FIR2024-0061_Fire_Alarm_Battery_Calculations_7.23.2024_12.48.30_PM_4395564j RED HAWK FIRE PROTECTION Evty v�a%lav�t' Date: 6/5/2024 Project: Sherwood Elem. School Fire Alarm Control Panel Upgreade Customer: Edmonds School District Site Address: 22901 106th Ave. W. Edmonds, WA 98020 NICET CERTIFICATION THESE FIRE ALARM DRAWINGS HAVE BEEN REVIEWED BY: MIKE SERESUN FIRE PROTECTION ENGINEERING TECHNOLOGY FIRE ALARM SYSTEMS - LEVEL III NICETCERTIFICATION# 101668 CERTIFICATION EXPIRES-1110112024 917 134th St. SW, Suite B-3, Everett, WA 98204 Project Manager: James Pan Cell Phone: 253-330-0736 Fire Alarm System Panel Calculations Pages: NOTIFIER" by Honeywell Total Current Primary Non -Alarm - C1 Primary Alarm - C2 0.446 0.835 C1 0.446 A 0.00 0.78 1.56 2.34 3.12 3.90 0.00 1.48 2.96 4.44 5.92 7.40 C2 0.835 A Power Used (Amps) Power Used (Amps) C3 0.426 A C4 0.875 A Device C1 Primary Non -Alarm C2 - Primary Alarm C3 - Secondary Non -Alarm CPU-320 1 x 0.25000 0.25000 1 x 0.25000 0.25000 1 x 0.25000 0.25000 CPS-24 1 x 0.00000 0.00000 1 x 0.00000 0.00000 1 x 0.04000 0.04000 LCD2-80 1 x 0.10500 0.10500 1 x 0.09800 0.09800 1 x 0.04500 0.04500 UDACT-2 Communicator 1 x 0.05200 0.05200 1 x 0.08700 0.08700 1 x 0.05200 0.05200 FSP-851 54 x 0.00030 0.01620 54 x 0.00030 0.01620 FST-851 17 x 0.00030 0.00510 17 x 0.00030 0.00510 NBG-12LX 47 x 0.00038 0.01763 47 IxI 0.00038 0.01763 SLC Loop Device Activation Current 1 x 0.40000 0.40000 Total Non- Total Standby 0.446 Total Alarm Load: 0.835 0.426 Alarm Load: Load: Secondary Only include those additional power supplies that are backed up by the control panels batteries. Device Qty Draw Total Primary Alarm Load - C2 0.835 0.835 CPS-24 1 x 0.040 0.040 NCA2 - Backlight Off with loss of AC 0 x -0.200 APS-6R Power Supplies 0.000 APS2-6R Power Supplies 0.000 ACPS-610 Power Supplies 0.000 FCPS-24S6 Power Supplies 0 FCPS-24S8 Power Supplies HPFF8 Power Supplies ro�0,00E. HPFF12 Power Supplies DAA2 Series I 0.000 DAX Series 0.000 DAA Series 0.000 DS-DB 0.000 FireVoice Panels 0.000 FireVoice Distributed Audio Panels 0.000 N FC-501100 0.000 NFC Distributed Audio 0.000 XPIO 1 0.000 AA-30 0 x 3.000 AA-120 0 x 7.300 Other Power Supply 0 x 0.000 Other Power Supply 0 x 0.000 Other Power Supply 0 x 0.000 Total Standby Alarm Load: 0.875 N OT I F I E R by Honeywell Notifier NFS-320 Fire Alarm Control Panel Protected Premises: Sherwood Elem. School Edmonds School District Address: 22901 106th Ave. W. City: Edmonds State: WA Prepared By: Red Hawk Fire Protection - James Pan Address: 917 134th St SW City: Everett State: WA AC Branch Current Requirements Current required by source to power the fire alarm system. Email: i 5.00 AMPS @ 120 VAC Primary Standby Load 0.45 Amps Current load on the primary power supply during non -alarm conditions. Primary Alarm Load 0.84 Amps Current load on the primary power supply during alarm conditions. Secondary Load Requirements 12.35 Amp Hours Total Secondary Load from the calculation table below. Date: 6/5/2024 Zip: 98020 Phone: 253-330-0736 @redhawkfp.com Zip: 98204 Current Draw Time (hours) Total (AH) Secondary Standby Load 0.426 A x Required Standby Time 24 hours 10.22 Secondary Alarm Load 0.875 A x Required Alarm Time (hours) 0.084 hours 0.07 Total Secondary Load 10.30 Derating factor x 1.2 Secondary Load Requirements (Amp Hours) 12.35 Battery Selection 18 Amp Hours Select batteries from the list below. 18 AH BAT-12180 Battery (12 volt) E Two C Four (two 12VDC sets in parallel) AH Page 1 of 2 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Alarm Load ■ Spare Battery Capacity 1% 190 ■ Secondary Standby Load Spare Battery Capacity SecondaryAlarm Load 31% Secondary Standby Load 68% Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (18AH) are within the charger range of this power supply (18-200AH). Spare Battery Capacity 5.65 Battery Selection AH - Secondary Load Requirements AH Secondary Standby Load 12.27 ISeconclary Standby Load AH *Deratin Factor Secondary Alarm Load 0.09 ISeconclary Alarm Load AH *Deratin Factor Page 2 of 2