APPROVED FIR2024-0016+Fire_Alarm_Battery_Calculations+2.21.2024_7.32.55_AM+4071985GENERAL NOTES
1. IT IS THE INTENT THAT THE GENERAL NOTES INDICATED HERE BE APPLICABLE ONLY TO THE
CONTRACTED SCOPE OF WORK INDICATED WITHIN THIS DRAWING PACKAGE. NOT ALL NOTES MAY APPLY
TO THIS PROJECT.
2. THESE GENERAL NOTES SHALL NOT BE APPLICABLE TO ANY EXISTING CONDITIONS WITHIN THE FACILITY.
I.E. EXISTING CONDITIONS FOUND TO BE PRESENT PRIOR TO THIS CONTRACT, WORK PREVIOUSLY
PERFORMED BY OTHER FIRE ALARM CONTRACTORS, SEPARATE WORK UNRELATED TO THIS CONTRACT,
SYSTEMS PREVIOUSLY APPROVED UNDER PAST CODES / REGULATIONS, ETC.
3. SIEMENS EQUIPMENT IS UNDERWRITERS LABORATORIES (UL) LISTED FOR POWER LIMITED INSTALLATION.
4. ANY RACEWAY RUNS THAT ARE INDICATED WITHIN THIS DRAWING PACKAGE ARE SHOWN DIAGRAMMATICAL
AND ARE FOR CIRCUITING PURPOSES ONLY. ALL RUNS SHOWN SHOULD NOT SERVE IN ANY WAY AS AN
ACTUAL ROUTING GUIDE FOR INSTALLATION OF RACEWAYS. EXACT INSTALL LOCATION SHALL BE FIELD
DETERMINED.
5. A STAMPED SET OF APPROVED FIRE ALARM PLANS SHALL BE ON THE JOB SITE AND USED FOR
INSTALLATION. ANY DEVIATION FROM APPROVED PLANS, INCLUDING THE SUBSTITUTION OF DEVICES
SHALL BE APPROVED BY THE AUTHORITY HAVING JURISDICTION/ INSPECTOR OF RECORD. SIEMENS
SHALL NOT BEAR ANY ADDITIONAL COST FOR RE -ENGINEERING AS A RESULT OF DEVIATIONS.
6. UNLESS OTHERWISE NOTED, ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT A MAXIMUM HEIGHT
OF 48" ABOVE FINISHED FLOOR TO THE OPERABLE PART.
7. WIRING SHALL NOT BE LOOPED UNDER DEVICE TERMINALS. WIRE MUST BE CUT FOR IN AND OUT RUNS
PRIOR TO INSTALLING UNDER DEVICE TERMINALS.
8. ELECTRICAL CONTRACTOR SHALL BE REQUIRED TO USE COLOR CODE AND/OR WIRE NUMBERS PER
CONTRACT DOCUMENTATION ON ALL WIRING. SUCH IDENTIFICATIONS SHALL BE MADE CONTINUOUS
THROUGHOUT ALL FIRE ALARM CIRCUITS, CONNECTIONS, TERMINATIONS AND AT JUNCTION BOXES.
9. WHERE SHIELDED CABLE IS USED, THE SHIELD SHALL BE CONTINUOUS AND GROUNDED ONLY ONCE AT
THE RESPECTIVE CONTROL PANEL.
10. T-TAPPING IS ONLY ACCEPTABLE ON SLC CLASS B CIRCUITS EXCEPT WHERE CONTRACT SPECIFICATIONS
PROHIBIT.
11. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANELS SHALL BE SUPERVISED TO THE PRINCIPAL
POINT OF ANNUNCIATION. (FIRE ALARM CONTROL PANEL(S) TO SUPERVISE ANNUNCIATOR PANEL(S),
SUB-PANEL(S), ALL CIRCUITS AND INITIATING DEVICES).
12. FIRE ALARM SIGNAL SHALL MEET ANSI S3.41, AUDIBLE EMERGENCY EVACUATION SIGNAL (TEMPORAL
PATTERN). FIRE ALARM AUDIBILITY SHALL BE NO LESS THAN 15db (PUBLIC MODE) OR 1OdB (PRIVATE
MODE) ABOVE AMBIENT SOUND THROUGHOUT THE AREA OF ALARM.
13. WHERE MORE THAN TWO VISUAL APPLIANCES ARE IN THE SAME FIELD OF VIEW, THEY SHALL BE
SYNCHRONIZED IN ACCORDANCE WITH NFPA 72.
14. CEILING MOUNTED VISUAL NOTIFICATION APPLIANCES SHALL BE MOUNTED BELOW VISUAL OBSTRUCTIONS,
AND WHEN THESE APPLIANCES ARE MOUNTED ABOVE 10' A.F.F., THEY SHALL BE DERATED OR
PROVIDED WITH PERFORMANCE -BASED ALTERNATIVE IN ACCORDANCE WITH NFPA 72.
15. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER INSTALLATION INSTRUCTIONS
AND LISTINGS. MISAPPLICATION OF EQUIPMENT AND SUCH, VOIDS ALL WARRANTIES EITHER EXPRESSED
OR IMPLIED WITH REGARDS TO LOSS, DAMAGE, LIABILITIES AND/OR SERVICE PROBLEMS.
16. UNLESS NOTED OTHERWISE ALL WIRING AND INSTALLATION METHODS SHALL CONFORM TO APPLICABLE
ELECTRICAL CODE. MINIMUM SIZE OF 3/4" METALLIC RACEWAY SHALL BE INSTALLED.
17. EFFORTS MUST BE PLACED ON MINIMIZING UNNECESSARY WIRE RUNS WITHIN DEVICE BACKBOXES. DO
NOT INSTALL WIRE WITHIN A BACKBOX THAT DOES NOT SERVE ITS CORRESPONDING DEVICE AND WHICH
MAY INHIBIT ITS PROPER INSTALLATION. GOOD WIRING/INSTALLATION PRACTICES MUST BE ADHERED TO
AT ALL TIMES.
18. AS FIELD CONDITIONS DICTATE ACTUAL RACEWAY INSTALLATIONS, DEVICE BACK BOXES AND JUNCTION
BOXES SHALL BE SIZED PER FIELD INSTALLING CONDITIONS. DEVICE BACK BOX SIZES INDICATED WITHIN
THIS DRAWING PACKAGE ARE MINIMUM REQUIREMENTS ONLY. AN INCREASE IN BACK BOX DEPTH,
ADDITION OF EXTENSION BOX/RING, ETC. MAY BE REQUIRED IN ORDER TO PROPERLY ACCOMMODATE
FOR WIRE QUANTITIES INSTALLED WITHIN THE RACEWAY.
19. THE INSTALLATION OF DEVICE BACKBOXES & WIRE SHALL BE SIZED AND INSTALLED PER APPLICABLE
ELECTRICAL CODE. IN ADDITION SUCH BOXES & WIRE SHALL BE INSTALLED IN A MANNER AS TO
ALLOW FOR THE EASE OF DEVICE INSTALLATION & FUTURE MAINTENANCE. THE INSTALLATION OF
DEVICES WHICH REQUIRE EXCESSIVE FORCE OR THE PINCHING OF WIRES IN ORDER TO PROPERLY SEAT
THE DEVICE TO ITS FINISHED SURFACE MAY RESULT IN GROUND FAULTS OR OTHER SYSTEM TROUBLES,
AND SHALL BE CONSIDERED AN UNACCEPTABLE INSTALLATION STANDARD.
20. DO NOT APPLY POWER TO CONTROL PANEL(S) UNTIL SIEMENS AUTHORIZED PERSONNEL HAVE VERIFIED
THE SYSTEM INSTALLATIONS. UPON SATISFACTORY COMPLETION OF THEIR INSPECTION, POWER WILL BE
APPLIED TO THE CONTROL PANEL(S). SIEMENS ASSUMES NO LIABILITY FOR ANY DAMAGE TO THE
EQUIPMENT SUPPLIED IF POWER IS APPLIED TO THE CONTROL PANEL(S) PRIOR TO INSPECTION OF THE
INSTALLATION BY SIEMENS AUTHORIZED PERSONNEL.
21. ALL 120VAC CIRCUITS FEEDING FIRE ALARM EQUIPMENT SHALL BE FROM A DEDICATED CIRCUIT MARKED
AS 'FIRE ALARM', MARKED RED, AND PROVIDED WITH A BREAKER LOCK -ON DEVICE.
22. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION
INSTRUCTIONS.
23. IN ACCORDANCE WITH NFPA 72, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION
CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY
HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED
PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED
24. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES, EXACT
ROUTING OF THE CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO
SUIT CONDITIONS. ALL THE CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.
25. FIRE ALARM CABLE INSTALLED IN UNDERGROUND RACEWAYS OR OTHER WET LOCATIONS SHALL BE
RATED/LISTED FOR WET LOCATIONS.
(E) CENTRAL MONITORING STATION INFORMATION
MONITORING COMPANY: SIEMENS INDUSTRY INC
CENTRAL STATION UL NO.# 603961 -026
ADDRESS: 8600 NORTH ROYAL LANE, SUITE 100
CITY / STATE / ZIP CODE: IRVING, TEXAS 75063
TELEPHONE NUMBER: (866) 552-7823 \ (877) 859-4135
FILE NO.: S7091
CCN: UUFX
(E) CIRCUIT INFORMATION
SIGNALING LINE CIRCUIT (SLC): CLASS B
NOTIFICATION APPLIANCE CIRCUITS (NAC): CLASS B
PATHWAY SURVIVABILITY: LEVEL 1
SPEAKER CIRCUIT VOLTAGE: 70V
SIEMENS CONTACT INFORMATION
PROJECT MANAGER: COLIN PINE
EMAIL: COLIN.PINE@SIEMENS.COM
SALES EXECUTIVE: JOHN MCNETT
EMAIL: JOHN.MCNE-FF@SIEMENS.COM
CONTRACTOR INFORMATION
CONTRACTOR NAME: CHARTER CONSTRUCTION, INC,
ADDRESS: 980 S, HARNEY STREET,
S EATTLE,
WA 98108
APPLICABLE CODES & REGULATIONS
STATE OF WASHINGTON ADOPTED CODES
-WASHINGTON STATE BUILDING CODE: 2018 EDITION
-WASHINGTON STATE FIRE CODE: 2018 EDITION
-WASHINGTON STATE MECHANICAL CODE: 2018 EDITION
-WASHINGTON STATE ENERGY CODE: 2018 EDITION
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA
-NFPA 70: 2017 EDITION
-NFPA 72: 2016 EDITION
CHECK LIST FOR START UP
THE FOLLOWING IS A LIST OF CRITERIA THAT MUST BE MEET PRIOR TO START UP
❑ MARK-UP THE SIEMENS FIRE SAFETY SHOP DRAWINGS, SHOWING THE ACTUAL WIRE RUNS. NOTE THAT
ANY DISCREPANCIES/CHANGES BETWEEN THE ACTUAL CONDITIONS AND THE SYSTEM DRAWINGS SHOULD
BE NOTED FOR INCLUSION ON THE FINAL RECORD DRAWINGS.
❑ ALL DEVICES HAVE BEEN INSTALLED AND TERMINATED PROPERLY.
❑ CONTACTED SIEMENS FIRE SAFETY PROJECT MANAGER 14 DAYS PRIOR TO SCHEDULED START UP.
❑ ALL FIELD DEVICES INCLUDING DETECTORS, MODULES, NOTIFICATION APPLIANCES BOTH VISUAL AND
AUDIBLE ARE ADDRESSED AND OUTPUT SET (AS REQUIRED) AND INSTALLED.
❑ IF YOUR SYSTEM IS BEING FURNISHED WITH A DIALER, APPLICABLE AMOUNT OF RJ31 X PHONE JACKS
MUST BE INSTALLED WITHIN 3 FEET OF THE MAIN FIRE ALARM CONTROL UNIT. THESE PHONE LINES
MUST BE CONNECTED BEFORE ALL BUILDING PHONE EQUIPMENT (NO "9" PREFIX), AND SHOULD HAVE
NO DIAL -OUT RESTRICTIONS. PROVIDE THE SIEMENS PROJECT MANAGER WITH A CUSTOMER EMERGENCY
CALL LIST. IF MONITORING NOT PROVIDED BY SIEMENS, THEN FOLLOWING INFORMATION MUST ALSO BE
OBTAINED PRIOR TO START UP: CENTRAL STATION ACCOUNT NUMBER, RECEIVER PHONE NUMBERS,
CENTRAL STATION VOICE LINE NUMBER, AND ALARM COMPANY PHONE NUMBER.
❑ CHECK HERE IF NOT APPLICABLE
CHECK FIELD WIRING WITH AN OHM METER:
ALL FIRE ALARM CIRCUITS SHOULD BE COMPLETED AND TESTED BEFORE THE ARRIVAL OF THE FIRE ALARM
AUTHORIZED PERSONNEL. CIRCUITS MUST BE FREE OF OPENS, SHORTS, AND GROUND FAULTS BEFORE
BEING CONNECTED TO THE SYSTEM. CIRCUITS SHOULD HAVE END OF LINE RESISTORS INSTALLED BEFORE
TESTING THEM. A WRITTEN CONFIRMATION SHALL BE PROVIDE TO SIEMENS BY THE INSTALLER
ACKNOWLEDGING ALL CIRCUITS HAVE BEEN TESTED. ADHERENCE TO THIS PRACTICE WILL SAVE TIME AND
MONEY FOR ALL CONCERNED PARTIES. IF IT IS A NAC CIRCUIT, THE RESISTOR IS WITH THE EQUIPMENT THAT
CONTROLS THAT CIRCUIT.
A GROUND FAULT IS A CONDUCTOR THAT IS CONNECTED TO GROUND. THEY CAN OCCUR FROM SKINNED
INSULATION OR INTERNAL DEVICE FAILURES. FIRE ALARM SYSTEMS MONITOR BOTH THE POSITIVE AND
NEGATIVE CONDUCTORS FOR SHORTS TO GROUND. SHORTS CAN BE DETECTED BY USING A CONTINUITY
DETECTOR OR AN OHMMETER. SIMPLY CONNECT ONE LEAD OF YOUR METER TO A GOOD GROUND SOURCE
AND THE OTHER TO THE CONDUCTOR YOU ARE TRYING TO TEST. THE METER SHOULD GIVE AN INDICATION
OF AN OPEN IF THE CIRCUIT IF FREE FROM A FAULT. MEG OHM GROUND FAULTS MAY INDICATE THE
PRESENCE OF WATER IN CONTACT WITH SYSTEM WIRING. ALL SYSTEM FIELD WIRING MUST BE FREE OF
GROUNDS AND SHORTS, BEFORE THE START UP.
❑ MEASURE EACH CONDUCTOR OF THE ADDRESSABLE LOOP (SLC) TO GROUND, CONDUCTOR TO
CONDUCTOR, CONDUCTOR TO SHIELD, AND SHIELD TO EARTH. THE RESISTANCE SHOULD BE GREATER
THAN 1 MEGA OHM. NOTE LINE TO LINE MEASUREMENTS REQUIRE ONE END OF THE PAIR TO BE
SHORTED. STRAY VOLTAGES SHOULD BE LESS THAN 1 VDC/AC. RECORD THE READINGS.
❑ MEASURE EACH CONDUCTOR OF THE NOTIFICATION APPLIANCE CIRCUIT (NAC) TO GROUND, AND
CONDUCTOR TO CONDUCTOR. THE RESISTANCE SHOULD BE GREATER THAN 1 MEGA OHM, WITHOUT THE
END OF LINE RESISTOR. STRAY VOLTAGES SHOULD BE LESS THAN 1 VDC/AC.
❑ MEASURE ACROSS THE CONDUCTORS OF A NOTIFICATION APPLIANCE CIRCUIT(NAC), YOUR READING
SHOULD BE EQUIVALENT TO THE VALUE OF THE END OF LINE RESISTOR INSTALLED AT THE LAST DEVICE.
IF THE MEASUREMENTS ARE NOT WITHIN THE ACCEPTABLE VALUES, THEN THE CIRCUIT WIRING HAS A SHORT,
OPEN, OR GROUND FAULT, AND IS NOT READY FOR START UP!
DEVICE CONDUIT WIRING GUIDELINE
INSTALLATION GUIDELINES: DEVICE BACKBOXES SHOULD NOT CONTAIN WIRE THAT DOES NOT SERVE ITS
ASSOCIATED DEVICE. TO PREVENT BACKBOX OVERFILL & IMPROPER DEVICE INSTALL, ALL EFFORTS MUST
BE MADE TO PREVENT UNNECESSARY WIRE FILL WITHIN DEVICE BACKBOXES. MOUNTING SPECIFICATIONS
INDICATED WITHIN THE EQUIPMENT & DEVICE LEGEND ARE MINIMUM RECOMMENDATIONS. JUNCTION
BOXES, EXTENSION RINGS, ETC. MUST BE INSTALLED AS NEEDED AND AS FIELD CONDITIONS DICTATE.
FLOOR PLAN EXAMPLE:
EXAMPLE DEFINED:
1A,4B,2C,1D 1A,4B,2C,1D 1A,4B,2C,1D
1A,46,2C,1D 1A,4B,2C,1D 1A,4B,2C,1D
15CD C
26,2c 2A*
p *-WHERE T-TAPPING
15CD C IS ALLOWED, THIS CAN
BE1AINCLASS B
DEPICTION OF A DIAGRAMMATICAL INSTALL SHOWN ON FLOOR PLAN
I ACTUAL FIELD INSTALLATION SLC CIRCUITS
DEVICE NUMBERING LEGEND
ADDRESSABLE ALARM INITIATING DEVICES
EXAMPLE:
@S 1-01 DEVICE ADDRESS
DEVICE INDICATES DEVICE ADDRESS
SYMBOL INDICATES CARD NUMBER
ABOVE EXAMPLE MEANS:
SMOKE DETECTOR, CARD 1, DEVICE ADDRESS 01
(E) CONDUIT WIRE FILL CHART
ELECTRICAL
FLEXIBLE METALLIC
RIGID METALLIC
FLEXIBLE LIQUIDTIGHT
METALLIC CONDUIT
CONDUIT
CONDUIT
METALLIC CONDUIT
CONDUIT
INTERNAL
*MAXIMUM
INTERNAL
*MAXIMUM
INTERNAL
*MAXIMUM
INTERNAL
*MAXIMUM
TRADE SIZE
DIAMETER
FILL-40%
DIAMETER
FILL-40%
DIAMETER
FILL-40%
DIAMETER
FILL-40%
3/4"
0.8240
0.2130
0.8240
0.2130
0.8360
0.2200
0.8300
0.2160
1 "
1.0490
0.3460
1.0200
0.3270
1.0630
0.3550
1.0540
0.3490
1 1 /4"
1.3800
0.5980
1.2750
0.5110
1.3940
0.6100
1.3950
0.6110
1 1 /2"
1.6100
0.8140
1.5380
0.7430
1.6240
0.8290
1.5880
0.7920
2"
2.0670
1.3420
2.0400
1.3070
2.0830
1.3630
2.0330
1.2980
* UNIT MEASUREMENTS INDICATED UNDER 40%
MAXIMUM
FILL REPRESENT
SQUARE INCHES.
FOR REFERENCE ONLY - RECOMMENDATION FOR CONDUIT SIZE PER N.E.C.
SCOPE OF WORK
THIS PROJECT IS BEING SUBMITTED AS A TENANT IMPROVEMENT TO THE FACILITIES EXISTING FIRE ALARM
SYSTEM. INSTALL DEVICES AS SHOWN IN EQUIPMENT LEGEND AND FLOOR PLANS OF THIS DRAWING
PACKAGE. SPLICE, CONTINUE, INSTALL & EXTEND WIRE AS NEEDED TO ENSURE PROPER OPERATING
CONDITIONS.
IT IS ASSUMED THAT THE FACILITIES EXISTING CONDITIONS (I.E. FIELD DEVICES, REMOTE EQUIPMENT,
SEQUENCE OF OPERATIONS, INTERFACE MODULES, ETC.) ARE ALL IN GOOD WORKING CONDITION. ANY
EXISTING EQUIPMENT, DEVICES, ETC. THAT MAY BE FOUND TO BE FAULTY SHALL NOT BE REQUIRED TO BE
CORRECTED OR REPLACED UNDER THIS CONTRACT.
UPON COMPLETION A COMPLETE PRETEST SHALL BE PERFORMED TO VERIFY FUNCTIONALITY. IF THE
FUNCTIONALITY IS COMPLETE THEN THE PROPER DOCUMENTATION SHALL BE SUBMITTED TO THE AUTHORITY
HAVING JURISDICTION PRIOR TO SCHEDULING A FINAL INSPECTION.
THIS PROJECT INCLUDES THE FOLLOWING:
TO BE ADDED-
09 CONTROL RELAY MODULES FOR WANDER DOOR INTERFACE
Zj� DEVICE INSTALLATIONIOPERATING GUIDELINES Zt
100°=
THE UL LISTED OPERATING TEMPERATURE RANGE FOR ALL ADDRESSABLE DEVICES IS
FROM 327 (0°C) TO 100°F (38°C). IF A DEVICE IS SHOWN IN AN AREA WHICH MAY
32 =
EXPERIENCE EXTREME COLD OR HEAT, CONTACT YOUR SIEMENS REPRESENTATIVE.
FIRE ALARM EQUIPMENT SHALL NOT BE STORED OR INSTALLED IN AREAS EXPOSED TO
THE ELEMENTS EXCEEDING NORMAL OPERATING CONDITIONS. LISTED WEATHERPROOF
DEVICES MAY BE INSTALLED AT EXTERIOR LOCATIONS PER MANUFACTURER
'
INSTRUCTIONS. ALL OTHER DEVICES NOT SPECIFICALLY LISTED AS WEATHERPROOF
MUST BE INSTALLED IN SUITABLE LOCATIONS OR LISTED NEMA ENCLOSURES
APPLICABLE FOR THE ANTICIPATED ENVIRONMENT AND DEVICES TO BE INSTALLED.
THE INSTALLATION OF A FIRE ALARM SYSTEM AND ANY FIRE ALARM EQUIPMENT MUST
NOT BE INSTALLED NEXT TO OR WITHIN CLOSE PROXIMITY OF ANY RADIO FREQUENCY
EQUIPMENT (EMI, RF, MF, HIGH OUTPUT, ETC.). SUCH INSTALLING CONDITIONS MAY
RF EMI
CAUSE UNDESIRABLE EFFECTS TO THE SYSTEM SUCH AS INTERMITTENT FAULTS,
IMPROPER SYSTEM OPERATIONS, FALSE ALARMS, ETC.
ENSURE EACH ADDRESSABLE DEVICE HAS BEEN PROPERLY PROGRAMMED PRIOR TO ITS
INSTALLATION. DO NOT TERMINATE WIRES ONTO ADDRESSABLE DEVICES BEFORE IT HAS
a
BEEN PROGRAMMED.
DPU
DO NOT REMOVE DUST COVERS FROM SMOKE DETECTORS UNTIL ALL CONSTRUCTION
HAS BEEN COMPLETED. DUST COVERS WHICH HAVE BEEN REMOVED FROM ANY
DETECTOR PRIOR TO THE FINAL CLEAN-UP OF ALL TRADES SHALL BE CLEANED OR
REPLACED, IN ACCORDANCE WITH NFPA 72. SIEMENS IS NOT RESPONSIBLE FOR
FAULTS FOUND TO BE RELATED TO CONTAMINATION.
E I
ALL INITIATING DEVICES (DETECTORS, PULL STATIONS, ETC.) AND NOTIFICATION
APPLIANCES (HORNS, STROBES, ETC.) MUST BE INSTALLED WITH BACKBOXES. THE
EQUIPMENT SHOULD NEVER BE SUPPORTED WITH THE CIRCUIT WIRES.
THE USE OF MAGNETS FOR THE PURPOSE OF TESTING DETECTORS FOR INITIATION OF
-
AN ALARM IS STRICTLY PROHIBITED. TESTING WITH A MAGNET DOES NOT SATISFY NFPA
72 TEST METHOD REQUIREMENT OF 'SMOKE ENTRY INTO THE SENSING CHAMBER', AND
MAY CAUSE UNDESIRABLE EFFECTS TO THE DETECTOR.
THE PAINTING OR MODIFYING OF ANY FIRE ALARM EQUIPMENT IS STRICTLY PROHIBITED
AND SHOULD NOT BE PERFORMED UNDER ANY CIRCUMSTANCES.
(E) CABLE LEGEND
CABLE TYPE
DRY LOCATION
CIRCUIT
DESIGNATION
WET LOCATION
DESCRIPTION
OPEN CABLE
IN CONDUIT
2-COND #16 TWISTED PAIR
2-COND #16 TWISTED PAIR
2-COND #16 TWISTED PAIR
SOLID FPL* CABLE
SOLID FPL* CABLE
FPL CABLE
(SLC) LOOP
D
WEST PENN #AQ225 OR
EQUIVALENT
ADDRESSABLE
RED JACKET -RED BLACK
RED JACKET -RED BLACK
RED JACKET -RED BLACK
THE ABOVE REFERENCED IS THE RECOMMENDED WIRE TYPE TO BE UTILIZED. WIRE SUBSTITUTIONS OF A SIMILAR TYPE AND
OF A LIKE NATURE MAY BE UTILIZED. THE USE OF ALTERNATE WIRE TYPES MUST BE ACCEPTED BY THE AHJ AND MEET THE
SAME CRITERIA, SPECIFICATIONS, LISTINGS, ETC. AS THE ABOVE WIRE INDICATED.
* - PROPER USE OF LISTED FPL/FPLR/FPLP CABLE SHALL BE USED IN APPLICABLE INSTALLATION PER ELECTRICAL CODE.
THIS PROJECT TO BE INSTALLED AS A CONDUIT INSTALLATION. PROVIDE REQUIRED SUPPORTS SPACED IN ACCORDANCE
WITH APPLICABLE ELECTRICAL CODE. PROVIDE CONDUIT OR OTHER RACEWAY WHERE REQUIRED BY CODE FOR PROTECTION
OF WIRING/CIRCUITS. WHERE CONDUIT IS USED, SIZE ACCORDINGLY TO THE CONDUIT FILL CHART AND APPLICABLE
ELECTRICAL CODE.
EXAMPLE: NUMBER OF CONDUCTOR PAIRS
WIRE TYPE DESIGNATION
METALLIC RACEWAY/OPEN CABLE/PLENUM CABLE/ETC. (WHERE APPLICABLE)
,MEANS
ABOVE EXAMPLE "2A" "2 TWISTED PAIR CABLES" ALL WIRE AND CABLE TO BE SIGNED, TYPED AND CONDUIT FILL
PER ELECTRICAL CODE AND MANUFACTURER'S RECOMMENDATION.
BUILDING/PROJECT INFORMATION
BUILDING OCCUPANCY: A/B/R-1/R-2/S
SPRINKLERS: YES
CONSTRUCTION TYPE: TYPE 1 A
NUMBER OF STORIES: 1 GARAGE + 3 FLOORS
Approved
DFM GMris Burt
South County Fire
Date: 02/27/2024
02-27-2024
PLAN REVIEW
NOTES: APPROVED
DFM BURT
SHEET INDEX
SHEET NUMBER
SHEET TITLE
FAO. 01
SYSTEM INFORMATION & NOTES
FAO.02
EQUIPMENT LIST, SEQUENCE OF OPERATIONS, WIRING DETAILS & CABCS
FA1.10
FIRST LEVEL FIRE ALARM PLAN
FA1.20
SECOND LEVEL FIRE ALARM PLAN
FA1.30
THIRD LEVEL FIRE ALARM PLAN
FA2.01
SYSTEM RISER DIAGRAM
TYPICAL CALLOUTS & ABBREVIATIONS
AC = ABOVE CEILING HT = HEIGHT
AFF = ABOVE FINISHED FLOOR ID = IN -DUCT MOUNTED
AHJ = AUTHORITY HAVING JURISDICTION IDC = INITIATING DEVICE CIRCUIT
AHU = AIR HANDLING UNIT MAX = MAXIMUM
ANN = ANNUNCIATOR MIN = MINIMUM
BMS = BUILDING MANAGEMENT SYSTEM N = NEW
C = CEILING MOUNTED N/A = NOT APPLICABLE
"C = CONDUIT (CIRCULAR RACEWAY) NAC = NOTIFICATION APPLIANCE CIRCUIT
CD = (i.e., 15CD) CANDELA NIC = NOT IN CONTRACT
CFM = CUBIC FEET PER MINUTE (AIRFLOW) NTS = NOT TO SCALE
CKT = CIRCUIT PS = POWER SUPPLY
CSFD = COMBINATION SMOKE FIRE DAMPER RA = RETURN -AIR GRILL MOUNTED
DACT = DIGITAL ALARM COMM. TRANSMITTER RL = RELOCATED DEVICE
DR = DROP & RE -HANG EXISTING RR = REMOVE EXISTING, REPLACE w/ NEW
E = EXISTING SF = DEVICE MOUNTED IN SUB -FLOOR
EL = ELEVATOR RECALL SLC = SIGNALING LINE CIRCUIT
EOL = END OF LINE TBD = TO BE DETERMINED
EOLP = END OF LINE POWER MODULE TYP = TYPICAL
EPO = EMERGENCY POWER OFF OF = UNDER -FLOOR
ER = EXISTING TO BE RELOCATED UON = UNLESS OTHERWISE NOTED
FAA = FIRE ALARM ANNUNCIATOR WM = DEVICE WALL MOUNTED
FACP = FIRE ALARM CONTROL PANEL WP = WEATHERPROOF
FACU = FIRE ALARM CONTROL UNIT X = DEMO EXISTING
FATC = FIRE ALARM TERMINAL CABINET XP = EXPLOSION PROOF
FBO = FURNISHED BY OTHERS EX = EXISTING DEVICE
FSD = FIRE SMOKE DAMPER VL = VERIFY LOCATION IN FIELD
(E) WIRING GUIDELINES
PLENUM CABLE VS. NON -PLENUM
THE NEC RECOGNIZES 3 TYPES OF POWER LIMITED FIRE ALARM CABLING:
FPL - THIS IS A GENERAL USE POWER LIMITED FIRE ALARM CABLE. IT CANNOT BE USED IN A PLENUM SPACE OR
FOR RISERS (CABLING BETWEEN FLOORS), CABLE MUST BE IN CONDUIT.
FPLR - THIS IS A POWER LIMITED RISER RATED CABLE THAT CAN BE USED FOR GENERAL PURPOSES OR
BETWEEN FLOORS. IT CANNOT BE USED IN A PLENUM SPACE, CABLE MUST BE IN CONDUIT.
FPLP - THIS IS A POWER LIMITED CABLE THAT CAN BE USED IN A PLENUM, RISER, OR FOR GENERAL PURPOSE.
A PLENUM IS ANY AREA USED TO CONDUCT ENVIRONMENTAL AIR. PLENUM SPACES CAN BE DUCTWORK, THE
SPACE ABOVE A DROP CEILING, OR BELOW A RAISED FLOOR. BECAUSE THESE SPACES ARE BEING USED FOR THE
AIR HANDLING SYSTEM. THERE ARE STRICT RULES THAT MUST BE FOLLOWED TO REDUCE THE RISK OF
INTRODUCING TOXIC FUMES IN THE EVENT OF A FIRE. SINCE FIRE ALARM CABLING IS OFTEN INSTALLED EXPOSED,
WITHOUT CONDUIT, ABOVE DROP CEILINGS THE CABLING MUST BE RATED FOR USE IN A PLENUM SPACE.
(E) WIRING REQUIREMENTS
• THE DRAIN SHIELD IS A VERY IMPORTANT PART OF THE SYSTEM INSTALLATION. SHIELDED WOULD NOT SPECIFY
SHIELDED CABLE IF IT WAS NOT NECESSARY. SHIELDS SHOULD BE KEPT CONTINUOUS THROUGHOUT THE
CIRCUIT AND KEPT FREE FROM ANY REFERENCE TO EARTH GROUND.
• SHIELDED CABLE CAN BE FPL, FPLR, OR FPLP. NETWORK COMMUNICATIONS BETWEEN FIRE ALARM CONTROL
PANELS AND REMOTE ANNUNCIATORS REQUIRE SHIELDED CABLE.
• INTELLIGENT ADDRESSABLE INITIATING DEVICES REQUIRE NON -SHIELDED CABLE.
• NOTIFICATION APPLIANCES (I.E. - HORN/STROBES, HORNS, ETC.) REQUIRE NON -SHIELDED CABLE.
• UNDERGROUND CABLE, WHETHER OR NOT INSTALLED IN CONDUIT, SHALL BE LISTED AS UNDERGROUND BURIAL
TYPE.
• WIRING IS TO BE INSTALLED POINT TO POINT WITH NO SPLICING.
VICINITY MAP
NORTH SCOPE OF WORK:
CHARTER CONSTRUCTION SUNRISE FA T.I.
0 SUNRISE OF EDMONDS,
0
1 750 EDMONDS WAY,
1 EDMONDS, WA 98020.
1
1,th St SW
1 L
j=5th Stsw 1 w
26th St SNf 226th St SW
g 15th StSW 15th St SW o
rn Q 1 r
s
Edmonds -Westgate 1 1~ a n
Veterinary Hospital PS
:E I PI SW 226th pf s ✓
2261tt � _ 1
0
n Edmo I ds Memorial
Cemetery
5,a
Rosewood CourteQ �a
1 0
IN
m 22711, PI SV
Sunrise o
t
228111 St SVi
oyo Edmonds Goodwill
Thrift store
r 0 QAmanda AHPhoto
n
Pagliacci Pizza Anytime Fitness
Pizza -3z Edmonds
L
Hattrup & Associates PS o
t
QFC® `
19th PI SW MaC2 ro -Tl®
Fast Food • Y
IN
T
rr,.i.,o uh1. no.,tim,.,110 O
APPROVAL STAMPS
SIEMENS
SIEMENS INDUSTRY, INC.
15900 SE EASTGATE WAY
BELLEVUE, WA 98008
425.507.4300
800.952.6348 (24-HR SERVICE)
LICENSE: CC #SIEME11919PP
This drawing and the information and design application
herein contained is the property of SIEMENS INDUSTRY,
INC. and is loaned upon the express condition that the
some be returned to SIEMENS INDUSTRY, INC. upon
request; all information herein contained shall be treated
as secret and confidential; no reproduction of this
drawing or part thereof shall be made without the written
consent of SIEMENS INDUSTRY, Incorporated.
F I R2024-0016
RECEIVED
Feb 23 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVIEWED
THIS DRAWING PACKAGE HAS BEEN REVIEWED AND FOUND TO
BE COMPLIANT WITH APPLICABLE REQUIREMENTS
JOHN ITREJ AN NICET LEVEL: IV
DATE SIG ED. 02/19/2024 FIRE ALARM SYSTEMS
CONTROL LOG: 2024-015 CERT: 104316
AGENCY REFERENCE:
00 02/15/24 1 ISSUED FOR PERMIT I APK
REV DATE REMARKS INTL
NO.
1 DRAWN: APK 1
CHECKED: G N
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
SYSTEM INFORMATION & NOTES
JOB NUMBER:
440P-371895
PROJECT NAME \ ADDRESS:
CHARTER CONSTRUCTION SUNRISE FA T.I.
SUNRISE OF EDMONDS,
750 EDMONDS WAY,
EDMONDS, WA 98020.
DRAWING
NUMBER:
FA0m01
SHEET SIZE: ARCH E1 - 3002
NEW EQUIPMENT LIST ALL PARTS ARE SIEMENS
UNLESS OTHERWISE NOTED
INITIATING DEVICES
SYMBOL
QTY
MODEL/PART NUMBER
DESCRIPTION
ROUGH IN
FACP
(E)
DESIGO MODULAR
DESIGO FIRE SAFETY MODULAR FIRE ALARM CONTROL UNIT
SEMI -FLUSH OR
SURFACE MOUNT
ER MI
09(N)
54370-B1-A1
INTELLIGENT CONTROLLABLE RELAY w/ SINGLE INPUT MONITOR MODULE
4S DEEP BOX
EXISTING EQUIPMENT LIST
FACU COMPONENTS
SYMBOL
QTY
MODEL
NUMBER
DESCRIPTION ALL PARTS ARE SIEMENS
UNLESS OTHERWISE NOTED
ROUGH IN
FACP
(E)
CAB3-BB
500-633011
THREE ROW CABINET BACKBOX
---
(E)
CAB3-BD 500-633010
THREE ROW CABINET INNER AND OUTER DOOR SET
---
(E)
OD -LP
500-633016
OUTER DOOR ROW LENS PLATE
INTERNAL PANEL
COMPONENT
(E)
OD -BP
500-633017
OUTER DOOR ROW BLANK PLATE
INTERNAL PANEL
COMPONENT
(E)OD-GP
500-633018
OUTER DOOR ROW VENTED GRILL PLATE
INTERNAL PANEL
COMPONENT
(E)
XDACT-ASSY
S54430-A5-A1
DIGITAL ALARM COMMUNICATION TRANSMITTER ASSEMBLY FOR XLS
INTERNAL PANEL
COMPONENT
(E)
FCA2015-U1
S54400-A63-A1
DIGITAL ALARM COMMUNICATION TRANSMITTER FOR XLS
INTERNAL PANEL
COMPONENT
(E)
ZAM-180
500-035600
ZONE AMPLIFIER MODULE (180 WATTS)
INTERNAL PANEL
COMPONENT
(E)
CC-5
500-633037
5-SLOT CARD CAGE
INTERNAL PANEL
COMPONENT
(E)
ZIC-4A
500-033050
4 CIRCUIT ZONE INDICATING CARD
INTERNAL PANEL
COMPONENT
(E)
ZIC-86
500-648670
8-CIRCUIT ZONE INDICATING CARD
INTERNAL PANEL
COMPONENT
(E)
NIC-C
500-033240
NETWORK INTERFACE CARD
INTERNAL PANEL
COMPONENT
(E)
PSC-12
500-033340
POWER SUPPLY WITH BATTERY CHARGER
(INCLUDES PTB TERMINATION BOARD)
INTERNAL PANEL
COMPONENT
(E)
PSX-12
500-034120
POWER SUPPLY EXTENDER
INTERNAL PANEL
COMPONENT
(E)
PTB
500-033390
POWER TERMINATION BOARD
INTERNAL PANEL
COMPONENT
(E)
DAC-NET
500-035100
DIGITAL AUDIO CARD D-NET
INTERNAL PANEL
COMPONENT
(E)
XDLC
S54430-68-A1
DEVICE LOOP CARD (COMPATIBLE w/ ISOLATION DEVICES)
INTERNAL PANEL
COMPONENT
(E)
CAB-BATT
500-633917
BATTERY CABINET FOR UP TO (2) 100 A.H. BATTERIES
SURFACE OR
SEMI -FLUSH MOUNT
(E)
PS-121000
�A730026435
BATTERY 12 VOLT 100 AMP HOUR (SET)
BATTERY CABINET
ALL ARE SIEMENS
ANNUNCIATOR COMPONENTS UNLESSRTS OTHERWISE NOTED
SYMBOL
QTY
MODEL
NUMBER
DESCRIPTION
ROUGH IN
FAA
(E)
SSD-C
REMOTE ANNUNCIATOR PANEL
4S DEEP BOX
REMOTE POWER SUPPLY PANEL COMPONENTS UALL PATS ARE SIEMENS
NLESSROTHERWISE NOTED
SYMBOL
QTY
MODEL
NUMBER
DESCRIPTION
ROUGH IN
12 24
(E)
PS-12/24-8
FIRE ALARM POWER SUPPLY
SURFACE MOUNT
ALL ARE SIEMENS
INITIATING DEVICES UNLESSRTS OTHERWISE NOTED
SYMBOL
QTY
MODEL
NUMBER
DESCRIPTION
ROUGH IN
O OS A
(E)
FDOT421
S5432046-A1
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR HEAD
DB-11
FE)
DB-11
500-094151
DETECTOR BASE
4S DEEP BOX w/
1-GANG RING
0
(E)
FDT421
S54320-F5-A1
INTELLIGENT HEAT DETECTOR HEAD
DB-11
(E)
DB-11
500-094151
DETECTOR BASE
4S DEEP BOX w/
1-GANG RING
❑F
(E)
HMS-S
500-033200
INTELLIGENT MANUAL PULL STATION
DUAL ACTION
4S DEEP BOX w/
1-GANG RING
TRI-R
(E)
XTRI-R
S54370-B1-Al
INTELLIGENT CONTROLLABLE RELAY w/ SINGLE INPUT MONITOR MODULE
4S DEEP BOX
TRI-S
(E)
XTRI-S
S54370-B3-A1
INTELLIGENT SINGLE INPUT MONITOR MODULE
4S DEEP BOX
TRI-D
(E)
XTRI-D
S54370-B2-A1
INTELLIGENT DUAL INPUT MONITOR MODULE
4S DEEP BOX
ICP
(E)
500-034860
INTELLIGENT CONTROL POINT MODULE
4S DEEP BOX
NOTIFICATION DEVICES ALPARSARE SIEMENS
UNLESSOTHERWISE NOTED
SYMBOL
QTY
MODEL
NUMBER
DESCRIPTION
ROUGH IN
Lr N 15 30
110
(E)
E70-24MCW
MULTI -CANDELA SPEAKER/NON-LED STROBE, 25/70V, WALL MOUNT -WHITE
FIELD SELECTABLE 15/30/75/110cd, 1/8-2W
4S DEEP BOX w/
1-GANG RING
F 15
75
110
(E)
RSS-24MCW
MULTI -CANDELA NON -LED STROBE, WALL MOUNT - WHITE
FIELD SELECTABLE 15/30/75/110cd
4S DEEP BOX w/
EXTENSION
(E)
E70
FIELD KSEL CTABOLE 1�g I8W MOUNT -RED
EXTENSION4S DEEP BOX w/
ALL ARE SIEMENS
MISCELLANEOUS DEVICES UNLESSRTS OTHERWISE NOTED
-
-----
END OF LINE RESISTOR
F.B.O.
®
-
F.B.O.
FOREIGN SYSTEM INTERFACE
F.B.O.
�M
-
DHF-1224C
FIRE ALARM DOOR
F.B.O.
O� SINGLE INPUT RELAY MODULE WIRING DIAGRAM
NOT TO SCALE -- SEE THE INSTALLATION INSTRUCTIONS FOR ADDITIONAL INFORMATION
SLC WIRING SHOWN FOR POLARITY INSENSITIVE USAGE.
FOR ISOLATOR MODE SEE BELOW.
FROM + +
PREVIOUS DEVICE _ _ _ TO NEXT DEVICE
OR FACP - i
Q13 A, O
- - - R _ TO CONTROLLED DEVICE
XTRI-R' (NO/NC CONTACTS AS
- APPLICABLE)
RELAY MUST BE MOUNTED
SUPERVISED I WITHIN 3 FEET OF
SWITCH* CONTROLLED DEVICE
EOL
Xnf-R FEW OONTACr PARNGS
APFRAGE VOLTAGE TYPE
IA 3W& RENM tEE4
3SA 12Wx MUCINE 0.6 PF O AA
IOA 3W& iii5 N U PF
SLC WIRING FOR ISOLATOR MODE USAGE - UP TO 30 DEVICES IN POLARITY INSENSITIVE MODE
WITH UP TO 200 LINE RESISTANCE MAY BE CONNECTED BETWEEN TWO DEVICES IN ISOLATOR
MODE. MAX 190 DEVICES IN ISOLATOR MODE PER XDLC.
FROM
PREVIOUS DEVICE TO NEXT DEVICE
OR FACP
z
O
a
U
� Z
w
W
`Rn
C Y N
a I-
o
g9N E
a��yo
o<
U CJ 9k
� O=OwZw
CD C-, z
Z Z2pwc
CD C-, =
�Z�
m�0 0��
� lr'ry'A , V
O r N W ME a
U wozo3�
owoc x
U_ w of (n
WOfLi �
*CAN BE CONFIGURED TO MONITOR N/O OR N/C CONTACTS. VERIFY APPLICATION WITH FIELD PERSONNEL. � (n a_w a- o a_
ACV IM 4i16
MODEL DESCRIPTION IMOUNTING CONFIGURATION (SEE SYMBOLS LEGEND FOR REQ'S)
XTRI-R SINGLE INPUT RELAY MODULE 4" SQUARE
�2 I WANDER DOOR CONTROL WIRING DIAGRAM
G NOT TO SCALE -- SEE APPLICABLE DEVICE INSTRUCTIONS FOR ADDITIONAL INFORMATION
FIRE ALARM RELAY
(NO/NC CONTACTS AS APPLICABLE) - }FIRE INTERFACE CONTROL
\\-WANDER DOOR CONTROLLER
(BY OTHERS)
�3 I FIRESTOP DETAIL - GYPSUM STUD WALL
NOT TO SCALE -- SEE APPLICABLE EQUIPMENT INSTRUCTIONS FOR ADDITIONAL INFORMATION
System No. W-L-1001
F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3)
T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3)
L Rating At Ambient - Less Than 1 CFM/sq ft
L Rating At 400 F - Less Than 1 CFM/sq ft
114-00-1111
LA 16
SECTION A -A
1. Wall Assembly - The 1, 2, 3 or 4 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the
manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include
the following construction features:
A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs to consist
of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and
cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum wallboard
type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series
Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm).
2. Through Penetrant - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or eccentrically within the firestop
system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max
2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic
pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. pipe, nom 12 in. (305 mm) diam (or smaller)
or Class 50 (or heavier) ductile iron pressure pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic
tubing.
D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:
1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both
sides of floor or wall assembly.
OMEGA FLEX INC
2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both
sides of floor or wall assembly.
GASTITE, DIV OF TITLEFLEX
3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both
sides of floor or wall assembly.
WARD MFG LLC
3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1, 2,
3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk
applied to gypsum board/penetrant interface at point contact location on both sides of wall. The hourly F Rating of the firestop system
is dependent upon the hourly fire rating of the wall assembly in which it is installed, as shown in the following table. The hourly T Rating
of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which
it is installed, as tabulated below:
Max Pipe or
Conduit Diam in.
(mm)
F Rating Hr
T Rating Hr
1 (25)
1 or 2
0+, 1 or 2
1 (25)
3 or 4
3 or 4
4 (102)
1 or 2
0
6 (152)
3 or 4
0
12 (305)
1 or 2
0
+When copper pipe is used, T Rating is 0 hr.
3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant,
*Bearing the UL Classification Marking
(E) SEQUENCE OF OPERATIONS
Control Unit
Building Sequence of Operations
Notification
Required
Fire
Safety
Control
Annunciation
AUDIBLE MESSAGE TO BE (FEMALE VOICE,
ENGLISH) - "May I have your attention please,
may I have your attention please? There has
00
0
been a fire emergency reported in the building.
_
o
o
N
o
4.1
(n
0
o
Please evacuate the building by the nearest
o
c�
J
N
O
cA
00
U
v 0'
>
exit, do not use the elevators."
J
N
-a
o
0
0
0
C
N
(n
(D
-
�
N
M
L
c)
O
},
}'
C
0
0)
�.
N
0
N
a)
Z
Z
O
^�'
4-
(73
2
N
a)
N
0
O
IV
U)
O
>_
o
0)
C
(
O
E
O
4-
N
�
N
0
E
'-
a)
}'
� 0
0 O
>_
0
70
>_
N
o
:
c
U
N
(�
a
M
o
C
C
�'
°
c>3
°
,_
°'
X
70
* - Elevator recall to primary or alternate floor and
P Y
�
w
J
�
M
v,
o
Ta
E
o
o
M
M
0 E
.-.
.-.
o
m
m
Visual Warning (Firefighter Hat) shall be
M
U
0
to ^
(n
0
-
�4_1_
�_
L
L
o
o
performed by the elevator controller per the
Q
j
O
o
T E
N
L E
N
0
0
Elevator Code ASME A17.1
¢
cn
I--
a)
� 0
O 0
� �
N
�
0
Q
M 0
N
N=
�
a
a
L
0 0
0
0
0
O
E
O
� O
w O
J
N
E
p ��
a) a)
a)
a) O
>
0,�6(
> (u_
0�6X U
�
�
�
(D
O
>,
a) �
O
�
>
U
>
U
O
O
O
N
-
IY
-0
w e
D-0
-0
_0
L
M
2 O
U
M
M�
0
a)
W N
_�
U�
a)
c�
a)
c�
CL
N�
.O4_1
0
C
C
}'
M
a�
aJ �
a a�
�
O a_
IlY �
n
0-
a)
o
V) ch
o
(n
0
(� a)
Z
a) -0
U
U
O
-
0
>
0
0
o
(D
Q-1
cn Q
Q
-_
cn
cn
(n
- }.
O
0
>
m
a)
W
U
E O
E O
E O
�_
�
a) O
(D
( O
(D4_1
N _r
(73
(>3
a)
M
>
a)
cQ
c>3
ca
c>3
>,
to
ca
c�
c�
c�
a...
System Inputs
Q
Q
Q
r_
Q
L
��
L
��
M
��
U (D
Q
0
Z
U a)
Q~
U
Q
U O
Q 0
U
Q
- M
¢ co
W O
T_�
W
Iz
W
Of
0
a]
0
U
Q
>
Manual fire alarm box
X
X
X
X
X
X
X
X
Smoke detector above FA panel
X
X
X
X
X
X
X
X
Smoke detector @ door hold location
X
X
X
X
X
X
X
X
Area smoke / heat detector
X
X
X
X
X
X
X
X
Top of stair smoke detector
X
X
X
X
X
X
X
X
Patient room smoke detector / heat detector
X
X
X
X
X
X
X
X
X
X
X
Residential unit smoke sensor
X
X
X
X
Residential ADA unit smoke sensor
X
X
X
X
X
Elevator lobby smoke detector -main floor
X
X
X
X
X
X
X
X
X
X
Elevator lobby smoke detector -all other floors
X
X
X
X
X
X
X
X
X
X
Elevator machine room @ main floor smoke det
X
X
X
X
X
X
X
X
X
X
X
Elevator machine room heat detector
X
X
X
X
X
X
X
X
X
Elevator hoistway smoke detector
X
X
X
X
X
X
X
X
X
X
X
Elevator hoistway heat detector
X
X
X
X
X
X
X
X
X
Elevator120VAC shunt trip circuit failure
X
X
X
Sprinkler water flow switch
X
X
X
X
X
X
X
X
Sprinkler valve supervisory switches
X
X
X
Ansul or HOOD system activation
X
X
X
X
X
X
X
X
FACU 120VAC power failure
X
X
X
X
X
Remote power supply trouble (power, wiring)
X
X
X
System device trouble
X
X
X
System wiring trouble (ground, open, short)
X
X
X
SEQUENCE OF OPERATIONS TO MATCH THE EXISTING BUILDING SEQUENCE OF OPERATIONS
(E) FIRE ALARM CONTROL PANEL BATTERY CALCULATION
BUILDING NAME: SUNRISE SENIOR LIVING
PANEL NAME: FACP
PANEL LOCATION: ELEC. 04
Qty Model Description
Standby Current (mA)
Alarm Current (mA)
Per
Device
Current
Total
Current
6.2V
Backplane
Current
6.2V to 24V
equivalent
current
24V
Backplane
Current
24V Screw
Terminal
Current
Per
Device
Current
Total
Current
A
B (Qty*A)
C
D (C*6.2/24)
E
F
G (D+E+F)
H (Qty*G)
1
FCM2041-U2
Desigo Modular Operator Interface
125
125
195
195
195
1
PSC-12
Power Supply/Battery Charger
150
150
150
150
150
4
Active Relays
20
80
20
20
80
1
PSX-12
Power Supply Extender
150
150
150
150
150
1
DAC-NET
Digital Audio Card with Network
230
230
230
230
230
1
NIC-C
Network Interface Card
120
120
120
120
120
1
XDMC
Digital Message Card
170
170
140
36.17
140
176.17
176.17
1
ZAM-180
Zone Amplifier Module 180 Watts
300
300
300
300
300
180
Speaker Load Watts
0
0
51.11
51.11
9199.8
1
ZAM-180 (Backup)
Zone Amplifier Module 180 Watts
300
300
0
0
1
ZIC-4A
Zone Indicating Card
89
89
89
89
89
4
Active Speaker Circuits
0
0
34
34
136
1
ZIC-8B
Zone Indicating Card
105
105
0
0
8
Active Circuits
0
0
17
17
136
4
XDLC
Class X Device Loop Card
100
400
1
0.26
100
100.26
401.04
208
FDOT421
Photo -thermal detector
0.25
52
0.41
0.41
85.28
3
FDT421
Thermal detector
0.25
0.75
0.41
0.41
1.23
8
HCP
Addressable control point
1
8
1
1
8
11
HMS-S
Manual station
0.9
9.9
0.9
0.9
9.9
10
XTRI-D
X Dual input module
0.5
5
0.95
0.95
9.5
19
XTRI-R
X Single input/single relay module
0.5
9.5
1
0.75
0.75
14.25
1
XTRI-S
Ix Single input module
0.5
0.5
0.65
0.65
0.65
1
FCA2015-U1
IDigitalAlarm Communicator Transmitter
33.5
33.5
43.5
43.5
43.5
Total Standby Current: 2.3381 Amps Total Alarm Current: 11.5353 Amps
BATTERY SIZING CALCULATIONS:
Total Standby Current: 2.3381 Amps Standby Time Required: 24 Hours
Total Alarm Current: 11.5353 Amps Alarm Time Required: 15 Minutes
Total Standby Current x Standby Time: 56.1144 Ah Battery Size Provided: 100 Ah
Total Alarm Current x Alarm Time: 2.8838 Ah Calculated Minimum Battery: 73.75 Ah
Total LOAD (Total Standby Ah + Total Alarm Ah): 58.9982 Ah Spare Battery Capacity: 26.25 Ah
Min. Battery Size (Total LOAD x 1.25 Safety Factor): 73.7478 Ah
120VAC Current: 7 Amps
APPROVAL STAMPS
SIEMENS
SIEMENS INDUSTRY, INC.
15900 SE EASTGATE WAY
BELLEVUE, WA 98008
425.507.4300
800.952.6348 (24-HR SERVICE)
LICENSE: CC #SIEME11919PP
This drawing and the information and design application
herein contained is the property of SIEMENS INDUSTRY,
INC. and is loaned upon the express condition that the
some be returned to SIEMENS INDUSTRY, INC. upon
request; all information herein contained shall be treated
as secret and confidential; no reproduction of this
drawing or part thereof shall be made without the written
consent of SIEMENS INDUSTRY, Incorporated.
RECEIVED
Feb 23 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVIEWED
THIS DRAWING PACKAGE HAS BEEN REVIEWED AND FOUND TO
BE COMPLIANT WITH APPLICABLE REQUIREMENTS
JOHN ITREJ AN NICET LEVEL: IV
DATE SIG ED: 02/19/2024 FIRE ALARM SYSTEMS
CONTROL LOG: 2024-015 CERT: 104316
AGENCY REFERENCE:
00 02/15/24 JISSUED FOR PERMIT I APK
REV DATE REMARKS INTL
NO.
1 DRAWN: APK 1
CHECKED: G N
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
EQUIPMENT LIST, SEQUENCE OF
OPERATIONS, WIRING DETAILS &
CALCS
JOB NUMBER:
440P-371895
PROJECT NAME \ ADDRESS:
CHARTER CONSTRUCTION SUNRISE FA T.I.
SUNRISE OF EDMONDS,
750 EDMONDS WAY,
EDMONDS, WA 98020.
DRAWING
NUMBER:
FAOmO2
SHEET SIZE: ARCH E1 - 3002
APPROVAL STAMPS
DRAWING NOTE:
LALLEVICES OUTSIDE AREA OF WORK SHALL BE
CONSIDERED AS EXISTING TO REMAIN.
DRAWING NOTE:
ALL DEVICES NOT INDICATED WITH AN ASSOCIATED
CALLOUT SHALL BE CONSIDERED AS EXISTING TO REMAIN.
NOTES
ABBREVIATIONS:
(E) EXISTING DEVICES
(N) NEW DEVICES
N.I.C. NOT IN CONTRACT
GENERAL NOTES:
1. CONTROL RELAY MODULES SHALL BE MOUNTED WITHIN 3FT
FROM THE CONTROLLERS.
KEY NOTES: 0
1. 24 VDC POWER SUPPLY FOR ALL WANDER DOORS SHALL BE
PROVIDED BY OTHERS.
SIEMENS
SIEMENS INDUSTRY, INC.
15900 SE EASTGATE WAY
BELLEVUE, WA 98008
425.507.4300
800.952.6348 (24-HR SERVICE)
LICENSE: CC #SIEME11919PP
This drawing and the information and design application
herein contained is the property of SIEMENS INDUSTRY,
INC. and is loaned upon the express condition that the
same be returned to SIEMENS INDUSTRY, INC. upon
request; all information herein contained shall be treated
as secret and confidential; no reproduction of this
drawing or part thereof shall be made without the written
consent of SIEMENS INDUSTRY, Incorporated.
RECEIVED
Feb 23 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVIEWED
THIS DRAWING PACKAGE HAS BEEN REVIEWED AND FOUND TO
BE COMPLIANT WITH APPLICABLE REQUIREMENTS
JOHN MAITREJ
DATE SIG9ED: 02/19/2024 -
CONTROL LOG: 2024-015
AGENCY REFERENCE:
NICET LEVEL: IV
FIRE ALARM SYSTEMS
CERT: 104316
1 00 02/15/24 JISSUED FOR PERMIT APK
N0.
REV DATE REMARKS INTL
DRAWN: AP K
CHECKED: G N
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
FIRST LEVEL FIRE ALARM PLAN
JOB NUMBER:
440P-371895
PROJECT NAME \ ADDRESS:
CHARTER CONSTRUCTION SUNRISE FA T.I.
SUNRISE OF EDMONDS,
750 EDMONDS WAY,
EDMONDS, WA 98020.
NORTH
FIRST LEVEL FIRE ALARM PLAN
SCALE: 1/8 11 = 1 9_091 0 4' 8' 16' 0
DRAWING
NUMBER: FAI
■ l 0
SHEET SIZE: ARCH E1 - 3002
DRAWING NOTE:
ALL DEVICES OUTSIDE AREA OF WORK SHALL BE
CONSIDERED AS EXISTING TO REMAIN.
APPROVAL STAMPS
DRAWING NOTE:
ALL DEVICES NOT INDICATED WITH AN ASSOCIATED
CALLOUT SHALL BE CONSIDERED AS EXISTING TO REMAIN.
NOTES
ABBREVIATIONS:
(E) EXISTING DEVICES
(N) NEW DEVICES
N.I.C. NOT IN CONTRACT
GENERAL NOTES:
1. CONTROL RELAY MODULES SHALL BE MOUNTED WITHIN 3FT
FROM THE CONTROLLERS.
KEY NOTES: 0
1. 24 VDC POWER SUPPLY FOR ALL WANDER DOORS SHALL BE
PROVIDED BY OTHERS.
SIEMENS
SIEMENS INDUSTRY, INC.
15900 SE EASTGATE WAY
BELLEVUE, WA 98008
425.507.4300
800.952.6348 (24-HR SERVICE)
LICENSE: CC #SIEME11919PP
This drawing and the information and design application
herein contained is the property of SIEMENS INDUSTRY,
INC. and is loaned upon the express condition that the
same be returned to SIEMENS INDUSTRY, INC. upon
request; all information herein contained shall be treated
as secret and confidential; no reproduction of this
drawing or part thereof shall be made without the written
consent of SIEMENS INDUSTRY, Incorporated.
RECEIVED
Feb 23 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVIEWED
THIS DRAWING PACKAGE HAS BEEN REVIEWED AND FOUND TO
BE COMPLIANT WITH APPLICABLE REQUIREMENTS
JOHN MAITREJ
DATE SIG9ED: 02/19/2024 -
CONTROL LOG: 2024-015
AGENCY REFERENCE:
NICET LEVEL: IV
FIRE ALARM SYSTEMS
CERT: 104316
1 00 02/15/24 JISSUED FOR PERMIT APK
N0.
REV DATE REMARKS INTL
DRAWN: AP K
CHECKED: G N
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
SECOND LEVEL FIRE ALARM PLAN
JOB NUMBER:
440P-371895
PROJECT NAME \ ADDRESS:
CHARTER CONSTRUCTION SUNRISE FA T.I.
SUNRISE OF EDMONDS,
750 EDMONDS WAY,
EDMONDS, WA 98020.
NORTH
SECOND LEVEL FIRE ALARM PLAN
SCALE: 1/8 11 = 1 9_011 0 4' 8' 16' 0
DRAWING
NUMBER: FAI
■ 2 O
SHEET SIZE: ARCH E1 - 3002
DRAWING NOTE:
ALL DEVICES OUTSIDE AREA OF WORK SHALL BE
CONSIDERED AS EXISTING TO REMAIN.
APPROVAL STAMPS
DRAWING NOTE:
ALL DEVICES NOT INDICATED WITH AN ASSOCIATED
CALLOUT SHALL BE CONSIDERED AS EXISTING TO REMAIN.
NOTES
ABBREVIATIONS:
(E) EXISTING DEVICES
(N) NEW DEVICES
N.I.C. NOT IN CONTRACT
GENERAL NOTES:
1. CONTROL RELAY MODULES SHALL BE MOUNTED WITHIN 3FT
FROM THE CONTROLLERS.
KEY NOTES: 0
1. 24 VDC POWER SUPPLY FOR ALL WANDER DOORS SHALL BE
PROVIDED BY OTHERS.
SIEMENS
SIEMENS INDUSTRY, INC.
15900 SE EASTGATE WAY
BELLEVUE, WA 98008
425.507.4300
800.952.6348 (24-HR SERVICE)
LICENSE: CC #SIEME11919PP
This drawing and the information and design application
herein contained is the property of SIEMENS INDUSTRY,
INC. and is loaned upon the express condition that the
same be returned to SIEMENS INDUSTRY, INC. upon
request; all information herein contained shall be treated
as secret and confidential; no reproduction of this
drawing or part thereof shall be made without the written
consent of SIEMENS INDUSTRY, Incorporated.
RECEIVED
Feb 23 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVIEWED
THIS DRAWING PACKAGE HAS BEEN REVIEWED AND FOUND TO
BE COMPLIANT WITH APPLICABLE REQUIREMENTS
JOHN MAITREJ
DATE SIG9ED: 02/19/2024 -
CONTROL LOG: 2024-015
AGENCY REFERENCE:
NICET LEVEL: IV
FIRE ALARM SYSTEMS
CERT: 104316
1 00 02/15/24 JISSUED FOR PERMIT APK
N0.
REV DATE REMARKS INTL
DRAWN: AP K
CHECKED: G N
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
THIRD LEVEL FIRE ALARM PLAN
JOB NUMBER:
440P-371895
PROJECT NAME \ ADDRESS:
CHARTER CONSTRUCTION SUNRISE FA T.I.
SUNRISE OF EDMONDS,
750 EDMONDS WAY,
EDMONDS, WA 98020.
NORTH
THIRD LEVEL FIRE ALARM PLAN
SCALE: 1 /V„ = 1 9_091 0 4' 8' 16' (D
DRAWING
NUMBER: FAI
■ 3 0
SHEET SIZE: ARCH E1 - 3002
� I �
APPROVAL STAMPS
I
NOTES
ABBREVIATIONS:
(N) NEW DEVICES
N.I.C. NOT IN CONTRACT
DRAWING NOTES:
1. ALL DEVICES OUTSIDE AREA OF WORK SHALL BE CONSIDERED
AS EXISTING TO REMAIN.
2. ALL DEVICES NOT INDICATED WITH AN ASSOCIATED CALLOUT
SHALL BE CONSIDERED AS EXISTING TO REMAIN.
GENERAL NOTES:
1. CONTROL RELAY MODULES SHALL BE MOUNTED WITHIN 3FT
FROM THE CONTROLLERS.
KEY NOTES:
1. 24 VDC POWER SUPPLY FOR ALL WANDER DOORS SHALL BE
PROVIDED BY OTHERS.
9
N.I.C.
SCOPE OF WORK
1
1
1
Iz-no IC 1
(N) M� D A OP
� WANDER � S OB CI UI
� DOOR S 1,
RELEASE
1
/_ E mmommommor E' _
1
1
1-153 1-152 1-151 1-150
1
1 (N) Et
(N) <D (N) RM (D(N) RM
/
WANDER DOOR RELEASE
9,M � E _i
1 -72,3
4
V,
2-171
D A OP 4 (N) RM (j)
P SI P W F WANDER
L. S K U DS 1 DOOR
A RELEASE
JM MENNEEMEMSt we _/lEmom�W _
,Pr6V.4S
0
1-154
(N) RM
1 WANDER
1 DOOR 1
1 RELEASE r
,P,
9 O
C
3/04"
C 1EMENS
SIEMENS INDUSTRY, INC.
15900 SE EASTGATE WAY
BELLEVUE, WA 98008
425.507.4300
800.952.6348 (24-HR SERVICE)
LICENSE: CC #SIEME11919PP
This drawing and the information and design application
herein contained is the property of SIEMENS INDUSTRY,
INC. and is loaned upon the express condition that the
same be returned to SIEMENS INDUSTRY, INC. upon
request; all information herein contained shall be treated
as secret and confidential; no reproduction of this
drawing or part thereof shall be made without the written
consent of SIEMENS INDUSTRY, Incorporated.
RECEIVED
Feb 23 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVIEWED
THIS DRAWING PACKAGE HAS BEEN REVIEWED AND FOUND TO
BE COMPLIANT WITH APPLICABLE REQUIREMENTS
JOHN ITREJ AN NICET LEVEL: IV
DATE SIG ED: 02/19/2024 FIRE ALARM SYSTEMS
CONTROL LOG: 2024-015 CERT: 104316
AGENCY REFERENCE:
RI I 1 00 02/15/24 ISSUED FOR PERMIT APK
REV DATE REMARKS INTL
4 4S 4S, No.
DRAWN: AP K
E T A P —1 `2 P -1 24 P 12 4 CHECKED: G N
S S— SHEET DESCRIPTION:
FIRE ALARM SYSTEM
:k
SYSTEM RISER DIAGRAM
PER ER
JOB NUMBER:
440P-371895
PROJECT NAME \ ADDRESS:
CHARTER CONSTRUCTION SUNRISE FA T.I.
0 0 L I SUNRISE OF EDMONDS,
750 EDMONDS WAY,
EDMONDS, WA 98020.
NORTH
SYSTEM RISER DIAGRAM DRAWING
1 NUMBER: FA2m01
SCALE: NOT TO SCALE
SHEET SIZE: ARCH E1 — 3002