REVIWED BLD BLD2020-0997+Interior_Lighting_Summary+9.28.2020_8.34.48_AM2015 Washington State Fnerov Code Compliance Forms for Commercial Buildinas including R2. R3. R4 over 3 stories and all R1 Revised Nov 2017
Project Info
Project Title: Firdale Village Fire Restoration
Date 7/16/2020
Compliance
Applicant Information. Provide contact information for individual mho can
For Buildin Martment Use
forms do not
respond to inquiries about compliance form information provided.
B�DLO2O-O997
Company Name: BC Investigative Engineers
require a
password to
RECEIVED
Company Address: 3605 C St NE, Auburn, WA 98002
use.
Instructional and
Se 28 2020
p
calculating cells
Applicant Name: Jesse Binford
are mite-
protected.
CITY OF EDMONDS
DEVELOPMENT SERVICES
Applicant Phone: 253-833-5557
DEPARTMENT
Applicant Email: jbinford@bcie.net
Project Description
0 New Building QAddition G1 Alteration Q No Lighting Scope
Include PROJ-SUM form (included in envelope forms workbook) with lighting compliance forms.
Interior Lighting System
Description
REVIEWED
BY
CITY OF EDMONDS
12 Interior Lighting Plans Included
Interior Lighting Power
0 Building Area Method 61 Space -by -space Method
Allowance Method
Select method used in project.
Interior Lighting Controls
0 All C405.2.1- C405.2.8 Lighting Controls [3C405.2 Exception 5 Luminaire Level
Lighting Controls (LLLC)
o Additional Efficiency Package Option
C406.4 Enhanced Digital Lighting
To comply with C406.4, no less than 90% of the total installed interior lighting power shall comply Wth
required controls per C406.4.
Dwelling Unit Interior
Permanentlyinstalled interior lighting fixtures in dwelling units comply mith: • No Dwelling
Lighting
0C405.2 thru C405.5 Commercial Lighting Controls and LPA Units
OC406.3 High Efficacy Lighting
OR404.1 Residential High Efficacy Lighting. Dwelling unit lighting complies with WSEC Residential
provisions in lieu of WSEC Commercial provisions.
Exterior Lighting System
Description
0 Exterior Lighting Plans Included
Building Additions
Compliance Method Interior lighting Exterior lighting
Lighting systems in addition area comply with all applicable
provisions as a stand alone new construction project
Refer to Section C502.2.6 for additional
-
requirements.
Lighting systems in addition are combined with existing
building lighting systems to demonstrate compliance
Addition is combined with existing:
For interior lighting projects, include new + existing -to -remain interior lighting fixture wettage in
Proposed Lighting Wattage table in LTG-INT-BLD orLTG-INT-SPACE form.
For exterior lighting projects, include new + existing -to -remain exterior lighting fixture viattage in
Proposed Tradable and Proposed Non -Tradable Lighting Wattage tables in LTG-EXT form.
2015 Washinqton State Enerqv Code Compliance Forms for Commercial Buildinqs includinq R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Firdale Village Fire Restoration
Date 7/16/2020
Change of Space Use
0 Existing interior lighting systems in areas under -going a change in space use are upgraded to
comply with LPAs for the new space types per Tables C405.4.2(1) or C405.4.2(2).
Identify interior spaces requiring LPD upgrade to the current Code in Proposed Lighting Wattage
table in LTG-INT-BLD or LTG-INT-SPACE form.
Interior and Exterior
Lighting Alterations
Lighting Power Interior lighting Parking garage Exterior lighting
50% or more of existing are replaced 0 0 Q
Select all Lighting Power and Lighting
Control elements that apply to the scope
...... ............ ... ......_
Less than 50% of existing are replaced0 0 0
of the retrofit project. If project includes a
---------------
combination of spaces where less than
Lamp and/or ballast replacement only
13 13
50% of the existing fixtures are replaced
- existing total wattage not increased
in some spaces, and 50% or more of the
fixtures are replaced in others, then
a
50% or more replaced - Total lighting power of new + existing -to -remain fixtures shall comply with
provide separate lighting power
total LPA per Sections C405.4.2 and C405.5.2. Include new + existing -to -remain fixtures in
compliance forms for the tvio retrofit
Proposed Lighting Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
conditions. Spaces undergoing the same
Less than 50% replaced - Total lighting power of new+ existing -to -remain fixtures shall not exceed
type of retrofit may be combined into one
the total lighting power prior to alteration. Include new + existing -to -remain fixtures in the Proposed
lighting power compliance form.
Lighting Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
50% threshold applies to numberof luminaires for interior spaces and parking garages, and total
Refer to Section C503.6 for additional
installed wattage for exterior luminaires.
requirements.
Lighting Controls Interior lighting Parking garage Exterior lighting
All alteration lighting controls shall be
New wiring installed to serve added �—
commissioned perC408.3.
fixtures and/or fixtures relocated to 0 0 0
new circuit(s)
New or moved lighting panel 0 0 Q
Interior space is reconfigured -
luminaires unchanged or relocated
New wiring or circuit - For interior lighting, provide required manual controls per C405.2.3,
occupancy sensor controls per C405.2.1, daylight responsive controls per C405.2.4 and application
No changes are being made to
specific lighting controls per C405.2.5. For exterior lighting, provide required controls per C405.2.7.
the interior or exterior lighting
New or moved panel - Provide all applicable lighting controls as noted for New Wiring and automatic
systems and existing space
time switch controls per C405.2.2.
uses and configuration are not
Reconfigured interior space - Provide all required lighting controls that apply to a new interior
changed.
space. Application specific lighting control provisions per C405.2.5 do not apply to reconfigured
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Firdale Village Fire Restoration
Date 7/16/2020
Calculation
Area NOTE
O New Construction O Addition - Q Addition
Q Spaces where < 50% of Q Spaces where >_ 50% of O Spaces where the Use
For Building Department Use
LPA
Calculation
Type
0 Standard O Additional Efficiency Package Option
C406.3 Reduced Interior Lighting
To comply with C406.3, the Proposed LPD shall be 25% lower than the Target LPA.
Refer to C406.3 for additional requirements.
User Note
Only spaces with
lighting changes
Maximum Allowed Lighting Wattage""
Location (plan #,
room #)
Space Type
Ceiling
Height NOTE 2
Gross Interior
Area in ftZ
Allowed
Watts per ftZ
Watts Allowed
(watts/ftZ x area)
Unit 9623 -
Reception - Al .1
Lobby: all other
7.5
219
0.720
158
Unit 9623 - Waiting
Room -Al. 1
lobby: all other
8. 6
165
0 . 720
119
Unit 9623 -
Bronzing Area -
Al.1
Conference/meeting/multipurpose
8.8
229
0.980
224
Unit 9623 -
Restroom -Al. 1
Restroom: all other
7.75
37
0.780
28
Total Area 649
Retail Display Allowance from LTG-INT-DISPLAY
Lobby Art/Exhibit Display Allowance from LTG-INT-DISPLAY NOTE 8� Allowed Watts 529
Proposed Lighting Wattage NOTES
Location (plan #,
room #)
Fixture Description NOTE 4, 5, 6
Number of
Fixtures
Watts/
Fixture NOTE?
Watts
Proposed
Unit 9623:
Reception: A2.0
2 Tube Fluorescent, Lamp T8 4 Feet
2
64
128
Unit 9623: Waiting
Room: A2.0
1 Tube Fluorescent, Lamp T8 4 Feet
1
32
32
Unit 9623 -
Bronzing Area:
A2.0
1 Tube Fluorescent, Lamp T8 4 Feet
2
32
64
Unit 9623:
Restroom: A2.0
A21 Light Bulb - Existing
2
23
46
Proposed Retail Display Lighting from LTG-INT-DISPLAY
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Watts
1 270
Interior Lighting Power Allowance COMPLIES
Note 1 - List all unique space types per Table C405.4.2(2) that occurin the project scope. Select space type category from drop down menu.
Note 2 - Indicate ceiling height for atriums and spaces utilizing the ceiling height adjustment per Table C405.4.2(2), Footnotes d thru f.
Note 3 - List all proposed lighting fixtures including exempt lighting equipment and existing -to -remain fixtures.
Note 4 - For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type (if included).
For
track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
Note 5 - For lighting equipment eligible for exemption per C405.4.1, note exception number and leave Watts/Fixture blank.
Note 6 - Existing -to -remain fixtures shall be included in the Proposed Lighting Wattage table in the same manner as new fixtures. Identify as
existing
in fixture description.
Note 7 - For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other approved source. For
luminaires with screw -in lamps, enter the manufacturer's listed maximum input wattage of the fixture (not the lamp wattage). For low
voltage
lighting, enter the wattage of the transformer. For line voltage track/busway systems, enter the larger of the attached luminaire wattage or
50
watts/lineal foot, or enter the wattage limit of permanent current limiting device.
Note 8 - Lobby Art/Exhibit Display Allowance is independent of the Maximum Allowed Lighting Wattage. Enter all proposed lobby art/exhibit display
fixtures in LTG-INT-DISPLAYform only.
Note 9 - Calculation Area Details:
a. Lighting fixtures in a building addition may comply as a stand alone project, or they may be combined with the overall existing building
lighting systems to demonstrate compliance. Refer to C502.1.
b. For alterations and building additions, provide Space Types and gross interior areas in the Maximum Allowed Lighting Wattage table. If
building addition wall comply as combined with the overall existing building lighting systems, include all applicable existing Space Types
and cross interior areas.