FIR2024-0061_Fire_Alarm_Equipment_Specification_Sheets_7.23.2024_12.48.36_PM_4395565RED HAWK
)� FIRE PROTECTION
EvBv V%aihin.c
Date: 6/ 5/ 2024
Project: Sherwood Elem. School
Fire Alarm Control Panel Upgreade
Customer: Edmonds School District
Site Address: 22901 106th Ave. W.
Edmonds, WA 98020
Material List of Data Sheets
Item Manufacturer Model # Description
1 Notifier NFS-320 Addressable Fire Alarm Control Panel
(END)
917 134th St. SW, Suite B-3, Everett, WA 98204
Project Manager: James Pan
Cell Phone: 253-330-0736
Fire Alarm System Product Submittals
Pages:
This page intentionally left blank
DN-60637: L
NFS-320SYS(E)
Intelligent Addressable
Fire Alarm System
General
The NFS-320SYS intelligent Fire Alarm Control Panel is part of
the ONYX® Series of Fire Alarm Controls from NOTIFIER.
As a stand-alone small -to -large system, or as a large network,
the ONYX Series of products meet virtually every application
requirement.
The modular design of the ONYX Series makes system plan-
ning easier. The panel can be configured with just a few devices
for small building applications, or networked with many devices
to protect a large campus or a high-rise office block. Simply add
additional peripheral equipment to suit the application. Wireless
fire protection can be added with the SWIFT wireless gateway
and devices.
NOTE: Unless called out with a version -specific "E" at the end of
the part number, "NFS-320SYS" refers to models NFS-320SYS
and NFS-320SYSE, similarly, "CPU-320SYS" refers to models
CPU-320SYS and CPU-320SYSE.
Features
• Certified for seismic applications when used with the appro-
priate seismic mounting kit.
• Approved for Marine applications when used with listed com-
patible equipment,See DN-60688.
• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6
or 7.
• Up to 159 detectors and 159 modules per SLC; 318 devices
maximum.
— Detectors can be any mix of ion, photo, thermal, or multi -
sensor; wireless detectors are available for use with the
FWSG.
— Modules include addressable pull stations, normally open
contact devices, two -wire smoke detectors, notification, or
relay; wireless modules are available for use with the
FWSG.
• Optional FWSG Wireless SWIFT Gateway supports wireless
SLC devices.
Standard 80-character display.
• Network options:
— High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA).
— Standard network for up to 103 nodes (NFS2-3030, NFS2-
640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYX -
Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-
300/400, AFP-1010, and AM2020). Up to 54 nodes when
DVC-EM is used in network paging.
• 6.0 A switch mode power supply with four Class A/B built-in
Notification Appliance Circuits (NAC). Selectable System
Sensor, Wheelock, or Gentex strobe synchronization.
• Built-in Alarm, Trouble, and Supervisory relays.
• VeriFire° Tools online/offline program option. Sort Mainte-
nance Reports by compensation value (dirty detector), peak
alarm value, or address.
• Autoprogramming and Walk Test reports.
• Multiple central station communication options:
— Standard UDACT
— Internet
— Internet/GSM
• 80-character remote annunciators (up to 32).
�J NOTI FI ER"
by Honeywell
NFS-320SYS
• EIA-485 annunciators, including custom graphics.
• Printer interface (80-column and 40-column printers).
• History file with 800-event capacity in nonvolatile memory,
plus separate 200-event alarm -only file.
• Alarm Verification selection per point, with automatic counter.
• Positive Alarm Sequence (PAS) Presignal.
• Silence inhibit and Auto Silence timer options.
• March time/temporal/California two -stage coding/strobe syn-
chronization.
• Field -programmable on panel or on PC, with VeriFire Tools
program check, compare, simulate.
• Full QWERTY keypad.
• Charger for up to 200 hours of standby power.
• Non -alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
• Automatic time control functions, with holiday exceptions.
• Surface Mount Technology (SMT) electronics.
• Extensive, built-in transient protection.
• Powerful Boolean logic equations.
FLASHSCAN 9NTELLIGENTFEATURES
• Polls up to 318 devices in less than two seconds.
• Activates up to 159 outputs in less than five seconds.
• Multicolor LEDs blink device address during Walk Test.
• Fully digital, high -precision protocol (U.S. Patent 5,539,389).
• Manual sensitivity adjustment — up to nine levels.
• Pre -alarm ONYX intelligent sensing — up to nine levels.
• Day/Night automatic sensitivity adjustment.
• Sensitivity windows:
— Ion — 0.5 to 2.5%/foot obscuration.
— Photo — 0.5 to 2.35%/foot obscuration.
— Laser (VIEW — 0.02 to 2.0%/foot obscuration.
— Acclimate® PIusTM — 0.5 to 4.0%/foot obscuration.
— IntelliQuadTM — 1.0 to 4.0%/foot obscuration
— IntelliQuadTM PLUS — 1.0 to 4.0%/foot obscuration
• Drift compensation (U.S. Patent 5,764,142).
DN-606371 • 3/8/17 — Page 1 of 6
• Degraded mode — in the unlikely event that the CPU-
320SYS microprocessor fails, FlashScan detectors revert to
degraded operation and can activate the CPU-320SYS NAC
circuits and alarm relay. Each of the four built-in panel circuits
includes a Disable/Enable switch for this feature.
• Multi -detector algorithm involves nearby detectors in alarm
decision (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing.
• Maintenance alert (two levels).
• Self -optimizing pre -alarm.
FSL-751 (VERY INTELLIGENT EARLY WARNING)
SMOKE DETECTION TECHNOLOGY
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non -smoke signals (U.S. Patent
5,831,524).
• Addressable operation pinpoints the fire location.
• Early warning performance comparable to the best aspiration
systems at a fraction of the lifetime cost.
FAPT-851 ACCLIMATE IPLUS—
L OW -PROFILE INTELLIGENT MULTI -SENSOR
• Detector automatically adjusts sensitivity levels without oper-
ator intervention or programming. Sensitivity increases with
heat.
• Microprocessor -based technology; combination photo and
thermal technology.
• Low -temperature warning signal at 40°F ± 5°F (4.44°C ±
2.77°C).
Up to 32 remote displays
o 0 Lo00
FDU-80 FDU-80
KDM-R2 display
OR
Sample
System
Options
0000 0
FDU-80
A/Q1-11
FSC-851 IntelliQuad
FAPT-851 Acclimate PLU
FSL-751 FlashScan VIE
FSP-851 Photo
FSI-851 Ion
FST-851 Thermal
FSA-8000
etc.
NFS-320SYS
"C" cabinet size shown
FSC-851 I NTELLIQ UAD TM
ADVANCED MULTI -CRITERIA DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO,
and flame).
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance -alarm immunity.
INTELLIGENT FAAST ®DETECTORS FSA-5000, FSA-8000,
FSA-20000 AND FSA-20000P
• Connects directly to the SLC loop of compatible ONYX series
panels.
• Provides five event thresholds that can be individually pro-
grammed with descriptive labels for control -by -event pro-
gramming; uses five detector addresses.
• Uses patented particle separator and field -replaceable filter
to remove contaminants.
• Advanced algorithms reject common nuisance conditions
• FSA-5000 covers 5,000 square feet through one pipe.
• FSA-8000 covers 8,000 square feet through one pipe.
• FSA-20000 covers 28,800 square feet through one to four
pipes.
• FSA-20000P covers 28,800 square feet through one to four
addressable pipes. Supports addressable pipes to pinpoint
location of alarm events.
FCO-851 INTELLIQUAD TM PLUS
ADVANCED MULTI -CRITERIA FIRE/CO DETECTOR
• Detects all four major elements of a fire.
• Separate signal for life -safety CO detection.
• Optional addressable sounder base for Temp-3 (fire) or
Temp-4(CO) tone.
• Automatic drift compensation of smoke sensor and CO cell.
SLC Intelligent Loop 1
DEVICES-
—
o
0 0
o FWSG
NBG-12LXt
�r
XP6/10 1/0 Modules
S
W
FMM-1 FCM-1
IDC
NAC
FRM-1
Relay Contact
EIA-485 2048 annunciator/control points
■ ■ o 0
ACM-8R ACM/AEM-24AT LDM-32
Relay Control LED Annunciator Custom Graphics
Dualphone
lines to
EIA-232 Optional 318-point UDACT Central
1 Station
PRN Series Printer NFS-320SYSdia1-2014—f
Page 2 of 6 — DN-60637:L • 3/8/17
• High nuisance -alarm immunity.
SWIFT WIRELESS
• Self -healing mesh wireless protocol.
• Each SWIFT Gateway supports up to 50 devices: 1 wireless
gateway and up to 49 SWIFT devices.
• Up to 4 wireless gateways can be installed with overlapping
network coverage.
RELEASING FEATURES
• Ten independent hazards.
• Sophisticated cross -zone (three options).
• Delay timer and Discharge timers (adjustable).
• Abort (four options).
• Low-pressure CO2 listed.
VOICE AND TELEPHONE FEATURES
• Integrates with FirstCommand SeriesSee DN-60772.
• Telephone applications require NFC-FFT.
HIGH -EFFICIENCY O FFvNE SWITCHING
3.O A POWER S UPPLy (6.0 A IN A LARM)
• 120 or 220/240 VAC.
• Displays battery current/voltage on panel (with display).
FlashScan, Exclusive
World -Leading Detector Protocol
At the heart of the NFS-320SYS is a set of detection devices
and device protocol — FlashScan (U.S. Patent 5,539,389).
FlashScan is an all -digital protocol that gives superior precision
and high noise immunity.
In addition to providing quick identification of an active input
device, this protocol can also activate many output devices in a
fraction of the time required by competitive protocols. This high
speed also allows the NFS-320SYS to have the largest device
per loop capacity in the industry — 318 points — yet every input
and output device is sampled in less than two seconds. The
microprocessor -based FlashScan detectors have bicolor LEDs
that can be coded to provide diagnostic information, such as
device address during Walk Test.
ONYX Intelligent Sensing
Intelligent sensing is a set of software algorithms that provides
the NFS-320SYS with industry -leading smoke detection capa-
bility. These complex algorithms require many calculations on
each reading of each detector, and are made possible by the
very -high-speed microcomputer used by the NFS-320SYS.
Drift Compensation and Smoothing: Drift compensation
allows the detector to retain its original ability to detect actual
smoke, and resist false alarms, even as dirt accumulates. It
reduces maintenance requirements by allowing the system to
automatically perform the periodic sensitivity measurements
required by NFPA 72. Smoothing filters are also provided by
software to remove transient noise signals, such as those
caused by electrical interference.
Maintenance Warnings: When the drift compensation per-
formed for a detector reaches a certain level, the performance of
the detector may be compromised, and special warnings are
given. There are three warning levels: (1) Low Chamber value,
usually indicative of a hardware problem in the detector; (2)
Maintenance Alert, indicative of dust accumulation that is near
but below the allowed limit; (3) Maintenance Urgent, indicative of
dust accumulation above the allowed limit.
Sensitivity Adjust: Nine sensitivity levels are provided for
alarm detection. These levels can be set manually, or can
change automatically between day and night. Nine levels of pre -
alarm sensitivity can also be selected, based on predetermined
levels of alarm. Pre -alarm operation can be latching or self -
restoring, and can be used to activate special control functions.
Self -Optimizing Pre -Alarm: Each detector may be set for "Self -
Optimizing" pre -alarm. In this special mode, the detector
"learns" its normal environment, measuring the peak analog
readings over a long period of time, and setting the pre -alarm
level just above these normal peaks.
Cooperating Multi -Detector Sensing: A patented feature of
ONYX intelligent sensing is the ability of a smoke sensor to con-
sider readings from nearby sensors in making alarm or pre -
alarm decisions. Without statistical sacrifice in the ability to
resist false alarms, it allows a sensor to increase its sensitivity to
actual smoke by a factor of almost two to one.
Field Programming Options
Autoprogram is a timesaving feature. The NFS-320SYS
"learns" what devices are physically connected and automati-
cally load them in the program with default values for all parame-
ters. Requiring less than one minute to run, this routine allows
the user to have almost immediate fire protection in a new instal-
lation, even if only a portion of the detectors are installed.
Keypad Program Edit (with KDM-R2) The NFS-320SYS, like
all NOTIFIER intelligent panels, has the exclusive feature of pro-
gram creation and editing capability from the front panel keypad,
while continuing to provide fire protection . The architecture
of the NFS-320SYS software is such that each point entry car-
ries its own program, including control -by -event links to other
points. This allows the program to be entered with independent
per -point segments, while the NFS-320SYS simultaneously
monitors other (already installed) points for alarm conditions.
VeriFireO Tools is an offline programming and test utility that can
greatly reduce installation programming time, and increase con-
fidence in the site -specific software. It is Windows® -based and
provides technologically advanced capabilities to aid the
installer. The installer may create the entire program for the
NFS-320SYS in the comfort of the office, test it, store a backup
file, then bring it to the site and download from a laptop into the
panel.
Placement of Equipment
in Chassis and Cabinet
The following guidelines outline the NFS-320SYS's flexible sys-
tem design.
Rows: The first row of equipment in the cabinet mounts in the
chassis shipped with the FACP. Mount the second, third, or
fourth rows of equipment in a CHS-4 Series chassis. Other
options are available; see your panel's installation manual.
Wiring: When designing the cabinet layout, consider separation
of power -limited and non -power -limited wiring as discussed in
the NFS-320SYS Installation Manual.
Positions: A chassis offers four basic side -by -side positions for
components; the number of modules that can be mounted in
each position depends on the chassis model and the size of the
individual module. There are a variety of standoffs and hardware
items available for different combinations and configurations of
components.
KDM-R2 Controls and Indicators
Program Keypad: QWERTY type(keyboard layout, below) .
12 LED indicators: Power; Fire Alarm; Pre -Alarm; Security;
Supervisory; System Trouble; Signals Silenced; Points Dis-
abled; Control Active; Abort; Pre -Discharge; Discharge.
Membrane Switch Controls: Acknowledge/Scroll Display; Sig-
nal Silence; Drill; System Reset; Lamp Test.
LCD Display: 80 characters (2 x 40) with long -life LED back-
light.
DN-606371 • 3/8/17 — Page 3 of 6
Ordering Information
• "Configuration Guidelines" on page 4
• "Networking Options" on page 4
• "Auxiliary Power Supplies and Batteries" on page 4
• "Audio Options" on page 4
• "Compatible Devices, EIA-232 Ports" on page 4
• "Compatible Devices, EIA-485 Ports" on page 4
• "Compatible Intelligent Devices" on page 4
• "Enclosures, Chassis, and Dress Plates" on page 5
• "Other Options" on page 6
CONFIGURATION G UIDELINES
NOTE: Stand-alone and network systems require a main display.
On stand-alone systems, the panel's keypad provides the required
display. On network systems (two or more networked fire panel
nodes), at least one NCA-2, NCS, or ONYXWorks annunciation
device is required.
NCA-2: Network Control Annunciator, 640 characters. On net-
work systems, the NCA-2 connects to (and requires) an NCM or
HS-NCM network communications module. Mounts in a row of
FACP node or in two annunciator positions. Non -English ver-
sions are available. For ULC applications, order NCA-2C; For
marine applications, order NCA-2-M; for non-English Marine
applications, order NCA-2-M and the appropriate KP-KIT-XX.
\� FACP with integral 3.0 A (6.0 A in alarm) power
supp y or an FS-320SYS system. FACP is factory -mounted on
a chassis with one Signaling Line Circuit; includes 80-character
display and documentation kit.Order one per system or as nec-
essary on a network system. (Non -English version also avail-
able: CPU-320SYS-FR.)
CPU-320SYSE: Same as CPU-320SYS but requires 220 VAC,
1.5 A, (3.0 A in alarm).
CPU-320SYS-C: Same as CPU-320SYS for ULC applications.
DP-DISP2: Dress panel for top row in cabinet with CPU-
320SYS/E installed.
BMP-1: Blank module for unused module positions.
BP24: Battery plate, required.
NETWORKING OPTIONS
NCM-W, NCM-F: Standard Network Communications Modules.
Wire and multi -mode fiber versions availableSee DN-6861 .
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network
Communications Modules that can connect to two nodes. Wire,
single -mode fiber, multi -mode fiber, and media conversion mod-
els are availableSee DN-60454.
RPT-W, RPT-F, RPT-WF: Standard -network repeater board with
wire connection (RPT-W), multi -mode fiber connection (RPT-F),
or allowing a change in media type between wire and fiber (RPT-
WF). Not used with high-speed networksSee DN-6971.
ONYXWorks: UL-listed graphics PC workstation, software, and
computer hardwareSee DN-7048 for specific part numbers.
NFN-GW-EM-3: NFN Gateway, embedded See DN-60499.
NWS-3: NOTI•FIRE•NETTM Web ServerSee DN-6928.
CAP-GW: Common Alerting Protocol GatewaySee DN-60756.
VESDA-HLI-GW: VESDAnet high-level interface gateway.See
DN-60753.
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic
and high-speed NOTI•FIRE•NET networks through the NFN
GatewaySee DN-60679.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW.See
DN-60679.
A UXILIARY POWER SUPPLIES AND BATTERIES
ACPS-610: 6.0 or 10 A addressable charging power supplySee
DN-60244.
APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes
of power for peripheral devices. Includes battery input and trans-
fer relay, and overcurrent protection. Mounts on two of four posi-
tions on a CHS-4L or CHS-4 chassisSee DN-5952.
FCPS-24S6/-24S8: Remote 6 A and 8 A power supplies with
battery chargerSee DN-6927.
BAT Series: Batteries. NFS-320SYS uses two 12 volt, 18 to 200
AH batteriesSee DN-6933.
A UDIO OPTIONS
NFC-25/50: 25 watt, 25 VRMS, emergency Voice Evacuation
Control Panel (VECP) with integral commercial microphone, dig-
ital message generator, and single -/dual -channel Class A or
Class B speaker circuitsSee DN-60772.
COMPATIBLEDEVICE4 EIA-232 PORTS
PRN-7: 80-column printerSee DN-60897.
VS4095/S2: Printer, 40-column, 24 V. Mounted in external back -
box See DN-3260.
DPI-232: Direct Panel Interface, specialized modem for
extending serial data links to remotely located FACPs and/or
peripheralsSee DN-6870.
COMPATIBLEDEVICE4 EIA-485 PORTS
ACM-24AT: ONYX Series ACS annunciator - up to 96 points of
annunciation with Alarm or Active LED, Trouble LED, and switch
per circuit. Active/Alarm LEDs can be programmed (by pow-
ered -up switch selection) by point to be red, green, or yellow; the
Trouble LED is always yellowSee DN-6862.
AEM-24AT: Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 pointsSee DN-6862.
ACM-48A: ONYX Series ACS annunciator - up to 96 points of
annunciation with Alarm or Active LED per circuit. Active/Alarm
LEDs can be programmed (by powered -up switch selection) in
groups of 24 to be red, green, or yellow. Expandable to 96 points
with one AEM-48ASee DN-6862.
AEM-48A: Same LED capabilities as ACM-48A, expands the
ACM-48A to 96 pointsSee DN-6862.
ACM-8R: Remote Relay Module with eight Form-C contacts.
Can be located up to 6,000 ft. (1828.8 m) from panel on four
wiresSee DN-3558.
FDU-80: 80-character, backlit LCD display. Mounts up to 6,000
ft. (1828.8 m) from panel. Up to 32 per FACPSee FDU-80 (DN-
6820).
LCD2-80: Terminal and ACS mode. 80-character, backlit LCD
display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32
per FACPSee DN-60548.
LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32;
remote custom graphic driver modulesSee DN-0551.
SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers
SCS-8L, SCE-8L; eight (expandable to 16) circuits (HVAC only).
See DN-4818.
TM-4: Transmitter Module. Includes three reverse -polarity cir-
cuits and one municipal box circuit. Mounts in panel module
position (single -address -style) or in CHS2-M2 position See DN-
6860.
UDACT-2: Universal Digital Alarm Communicator Transmitter,
636 channelSee DN-60686.
UZC-256: Programmable Universal Zone Coder provides posi-
tive non -interfering successive zone coding. Microprocessor -
controlled, field -programmable from IBMR-compatible PCs
(requires optional programming kit). Up to 256 programmable
codesSee DN-3404.
COMPATIBLE INTELLIGENT DEVICES
NOTE: `A" suffix indicates ULC-Listed model.
FWSG Wireless SWIFT Gateway: Addressable gateway sup-
ports wireless SLC devices. Not appropriate for ULC applica-
tionsSee DN-60820.
Page 4 of 6 - DN-606371.3/8/17
FSA-5000: Intelligent FAASTO XS Fire Alarm Aspiration Sens-
ing Technology. Intelligent aspirating smoke detector for applica-
tions up to 5,000 sq.ft. For Canadian applications, order FSA-
5000A.
FSA-8000: Intelligent FAASTO XM Fire Alarm Aspiration Sens-
ing Technology. Intelligent aspirating smoke detector for appli-
cations up to 8,000 sq.ft. For Canadian applications, order FSA-
8000ASee DN-60792
FSA-20000: Intelligent FAASTO XT Fire Alarm Aspiration Sens-
ing Technology. Intelligent aspirating smoke detector for applica-
tions up to 28,800 sq.ft. For Canadian applications, order FSA-
20000ASee DN-60849.
FSA-20000P FAASTO XT PRO Intelligent Aspiration Detector For
applications up to 28,800 sq. ft. (2601 sq. m.) through one to four
addressable pipes. See DN-60792
FSB-200(A): Intelligent beam smoke detectorSee DN-6985.
FSB-200S(A): Intelligent beam smoke detector with integral
sensitivity testSee DN-6895.
FSC-851(A): FlashScan IntelliQuad Advanced Multi -Criteria
DetectorSee DN-60412.
FCO-851(A): FlashScan IntelliQuad PLUS Advanced Multi -Cri-
teria Fire/CO DetectorSee DN-60689.
FSI-851(A): Low -profile FlashScan ionization detectorSee DN-
6934.
FSP-851(A): Low -profile FlashScan photoelectric detectorSee
DN-6935.
FSP-851T(A): Low -profile FlashScan photoelectric detector with
135°F (57°C) thermalSee DN-6935.
FSP-851 R(A): Remote -test capable photoelectric detector for
use with DNR(W) duct detector housingsSee DN-6935.
FST-851(A): FlashScan thermal detector 135°F (57°C).See
DN-6936.
FST 851 R(A): FlashScan thermal detector 135°F (57°C) with
rate-of-riseSee DN-6936.
FST-851H(A): FlashScan 190°F (88°C) high -temperature ther-
mal detectorSee DN-6936.
FAPT851(A): FlashScan Acclimate Plus low -profile multi -sen-
sor detectorSee DN-6937.
FSL-751(A): FlashScan VIEW laser photo detector.See DN-
6886.
DNR(A): InnovairFlex low -flow non -relay duct -detector housing
(order FSP-851/FSP-851 R separately). Replaces FSD-751 PL/
FSD-751 RPLSee DN-60429.
DNRW(A): Same as above with NEMA-4 rating, watertightSee
DN-60429.
B224RB: Low -profile relay baseSee DN-60054.
B224BI: Isolator base for low -profile detectorsSee DN-60054.
B21OLP: Low -profile base. Standard U.S. style. Replaces
B710LPSee DN-60054.
B501(A): European -style, 4" (10.16 cm) baseSee DN-60054.
B20OS: Intelligent programmable sounder base, capable of pro-
ducing a variety of tone patterns including ANSI Temporal 3.
Compatible with sychronization protocolSee DN-60054.
B200SCOA: Based on B200SA, with added CO detector mark-
ings in English/French. For Canadian applications only.
B20OS-LF: Low -frequency version of B200S. See DN-60054.
B200SR: Sounder base, Temporal 3 or Continuous tone.See
DN-60054.
B200SR-LF: Low -frequency version of B200SR. See DN-
60054.
FMM-1(A): FlashScan monitor moduleSee DN-6720.
FDM-1(A): FlashScan dual monitor moduleSee DN-6720.
FZM-1(A): FlashScan two -wire detector monitor moduleSee
DN-6720.
FMM-101(A): FlashScan miniature monitor module.See DN-
6720.
FCM-1(A): FlashScan control moduleSee DN-6724.
FCM-I-REL(A): FlashScan releasing control moduleSee DN-
60390.
FRM-(A): FlashScan relay moduleSee DN-6724.
FDRM-1(A): FlashScan dual monitor/dual relay module.See
DN-60709.
NBG-12LX: Manual fire alarm station, addressable.See DN-
6726.
ISO-X: Isolator moduleSee DN-2243.
ISO-6: Six Fault isolator moduleSee DN-60844.
XP6-C(A): FlashScan six -circuit supervised control module.
See DN-6924.
XP6-MA(A): FlashScan six -zone interface module; connects
intelligent alarm system to two -wire conventional detection
zoneSee DN-6925.
XP6-(A): FlashScan six -relay (Form-C) control module. See
DN-6926.
XP10-M(A): FlashScan ten -input monitor module. See DN-
6923.
SLC-IM: SLC integration module, for VESDAnet detectors.See
DN-60755.
ENCLOSURES, CHASSIS, AND DRESS PLATES
CAB-4 Series Enclosure: The NFS-320SYS mounts in a CAB-
4 Series enclosure (available in three sizes, B-D). The backbox
and door are ordered separately. It requires BP2-4 battery plate.
A trim ring is available for semi -flush mounting.
EQ Series Cabinets: EQ series cabinets will house amplifiers,
power supplies, battery chargers and control modules. EQ cabi-
nets are available in three sizes, "B" through "D".See DN-
60229.
CAB -BM Marine System: Protects equipment in shipboard and
waterfront applications. Also order BB-MB for systems using
100 AH batteries. For a full list of required and optional equip-
ment, seeDN-60688.
CHS-4: Chassis for mounting optional equipment.
CHS-4L: Low -profile four -position Chassis.
DP-1 B: Blank Dress panel. Provides dead -front panel for
unused tiers.
NFS-LBB: Battery Box (required for batteries larger than
26 AH).
NFS-LBBR: Same as above but red.
SEISKIT-CAB: Seismic mounting kit. Required for seismic -certi-
fied applications with NFS-320SYS and other equipment
mounted in CAB-4 Series Enclosures. Includes battery bracket
for two 26 AH batteries.
SEISKIT LBB: Seismic kit for the NFS-LBB. Includes battery
bracket for two 55 AH batteries.
BACKBOXES
NOTE: "C" suffix indicates ULC-Listed model.
ABF-1 B(C) Annunciator Flush Box
ABF-1 DB(C) Annunciator Flush Box with Door
ABF-213 Annunciator Flush Box
ABF-2DB/C Annunciator Flush Box with Door
ABF-4113 Annunciator Flush Box
ABS-1TB Annunciator Surface Box
ABS-1 B(C) Annunciator Surface Box
ABS-2113 Annunciator Surface Box
ABS-211)(C) Annunciator Surface Box
ABS-41D(C) Annunciator Surface Box
BB-UZC: Backbox for housing the UZC-256 in applications where
the UZC-256 will not fit in panel enclosure. Black; for red, order
BB-UZC-R.
DN-606371 • 3/8/17 - Page 5 of 6
O THER OPTIONS
TEMPERATURE AND HUMIDITYRANGES
411: Slave digital alarm communicatorSee DN-6619.
411UDAC: Digital alarm communicatorSee DN-6746.
IPDACT-2/2UD, IPDACT Internet Monitoring Module: Con-
nects to primary and secondary DACT telephone output ports
for internet communications over customer -provided Ethernet
connection. Requires compatible Teldat VisorALARM Central
Station Receiver. Can use DHCP or static I PSee DN-60408.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For mount-
ing an IPDACT-2/2UD onto the panel chassis or CHS-4 series
chassis. Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT
mounting bracket. Red; for black, order IPENC-B.
IPGSM-4G: Internet and Digital Cellular Fire Alarm Communica-
tor. Provides selectable configurable paths: cellular only, IP only,
or IP primary with cellular backup. Connects to the primary and
secondary ports of a DACT For Canadian applications order
IPGSM-4GCSee DH-60769.
NOTE: For other options including compatibility with retrofit equip-
ment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document.
System Specifications
S YSTEM CAPACITY
• Intelligent Signaling Line Circuits ............................................
1
• Intelligent detectors.............................................................
159
• Addressable monitor/control modules ..................................
159
• Programmable software zones ...............................................
99
• Special programming zones ...................................................
14
• LCD annunciators per CPU-320SYS/E
(observe power).....................................................................
32
• ACS annunciators
per CPU-320SYS/E............................ 32 addresses x 64 points
SPECIFICATIONS
• Primary input power, CPU-320SYS board: 120 VAC, 50/60 Hz,
5.0 A. CPU-320SYS/E board: 220/240 VAC, 50/60 Hz, 2.5 A.
• Current draw (standby/alarm):
— CPU-320SYS(E) board: 0.250 A. Add 0.035 A for each NAC
in use.
— KDM-R2 (Backlight on): 0.100 A.
• Total output 24 V power: 6.0 A in alarm.
NOTE: The power supply has a total of 6.0 Amps of available
power. This is shared by all internal circuits. See Installation Man-
ual for a complete current draw calculation sheet.
• Standard notification circuits (4): 1.5 A each.
• Four -wire detector power: 1.25 A.
• Non-resettable regulated power outputs: 1.25 A each.
• Battery charger range: 18 AH — 200 AH. Use separate cabinet
for batteries over 26 AH.
• Float rate: 27.6 V.
CABINET SPECIFICATIONS
NFS-320SYS systems can be installed in CAB-4 Series cabinets
(three sizes with various door options, see DN-6857) .
• Shipping Weight:
— CPU-320SYS: 16.95 lb (7.69 kg).
— CPU-320SYSE: 17.2 lb (7.80 kg).
This system meets NFPA requirements for operation at 0 — 49°C
and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C
± 2°C. However, the useful life of the system's standby batteries
and the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is recom-
mended that this system and its peripherals be installed in an envi-
ronment with a normal room temperature of 15 — 27°C.
A GENCY L ISTINGS AND A PPROVALS
The listings and approvals below apply to the basic control panel.
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.
• UL Listed: S635.
• ULC Listed: S527-11.
• FM Approved.
• CSFM:7165-0028:0243.
• Fire Dept. of New York: COA #6212.
NOTE: For additional information on UL-listed model NFS-320 see
DN-7112. For additional information on UL- and ULC-listed model
NFS-320C, see DN-60085.
Marine Applications: Marine approved systems must be config-
ured using components itemized in this document. (See Main Sys-
tem Components, in "Product Line Information.) Specific
connections and requirements for those components are
described in the installation document, PN 54756. When these
requirements are followed, systems are approved by the following
agencies:
• US Coast Guard 161.002/50/0, 161.002/55/0 (Standard 46
CFR and 161.002).
• Lloyd's Register 11/600013 (ENV 3 category).
• American Bureau of Shipping (ABS) Type Approval.
NOTE: For information on marine applications, see DN-60688.
STANDARDS
The NFS-320SYS complies with the following UL Standards and
NFPA 72, International Building Code (IBC), and California Build-
ing Code (CBC) Fire Alarm Systems requirements:
• UL 864, 9th Edition (Fire).
• UL 1076 (Burglary).
• UL 2572 (Mass Notification Systems). (NFS-320SYS version
20 or higher.)
• ULC S527-11
• LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-
sory).
• AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
• REMOTE STATION (Automatic, Manual and Waterflow)
(requires 4XTMF).
• PROPRIETARY (Automatic, Manual and Waterflow).
Not applicable for FM.
• EMERGENCY VOICE/ALARM.
• OT, PSDN (other technologies, packet switches, data network.
• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
• CBC 2007 (Seismic).
NOTI•FIRE•NETTM, IntelliQuadTM, ONYXWorksTM, and SWIFTTm are
trademarks; and Acclimate® PIUSTM, FirstCommand®, FlashScan®,
Intelligent FAAST®, NOTIFIERO, ONYX®, VeriFire®Tools, and VIEW are
registered trademarks of Honeywell International Inc. Windows® is a
registered trademark of Microsoft Corporation. IBM® is a registered
trademark of IBM Corporation.
02017 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
1S0 �oo� This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
ENGINEERING & MANUFACTURING All specifications are subject to change without notice.
QUALITY SYSTEMS country of origin: USA
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 6 of 6 — DN-60637:L • 3/8/17