Loading...
FIR2024-0016+Fire_Alarm_Equipment_Specification_Sheets+2.21.2024_7.33.39_AM+4071986RECEIVED SIEMENS Feb 23 2024 CITY OF EDMONDS Siemens Industry, Inc. DEVELOPMENT SERVICES DEPARTMENT FIS Fire \ Life Safety Division 15900 SE Eastgate Way Bellevue, WA 98008 425.507.4300 For information Contact: Colin Pine colin.pine@siemens.com PRODUCT DATA SUBMITTAL 2/15/2024 Engineering Data for: Charter Construction Sunrise FA T.I. Fire Alarm System Sunrise of Edmonds, 750 Edmonds Way, Edmonds, WA 98020. 440P-371985 FI R2024-0016 THIS PAGE INTENTIONALLY LEFT BLANK FOR DUPLEX PRINTING SIEMENS SIEMENS Industy, Inc. - Fire / Life Safety Division 15900 SE Eastgate Way Bellevue, WA 98008 Tel: 425.507.4300 I:3-4dJA-1:1I77e7-A Charter Construction Sunrise FA T.I. Sunrise of Edmonds, 750 Edmonds Way, Edmonds, WA 98020. FIRE ALARM SUBMITTAL TABLE OF CONTENTS MODEL NUMBER DESCRIPTION XLS / Desigo Modular EQUIPMENT Desigo Modular Existing Fire Alarm Voice Control Panel XLS/Desigo Addressable Devices XTRI-R Addressable Relay / Monitor Module with Dual Isolators THIS PAGE INTENTIONALLY LEFT BLANK FOR DUPLEX PRINTING ❑ Siemens ISOtechnologyTM Provides "True Class-X" operation meeting NFPA 72 SLC field wiring requirements Supports 252 ISOtechnology ready devices per loop, and in mixed mode up to 30 devices between isolated devices ❑ Dual input on Model XTRI-D, via a single address ❑ Integral single -pole, double -throw (SPDT) relay on Model XTRI-R: - Up to 4 Amps. ❑ Low current draw ❑ Polarity insensitive (in non -isolation mode) via SureWireTM technology: - Modern technology supports comprehensive system and interface communication ❑ Multi -color light -emitting diode (LED) indicates system status: GREEN I AMBER I RED ❑ Mounts in a 4-inch (10.2 cm.) square, 2- '/4" (5.7 cm.) deep single -gang or double - gang back box ❑ Non -obstructive front-end access to programming port and wiring terminals SIEMENS The Siemens — Fire Safety XTRI-series Intelligent Interface Modules are designed to provide the means of interfacing direct shorting devices to the fire -alarm control panel (FACP) SLC. All modules take up one (1) address on the loop. Each XTRI-series interface module provides the "built-in" ISOtechnology feature - intelligent dual isolation meeting NFPA 72 Class X (Style 7) wiring requirements. Up to 252 isolators per loop and up to 30 devices between isolators (wired in polarity -insensitive mode). Additionally, the devices between isolators can either be'H'-series or the more contemporary' X'-series detection devices. The Siemens — Fire Safety XTRI-series Intelligent Interface Modules are available in three (3) individual types: > One (1) Dual -Input: XTRI-D > Two (2) Single -Inputs: XTRI-R (with relay) I XTRI-S - The single -input versions are each designed to monitor a normally open (N.0) or KQ normally closed dry contact XTRI-D I XTRI-R I XTRI-S incorporates ISOtechnology — the configurable, built-in dual isolator function. Additionally, an XTRI-series interface module supports NFPA 72 Class X (Style 7) survivability requirements for shorts while providing reliable alarm communication to the Siemens FACP. The isolation feature found on the XTRI-series Intelligent Interface Modules gives information as to the location of the fault. When a short occurs, the panel can identify the fault automatically, and the module recognizes the short location (in front of the device or behind the device). Overall, the built-in isolators improve the diagnostics and location of the problem, including a short. The modules are configurable by a Siemens compatible FACP (or panels) in an isolator (polarity sensitive) or non -isolator (polarity insensitive) mode. When a XTRI-series interface module is configured as an isolator, that module has the capacity of functioning as both an inlout device, as well as an isolator. Advanced troubleshooting is provided by compatible ❑ Device Programmer I Test Unit programs panels by identifying when a XTRI-series interface and verifies address, as well as tests module is configured as an isolator, but is wired device functionality incorrectly in apolarity-insensitive mode. ❑ Restriction of Hazardous Substances Each Model XTRI-series device has a multi -color LED that (RoHS) compliant flashes when GREEN operating in Normal mode; ❑ UL864 I UL2572 I UL2017 Listed; CAN/ULC- if the unit is in a Trouble' condition, and RED to S527 & CAN/ULC-S576 Listed indicate a change of status. - File S24304, Vol. 3 Model XTRI-S ❑ FM Approved This single -input interface module can only monitor and report the status of a N.O. or N.C. contact. RoHS 0 E KFI Siemens Smart Infrastructure -Building Products Intelligent Device Interface Module Data Sheet6167 usa.siemens.com/fire 1. 4" (10.2 cm.) square box I r cm.) back box f, 7: -_; 2. 3.5" (8.9 cm.) ti7 _ 30 double -gang �� �?- back box i 3. 5" (12.7 cm.) square switch ST plate, supplied) Intelligent Device Interface Module Model XTRI-R Through the use of an addressable 'Form C relay, the Model XTRI-R relay and contact device input are controlled at the same address. The relay and input contact can be controlled as a separate function from a Siemens compatible FACP. The relay is typically used where control or shunting of external equipment is required. Model XTRI-D Model XTRI-D is a dual -input module that is designed to supervise and monitor two (2) sets of dry contacts. Model XTRI-D only requires one (1) address, but responds independently to each input. Model XTRI-D is ideal for monitoring a water -flow switch and its respective valve tamper switch. PROGRAMMING HOLES z 3 4 . SLOT KE �` � • �� TAB 6 THERE IS NO ^' " DIRECTIVITY — DESIGN FOR DPU ` CONNECTION. IT PLUG FROM IS ALLOWED TO THE DPU INSERT THE PLUG PROGRAMMER' AT EITHER DIRECTION TESTER NOTES: Each interface module mounts directly to a user -supplied switchbox. The electrical boxes, seen above, are supplied -by -others (130). Models XTRI-D, XTRI-R and XTRI- S mount directly onto a 4-inch (10.2 cm.) square, 2 %` (5.7 cm.) - deep box back box, or to a user - supplied double -gang 3'/z" deep back box. A 5" (12.7 cm.) square, off-white faceplate is included in each shipment of a Siemens Model XTRI-series module. Field -Device Programmer / Test Unit Siemens - Fire Safety innovative technology allows Model XTRI-series intelligent interface modules to be programmed via the Siemens field -device programmer I test unit (Model DPU), which is a compact, portable and menu -driven accessory for electronically programming and testing Siemens peripheral modules and devices promptly and reliably. For instance, the field technician selects the accessory's program mode, and enters the desired address. Model XTRI-series interface module is connected to Model DPU with the programming cable provided with the tester. NOTE: Since the XTRI-series of interface modules are advanced initiating devices, the latest Model DPU firmware update is required. Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. - dials and rotary switches), and reduces installation and service costs by electronically programming and testing the module prior to installation. When set in test' mode, Model DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the module is operating properly. Each field -device programmer 1 test unit operates on AC power or rechargeable batteries, providing flexibility and convenience in the programming I testing of fire -safety equipment from practically any location. Additionally, with the use of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating conditions that could negatively affect any electro-mechanical-addressing mechanism. Siemens 'X' modules may be used along with Model 'H'-series intelligent detectors; Model 'HMS' -series addressable manual stations, or any other 'H'-series addressable intelligent module (e.g. Model HZM or Model HCP). Additionally, the X-series modules are compatible with all Desigo and Cerberus Pro detectors and peripherals of the same circuit. Interspersing 'X' & 'H'-series devices on the same loop is mostly permitted, but there are exceptions: Models HLIM (isolation module) and SBGA-34 (audible base) cannot be used with 'X' devices on the same loop. Siemens Smart Infrastructure - Building Products -2- usa.siemens.comlfire Models XTRI-D I XTRI-R I XTRI-S intelligent interface modules are UL Listed I ULC Listed. Environmental operating conditions for each interface module is 32°F (0*Q to 1207 (49*Q with a relative humidity of no greater than 95%, non -condensing. LED lindicators FLASH FLASH COLOR CONDITION INTERVALS [in seconds] Normal supervisory operation 10 YELLOW: Device is in trouble and needs to be replaced 4 Locate Alarm' 1 Output Device (XTRI-R only) 10 NO FLASH: Power is not being received I Replacement is needed -echnical Data OPERATING VOLTAGE RANGE: 13VDC — 32VDC RELATIVE HUMIDITY: 0 — 95% (non -condensing) ACTIVE' 0R'STANDBY' CURRENT, MAX.: 500uA LINE SIZES AMERICAN WIRE GAUGE (AWG) 14 AWG, max. 18 AWG, min. CURRENT DRAW MAX I AVG. XTRI-S 650pA XTRI-R 750pA XTRI-D 95OpA RELAY RATINGS: (for Model XTRI-R) RESISTIVE: 4 Amps 1 125 VAC 4 Amps 130 VDC INDUCTIVE: 3.5A,120 VAC (0.6 pF) 3.OA, 30 VDC (0.6 pF) 2.OA,120 VAC (0.4 pF) 2.OA,120 VAC (0.35 pF) 2.OA, 30 VDC (0.35 pF) Details for Ordering PART PRODUCT NUMBER S54370 B3 Al Single Input Module Single Input Module S54370 B1 Al (with relay) S54370 B2 Al Dual Input Module 500 033260 Device Programmer / Test Unit NOTE: Refer to installation manual: P/N - A6V101055479 to ensure Model XTRI-D I XTRI-R XTRI-S compatibility with the Siemens FACPs intended for use in the given application. NOTICE- The information contained in this data -sheet document is intended only as a summary, and is subject to change without notice. The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information. Copies of install -type, instruction sheets -as well as the General Product Warning and Limitations document, which also contains important data, are provided with the product, and are available from the Manufacturer. Data contained in the aforesaid type of documentation should be consulted with a fire -safety professional before specifying or using the product. Any further questions or assistance concerning particular problems that might arise, relative to the proper functioning of the equipment, please contact the Manufacturer. SIEMENS