APPROVED BLD2024-0255+Plumbing_Plan+2.26.2024_11.35.18_AM+4082619KRUGER BUILDING
TENANT IMPROVEMENT
PLUMBING
LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
LINE TYPE
DESCRIPTION
LINE TYPE
DESCRIPTION
E
END CAP
Ik
BALL VALVE
PT
PRESSURE TRANSDUCER
DOMESTIC COLD WATER
GRWUG
GREY WATER WASTE UNDERGROUND
-
D
CONCENTRIC REDUCER
I ►'J I
BUTTERFLY VALVE
O
AREA DRAIN
- -
DOMESTIC HOT WATER
GRW
GREY WATER WASTE
FLOW ARROW
CHECK VALVE
®
FLOOR CLEANOUT
- - -
DOMESTIC HOT WATER RETURN
GREY WATER WASTE SUDS
D
PIPE DROP
T�
I`LJ'I
CIRCUIT SETTER
®
FLOOR DRAIN
RECLAIMED/RECYCLED WATER
SEWAGE EJECTOR DISCHARGE
RCW
PIPE RISER
><
GATE VALVE
O
FLOOR SINK, SQUARE OR ROUND
INDUSTRIAL COLD WATER
SUMP PUMP DISCHARGE
CW
TEE UP
I T
GLOBE VALVE
®
HUB DRAIN
INDUSTRIAL HOT WATER
CD
CONDENSATE DRAIN
IHW
TEE DOWN
NEEDLE VALVE
O
OVERFLOW DRAIN
IHWR
INDUSTRIAL HOT WATER RETURN
Ar
ARGON
i I i
UNION
RELIEF VALVE
®
ROOF DRAIN
IRRIGATION WATER
CA
COMPRESSED AIR
IRR
30
P-TRAP
PRESSURE REDUCING VALVE
a
ROOF RECEPTOR
TEMPERED WATER
CDA
CLEAN DRY AIR
TW
HOSE BIBB
PRESSURE SUSTAINING VALVE
WALL CLEANOUT
TRAP PRIMERS
IA
LAB / INSTRUMENT AIR
TP
GAS COCK
MOTORIZED 2W-CV
O
INDICATES ITEMS FURNISHED AND INSTALLED
BY MECHANICAL CONTRACTOR
FILTERED WATER
N2
NITROGEN
FW
GM
GAS METER
MOTORIZED BUTTERFLY 2W-CV
O
INDICATES ITEMS FURNISHED AND INSTALLED
BY ELECTRICAL CONTRACTOR
SOFT COLD WATER
02
OXYGEN
SFT
AQUA STAT
MOTORIZED 3W-CV
-H+-)
ELECTRICAL EQUIPMENT CONNECTION
LOCATION BY ELECTRICAL CONTRACTOR
NATURAL GAS SYSTEMS
SG
SPECIALTY GASES
NG
I
B_F P-1
BACKFLOW PREVENTER
DRAIN VALVE WITH END CAP
xX-1
PLUMBING FIXTURE CALLOUT
MEDIUM PRESSURE GAS SYSTEMS
LVAC
LAB VACUUM
MPG
DOUBLE CONTAINMENT PIPE SLEEVE
AIR VENT - AUTO
WCO-1
PLUMBING FIXTURE CALLOUT x1.5
HIGH PRESSURE GAS SYSTEMS
VAC
PROCESS VACUUM
HPG
®
FLEX CONNECTION
AIR VENT - MANUALX
PLUMBING RISER TAG
- - NGV - - - NGV
NATURAL GAS VENT
HV
HOUSE VACUUM
HAMMER ARRESTOR
y
MOTORIZED BUTTERFLY 3W-CV
(DIVERTING)
Q
PLUMBING EQUIPMENT TAG
SANITARY WASTE UNDERGROUND
DIR
DEIONIZED WATER RETURN
FM
FLOW METER TURBINE
f� • If
• /
MOTORIZED BUTTERFLY 3W-CV (MIXING)
#
ACX xx
DETAIL BUBBLE
SANITARY WASTE
DIS
DEIONIZED WATER SUPPLY
®
PUMP
,{�
BALL VALVE WITH HOSE CONNECTION
®
POC
SANITARY WASTE SUDS
ROR
REVERSE OSMOSIS RETURN
1
THERMOMETER
PRESSURE GAUGE WITH SHUT-OFF
VALVE
X%
PIPE SLOPE
- -
- - - - - - - - - - - -
SANITARY VENT UNDERGROUND
ROS
REVERSE OSMOSIS SUPPLY
®
VACUUM BREAKER
I I
PLUG VALVE
( (
REVISION CLOUD
- -
- - - - - - - - - - - -
SANITARY VENT
PCWR
PROCESS COOLING WATER RETURN
INSULATION
MIXING VALVE
REVISION DELTA
STORM DRAIN UNDERGROUND
PCWS
PROCESS COOLING WATER SUPPLY
TEMPERATURE SENSOR & THERMO
WELL
SOLENOID VALVE
O
SHEET NOTE
STORM DRAIN
LWUG
LAB WASTE UNDERGROUND
FM
FLOW METER INLINE
SEISMIC SHUT-OFF VALVE
OVERFLOW DRAIN UNDERGROUND
LW
LAB WASTE
T
PETE'S PLUG
STRAINER WITH BLOW DOWN VALVE
OVERFLOW DRAIN
- - - LV - - - LV - - - LV -
LAB VENT
®
AUTO FLOW CONTROL
STRAINER
GREASE WASTE
GW
ABBREVIATIONS
ABBR.
DESCRIPTION
ABBR
AP
ACCESS PANEL
GPM
AFF
ABOVE FINISHED FLOOR
GD
AHJ
AUTHORITY HAVING JURISDICTION
GW
AD
AREA DRAIN
IE
AW
AUTOMATIC CLOTHES WASHER
IW
BFF
BELOW FINISHED FLOOR
JS
BOP
BOTTOM OF PIPE
BT
BATHTUB
KS
COTG
CLEAN OUT TO GRADE
LV
CTE
CONNECT TO EXISTING
MS
DCW
DOMESTIC COLD WATER
MH
DIA,O
DIAMETER
DN
DOWN
N
DHW
DOMESTIC HOT WATER
NC
DHWR
DOMESTIC HOT WATER RETURN
NIC
NO
E
EXISTING
NTS
ED
EMERGENCY DRAIN
NPT
EL
ELEVATION
EWH
ELECTRIC WATER HEATER
OD
EX
EXPANSION TANK
PD
F
FUTURE
POC
FCO
FLOOR CLEAN OUT
PSI
FD
FLOOR DRAIN
FF
FINISH FLOOR
PSIG
FS
FLOOR SINK
PRV
APPLICABLE CODES
DESCRIPTION
ABBR.
DESCRIPTION
WASHINGTON PLUMBING PROJECTS:
GALLONS PER MINUTE
R
RELOCATED
GUTTER DRAIN
RD
ROOF DRAIN
ALL WORK SHALL BE IN FULL ACCORDANCE WITH APPLICABLE
GREASE WASTE
RCW
RECYCLED WATER
LOCAL, STATE, AND FEDERAL CODES, LAWS AND REGULATIONS
ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WI'
INVERT ELEVATION
SD
STORM DRAIN
BUT NOT LIMITED TO:
INDIRECT WASTE
SOV
SHUT-OFF VALVE
SH
SHOWER
• 2018 INTERNATIONAL BUILDING CODE WITH WA AMENDME
JANITOR SINK
SK
BREAK ROOM/COFFEE SINK
• 2020 NATIONAL ELECTRICAL CODE WITH WA AMENDMENT
SS
SANITARY SEWER/SANITARY WASTE
• 2018 INTERNATIONAL MECHANICAL CODE WITH WA AMEN[
KITCHEN SINK
• 2018 UNIFORM PLUMBING CODE WITH WA AMENDMENTS
TD
TRENCH DRAIN
• 2018 WASHINGTON STATE ENERGY CODE
LAVATORY
TP
TRAP PRIMER
• 2018 INTERNATIONAL FIRE CODE WITH WA AMENDMENTS
TYP
TYPICAL
MOP SINK
MANHOLE
U
URINAL
NEW
V
VENT
ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING
NORMALLY CLOSED
V
VESSEL
ADDITIONAL GUIDELINES WHERE REQUIRED BY CODE:
NOT IN CONTRACT
VTR
VENT THROUGH ROOF
NORMALLY OPEN
VIF
VERIFY IN FIELD
• SHEET METAL AND AIR CONDITIONING CONTRACTORS
NOT TO SCALE
NATIONAL ASSOCIATION (SMACNA)
NATIONAL PIPE THREAD
WCO
WALL CLEAN OUT
• AMERICAN SOCIETY OF HEATING, REFRIGERATION AND
WC
WATER CLOSET
AIR-CONDITIONING ENGINEERS (ASHRAE)
OVERFLOW DRAIN
WM
WATER METER
• AMERICAN SOCIETY OF PLUMBING ENGINEERS (ASPE)
• AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
PLANTER DRAIN
• AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
POINT OF CONNECTION
• NATIONAL FIRE PROTECTION AGENCY (NFPA)
POUNDS PER SQUARE INCH
• OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
POUNDS PER SQUARE INCH(GAUGE)
PRESSURE REDUCING VALVE
SCOPE OF WORK
1. REPLACE (2) LIKE -FOR -LIKE WATER HEATERS.
2. REPLACE (1) DRINKING FOUNTAIN WITH (1) ADA
HI-LO DRINKING FOUNTAIN.
H,
City Of Edmonds
TS
Building Department
rnd�c
PLUMBING
Addresa
21600 HIGHWAY 99
Owner
KRUGER CLINIC
Approved
Date 03/19/2024
Buildinc,
Official Erg
Permit 111
----------------------
umber
-------ml I--mnq4-Qq
DRAWING INDEX
DRAWING INDEX KEY:
NOT INCLUDED WITH ISSUE
NEW OR REVISED
O NO CHANGES
C)
O
U
LLI
LLI
Z
U
_
~
W
I_
LU
�
N
o
N
CDNO.
SHEET
DRAWING TITLE
P0.00
COVER SHEET
P0.01
CONSTRUCTION REQUIREMENTS, EQPT. SCHEDULES
P2.01
1ST FLOOR DEMO & PLUMBING PLAN, PL DETAILS
VICINITY MAP
Stevens Court Apartments
19
F2'76t�h'�S, S�WI
-Id
)onds
iopedic Center
216th St SW
Swedish Oncology
Social Work - Edmonds
1P
2 6th St S•W
IC
9 Sahn- I
JeTT
0Sche
Chan
Emerald City
Engineers, Inc
� I
5300 DENVER AVENUE SOUTH
SEATTLE, WASHINGTON 98108
(206) 787-8500
THE PLANS AND SPECIFICATIONS HEREIN
ARE OWNED BYAND FOR THE SOLE USE OF
ACCO ENGINEERED SYSTEMS, INC. (`ACCO'),
AND MAY NOT BE REPRODUCED OR USED
BY OTHERS FOR ANY PURPOSE UNLESS
AUTHORIZED BYACCO IN WRITING. ACCO
CANNOTACCEPTANYLIABILITY, WARRANTY, OR
OBLIGATION IN THE EVENT OF UNAUTHORIZED USE.
EXPIRES: 11-28-2024
ALL
ORK SUBJECT
O FIELD
IN
ECTION FOR
OD
COMPLIANC
IP�OAN�D JOB SITEI
L1 02/23/2024
No. Date
Revisions
PERMIT SET
Description
7Project
KRUGER BUILDING
TENANT IMPROVEMENT
21600 HIGHWAY 99
EDMONDS, WA 98026
MN IBy
Title
RECEIVED
COVER SHEET
Feb 26 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
M.NOYES
T.TOUTONGHI
Designed By
Checked By
M.NOYES
S. ELLIS
Drawn By
Project Manager
60940540
AS NOTED
Job Number
Scale
PO.00
PIPING VOLUME AND MAXIMUM PIPING LENGTHS
(WSEC C404.3.1)
NOMINAL PIPE SIZE (INCHES)
VOLUME (LIQUID OUNCES PER FT
LENGTH)
MAXIMUM PIPING LENGTH
PUBLIC LAVATORY FAUCETS
OTHER FIXTURES AND APPLIANCES
1/4
0.33
6
50
5/16
0.5
4
50
3/8
0.75
3
50
1/2
1.5
2
43
5/8
2
1
32
3/4
3
0.5
21
7/8
4
0.5
16
1
5
0.5
13
1 1/4
8
0.5
8
1 1/2
11
0.5
6
2 OR LARGER
18
0.5
4
MECHANICAL ID
AND
PLUMBING
PIPE LABELLING
SYMBOL
SERVICE
MARKER LETTERING
MARKER COLOR
LETTER COLOR
DCW
DOMESTIC COLD WATER
POTABLE COLD WATER
GREEN
WHITE
DHW
DOMESTIC HOT WATER
POTABLE HOT WATER
GREEN
WHITE
DHWR
DOMESTIC HOT WATER RETURN
POTABLE HOT WATER RETURN
GREEN
WHITE
LCW*
LAB COLD WATER
NON -POTABLE COLD WATER
YELLOW
BLACK
LHW*
LAB HOT WATER
NON -POTABLE HOT WATER
YELLOW
BLACK
LHWR*
LAB HOT WATER RETURN
NON -POTABLE HOT WATER RETURN
YELLOW
BLACK
SW
SANITARY WASTE
SANITARY WASTE
YELLOW
BLACK
SV
SANITARY VENT
SANITARY VENT
YELLOW
BLACK
NOTES:
1. Install labell on piping mains every 40 ft and at all equipment connections.
2. Wrap piping label end with flow arrow tape, letter sizing per pipe size.
3. All labelling shall be per upc 601.3 / WAC.
4. *Additional labelling shall be per upc 601.3.2 / WAC - Yellow label w/ black letters - CAUTION: NON -POTABLE WATER, DO NOT DRINK
PIPING INSULATION REQUIREMENTS
(PER 2018 WSEC/SEC REQUIREMENTS SECTION C403.10.3)
FLUID
OPERATING
TEMP RANGE (°F)
INSULATION CONDUCTIVITY
NOMINAL PIPE SIZE (IN.)
CONDUCTIVITY
BTU*IN/(H*FT2*°F)
MEAN RATING
TEMP, °F
<1
1 TO < 1 1
1 2 TO < 4
4 TO < 8
> 8
> 350
0.32 - 0.34
250
4.5
5.0
5.0
5.0
5.0
251 -350
0.29 - 0.32
200
3.0
4.0
4.5
4.5
4.5
201 - 250
0.27 - 0.30
150
2.5
2.5
2.5
3.0
3.0
141 - 200
0.25 - 0.29
125
1.5
1.5
2.0
2.0
2.0
105 - 140
0.21 - 0.28
100
1.0
1.0
1.5
1.5
1.5
40 - 60
0.21 - 0.27
75
0.5
0.5
1.0
1.0
1.0
< 40
0.20 - 0.26
75
0.5
1.0
1.0
1.0
1.5
NOTES:
1. FOR PIPING SMALLER THAN 1 1/2" AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES, REDUCTION OF THESE THICKNESSES BY 1" SHALL BE PERMITTED BUT NOT TO
A THICKNESS LESS THAN 1".
2. INSULATION IS NOT REQUIRED FOR CONDENSATE DRAIN PIPING FROM A DX COOLING COIL PER WSEC/SEC 403.10.3 EXCEPTION 3. IT IS RECOMMENDED THAT IF THE DRAIN
PIPING IS LOCATED WITHIN A PLENUM THAT IS NOT USED AS A RETURN AIR PATH, OR OTHER UNCONDITIONED SPACE WITH LIMITED AIRFLOW, THE DRAIN PIPE SHOULD BE
INSULATED WITH 0.5" THICK INSULATION TO PREVENT CONDENSATION ON THE OUTSIDE OF THE PIPE.
PLUMBING PIPING SCHEDULE
SERVICE
LOCATION
SIZE
PIPE TYPE
MAT'L STD
FITTINGS
JOINTS
WORKING
TEST
PRESS.
PRESS.
COLD WATER
ABV GRADE
Y4' - 2"
COPPER TYPE L
ASTM B88
WROUGHT COPPER
WATER SAFE SOLDER
80 PSIG
150 PSIG
HOT WATER
COPPER TYPE L
ASTM B88
TEE DRILL
WATER SAFE SOLDER
COPPER,BRASS
HOT WATER CIRC
COPPER TYPE L
ASME B16.51
COPPER ALLOY
PRESS
2Y2' AND
COPPER TYPE L
ASTM B88
WROUGHT COPPER
SILVER BRAZED
ABOVE
TEE DRILL
WATER SAFE SOLDER
OR FLANGED
SANITARY WASTE
ABV GRADE
1Y4" AND ABV
COPPER DWV
ASTM B306
COPPER DWV
50/50 SOLDER
AMBIENT
10 FT H2O
NO HUB CI
CISPI 301
VENT
NO HUB Cl
NO HUB
SANITARY WASTE
BLW GRADE
1Y4" AND ABV
SCH 40 PVC
ASTM D1785
SCH 40 PVC
SOCKET WELD
AMBIENT
10 FT H2O
VENT
INDIRECT DRAIN
ABV GRADE
Yy, _ 1
COPPER TYPE L
ASTM B88
WROUGHT COPPER
50/50 SOLDER
AMBIENT
N/A
1Yz" AND ABV
COPPER DWV
ASTM B306
WROUGHT COPPER
50/50 SOLDER
WATER HEATER SCHEDULE
ELECTRICAL DATA
GAS
TAG
LOCATION
MANUFACTURER
MODEL No.
DIMENSIONS
GPH @ 80°F
RISE
EWT
LWT
SUPPLY
STORAGE
(GAL)
WEIGHT
(LBS)
REMARKS
E-POWER
KW
V
PH
(Y/N)
(btu)
105C MECHANICAL
BRADFORD WHITE
M-11-120-18-3SF-37
64-1/2"x 30-1/4"Q
93
120
18
1480
DEMO EXISTING UNIT. REPLACE WITH
LIKE -FOR -LIKE.
106D MECHANICAL
AO SMITH
DVE 120
62-114"x 29-112"0
93
120
1
1385
DEMO EXISTING UNIT. REPLACE WITH
LIKE -FOR -LIKE.
CEHD WITH 3 ELEMENTS. 208 VOLT CONVERSION
EWH-1
105C MECHANICAL
BRADFORD WHITE
CEHD120A183*CF
64-11/16" x 30-1/4"0
93
40
120
18
208
3
N
N
119
1425
KIT: 415-51043-78. DIVERSITECH UC3636-3 R-10 MIN
PAD. FIELD VERIFY 208V/3P AVAILABLE ONSITE.
MEETS ASHRAE/IES 90.1 STANDARD. 150 PSI
RATING. GLASS -LINED INTERIOR. ASME RATED T&P
EWH-2
106D MECHANICAL
AO SMITH
DRE-120-18
62-1/4" x 29-1/2"
92
40
120
18
208
3
N
N
119
1385
RELIEF VALVE. DIVERSITECH UC3636-3 R-10 MIN
PAD. FIELD VERIFY 208V/3P AVAILABLE ONSITE.
PLUMBING FIXTURE SCHEDULE
ROUGH -IN
TAG
DESCRIPTION
ITEM
MANUFACTURER
MODEL No.
REMARKS
WASTE
VENT
DHW
DCW
RCW
FLOWRATE
MOTION ACTIVATED INDOOR WALL MOUNT ADA HI-LO STAINLESS STEEL FILTERED WATER
COOLER SHALL INCLUDE AN ASHRAE COMPLIANT, HERMETICALLY SEALED R-134A
REFRIGERATION SYSTEM WITH THERMOSTAT. ADA COMPLIANT TO ICC Al17.1, CSA B651, DOSS
DF-1
DRINKING FOUNTAIN
FOUNTAIN:
HAWS
1202SFH
2"
2"
-
1/2"
-
0.5 GPM
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN WHEN PROPERLY INSTALLED. ASHRAE 18
COMPLIANT CHILLING CAPACITY OF 8.0 GALLON PER HOUR OF 50 DEGREE DRINKING WATER,
BASED ON 80 DEGREE INLET WATER AND 90 DEGREE AMBIENT TEMPERATURE. 115 VOLT, 350
WATT. DIMENSIONS: (L x W x H) 18-3/4" x 34-1/16" x 31-3/4".
PLUMBING GENERAL NOTES
EXCEPT AS MODIFIED BY A WRITTEN CONTRACT SIGNED BY ACCO
MECHANICAL CONTRACTORS (THE "DESIGN -BUILDER"), THE DRAWINGS,
SPECIFICATIONS, AND OTHER DOCUMENTS, INCLUDING THOSE IN
ELECTRONIC FORM PREPARED BY OR FOR AND/OR FURNISHED BY
DESIGN -BUILDER ARE "INSTRUMENTS OF SERVICE." THE DESIGN -BUILDER,
DESIGN -BUILDER'S CONSULTANTS AND OTHER PROVIDERS OF
PROFESSIONAL SERVICES INDIVIDUALLY SHALL RETAIN A FULLY PREPAID,
UNRESTRICTED, PERPETUAL LICENSE IN THE INSTRUMENTS OF SERVICE
AS WELL AS ALL COMMON LAW, STATUTORY AND OTHER RESERVED
RIGHTS, INCLUDING COPYRIGHT IN THOSE INSTRUMENTS OF SERVICE
FURNISHED BY THEM.
THE INSTRUMENTS OF SERVICE FURNISHED BY DESIGN -BUILDER ARE FOR
SOLE USE BY DESIGN -BUILDER IN CONSTRUCTING THE SUBJECT PROJECT.
THE INSTRUMENTS OF SERVICE ARE NOT SUITABLE FOR BIDDING OR
CONSTRUCTING BY OTHER CONTRACTORS. THEREFORE, IF
DESIGN -BUILDER IS NOT RETAINED AS THE DESIGN -BUILD CONTRACTOR TO
PERFORM THE WORK DEPICTED IN THE INSTRUMENTS OF
SERVICE,WITHOUT THE PRIOR WRITTEN CONSENT OF THE DESIGN
BUILDER, THE INSTRUMENTS OF SERVICE MAY NOT BE REPRODUCED OR
USED FOR ANY PURPOSE EXCEPT FOR GENERAL REFERENCE.
DESIGN -BUILDER DISCLAIMS ALL LIABILITY FOR ANY ADAPTATION,
MODIFICATION, OR INTERPRETATION OF THE INSTRUMENTS OF SERVICE
OR FOR ANY OTHER UNAUTHORIZED USE OF THESE INSTRUMENTS OF
SERVICE.
THESE DOCUMENTS WERE PREPARED FOR CONSTRUCTION BY
DESIGN -BUILDER ONLY. DESIGN -BUILDER DEVELOPED THESE DOCUMENTS
WITH ENGINEERING SOLUTIONS AND CONSTRUCTION MEANS AND
METHODS UNIQUE TO DESIGN -BUILDER FOR THE CONSTRUCTION OF THE
SUBJECT PROJECT AND ARE NOT APPROPRIATE FOR OTHERS TO BID OR
BUILD FROM. IN ADDITION, THESE DRAWINGS WERE DEVELOPED FROM
INFORMATION MADE KNOWN TO DESIGN -BUILDER AS OF THE DATE OF THE
DOCUMENT AND WOULD NOT INCLUDE LATER CHANGES ALL PLUMBING
FIXTURES ARE TO BE LOCATED AND MOUNTED PER THE ARCHITECTURAL
FLOOR PLANS AND ELEVATIONS.
3. HOT WATER SUPPLY AND RECIRCULATING PIPING TO BE INSULATED PER
THE PIPE INSULATION REQUIREMENTS TABLE ON THIS SHEET. THE
INSULATION SHALL MEET MAXIMUM FLAME SPREAD: 25, MAXIMUM FUEL
CONTRIBUTED: 50,AND MAXIMUM SMOKE DEVELOPMENT: 50.
4. WATER AND DRAINPIPES AND ANGLE VALVES UNDER LAVATORIES FOR
PERSONS WITH DISABILITIES SHALL BE INSULATED PER ADA STANDARD.
5. WATER HEATERS SHALL BE SECURED IN PLACE WITH (2) 26 GA x 1 1/2"
SHEET METAL STRAP AROUND THE WATER HEATER. STRAPS SHALL BE
INSTALLED ON THE UPPER 1/3 AND LOWER 1/3 OF THE WATER HEATER,
AND SECURED AT EACH END BY A #12 SCREW EMBEDDED MINIMUM 1 1/2"
INTO SOLID WOOD STUDS (OR MIN. 1" INTO METAL STUDS). THE BOTTOM
STRAP SHALL BE LOCATED ABOVE CONTROLS.
6. ALL PLUMBING VENTS SHALL TERMINATE THRU ROOF NOT LESS THAN 121,
ABOVE DECK, NOT LESS THAN 10' FROM ANY OUTSIDE AIR INTAKE OR
OPENING TO BUILDING, AND NOT LESS THAN T FROM ANT EXTERIOR
WALL/PARAPET OF THE BUILDING.
7. BY OTHERS:
A. GENERAL CONTRACTOR: ALL ACCESS PANELS, CUTTING, PATCHING,
FRAMING, FURRING, PAINTING, AND CONCRETE WORK.
B. ELECTRICAL CONTRACTOR: ALL ELECTRICAL SERVICE REQUIRED FOR
PLUMBING EQUIPMENT.
C. MECHANICAL CONTRACTOR: ALL MECHANICAL EQUIPMENT AND DRAIN
PANS.
8. VERTICAL CHECK VALVES SHALL BE SPRING TYPE. HORIZONTAL CHECK
VALVE SHALL BE SWING TYPE.
9. ALL FAUCETS ARE TO BE OPERABLE WITH ONE HAND WITHOUT REQUIRING
GRASPING OR TWISTING. THE FORCE TO OPERATE SHALL NOT EXCEED 5
LBS, TYPICAL ALL FAUCETS.
10. POTABLE WATER SYSTEMS TO BE DISINFECTED AS REQUIRED BY UPC/SPC
AND THE AHJ.
11. SANITARY SEWER WASTE AND LAB WASTE DRAIN LINES TO BE SLOPED AT
MINIMUM 1/4" PER V-0". 4" OR GREATER MAY BE SLOPED AT MINIMUM 1/81,
PER V-0" WITH APPROVAL FROM THE AHJ.
12. POINT OF CONNECTION TO THE EXISTING PIPING SHALL BE VERIFIED IN THE
FIELD. EXACT LOCATION OF POINT CONNECTION MAY VARY BASED ON THE
ACTUAL FIELD CONDITIONS.
13. ALL CLEANOUTS TO BE LOCATED AT ACCESSIBLE LOCATIONS.
14. ALL CONDENSATE PIPING TO BE SLOPED AT 1/8" PER V-0" MIN, AND IN FULL
COMPLIANCE WITH UPC/SPC .
15. FIXTURES WITH SEPARATE HOT AND COLD SUPPLY HANDLES INCLUDING
BUT LIMITED TO 3 COMP SINK, PRE -RINSE SINK, JANITOR SINK, MOP SINK,
SHALL HAVE CHECK VALVES INSTALLED IN THE HOT AND COLD WATER
SUPPLIES TO PREVENT CROSSOVER.
16. FOR RECYCLED WATER:
PROVIDE SIGN PURPLE (PANTONE COLOR #512) BACKGROUND AND SHALL
BE IMPRINTED IN NOMINAL 1/2" HIGH, BLACK UPPER CASE LETTERS, WITH
THE WORDS "CAUTION: RECYCLED WATER, DO NOT DRINK" IN COMPLIANCE
WITH UPC/SPC .
AN INITIAL AND SUBSEQUENT ANNUAL CROSS -CONNECTION INSPECTION
AND TEST SHALL BE PREFORMED ON BOTH POTABLE AND RECLAIMED
WATER SYSTEMS IS REQUIRED PER UPC/SPC .
17. SHOP DRAWING AND ENGINEERING CALCULATIONS FOR ANCHORAGE,
SUPPORT, AND SEISMIC BRACING OF MECHANICAL EQUIPMENT, PIPING,
ETC. NOT SHOWN ON DRAWING SHALL BE PROVIDED BY THE CONTRACTOR
AND SHALL BE SUBMITTED TO THE AHJ AS A DEFERRED SUBMITTAL
PACKAGE.
18. INFRASTRUCTURE NEEDED FOR PIPING AND EQUIPMENT SUPPORT
ATTACHMENTS SUCH AS WALL BACKING, DESIGN OF CONCRETE PADS, ETC.
SHALL BE INDICATED ON STRUCTURAL DRAWINGS.
5300 DENVER AVENUE SOUTH
SEATTLE, WASHINGTON 98108
(206) 787-8500
THE PLANS AND SPECIFICATIONS HEREIN
ARE OWNED BYAND FOR THE SOLE USE OF
ACCO ENGINEERED SYSTEMS, INC. (`ACCO'),
AND MAY NOT BE REPRODUCED OR USED
BY OTHERS FOR ANY PURPOSE UNLESS
AUTHORIZED BYACCO IN WRITING. ACCO
CANNOTACCEPTANYLIABILITY, WARRANTY, OR
OBLIGATION IN THE EVENT OF UNAUTHORIZED USE.
EXPIRES: 11-28-2024
1
02/23/2024
PERMIT SET
MN
No.
Date
Description
By
Revisions
Project
KRUGER BUILDING
TENANT IMPROVEMENT
21600 HIGHWAY 99
EDMONDS, WA 98026
Title
CONSTRUCTION RECEIVED
Feb 26 2024
REQUIREMENTS CILOPMETSERVI
DEVELOPMENT SERVICES
& EQUIPMENT SCHEDPU"C'Es
M.NOYES
Designed By
M.NOYES
Drawn By
60940540
Job Number
T.TOUTONGHI
Checked By
S. ELLIS
Project Manager
AS NOTED
Scale
ELEC
ROOM
105
STORAGE
105B
SCOPE OF WORK
' ELEVATOR
1 Mf H) C, SERVICE
106D 106C
EVH
(D) C
HALLWAY
106A
DEMO EXISTING ELECTRIC WATER HEATER
REPLACE WITH LIKE -FOR -LIKE.
FIELD -VERIFY MFGR OF (D) AND (N) MATCH.
EXISTING ELECTRIC WATER HEATER.
SCE WITH LIK=-EoR-1 IKE.
VERIFY MFG R OF (D) AND (N) MATCH.
WORK
EqH
1
(D)
ELECTRICAL
106E
r
SUITE 110
VACANT
SUITE 100
RAYMOND LIU DDS
RR
104
MAIL
104B
1
103
DEMO EXISTING
DRINKING FOUNTAIN.
MAIN
LOBBY
100
SCOPE OF WORK
SUITE 120
SWEDISH ADMIN
71C
(D)
tl
SUITE 150
SWEDIS[I EDMONDS WOUND
ELEC
ROOM
105
'AGE
5B
TIE INTO (E) DCW, DHW, T&P RELIEF, &
DHWC IF APPLICABLE. SEE P2.01/1 FOR
CONNECTION DETAILS. FIELD -VERIFY (E)
SCOPE
OF WOi
PIPE CONFIGURATION & MATCH.
F1
FIELD -VERIFY MFGR OF (D) AND (N) MATCH.
RE ACE EXISTING ELECTRIC
W TER HEATER WITH LIKE -FOR -LIKE.
AD (N) EXPANSION TANK IF (E) IS
ELEVAT60 SABLE OR MISSING.
M H ICAL
SERVICE ELECTRICAL
106D
106C 106B
E2H
I
HALLWAY
106A
TI I INTO (E) DCW,
W, T&P RELIEF, &
WC IF APPLICAE
LE. SEE P2.01/1 FOR
CONNECTION DET
I S. FIELD -VERIFY (E)
PIPE CONFIGURAT
N &MATCH.
FI FFD-VERIFY MFG
OF (D) AND (N) MATCH.
R PLACE EXISTIN
ELECTRIC
TITER HEATER W
D (N) EXPANSIO
- -
TANK IF (E) IS
Sc0
FD . N�ABLE'¢�l, I,S
NG.
CRAWL CRAWL 1
ACCESS ACCESS P2.o
105D � 105D
1ST FLOOR PLUMBING DEMO PLAN
1 /8"=1 '-0"
115-F TWR ` W
DCW —
120'F DHW — —
I
EXISTING EXPANSION TANK
I
NIPPLE/UNION
T&P TO APPROVED
RECEPTOR
CONNECT NEW WATER HEATER
TO EXISTING DCW, DHW,
DHWR, DRAIN, T&P, ETC.
HOLDRITE OS-120
SEISMIC RESTRAINT
AT )13 AND 3/3 HEIGHT
DRAIN
PAD R-10 MIN
OR STAND, 3" MINIMUM HEIGHT.
FIELD VERIFY IF EXISTING.
1" MINA
AQUASTAT
EXISTING CIRCULATION PUMP
PETE'S PLUG (TYP)
" DRAIN WITH HOSE CONNECTION (TYP)
)Z"BOILER VALVE
W/HOSE CONNECTION
ELECTRIC WATER HEATER DETAIL
EWH
1
(N)
I!QFELVAIOR
RR Sy
104 ��
0
IMAIL REPLACE (E) DRINKING FOUNTAIN WITH
104B (N) WALL -MOUNTED ADA BI-LEVEL
DRINKING FOUNTAIN. DF-1 TO BE
MOUNTED FLUSH WITH ALCOVE WALL TO
F_ ALLOW FOR ADA CLEARANCES.
TIE INTO (E)
DCW, SW, & SV
SUITE 110
VACANT
MAIN
LOBBY
100
SCOPE OF WORK
SUITE 100
RAYMOND LIU DDS
1ST FLOOR PLUMBING PLAN
1 /8"=1 '-0"
48" x 36" ADA CLEARANCE TO BE
CENTERED ON LOW FOUNTAIN.
DF
1
(N)
T-8"
2'-108"
1, 316„
r
O
JIT HIGH UNIT
DRINKING FOUNTAIN HIGH SIDE TO BE
MOUNTED FLUSH WITH ALCOVE WALL
TO ALLOW FOR MIN. 36" CLEARANCE
CENTERED ON LOW UNIT. INSTALL
PER MFR IOM.
TIE INTO (E) DCW, SW, SV. FIELD
VERIFY ALL PLUMBING UTILITIES.
DF-1 ADA CLEARANCE DETAIL
�J
(N)
2
P2.01
1�
SUITE 150
SWEDIS[I EDMONDS WOUND CENTER
� I
5300 DENVER AVENUE SOUTH
SEATTLE, WASHINGTON 98108
(206) 787-8500
THE PLANS AND SPECIFICATIONS HEREIN
ARE OWNED BY AND FOR THE SOLE USE OF
ACCO ENGINEERED SYSTEMS, INC. (`ACCO"),
AND MAY NOT BE REPRODUCED OR USED
BY OTHERS FOR ANY PURPOSE UNLESS
AUTHORIZED BYACCO IN WRITING. ACCO
CANNOTACCEPTANYLIABILITY, WARRANTY, OR
OBLIGATION /N THE EVENT OF UNAUTHORIZED USE.
EXPIRES: 11-28-2024
1
02/23/2024
PERMIT SET
MN
No.
Date
Description
By
Revisions
Project
KRUGER BUILDING
TENANT IMPROVEMENT
21600 HIGHWAY 99
EDMONDS, WA 98026
Title R
1ST FLOOR DEMO- CEIVED
eb 26 2024
PLUMBING P LA N I DEVCITY
ELO MPENT SOERV CES
PLUMBING DETAILS DEPARTMENT
I M.NOYES
1Designed By
M.NOYES
Drawn By
60940540
T.TOUTONGHI
Checked By
S. ELLIS
Project Manager
AS NOTED
IJob Number Scale
SCALE: V = 1'4'
SCALE: 1" = 1'-0"
P2.01