventilation Fan
Outlet
0.0,
0.00000,
01
01
01
-
Zone Air
-1
73.31
0.010251
12281
81
183691
120
Return Plenum
Outlet
0.01
0.010251
12281
81
01
-
Air Density x Heat Capacity x Conversion Factor At sea level = 1. 080; At site altitude = 1. 080 BTUI(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor- At sea level = 4746.6; At site altitude = 4746.6 8 TUI(hr-CFM)
Site Altitude = 0. 0 It
TABLE 2: ZONE DATA
Component
Location
Dry -Bulb
Temp
(*F)
Specific
Humidity
(IbIlb)
Airflow
(CFM)
CO2 Level
(ppm)
Sensible
Heat
(BTU/hr)
Latent
Heat
(BTU/hr)
Zone I ( Cooling
Ventilation Air
14
-
Cooling Coil Inlet
73.51
0.01025
1228
0
-
-
Cooling Coil Outlet
59.5
0.01023
1228
0
18556
126
Heating Coil Inlet
59.5
0,01023
1228
0
-
-
Heating Coil Outlet
59.5
0.01023
1228
0
0
Zone Air
73.3
0.01025
1228
0
18369
Hourly Analysis Program 5. 10 Page 6 of 6
MECHANICAL ABBREVIATIONS
A
AMPS
BC
NTERNATIONAL BUILDING CODE
AC
AIR CONDITIONING
icw
iNDUSTRIAL COLD WATER
ACH
IF
A R CHANGES PER HOUR
ID
INSIDE DIAMETER/DIMENSION
ACT
ACOUSTICAL CEILING TILE
IE
INVERT ELEVATION
AD
ACCESS DOOR
IEER
INTEGRATED ENERGY EFFICIENCY RATIO
ADDI
ADDITIONAL
IMC
INTERNATIONAL MECHANICAL CODE
AFF
ABOVE FINISHED FLOOR
IN
INCHES
AFG
ABOVE FINISHED GRADE
IN ING
INCHES WATER GAUGE
AHU
AIR HANDLING UNIT
IPLV
INTEGRATED PART LOAD VALUE
ALUM
ALUMINUM
KW
KILOWATTS
AMP/AMPS
AMPERAGE
LAT
LEAVING AIR TEMPERATURE
AP
ACCESS PANEL
LB/LBS
POUND/POUNDS
ARCH
ARCHITECT
LF/LIN FT
LINEAL FOOT/FEET
BC
BEADED COLLAR
LPG
LIQUID PROPANE GAS
BDD
BACKDRAFT DAMPER
LIPS
LOW PRESSURE STEAM
BF
BELOW FLOOR
LVG
LEAVING
BHP
BRAKE HORSEPOWER
LWA
SOUND POWER RATING LEVEL (IN DB)
BLDG
BUILDING
LWG
LOW WALL GRILLE
BOD
BOTTOM OF DUCT
LWT
LEAVING WATER TEMPERATURE
BOP
BOTTOM OF PIPE
MAX
MAXIMUM
BOT
BOTTOM
MAU
MAKE UP AIR UNIT
BS
BIRD SCREEN / BLACK STEEL
MBH
1000 BRITISH THERMAL UNITS/HOUR
BTU
BRITISH THERMAL UNIT
MCA
MINIMUM CIRCUIT AMPACITY
BTUH
BRITISH THERMAL UNITS PER HOUR
MD
MOTORIZED DAMPER
CAP
CAPACITY
MFR
MANUFACTURER
CBD
CALIBRATED BALANCING DAMPER
MISC
MISCELLANEOUS
cc
CONTROLS CONTRACTOR
MIN
MINIMUM/MINUTE
CD
CEILING DIFFUSER/CONDENSATE DRAIN
MPS
MEDIUM PRESSURE STEAM
CDWR
CONDENSER WATER RETURN
MT
MOUNT
COWS
CONDENSER WATER SUPPLY
MTD
MOUNTED
CFM
CUBIC FEET PER MINUTE
MUW
MAKE-UP WATER
CHWR
CHILLED WATER RETURN
NA
NOT APPLICABLE
CHINS
CHILLED WATER SUPPLY
NC
NORMALLY CLOSED/NOISE CRITERIA
CLG
CEILING
NG/NGAS
NATURAL GAS
COIL
COLUMN
NIC
NOT IN CONTRACT
CONC
CONCRETE
NO
NORMALLY OPEN/NUMBER
COND
CONDENSATE
NPW
NON -POTABLE WATER
CONN
CONNECT/CONNECTED/CONNECTION
N-R
NON-RESIDENTIAL
CONT
CONTINUOUS/CONTINUATION
OA/OSA
OUTSIDE AIR
CONTR
CONTRACTOR
OBD
OPPOSED BLADE DAMPER
COORD
COORDINATE
OD
OUTSIDE DIAMETER/DIMENSION
COP
COEFFICIENT OF PERFORMANCE
PCF
POUNDS PER CUBIC FOOT
CT
COOLING TOWER
PD
PRESSURE DROP
CU
CUBIC/CONDENSER UNIT
PH
PHASE
cW
DOMESTIC COLD WATER/CONDENSER WATER
POC
POINT OF CONNECTION
DB
DUCTBOARD/DRY BULB/DECIBEL
P/PRESS
PRESSURE
DOC
DIRECT DIGITAL CONTROL
PSI
POUNDS PER SQUARE INCH
DEFL
DEFLECTION
PSIG
POUNDS PER SQUARE INCH GAUGE
DEG
DEGREE/DEGREES
QTY
QUANTITY
DIA
DIAMETER
R
RETURN GRILLE/RELOCATED/RETURN
DMPR
DAMPER
RA
RETURN AIR
ON
DOWN
RD/RND
ROUND
DOAS
DEDICATED OUTSIDE AIR SYSTEM
REF
REFERENCE
DWG
DRAWING
REQ
REQUIRED
EXH
EXHAUST
RESID
RESIDENTIAL
EA
EACH
RF
RELIEF
EAT
ENTERING AIR TEMPERATURE
RG
REFRIGERANT DISCHARGE GAS
EC
EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR
RL
REFRIGERANT LIQUID
EER
ENERGY EFFICIENT RATING
RPM
REVOLUTIONS PER MINUTE
EF
EXHAUST FAN
IRS
REFRIGERANT SUCTION
EFF
EFFICIENCY
s
SUPPLY
EL
ELEVATION
SA
SUPPLY AIR
ELEC/ELECT ELECTRICAL/ELECTRIC
SAT
SATURATION/SUPPLY AIR TEMPERATURE
EMCS
ENERGY MANAGEMENT CONTROL SYSTEM
SD
SMOKE DETECTOR
ENT
ENTERING
S/D
SUP & DRIVE CONNECTION
EQUIP
EQUIPMENT
S-C
SEATTLE - CODE
ESP
EXTERNAL STATIC PRESSURE
SEER
SEASONAL ENERGY EFFICIENCY RATNG
EWT
ENTERING WATER TEMPERATURE
SENS
SENSIBLE
EXIST/(E)
EXISTING
SL
SOUND LINED
EXH
EXHAUST
SM
SHEETMETAL
F
FAHRENHEIT
SPEC
SPECIFICATION
FAC
FIRE ALARM CONTRACTOR
so
SCREENED OPENING
FD
FIRE DAMPER
SOG
SLAB ON GRADE
FDC
FIRE DEPARTMENT CONNECTION
SP
STATIC PRESSURE
FF
FINISHED FLOOR
SF
SQUARE FEET
FIC
FURNISHED AND INSTALLED BY CONTRACTOR
SS
STAINLESS STEEL
FIO
FURNISHED AND INSTALLED BY OWNER
STRUC
STRUCTURAL
FLA
FULL LOAD AMPS
TA
TRANSFER AIR
FLEX
FLEXIBLE
TEMP
TEMPERATURE/TEMPORARY
FLR
FLOOR
TBD
TO BE DETERMINED
FOB
FLAT ON BOTTOM
TOD
TOP OF DUCT
FDIC
FURNISHED BY OTHERS,
TOS
TOP OF STEEL/TOP OF SLAB
INSTALLED BY CONTRACTOR
TOT
TOTAL
FOS
FLAT ON SIDE
TSP
TOTAL STATIC PRESSURE
FOT
FLAT ON TOP
TSTAT
THERMOSTAT
FP
FIRE PROTECTION
TYP
TYPICAL
FPM
FEET PER MINUTE
UH
UNIT HEATER
FSD
FIRE/SMOKE DAMPER
UNO
UNLESS NOTED OTHERWISE
FT
FOOT/FEET
V
VOLT
FUT
FUTURE
VD
VOLUME DAMPER
FV
FACE VELOCITY
VEL
VELOCITY
G
GRILLE
VERT
VERTICAL
CA
GALIGE/GALLON
VFD
VARIABLE FREQUENCY DRIVE
GALV
GALVANIZED
VOL
VOLUME
GC
GENERAL CONTRACTOR
W
WRAPPED DUCT
GPM
GALLONS PER MINUTE
WEI
WET BULB
GIRD
GRILLE/REGISTER/DIFFUSER
WG
WATER GAUGE
GWB
GYPSUM WALL BOARD
W/
WITH
HD
HEAD
W/o
WITHOUT
HORIZ
HORIZONTAL
W/SF
WATTS PER SQUARE FOOT
HP
HORSEPOWER
WSEC
WASHINGTON STATE ENERGY CODE
HR
HOUR
HSPF
HEATING SEASONAL PERFORMANCE FACTOR
HT
HEIGHT
HWTG
HIGH WALL TRANSFER GRILLE
HVIR
HOT WATER RETURN
HWS
HOT WATER SUPPLY
HX
HEAT EXCHANGER
HZ
HERTZ
MECHANICAL LEGEND
J10"XIO'N
RECT SUPPLY AIR DUCT
UP/TOWARD
t1o'X10""
RECT SUPPLY AIR DUCT
-MM10
DN/AWAY
10 X10
RECT EXHAUST OR RETURN DUCT
. .
,IniqE
UP/TOWARD
io"Xio",/
RECT EXHAUST OR RETURN DUCT
DN/AWAY
10
ROUND DUCT - UP/TOWARD
ROUND DUCT - DN/ AWAY
FLATOVAL DUCT - UP/ TOWARD
FLATOVAL DUCT - ON/ AWAY
DUCT OVERLAP
10'0 T,
BOOT TAP
45' TAP
lo"o
loll',
VOLUME DAMPER
CALIBRATED BALANCING DAMPER
RISE(R) & DROP(D)
TRANSITION
TURNING VANES/SPLTTERS
DUCT MOUNTED SMOKE DETECTOR
BACK DRAFT DAMPER
FLEXIBLE DUCT
AIR FLOW (FORCED AIR)
11�WCOMBINATION FSD
FIRE DAMPER
SMOKE DAMPER
MOTOR OPERATED DAMPER
EE
ACCESS DOORS
SOUND TRAP
FLEX CONNECTION
67)ff6-
ACOUSTICALLY LINED DUCT
OD = OUTSIDE DIMENSIONS
SL = SOUND LINING (THICKNESS)
`990SAM FABRIC DUCT
CLEARANCE
SUPPLY AIR DIFFUSER
(WITH CORE BLANKOFF/ROTATE)
CEILING RETURN, TRANSFER OR
EXHAUST AIR GRILLE
SLOTTED DIFFUSER (PLAN VIEW)
REVISION CLOUD & TRIANGLE
ff-0 ROUND DUCT SYMBOL
liql"o FLATOVAL DUCT SYMBOL
DEGREES SYMBOL
POINT OF CONNECTION
CD1-100 GIRD TAG IDENTIFIER = TYPE-CFM
SIZE
T'STAT/TEMP SENSOR @CARBON DIOXIDE
HUMIDITY SENSOR SENSOR
SMOKE DETECTOR @CARBON MONOXIDE
STATIC PRESSURE SENSOR SENSOR
Q OCCUPANCY SENSOR @SENSOR
EXISTING DUCTWORK
DEMO DUCTWORK
WALL -MOUNTED GRILLE
PIPE ELBOW UP
PIPE ELBOW ON
DIRECTION OF FLOW
DIRECTION OF SLOPE DOWN
PLUG OR CAP
PRESS REDUCING ASSEMBLY
SOLENOID VALVE
PI IMP
�-CHWS/CHWR-s
CHILLED WATER SUPPLY/RETURN
RL/RS-
REFRIGERANT LIQUID/SUCTION
Z--- NG ---s
NATURAL GAS
z LPG
LIQUID PROPANE GAS
�-CDWS /CDWR-5
CONDENSER WATER SUPPLY/RETURN
Z��-HWS/HWR-
HEATING WATER SUPPLY/RETURN
Z COND --- 5
CONDENSATE
a FOv ----s
FUEL OIL VENT
-FOS/FOR-
FUEL OIL SUPPLYIRETURN
z ROG
REFRIGERANT DISCHARGE GAS
MECHANICAL GENERAL NOTES
1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2015 19C, 2015 WSEC, 2015 IMC, &
& SIMILAR YEAR WAC 296-104 BOILER RULES.
2. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNO.
3. LOCATION AND DETAILS OF EQUIPMENT DUCT ROUTING AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LOCATIONS WITH
OTHER TRADES. INSTALL IN ACCORDRE WITH APPkTVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE.
4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.
5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK DETAILS SHALL BE THE SAME
AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEEk PRIOR TO PROCEEDING.
6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNO.
7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, LOW PRESSURE DUCTWORK
RDOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2" CONSTRUCTION STANDARDS WITH
AL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, HIGH VELOCITY EXHAUSTS, ETC TO MEET 4" CONSTRUCTION STANDARDS
WITH SEAL CLASS A. DUCT RISERS IN SHAFTS WITH DAMPERED PENETRATIONS TO MEET 6" CON! STANDARDS WITH SEAL CLASS A.
8. ALL COUNG DIFFUSERS ARE 4-WAY THROW UNLESS NOTED OTHERWISE.
9. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS BEFORE SOUND LINING HAS BEEN ACCOUNTED FOR (SOUND LINING 0 1', UNO)
10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY VENTS, STREETS, LOADING DOCK,
NEIGHBORING LOT LINES & FUEL BURNING EQUIPMENT OR 3 FEET BELOW OR 25' ABOVE ANY CONTAMINANT SOURCE WITHIN 10 FEET.
11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING PER C403.3.1 & C403.2.4.7:
0% TO 100% OF THE DESIGN SUPPLY AIR WITH FAULT DETECTION & DIAGNOSTIC REPORTING.
-CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOLING LOADS.
INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED.
12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTORIZED CLASS 1 LOW LEAK (0 CFM/SF 0 1" WG) DAMPERS (OR
GRAVITY PER EXCEPTIONS IN C403.2.4.3) DAMPERS WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE, UNO FOR SMOKE
CONTROL SYSTEM OPERATION.
13. THE CONTROL SYSTEM SHALL MEET C403 AND BE
14.
SET FOR DIFFERENT DAY TYPES PER WEEK,
CAPABLE OF VARYING FLOWS
15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE SMACNA AND ASCE 7. ALL LIFE
SAFETY OR HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip=1.5 FOR RESTRAINT MftHODS OR AS NOTED ON THE DRAWINGS.
REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS.
16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B.
WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS.
17. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED PER CODE.
18. ALL PIPING PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE SEALED WITH AN UL APPROVED FIRE CAULKING.
ALL MATERIALS EXPOSED WITHIN PLENUMS SHALL BE NON-COMBUSTIBLE OR SHALL BE UL LISTED AND LABELED FOR INSTALLATION IN PLENUMS OR
AS HAVING A FLAME SPREAD INDEX !9 25 AND A SMOKE -DEVELOPED INDEX OF !9 50.
19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED IN THE RETURN AIR, PER MECH CODE, SUCH AS WAC
EQUIPMENT DELIVERING �NOT ExHAuspr >2000 CFM (INCLUDING MULTIPLE UNITS DUCTED INTO COMMON DISTRIBUTION OR RETURN, WITH A TOTAL
SUPPLY >2000 CFM) 0 EACH STO OF RETURN SYSTEMS OVER 15,000 CFM IN A MULTI -STORY INSTALLATION, NOT IN SYSTEMS SERVING SINGLE
ROOMS/SPACES. SMOKE DETECTORS SHALL BE FIC (ELEC) UNO. POWER -WIRING AND INTERLOCK TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR
AS APPLICABLE. VAV BOX (WITH FAN) SHUTDOWN CAN BE THROUGH CONTROLS SYSTEM.
20. ARCHITECTURAL ACCESS PANELS SHALL BE PROVIDED AND INSTALLED BY GC AT ALL CONCEALED EQUIPMENT AND DEVICE LOCATIONS, UNLESS NOTED
OTHERWISE.
21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.
MOTOR EFFICIENCIES TO MEET OR EXCEED CODE MINIMUM.
22. FOR ALL 'SEALED AIR TIGHT" OR PRESSURIZED SHAFTS/ROOIVS, THE FOLLOWING SHALL OCCUR:
-ALL VERTICAL JOINTS & CORNERS SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE JOINT (BY GC).
-TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH�BY GC�.ILL
-ANY FLOOR DECKING PERPENDICULAR TO THE CONSTRUCTION SHALL BE CAULKED ( CC). ING WITH ROCK WOOL IS NOT ACCEPTABLE.
-ANY PENETRATIONS OF THE CONSTRUCTION (DUCTWORK CONDUIT PIPING I ES
Et SHALL BE SEALED ON BOTH S D
-ALL DOORS SHALL BE PROVIDED WITH fiGHI FITTING �ASKETS WD THRE HO D SWEEPS AND OPEN AGAINST THE DIRECTION OF PRESSURE.
USE SECTION 909.5 OF THE 2012 IBC FOR MAX ALLOWABLE LEAKAGE AREA, FOLLOWINd THE GUIDELINES FOR TIGHT STAIR SHAFT CONSTRUCTION.
23. ALL ADHESIVES, SEALANTS, PAINTS AND COATINGS USED DURING THE INSTALLATION/FINISH WORK SHALL MEET THE LEED REQUIREMENTS FOR IEQ.
24. MAXIMUM STANDARD LENGTH OF FLEXIBLE DUCT SHALL BE 12 FEET, UP TO 25' MAXIMUM LENGTH IS ACCEPTABLE IF;
FLEX DUCT&-181 TESTED & NOT "CONNECTORI IS USED DUCT 0 IS INCREASED BY 1 NOMINAL SIZE & BENDS DO NOT EXCEED 235' TOTAL.
REFER TO I TALLATION DETAILS FOR SUPPORT RE UIREMENYS. FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING
SHALL BE < 50. USE THERMAFLEX MODEL G-KM FOR LON AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL.
25. ELECTRICAL METERING OF SYSTEMS AS REQUIRED BY ENERGY CODE SECTION C409 IS BY ELECTRICAL. THE ELECTRICAL DESIGN & CONTRACTOR TEAM
WILL FURNISH THE NECESSARY ELECTRICAL DISTRIBUTION AND METERING COMPONENTS - SEE ELECTRICAL DRAWINGS. THE MECHANICAL CONTRACTOR
WILL FURNISH A BUILDING MANAGEMENT SYSTEM CAPABLE OF COLECTING AND STORING THE INFORMATION WITH A VISIBLE DISPLAY/NOTIFICATION
READILY ACCESSIBLE TO OPERATION AND MANAGEMENT PERSONNEL AS REQUIRED.
6. C406 "ADDITONAL ENERGY PACKAGE OPTIONS" AS APPLICABLE
MINIMUM DUCT INSULATION LAST UPDATED 07/11/16
DUCT TYPE
DUCT LOCATION (IN HEATED AND MECHANICALLY COOLED DUCT SYSTEM)
INSULATION
R-VALUE
REMARKS
SUPPLY & RETURN
NOT WITHIN CONDITIONED SPACE: OUTSIDE BUILDING
F-8-
_71TT-_
OUTSIDE AIR
WITHIN CONDITIONED SPACE: INSIDE BUILDING
NOTES 4 & 5
1,2,3,4,5
SUPPLY & RETURN
NOT WITHIN CONDITIONED SPACE: INSIDE BUILDING
R-6
SUPPLY AIR
<rc;o f)R � I nc;o
WITHIN CONDITIONED SPACE
R-3.3
1,2
1 REFER TO C403.2.8 FOR FURTHER REQUIREMENTS & ALSO R403 FOR RESIDENTIAL INSTALLATIONS
2 INSULATED COOLED DUCTS REQUIRED A VAPOR RETARDER (PERM < 0.5) AND SEALED JOINTS
3 WEATHERPROOF BARRIER REQUIRED AROUND DUCTWORKTO MAINTAIN WATER TIGHTNESS
4 INSULATE OUTSIDE AIR DUCTS TO BUILDING D(TERIOR WALL LEVEL PER ENERGY CODE SECTION: C403.2.8.1 UNTIL
CONNECTED TO EQUIPMENT SERVED OR TO THE CODE REQUIRED SHUTOFF DAMPER (AND J'THICK INSULATION MIN .
TO PREVENT CONDENSATION ON DUCTS IN PLENUM UP TOTHE HEATING OR COOLING EQUIPMENT)
D K-/ '-AN ft Ubt:U IN LU:U Of- WILUINU tNVtLUPE INSULATION LEVEL IF: DEDICATED OUTSIDE AIR SYSTEM AND <2,800 CFM SUPPLY AIR
MINIMUM PIPE INSULATION LAST UPDATED: 07/11/16
FLUID DESIGN INSU ON CONDUCTIVITY
NOMINAL PIPE D INCH)
OPERATING CONDUCTIVITY
TEMP *
MEAN TEMP
RATING 'F
<1
1 TO 1-1/i
I <1-1/ 1 <4
4TO
1 <8
HEATING SYSTEM
NOE
E, HYDRONIC
HOT WATER, DOMESTIC
HOT WATER
RECIRC)
>350
0.32-0.34 250
4.5
so
5.0
5.0
251-350
0.29-0.32 200
3.0
4.0
4.5
1 4.5
4.5
201-250
0.27-0.30 150
2m5
2.5
2.5
3.0
3.0
141-200
0.25-0.29 125
1.5
1 1.5
2.0
+=:j.0
2.0
105-140
0.21-0.28 100
1.0
1.0
1.5
1 1.5
1.5
CONDENSATION)
N/A
0.21-0.27 75
0.5 0.5
0.5
1 0.5 005
COOLLNG SYSTEMS (CHILLED WATER, BRINEAND REFRIGERANT, WATERSIDE ECOON.OMIZER
1
40.60 -0 .27 7
1 0.21 5
1 5
fEEM§I.*
.0
1 1.0
1 <40 1 0.20-0.26 1 __75
OTE:
501
1.0
1 1.0
1 1.0
NOT REQUIRED FOR STRAINERS, CONTROL VALVES & BALANCING VALVES ASSOCIATED WITH PIPING I" OR LESS IN DIA.
TYPICAL CONDENSER WATER PIPE IN NON -ECONOMIZER SYSTEMS IS NOT INSULATED SEE R403 FOR RESIDENTIAL INSTALLATIONS.
appWIDIVE
V�A
'Ns wgs
N �Gs B
DRAWING INDEX
SHEE'r NO.
SHEET TITLE
CURRENT
REVISION
M0600
LEGEND. ABBREVATIONS, G ERAL NOTES. & SHEEr INDP( - WAC
M0601
�A;HLUULE SHEEI - HVAC
M101
IST FOOR PLANS - WAC
SPLIT SYSTEM INDOOR FAN COIL SCHEDULE
(REPLACEMENT UNIT)
LAST UPDATED: 06/06/18
UNIT
MOUNTING/
BASIS OF
ASSOCIATE
ESP
REFR
HEATER
ELECTRICAL
SOUND
WEIGHT
TAG
LOCATION
SERVES
DESIGN
CONDENSEI
IN WG
I MAX
INE
I KW
Fa __1
V/PM
dBA
BS
REMARKS
FOJ-1
WALL HUNG
I SERVER RM
DAIKIN FTK24NMVIU
I CU-1
I 403/5Z21 7_1 3
1 NA
I NA
NA
.3
1 208 30/1
�7_
1 3 "/53
_
2,
I 1-5
M" ! �U� 1 W —IFIMI'l LI�Ulrl—1 I —QUIREME1.1 S kELEC,RICA4 WEIGHT, SIZE, ET C W! TH APPROVED SUBMI ITAL5 PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER
MANUFACTURERS REQUIREMENTS
REMARKS:
1 ELECTRICAL CONTRACTOR TO PROVIDE SOCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE.
MANUFACTURER TO PROVIDE SCCR LISTING (S KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE.
2 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. PROVIDE WITH WALL -MOUNTED WIRELESS PROGRAMMABLE T'STAT, REFER TO MFGS REQUIREMENTS FOR REFRIGERANT PIPE SIZES
3 INDOOR UNIT POWERED FROM OUTDOOR UNIT BY ELECTRICAL CONTRACTOR
4 TERMINATE CONDENSATE LINE OUTSIDE THE BUILDING WHERE IT WONT CREATE NUISANCE
5 ECONOMIZER EXEMPT PER 2015 WSBC C403.3 EXCEPTION 10 (UNIT IS SERVING SERVER ROOM AND IS 15% MINIMUM HIGHER EFFICIENCY THAN THE 13 SEER REQUIREMENT)
SPLIT SYSTEM OUTDOOR UNIT SCHEDULE
(REPLACEMENT UNIT)
LAST UPDATED: 06/06/18
UNIT
TAG
MOUNTTIINGl
L'C'
I ARVFA
SE :D
BASIS
OF DESIGN
ASSOCIATED
FAN COIL
COOLING CAPACITY
BTUH
ELECTRICAL
SOUND
dBA
WEIGHT
I LBS
REMARKS
RATED SENSIBLE
I SEER / EER
MCA I WPH
CU-1
GROUND
I SERVER RM
DAIKIN RK24NMVJU
FCU-1
21,200
15,760..
1 18 L 12.5
i 18.3 1 208-230/1
1 55
1 108
1-7
GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL I
MANUFACTURERS REQUIREMENTS
REMARKS:
I ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER.
MANUFACTURER TO PROVIDE SOCR. LISTING (S KATC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE.
2 SPLIT SYSTEM UNITS REQUIRE DISCONNECT AT THE ROOF CONDENSING UNIT BY ELECTRICAL CONTRACTOR
3 INVERTER DRIVEN COMPRESSOR, TEST CONDITIONS BASED ON AHRI 210/240
4 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES FOR EACH UNIT CONNECTION, WIND BAFFLE, LOW AMBIENT
OR HEAD PRESSURE CONTROL SUITABLE FOR LOW AMBIENT COOLING - ADDITIONALLY, CONFIRM CONTROL WIRE GAUGE (14 OR 16 AWG) WITH SUBMITTALS PRIOR TO INSTALLATION TO INDOOR U
5 REFRIGERANT: R-410A PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS
6 PROVIDE COATING FOR MARINE ENVIRONMENT
7 ECONOMIZER EXEMPT PER 2015 WSEC C403.3 EXCEPTION 10 (UNIT IS SERVING SERVER ROOM AND IS 15% MINIMUM HIGHER EFFICIENCY THAN THE 13 SEER REQUIREMENT)
7,-
D
Her ison
Building Today, Defining Tomorrow
Hermonson Company U-P
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermans n.conn
Contractor Reg #: HERMACLO05W
WASHINGTON STATE
FERRY - EDMONDS
SERVER ROOM
199 SUNSET AVE. S.
EDMONDS, WA 98020
ODOR,V,
WAS
36149
L
Revisions
06/13/18 MG ISSUE FOR PERMIT
No. Date By Description
Design Team
Design MG
Drawn FVP
Checked DTN
Pre -Construction Number 14-18-12960
Constmcfton Number
Issue Date 06/13/18
SCHEDULE SHEET
- HVAC
RECEIVED I
JUN 14 2018 ISSUE FOR PERMIT
EVEL0PMENT SERIACES
1-1---
1ST FLOOR DEMO PLAN - HVAC
SCALE: 1/2" = 1'-0"
REFRIGERANT LINE SETS,
SEE SUBMITTALS FOR SIZES.
CONNECT NEW J'CONIDENSATE TO
EXISTING CONDENSATE PIPING
1 ST FLOOR PLAN - HVAC
SCALE: 1/2" = V-0"
KEY PLAN
SCALE: NONE
FOR CITY USE:
ML
Hermanson
Building Today, Defining Tomorrow
Hermanson Company LLP
1221 2nd Asmi, North
Kent Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
—,hemn nson.corn
Contractor Reg f: HERMACLO05BJ
WASHINGTON STATE
FERRY - EDMONDS
SERVER ROOM
199 SUNSET AVE. S.
EDMONDS, WA 98020
ODOR
Xz
36149
AL
Revisions
05/13/18 MG ISSUE FOR PERMIT
No. Date By Description
Design Team
Design MG
Drawn FVP
Checked DTN
Pre —Construction Number 14-18-12960
Construction Number
Issue Data 06/13/18
1ST FLOOR PLANS
- HVAC
M2.01
JUN 14 2018
DEVELOPMENT SEFMCEJ ISSUE FOR PERMIT
COUNTER