RESUB 1-FIR2023-0064+Fire_Alarm_Equipment_Specification_Sheets+9.20.2023_9.36.21_AM+3793459RESUB
Sep 20 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SIEMENS
Siemens Industry, Inc.
FIS Fire \ Life Safety Division FIR2023-0064
15900 SE Eastgate Way
Bellevue, WA 98008
425.507.4300
For information Contact:
COLIN PINE
colin.pine@siemens.com
PRODUCT DATA SUBMITTAL
9/15/2023
Engineering Data for:
SUNRISE SENIOR LIVING FA UPGRADE
Fire Alarm System
750 EDMONDS WAY
EDMONDS, WA 98233
440P-347628
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
SIEMENS
SIEMENS Industy, Inc. - Fire / Life Safety Division
15900 SE Eastgate Way
Bellevue, WA 98008
Tel: 425.507.4300
1.1 r]dJA r]d N7-lsl rz
SUNRISE SENIOR LIVING FA UPGRADE
750 EDMONDS WAY
EDMONDS, WA 98233
FIRE ALARM SUBMITTAL TABLE OF CONTENTS
MODEL NUMBER DESCRIPTION
XLS / Desigo Modular EQUIPMENT
XDLC Device Loop Card (Isolator compatible)
CAB-BATT Battery Cabinet for (2) 100 A.H. Batteries
Annunciators
SSD-C
System Status Display w/ Control
XLS/Desigo Addressable Devices
FDT421
Intelligent Thermal (Heat) Detector Head
FDOT421
Intelligent Multi -Sensor Smoke/Heat Detector
DB-11
Detector Base
HMS-S
Single -Action Manual Pull Station
HCP
Supervising Control Point Module
XTRI-R
Addressable Relay / Monitor Module with Dual Isolators
XTRI-D
Addressable Dual Monitor Module with Dual Isolators
XTRI-S
Addressable Monitor Module with Dual Isolators
Batteries
PS-121000 100 Amp -Hour 12VDC Battery
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
❑ Supports up to 252 addressable points
❑ Operates and maintains all devices
residing on up to four (4) 'Class A', eight
(8) 'Class B' addressable circuits
❑ Compatible with Siemens intelligent,
addressable'X' and 'H'-series devices:
Multi -criteria / Carbon Monoxide (CO)
Detector with ASAtechnology "
Multi -criteria Detector
with ASAtechnolog/M
Multi -criteria Detector
Thermal (Heat) Detector
Input / Output Interface Module
❑ Polarity insensitive (in non -isolation
mode) via SureWireTm technology:
- Modern technology supports
comprehensive system and interface
communication
❑ Quantity 16 diagnostic light -emitting
diodes (LEDs) for easy circuit diagnosis
❑ Microchip controls on -board isolators
❑ Device Programmer / Tester
(Model DPU) programs and verifies
device's address:
- programming capabilities include
testing a duct detector, as well as
other Siemens addressable devices
❑ Supports 'Class B' 1 'Class A' I 'Class X'
wiring
❑ Supports T-Tapping
❑ Degrade mode
❑ UL864 I CAN / ULC Listed
SIEMENS
The Siemens - Fire Safety Class X' Device Loop Card (Model XDLC) is the interface
used for connecting Siemens addressable, intelligent 'X' as well as 'H'-series
devices.
Each Model XDLC plugs into one (1) slot of the Model CC-2 or Model CC-5 card cage.
Programming for Model XDLC is accomplished via the Desigo Fire Safety Modular
system custom -configuration tool, Zeus-D. Model XDLC takes one (1) address on
the network, communicating up to a total 252 detectors and devices. Model XDLC
has 16 LEDs for diagnostic purposes, and provides ground -fault detection and zone -
isolation circuitry.
The Class X' Device Loop Card (Model XDLC) initializes, operates and maintains all
devices residing on up to four (4) 'Class A', eight (8) 'Class B' addressable circuits.
Model XDLC communicates all relevant device and event data (-Alarm', -Trouble' and
Supervisory' commands) to a Desigo Fire Safety Modular (Desigo Modular) fire -
alarm control panel (FRCP), and supervises the device loop circuit.
Model XDLC is polarity insensitive via SureWire technology, which greatly reduces
commissioning time normally spent tracing down crossed -field wiring. Model XDLC
communicates detector data, such as sensitivity of intelligent fire detectors and
logic -function information, to the Desigo Modular Operating Unit (Model FCM2041-
U2), which is located within a given Desigo Modular system.
Each device loop card supports four (4) 'Class A', eight (8) 'Class B' circuits for up to
a total of 252 addressable devices - as well as relay and audible bases, remote lamps
and duct -detector housings in any combination.
The microprocessor in a Model XDLC controls the
on -board isolation, in case there is a fault (short) in
any of the circuits, thus allowing the other circuit
to continue operating. For continuous protection,
the on -board microprocessor continues to operate
even in the event of a CPU failure.
NOTE: Refer to installation manual: WIN -
A6V101040156 to ensure Model XDLC
compatibility with the Siemens FACPs
intended for use in the given application.
Ukm
Side View _
Front View
Siemens
Smart Infrastructure - Building Products
Data Sheet 7312
usa.siemens.comlfire
in 'Class X' Device Loop Card
1 to a Siemens Card Cage
'Class X' Device Loop Cards are UL Listed I ULC Listed for indoor dry locations within a temperature range of 120'/-3°F
(49'/-2°C) to 32'/-3°F (O'I-2°C) and a relative humidity of 93'I-2% at a temperature of 90'/-3°F (32'/-20C).
Technical Data
24V CURRENT DRAW:
0
[Back Plane]
24V CURRENT DRAW:
100mA + 1.4mA
[Screw Terminal]
pertlevice
6.2V CURRENT DRAW:
1 mA, max.
[Back Plane]
24V CURRENT DRAW:
100mA+ 1.4mA
[Standby]
per device
DEVICE LOOP: 500mA, max.
[@ 30 VDC Max.] (power limited)
NOTICE- The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
Details
forOrdering
MODEL
PART
OR TYPE
NUMBER
PRODUCT
XDLC
S54430-138-A1
Class X
Device Loop Card
SIEMENS
Product
❑ One (1) 1 two (2) 1 three (3) row enclosure The enclosures used with Desigo Fire Safety Modular systems (Models CAB1,
types CAB2, and CA133), along with their accessories, provide a complete set of
hardware for mounting all main system and remote transponder cards and
❑ Blank plates (ordered separately) for inner modules.
and outer doors
The hardware allows each DSFM system to be configured for a wide variety of
❑ Clear lens and grill plates (sold separately) applications. Included in the enclosure series are backbox and door sets;
for use with outer door removable mounting plates and clear lenses; louvered ventilation grill plates,
❑ UL 864 Listed, ULC Listed and blank plates for use with the enclosure doors.
All enclosures come with ground straps for the inner and outer doors; shield
termination lugs; grounding lugs, and tie wrap lances for securing wire.
All enclosures can also mount system backup batteries up to 31AH in capacity.
&' I �� One -row system enclosure [with mounted optional [with mounted optional
u inner door] inner door]
Siemens Data Sheet 7327
Smart Infrastructure — Building Products usa.siemens.comlfire
Single -Row Enclosure
Model CAB1, the smallest of the
Desigo Fire Safety Modular system
enclosures, can house a single Model
CAB -MP cabinet mounting plate for
mounting card cages, power supplies
and bulk amplifiers. Model CAB1 also
has four (4) mounting slots on the
inner door for mounting an Operator
Interface (01) and Model ID -MP switch
module brackets.
Each Model CAB1 comes complete
with a black back box, with black
inner and outer doors, a single lock -
and -key set on the outer door, and a
single OD -LP outer door lens plate
(installed). A red version (Model
CAB1 R) is also available.
Approximate size is 27" (68.6cm.)
high; 26" (66cm.) wide, and 8"
(20.3cm.) deep.
Two -Row Enclosure
Model CAB2 is the mid -sized Desigo
Fire Safety Modular enclosure capable
of housing a maximum two (2) Model
CAB -MP cabinet mounting plates.
The inner door has two (2) rows of
four (4) mounting slots. The outer
door has space for mounting two (2)
outer door plates (Models OD -LP, OD -
BP or OD -GP). The outer door can be
configured to open from either side.
Model CAB2 consists of the Model
CAB2-BB back box; the Model CAB2-
BD black inner and outer door
package, and one (1) Model OD -LP
lens plate. The outer door has a single
lock and key set installed. Red doors
are available in Model CAB2-RD.
Additional door mounting plates must
be ordered separately. Approximate
size is 45" (114.3cm.) high, 26"
(66cm.) wide, and 8" (20.3cm.) deep.
Three -Row Enclosure
Model CAB3, the largest single Desigo
Fire Safety Modular enclosure
available, can house a maximum three
(3) Model CAB -MP cabinet mounting
plates in the enclosure, and three (3)
rows of inner door mounting slots. The
outer door can be configured to open
from either side. Model CAB3 consists
of the Model CAB3-BB back box; the
Model CAB3-BD black inner and outer
door package, and one (1) Model OD -
LP lens plate.
The outer door has two (2) locks and
key sets installed. Red doors are
available via Model CAB3-RD.
Additional door mounting plates
must be ordered separately.
Approximate size is 63" (160cm.)
high, 26" (66cm.) wide, and 8"
(20.3cm.) deep.
Enclosure Trim Kits
Trim kits are available for all system
enclosures for semi -flush mounting
applications. Model CAB1-TK (for
black enclosures) and Model
CAB1 R-TK (for red enclosures) fit
Models CAB1 and CAB1-R
enclosures. Similarly, Models
CAB2-TK and CAB2R-TK fit the
Model CAB2 enclosure, and Models
CAB3-TK and CAB3R-TK fit the
Model CAB3 enclosure.
CAB2-XBD CAB3-XBD
Remote Transponder Doors
The Desigo Fire Safety Modular
system can use remote
transponders for mounting
additional modules such as
amplifiers, without requiring an
Operator Interface (01) or any
control switches.
Special doors are available for
systems using Model CAB2 or
Model CAB3 remote transponders.
Models CAB2-XBD and CAB3-XBD
omit the unused inner door and
come complete with ventilation
louvers built into the door.
Model CAB2-XBD comes in black,
and fits specifically on Model CA132-
BB. Model CAB3-XBD also comes in
black, and fits specifically on
Model CAB3-BB.
Remote transponder doors are also
orderable in red: Models CAB2-XRD
and CAB3-XRD.
Outer -Door Grill Plate
Model OD -GP also covers an entire
row on the outer door of a system
cabinet, but has four rows of
ventilation louvers on it. Model OD -
GP is mounted in front of system bulk
amplifiers, card amplifiers, or other
modules that generate heat. Using
Model OD -GP will permit airflow
across these modules to aid in heat
dissipation. A single grill plate is
included with each Model OG-GP.
Remote System Enclosures
Models REMBOX2 and REMBOX4 are
Desigo Fire Safety Modular system
enclosures that are used for remotely
mounting inner -door modules, such
as the Desigo Modular 01, Model
SCM-8, Model LCM-8 and Model FMT.
REMBOX4 hardware used with Desigo
Fire Safety Modular systems are
thinner than the regular CAB
enclosures, just 5" (12.7cm.) deep
overall, and are perfect for mounting
in places where space is limited (such
as lobbies or behind a receptionist's
desk).
Due to their smaller depth, no card
cages, power supplies or bulk
amplifiers can be mounted in a given
REMBOX. However, modules such as
the Remote Network Interface Module
(Model RNI); the Output -Control
Module (Model OCM-16) and the
Supervised Input Module (Model SIM-
16) can be mounted in a REMBOX.
Due to the depth of the Live Voice
Module (Model LVM) and the Model
FMT firefighters' master telephone, no
Model OCM-16 or Model SIM-16
modules can be used simultaneously
with Model LVM or Model FMT.
Models REMBOX2 and REMBOX4
are designed for flush mounting
with no trim kit required. Both
enclosures also come with a clear
lens plate on the cover.
Siemens _
usa.siemens.comlfire
Smart Infrastructure — Building Products _2
(with doors closed)
(with doors open)
Two -Module Remote Enclosure
Model REMBOX2 has two (2) inner -
door module spaces, and can hold
on Desigo Modular 01, up to two
(2) switch -module brackets, one
(1) Model LVM. Combinations are
permissible.
Model REMBOX2 can also mount a
single Model RNI on a bracket
included in the backbox. A bracket
(Model REMBOX2-MP) can be used
to mount up to four (4) Model
OCM-16s or Model SIM-16
enclosures. Model REMBOX2-MP
must be purchased separately.
Approximate size of Model
REMBOX2 is 14-1 /2" (36.8cm.)
wide, 18-112" (47cm.) high and 5"
(I 2.7cm.) deep.
NOTE: A red, (2) two -module remote
lobby enclosure (Model
REMBOX2R) is also available.
Four -Module Remote Enclosures
Model REMBOX4 has space for
mounting four (4) inner door
modules. Any combination (two -
module spaces), switch module
brackets, Model LVM or Model
FMT (one -module space each) on
a Desigo Modular OI can be used.
Unused module spaces can be
covered with Model ID-SP blank
plates.
Cabinet Mounting Plate
The cabinet mounting plate (Model
CAB -MP) provides mounting for a single
row of modules in a Desigo Modular
system cabinet. Four (4)-module spaces
are available on Model CAB -MP. Model
CAB -MP is used to mount the Model CC-
5 card cage, the Model CC-2 card cage,
the Model PSC-12 power supply, the
Model PSX-12 power supply extender,
and the Model ZAM-80 I 180 zone
amplifiers.
Inner -Door Mounting Plate
The inner door mounting plate (Model
ID -MP) is mounted on the inner door of
a CAB enclosure. Model ID -MP plates are
used to mount Model SCM-8 switch
control modules; Model LCM-8 LED
control modules, or with Model FCM-6.
Four (4) mounting plates are included in
each Model ID -MP. Each mounting plate
has four (4) spaces for control modules,
and can hold either four (4) Model SCM-
8 modules {one [1 ] control module
space each}; four (4) Model LCM-8
modules {one [1 ] control module space
each}; or two (2) Model FCM-6 modules
{two [2] module spaces each}.
Combinations are also allowed. Blank
spaces in Model ID -MP can be covered
using the Model BCM blank control
module plate. A maximum four (4)
Model ID -MP plates can be mounted in a
single row on the inner door.
Inner -Door Single Blank Plate
Model ID-SP is used to cover any single
module blank spaces on the inner door
not used to mount a Desigo
Modular OI or one (1) Model ID -MP.
Up to four (4) Model ID-SP plates
can be mounted in a single row on
the inner door. Two (2) blank plates
are included in each Model ID-SP.
Class X Assembly Plate
The XDACT Assembly (Model
XDACT-ASSY) is the blank plate
used for holding the optional
Digital Alarm Communication
Transmitter (DACT), Model
FCA2015-U1. The XDACT
assembly vertically mounts on the
back, left-hand side of an inner
door of any type of Desigo
Modular panel, adjacent to an
Operator Interface (01).
Model BCM
Blank Control Module Plate
Model BCM is used on Model ID -
MP to cover any blank areas where
control modules are not used. A
maximum four (4) Model BCM
plates can be mounted on a single
Model ID -MP. Four (4), blank -
module plates are included in
each Model BCM.
Outer Door Lens Plate
Model OD -LP is a clear plastic lens
plate mounted on the outer door of
a system cabinet. Model OD -LP is
used to allow operators to see the
system interface and controls
mounted on the inner door, but
restricts access to unauthorized
users. Model OD -LP covers an entire
row on the outer door.
A single lens plate is included with
each Model OD -LP.
Siemens
Smart Infrastructure — Building Products —3— usa.siemens.comlfire
Outer Door Blank Plate
The Outer Door Blank Plate (Model
OD -BP) is used to cover an entire
row of a Desigo Modular system
cabinet. Model OD -BP is mounted
when no module is used in that
location. Model OD -BP is mounted
on the outer door, and one (1) blank
plate is included with each order.
Inner
Door
Outer
Door
Adapter
Plate
MME-3—series Enclosure Adapters
Model XLS-MME3-ADPT, which
must be used in conjunction with
Model CAB -MP plates, is an
adapter that allows Desigo
Modular cards to be mounted in
older -generation MXL Model
MME-3—series or Model MBR-2
medium black enclosures.
Model XLS-MME3R-ADPT, which
must be used in conjunction with
Model CAB -MP plates, is an
adapter that allows Desigo
Modular cards to be mounted in
older -generation MXL Model
MME-3R medium red enclosures.
oor Door
dapter
D
Plate
MSE-3—series Enclosure Adapters
Model XLS-MSE3-ADPT is an adapter that
allows Desigo Modular cards to be
mounted in older -generation MXL-IQ
Model MSE-3L or Model MSE-3M black
enclosures.
Model XLS-MSE3R-ADPT is an adapterthat
allows Desigo Modular cards to be
mounted in older -generation MXL-IQ
Model MSE-3LR or Model MSE-3MR red
enclosure.
Plate
RCC13-series Enclosure Adapters
Model XLS-RCC13F-ADPT is an adapter
that allows the Desigo Modular Model
SSDI-C series remote annunciator to be
mounted in older -generation Model RCC-
1 F or Model RCC-3F black, flush -mount
enclosure.
Model XLS-RCC13FR-ADPT is an adapter
that allows the Model SSDI-C series to be
mounted in older -generation RCC-1 FR and
RCC-3FR, red flush -mount enclosure.
M
Plate
mo !
RCC-1—series Enclosure Adapters
Model XLS-RCC1-ADPT is an adapter that
allows the Desigo Modular Model SSDI-C
series remote annunciator to be mounted
in older -generation Model RCC-1 surface -
mount enclosure.
Remote Transponders
Desigo Modular systems can use
remote transponders for mounting
additional modules such as
amplifiers without requiring a
Desigo Modular operator interface
or any control switches.
Special doors are available for
systems using Model CAB2 or Model
CAB3 remote transponders. These
doors (Models CAB2-XBD and CAB3-
XBD) omit the unused inner door,
and come complete with ventilation
louvers built into the door.
Special doors are available for
systems using Model CAB2 or
Model CAB3 remote transponders.
These doors (Models CAB2-XBD and
CAB3-XBD) omit the unused inner
door, and come complete with
ventilation louvers built into the
door.
Enclosure Trim Kits
Trim kits are available for all Desigo
Modular system enclosures for
semi -flush mounting applications.
Model CAB1-TK (for black
enclosures) and the Model CAB1 R-
TK (for red enclosures) fit inside the
Models CAB1 and CAB1 R
enclosures. Similarly, Models CAB2-
TK and CAB2R-TK fit inside the
Model CAB2 enclosure, while
Models CAB3-TK and CAB3R-TK fit
the Model CAB3 enclosure.
Siemens _
Smart Infrastructure — Building Products _4 usa.siemens.comlfire
IM
MODEL
PART
PRODUCT
OR TYPE
NUMBER
Blank Control
BCM
500-033320
Module Plate
[Four (4) per
package]
Field -mounted
CAB-BATT
500-633917
enclosure for 100AH
batteries, black
Field -mounted
CAB-BATT-R
500-634925
enclosure for 100AH
batteries, red
Complete Single -Row
CAB1
500-633007
Cabinet, black
CAB1R
500-633728
Complete Single -Row
Cabinet, red
CAB1-TK
500-633013
Single -Row Trim -kit
Cabinet, black
CAB1 R-TK
500 633729
Single -Row Trim -kit
Cabinet, red
CAB2-BB
500-633009
Two -Row
Back Box, black
CAB2-RB
500 634941
Two -Row
Back Box, red
Two -Row Inner &
CAB2-BD
500-633008
Outer Door Set,
black
CAB2-RD
500-633755
Two -Row Inner &
Outer Door Set, red
CAB2-TK
500-633014
Two -Row Trim -kit
Cabinet, black
CAB2R-TK
500-633753
Two -Row Trim -kit
Cabinet, red
CA132-XBD
500-633768
CAB2
[Transponder
Door
Medium -Enclosure
CAB2-XRD
500-633792
Transponder Door
[mounts to Model
CAB2-RB
CAB3-BB
500-633011
Three -Row
Back Box, black
CAB3 RB
500-634942
Three -Row
Back Box, red
Three -Row Inner &
CAB3 BD
500-633010
Outer Door Set,
black
CAB3-RD
500-633757
Three -Row Inner &
Outer Door Set, red
CAB3-TK
500-633015
Three -Row Trim -Kit
Cabinet, black
CAB3R-TK
500-633754
Three -Row Trim -Kit
Cabinet, red
CAB3-XBD
500-633769
CAB3
Transponder Door
Large -Enclosure
CAB3-XRD
500-633793
Transponder Door
[mounts to Model
CAB3-RB]
MODEL
PART
PRODUCT
ORTYPE
NUMBER
Module
CAB -MP
500-633012
Mounting Plate
Bracket to hold down
55AH batteries in
CAB-55-BRKT
S54430-B1-A1
CAB-BATT enclosure
[ Required for Seismic
Applications ]
Bracket to hold down
100AH batteries in
CAB-100-BRKT
S54430-132-A1
CAB-BATT enclosure
[ Required for Seismic
Applications ]
ENCL-01
S54465-C63 AlFSN,Uclosure
y-lock)
Inner -Door Enclosure
ID -MP
500-633027
Mounting Plate
[four (4) per package]
Single -Door Inner -Door
ID-SP
500-633028
Enclosure Mounting
Plate
[two (2) per package]
OD -BP
500-633017
Outer Door
Blank Plate, black
OD-BP-R
500-634919
Outer Door
Blank Plate, red
OD -GP
500-633018
Outer
Grill Plate, black
OD-GP-R
500-634920
Outer Grill Plate, red
OD -LP
500-633016
Outer Door Lens Plate
(2) Two -module
REMBOX2
500-633772
remote lobby
enclosure, black
(2) Two -module
REMBOX2R
500-650612
remote lobby
enclosure, red
Mounting plate for
REMBOX2-MP
500-634211
Models OCM-16 /
SIM-16 in Model
REMBOX2
(4) Four -module
REMBOX4
500-633914
remote lobby
enclosure, black
(4) Four -module
REMBOW
500-650613
remote lobby
enclosure, red
Mounting plate for
REMBOX4-MP
500-634212
Models OCM-16 /
SIM-16 in Model
REMBOX4
MODEL
PART
PRODUCT
OR TYPE
NUMBER
XDACT-ASSY
S54430-A5-A1
XDACTMounting
Plate (with cable)
XLS-MLE6-ADPT
S54430-C9-A1
MLE-6 Enclosure
Adapter, black
XLS-MLE6R-ADPT
S54430-C9-A2
MLE-6R Enclosure
Adapter, red
MME-3 and MBR-2
XLS-MME3-ADPT
S54430-C8-A1
enclosure
adapters, black
XLS-MME3R-ADPT
S54430-C8-A2
MME-3 and MBR-2
encl. adapters, red
XLS-MSE2-
MSE-2 enclosure
ADPT
S54430-C7-A1
adapter, black
XLS-MSE2R-ADPT
S54430-C7-A2
MSE-2 enclosure
adapter, red
MXL-IQ I MSE-3L &
XLS-MSE3-ADPT
S54430-C14-A1
MSE-3M enclosure
adapters, black
MXL-IQ I MSE-31_ &
XLS-MSE3R-ADPT
S54430-C14-A2
MSE-3M enclosure
adapters, red
XLS-RCC1-ADPT
S54430-Z14-A1
RCC-1 enclosure
adapter, black
RCC-1 F I RCC-3F
XLS-RCC13F-ADPT
S54430-Z13-A1
enclosure adapter,
black
RCC-1 F I RCC-3F
XLS-RCC13FR-ADP
S54430-Z13-A2
enclosure adapter,
red
Siemens _
usa.siemens.comlfire
Smart Infrastructure — Building Products _5
NOTICE— The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets —as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
❑ 4 rows - 40-character alphanumeric
LCD screen, backlit upon status
change or display toggling
❑ Audible and event -status
light -emitting diodes (LEDs)
❑ Scroll buttons to view additional
events
❑ Local sounder
❑ Supports 'Class B' or'Class A' wiring
❑ Built-in transient protection
❑ Mounts in its own enclosure or
REMBOX-series enclosure
❑ Optional local -system control
❑ Downloadable firmware
❑ UL864 & CAN / ULC-S576 Listed
SIEMENS
Auct Overview
The System -Status Display (SSD Series) is a remote light -emitting diode (LED)/
liquid -crystal display (LCD) display unit that shows the local status of a Desigo Fire
Safety Modular system. A LED will illuminate when Alarm I Supervisory I Trouble
and Security events occur on the system. A (4) four -line LCD will give details of
the event in alphanumeric form. The display can be toggled to display additional
events. Optional remote -system -control capabilities are available.
•- •
The SSD Series display has separate LEDs for Alarm
Supervisory I Trouble and Security events on the
Desigo Fire Safety Modular system. Each LED will
flash when unacknowledged events of that type are
present on the system. The LED will change to
steady, upon acknowledgment of the event.
Also, there are two (2) LEDs that indicate the state
of audible circuits on the system: one (1) LED to
indicate that the circuits are active and one (1) LED
to indicate the circuits have been silenced.
The LCD display on the Model SSD-series display
has four (4) rows — 40 characters for each row.
When the Desigo Fire Safety Modular system is
in its normal supervisory state with no events
present, the display will annunciate the system
ID information, the date and the time of day.
When an event occurs on the system, the LCD
display will show the event type and address,
the time of the event, the custom message for
that address, the usage of the device, and
whether the event is acknowledged' or not.
Additionally, the display will show the total
number of all types of events present on the
system. The display has a backlight feature that
operates upon receiving any event information
or when any operator buttons are pressed.
System -Status Display Series
(with control for remote
enclosures)
System -Status Display Series
A local sounder is included with the Model SSD-series display that operates when
any events are displayed on the system. The sounder can be optionally disabled
through software programming. Pressing any operator buttons will silence the
local sounder when an event is present.
The SSD Series display has two (2) display -control buttons that are used to display
the next or the previous event information in the sequence, and a local sounder
silence button. Programming for the SSD Series display is done with the Zeus-D
programming tool.
Siemens
Smart Infrastructure - Building Products
Data Sheet 7326
usa.siemens.com/fire
Models SSD-C and Model SSD-C-REM have three (3) additional control buttons for acknowledging events, silencing
audible circuits, and resetting the system. Model SSD-C has an integral key switch that enables these control buttons to
operate. Model SSD-C-REM is located within a locked cabinet, so no additional key switch is required for enabling the
control buttons.
The SSD Series display is remotely connected to the H-Net communication bus from any Model NIC-C interface in a
Desigo Fire Safety Modular system enclosure using Class B or Class A wiring. 24VDC is required to run the SSD Series
display, and can be provided from a Model PSC-12 Power Supply or PSX-12 Power Supply Extender in the Desigo Fire
Safety Modular system enclosure. Power from other UL Listed 24VDC power sources is also acceptable.
The SSD Series display has screw terminals capable of supporting 12 to 22-gage wires. The H-Net communication from the
Desigo Fire Safety Modular system can be terminated on the SSD Series display, or may pass through for communication with
other modules. Diagnostic LEDs on the SSD Series display indicate power and communication status.
Models SSD and SSD-C can be mounted in a (2) two -gang electrical box or a (4) four -inch square electrical box. No
flush -trim kit is required. The unit is approximately 10-112" (26.7cm.) wide, 6-118" (15.2cm.) high, and1-112" (3.8cm.)
deep.
The Model SSD-C-REM is mounted in a Model REMBOX2 or Model REMBOX4 Remote Lobby Enclosure, or any CAB
enclosure inner door. Model SSD-C-REM requires two (2) module spaces in the remote lobby enclosure, and its bracket
supports the mounting of four (4) inner door modules (such as Model SCM-8 or Model LCM-8 modules) below the
display. The inner door module spaces are arranged in two (2) rows of (2) two -module spaces.
Products are UL 864 10th Edition Listed for indoor dry locations within a temperature range of 120+1-3°F (49+1-2°C)
to 32+1-3°F (0+1-2°C) and a relative humidity of 93+I-2% at a temperature of 90+I-3°F (32+1-2°C).
Electrical Ratings
SSD-C
TYPICAL 200mA (max) at 24 VDC
INPUT VOLTAGE 24 VDC (Nominal)
( 31 VDC max ) filtered
NOTE:
An auxiliary -regulated, power -limited power supply
may be used to provide power to Model SSD. The
power supply must be UL Listed for Fire -Protection
Signaling Application. Be sure to also include Model
SSD-C in the battery calculations.
SSD I SSD-INTL
TYPICAL
200mA (max) at 24 VDC
INPUT VOLTAGE
24 VDC (Nominal)
( 31 VDC max ) filtered
NOTE:
An auxiliary -regulated, power -limited power supply
may be used to provide power to Model SSD. The
power supply must be UL Listed for Fire -Protection
Signaling Application.
SSD-C-REM
TYPICAL
200mA (max) at 24 VDC
INPUT VOLTAGE
24 VDC (Nominal)
( 31 VDC max ) filtered
NOTE:
An auxiliary -regulated, power -limited power supply
may be used to provide power to Model SSD-C-REM.
The power supply must be UL I ULC approved for Fire
Protection Signaling Application. Be sure to also
include Model SSD-C-REM in the battery calculations.
MODEL
PART
PRODUCT
OR TYPE
NUMBER
SSD
E0-03417]
System-Status Display
SSD-C
500-648733
System -Status Display
[with control]
System -Status Display
SSD-C-REM
500-634773
[with control for remote -lobby
enclosure]
REMBOX2
500-633772
Small Remote -Lobby Enclosure
REMBOX4
500 633914
Large Remote -Lobby Enclosure
BCM
500-033320
Blank Control Module Plate
Siemens
Smart Infrastructure — Building Products —2— usa.siemens.comlfire
NOTICE- The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
❑ Built-in ISOtechnologyTM
❑ Compatible with Siemens Model ' H'-
series devices on the same loop (with
Desigo Fire Safety Modular I FireFinder
XLS/V I FC/FV20-series fire -alarm
control panels
❑ Contains seven (7) field -selectable
settings in a temperature range of 135°F
- 175°F (57.2°C - 78.9°C)
❑ Provides a low -temperature warning of
40°F (4.4°C)
❑ Field programmable as rate -of -rise or
fixed temperature
❑ Tri-color detector -status light -emitting
diode (LED) with 360 'view
❑ Compatible with Model DPU (device
programmer / loop tester)
❑ Utilizes advanced, microprocessor -based
signal processing
❑ Each detector is self -testing:
- complete diagnostics performed
every 10 seconds
❑ Polarity insensitive via SureWireTM
technology
❑ Functions with Model DB-11-series
mounting bases
❑ Superior electromagnetic interference
(EMI) and radio -frequency interference
(RFI) immunity
❑ Restriction of Hazardous Substances
(RoHS compliant)
❑ UL 521 Listed, ULC Listed; CSFM (#7272-
0067:0258) Approved
SIEMENS
ProductOverview
The Intelligent Thermal (Heat) Detector (Model FDT421) provides an advanced method
of detection, address programming supervision - combined with sophisticated FACP
communication. Model FDT421 uses a state-of-the-art thermistor, microprocessor and
advanced signal analysis, providing high reliability and accuracy.
Additionally, Each Model FDT421 unit is UL listed including advanced built-in
ISOtechnologyTm - a "True Class-V SLC operation (use is optional) greatly
improving system reliability and circuit integrity while providing advanced
addressable fault finding.
Each model FDT421 is a cost-effective, two -wire I addressable thermal detector that
provides a distinctive, advanced feature: seven (7) field -selectable temperature
settings specially tailored for application -specific detection needs combined with Class-
X SLC operation built-in avoiding additional installation and material cost.
The temperature -range settings for each Model FDT421 detector is between 1357
(57°C) - 175°F (79°C) with fixed and rate -of -rise programmability. This variance
provides the customer with maximum flexibility to program the temperature settings to
suit multiple application needs and changing environmental conditions.
Model FDT421 can be configured to provide a low -temperature warning signal at
407 (4.4°C). This feature - along with a compatible FACP (Design Fire Safety
Modular I FireFinder XLS/V or with Desigo FC /FV2025 or FC /FV2050 FACPs) - serves
as prevention of water freezing in pipes for sprinkler systems, meeting NFPA 72.
Model FDT421 also utilizes a modern, accurate and shock -resistant thermistor to
sense significant changes in temperature.
Each Model FDT421 detector has seven (7) pre-programmed parameter sets that can
be selected by the Siemens FRCP.
raw
Thermal (Heat) Detector
Siemens
Smart Infrastructure - Building Products
Data Sheet 6151
usa.siemens.com/fire
1. Thermistor
Model FDT421
RED
conditions:
1. Dust cover
2. Thermal (heat) detector
NOTE: Each detector consists of a
dust -resistant chamber, a solid state,
functional internal sensor, and
microprocessor -based electronics
with a low -profile plastic housing.
Every Model FDT421 fire detector is
shipped with a protective dust cover.
!rvision and Testing
contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct colors: GREEN
During each flash interval, the microprocessor -based detector monitors the following fire -system
Temperatures reaching programmed thresholds
Internal sensors and electronics are functional
Based on the results of the monitoring, the LED indicator flashes the following:
FLASH COLOR
CONDITION
FLASHINTERVAL
[in seconds]
Normal supervisory operation.
GREEN*:
Temperature has not reached programmed
10
alarm thresholds or set points.
YELLOW:
Detector is not operating at
4
normal capacity and needs replacement.
Alarm' condition
1
NO FLASH:
Detector is not powered.
—
* denotes LED can be turned OFF
Please follow the corresponding description of the panel used.
A quick visual inspection is sufficient to indicate the condition of the detector at any time.
If more detailed information is required, a printed report can be provided from the respective Desigo Fire Safety Modular
FireFinder XLSIV or Model FC20-series FACPs that indicates the status and settings assigned to each individual detector.
M__W W
All Model FDT421 detectors use a surface -mounting base, Model DB-11 or Model DB-11 E, which mounts on a 4-inch
(10.2 cm.) octagonal, square or single -gang electrical box. The base utilizes screw -clamp contacts for electrical
connections and self -wiping contacts for increased reliability.
The Model DB-11 detector base can be used with the optional Siemens Model LK-11 detector locking kit, which contains
50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has
aesthetically conducive plugs to cover the outer mounting -screw holes.
Model FDT421 may be installed on the same initiating circuit with the Siemens Model 'H'-series detectors and devices
[when used with Desigo Fire Safety Modular I Model FC20-series I FireFinder XLSIV FACPs] —
• HFP-11, HFPT-11
• Model 'XTRI' - series interfaces
• Model 'XMS' - series manual stations
• Model 'HTRI' - series interfaces
• Model'HMS'- series manual stations
• Model'HCP' - output control modules
• Model 'HZM' - series of addressable, conventional zone modules
Siemens
Smart Infrastructure - Building Products —2— usa.siemens.comlfire
Installation of Model FDT421 intelligent, addressable thermal detector requires a two -wire SLC circuit. In many retrofit
cases, existing wiring may be used. 'T-tapping' is permitted only for Style 4 (Class B) wiring. Model FDT421 is polarity
insensitive when not used in Class-X mode, which can reduce installation and debugging times. The unit's value is
multiplied with built-in ISOtechnology the True Class-X - NFPA 72 compliant SLC isolation feature, supporting up to 252
isolation ready devices per loop. When used in mixed mode a maximum of 30 non -isolated devices between isolation
devices (wired in polarity -insensitive mode). Each detector fits into one (1) wall -or -ceiling footprint, and only occupies
one (1) address on the signal -line circuit (SLC).
Model FDT421 can be applied within the maximum 50-feet (15.24 m.) center spacing (2,500 sq. ft. [232.3 sq. m.1) per
Underwriters' Laboratories. This application guide is based on ideal conditions, specifically, smooth -ceiling surfaces,
minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not
mount detectors in close proximity to heating I ventilation I air-conditioning (HVAC) outlets. Exposed joists or beamed
ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire -protection system
engineering and common sense dictate how and when fire detectors are installed and used. Contact your local
Siemens - Fire Safety distributor or sales office whenever you need assistance applying Model FDT421 in unusual
applications.
Be sure to follow NFPA guidelines and UL Listed I ULC Listed installation instructions included with every Siemens - Fire
Safety detector - and local codes for all fire -protection equipment.
Model FDT421 is a plug-in, (2) two -wire thermal (heat) detector, compatible with Desigo Modular I FireFinder XLSIV
and Model FC20-series FACPs. Each Model FDT421 detector has microcomputer -chip technology and highly stable,
solid-state electronic circuitry. Model FDT421 detectors utilize a modern, accurate and shock -resistant thermistor to
sense temperature changes. This electronic -sensing method virtually eliminates thermal lag associated with mechanical
temperature -sensing devices and provides almost instantaneous temperature status to the FRCP.
Model FDT421 provides seven (7) field -selectable, pre-programmed temperature settings:
Fixed Temperature set points (5)
Rate of Rise set points (2)
• Fixed 135°F (57°C)
• Fixed 145°F (63°C)
• Rate -of -Rise: 15°F 1 min. (8.3°C) at fixed 135°F (57°C)
• Fixed 155°F (68°C)
• Rate -of -Rise: 15°F I min. (8.3°C) at fixed 175°F (79°C)
— — —
• Fixed 165°F (74°C)
• Fixed 175°F (79°C)
Additionally, the Model FDT421 detector has the following optional feature:
• Model FDT421 provides indication of potential water freezing for sprinkler systems, via configuration
for reporting a low -temperature warning of 40°F (4.4°C).
This feature is compatible with Desigo Modular systems, as well as with FireFinder XLSIV and Desigo
FCIFV2025 or FCIFV2050 FACPs.
4.13" (14.5 cm.)
0
AM
Siemens
Smart Infrastructure - Building Products -3- usa.siemens.comlfire
Model FDT421 is compatible with the Siemens field -device programmer / test unit (Model DPU), which is a compact,
portable and menu -driven accessory for electronically programming and testing these addressable detectors promptly and
reliably. For instance, the field technician selects the accessory's program mode, and enters the desired address.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. — dials and rotary
switches), and reduces installation and service costs by electronically programming and testing the detector prior to
installation. When set in 'test' mode, Model DPU will perform a series of diagnostic tests without altering the address or
other stored data, allowing technicians to determine if the detector is operating properly.
Each field -device programmer / test unit operates on AC power or rechargeable batteries, providing flexibility and
convenience in the programming / testing of fire -safety equipment from practically any location. Additionally, with the use
of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating conditions
that can accompany the vitality of a mechanical -addressing mechanism.
The encompassing result is an intelligent detector that provides enhanced detection capability to a wide range of products
of combustion — while offering unsurpassed rejection to nuisance -alarm sources, including: dust I steam I aerosols and
other deceptive phenomena that could cause false alarms.
Technical
Data
'32°-'120°F (0°-'49°C)
[with 145°F (63°C) 1155°F (68°C)
OPERATING
11657 (74°C) and 175°F (79°C)
TEMPERATURE:
alarm -threshold settings]
132°-'1007, (0°-'38°C)
[With 135°F (57°C) alarm
threshold setting]
Model FDT421 provides
seven (7) field -selectable,
pre-programmed
temperature settings:
• Fixed 135°F (57°C)
• Fixed 145°F (63°C)
• Fixed 155°F (68°C)
THERMAL
• Fixed 165°F (74°C)
RATING:
Fixed 175°F (79°C)
Rate -of -Rise:
15°F/ min.(8.3°C)
at fixed 135°F (57°C)
Rate -of -Rise:
157/ min.(8.3°C)
at fixed 175°F (79°C)
RELATIVE
0 - 95%
HUMIDITY:
(non -condensing)
AIR
PRESSURE:
No effect
INPUT VOLTAGE
16VDC - 30VDC
RANGE:
ALARM'
410pA
CURRENT, MAX:
'STANDBY'
250pA
CURRENT, MAX:
MAXIMUM
50-ft. (15.24 m.) centers
SPACING:
(2500 sq. ft. 1232.3 sq. m.),
per NFPA 72 and ULC-S524
DETECTOR
0.317 Lbs. (0.144 kg.)
WEIGHT:
CompatibilitiesPanel
MODEL
DATA
OR
SHEET
PANEL
TYPE
XLS
6300
FireFinder (fire)
XLSV
6340
FireFinder (fire w/ voice)
Desigo
Modular
7300
Desigo Modular (overview)
FC2005
6813
Desigo Fire Safety
50-point addressable
FC2025
Desigo Fire Safety 252-pt.
addressable (fire)
6815
FC2050
Desigo Fire Safety 504-pt.
addressable (fire)
Desigo Fire Safety
FV2025
252-point addressable
(fire w/ Intelligent Voice
Communication [IVC])
6821
504-pt. addressable
FV2050
(fire w/ Intelligent Voice
Communication [IVC])
Details for Ordering
MODEL
PART
OR
NUMBER
PRODUCT
TYPE
FDT421
S54320-F5-A1
Thermal (Heat) Detector
Compatible Devices
MODEL
PART
OR
NUMBER
PRODUCT
TYPE
Sounder base with Loop -
ABHW-4B
S54320-F13-A1
Power Option
Sounder base for
ABHW-0S
S54320-F14A1F
Sleeping Areas
Surface Mount Adapter Box
ADB-BOX
500-698360
for Audible Base
Relay base compatible with
DB2-HR
S54370-F12-A1
Siemens standard and
advanced detectors
Detector
DB-11
500-094151
Mounting Base
DB-11E
500-094151E
Detector Base, small
Remote Alarm Indicator:
RL-HC
500-033230
4"(10.2 cm) octagon -box
mount, red
RL HW
500 033310
Remote Alarm Indicator:
single -gang box mount, red
LK-11
500-695350
Base Locking Kit
See: www.STI-USA.com for further
details on ordering Model STI-9604
In Canada order:
MODEL
OR
PART
PRODUCT
NUMBER
TYPE
Detector Mounting
DB-11C
500-095687
Base, ULC Listed
Siemens
Smart Infrastructure - Building Products —4— usa.siemens.com/fire
NOTICE- The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
❑ UL 268 7th Edition Listed
❑ Built-in ISOtechno/ogyTM
❑ 252 Isolation devices per SLC
❑ Each detector is self -testing:
complete diagnostics performed every
10 seconds
self -monitored for sensitivity within
UL Listed limits
❑ Listed, approved as a heat detector:
Rate -of -Rise Detection: 15°F / min.
(8.3°C / min.)
Fixed: 135°F (57°C)
❑ Superior electromagnetic interference
(EMI) and radio -frequency interference
(RFI) immunity
❑ Field programmable as rate -of -rise or
fixed temperature, per Alarm Source 2' 1
Standard parameter
❑ Tri-color detector -status light -emitting
diode (LED) with 360' view
❑ Compatible with Model DPU (device
programmer / loop tester)
❑ Polarity insensitive via SureWireTM
technology (in non -isolator mode)
❑ Functions with Model DB-11-series
mounting bases
❑ Restriction of Hazardous Substances
(RoHS compliant)
❑ Automatic environment compensation
❑ UL Listed I FM, CSFM Approved
UL 268: 'Open Area Smoke Detection'
UL 268A (Duct) - Direct -in -Duct' use
UL 521: Open Area Heat Detection'
ULC-S529:'System Smoke Detector'
ULC-S530: Heat Actuated Fire Detection'
FM 3230:'Open Area Smoke Detection'
FM 3210:'Open Area Heat Detection'
CSFM I File: 7272-0067:0258
SIEMENS
The Photoelectric I Thermal (Heat) Detector (Model FDOT421) is an intelligent,
addressable multi -criteria detector that incorporates optical and thermal sensors, and
uses signals in a neural network to create an intelligent multi -criteria detector. The
encompassing result is a detector that provides enhanced detection to a wide range of
products of combustion.
Model FDOT21 is UL 268 7th Ed. listed and incorporates advanced built-in
ISOtechnologyrM - True Class-X SLC operation (use is optional) greatly improves
reliability, circuit integrity and provides advanced addressable fault finding.
The multi -criteria detector additionally has state-of-the-art microprocessor
circuitry (with error check), as well as detector self -diagnostics and supervision
programs that is used on Desigo Fire Safety Modular I FireFinder XLS/V and on
Model FC/FV20-series Desigo Fire Safety fire -alarm control panels (FACPs).
Additionally, Model FDOT421 is a plug-in and addressable two -wire multi -criteria
detector (with both photoelectric and thermal sensors) whose value is increased
with built-in ISOtechnology feature, that is compatible with all current Siemens
intelligent, addressable systems.
Operation
Model FDOT421 utilizes an infrared light emitting diode (IRLED), and infrared
light -sensing photodiode. Under normal conditions, light transmitted by the LED
is directed away from the photodiode and scattered through the smoke chamber
in a controlled pattern.
The smoke chamber is designed to manage light dissipation and extraneous
reflections from dust particles or other non -smoke, airborne contaminants in such
a way as to maintain stable, consistent detector operation. When smoke enters
the detector chamber, light emitted from the IRLED is scattered by the smoke
particles, and is received by the photodiode.
Model FDOT421 also utilizes a modern, accurate and shock -resistant thermistor to
sense temperature changes.
The signal processing with detection algorithms OWL
allows the detector to first gather smoke and thermal
data, and then analyze this information in the
detector's neural network.' By comparing data
received with the common characteristics of fires or
fire signatures, Model FDOT421 can compare these
signals to those of deceptive phenomena that cause
other detectors to trigger a false alarm. Multi -criteria Fire Detector
Each Model FDOT421 detector provides three (3) pre-programmed parameter sets
that can be selected by the FRCP.
LISTED APPROVED
Siemens Data Sheet 6150
Smart Infrastructure - Building Products
usa.siemens.com/fire
1. Labyrinth
2. Optical
transmitter
3. Optical
receiver
4. Heat sensor
1. Dustcover
2. Multi -criteria detector
NOTE: Each detector consists of a
dust -resistant photoelectric
chamber, a solid state, non -
mechanical thermal sensor,
and microprocessor -based
electronics with a low -profile
plastic housing.
Every Model FDOT421
fire detector is shipped with
a protective dust cover.
1
!Ave '0
Model FDOT421 provides two (2) different alarm sources that can be selected individually (ON or OFF) by the control
panel.
Alarm Source 1 (Neural Network) — Combines smoke (heat) with the following field -selectable profiles:
• Standard • Duct
Standard: This parameter set, which is practically ideal for normal office, hotel -lobby -type applications, is the default
setting. This parameter set additional offers improved resistance to false alarms in areas where misleading
deceptive sources and helps reduce cooking nuisance alarms (UL 268 7th Ed. Listed)
Duct: When using this detector direct in air duct applications, be sure the detector is set to the parameter "Duct".
Alarm Source 2 (Thermistor) — Heat only; provides the following:
• Static I fixed at 135°F (57°C), default setting
• Rate -of -Rise detection at 15°F I min. (8.3°C I min.)
If the detector is not programmed, Model FDOT421 will default to a 'standard' profile setting, which allows operation
for a normal office -type environment. Model FDOT421 contains a tri-color LED indicator, capable of flashing any one
(1) of three (3) distinct colors: GREEN I ... I RED. During each flash interval, the microprocessor -based detector
monitors the following fire -system conditions:
• Smoke in its sensing chamber
• Smoke sensitivity is within the range indicated on the nameplate label
• Internal sensors and electronics
Based on the results of the monitoring, the LED indicator flashes the following:
FLASH COLOR
CONDITION
FLASH INTERVAL
[in seconds]
GREEN*:
Normal supervisory operation.
10
Smoke sensitivity is within rated limits.
YELLOW:
Detector is in trouble and needs replacement.
4
'
Alarm' condition
1
NO FLASH:
Detector is not powered.
—
* denotes LED can be turned OFF
Please follow the corresponding description of the panel used.
A quick visual inspection is sufficient to indicate the condition of the detector at any time.
If more detailed information is required, a printed report can be provided from the respective Desigo Fire Safety
Modular I Model FC20-series I FireFinder XLSIV FACPs that indicates the status and settings assigned to each detector.
Siemens
Smart Infrastructure - Building Products —2— usa.siemens.comlfire
All Model FDOT421 detectors use a surface -mounting base I Model DB2-HR I DB-11 or Model DB-11 E. Each base
mounts onto a 4-inch (10.2 cm.) octagonal, square or single -gang electrical box. The base utilizes screw -clamp
contacts for electrical connections and self -wiping contacts for increased reliability.
The Model DB-11 detector base can be used with the optional Siemens Model LK-11 detector locking kit, which
contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11
has aesthetically conducive plugs to cover the outer mounting -screw holes.
Model FDOT421 may be installed on the same initiating circuit with the following [when used with Desigo Fire Safety
Modular Model FC20-series I FireFinder XLSIV FACPs1 -
• XTRI Series interface modules
• HTRI series interface modules
• HMS & XMS series manual stations
HFP-11, HFPT-11 detection devices
HCP output control modules
HZM conventional zone module
Each detector is shipped with a protective dust cover, consists of the following:
• Built-in ISOtechnology for True-Class-X SLC performance
• Dust -resistant photoelectric chamber
• Solid State, non -mechanical thermal sensor
• Microprocessor -based electronics with a low -profile plastic housing
All Model FDOT421 detectors are approved for operation within the UL-specified temperature range of 320F to 100°F
(0 - 38°C).
Installation of Model FDOT421 intelligent, addressable multi -criteria detectors requires a two -wire circuit.
In many retrofit cases, existing wiring may be used. 7-tapping' is permitted only for Style 4 (Class B) wiring.
Model FDOT421 is polarity insensitive, which can greatly reduce installation and debugging times. When operating in
NFPA 72 Class-X applications SLC polarity must be maintained to support up to 252 isolation ready devices per loop.
When used in mixed mode a maximum of 30 non -isolated devices between isolation devices (wired in polarity -
insensitive mode). See control panel install document for further details.
Model FDOT421 can be applied within the maximum 50-feet (15.24 m.) center spacing (2,500 sq. ft.
[232.2 sq. m.1) per Underwriters' Laboratories. This application guide is based on ideal conditions, specifically,
smooth -ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the
actual detector. Do not mount detectors near to heating I ventilation I air-conditioning (HVAC) outlets. Exposed joists
or beamed ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire -protection system
engineering and common sense dictate how and when fire detectors are installed and used. Contact your local
Siemens - Fire Safety distributor or sales office whenever you need assistance applying Model FDOT421 in unusual
applications.
Be sure to follow NFPA guidelines and UL Listed 1 ULC Listed installation instructions - included with every Siemens -
Fire Safety detector - and local codes for all fire -protection equipment.
Model FDOT421 is a plug-in, (2) two -wire Photoelectric I Thermal (heat) detector, compatible with Model FC20-series
Desigo Fire Safety Modular Model FC20-series I FireFinder XLSIV FACPs. Each Model FDOT421 detector has
microcomputer -chip technology and highly stable, solid-state electronic circuitry. Model FDOT421 detectors utilize a
modern, accurate and shock -resistant thermistor to sense temperature changes. This electronic -sensing method
virtually eliminates thermal lag associated with mechanical temperature -sensing devices, and provides almost
instantaneous temperature status to the FACP.
Model FDOT421 provides seven (7) field -selectable, pre-programmed temperature settings:
• Fixed 1357 (57°C) • Rate -of -Rise: 1571 min. (8.3°C)
This feature is compatible with Model FC20-series Desigo Fire Safety Modular Model FC20-series I FireFinder XLSIV
systems, as well as with FC I FV2025 or FC I FV2050 FACPs.
Siemens
Smart Infrastructure - Building Products -3- usa.siemens.comlfire
Model FDOT421 is compatible with the Siemens field -device programmer / test unit (Model DPU), which is a compact,
portable and menu -driven accessory for electronically programming and testing these addressable detectors promptly and
reliably. For instance, the field technician selects the accessory's program mode, and enters the desired address.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. - dials and rotary
switches), and reduces installation and service costs by electronically programming and testing the detector prior to
installation. When set in test' mode, Model DPU will perform a series of diagnostic tests without altering the address or
other stored data, allowing technicians to determine if the detector is operating properly.
Each field -device programmer / test unit operates on AC power or rechargeable batteries, providing flexibility and
convenience in the programming / testing of fire -safety equipment from practically any location. Additionally, with the
use of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating
conditions that can accompany the vitality of a mechanical -addressing mechanism.
The encompassing result is an intelligent detector that provides enhanced detection capability to a wide range of products
of combustion - while offering unsurpassed rejection to nuisance -alarm sources, including: dust I steam I aerosols and
other deceptive phenomena that could cause false alarms.
Technical
Data
OPERATING
*32° -'1007
TEMPERATURE:
(0° -18°C)
RELATIVE
0 - 95%
HUMIDITY:
(non -condensing)
AIR PRESSURE:
No effect
INPUT VOLTAGE
16VDC - 30VDC
RANGE:
ALARM,
410pA
CURRENT, MAX.:
'STANDBY,
250pA
CURRENT, MAX.:
MAXIMUM
30-ft. (9.144 m.) centers
SPACING:
(900 sq. ft. 183.6 sq. m.),
per NFPA 72 and ULC-S524
• Fixed 135°F (57°C)
THERMAL
• Rate -of -Rise:
RATING:
15°F / min. (8.3°C)
at fixed 135°F (57°C)
DETECTOR
0.317 Lbs. (0.144 kg.)
WEIGHT:
MECHANICAL
UL Listed / ULC Listed
PROTECTION
with STI Guard Model
GUARD:
STI-9604
• UL268 3.52-4.17% / ft obs.
SENSITIVITY
ULC 3.52-4.27% / ft obs.
RANGE:
UL268A 2.32-2.84% / ft
obs. (direct in -duct)
Panel
Compatibilities
MODEL
DATA
OR TYPE
SHEET
PANEL
XLS
6300
FireFindeO (fire -only overview)
XLSV
6340
FireFinder (fire w/ voice)
Desigo
7300
Desigo Modular
Modular
(system overview)
FC901
5813
Desigo Fire Safety
50-point addressable
FC2025
Desigo Fire Safety
252-pt. addressable (fire)
6815
FC2050
Desigo Fire Safety 504-pt.
addressable (fire)
Desigo Fire Safety
252-point addressable
FV2025
(fire w/ Intelligent Voice
Communication [IVC])
6821
504-pt. addressable
FV2050
(fire w/ Intelligent Voice
Communication [IVC])
Details for Ordering
MODEL
PART
OR TYPE
NUMBER
PRODUCT
Addressable
FDOT421
554320-F6-A1
Multi -Criteria
Fire Detector
Compatible Devices:
MODEL
PART
OR TYPE
NUMBER
PRODUCT
Sounder base with
ABHW 4B
S54320 F13 Al
Loop-PowerOption
Sounder base for
ABHW 4S
554320 F14 Al
Sleeping Areas
ADB BOX
500 698360
Surface Mount Adapter
Box for Audible Base
Relay base compatible
DB2 HR
S54370 F12 Al
with Siemens standard
and advanced detectors
Detector Mounting Base
DB 1 1
500 094151
(for Series 11)
DB 1 1 E
500 094151E
Detector Base (small)
Remote Alarm
RL-HW
500 033310
Indicator:
Single -gang -box
mount, red
Remote Alarm
RL-HC
500 033230
Indicator:
4" (10.2 cm.) octagon -
box mount, red
LK 1 1
F500-695350
Base Locking Kit
(for Series 11)
See: www.STI-USA.com for further details
on ordering Model STI-9604
In Canada order:
MODEL
PART
PRODUCT
OR TYPE
NUMBER
Detector
DB-1 1 C
500-095687
Mounting Base,
ULC Listed
Siemens
Smart Infrastructure - Building Products —4— usa.siemens.com/fire
NOTICE- The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
iMENS
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
SIEMENS
❑ Each detector base supports Isolation The detector bases are low -profile, surface mounting bases used with various
field wiring for ISOtechnology feature Siemens — Fire Safety conventional and addressable detectors. Model DB2-HR, which
is a redesign of Model DB-HR, is compatible with the standard, addressable type of
❑ All bases compatible with optional intelligent detectors, as well as the multi -criteria detection devices utilizing the
Model LK-11 detector -locking kit patented ASAtechnoloyfm
❑ Each detector base also functions with Model DB2-HR supports operation with Siemens' 50-point addressable; 252-point
the addressable Models FD0421, addressable; 504-point addressable, and FireFinder® XLS I Modular fire systems. A
FDOT421, FDOOT441, FDOOTC441 and relay output from the fire detector base for signaling other devices is provided by
FDT421 intelligent detectors
Model D132-HR.
❑ Model DB2-HR is compatible with The detector bases use screw -clamp contacts for electrical connections and self-
ASAtechnology multi -criteria detectors wiping contacts for increased reliability. Further, the bases can be used with the
optional Model LK-11 detector locking kit, which contains 50 detector locks and an
❑ Each detector base is compatible with installation tool, to prevent unauthorized removal of the detector head.
Model'H', "l1"and "121"series of
conventional detectors
❑ Model DB2-HR has backwards Models DB-11 and DB-11 E are standard bases for Model 'H'-series 11" and Model
compatibility with SiemensModel'H'- "121"-series conventional detectors. Model DB-11 has a 6" (15.2 cm) diameter, and
series intelligent detectors
the diameter for Model DB-11 E is 4.5 inches (11.4 cm).
❑ Models D13-11 and D13-11 E mount on a Moreover, Models DB-11 and DB-11 E mount on a 4"-square, (10.2 cm) octagon or
4-inch octagon, square or single gang electrical box single -gang box. Model DB-11 has integral, decorative plugs to cover the outer
screw holes.
❑ Model D13-11 has plugs to cover the However, Model DB2-HR mounts on a double -gang, 4-inch (10.2 cm.) square
outer -mounting screw holes electrical box.
❑ Model DB2-HR mounts on a 4"-square,
double -gang electrical box
❑ UL268 Listed, ULC-S529 Listed
❑ FM, CSFM and NYC Fire Department
Approved
a �
�IkTA F.
AW
mow
FMO'
APPROVED
Siemens Data Sheet 6161
Smart Infrastructure — Building Products usa.siemens.comlfire
I r-----6"(11.4cm.)Diameter I
1/2" i1 27 c m 1 1171ry E
` I r4V
I
I I�
J
Diameter I----r""
I L_ 2-3/4"(7cm.)--J I
_ L--- 4-1/8' (te.s cm.]Diemeter---J
ee- �
Note: The Model D13-11 E base detector has
a diameter dimension of 4.5" (11.4 cm).
Wiring Diagrams
moic%ie OlMq ro 1b
�rzQoaaa.eT.ucmra�o�rcTw
a e
e
s s
cwTION
I. Do nerux aop.e carte antler bex arminel S. BreeY wln °a9m�'.'�'°`•"`0^m^°°^'^M
t. erwiY e�.rYsan of connscrion. ��1
3. YAr e�rowYe Yeaetl to convole crnicslsylem
bsY4MISYr�1 u ma�nM eHecbrmtl ope.n.l
r1�lYle�IMbOLLY e..ka M M rorowM ucw.
Note: The illustration above is typical wiring for Models D13-11 and D13-11 E
(using Models 01-1121, OP121, and Hll21 detectors).
LINE1•
TONEXTBASE DO NOT USEAN
END OF LINE DEVICE
DETECTOR BASE
MODEL D&11/DB-11E
FROMADDRESSABLE
0
DEVICE CIRCUIT OF A
5 la
5 10
5
COMPATIBLE CONTROL
OPTIONAL
TB1
NCI RELAY CONTACTS
UNITORPREVIOUS
B 1b REMOTE
ALARM
B 1b
( } 3A, 120 VAC
ADDRESSABLE DEVICE
TB2
0 INDICATOR
0
i8
3A, 30 VDC
MODELS TB3
8727W / B727C/
RL-HW / RL-HC
UNE2'
DO NOT USEAN
END OF LINE DEVICE
SUPERVISEDAND POWER LIMITED
TO NEXT BASE
Note: The illustration above is typical polarity insensitive wiring for Models D13-11 and
D13-11 E (using Models FD0421 1 FDOOT441 I FDOOTC441 1 FDOT421 1 FDT421
detectors).
UNE1 TO NEXT BlS; DONOTUSEM
END OF UNE DEMCE
DETECTOR BASE
MODELDB-11/D&11E
T,,',4n9�'d
SIEMENSco bble contrd unit
5 to OPNOmL
\ REMOTE
TBI
5 1.
B 1b
J5+
/I
NTACTS•
RELAY VA
e 1b PiM
M
INDICATOR
T@
--
Je- lnc
} A
3q WVOC
MODELS
8727W I8727C1
B3
RL+M' I RL-HC
UNE2 -
-
0 DONOTUSEAN
END OF UNE DEMCE
TO NM BASE
Note: The illustration above is typical isolator mode wiring for Models DB-11 and DB-
11 E (using Models FD0421 1 FDOOT441 1 FDOOTC441 I FDOT421 1 FDT421 detectors).
vE a
ua 1_ glerIIT�O
�
~
rolemll�reaeo
eeleeanrlEur eAer
coos uaYw
vur ova
Mvl wsn ne1oG:0M.
oro.rnATaao owwr
se:Ye:NswureN.
roc wNnen Yrora .L
�''�'
l ovnAcn
TYE Aeur mNTKn
,aE�e�..o�rue w n�
Tic.
sL 1mvK
)A ]o VfK
e141
AeerT CaoTMI
rorEn orvu
L1~EI OOM011�E MIfIO
6 YlE 1te10
IIEI ~
NIA�OOueL7Og1�Ae MIRM�b01hw aEtTwrlr Wt 01 fMlDilF e� 0 M'Aa
07eN,�r01•t �+w • u�.uw.erawbanso..oM.n u.wiva,rnw
Note: The illustration above is typical wiring for Model D132-HR for polarity -
insensitive detectors.
Siemens
Smart Infrastructure — Building Products -2_ usa.siemens.comlfire
MODEL
PART
OR TYPE
NUMBER
PRODUCT
DB-11
500-094151
Low -Profile Surface -Mount Base
DB-11 C
500-095687
Low Profile Surface -Mount Base [Canada]
DB-11 E
500-094151 E
Smaller -Diameter Detector Base
DB-HR
500-033220
Relay Base for'H'-Series Intelligent Detector
Relay base compatible with standard and advanced
DB2-HR
S54370-F12-A1
detectors; backwards compatible with Model 'H'-series
intelligent detectors
FDT421
S54320 F5-Al
Thermal (Heat) Detector
FDOT421
S54320-F6-A1
Addressable Multi -Criteria Fire Detector
FDO421
S54320-F4-A1
Photoelectric Smoke Detector
FDOOT441
S54320-F7-A1
Multi -Criteria Fire Detector with ASAtechnologyTm
FDOOTC441
S54320-F8-A1
Multi -Criteria Fire / CO Detector with ASAtechnologyTM
LK-11
500-695350
Base Locking Kit for Model "IV -series detectors
H1121
S54372-F3-A1
Heat Detector
OH121
S54372-F2-A1
Multi -Sensor Smoke Detector
OP121
S54372-Fl-Al
Photoelectric Smoke Detector
NOTICE— The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets —as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
SIEMENS
❑ Durable metal design The Siemens intelligent manual fire -alarm boxes (Models HMS-S I HMS-SZ and
❑ Shock and vibration resistant HMS-D I HMS-DZ) provide the most advanced method of address programming and
supervision.
❑ Single-action (Model HMS-S I -SZ) and Each Model HMS -series manual box achieves the state of an 'intelligent -initiating
double -action (Model HMS-D I -DZ) device' by incorporating custom microcomputer -chip technology with sophisticated,
stations bi-directional communication capabilities with the panel, which include Siemens
❑ Pull -down lever is down, until Modular, as well as Siemens 50-point, 252-point and 504-point addressable FACPs.
manually reset The Model HMS- series manual fire -alarm boxes are also included in US Coast Guard
• Reset with Allen Key (USCG) approval for use in marine and other harsh environments, when used with
• No break rods necessary the Siemens 252-point and 504-point USCG approved addressable system.
❑ Custom microcomputer -chip
technology
❑ Polarity insensitive via SureWireTM
technology
❑ Dynamic supervision to the fire -alarm
control panel (FACP)
• Device Programmer Unit (Model
DPU) programs and verifies
address and tests functionality of
each device
❑ Electronic -address programming
(EEPROM) is easier, as well as more
efficient, dependable
❑ Surface or semi -flush installation
❑ Two -wire
❑ Americans with Disabilities Act (ADA)
Compliant
❑ UL Listed
❑ USCG (161.00216010),
❑ FM (#3015946 & 3052621),
CSFM (#7150-0067:0036)
❑ NYC Fire Dept. (#202-12E, Vol. 1)
Approved
Models HMS-S I HMS-SZ and HMS-D I HMS-DZ are
constructed of durable, molded polycarbonate material
that is matte finished in red with raised white lettering.
The housing accommodates a 'pull -down' lever, which —
when operated — locks into position; indicating the fire -
alarm box has been activated.
The pull -down lever remains down 1 in the 'locked'
position, until the fire -alarm box is manually reset. The
manual fire alarm box can only be reset by opening the
hinged housing cover with an Allen key; followed by
closing and locking the cover. Models HMS-S I -SZ and
HMS-D I -DZ operate with Siemens — Fire Safety FACPs.
The microcomputer chip to the manual fire -alarm box
has the capacity of storing — in memory — identification
and important operating -status data.
Models HMS-S I -SZ and HMS-D I -DZ are fitted with
screw terminals for connection to an addressable circuit,
and can be either surface or semi -flush mounted.
The Model HMS -series manual fire -alarm boxes derive
their power, communicate information and receive
commands over a single pair of wires. Each box is
compatible on the same circuit with all Model W-series
detectors, interfaces or addressable, conventional zone
modules.
U`
a
® APPROVFMED �® 9
1 iu— ni is 1
Dual -Action Station
Model HMS-S I -SZ
Single -Action Station
Siemens Data Sheet 6306
Smart Infrastructure - Building Products usa.siemens.comlfire
Mounting Diagram
Innovative technology from Siemens — Fire Safety also allows all Model HMS -series intelligent manual fire -alarm boxes to be
programmed via the Device Programmer I Test Unit (Model DPU). The programmer 1 tester is a compact, portable and menu -
driven accessory that makes programming and testing of a manual fire -alarm box device faster, easier and more dependable
than previous methods.
Model DPU eliminates the need for mechanical -addressing mechanisms of a device because Model DPU electronically sets the
address of the manual fire -alarm box into its microcomputer chip, non-volatile memory. Therefore, vibration, corrosion and
other conditions -- which can compromise the functionality of mechanical -addressing mechanisms — are no longer an issue.
ELECTRICAL
Current Draw 0.9mA
(Active or Standby)
INDOOR I DRY CONDITIONS
Operating
32' — 100°F
Temperature Range
(0° — 38°C)
Operating
0 — 93%,
Humidity Range
non -condensing
+ denotes Country Of Origin
Siemens
Smart Infrastructure — Building Products —2_ usa.siemens.comlfire
NOTICE- The information contained in this data -sheet document is intended
only as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets — as well as the General
Product Warning and Limitations document, which also contains
important data, are provided with the product. All are available
from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
SIEMENS
.-
• •.
❑ Intelligent device for use with various
Model HCP I -Z from Siemens — Fire Safety is an intelligent control point device
Siemens — Fire Safety fire -alarm
designed for use with Siemens — Fire's NAC series of alarm signaling devices.
control panels (FACPs)
Additionally, various Siemens — Fire Safety FACPs, which include Siemens Modular as
well as the 50-point, 252-point and 504-point addressable FACPs can recognize
❑ Used as a telephone zone, speaker
Model HCP devices.
zone or notification appliance circuit
(NAC)
Model HCP I -Z can be configured as an independent, remotely located telephone
zone, speaker zone or NAC. Model HCP I -Z is programmed and tested using the
• Provides NACs when used
Device Programming I Test Unit (Model DPU), which eliminates the need for
with a Siemmensess FACP
mechanical -addressing mechanisms (i.e. — program jumpers, DIP switches or rotary
• Used as a NAC under the Siemens -
dials).
Fire Safety NAC product line
Model HCP is supervised for loss of 24 VDC input power, as well as short -or -open
• Provides either a 25V (35 Watts) or
70.7V (25 Watts) single -channel
output -zone wiring. Model HCP I -Z mounts in a standard double -gang or 4" (10.2
speaker zone (only used with
cm.) square electrical box.
Siemens Modular and FireFinder
When Model HCP I -Z is programmed as a speaker zone, the high -power audio risers
XLS)
are supervised using the Model ZAC-40 zone amplifiers. Programmed as a telephone
• Provides firefighters' telephone
zone, the telephone riser is supervised by the (8) Eight -Zone Telephone Card (Model
circuit (only used with Siemens
TZC-8B).
Modular and FireFinder XLS FACPs)
Specifications
❑ Polarity insensitive with SureWiret
Model HCP I -Z communicates through the analog loop of Models XDLC for Modular
technology
systems (Model DLC for FireFinder). Each control -point device can be wired in either
❑ Mounts on standard electrical box
Class A (Style Z) or Class B (Style Y). The 24 VDC power input comes from either the
FACP or from any UL Listed power -limited, auxiliary power supply.
• 4" (10.2 cm.) square or double gang
❑ No mechanical -address programming
required
❑ Includes a dial -tone generator for
telephone use
❑ Supervised input and output power
❑ UL Listed, ULC Listed
❑ CSFM and NYC Fire Dept. Approved
For Siemens Modular I FireFinder XLS systems, compatible power supplies for the
intelligent control point device are:
■ Model PSC-12 power supply
■ Model PSX-12 power -supply extender
■ Models PAD-3, PAD-4 NAC extenders, or
• Any power -limited, 24 VDC power
supply that is UL Listed for fire -
protective -signaling use
For the Siemens 50-point, 252-point and
504-point addressable fire systems,
compatible power supplies include:
■ Siemens NAC circuits
■ PAD-3 or PAD-4 NAC Extenders
■ Any power -limited, 24 VDC power
supply that is UL Listed for fire -
protective -signaling use
Intelligent Control Point Device
Siemens
Smart Infrastructure - Building Products
Data Sheet 6311
usa.siemens.com/fire
1
Siemens Modular, 252- and 504-point systems support
up to 60 Model HCP I -Z devices per SLC. Siemens 50-
point, addressable fire system supports a maximum of
50 addressable devices of all types.
NOTE: The maximum NAC load that may be connected
from Model HCP I -Z into a 50-point, 252-point or 504-point
fire system is 1.50 Amps at 24VDC.
The H-series intelligent control point device is UL 864
Listed for indoor dry locations within a temperature
range of 120 +/- 3°F (49 +/- 2°C) to 32 +/- 3°F (0+/-2°C)
and a relative -humidity range of 93 +/- 2% at a
temperature of 90 +/- 3°F (32 +/- 2°C).
Use a standard 3-112" (8.9 cm.)
deep, double -gang electrical
switchbox or a 4" (10.2 cm.)
square electrical box that is 2-1/8".
(5.4 cm.) deep with either a 1.5"
(3.8cm.) deep extension or a
1.25" (3.2cm.) deep plaster -ring
extension.
2. Connect the field wiring. Insert
Model HCP into the box and
fasten the device plate to the box.
3. Cover the device front plate with
the 5" (12.7 cm.) switchplate
(supplied) and fasten with two (2)
plate screws.
Mounting Diagram
Electrical
Current Draw
(Active or Standby) 1.OmA
+ denotes Country of Origin
4-INCH SQUARE BOX
DOUBLE GANG BOX
2 1/84NCHES
DEEP
3 1/2414CHES DEEP
`
O O
0
--
--
O
®
HCP
0
HCP
O O
0®
O O
0®
S WITCHPLATE
SWITCH PLATE
54NCHES SQUARE
SINCHES SQUARE
(SUPPLIED)
(SUPPLIED)
NOTICE- The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire -safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
iyi4MCIP1
❑ Siemens ISOtechnologyTM
Provides "True Class-X"
operation meeting NFPA 72 SLC
field wiring requirements
Supports 252 ISOtechnology ready
devices per loop, and in mixed
mode up to 30 devices between
isolated devices
❑ Dual input on Model XTRI-D, via a single
address
❑ Integral single -pole, double -throw (SPDT)
relay on Model XTRI-R:
- Up to 4 Amps.
❑ Low current draw
❑ Polarity insensitive (in non -isolation
mode) via SureWireTM technology:
- Modern technology supports
comprehensive system and interface
communication
❑ Multi -color light -emitting diode (LED)
indicates system status:
GREEN I AMBER I RED
❑ Mounts in a 4-inch (10.2 cm.) square, 2-
1/4" (5.7 cm.) deep single -gang or double -
gang back box
❑ Non -obstructive front-end access to
programming port and wiring terminals
SIEMENS
The Siemens - Fire Safety XTRI-series Intelligent Interface Modules are designed to
provide the means of interfacing direct shorting devices to the fire -alarm control
panel (FRCP) SLC. All modules take up one (1) address on the loop.
Each XTRI-series interface module provides the "built-in" ISOtechnology feature -
intelligent dual isolation meeting NFPA 72 Class X (Style 7) wiring requirements.
Up to 252 isolators per loop and up to 30 devices between isolators (wired in
polarity -insensitive mode). Additionally, the devices between isolators can either
be'H'-series or the more contemporary' X'-series detection devices.
The Siemens - Fire Safety XTRI-series Intelligent Interface Modules are available in
three (3) individual types:
> One (1) Dual -Input: XTRI-D
> Two (2) Single -Inputs: XTRI-R (with relay) I XTRI-S
- The single -input versions are each designed to monitor a normally open
(N.0) or (N.C) normally closed dry contact
XTRI-D I XTRI-R I XTRI-S incorporates ISOtechnology - the configurable, built-in
dual isolator function. Additionally, an XTRI-series interface module supports
NFPA 72 Class X (Style 7) survivability requirements for shorts while providing
reliable alarm communication to the Siemens FACP. The isolation feature found on
the XTRI-series Intelligent Interface Modules gives information as to the location of
the fault. When a short occurs, the panel can identify the fault automatically, and
the module recognizes the short location (in front of the device or behind the
device).
Overall, the built-in isolators improve the diagnostics and location of the problem,
including a short.
The modules are configurable by a Siemens compatible FACP (or panels) in an
isolator (polarity sensitive) or non -isolator (polarity insensitive) mode. When a
XTRI-series interface module is configured as an isolator, that module has the
capacity of functioning as both an in/out device, as well as an isolator.
Smart Infrastructure -Building Products
usa.siemens.comlfire
- 1. 4" (10.2 cm.)
-;� square box I
r cm.) back box
f, 7:
-_; 2. 3.5" (8.9 cm.)
30 double -gang
back box
i
3. 5" (12.7 cm.)
square switch
plate, supplied)
Intelligent Device
Interface Module
Model XTRI-R PROGRAMINGNOLES
Through the use of an addressable 'Form C relay, the Model -
XTRI-R relay and contact device input are controlled at the
same address. The relay and input contact can be controlled
as a separate function from a Siemens compatible FRCP. The
relay is typically used where control or shunting of external
equipment is required. SLOTFOR
LOCATING
TAB 6'
Model XTRI-D
Model XTRI-D is a dual -input module that is designed to
MI
supervise and monitor two (2) sets of dry contacts. Model cTNm —
XTRI-D only requires one (1) address, but responds DESIGN FOR DPUXVCONNE�..
independently to each input. Model XTRI-D is ideal for ISALLO EDN R THE PLUG
p Y P IS ALLOWED TO THE DPU
monitoring a water -flow switch and its respective valve INSERT THE PLUG PROGRAMMER
tamper switch. AT EITHER DIRECTION TESTER
NOTES:
Each interface module mounts
directly to a user -supplied
switchbox.
The electrical boxes, seen above,
are supplied -by -others (130).
Models XTRI-D, XTRI-R and XTRI-
S mount directly onto a 4-inch
(10.2 cm.) square, 2'/4" (5.7 cm.) -
deep box back box, or to a user -
supplied double -gang 3'/z" deep
back box.
A 5" (12.7 cm.) square, off-white
faceplate is included in each
shipment of a Siemens Model
XTRI-series module.
Field -Device Programmer / Test Unit
Siemens - Fire Safety innovative technology allows Model XTRI-series intelligent interface modules to be programmed via the
Siemens field -device programmer / test unit (Model DPU), which is a compact, portable and menu -driven accessory for
electronically programming and testing Siemens peripheral modules and devices promptly and reliably. For instance, the
field technician selects the accessory's program mode, and enters the desired address.
Model XTRI-series interface module is connected to Model DPU with the programming cable provided with the tester.
NOTE: Since the XTRI-series of interface modules are advanced initiating devices, the latest Model DPU firmware update is
required.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. - dials and rotary
switches), and reduces installation and service costs by electronically programming and testing the module prior to
installation. When set in test' mode, Model DPU will perform a series of diagnostic tests without altering the address or
other stored data, allowing technicians to determine if the module is operating properly.
Each field -device programmer I test unit operates on AC power or rechargeable batteries, providing flexibility and
convenience in the programming I testing of fire -safety equipment from practically any location. Additionally, with the use of
a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating conditions that
could negatively affect any electro-mechanical-addressing mechanism.
Siemens 'X' modules may be used along with Model 'H'-series intelligent detectors; Model 'HMS' -series addressable manual
stations, or any other 'H'-series addressable intelligent module (e.g. Model HZM or Model HCP). Additionally, the X-series
modules are compatible with all Desigo and Cerberus Pro detectors and peripherals of the same circuit.
Interspersing 'X' & 'H'-series devices on the same loop is mostly permitted, but there are exceptions: Models HLIM (isolation
module) and SBGA-34 (audible base) cannot be used with 'X' devices on the same loop.
Siemens
Smart Infrastructure - Building Products -2- usa.siemens.com/fire
Models XTRI-D I XTRI-R I XTRI-S intelligent interface modules are UL Listed I ULC Listed. Environmental operating conditions for
each interface module is 327 (0°C) to 120°F (49'Q with a relative humidity of no greater than 95%, non -condensing.
LED lindicators
FLASH
FLASH
COLOR
CONDITION
INTERVALS
[in seconds]
GREEN*:
Normal supervisory operation
10
YELLOW:
Device is in trouble and needs to be replaced
4
Locate I 'Alarm'
1
Output Device (XTRI-R only)
10
Power is not being received t
NO FLASH:
Replacement is needed IF
-
M -echnical
Data
OPERATING VOLTAGE RANGE:
13VDC - 32VDC
RELATIVE HUMIDITY:
0 - 95%
(non -condensing)
'ACTIVE' OR'STANDBY'
CURRENT, MAX.:
500pA
LINE SIZES
AMERICAN WIRE GAUGE (AWG)
14 AWG, max.
18 AWG, min.
CURRENT DRAW
MAX IAVG.
XTRI-S
650pA
XTRI-R
750pA
XTRI-D
950pA
RELAY RATINGS:
(for Model
XTRI-R)
RESISTIVE:
4 Amps 125 VAC
4 Amps 30 VDC
INDUCTIVE:
3.5A, 120 VAC (0.6 pF)
3.OA, 30 VDC (0.6 pF)
2.OA, 120 VAC (0.4 pF)
2.OA, 120 VAC (0.35 pF)
2.OA, 30 VDC (0.35 pF)
Details for Ordering
MODEL
PART
PRODUCT
OR TYPE
NUMBER
XTRI-S
S54370-133-A1
Single Input Module
XTRI-R
S54370 B1 Al
Single Input Module
(with relay)
XTRI-D
S54370 B2 Al
Dual Input Module
DPU
=500-033260Device
Programmer /
Test Unit
NOTE: Refer to installation manual: PIN -
A6V101055479 to ensure Model XTRI-D I XTRI-R
XTRI-S compatibility with the Siemens FACPs intended
for use in the given application.
NOTICE- The information contained in this data -sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install -type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation
should be consulted with a fire -safety professional before
specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
J
THIS PAGE INTENTIONALLY LEFT
BLANK FOR DUPLEX PRINTING
POLDER %
���%SON/�
PS-121000 12 Volt 100.0 AH
Rechargeable Sealed Lead Acid Battery We've Got The Power.Tm
• U: Universal
terminals: Heavy-duty
posts with 'nut & bolt'
fasteners
• T6: Threaded insert
w. 6 mm stud fastener
sealee rze�nareeaoie
aa„e�
MODEL PS-121000D
� i oaoamv �"
U: Positive U: Negative
(Terminal
00
(Terminal
100
16II-
oII-
3
N
T6
H
I�
w
a® T_ ®�
a o
� ea„ary o 0 0 o T
PEA 50M/C. HT H
I- L �I
L: 12.00 (305) W: 6.60 (168) H: 8.15 (207) HT 8.98 (228)
Tolerances are +/- 0.04 in. (+/- 1 mm) and +/- 0.08 in. (+/- 2mm) for
height dimensions. All data subject to change without notice.
• Absorbent Glass Mat (AGM) technology for superior
performance
• Valve regulated, spill proof construction allows safe
operation in any position
• Power/volume ratio yielding unrivaled energy density
• Rugged impact resistant ABS case and cover (UL94-HB)
• Integrated ABS carrying handles for ease of movement
• Approved for transport by air. D.O.T., I.A.T.A., F.A.A.
and C.A.B. certified
• U.L. recognized under file number MH 2O845
Nominal Voltage.......................................................12 volts (6 cells)
Nominal Capacity
20-hr. (5A to 10.50 volts) .............................................. 100.0 AH
10-hr. (9.2A to 10.50 volts) ............................................. 92.0 AH
5-hr. (15.8A to 10.20 volts) ........................................... 79.0 AH
1-hr. (55.2A to 9.00 volts) ............................................. 55.2 AH
15-min. (175A to 9.00 volts)................................................43.8 AH
Approximate Weight ..................................... 68.00 lbs. (30.84 kg)
Energy Density (20-hr. rate) ............. 1.86 W-h/in3 (113.45 W-h/1)
Specific Energy (20-hr. rate) ............ 17.65 W-h/lb (38.91 W-h/kg)
Internal Resistance (approx.) ....................................... 5 milliohms
Max Discharge Current (7 Min.) ............................. 300.0 amperes
Max Short -Duration Discharge Current (10 Sec.) .. 750.0 amperes
Shelf Life (% of nominal capacity at 68°F (20°C)
1 Month................................................................................. 97%
3 Months................................................................................ 91 %
6 Months............................................................................... 83%
Operating Temperature Range
Charge.................................................4°F (-20°C) to 122°F (50°C)
Discharge.............................................40°F (-40°C) to 140°F (60°C)
Case.................................................................................. ABS Plastic
Power -Sonic Chargers ........................................... PSC-121 OOOOA-C
MODEL
FINAL
VOLTAGE
WATTS PER CELL @ 250 C
5 MIN
10 MIN
15 MIN
20 MIN
30 MIN
45 MIN
60 MIN
1.75
550
395
312
267
207
152
128
PS-121000
1.70
586
413
324
277
212
155
129
1.67
605
421
330
283
215
158
130
Discharge Time vs. Discharge Current
20
15
10
d L 5
E
H
d 2
rn
N — 1
30
E
10
5
\
Final
Voltage
10.5V
10.2V
9.6V �\
9.0V
40°(
20%
0°(
8.1 V
5.0 10 20 50 100 200
Discharge Current (A)
14.0
13.0
8.0
Discharge Characteristics
on
!
!1
\I
10
ki
I
II
k
1
MUSEUM-,
am
M
.. -
SAFE
011101
■011�011■-.11.,
1.2 2.4 6 12 24 36 48 1 2 4 6 810 20 40
(104°F)
(68°F) I= min I' h I
(32°F) Discharge Time
Cycle Applications: Limit initial current to 20A. Charge until battery voltage (under
charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts
until current drops to under 1 A. Battery is fully charged under these conditions, and
charger should be disconnected or switched to "float' voltage.
"Float" or "Stand -By" Service: Hold battery across constant voltage source of 13.5
to 13.8 volts continuously. When held at this voltage, the battery will seek its own
current level and maintain itself in a fully charged condition.
Note: Due to the self -discharge characteristics of this type of battery, it is imperative
that they be charged within 6 months of storage, otherwise permanent loss of
capacity might occur as a result of sulfation.
100
O
80
C
0
dui 60
m
y
Z 40
CU
m
Shelf Life & Storage
Charging is not
necessary unles
100 % of capaciy
is required.
5°C
(41
°F)
Charging before
use is necessary
to help recover
full capacity.
Charge may fail
to restore full
capacity. Do not
40°C
30°C
20°C
(104°F)
(86°F)
(68°F)
tetbatteeiesreac
this state.
U 0
0 2 4 6 8 10 12 14 16 18 20
Standing Period (Months)
Power -Sonic offers a wide range of chargers suitable for batteries up to 100AH.
Please refer to our website www.power-sonic.com for a complete range of useful
Please refer to the Charger Selection Guide in our specification sheets for "C-Series
downloads, such as product catalogs, material safety data sheets (MSDS), ISO
Switch Mode Chargers" and "Transformer Type A and F Series". Please contact our
certification, etc..
Technical department for advice if you have difficulty in locating suitable models.
Contact Information
www.power-sonic.com
DOMESTIC SALES CUSTOMER SERVICE
TECHNICAL SUPPORT INTERNATIONAL SALES
Tel: +1-619-661-2020 Tel: +1-619-661-2030
Tel: +1-619-661-2020 Tel: +1-650-364-5001
Fax: +1-619-661-3650 Fax: +1-619-661-3648
Fax: +1-619-661-3648 Fax: + 1 -650-366-3662
nafional-sales@power-sonic.com customer-service@power-sonic.com
support@power-sonic.com internafionalwles@power-sonic.com
CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: + 1 -619-661-2020 • Fax: +1-619-661-3650 0114 1M
9 2013. Power -Sonic Corporation. All rights reserved. All trademarks are the property of their respective o