APPROVED FIR2022-0059+Fire_Sprinkler_Equipment_Specification_Sheets+6.7.2022_8.19.59_AM+2916159FIR2022-0059 Advanced Fire Protection Submittals For: Paradise Lane Building B RECEIVED Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 1 Pendent Sprinkler Victaulic V2740 Wht.Rec. 155 2 Dry Pendent Sprinkler Victaulic V3606 Chr. Sleeve & Skirt 3 Dry Sidewall Sprinkler Victaulic V3610 Chr. Sleeve & Skirt 4 CPVC Haneers Afcon 510,513&514 5 Riser Manifold Lansdale Valve 2" 650-375-00260 6 FDC Guardian 2 %2"Brass 6014 7 CPVC Pipe & Fittings Spears 8 9 10 REVIEWED BY CITY OF EDMONDS ITEM # 1 Victaulic° FireLockrm Series FL-RES Residential, Quick Response Pendent and Recessed Pendent, Ataulicd K3.0 (4.3), K4.9 (7.0)9 K5.6 (8.0), K6.9 (9.9) 43.01 1.0 PRODUCT DESCRIPTION SIN ORIENTATION K FACTORI _ CONNECTION _ MAX. WORKING PRESSURE GLOBE RE -DESIGNATION GLOBE EQUIVALENT SPRINKLER V27 Recessed V3010 V2740 ■ V5610 V3426 T %n 4- RESIDENTIAL V3010 PENDENT loln 425.I. '/2" NPT/15 mm 175 psi (1200 kPa) GL3010 AVAILABLE WRENCHES V27 Open End V56 Recessed V56 Open End ■ V2740 T PENDENT 4.9ImpJ7.1 S.L 1/2" NPT/15 mm 175 psi (1200 kPa) 0_ ■ Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL: 7psi/48 kPa/,5 bar Temperature Rating: See tables in section 2,0 1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. DENT SPRINKLERS V5610 PENDENT 5.6 Imp /8.1 S.I. 1/2" NPT/15 mm 175 psi (1200 kPa) GL5610 V3426 PENDENT 6.9 ImpJ9.9 S_I_ 3/4" NPT/20 mm 175 psi (1200 kPa) V34 Recessed V34 Open End ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 43.01 16382 Rev A Updated 03/2021 ® 2021 Victaulic Company. All rights reserved. 1 ictauliic` victaulic.com 2.0 CERTIFICATION/LISTINGS Max. Coverage Area Deflector to Listing Agency/ Approved Width X Ceiling/ Mounting Minimum: Nominal K Factor Temperature Ratings Length Flow Pressure Adjustment Surface Distance Spacing Ft. x Ft GPM PSI in in Ft. SIN Imperial S.I2 155°F/68°C 175°F/79°C 200°F/93°CI m x m Umin kPa mm (mm) m 12 x12 8 7.1 V3010 3.0 4.2 cULus EU I cULus cULus 3.7 x 3.7 30.3 49 1/2 i 14 x 14 10 11.1 15 4.3 x 4.3 37.8 76.5 12 x 12 13 7.0 3.7 x 3.7 49.2 48 14 x 14 13 7.0 Smooth Ceilings 4.3 x 4.3 49.2 48 1/2 and Recessed 16 x 16 13 7.0 15 and 20 See Installation V2740 4.9 7.1 cULus cULus N/A 4.9 x4.9 I 49.2 48 Detail 18 x 18 17 12.0 Smooth Ceilings 5.5 x 5.5 64.4.3 83 Exposed 20 x 20 20 16.7 1/2 Max. 4 (101.6) 6.1 x6.1 75.7 115 15 12 x 12 15 7.2 Beamed Ceilings 3.7 x_3.7 57 _ 50 _ Adjacent 8 16 x 16 19 11.5 per NFPA 13, 13D, 2.4 4.9 x 4.9 72 79 1/; or 13R V5610 5.6 8.1 cULus NA N/A 18 x 18 21 14.1 15 as appropriate 5.5 x 5.5 79 97 20 x 20 24 18.4 Beamed Ceilings 6.1 x6.1 91 127 In Beam 14 Max. Beam 12 x 12 20 8.4 Depth 3.7 x 3.7 75.7 58 Recessed in Beam: 14 x 14 20 8.4 See Installation 4.3 x 4.3 75.7 58 detail V3426 6.9 9.9 cULus cULus N/A 16 x 16 20 8.4 1/2 and 1/4 4.9 x 4.9 75.7 58 15 and 20 18 x 18 20 8.4 5.5 x 5.5 75.7 58 20 x 20 22 10.2 6.1 x 6.1 83.3 70 NOTE • Listings and approval as of printing. 43.01 16382 Rev A Updated 03/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaulilcr victaulic.com 3.0 SPECIFICATIONS — MATERIAL Deflector: Bronze Bulb Nominal Diameter: 3.Omm Load Screw: Bronze Pip Cap: Bronze Spring Seal Assembly: PTFE coated Beryllium nickel alloy Frame: Brass Lodgement Spring: Stainless Steel Installation Wrench: Ductile iron Sprinkler Frame Finishes: • Plain brass • Chrome plated • White polyester painted • Flat black polyester painted • Custom polyester painted NOTE / • For cabinets and other accessories refer to separate sheet. '/�6"/11 mm Nominal make -in Frame Pip cap and spring sealBulbLoad screw rV3010 Denector r/�6"/11 mm make -in Frame Lodgement springPip cap and/ fNinal spring sealm Bulb Load screw Deflector 1 27 mm V2740 7%"/11 mm Nominal make -in Frame Pip cap and spring seal t 2 , mm Bulb Load screw Deflector — 1'/,"/ 32 mm V5610 k"/13 mm FNominal make -in f Lodgement s Pip cap ar spring se Load s< Defl 43.01 16382 Rev A Updated 03/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 3 JctaulicJ victaulic.com 4.0 DIMENSIONS Ya"/3 mm Min. W/16 mm Max. 1 Yi /32 mm Min. 1 W/44 mm Max. 1725 mm Max. (1/4' Adj.) 3W/14 mm Max. (1h' Adj.) A76 mm Min. 1'V6'/43 mm Max. 13is7%30 mm Min. (1/V Adj.) 1;16724 mm Min. (1/4" Adj.) 23/a'/60 mm 2751 mm Hole in ceiling 75 mm V3010 2%"/60 mm 2/51 mm Hole in ceiling 2"A61 75 mm V2740 Typical ceiling Finished surface Finished surface 43.01 16382 Rev A Updated 03/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 4 ✓ctaiulie victaulic.com 4.0 DIMENSIONS (CONTINUED) 21'e /60 mm 2'/51 mm — Hole in ceiling %-/3 mm Min. r I %"/16 mm Max. 1 N /32 mm Min. 1 W/44 mm Max. 2'3fe / _ 75 mm V5610 2%'/60 mm _ 2"/51 mm Hole in ceiling E: - - - --- I 7/e%22 mm Max. (W Adj) IWA 6 m m Max. N2" Adj.) A73mm Min. tW/29 mm Min. (3AAdj.) 13A"/34 mm Min. ('h" Adj.) 17/s'/47 mm Max. 2416 / 75 mm V3426 Typical ceiling surface Typical ceiling a � Finished surface 43.01 16382 Rev A Updated 03/2021 0 2021 Victaulic Company. All rights reserved. Victaulic.com 5 Jctaulicr victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS A WARNING Read and understand all instructions before attempting to install y� any Victaulic products. �1 • Always verify that the piping system has been completely depressur- ized and drained immediately prior to installation, removal, adjust- ment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from-67°F/-55°C. User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms "Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 43.01 16382 Rev A Updated 03/2021 © 2021 Victaulic Company. All rights reserved. ✓ctaulilf victaulic.com 0 ITEM # 2 FireLockT" Series FL-QR/DRY Standard Coverage, Quick Response Dry, Upright, Pendent and �Otaulia Recessed Pendent Sprinklers K5.6 (8.1), K8.0 (11.5) 45.01 6 1.0 PRODUCT DESCRIPTION SIN ORIENTATION_ K-FACT0R1 CONNECTION MAX WORKING PRESSURE ESCUTCHEON _ GLOBE EQUIVALENT UPRIGHT QUICK RESPONSE DRY Imp./8.1 S.I. PT/25mm BSPT/1"IGS 175 psi (1200 kPa) Plain GL5639 PENDENT QUICK RESPONSE DRY SPRINKLERS SIN V3606 ORIENTATION PENDENT K-FACTORI 5.61mp./8.1 S.I. CONNECTION 1" NPT/25mm BSPT/1" IGS MAX WORKING PRESSURE ' 175 psi (1200 kPa) ESCUTCHEON _ Plain/Flush/Sleeve and Skirt/Extended GLOBE EQUIVALENT GL5635 V3604 UPRIGHT 8.0 Imp./l 1.5 S.I. 1" NPT/25mm BSPT/1" IGS 175 psi (1200 kPa) Plain_ GL8139 V3608 PENDENT _ _ 8.0 Imp./l 1.5 S.I. 1" NPT/25mm 13SPT/1" IGS 175 psi (1200 kPa) Plain/Flush/Sleeve and Skirt/Extended GL8135 RECESSED PENDENT QUICK RESPONSE DRY SPRINKLERS SIN V3606 ORIENTATION PENDE K-FACTORI 5.61 . 8.1 S.I. CONNECTION 1" NPT/ m BSPT/1" IGS MAX WORKING PRESSURE psi (1200 kPa) ESCUTCHEON Recessed BE EQUIVALENT GL5635 AVAILABLE GUARDS/SHIELDS SPRINKLER — _ V34N36 V34N36 Intermediate Shield — -- ---- ---Upri ht Pendent ■ • AVAILABLE WRENCHES Sprinkler V36 Recessed V36 Open End Upright ■ Pendent ■ Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: Pendent: 7 psi/48 kPa/.5 bar Upright: 12 psi/83 kPa/0.8 bar Temperature Rating: See tables in section 2.0 1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. V3608 PENDENT 8.0 I MPA I S.I. 1" NPT/25mm 13SPT/1" IGS 175 psi (12.00 kPa) Recessed GL8135 V34N36 Int. Shield/Guard ■ 3/16 Hex Bit (V9) IN ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT victaulic.com 45.01 15896 Rev B Updated 06/2021 0 2021 Victaulic Company. All rights reserved. 1 ictaul1wr victaulic.com 2.0 CERTIFICATION/LISTINGS coos <FM> usTrn APPROVALS/LISTINGS SIN V3602 V3604 Nominal K Factor Imperial 5_6 8.0 Nominal K Factor 5.12 8.1 1 11.5 Orientation Upr�ht Fright Escutcheon Plain Plain Approved Temperature Ratings F%C° 135°F/57°C 135°F/57°C 1SS°F/68°C 155°F/68°C cUlus 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C FM 155°F/68°C 155°F/68°C 200°F/93°C 200°F/93°C 286°F/141°C CCC 155°F/68°C APPROVALS/LISTINGS SIN V3606 V3608 V3606 V3608 Nominal K Factor Im ep rialrial 5.6 J 8.0 S.6 8_0 Nominal K Factor S.I 2 8.1 11.5 _ 8.1 _1-1.5 Orientation _ Pendent Pendent Pendent Pendent Escutcheon Plain, Flush, Slv & Skt, Ext Plain, Flush, Slv & Skt, Ext Recessed _ 1 _ Recessed Approved Temperature Ratings F°/C° 135°F/57°C 135°F/57°C 135°F/57°C 13S°F/570C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 2867/141°C 286°F/141°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C FM 155°F/68°C 155°F/68°C 155°F/68°C 1550F/680C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C _ CCC 155°F/68°C 155°F/68°C 2 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10. NOTES • Listings and approval as of printing. • Temperatures are listed for all hazards and approved for V3605 and V3606 dry sprinklers up to 48' length. 45.01 15896 Rev B Updated 06/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctauliid victaulic.com 3.0 SPECIFICATIONS — MATERIAL Deflector: Brass or Stainless Steel Spring seal assembly Bulb Nominal Diameter: 3.Omm Torsion spring Split Spacer: Stainless Steel Inlet fitting Load Screw: Brass Pip Cap: Stainless Steel Inner tube Spring Seal Assembly: PTFE coated Beryllium nickel alloy and stainless steel Outer tube Frame: Brass Inlet Fitting: Brass Outer Tube: Galvanized steel pipe Inner Tube: Stainless Steel Orifice insert Orifice Insert: Stainless Steel Escutcheon plate Escutcheon/Plate: 1010 - 1018 mild steel and stainless Frame Split spacer steel Pip cap Torsion Spring: SST wire Bulb Load screw Installation Wrench: Ductile iron Deflector Sprinkler Frame Finishes: Material Specifications V3606,V3608 • Plain brass • Chrome plated • White painted3, 4 • Bright White painted3, 4 • Flat black painted34 Deflector Load screw • Custom painted3 4 Bulb • VC-25055 Pip cap Split spacer 3 Not available on the Intermediate Level Style Pendent. Frame 4 UL Listed for corrosion resistance. 5 UL Listed and FM Approved for corrosion resistance. -- Orifice insert NOTES • Weather resistant escutcheon available upon request. • For cabinets and other accessories refer to separate sheet. Outer tube Innertube Escutcheon optional (Not provided) 45.01 15896 Rev B Updated 06/2021 © 2021 Victaulic Company. All rights reserved. spring Inlet fitting Spring seal assembly J Material Specifications V3602,V3604 �OtaUlliC victaulic.com 3 victaulic.com 4.0 DIMENSIONS Tee with same outlet size 1" IGS fitting as sprinkler thread size. See'Important Installation 0 Information, later in this document 1 "NPTBSPT A (3YW �'' A — 79 mm Min.) (2'/ — — 51 mm Min.) I rh^/ 47 mm 47 mm Plain Barrel, Grooved Plain Barrel, Threaded V3606, V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C _ Tee with same outlet size 1" IGS fitting / V as sprinkler thread size. See'Important InstallationInformation' later in thisdocument. A PTBSPT (23s /1�.°/44 mm Min. A3/4'/44 mm Min. 67 mm Min.)_�_Hole in ceiling (1 /z"/Hole in ceiling38 mm Min.) local ceiling } i�ypical ceiling 47101 mm I -Finished surface 47101 mm Finished surface 2�h'/63 mm 21h'/63 mm I / i -3'1w182 mm- 3/4782 mm ( Sleeve and Skirt, Grooved Sleeve and Skirt,Threaded V3606, V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Optional Interchangeable Escutcheons Escutcheon "A" Dimension_ Adjustment Plain Barrel A=A Flush A='/4"/6mm Recessed Slv/Skrt A=-13/8'/35mm 45.01 15896 Rev B Updated 0612021 ® 2021 Victaulic Company. All rights reserved. x/ictsulicr victaulic.com virfaulir rnm 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size as sprinkler thread size. i i i WSee'Important Installation Information, later in this document. I'NPT/BSPT A (1$4% 11h"/38 mm Min. 44 mm Min.) Hole in ceiling 6/mm �calceiling 21/ I A�1 I `Finished surface 51 mm %-3776 mm- J Flush,Threaded V3606,V3608 Tee with same outlet size i as sprinkler thread size. i ii ,-see 'Important Installation Information; later in this document. 1 ° NPT/BSPT FA - - 51 mm Min.) 1/4 / r6 m m 2"/ 51 mm Ir 3776 mm -.I Intermediate, Threaded V3606,V3608 1' IGS fitting O A 75 mm Min.) j 11/h'/38 mm Min. I-~ I Hole in ceiling 6/mm Typical ceiling 2"/ 51 mm Finished surface 3'/76 mm Flush, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40`F/5`C 1" IGS fitting F-1 0 A (215167 74 mm Min.) IW/ 6mm 51 m 3'/76 mm Intermediate, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40"F/5"C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A" Dimension Adjustment Plain Barrel A=A Flush A=-'/4"/6mm Recessed A=+'/4%6mm Slv/Skrt A=-11/8"/35mm_� 45.01 15896 Rev B Updated 06/2021 ® 2021 Victaulic Company. All rights reserved. ✓ctsulirr victaulic.com 5 victaulic.com 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size as sprinkler thread size. I I I vSee"Important Installation Information' later in this document. 1 " N PT/BSPT A — —_ (2Y4°/ _Y /51mmMin. 57 mm Min.} Hole in ceiling Typical ceiling IW/47 mm 1Ye%28 mm surface 1' IGS fitting O A F1_ 87 mm Min.) r1mn. g 1'%'/47mm 1AV, m Finished surface 21V73 mm--1 L W-2%7/3 mm—i Recessed, Threaded Recessed, Grooved V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40"F/5'C '---T17%"/47 mm 1'h"/38 mm Min. Hole in ceiling A 1-� ('/51 mm Min.) yj Typical ceiling 2 Finished surface 1' NPT/BSPT Tee with same outlet size as sprinkler thread size. See'Important Installation — — Information', later in this Installed Dimensions, Threaded document. V3602,V3604 17/ 47 mm lY2"/38 mm —�— Hole in c ng ypical ceiling A (3Ye"/80 mm Min.) Finished surface - --1' IGS Fitting Installed Dimensions, Grooved V3602,V3604 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A" Dimension_ Adjustment Plain Barrel A=A Flush A A= 1/4"/6mm Recessed A=+'/4"/6mm Slv/Skrt A=-13/s"/35m m 45.01 15896 Rev B Updated 06/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com victaulic.com 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size 1 (1' as sprinkler thread size. See"Important Installation Information, later in this document. PT/BSPT A (1'72y } I 29e'mimMin. oicelin38 mm Min.) le g Typical,ceilng 5'/128 4 3Y2'/89 mm Extended Sleeve and Skirt, Threaded V3606,V3608 Finished surface 1' IGS fitting A (2 67 mm Min.) 2Hole i mm Mtn. _ Hole n ceiling I 1—� 1 Typical,ceiling Finished surface 57128 mm 334796 mm 1— 3Yz"/89 mm -« Extended Sleeve and Skirt, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A" Dimension Adjustment Plain Barrel A=A Flush A=-1/4"/6mm Recessed A=+'/4"/6mm S lv/Skrt A=-1 3/a"/35 m m 45.01 15896 Rev B Updated 06/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 7 ✓ctnuliie victaulic.com 5.0 PERFORMANCE - Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS A WARNING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from—670F/-55'C. 1-4 : ViCtaulic FireLockT" Automatic Scrinklers In i n n Maintenance In�tr�&lQn; I -Mg. St,le V9 Victaulic Firel-ock"m IGSTM Installation-Read,TM S kl _Hine Installation Instruction: User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms "Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 45.01 15896 Rev B Updated 06/2021 © 2021 Victaulic Company. All rights reserved. ✓ctaulie victaulic.com F,7 ITEM # 3 FireLock"' Series FL-QR/DRY/SW Standard Coverage Quick Response Dry Horizontal Sidewall and Recessed Horizontal Sidewall Sprinklers ✓ctaulicr K5.6 (8.1 SI), K8.0 (11.5 SO 45.02 1.0 PRODUCT DESCRIPTION HORIZONTAL SIDEWALL QUICK RESPONSE DRY SPRINKLERS _ SIN: V3610 — V3612 Orientation HORIZONTAL HORIZONTAL K-FACTOR' _qF 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1" NPT/25mm BSPT/1" IGS 1" NPT/25mm BSPT/1" IGS MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) r j Plain/Flush/Recessed Plain/Flush/Recessed ESCUTCHEONS Sleeve and Skirt/Extended Sleeve and Skirt/Extended_ GLOBE EQUIVALENT GL5641 GL8141 RECESSED HORIZONTAL SIDEWALL QUICK RESPONSE DRY SPRINKLERS SIN V3610 V3612 ORIENTATION HORIZONTAL HORIZONTAL K-FACTORI 5.6 Imp.:+. i `-.l. 8.0 ImpJ11.5 5.1. CONNECTION 1' _ 5mmBSPT/1"IGS � 1"NPT/25mm BSPT/1"IGS_ MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) ESCUTCHEONS Recessed � Recessed GLOBE EQUIVALENT �GL5641 GL8741 . AVAILABLE WRENCHES _ SPRINKLER V36 Recessed V36 Open End 3he _Hex -Bit (V9) Sidewall ■ ■ i ■ Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL/FM: 7 psi/48 kPa/.5 bar Temperature Rating: See tables in section 2.0 r For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 45.02 15954 Rev C Updated 11/2021 m 2021 Victaulic Company. All rights reserved. �c 1 taulicr `-.l. 8.0 ImpJ11.5 5.1. CONNECTION 1' _ 5mmBSPT/1"IGS � 1"NPT/25mm BSPT/1"IGS_ MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) ESCUTCHEONS Recessed � Recessed GLOBE EQUIVALENT �GL5641 GL8741 . AVAILABLE WRENCHES _ SPRINKLER V36 Recessed V36 Open End 3he _Hex -Bit (V9) Sidewall ■ ■ i ■ Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL/FM: 7 psi/48 kPa/.5 bar Temperature Rating: See tables in section 2.0 r For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 45.02 15954 Rev C Updated 11/2021 m 2021 Victaulic Company. All rights reserved. �c 1 taulicr victaulic.com 2.0 CERTIFICATION/LISTINGS cQus <R> unm HORIZONTAL SIDEWALL APPROVALS/LISTINGS SIN_ V36102 V3612 Nominal K Factor Imperial 5.6 8.0 Nominal K FactorS.l'_ 8.1 11.5 Orientation Horizontal Horizontal Escutcheon Plain, Flush, Slv and Skt, Ext Plain, Flush, Slv and Skt, Ext Approved Temperature Ratings F°/C° 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 135°F/57°C FM 155°F/68°C 200°F/93°C 286°F/141°C _I RECESSED HORIZONTAL SIDEWALL APPROVALSILISTINGS SIN V3.6102 V3612 _ K Factor Imperial 5.6 8.0 _Nominal I Nominal K Factor 1 I 8.1 _ 11.5 _S.I Orientation _ Horizontal_ Horizontal Escutcheon Recessed Recessed Approved Temperature Ratings F°/C° 135°F/57°C 135°F/57°C 155°F168°C 155°F/68°C cULus 200°F/93°C 200°F/93°C I 286°F/141°C 286°F/141°C 135°F/57°C FM 155°F/68°C — 200°F/93°C — For K-Factor when pressure is measured in Bar, multiply S.I. units by 10. z cULus Listed for light hazard only with deflector 4" — 12' below the ceiling. NOTES • Listings and approval as of printing. • Temperatures are listed for light hazard and approved for V3610 dry sprinklers up to 48" length cULus and 36" for FM. • Temperatures are listed for light and ordinary hazards and approved for V3612 dry sprinklers up to 48' length cULus. 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaulic victaulic.com 3.0 SPECIFICATIONS — MATERIAL Deflector: Brass or Stainless Steel Bulb Nominal Diamter: 3.Omm Split Spacer: Stainless Steel Load Screw: Brass Pip Cap: Stainless Steel Spring Seal Assembly: PTFE coated Beryllium nickel alloy and stainless steel Frame: Brass Inlet Fitting: Brass Outer Tube: Galvanized steel pipe Inner Tube: Stainless Steel Orifice Insert: Stainless Steel Escutcheon/Plate: 1010 - 1018 mild steel and stainless steel Torsion Spring: SST wire Installation Wrench: Ductile iron Sprinkler Frame Finishes: • Plain brass • Chrome plated • White painted3 • Bright White painted3 • Flat black painted3 • Custom painted3 • VC-25044 3 UL Listed for corrosion resistance. 4 UL Listed and FM Approved for corrosion resistance. NOTES • Weather resistant escutcheon available upon request. • For cabinets and other accessories refer to separate sheet. Split spacer Inlet fitting Pip cap Estucheon plate Outer tube — Bulb Torsion spring Load screw Defector — Orifice insert Inner tube Spring seal assembly Material Specifications V3610,V3612 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 3 ✓ataulil victaulic.com 4.0 DIMENSIONS Finished ceiling V3610 127305 mm Tie with same outlet size 4"/102 mm as sprinkler thread size. V3612 A See "Important Installation 2 /4 / (2•/ Information", later in this 67152 mm 58 mm 51 mm Min.) document 4'1102 mm — per NFP I.NPT I I I I I I I I I I I I lain Barrel, Threaded — — — —� V3610,V3612 MEMEMEW Finished ceiling V3610 12°/305 mm / 4°/102 mm V3612 2y4 '/ A 6'/152 mm 56 mm� (31 / 4'/102 mm 79 mm h .) 1 ° IGS fiiting per NFPA I I I I 1 1 I Plain Barrel, Grooved V3610,V3612 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 10 ✓ct U, iiCr victaulic.com 4.0 DIMENSIONS (CONTINUED) Finished ceiling V3610 12"7305 mm 4"/102 mm V3612 67152 mm 37 76 mm�_ 4"/102 mm per NFPA I I IL IL 31 1 1 t 1 lh./ 38 mm Mir/ Hole in I /4 Typical wall 6mm A 64 mm 44 mm Min.) Flush, Threaded V3610,V3612 Finished ceiling V3610 12"/305 mm 4"/102 mm V3612 6"/152 mm 4"/102 mm per INFPA b4 mm 75 mm Min.) Flush, Grooved V3610,V3612 45.02 15954 Rev C Updated ll/2021 ® 2021 Victaulic Company. All rights reserved. Tee with same outlet size as sprinkler thread size. SInfomportanton-, l Installation Information; later in this document I I VIGS fitting ✓ctsulic victaulic.com 5 victaulic.com 4.0 DIMENSIONS (CONTINUED) Finished ceiling V3610 12"/305 mm 4"/102 mm V3612 6"/152 mm 47102 mm per NFN V 127 4"/1 V; 671. 4711 per 11%'/41 mm 57 mm Min.) Recessed, Threaded V3610,V3612 Finished ceiling tw mm min.) Recessed, Grooved V3610,V3612 45.02 15954 Rev C Updated 11/2021 ® 2021 Victaulic Company. All rights reserved. Tee with same outlet size as sprinkler thread size. See"Important Installation Information; later in this document i 1" IGS fitting x/ictsulice victaulic.com L victaulic.com 4.0 DIMENSIONS (CONTINUED) Finished ceiling V3610 12"/305 mm 4"/102 mm V3612 33ife"/ 67152 mm 81 mm 4"/102 mm per NF� 41.4"/115 mm 3"/77 mm Typical ceiling (1 L 38 mm Min.) Sleeve & Skirt, Threaded V3610,V3612 Finished telling V3610 12"/305 mm 47102 mm V3612 31/6"/ 6°/152 mm 81 mm 47102 mm per NFPA 4'/z"/1 3"/1 I I k- I I 1-a"/ 44mmMin. Hole in Typical ceiling 67 mm Min.) Sleeve & Skirt, Grooved V3610,V3612 45.02 15954 Rev C Updated 1112021 m 2021 Victaulic Company. All rights reserved. Tee with same outlet size as sprinkler thread size. See"Important Installation Information, later in this document I" IGS fitting ✓ctaulid %A^+—dir rAm 7 victaulic.com 4.0 DIMENSIONS (CONTINUED) Finished ceill. 127305 mm 47102 mm 67152 2 mm 1" NPTBSPT I i-11 IL I I i I I I � � 36 mm Min.) Extended, Sleeve & Skirt, Threaded V3610,V3612 Finished ceiling V3610 12"/305 mm 4'/102 mm V3612 J89mm 6'/152 mm / per N per FPA , 5Y."/133 mm 4"/102 mm A (2%'/ 67 mm Min.) Extended, Sleeve & Skirt, Grooved V3610, V3612 45.02 15954 Rev C Updated ll/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com S Tee with same outlet size as sprinkler thread size. See'Important Installation Information, later in this document I I 1' IGS fitting ✓ctoulid victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS 6. - � VIV v A WARNING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from-67°F/-55°C. 1-40, Victaulic FireLockTm Automatic Sorinklers Installation and Maintenance Instructions V t. V9 Victaulic FireLockTI IGSTI In II-T"'_;orinkler Coupling Installation Instructions User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms 'Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United Slates and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. ✓ctaulicr victaulic.com we ITEM # 4 510 1 jL f C.p. Y C. HANGER SIZE - 3/41' thru 2" pipe, MATERIAL- Carbon Steel. FINISH - Mil. Galvanized. LISTINGS - EX 4231 et. us EX 2551 FUNCTION - Use on C.P.V.C., Copper or Steel piping installed per N.F.P.A. 13 Hanger/ Restrainer 13R and 13D. Acts as a hanger and or restrainer. INSTALLATION - Install on top' bottom or side of beam. Hanger spacing by pipe type -per NFPA 13. NOTE: On copper - insulate pipe' UL listed fasteners tested per NFPA 13, as follows. IN WOOD: © o Stabilize -Only isted screw famished with product. CPVC and Copper Pipe - #9051 Steel Pipe-1/4"xl1/2" lag screw - needs no pre -drilling. r , IN.STEEL: CPVC, Copper and Steel Pipe - 14' or #14 Tek Screw. IN CONCRETE: fasteners, CPVC, Copper and Steel Pipe - Shot type, "Only when installed prior to pipe insertion". FEATURES • Offset edge eliminates abrasion. installation. * Retainer dimples secure hanger to pipe during * Required #905 screw has 5/16 hex head - needs no pre -drilling. ORDERING - Part # and pipe size. *CAN ALSO BE USED TO REPLACE - #520 TIN STRAP 12102 513 prpE / V.pe •cC. GER SINGLE FASTENER SIZE - 3/4" thru 2" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized LISTINGS - 0 W" EX 4231 EX 2551 FUNCTION - Use on C.P.V.C., Copper or Steel piping installed per N.F.P.A. 13, 13R and 13D. Hanger when tab is up and fastener in horizontal position. Restrainer when tab is down and fastener in horizontal position.' INSTALLATION -_ Install on side of beam. Can install on top of beam to stabilpipe. Hanger spacing by pipe typeper NFPA NOTE: On copper - insulate pipe. UL listed fasteners tested per NFPA 13, as follows. IN WOOD: CPVC and Copper Pipe - #905 listed screw furnished with product. Steel-1/4"xI 1/2" lag screw - needs no pre -drilling, IN STEEL: CPVC, Copper and Steel Pipe -1/4" or#14 Tek Screw. IN CONCRETE: fasteners, CPVC, Copper and Steel Pipe - Shot type "Only when installed prior to pipe insertion". FEATURES * Offset edge eliminates abrasion. * Required #905 screw has 5116 hex head - needs no p re -drilling. ORDERING - Part # and pipe size. Hanger Restrainer Stabilize - Only 12102 514 OFFSET - 1 11 E / V.Pe `cCe NGER / RESTRAINER Hanger/ Restrainer SIZE - 3/4" thru 2"pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized.. LISTINGS - OEX 4231 °S EX-2551 PATENT - Pending. FUNCTION - Use on C.P.V.C., Copper or Steel piping installed per N.F.P.A. 13, 1311 and 137,%. Acts as a hanger and restrainer. INSTALLATION - Install on top, bottom or side of beam. Install on 3/8"60mp0site wood web joist, using #906 backing nuts.- see drawing. Hanger spacing by pipe type - per NFPA 13. --Snap over pipe then squeeze strap back around pipe allowing pipe to slide freely. NOTE: On copper - insulate pipe. UL listed fasteners tested per NFPA 13, as follows. IN WOOD: CPVC and Copper Pipe - #905 listed screw furnished with product. Steel Pipe - 1/4"xl 1/2" lag screw - needs no pre -drilling. IN STEEL: CPVC, Copper and Steel Pipe- 114" or #14 Tek Screw. IN CONCRETE: CPVC, Copper and Steel Pipe: Shot. type fasteners, "Only when installed prior to pipe insertion." FEATURES * 1 1/2" Offset allows elimination of wood blocking. * 3/4" and I" pipe size have common center -line. * Leg design produces superior strength. * Offset edge eliminates abrasion. * Required #905 screw has 5/16 hex head - needs no pre -drilling. ORDERING - Part # and pipe size. Stabilize - Only 12/02 ITEM # 5 LANSDALE-..q VALVE &MANUFACTURING BUcco 1040 Broadway, Westiville, NJ 08093 Toll Free: (800) 543-4194 • Fax: (602) 484-9248 www.breccocorp.com RESIANNIZAL RISER Features: • Lead Free stainless steel body construction with all brass trim • Factory assembled • Factory pressure tested at 200psi (13.8 bar) • NPT (female x female) connections • Slim design allows for easy installation • Optimum sensitivity is assured through a dedicated FM approved/UL and ULC Listed Water Flow Detector • Choice of 3 kinds of trim: Basic Trim Basic Trim w/Test & Drain Basic Trim w/Pressure Relief Kit Size as c m Basic Trim w est & Drain Basic Trim w ressure Relief Kit 1" 650-375-00100 650-375-00280 650-375-00200 11/4" 650-375-WI20 650-375-00740 650-375-00220 1%11 650-375-00160 650-375-00760 650-375-O024e_ 2" 650-375-00180 650-375-00840 650-375-00260 .37" FLOOR CONTROL VALVE C ANDTESTASSEMBLY 9.55 PROJECT INFORMATION Address: Contractor: Engineer: Submittal Data: Notes 1: Notes 2: A Size A 191 .75" 11/4" 1.0211 MIN 1.0219 2" 1.02„ APPROVAL STAMP ❑ Approved ❑ Approved as noted ❑ Not aDDroved Remarks: i -� =800.327.6584 Yn AN T, INC. 00.827.3869 DETAIL AND SUBMITTAL SHEET Project/Location: Date: Architect/Engineer: Contractor: []Appropriate Selection Used as auxiliary connections through which the fire department can pump water to supplement existing water supplies. Provides 250 GPM flow (mini- mum), per 21h" inlet. Single - inlet connections incorporate a straight-thru, non-clappered de- sign with female NPT outlets. Two and three-wav inlet connections feature brass bodies (angle or straight pattern), with integral drop -clapper inlets and female NPT outlets Standard components, al! connections: Female hose thread swivel inlets, plugs with chains and identification plate. Cast brass construction, standard. 6002 M6014 ❑ 6015 ❑ 6016 ❑ 6017 1'/2" 2'/2" 3" 21/:° 3„ 21/2" /i' 2' '/z" 'h" O.D. 7" O.D. 7" O.D. x 7" 6" x 7" Indentification Plate Lettering: AUTO SPKR and Three -Way Connections ModelTwo utlett Outlet _ Clappers i ❑6024 Back 4" x 2'/2" x 2'h" 2 — 7" ❑6025 Bottom 4" x 2'/z" x 21/2" 2 7'/s" 7'❑6026 Top 4" x 2'/2" x 2'/z" 2 1121/'e"67/8" 7'/s"" 7" ❑6027 Back 6" x 2'h"x 2'h" 2 ❑6028 Bottom 6" x 21h" x 2'/2" 2 1s 7'/s' 75/a" ❑6029 Top 6" x 21h" x 21/z" 2 121/s" 8" 9" 7%" ❑6034* Back 4" x 21/2" x 21/2" x 21h" 3 173/e" 6Va" --- 7" ❑6037 Back 6" x 21/2" x 21/2" x 2'h" 3 173/a" 61/s" --- 7" ❑6038 Bottom 6" x 2'!2" x 2'/2" x 2'/2" 3 173/a" 75/s" 71/e' 7" ❑6039 Top 6" x 21h" x 2'h" x 2'/z" 3 173/e" 7%" 1 7'/s" 7" Indentification Plate Lettering AUTO SPKR []AUTO SPKR & STANDPIPE ❑STANDPIPE ❑ DRY STANDPIPE *with steel bogy only. Optional Finish: [I -B Polished Brass Threads: -C Rough Chrome Plated ❑ NST ❑ -D Polished Chrome Plated ❑ Other 1'12"Nipple—� Plate (by others) O SwiveI c Inlet Plug 3' 41/.° s002 3'/," or 4'/e 21h" or 3° Plate Nipple —s (by others) Swivel Inlet o et Plug 7" .16015 2'fi or 3' Nipple—� (by others) S el� o Inlet Plug 31, 7 31/ " or 41/: Dia. Plate i I� k 6' —"I �A A- C1. 2'/2" Nipple (by others) Swivel. " let Plate 31/: Dla. O g' In Plug 6024-6029 —� D ts" 211i Nipple (by others) Swivel ° Inlet Plate 3'/: Dia. � T. 00 Plug 1 D 23' 6034-6039 Contact factory for current listings and approvals ITEM # 7 -- - Fr GPVG RRE SPRINKLER.1�2 FG-2.0609 C'orilplete yyStetit of Pipe, Fittings & ,!'Olver-1t u'emerlt Corrosion Resistanto Superior Flow e-Erie of Thstallation Spears° FiameGuardo CPVC Fire Sprinkler Products provide a cost effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of installation and quick assembly with readily available tools. CPVC Fire Sprinkler Systems are based on proven epvc-tw- gMl2MitPRAD1ICCb products that have been in continuous service for over40years. Spears®FlamP-GuarO products are approved by UL®, Fly`' Global, LPCB and Certified by NSF International for potable water use. Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not Sustain Biological Growth Unlike metal systems, FlameGuard® CPVC products never rust, scale or pit and do not sustain biological growth - a h can use of Microbiologically Influenced Corrosion (Nn ) destroy metal fire sprinkler systems from the inside out. Superior Flow Characteristics for Lower Friction Losses The smooth -wall interior surfaces of FlameGuard CPVC systems result in reduced friction loss over metal systems. The design flow characteristics remain constant throughout the life of the product because there is no interior corrosion in the system due to microbiological activity. Pressure Rated to 175psi (12OOkpa) @ 1500 F (65C 0) FlacmeGuardo CPVC Products are produced in combinations of Schedule 40 and Schedule 80 Fitting configurations con- forming to ASTM F 43 8 or F 439 standards and FlameGuard° SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F 442 standards. UL® Rated working pressure is 175 psi (1200kpa) @ 150°F (65°C) (LPCB rated to 120T) (49°C). Easy Installation for Lower Costs FlameGuard° CPVC system. installations significantly reduce costs over conventional metal piping by virtually eliminating prefabrication. Systems can be fully. installed on site using solvent cement joining methods. UL® Listed for U.S. and Caaada in NFPA 13,13R Sa 13D Systems FlameGuard° CPVC Fire Sprinkler Products are UL® listed for U.S. and Canada applications for Light Hazard occupancies as defined in NFPA 13, Residential occupancies up to and including 4-stories as defined in NFPA 13R, and Residential occupancies for one and two family dwellings and manufactured homes as defined in NFPA 13D. Consult Spears® FlameGuard° CPVC Fire Sprinkler Products installation Instructions and NFPA Standards for additional applications including air plenum, system risers, concealed, exposed, underground, combustable attic, garage, basement and low pressure dry piping installations. Full Limited Lifetime Warranty FlameGuard° CPVC Fire Sprinkler Products carry a limited lifetime warranty against defects in material or workmanship. Consult Spears® warranty for additional details. _ PROGR�S,�IVEPRODUCT,S'FPO �G.. - SN RS® WOVATfON a4F TECNNOLOGY Visit our web site: wwvv.spearsmfg.com N Cur,FCC @sae 9 LPCB o tJKAS 007 Spears° F[a a uar ° . G The Leader in Innovative C.PVC Fire Sprinkler System Products Pioneer in Molded -in Fetal insert Head Adapters Spears® pioneered the development of the FlameGuard- molded -in -place metal thread insert for connection of sprinkler heads to CPVmC aleta sprinkler &PIP systems, plus Metal FIPT threaded female adapters for p transitions - Developed the Special Reinforced (SR) plead Adapters ® rd® continuous improvement program developed the 1,(, Spears FlameGua 4. E. technology to produce a superior patented plastic .threaded fitting -the .-� ; .; s a patented Special Reinforced (SR) Design. This unique design trees at generated by thermoplastic compression process that equalizes s tapered thread joint make-up. All CPVC plastic body andeads. provide a more uniform construction and improved corrosion resistance. Now, the Revolutionary TorqueSafeTM Gasket Sealed Head Adapter Requires NO Thread Sealants a Eliminates Stress • Prevents Over Tightening Provides Easy Frame Alignment Spears® revolutionary design features a special ps � a �� base of the threads �•, ded-in-place Brass Thread Insert fitted with an elastomer gasket The gasket seal allows a modified thread design that eliminates radial stress and associated problems typical with tapered thread joint make up. The insert is designed to rotate for easy sprinkler frame alignment without over tightening. Patent Pending. Fall Assortment of Specialty Products & Fitting Configurationsth Spears® FlameGuarde provides the specialty fittings needed t d in today s fire sprinkler sy e head adapter for ease . loce e adjustable drop nipple for fine-tuning to finished ceiling height, during installation. Plus, Spears® FlameGuard® line offers sfaCassortment so Male Adapters, Grooved sprinkler oup�g configurations including Tees, Elbows, Flanges, Couplings, p Adapters and Unions, sizes 3/4" through 3 Complete Size Mange of CPVC Pipe k' Spears® FlameGuard° CPVC Fire Sprinkler Pipe is available y , 1� s to ASTM standard for - -` - in sizes 3/4 to 3 . Conform F 442 stun x���-•: '_��r � a M. I. �� SDR 13.5 CPVC pipe. Spears° Solvent Cements & Thread Sealant FlanieGuard'products should be installed using Spears® FS-�eO � �orpompatibility with Flam qua threadedolvent Cement. For joints, use Spears® �LUE 75�' Thread Sealant that has been CPVC Fire Sprinkler Products. Spears® TorqueSafe Gasket Sealed Adapter requires no sealant. Consult sprinkler head manufacturer prior to use. Installation Training Available m Contact Spears° Technical Services for Details ation Instructions, National Flaty1eCuard "Products mustbe installed in accordance and in accordance with local codes. Code requirementsndrinkierPiping Products lfield conditions may differ. Fire Protection Association standards 13, I3R, 1 , It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. F'`SPEAIS � � —no e., _G Manufacturing Company. All Rights Reserved, Printed in the United States of America w ri. SPEAR° ®RpORA UFAC UP'llOFFICE COMPANY 15853 Olden St., Sylmar, CA 91342 a PO Box 9203, Sylmar, CA 91392 (818) 364-1611 o wwa•spearsmfg.com FG-2-0609