FIR2022-0003+Fire_Sprinkler_Equipment_Specification_Sheets+1.12.2022_1.05.09_PM+2617359
FIR2022-0003 RECEIVED Jan 20 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Advanced Fire Protection Submittals For: Paradise Lane Building A 1 Pendent Sprinkler Victaulic V2740 Wht.Rec. 155 2 Dry Pendent Sprinkler Victaulic V3606 Chr. Sleeve & Skirt 3 Dry Sidewall Sprinkler Victaulic V3610 Chr. Sleeve & Skirt 4 Double Check Assembly Ames 2" 2000B 5 Riser Manifold Lansdale Valve 2" 650-375-00260 6 FDIC Guardian 2 '/z"Brass 6014 7 CPVC Pipe & Fittings Spears 8 CPVC Hangers Afcon 510,513&514 9 10 REVIEWED BY CITY OF EDMONDS IT-9 E# 1 Victaulic® FireLock"m Series FL-RES Residential, Quick Response Pendent and Recessed Pendent, ✓0—to U r K3.0 (4.3)9 K4.9 (7.0), K5.6 (8.0)9 K6.9 (9.9) 43.01 1.0 PRODUCT DESCRIPTION J RESIDENTIAL SIN V3010 ORIENTATION_ PENDENT K-FACTORI 3.0 ImpJ4.2 S.L _— - CONNECTION___ MY' NPT/15 mm MAX. WORKING PRESSURE' 175 psi (1200 kPa) GLOBE RE -DESIGNATION GL3010 GLOBE EQUIVALENT NT/RECESSECENDENT SPRINKLERS V2740 V5616 PENDENT PENDENT 491mpJ71 S.I. 561mp./8.1 S.I. 1/2" NPT/15 mm 1/2" NPT/15 mm 175 psi (1200 k_Pa) 175 psi (1200 kPa) - _ GL5610 _ GL4910 - AVAILABLE WRENCHES SPRINKLER V27 Recessed V27 Open End V56 Recessed V56 Open End V34 Recessed - V3010 - -- - - _._. ._._ ■ . _ V2740 ■ ■ ' V5610 ■ ■ V3426 ■ Factory Hydrostatic Test: 100% Q 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL: 7psi/48 kPa/.5 bar Temperature Rating: See tables in section 2.0 1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. V3426 PENDENT 6.91 mpJ9 9 S.I. 3/4" NPT/20 mm 175 psi (1200 kPa) V34 Open End ■ ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 43.01 16382 Rev A Updated 0312021 0 2021 Victaulic Company. All rights reserved. tau 1 iclic' victaulic.com 2.0 CERTIFICATION/LISTINGS Max. Coverage Area Deflector to Listing Agency/ Approved Width X I Ceiling/ Mounting Minimum Nominal K Factor Temperature Ratings Length Flow Pressure Adjustment Surface Distance Spacing Ft. x Ft GPM PSI in in Ft. SIN Imperial S.12 155°F/68°C 175°F/79°C 200°F/93°C m x m Umin kPa mm (mm) m 12 x 12 8 7.1 V3010 3.0 4.2 cULus EU cULus cULus 3.7 x 3.7 30.3 49 th 14 x 14 10 11.1 15 4.3 x 4.3 37.8 76.5 _ 12 x 12 13 7.0 3.7 x 3.7 49.2 48 14 x 14 13 7.0 Smooth Ceilings 4.3 x 4.3 49.2 48 1/2 and 1/4 Recessed 16 x 16 13 7.0 1 S and 20 See Instation V2740 4.9 7.1 cULus cULus N/A 4.9 x 4.9 49.2 48 tally 18 x18 17 12.0 Smooth Ceilings 5. 5.5 x 5.5 64.3 83 Exposed 20 x 20 20 16.7 1/2 Max. 4 (101.6) 6.1 x6.1 75.7 115 15 12 x 12 .- 15 7.2� Beamed Ceilings 3.7 x 3.7 57 - 50 Adjacent 8 j 16 x16~ 19 11.5 per NFPA 13,13D, 2.4 4.9 x 4.9 72 79 1/2 or 13R V5610 5.6 8.1 cULus NA N/A ! 78 x18 21 14.1 15 as appropriate 5.5 x 5.5 79 97 20 x 20 24 18A Beamed Ceilings 4_ 6.1 x 6.1 91 127 In Beam 14 Max. Beam 12 x 12 20 8.4 Depth 3.7 x 3.7 75.7 58 Recessed in Beam: 14 x 14 20 8.4 See Installation 4.3 x 4.3 75.7 58 detail V3426 6.9 9.9 cULus cULus N/A 16 x 16 20 8.4 1/2 and 3/4 4.9 x 4.9 75.7 58 15 and 20 18 x 18 20 8.4 5.5 x 5.5 75.7 58 20 x 20 22 10.2 6.1 x 6.1 83.3 70 NOTE • Listings and approval as of printing. 43.01 16382 Rev A Updated 03/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 11UIiiCr victaulic.com 3.0 SPECIFICATIONS — MATERIAL Deflector: Bronze Bulb Nominal Diameter: 3.Omm Load Screw: Bronze Pip Cap: Bronze Spring Seal Assembly: PTFE coated Beryllium nickel allay Frame: Brass Lodgement Spring: Stainless Steel Installation Wrench: Ductile iron Sprinkler Frame Finishes: • Plain brass • Chrome plated • White polyester painted • Flat black polyester painted • Custom polyester painted NOTE / • For cabinets and other accessories refer to separate sheet. Frame Pip cap and spring seal — Bulb Load screw - Deflector Frame Lodgement spring Pip cap and _ spring seal Bulb Load screw Deflector Frame Pip cap and spring seal — Bulb Load screw Deflector f Lodgement s Pip cap ar spring se Load s< Defl 1W/ 28 mm V3010 27 mm V2740 32 mm V5610 'A� 1711 mm Nominal make -in e'14'7 57 mm M6"111 mm Nominal make -in 23/e"/ 60 mm %"/]I mm Nominal make -in mm Yz"113 mm ake-in 43.01 16382 Rev A Updated 03/2021 m 2021 Victaulic Company. All rights reserved. victaulic.com 3 ✓ctaulid victaulic.com 4.0 DIMENSIONS Y873 mm Min. W/16 mm Max. 1'W/32 mm Min. 1 3a"/44 mm Max. 1725 mm Max. (1/' Adj.) 3/a°/14 mm Max. OW Adj.) 1/476 mm Min. PA6743 mm Max. 13f6'130 mm Min. (1/A" Adj.) 1A6'/24 mm Min. (8/4' Adj.) 2%"/60 m m 2751 mm Hole In ceiling 21516 / 75 mm V3010 2%"/60 mm 2'/51 mm Hole in ceiling 2"A6'/ 75 mm V2740 i //,11A Typical Finished surface ceiling Finished surface 43.01 16382 Rev A Updated 03/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 4 ✓ctauhe victaulic.com 4.0 DIMENSIONS (CONTINUED) 21'e /60 mm 2Y51 mm Hole in ceiling Y//3 mm Min. W/16 mm Max. 11/4'/32 mm Min. 1 - "/44 mm Max. /% 75 mm V5610 24V/60 mm _ 2"/51 mm Hole in ceiling 7/a%22 mm Max. (-Y4' Ad'.) 1 � 6 mm Max. Q/z" Adj.) "/3mm Min. -w,., 1ya'/29 mm Min. ('AAdj.) 1%"/34 mm Min. ('h" Adj.) 17A'/47 mm Max. 211tc"/ 75 mm V3426 Typical ceiling Finished surface Typical ceiling Finished surface 43.01 16382 Rev A Updated 03/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 5 ✓ctaulid victaulic.com r — 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS A WARNING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressur- ized and drained immediately prior to installation, removal, adjust- ment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. I 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from-67°F/-55°C. User Responsibility for Product selection and Su -lability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms "Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. Al products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 43.01 16382 Rev A Updated 03/2021 © 2021 Victaulic Company. All rights reserved. ✓ctauliicr victaulic.com ITEM # 2 FireLock'" Series FL-QR/DRY Standard Coverage, Quick Response Dry, Upright, Pendent and Recessed Pendent Sprinklers K5.6 (8.1), K8.0 (11.5) a / 7 \ M ✓ t_au Lar 45.01 1.0 PRODUCT DESCRIPTION UPRIGHT QUICK RESPONSE DRY ERS SIN ASP V3602 V3604 ORIENTATION _ UPT _ _UPRIGHT K-FACTOR' ImpJ8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION PT/25mm BSPT/1" IGS 1" NPT/25mm BSPT/1" IGS MAX WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) ESCUTCHEON Plain Plain GLOBE EQUIVALENT G1-5639 GL8139 SIN ORIENTATION K-FACTOR' _ CONNECTION MAX WORKING PRESSURE _ ESCUTCHEON_ GLOBE EQUIVALENT SIN ORIENTATION K-FACTOR' CONNECTION MAXWORKING PRESSURE ESCUTCHEON GLOBE EQUIVALENT SPRINKLER_ Upht PENDENT QUICK RESPONSE DRY SPRINKLERS V3606 V3608 PENDENT PENDENT 5.61mp./8.1 S.I. 8.0Imp./11.5 S.I. 1" NPT/25mm BSPT/1" IGS 1" NPT/25mm BSPT/1" IGS 175 psi (1200 kPa) 175 psi (1200 kPa) Plain/Flush/Sleeve and Skirt/Extended Plain/Flush/Sleeve and Skirt/Extended GL5635 GL8135 RECESSED PENDENT QUICK RESPONS DRY SPRINKLERS V3606 PENDE 5.61m . 8.1 S.I. 1" NPT/ m BSPT/1" IGS psi (1200 kPa) Recessed__ GL5635 AVAILABLE GUARDS/SHIELDS V34N36 V34N36 Intermediate Shield ■ V3608 PENDENT 8.0 Imp./11.5 S.I. I" NPT/25mm BSPT/1"IGS 175 psi (1200 kPa) Recessed GL8135 V341V36 Int. Shield/Guard AVAILABLE WRENCHES Sprinkler V36 Recessed V36 Open End f 3116 Hex Bit V-9) qPriP11 t I ----- --■ - ■ Pendent ■ ■ Factory Hydrostatic Test: 100% ® 500 psi/3447 kPa/34 bar Min. Operating Pressure: Pendent: 7 psi/48 kPa/.5 bar Upright: 12 psi/83 kPa/0.8 bar Temperature Rating: See tables in section 2.0 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 45.01 15896 Rev B Updated 06/2021 0 2021 Victaulic Company. All rights reserved. 1 Ac—taul—icr victaulic.com 2.0 CERTIFICATION/LISTINGS c& FM usrm APPROVALS/LISTINGS SIN V3602 V3604 Nominal K Factor Imperial 5.6 8.0 Nominal K Factor S.I 2 8.1 11.5 F Orientation Upright Upright Escutcheon Plain Plain Approved Temperature Ratings F%C° 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 286°F/141'C 286°F/141°C 135°F/57°C 135°F/57°C FM 155°F/68°C 155°F/68°C 200'F/93°C 200°F/93°C CCC 155°F/68°C / %/ APPROVALS/LISTINGS SIN V3606 V3608 V3606 V3_6_08 Nominal K Factor Imperial 5.6 8.0 5.6 8.0 Nominal K Factor S.I 2 8.1 1 11.5 �_ 8.1 11.5 Orientation Pendent Pendent Pendent Pendent Escutcheon Plain, Flush, Slv & Skt, Ext Plain, Flush, Slv & Skt, Ext Recessed Recessed 1 Approved Temperature Ratings F°/C° 135°F/57°C 135°F/57°C 1357F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 286°F/1410C 286°F/141°C — — 135°F/57°C 135°F/57°C 135°F/57°C 135°°F/57°C FM 155°F/68°C 155°F/68°C 155°F/68°C 155F/680C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C CCC 155°F/68°C _i _ — 155°F/68°C — 2 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10. NOTES • Listings and approval as of printing. • Temperatures are listed for all hazards and approved for V3605 and V3606 dry sprinklers up to 48" length. 45.01 15896 Rev B Updated 06/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 A—c-tau—he victaulic.com 3.0 SPECIFICATIONS — MATERIAL Deflector: Brass or Stainless Steel Bulb Nominal Diameter: 3.Omm Split Spacer: Stainless Steel Load Screw: Brass Pip Cap: Stainless Steel Spring Seal Assembly: PTFE coated Beryllium nickel alloy and stainless steel Frame: Brass Inlet Fitting: Brass Outer Tube: Galvanized steel pipe Inner Tube: Stainless Steel Orifice Insert: Stainless Steel Escutcheon/Plate: 1010 - 1018 mild steel and stainless steel Torsion Spring: SST wire Installation Wrench: Ductile iron Sprinkler Frame Finishes: • Plain brass • Chrome plated • White painted3, 4 • Bright White painted3, 4 • Flat black painted3, 4 • Custom painted3, 4 • VC-25055 3 Not available on the Intermediate Level style Pendent. 4 UL Listed for corrosion resistance. 5 UL Listed and FM Approved for corrosion resistance. NOTES • Weather resistant escutcheon available upon request. • For cabinets and other accessories refer to separate sheet. Spring seal assemt Torsion sprir Inlet fittir Inner tut Outer tut Orifice ins, Escutcheon plt Fran Split span Pip cz Bu Load scre Deflect Material Specifications V3606,V3608 Deflector Load screw Bulb Pip cap Split spacer Frame Orifice insert Outer tube Inner tube Escutcheon optional (Not provided) T sion spring Inlet fitting Spring seal assembly Material Specifications V3602,V3604 45.01 15896 Rev B Updated 06/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 3 ✓ctRU1iid' victaulic.com 4.0 DIMENSIONS Tee with same outlet size I I I I as sprinkler thread size. �See'lmportant Installation Information, later in this document 1" NPTBSPT A — — (2"7 — — 51 mm Min.) I / I1/v/ 47 mm Plain Barrel, Threaded V3606,V3608 Tee with same outlet size as sprinkler thread size. I I I I See°Important Installation Information, later in this document. 1" NPTBSPT A 1-W/44 mm Min. j_�_ 38 mm Min.) /Hole in ceiling 47101 mm I Finished surface 21h'/63 mm �-31/V/82 mm---' Sleeve and Skirt, Threaded V3606,V3608 . 1' IGS fitting 0 A —�� (Ns'/ 79 mm Min.) 17A"/ 47 mn Plain Barrel, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40'F/5'C 1' IGS fitting 0 A (2 "/ —1 13A744 mm Min. 67 mm Min.) -- / Hole in ceiling 4"/101 mm fc+ � Finished surface 2'h"/63 mm L �iJ�t�) �3'/a"/82 mm � Sleeve and Skirt, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5'C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Optional Interchangeable Escutcheons Escutcheon W Dimension Adjustment Plain Barrel A=A Flush A= 1/a"/6mm Recessed A=+'/4"/6mm Slv/Skrt A= 13/e"/35mm 45.01 15896 Rev B Updated 06/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 12 ✓ctaulill Victaulic.com 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size as sprinkler thread size. W/"-See'Important Installation ^ I I Information; later in this document. 1 " NPT/BSPT A _ -- (11a'/ Y 11A'/38 mm Min. 44 mm Min.) 1 1 Hole in ceiling 6/mm -1I IIa jceiling 21/ IJ `Finished surface 51 mm Y-- 3776mm— Flush, Threaded V3606,V3608 Tee with same outlet size as er thread size. I i i�5ee Imrporltant Installation Information" later in this document. A1"NPT/BSPTT - - (27 1-�-i/ 51 mm Min.) 1/4'/ 6 mn 2"/ 51 mm l.- 3776 mm - J Intermediate, Threaded V3606,V3608 1" IGS fitting 0 A (211Sd7 75 mm Min.) 1'/z°/38 mm Min. 1 Hole in ceiling YW/ r 6 mm Typical ceiling i 51 mm- Finishedsurface /�T 3"/76 mm Flush, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C 1' IGS fitting 0 A (215V/ -_Y_- 74 mm Min.) 6mm 2"/ 51m 3'!76 mm Intermediate, Gi and V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40"F/5"C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A" Dimension_ Adjustment Plain Barrel A=A Flush A=-14"/6mm Recessed_ A=+1/4"/6mm Slv/Skrt A=-1 3/s'735mm 45.01 15896 Rev B Updated 06/2021 ® 2021 Victaulic Company. All rights reserved. victaul ic.com xACtauIiC victaulic.com 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size as sprinkler thread size. 11 1 See -important Installation Information' later in this document. 1' NPT/BSPT A _— (2'/<°/ /51 mm Min. 57 mmI Min.) Hole in ceiling Typical ceiling 1'%"/47 mm 1%a%28 mm surface 1° IGS fitting O A (3N"/ — �- 87 mm Min.) 2"/51 mm Min. Hole in ceiling Typical ceiling 1W/47 mm 1/"'/28 m Finished surface �-21W/73 mm-1 L �-21A'/73 mm--4 Recessed, Threaded Recessed, Grooved V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C 1 %°/47 mm 1'fi'/38 mm Min. _— —_ Hole in ceiling A (2°/51 mm Min.) 'ilTypical� eili Finished surface 1" NPT/BSPT Tee with same outlet size as sprinkler thread size. i I See'Important Installation — — Information' later in this Installed Dimensions, Threaded document. V3602,V3604 VA7 47 mm _�_ IYz"/38mm ' —�— Hole in c .ng ypical ceiling A QW/80 mm Min.) Finished surface 11' IGS Fitting Installed Dimensions, Grooved V3602,V3604 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A" Dimension Adjustment Plain Barrel A=A A=-'/4"/6mm _Flush_ Recessed A=+'/4"/6mm Slv/Skrt A=-1 3/e°/35mm 45.01 15896 Rev B Updated 06/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com M ✓ctaulicr victaulic.com 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size 1 — — as sprinkler thread size. See°Important Installation Information" later in this document. 7V21' NPT/BSPi A (123i5° 'mm Min. 38 mm Min.) _y_ role in ceiling Typical ceiling Finished surface 5"/128 33/4"/ m 3'h"/89 mm Extended Sleeve and Skirt, Threaded V3606,V3608 1' IGS fitting 0 A (25h"/ 23%"/60 mm Min. 67 mm Min.) _ _ _ _ Hole in ceiling rt Typical ceiling Finished surface 5"/128 mm &I 33A"/96 mm i� 3'h"/89 mm i Extended Sleeve and Skirt, Grooved V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5"C Standard offering includes made -on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A" Dimension Adjustment Plain Barrel A=A Flush A=-Y4"/6mm Recessed A=+�/4"/6mm Slv/Skrt A=-13/e"/35mm 45.01 15896 Rev B Updated 06/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com 7 �CtSUlliC victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS I A WARNING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from—67°F/-550C. 1-40• Viclaulic Firel ockT" Automatic Sprinklers Installa1on [r;l ",' :in n.:nce Instructions I-V9 Style V9 Victaulic FireLockT1 IGST" Installation - Read T" S, rinkler Cou, lin, I1 i .n Instructions User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms 'Patented" or "Patent Pending' refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 45.01 15896 Rev B Updated 06/2021 m 2021 Victaulic Company. All rights reserved. victaulic.com �OtU1U1iO' ITEM # 3 FireLockT" Series FL-QR/DRY/SW Standard Coverage Quick Response Dry Horizontal Sidewall and Recessed Horizontal Sidewall Sprinklers Ai-c-t-aulia K5.6 (8.1 SI), K8.0 (11.5 SO 45.02 1.0 PRODUCT DESCRIPTION HORIZONTAL SIDEWALL QUICK RESPONSE DRY SPRINKLERS SIN V3610 —JEMM6__ V3612 Orientation HORIZONTAL HORIZONTAL K-FACTOR' 5.61mp./8.1 S.I. 8.O Imp./11.5 S.I. CONNECTION I MAX. WORKING PRESSURE_ 1" NPT/25mm BSPT/1" IGS 175 I,si (1200 kPa) 1" NPT/25mm BSPT/1" IGS 175 psi (1200 kPa) Plain/Flush/Recessed Plain/Flush/Recessed ESCUTCHEONS Sleeve and Skirt/Exten_d_ed Sleeve and Skirt/Extended GLOBE EQUIVALENT GL5641 GL8141 RECESSED HORIZONTAL SIDEWALL QUICK RESPONSE DRY SPRINKLERS SIN V3610 V3612 ORIENTATION HORIZONTAL HORIZONTAL K-FACTORI 5.6Im . .. 8.0 ImpJ11.5 S.I. _ CONNECTION V. mm BSPT/1" IGS 1" NPT/25mm BSPT/1" IGS MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) ESCUTCHEONS_ Recessed Recessed GLOBE EQUIVALENT �' GL5641 GL8141 AVAILABLE WRENCHES _ SPRINKLER V36 Recessed V36 Open End She Hex -Bit (V9) _ Sidewall ■ ■ ■ Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL/FM: 7 psi/48 kPa/.5 bar Temperature Rating: See tables in section 2.0 r For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. 1 ictaulic 2.0 CERTIFICATION/LISTINGS Coos FM UM HORIZONTAL SIDEWALL APPROVALS/LISTINGS SIN_ V3_61_02 V3612 Nominal K Factor Imperial 5.6 8.0 �I Nominal K Factor S.I' 8.1 11.5 _ Orientation Horizontal Horizontal Escutcheon Plain, Flush, Slv and Skt, Ext Plain, Flush, Slv and Skt, Ext Approved Temperature Ratings F%C° 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 135°F/57°C 155°F/68°C FM 200°F/93°C - 286°F/141°C RECESSED HORIZONTAL SIDEWALL APPROVALSILISTINGS V3_6102 V3612 _ _SIN Nominal K Factor Imperial 5.6 8.0 Nominal K Factor 1 8.1 11.5 _ _S.I Orientation _ _ Horizontal Horizontal Escutcheon Recessed Recessed Approved Temperature Ratings F°/C° 135°F/57°C 135°F/57"C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 286°F/141"C 286°F/141°C 135°F/57°C FM 155°F/68°C 200°F/93°C r For K-Factor when pressure is measured in Bar, multiply S.I. units by 10. z cULus Listed for light hazard only with deflector 4" - 12' below the ceiling. NOTES • Listings and approval as of printing. • Temperatures are listed for light hazard and approved for V3610 dry sprinklers up to 48' length cULus and 36" for FM. • Temperatures are listed for light and ordinary hazards and approved for V3612 dry sprinklers up to 48' length cULus. 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctsulic victaulic.com 3.0 SPECIFICATIONS - MATERIAL Deflector: Brass or Stainless Steel Bulb Nominal Diamter: 3.Omm Split Spacer: Stainless Steel Load Screw: Brass Pip Cap: Stainless Steel Spring Seal Assembly: PTFE coated Beryllium nickel alloy and stainless steel Frame: Brass Inlet Fitting: Brass Outer Tube: Galvanized steel pipe Inner Tube: Stainless Steel Orifice Insert: Stainless Steel Escutcheon/Plate: 1010 - 1018 mild steel and stainless steel Torsion Spring: SST wire Installation Wrench: Ductile iron Sprinkler Frame Finishes: • Plain brass • Chrome plated • White painted3 • Bright White painted3 • Flat black painted3 • Custom painted3 • VC-25044 3 UL Listed for corrosion resistance. 4 UL Listed and FM Approved for corrosion resistance. NOTES • Weather resistant escutcheon available upon request. • For cabinets and other accessories refer to separate sheet. Split spacer — Pip cap Estucheon plate Inletfitting Bulb Outer tube Torsion spring Load screw — Orifice insert Inner tube Deflector—�\\ i---Spring seal assembly Material Specifications V3610,V3612 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com K, �CtaUllie victaulic.com 4.0 DIMENSIONS Finished ceiling V3610 127305 mm Tge with same outlet size as sprinkler thread size. 47102 mm A See "Important Installation V3612 2 /^ / �2•/ Information, later in this 67152 mm 58 mm 51 mm Min.) document 47102 m m per NFPA 1" NPT I 798 I I I � I Plain Barrel, Threaded — — — —� V3610,V3612 Finished ceiling V3610 12'/305 mm 4'/102 mm V3612 2VV/ A 6'/152 mm 4"/102 mm 56 mm (3Ye./ 79 mm J 1 " IGS fining per NFPA I I � I Plain Barrel, Grooved V3610,V3612 45.02 15954 Rev C Updated 11/2021 ® 2021 Victaulic Company. All rights reserved. victaulic.com M ✓ctaulic victaulic.com 4.0 DIMENSIONS (CONTINUED) Finished ceiling V3610 12"/305 mm 4'/102 mm V3612 6/152 mm 76 mm�_ 4'/102 mm per NFPA IL I` � 1 1 I I I I L 112"7 38 mm Mi Hole in II A./ Typicalwall 6mm A i13/47 64 mm 44 mm Min.) Flush, Threaded V3610,V3612 Finished ceiling V3610 12"/305 mm 4"/102 mm V3612 6"/152 mm 4"/102 mm per NFN 64 mm 75 mm Min.) Flush, Grooved V3610,V3612 45.02 15954 Rev C Updated 1112021 m 2021 Victaulic Company. All rights reserved. victaulic.com 6i Tee with same outlet size r as sprinkler thread size. / See'ImportantInstallation Information; later in this document I 1' IGS fitting ✓ctauliic victaulic.com 4.0 DIMENSIONS (CONTINUED) Finished ceiling V3610 127305 mm 4"/102 mm V3612 6"/152 mm 4"/102 mm per NFN V 127. 4"/1 V; 6"/ll 4"/11 per 15AY41 mm 57 mm Min.) Recessed, Threaded V3610,V3612 Finished ceiling Of nuu rvu11.1 Recessed, Grooved V3610,V3612 45.02 15954 Rev C Updated 11/2021 m 2021 Victaulic Company. All rights reserved. victaulic.com m Tee with same outlet size as sprinkler thread size. See "I mportant Installation Information", later In this document I I V IGS fitting ✓otoulid' victaulic.com 4.0 DIMENSIONS (CONTINUED) 127305 mm 47102 mm • per NFPA ,j V 12"/ 4"/1 V. 6"/1 4"/1 per Typical ceiling 4'/27115 mm A (Ph 3"/77 mm 38 mm Min.) Sleeve & Skirt, Threaded V3610, V3612 Finished ceiling Sleeve & Skirt Grooved V3610,V3612 45.02 15954 Rev C Updated 1112021 © 2021 Victaulic Company. All rights reserved. victaulic.com 7 Tee with same outlet size as sprinkler thread size. See"Important Installation Information, later in this document i 1 " IGS fitting �CtsuliC vini�nlir rnm 4.0 DIMENSIONS (CONTINUED) I-- "-- Finished ceiling 127305 mm 47102 mm 67152 mm 47102 mm per .36 mm Min.) Extended, Sleeve & Skirt Threaded V3610,V3612 Finished ceiling V3610 12'/305 mm 4'/102 mm V3612 m A— 6°/152 mm 4°/102 mm / per NFPA T 23A-/ 60 mm Min. Hole in wall .1— Typical ceiling A 5'1W/133 mm _ (2-% 4"/102 mm 67 mm Min.) Extended, Sleeve & Skirt Grooved V3610,V3612 45.02 15954 Rev C Updated 11/2021 ® 2021 Victaulic Company. All rights reserved. Tee with same outlet size as sprinkler thread size. See 'Important Installation Information; later in this document i 1' IGS fitting victaulic.com 8 JctaUhC victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS D INA1, PW! CW--W) A WART ING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from-67°F/-55°C. 1-40, Victaulic FireLock'" Automatic Sprinklers Installation. n i n In r, i ns -V9 Style V9 Victaulic Firel-ock'" IGS'" Installation- Ready— Sprinkler Coupling Installation Instructions User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms "Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 45.02 15954 Rev C Updated 11/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 9 ✓ctaulic ITEM # 4 Series Double Cbeek Valve Assemblies Features ° Ease ofmaintenance with only one 21'20008HO op«e (50mnm) ° Top entry ~ Replaceable seats and seat discs ° Modular construction " Compact design ° 16"-2^(15-6Dmn) Cast bronze — body construction Ble'OOUDB " Top mounted ball valve test cocks Omm) �'�`` ° Low pressure drop ~ No special tools required Series 2000B �e Check Valvem �mo �o nao be Installed at referenced c,vuu ""..' ° 16"-1^U5-25mnVhova cx to prevent tnuoocm`uwv. supply. Only tee handles those cross -connections identified by local inspection authorities as non -health hazard shall Lmallowed the use ofonapproved double check valve assembly. Cheokwith|omdouthohtyhminQjudndkdionreQardingveficalnriemoUon.hequonoyof Available Models mstingu,other installation requirements. Suffix: These valves meet the requirements ofASSEStd. 1015nnd/VA8mAStd. O510and are B-Ouortatumbal|walveu approved by the Foundation for Cross -Connection Control -and Hydraulic Research at the University Southern California. ern LE�- |eaab�|va|veo ' LH'locking handle ball valves (open ~���� position)position)°cifi~a~~~~~ SH' stainless steel ball valve handles A Doub|oCheckyb}veAaoomb}ynha||ha|notoUedatoaohnoted|000tioh.Tham000mb|y HC ' 21h^ inlet/outlet fire hydrant fitting ohu|| consist of two, positive seating check modules with captured am1nga and rubber seat (2^«m|we) discs. The check module seats and seat discs shall be replaceable. Service of -all internal secured with i steel bolts. The p'af�� --�,---nts ---�dmj- resilient mounted, re- silient Include e ' / . U� union connections oi|�n uau�dto�cocks. � assembly shall �emqu|mme�i�6fASSE81d.1on5 and AWWA Std. C510. Approved by the FomncliGon for Control and �»�e�S�x�� �D��I��� H»�mu|)v Research vt�ei]nkm� | cfSouthomCa�om|aAoomm�ysh�|hennAmes ��ux C� Series ^~~~---- Temperature Company 7�mpon�umRangm83~F-14V"F ` (5"C-60-C) Approvals - �F1'~~'--- ^ Maximum Working Pressure: 175p»| t ASSE.|APMO.CSA,UPC (12bars) A Approved by the Foundation for Cross -Connection Control and Hydraulic Research at the University ofSouthern California. Standards ° Model LBV|unot listed, ASSEStd. 1015.AVVYYAStd. C510 v ULClassified (U8Vmodels only) fu^-u^(19-5»mm) ` 6u9� UL/ |APN\OP831.CSABO4.5 ` Horizontal and vertical 'flow up" approval onall sizes. Job Name Contractor Job Location Approval_-- EnQiouor Cnnteauf6rhPO.No, Approval-__ — __ �� -_- _ -_Roprnoonmovnthe right to channeor MDdify product design, construction, specifications.' or materials vvithoUt prior notice and without incurring any obligation to make such _�--�'------� Ames productspecifications In u.S. customary units and metric are appro)dmate and are provided for reference onlY. for precise measurements, please contact ArnesTechnival Service. Ames reserves changes and modifications miAmes Dimensions - Weights A Suffix HC - Fire Hydrant Fittings dimension "A" = 23'/2" (594mm) Model Size (DN) in. mm Dimensions A B C F G H I Weight In. mm in. mm in. mm in. mm in. mm In. mm in. Imm lbs. k s. 2000B 1h 15 10 254 41A 117 2% 62 5 127 33/s 85 25A& 59 2'/,s 52 4.5 2 2000E M3 3/4 20 11%a 282 4 102 31h 79 6316 157 3% 87 21h 54 15/,6 33 5 2.3 20008 1 25 13'/4 337 5'/s 130 4 102 7'14 191 33/e 85 1IM6 43 1"/16 43 12 5.4 2000E 1'/4 32 '163A 416 5 127 35/1s 84 91h 241 5 127 3 76 2 50 15 6.8 2000B 1'/2 40 163/4 425 47A 124 316 89 93/4 248 519/1s 1 148 3'/s 79 21/4 68 15.86 7.2 2000B 2 50 19'/Z 495 6'/4 159 4 102 133A 340 61/s 156 3% 87 21%6 68 25.75 11.7 Strainer sold separately Capacities As compiled from documented foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California lab tests. 'Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) bars psi %" (15mm) H .6 12 0 .7 10 .5 8 .4 6 N .3 4 d .1 2 a` 0 0 0 /1 4 6 8 10 GP 0 / 7.6 15.2 22.8 30.4 38 / 5 7.5 10 1.5 2.3 3.0 bars psi/ 3/a" (20M Flow Rate w 1.5 22 9 1.2 18 .96 14 a .69 16 a .41 6. .14 2 0 5 10 15 AP 0X 38 57 7.5 2.3 bars psi 1 " (25mm) y 1.1 16 J .8 12 .7 10 y .4 6 E .3 4 IL .1 2 20 25 30 35 78 95 114 133 15 4.6 Flow Rate bars psi 11/4 (32mm) 1 14 H .8 12 .7 10 d .5 6 .4 6 .3 4 n` .1 2 0 0 0 10 20 30 40 50 6D 70 80 90 100 110 120 gpm AP 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps 12 gpm Flow Rate 45.6 ps bars psi 11h(40mm) mps y .8 12 J .7 10 .5 8 a .4 6 .3. 4 a 1 2 AP 10 20 30 40 50 6D 70 80 90 100 110 120 gpm 0 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.0 10 Ips 1.5 2.3 3.0 4.6 mps 2" (50mm) * 50 75 100 125 499----285 380 475 0 5 15 20 AP 0 1 38 57 76 25 30 35 40 45 95 114 133 152 171 50 55 60 qpm 190 209 228 5 7.6 10 1.5 2.3 3.0 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps -- -- _ -, Flow Rate IMP OMAN T.• inquire with governing authorities for local installation requirements. j A M E S E 9001 FIRE A Division of Watts Industries www.amesfirewater.com I CERTIFIED 875 National Drive • Suite #107 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-933.3 ES-A-2000B 0313 ©Ames Co. 2003 Printed in U.S.A. ITEM # 5 BREcco 1040 Broadway, Westiville, NJ 08093 Toll Free: (800) 543-4194 • Fax: (602) 484-9248 www.breccocorp.com RESIDENTIAL RISER Features: • Lead Free stainless steel body construction with all brass trim • Factory assembled • Factory pressure tested at 200psi (13.8 bar) • NPT (female x female) connections • Slim design allows for easy installation • Optimum sensitivity is assured through a dedicated FM approved/UL and ULC Listed Water Flow Detector • Choice of 3 kinds of trim: Basic Trim Basic Trim w/Test & Drain Basic Trim w/Pressure Relief Kit Size Basic Trim Basic Trim w est & Drain Basic Trim w ressure Relief 1" 650-375-00100 1 650-375-00280 650-375-00200 1'/4" 650-375-00120 650-375-00740 650-375-00220 1%" 650-375-00160 650-375-00760 — -375- 2" "650-375-00180 1 650-375-00840 650-375-00260 Im UL ISI® NO. E%t5B16 a— .7S FLOOR CONTROL VALVE ANDTESTASSEMBLY Size A 1 " .75" 1 1/a" 1.02" 1 h" 1.02" 2" n1.02" PROJECT INFORMATION APPROV AL STAMP Project: ❑ Approved Address: ❑ Approved anoted Contractor: ❑ Not a roved Engineer: Remarks: Submittal Data: Notes 1: Notes 2: ITEM # 6 GUARDIAN K(t FIRE EQUIPMENT, INC. MIAMI, FL Ph. 800.327.6584 •Fax 800.827.3869 Project/Location: Architect/Engineer: Contractor: ❑Appropriate Selection DETAIL AND SUBMITTAL SHEET Used as auxiliary connections through which the fire department can pump water to supplement existing water supplies. Provides 250 GPM flow (mini- mum), per 21/2" inlet. Single - inlet connections incorporate a straight-thru, non-clappered de- sign with female NPT outlets. Two and three-way inlet connections feature brass bodies (angle or straight pattern), with integral drop -clapper inlets and female NPT outlets Standard components, all connections: Female hose thread swivel inlets, plugs with chains and identification plate. Cast brass construction, standard. •. No. Outlet and Three -Way Size Connections Clappers. - C7 --- 7" ❑6024 Back 4" x 21/2" x 21/2" 2 115/8" 7'/e" ❑6025 Bottom 4" x 2'/2" x 21h" 2 121/8" 67/8' 71/8" 7" ❑6026 Top 4" x 2'/2" x 21h" 2 121/s" 67/8" 7'/s" 7" ❑6027 Back 6" x 2'/2" x 2'/2" 2 115/8" 77/e' --- 75/s" ❑6028 Bottom 6" x 2'/2" x 2'/2" 2 12'/e" 75/8' 7'/e' 75/8' ❑6029 Top 6" x 21h" x 21/2" 2 121/8" 8" 9" 75/e" ❑6034* Back 4" x 21h" x 21/2" x 21h" 3 17e/." 61/a" --- 7" ❑6037 Back 6" x 21/2" x 21/2" x 21/2" 3 173/e" 61/e" --- 7" ❑6038 Bottom 6" x 21/2" x 21h" x 21h" 3 17%" 75/8' 71/e" 7" ❑6039 Top 6" x 2'/2" x 21h" x 21h" 3 173/e" 75/e" 7'/e" 7" Indentification Plate Lettering AUTO SPKR ❑AUTO SPKR & STANDPIPE [:]STANDPIPE ❑ DRY STANDPIPE *With steel body only. Optional Finish: ❑ -B Polished Brass Threads: ❑ -C Rough Chrome Plated ❑ NST ❑ -D Polished Chrome Plated ❑ Other Date: 111: Nipple Plate (bothers) Swivel ia ° O Inlet Plug 3" 41/s s002 31/2" or 41/." Dia. 21l:" or 3" Plate (by others) Nipple � Swivels ° Inlet Plug 3 /, I T 6014/6015 21b" or 3" 31/z" or 4'/e Dia. Nipple— Plate (by others) Swlvel— o �" Inlet I I� Plug 3/z I -6"-+I 601616017 �A� B ug Th" Nipple (by otherms)—M El Swivel5A, � Inlet Plug s A—�I B L 2'h' Nipple (by others) Swivel Inlet Plug 3 lu 6034-6039 1 A— B� Plate 3'/s Dia. O 9 9" D Plate V. Imo-- 43 Contact factory for current listings and approvals TEM #11, 7 FlameGuard° VE RRE SPRINKLER PRODUCTS FG-2.0609 Cat�lBte ,t�r� of pipe, Fitt��gs �'olve��t �`ei<�elft 11 Corrosion Resistant *. Superto �'lo� & Ease off `' �h,�tallatwror� Spears° FlameGuard® CPVC Fire Sprinkler Products provide a cost effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of installation and quick assembly with readily available tools- CPVC Fire Sprinkler Systems are based on proven cpvcREMai PRoDUcis products that have been in continuous service for overOyears. Spears*FlameGuard° products are approved by UL®, FMB' Global, LPCB and Certified by NSF International for potable water use. Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not Sustain Biological Growth Unhke metal systems, FlameGuard® CPVC products never rust, scale or pit and do not sustain biological growth - a cause of Microbiologically Influenced Corrosion (NIIC) which can destroy metal fire sprinkler systems from the inside out. Superior Flow Characteristics for Lower Friction Losses The smooth -wall interior surfaces of FlameGuard® CPVC systems result in reduced friction loss over metal systems. The design flow characteristics remain constant throughout the life of the product because there is no interior corrosion in the system due to microbiological activity. Pressure Rated to 175psi (1200kpa) @ 150' F (65C °) FlameGuarde CPVC Products are produced in combinations of Schedule 40 and Schedule 80 Fitting configurations con- formingtoASTMF 438 orF 439 standards and FlameGuard° SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F 442 standards. UL® Rated working pressure is 175 psi (1200kpa) @ 150°F (65°C) (LPCB rated to 120T) (49°C). 101.11� w`sny�s ' Easy Installation for Lower Costs FlameGuard° CPVC system installations "gnifially reduce costs over conventional metal piping by y eliminating prefabrication. Systems can be, fully. installed on site using solvent cement joining methods. UL® Listed for U.S. and Caaada in N A 13,13R & 13D Systems FlameGuard° CPVC Fire Sprinkler Products are UL® listed for U.S. and Canada applications for Light Hazard occupancies as defined in NFPA 13, Residential occupancies up to and including 4-stories as defined in NFPA 13R, and Residential occupancies for one and two family dwellings and manufactured homes as defined in NFPA 13D. Consult Spears® FlameGuard® CPVC Fire Sprinkler products Installation Instructions and NFPA Standards for additional applications including air plenum, system risers, concealed, exposed, underground, combustable attic, garage, basement and low pressure dry piping installations. Full Limited Lifetime Warranty FlameGuard° CPVC Fire Sprinkler Products carry a limited lifetime warranty against defects in material or workmanship. Consult Spears® warranty for additional details. PROGRSSSIVEPRODUCTSF.ROM SPEARS O IANOWYOIV & TECHNOLOGY . - Visit our web site: www spearsmfg-corn 4 ceRr��.�c 9 PCB.-' UKAl N a° tnnuae�er+r so} o� srsr�s 007 V.0 The Leader in innovative Spears" FlaimeGuara 0 r r CP�7C Fire Sprinkler System Products Pioneer in Molded -in Metal Insert Read Adapters T. Spears® pioneered the development of the FlameGuard molded -in -place metal thread insert for connection of sprinkler heads to CpVC fire sprinkler systems, plus Metal FIPT threaded female adapters for metal -to -plastic transitions. Developed the Special Reinforced (SR) Read Adapters Spears FllameGuard' continuous improvement program developed the ed plastic .threaded fitting - the technology to produce a superior patent Design. This unique design incorporgene es a patented Special Reinforced (SR) thermoplastic compression process that equalizes stressesrated by tapered thread j oint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Now, the Revolutionary TbrqueSafeTM Gasket Sealed Read Adapter 0 Eliminates Stress ,1 Requires NO Thread Sealants - Provides Easy Frame Alignment - Prevents Over Tightening mo special lded-in-place Brass SpearsO revolutionary design features a e threads. Thread Insert fitted with an elastomer gasket seal at the base of th The gasket seal allows a modified thread design that eliminates radial stress and associated problems typical with tapered thread joint make up. The insert is designed to rotate for easy sprinkler frame alignment without over tightening. Patent Pending. Full Assortment of Specialty Products & Fitting CO figurations s the specialty fittings needed and days rinklmsSpearsO FlameGuardo provide e 0 ting -tuning to finished ceiling height,ringed head adapter for aseoflo a adjustable drop nipple for fine ffers sCa oPsprnklettinduring installation. Plus, SpearsO FlameGuard' line 0 oved Coupling configurations including Tees, Elbows, Flanges, Couplin, ps, Male Adapters, Gro sizes Adapters and Unions, si s 3/4" through 3". . . . . . . Complete Size Range of CPVC Pipe SpearsOlFlameGuard' CPVC Fire Sprinkler Pipe is available V in sizes 3/4" to 311. Conforms to ASTM F 442 standard for SDR 13.5 CPVC pipe. Spears® Solvent Cements & Thread Sealant one-Sorcompatibility dFlameGuard-products should be installed using Spears- FS-5' Thread Sealant that has been tewith FlameGuard joints, use Spears® BLUE 7 CPVC Fire Sprinkler Products. SpearsOTorq ueSateo Gasket Sealed Adapter requires no sealant, Consult sprinkler head manufacturer prior to use. Installation Training Available - Contact Spearso Technical Services for Details FiarneGuard- Products must be installed in accordance with SPeaTso CPVC Fire SprinklerPiping Products Installation Instructions, National Fire Protection Association Standards 13, 13R,1 3D, and in accordance with local codes. Code requirements and field conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. SPEARSO MANUFACTURING COMPANY X CoRpoRATE OFFICE P0 Box 9203, Sylmar, CA 91392 Sylmar, CA 91342 15853 olden St., (818) 364-1611 - wvvw.spearsmfg.com FG-2-0609 nc convriaht 2009 Spears, manufacturing Company. All Rights Reserved, Printed in the United states of America 101 T EM # 8 510 pjpF Cy.V6Ce HANGER SIZE - 3/4" thm 2" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTINGS - Q EX 4231 c S EX 2551 FUNCTION - Use on C.P.V.C., Copper or Steel piping installed per N.F.P.A. 13 13R and 13D. Acts as a hanger and or restrainer. INSTALLATION - Install on top; bottom or side of beam. Hanger spacing by pipe type - per NFPA 13, NOTE: On copper - insulate pipe' UL listed fasteners tested per NFPA 13, as follows. IN WOOD: CPVC and Copper Pipe - #905 listed screw famished with product. Steel Pipe-1/4"xll/2" lag screw - needs no pre -drilling. IN.STEEL: CPVC, Copper and Steel Pipe -1/4" or #14 Tek Screw. IN CONCRETE: a fasteners, CPVC, Copper and Steel Pipe - Shot typ "Only when installed prior to pipe insertion". FEATURES * Offset edge eliminates abrasion. * Retainer dimples secure hanger to pipe during installation. * Required #905 screw has 5/16 hex head - needs no pre -drilling. ORDERING - Part # and pipe size. *CAM ALSO BE USED TO REPLACE - 9520 TIN STRAP 12102 513 PIPE / Csl e i cC. HANGER SING.EE FASTENER SIZE - 3/4" thra 2" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTINGS - �� EX 4231 15 EX 2551 ` FUNCTION - Use on C.P.V.C., Copper or Steel piping installed per N.F.P.A. 13, 13R and 131). Hanger when tab is up and fastener in horizontal position. Restrainer when tab is down and fastener in horizontal position. INSTALLATION - Install on side of beam. Can install on top of beam to stabilize pipe. Hanger spacing by pipe type - per NFPA 13. NOTE: On copper - insulate pipe. UL listed fasteners tested per NFPA 13, as follows. IN WOOD: CPVC and Copper Pipe - #905 listed screw furnished with product. Steel-1/4"xl 1/2" lag screw - needs no pre -drilling. IN STEEL: CPVC, Copper and Steel Pipe -1/4" or#14 Tek Screw. IN CONCRETE: CPVC, Copper and Steel Pipe - Shot type fasteners, "Only when installed prior to pipe insertion" FEATURES * Offset edge eliminates abrasion- * Required #905 screw has 5116 hex head - needs no pre -drilling. ORDERING - Part # and pipe size. Hanger Restrainer Stabilize - Only 12/02 514 OFFSET o PIPE / C-P-V-C. RA Hanger/ Restrainer SIZE - 3/4" thru 2"pipe. MATERIAL - Carbon Steel - FINISH - Mil. Galvanized.. LISTINGS - EX 4231 (pus EX2551 PATENT - Pending. er or Steel piping installed per N.F.P.A. 13, FUNCTION - Use on C.P.V.C., Copp 13R and 13D. Acts as a hanger and restrainer. INSTALLATION - Install on top, bottom or side of beam. Install on 3/8"60mposite wood web joist, using #906 backing nuts.- see drawing. Hanger spacing by pipe type - per NFPA 13. --Snap over pipe then squeeze strap back around pipe allowing pipe to slide freely. NOTE: On copper - insulate pipe. UL listed fasteners tested per NFPA f3, as follows. IN WOOD: SCPVC and teel Pipe - 1/4px11/er 2' lag screw - needs no pre-d screw drilling. product. . IN STEEL: CPVC, Copper and Steel Pipe- 1/4" or #14 Tek Screw. IN CONCRETE: a fasteners, CPVC, Copper and Steel Pipe _ Shot.typ "Only when installed prior to pipe insertion,." FEATURES * 1 1/2" Offset allows elimination of wood blocking. * 3/4" and I" pipe size have common center -line. * Leg design produces superior strength. * Offset edge eliminates abrasion. * Required #905 screw has 5/16 hex head - needs no pre -drilling. - ORDERING - Part # and pipe size. Stabilize - Only 12/02